Sei sulla pagina 1di 8

ENGINEERING INFORMATION

Flow data,
flow factor and orifice size

Importance of properly sizing valves ρ is the density of the fluid in kilograms


per cubic metre
If the drop is less than assigned minimum
differential, the valve is oversized. In these
A
It is important to properly size a valve. There ρw is the density of water (see above) in situations, a valve with a lower minimum
are undesirable effects in both undersizing kilograms per cubic metre (according operating pressure differential should
and oversizing. to IEC 534) be employed or, alternatively, a smaller
sized valve with a more closely defined
Undersizing may result in: Kv factor.
Conditions to be known
1) the inability to meet desired flow require- The formulas necessary to determine the Kv
ments In general, we must know as many of the are quite complicated and for that reason a
2) the flashing of liquids to vapours on the conditions surrounding the application as series of flow graphs was developed which
outlet side of the valve possible. reduce that problem to one of a simple
3) a fall in the outlet pressure multiplication or division.
4) substantial pressure losses in the piping Flow required in cubic metres per hour
system (m3/h) for liquids, normal cubic metres per All flow calculations for a fluid have been
hour (nm3/h) for gases, or kilograms per simplified to a basic formula:
Oversizing may result in: hour (kg/h) for steam. These figures can be
obtained by simply asking the customer's
1) unnecessary cost of oversized equip- requirements or referring to the nameplates Flow required: Q
Kv = ---------------------
ment on pumping equipment, boiler room charts Graph factors: Fgm, Fsg, Fgl
2) variable flow through the valve or erratic or calculations.
control of the flow
The graph factors Fgm, Fsg, Fgl can be easily
3) shorter life of some valve designs through Inlet Pressure (p1) - This is usually obtained picked out by aligning known pressure con-
oscillating of internal parts to maintain from the source of the supply or by placing ditions on the graphs I to X on the following
required internal pressure differentials, a pressure gauge near the valve inlet. pages (for calculations see next page).
caused by lack of flow
4) erratic operation of some designs such Outlet Pressure (p2) - This can be obtained The tables below can be used to estimate
as failure to shift position due to lack of by gauge observations, but usually is tied a Kv if the orifice size is known, or to relate
required flow in 3- and 4-way valves in with specifications regarding allowable the approximate orifice size if the Kv is
5) erosion or wire drawing of seats in some system pressure drop. If we know the inlet known. The chart is based on the ASCO
designs because they operate in the pressure and the pressure drop, then the design of in-line globe type valves. The flow
nearly closed position outlet pressure is easy to determine. charts must be used for precise sizing and
converting Kv factors to actual flow terms,
Pressure Drop (∆p) - In large or complicated
Definition of Kv and the catalogue page must be consulted
systems, it is desirable to keep the pressure
for the actual Kv of a particular valve.
The flow coefficient Kv in cubic metres per drop across a valve to a minimum, and often
hour or litres per minute is a special volu- the customer will have definite specifications Approx. Approx.
metric flow rate (capacity) through a valve concerning the factor. Of course, if the valve orifice approx. Kv orifice approx. Kv
at a specified travel and at the following is discharging to atmosphere, the pressure size size
conditions: drop is equal to the inlet pressure when deal- (mm) (m³/h) (l/min) (mm) (m³/h) (l/min)
ing with liquids. However, when sizing valves
0,8 0,02 0,33 13 3 50,0
- the static pressure loss (∆pKv) across the for use with gases and steam, although the
valve may be discharging to atmosphere,
Availability, design and specifications are subject to change without notice. All rights reserved.

valve is 105 Pa (1 bar) 16 4 66,7


only 50 percent of the inlet pressure can 1,2 0,05 0,83
- the fluid is water within a temperature
be used for the pressure drop used in the 18 4,5 75,0
range of 278 K to 313 K (5°C to 40°C)
- the unit of the volumetric flow rate is cubic formulas (commonly called critical pressure 1,6 0,08 1,33 19 6,5 108
metre per hour or litres per minute drop). In all other cases, the pressure drop
is the difference between inlet and outlet 25 11 183
2,4 0,17 2,83
The Kv value can be obtained from test pressures. 32 15 250
results with the help of the following equa-
3,2 0,26 4,33
tion: Note: It is often difficult to understand the 38 22 366
meaning of the term "minimum operating 51 41 683
3,6 0,31 5,17
∆pKv . ρ pressure differential" (see page V045).
Kv = Q 64 51 850
∆p . ρw
Certain pilot operated valves function by 4,8 0,45 7,50
76 86 1433
where: differential pressures created internally
Q is the measured volumetric flow rate by "pilot" and "bleed" arrangements. This 6,4 0,60 10,0 80 99 1650
in cubic metres per hour or litres per differential is measured as the difference
100 150 2500
minute between inlet and outlet conditions on all
8 1,5 25,0
∆pKv is the static pressure loss of 105 Pa valve construction. If pressure conditions 125 264 4400
00011GB-2016/R01

(see above) are not known, but only flow information,


∆p is the measured static pressure loss we can use the graphs or formulas to solve 9 1,7 28,3 150 383 6375
across the valve in pascals the resulting pressure drop.

All leaflets are available on: www.asco.com


V050-1
Flow data, flow factor and orifice size - ENGINEERING INFORMATION

SAMPLE PROBLEMS

LIQUIDS (Tables I and III) AIR AND GASES (Tables I and IV - VII) STEAM (Tables VIII - X)

To find Kv: What Kv is required to pass 22  li- To find Kv: A valve is required to pass To find Kv: A valve is required to pass
tres of oil per minute with a specific gravity 14  nm3/h at an inlet pressure of 4 bar and 25 kg/h of saturated steam at an inlet pres-
of 0,9 and a pressure drop of 1,5 bar? a pressure drop (∆p) of 0,5 bar. sure of 1 bar and a ∆p of 0,2 bar.
Find the Kv if the fluid is carbon dioxide. What is the Kv?
The viscosity is less than 9° Engler.

Solution: The formula is: Solution: Refer to the 1-10 bar graph. Solution: Refer to the appropriate Steam
The formula used is: Graph.
Use the formula:

Q (m3 /h) Q (Nm3 /h) Q (kg/h)


Kv (m3 /h) = Kv (Nm3 /h) = Kv (m3 /h) =
Fgm . Fsg Fgm . Fsg Fgm

Q (m3 /h) Q (Nm3 /h) Q (kg/h)


Kv (l/min) = Kv (Nl/min) = Kv (l/min) =
Fgl . Fsg Fgl . Fsg Fgl

To find Fg, use the Liquid Flow Graph. Locate Fgm at the intersection of 4 bar inlet Locate Fg on graph corresponding to 1 bar
pressure and 0,5 bar pressure drop ∆p (along inlet pressure and a ∆p of 0,2 bar (along
The Fgm factor is that corresponding to a curve). Read down to Fgm = 43,5. curve).
pressure drop of 1,5 bar and equals 1,25. Fgl factor is 2,61. Fgm = 13,8 and the Fgl = 0,83
The Fgl factor is 0,075.
Locate Fsg corresponding to specific gravity
The Fsg factor can be obtained from the of carbon dioxide (= 1,5) on Fsg Chart.
Fsg chart and is that corresponding to 0,09 Fsg = 0,81
specific gravity and equals 1,05.

Therefore: Insert values into formula: Insert values into formula:

−3
Q (Nm3 /h) Q (kg/h)
Kv = 60.22.10 = 1 m3 /h Kv = = 14 = 0, 4 Nm3 /h Kv = = 25 = 1, 8 m3 /h
1, 25.1, 05 Fgm . Fsg 43, 5.0, 81 Fgm 13, 8

−3
Q (Nm3 /h) Q (kg/h)
Kv = 60.22.10 = 16, 7 l/min
14
Kv = = = 6, 62 Nl/min Kv = = 25 = 30 l/min
0, 075.1, 05 Fgl . Fsg 2, 61.0, 81 Fgl 0, 83

Availability, design and specifications are subject to change without notice. All rights reserved.
Formula for liquid Formula for gases (with temperature correction) (1)

(S.G.) (kg/m3) : specific gravity related to water for liquids (1)


To calculate the volumetric flow QN we must know:
(S.G.)N (kg/m3) : specific gravity related to air for gases - the KV coefficient
T1 (°C) : fluid temperature at the valve inlet - the specific gravity (S.G.)N of the fluid
T2 (°C) : fluid temperature downstream of the valve - the pressure loss Dp across the valve
Q (m3/h) : flow - the fluid pressure p2 downstream of the valve
QN (Nm3/h) : volumetric flow across the valve - the fluid temperature T1 at the valve inlet
Kv (m3/h) : flow coefficient
00011GB-2016/R01

p1 (bar) : pressure at the valve inlet


p2 (bar) : pressure downstream of the valve
Dp (bar) : pressure drop

All leaflets are available on: www.asco.com


V050-2
Flow data, flow factor and orifice size - ENGINEERING INFORMATION

Table I : Calculation factor Fsg Table II : Calculation factor Ft for temperature correction

A
Factor Fsg

Factor Ft

FLUID TEMPERATURE t2 (°C)


Specific gravity (S.G.)
The correction for temperature in the
OTHER GRAVITIES OTHER TEMPERATURES range of -7°C to 65°C is very small
and, therefore, can be ignored in
specific gravity (for 1 bar absolute and 15°C) ordinary applications

Table III : Flow calculation Fgm and Fgl for liquids

0,54
Factor Fgm (m3/h)
Factor Fgl (l/min)

0,48

0,42

0,36

0,30
Availability, design and specifications are subject to change without notice. All rights reserved.

0,24

0,18

0,12

0,06

0,03
00011GB-2016/R01

Pressure drop ∆p (bar)

All leaflets are available on: www.asco.com


V050-3
Flow data, flow factor and orifice size - ENGINEERING INFORMATION

Table IV : Flow calculation Fgm and Fgl for air/gas

Pressure drop ∆p (bar)


Inlet pressure 0,01 to 0,1 bar gauge)

Limiting flow curve - Do not read


beyond this curve

Factor Fgm (m3/h)


0,17 0,18 0,21 0,24 0,27 0,30 0,36 0,42 0,48 0,54
Factor Fgl (l/min)

Table V : Flow calculation Fgm and Fgl for air/gas


Pressure drop ∆p (bar)

Limiting flow curve - Do not read Availability, design and specifications are subject to change without notice. All rights reserved.
Inlet pressure of 0,1 to 1 bar (gauge)

beyond this curve


00011GB-2016/R01

Factor Fgm (m3/h)


0,24 0,30 0,36 0,42 0,48 0,6 0,72 0,84 0,96 1,08 1,2 1,32 1,44 1,56 1,68 1,8 1,92 2,04
0,54 0,66 0,78 0,9 1,02 1,14 1,26 1,38 1,5 1,62 1,74 1,86 1,98 2,1
Factor Fgl (l/min)
All leaflets are available on: www.asco.com
V050-4
Flow data, flow factor and orifice size - ENGINEERING INFORMATION

Table VI : Flow calculation Fgm and Fgl for air/gas

A
Pressure drop ∆p (bar)
Inlet pressure of 1 to 10 bar (gauge)

Limiting flow curve - Dot not read


beyond this curve

Factor Fgm (m3/h)


0,6 1,2 1,8 2,4 3,0 3,6 4,2 4,8 5,4 6 6,6 7,2 7,8 8,4 9 9,6 1,02 1,08
Factor Fgl (l/min)

Table VII : Flow calculation Fgm and Fgl for air/gas


Pressure drop ∆p (bar)
Availability, design and specifications are subject to change without notice. All rights reserved.

Inlet pressure 10 to 100 bar (gauge)

Limiting flow curve - Do not read


beyond this curve
00011GB-2016/R01

Factor Fgm (m3/h)


0 6 12 18 24 30 36 42 48 54 60 66 72 78 84 90 96 102
Factor Fgl (l/min)
All leaflets are available on: www.asco.com
V050-5
Flow data, flow factor and orifice size - ENGINEERING INFORMATION

Table VIII : Flow calculation Fgm and Fgl for steam


Pressure drop ∆p (bar)
Inlet pressure of 0,1 to 1 bar (gauge)

Limiting flow curve - Do not read


beyond this curve

Factor Fgm (m3/h)


0,18 0,3 0,42 0,54 0,66 0,78 0,9 1,02 1,08 1,14 1,2 1,26 1,32 1,38 1,44 1,5 1,56 1,62 1,68
0,24 0,36 0,48 0,6 0,72 0,84 0,96
Factor Fgl (l/min)

Table IX : Flow calculation Fgm and Fgl for steam Pressure drop ∆p (bar)
Inlet pressure 1 to 10 bar (gauge)

Limiting flow curve - Do not read


beyond this curve

Factor Fgm (m3/h)


0 0,6 1,2 1,8 2,4 3,0 3,6 4,2 4,8 5,4 6,0 6,6 7,2 7,8 8,4 9,6
Factor Fgl (l/min)

Table X : Flow calculation Fgm and Fgl for steam Availability, design and specifications are subject to change without notice. All rights reserved.
Pressure drop ∆p (bar)
Inlet pressure of 10 to 100 bar (gauge)

Limiting flow curve - Do not read


beyond this curve
00011GB-2016/R01

Factor Fgm (m3/h)


0 6 12 18 24 30 36 42 48 54 60 66 72 78 84
Factor Fgl (l/min)
All leaflets are available on: www.asco.com
V050-6
Flow data, flow factor and orifice size - ENGINEERING INFORMATION

ADDITIONAL FLOW FORMULAS AND Definition of Kv (or Cv) coefficient


PHYSICAL DATA
Valve flow coefficient Kv (or Cv) is the flow of
water (specific gravity = 1), expressed in vol-
ume unit "A" per time unit "B", that will pass
through a valve at a pressure drop equal to
pressure unit "C" (see table below). A
Kv and Cv conversion table
units
symbol conversion formulas
volume "A"/ time "B" pressure "C"
l / min bar Kv 1 Kv = 0,06 Kvh = 0,05 Cve = 0,07 Cv
m /h
3
bar Kvh 1 Kvh = 16,7 Kv = 0,97 Cve = 1,17 Cv
gallon GB (Imp. gallon) / min psi Cve 1 Cve = 17,1 Kv = 1,03 Kvh = 1,2 Cv
gallon US / min psi Cv 1 Cv = 14,3 Kv = 0,85 Kvh = 0,83 Cve

Flow calculation Air and gases Steam and vapours (e.g. refrigerants)
General: Pressure drop values for which no Fgm = 18, 9 ∆p (2p1 − ∆p) (m³/h) For steam:
curves are shown, may be determined by
Fgm = 15, 83 ∆p(2P1 − ∆P) (m³/h)
interpolation in the graphs. However, more Fgl = 1, 13 ∆p (2p1 − ∆p) (l/min)
accurate results can be obtained for the
calculation of the required values by using Fgl = 0, 95 ∆p(2P1 − ∆P) (l/min)
Example: Dp = 0,4 bar;
the following equations (on which the flow
p1 = 3 bar gauge or
graphs are based): Example: Dp = 7 bar,
4,013 bar absolute.
p1 = absolute inlet pressure (bar) = p1 = 40 bar or
gauge pressure plus atmospheric Calculation: 41,013 bar abs.
pressure of 1,013 bar
Fgm = 18, 9 0, 4(8, 026 − 0, 4) = 33 m3 /h Calculation:
p2 = absolute outlet pressure (bar) =
gauge pressure plus atmospheric
Fgl = 1, 13 0, 4(8, 026 − 0, 4) = 1, 97 l/min Fgm = 15, 83 7(82, 026 − 7) = 363 m /h
3
pressure of 1,013 bar
∆p = p1 - p2 = pressure drop across the
valve (bar) Note: The gas equations only apply accu-
t = 0°C rately to a fluid temperature of 20°C (for the Fgl = 0, 95 7(82, 026 − 7) = 21, 8 l/ min
purpose of this catalogue, the standard cubic
Note: In most systems it is desirable to keep metre nm3 has been defined at 20°C and
Note 1: The steam formulas apply to
the pressure drop to a minimum. If neces- 1,013 bar absolute or 760 mm mercury).
saturated steam. For superheated steam
sary - in case of liquids - the pressure drop At a different temperature (= t2 °C) the
a correction factor is required.
may equal the total inlet (gauge) pressure. determined Kv1 value must be adjusted by
Contact ASCO.
This also applies to air, gases and steam the following correction factor.
up to 1,013 bar inlet (gauge) pressure but Note 2: For vapours, e.g. chlorofluorocar-
for these fluids never use a ∆p greater than Ft = 293
bons (CFCs), various other factors have to
50% of the absolute inlet pressure because 273 + t 2 be considered.
excessive pressure drops will cause an ir-
Specific gravity of various liquids at 20°C
Availability, design and specifications are subject to change without notice. All rights reserved.

regular flow. If∆p is not specified and this


information is needed to size the valve, a (related to water at 4°C) Specific gravity of various gases (at 20°C
rule of thumb is to take 10% of the inlet Alcohol, Ethyl 0,79 and atm. pressure and related to air)
pressure as pressure drop. Bezene 0,88 Acetylene 0,91
Carbon tetrachloride 1,589 Air 1,000
Liquids Castor Oil 0,95 Ammonia 0,596
Fuel Oil no. 1 0,83 Butane 2,067
Fgm = ∆p (m3 /h) Fuel Oil no. 2 0,84 Carbon dioxide 1,53
Fuel Oil no. 3 0,89 Chloride 2,486
and Fuel Oil no. 4 0,91 Ethane 1,05
Fuel Oil no. 5 0,95 Ethyl chloride 2,26
Fuel Oil no. 6 0,99 Helium 0,138
Fgl = 0, 06 ∆p (l/min) Gasoline (petrol) 0,75 to 0,78 Methane 0,554
Glycerine 1,26 Methyl chloride 1,785
Example: For ∆p = 1,7 bar, Fgm  =  1,3 (m3/h) Linseed Oil 0,94 Nitrogen 0,971
and Fgl = 0,08 (l/min) will be found. Olive Oil 0,98 Oxygen 1,105
Turpentine 0,862 Propane 1,56
Note: If the fluid viscosity is higher than 300 Water 1,000 Sulphur dioxide 2,264
00011GB-2016/R01

SSU (approx. 9°E), the determined Kv-value


must be adjusted. Contact us. Kv1
The actual flow factor is: Kv 2 =
Ft

All leaflets are available on: www.asco.com


V050-7
Flow data, flow factor and orifice size - ENGINEERING INFORMATION
FLOW COEFFICIENTS
. C and b (following standard ISO 6358) :
Coefficients C (sonic conductance) and b (critical pressure ratio) following standard ISO 6358 allow flow calculation under sonic
conditions (See solenoid pilot valves 195/LISC - section I).

q*m q*: mass flow rate q*m (kg/s) or volume q*v (m3/s) through a component at sonic flow
C=
ρo p1 p1: inlet pressure (bar)
q*v ρo = 1,3 kg/m3 : density under standard conditions (p0 = 1 bar, T0 = 293,15 K and 65% relative humidity)
C=
p1

b : pressure ratio below which the flow is sonic:


P2 P2: outlet pressure (bar)
b=
P1 P1: inlet pressure (bar)
qm depending on P1, T1
and C
P1 and T1 are constant
q*m
Ellipse quarter, depending on
P1, T1 and C and b coefficients

T1, temperature (°K) measured when the flow is sonic


0 b 1
Pout / Pin
Sonic flow Subsonic flow

CALCULATION OF FLOW (for air and gas)


. Defining flow at 6 bar:
The corresponding leaflets give for each product its mean flow in litres per minute at 6 bar at a standard reference atmosphere
(ANR) conforming to ISO 8778 (with ∆ P = 1 bar)
. Calculation of flow:
∆ P < P inlet /2 ∆ P ≥ P inlet /2
(Maximum allowable flow)
Q = 28,16 x Kv x ∆P x Pin Q = 14 x Kv x Pout

including correction for temperature and density including correction for temperature and density

Q = 475 x Kv x (∆P x Pin) Q = 238,33 x Kv x Pout x 1


(Ta x d)
Availability, design and specifications are subject to change without notice. All rights reserved.
(Ta x d)

Q = Flow in l/min Pin = Absolute inlet pressure, in T
bar a
= Absolute temperature, in Celsius degrees
∆P = Differential pressure, in bar
Pout = Absolute outlet pressure, in
bar d = Density compared with air
00011GB-2011/R01

All leaflets are available on: www.asco.com


V050-8

Potrebbero piacerti anche