2) Piping length
Length as pipe diameter 1/4" 3/8" 1/2" 5/8" 3/4" 7/8" 1" 1 1/8" 1 1/4" 1 3/8" 1 1/2" 1 5/8" 1 3/4" 1 7/8" 2" 2 1/8"
1. Liquid piping m 35.00
2. Gas piping m 35.00
3. High pressure gas piping m
Restriction of pipe length Restriction (Based on installation manual) Actual piping length Equivalent piping length
1. Total piping length m 1000.00 35.00
2. Maximum piping length m 200.00 35.00 35.00
3. Main pipe length m 35.00
4. Piping length between the first branch and the farthest indoor unit m 45.00/90.00
5. Level difference between outdoor and indoor unit(Max)
m 40.00/110.00 -2.00
(OD above ID unit / OD below ID unit)
6. Level difference between indoor units m 50.00
- The system configuration may be different from the actual installation conditions, refer to the installation manual.
- The system configuration may be different from the actual installation conditions, refer to the installation manual.
Kcal/h 24200
Cooling (SHC) kW 21.9217
Kcal/h 18850
Heating kW 31.6517
Kcal/h 27220
Power Power Input(Nominal) Cooling 790
W
Heating 790
Current Input Cooling 5.9
A
Heating 5.9
Fan Motor Type - Sirocco Fan
Output W 400
Number of unit EA 1
Shipping Weight kg