Sei sulla pagina 1di 100

Fault Analysis

Ed Khan
August, 2013

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Disclaimer

This material being presented is based on good engineering and industry practices. It also contains views and
engineering approach of the presenter based on his personal experiences as a practicing engineer.
Neither the presenter nor Quanta Technology is responsible for any damages, direct or consequential, that may
arise as a result of applying the knowledge gained from this course. Every application in the field needs specific
approach based on all the facts surrounding the application. The material presented is general and must be
applied after taking all facts and deviations into consideration.

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis

Power systems , in normal state, operate as a


balanced three phase ac.
However, there are a number of unavoidable and
undesirable events that temporarily disrupt the
normal operation of power system

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis

What is short circuit?


If the insulation of the system should fail at any
point, or if a conducting object should come in
contact with a bare power conductor a “short circuit”
or “fault” is said to occur.

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis

Is it possible to build a fault-proof” power system?


No
Practically: Very difficult
Economically: Will be extremely expensive

Modern power systems, designed with a high level


of insulation and with main and backup configuration
helps avoid complete shutdown
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis

Consequences of Short Circuits

Consequences vary depending on:


 The type of fault
 Duration of the fault
 Location of the fault
 Short circuit capacity of the source

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis

Consequences of Short Circuits

Consequences Include:
 Damage to Insulation
 Welding of conductors
 Fire and damage to life
 Deformation of busbars
Transformer damage (on through faults
Cable damage
Voltage dips resulting in load of motor loads
 Control and monitoring circuits will be disturbed
Loss of system stability if fault remains for too long
Loss of faulty network
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis

Three Phase Fault

Phase-Phase Fault
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis

Phase-Ground Fault

Phase-Phase-Ground Fault
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis

Open Phase

80% of faults are line-ground


15% of faults are line-line
5% of faults are three phase

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis Using Ohms

Transmission Line
Source 1.4 ohms
0.3809 ohms 13.8 kV
13.8 kV

Resistance Ignored

1.4 Ohms
0.3809 Ohms
If=V/X=7967.43/(0.3809+1.4)
=4473.82A
13.8 kV 1.73205
=7967.43V

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis Using Ohms

Transmission Line
5 MVA
Source 0.10 ohms at 4.16 kV
2.285 ohms
0.3809 ohms 13.8 kV 4.16 kV
at 13.8 kV
At 13.8 kV

When two voltage levels are involved,


ohmic method becomes cumbersome

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis

Transmission Line
5 MVA
Source 0.10 ohms at 4.16 kV
2.285 ohms
0.3809 ohms 13.8 kV 4.16 kV
at 13.8 kV
At 13.8 kV
Fault is at 4.16 kV bus.
Hence all impedances have to be referred Resistance Ignored
To 4.16 kV bus

Source impedance:
.3809 * 4.16^2/13.8^2=0.0346 ohms referred to 4.16 kV

Transformer impedance is referred to 13.8 kV


We need it referred to 4.16 kV.
2.285 * 4.16^2/13.8^2=0.2076 ohms referred to 4.16 kV
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis

Transmission Line
5 MVA
Source 0.10 ohms at 4.16 kV
.2076 ohms
0.0346 ohms 13.8 kV 4.16 kV
at 4.16 kV base
At 4.16 kV base

Resistance Ignored
0.2076 Ohms

0.10 Ohms
0.0346 Ohms
If=V/X=7967.43/(0.0346+0.2076+0.1)
=23282.96 A
13.8 kV 1.73205
=7967.43V

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


1500kW
Pf 0.8
Fault Analysis 4.16 kV Passive Load

5MVA Transmission Line


Source 0.277 ohms 1.4 ohms
0.3809 ohms 13.8 kV Motor
referred to X”d=.6922
referred to 4.16 kV side
13.8 kV 1800kW ohms
Pf 0.8
Passive Load

Transformer Load Transmission Line Motor


Source Load Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis

Source Load Transformer Load Transmission Line Motor

In short circuit calculations we ignore:


Capacitor discharge current
Transformer magnetizing branch
Load
Line capacitance
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis

Pwr. Co 500 MVA SC


Capacity

13.8 kV

5 MVA
13.8 kV/4.16 kV
Z=6%

4.16 kV

5 MVA Motor
X”d=0.25 per unit
Motor

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis

Base Current in amperes = Base KVA/(Base voltage in kV)

Base impedance=Base voltage in volts/Base current in amperes

Base impedance= (Base voltage in kV)2 X 1000/base KVA

Base impedance=Base voltage in kV/base MVA

Base power in KW = Base KVA

Base power in MW = Base MVA

Per Unit impedance of a circuit element=actual impedance in ohms/base impedance in ohms

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Calculate the three phase fault
500 MVA SC
current using per unit
Pwr. Co
Capacity Method using 100MVA as a base.
13.8 kV
Ignore resistances
5 MVA
13.8 kV/4.16 kV XS = MVAbase/MVASC
Z=6% =100/500=0.200 pu

4.16 kV
XTX=XTX (old)*MVAbase /MVATX
=0.06*/(100/5)=1.2 pu
5 MVA Motor
X”d=0.20 per unit
Motor XMTR=XMTR (old)*MVAbase/MVAMTR
=0.20*/(100/5)=4.0 pu

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Xf=0.2+1.2 paralleled with 4

=1.037 pu

IF=Ef/Xf=1.0/1.037=.9673 pu
0.2
IBASE =KVABASE /(1.732*KVBASE )

1.2 =100,000/(1.732*4.16)
=13,879A

X If= IBASE * If (in pu)


4
=13,879*0.9643
=13,383 A

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Use 100 MVA base
300 MVA SC
Pwr. Co
Capacity

13.8 kV

1 MVA
13.8 kV/4.16 kV 1 MVA
Z=5% 13.8 kV/6.9 kV
Z=6%
4.16 kV

6.9 kV

Motor
Motor Gen
600 HP 1MVA
X”d=0.25 per unit 200 HP X”d=0.10 per unit
X”d=0.25 per unit
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis
41.6

300 MVA SC 0.33 5


Pwr. Co
Capacity

13.8 kV 6

1 MVA
13.8 kV/4.16 kV
Z=5%
1 MVA
X
13.8 kV/6.9 kV
4.16 kV 125 10
Z=6%
6.9 kV

Motor
Motor Gen
600 HP 1MVA
X”d=0.25 per unit 200 HP X”d=0.10 per unit
X”d=0.25 per unit
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis

41.6
46.6
0.33 5 0.327
0.33

6
6 6

X X X
125 10
9.26 9.26

Eq fault impedance=parallel combination of 9.26 and 6.327=3.759

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis

Base MVA =100


Base Current=100*1000/(1.732*6.9)=8367.64
Eq Fault impedance is=3.76 pu
I pu=Vpu/Zpu=1/3.76=0.266
Fault Current=8367.64*0.266=2226A

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Advantages of Per Unit Calculations:
1. Impedance provided by manufacturers is listed in per cent or
per unit
2. Publications listing average ratings of electrical equipment is
provided in per cent or per unit based on equipment base rating
3. The per unit impedance of three phase transformers is not
effected by the way in which it is connected. The relationship
of voltage bases on the primary and secondary still is determined
by the primary and secondary voltage rating
4. When impedance in in ohms is specified in an equivalent circuit,
each impedance must be referred to the same circuit by
multiplying it by the square of the ratio of the rated voltages of the
two sides of the transformer.
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis
Data Required:
1. Utility Service Entrance
2. Induction Motor
3. Synchronous Motor
4. Generators
5. Cables
6. Transmission Lines
7. Bus Ducts/Isophase Bus
8. Transformers
9. Circuit Breakers
10. Switches
11. Fuses
12. Neutral Grounding Methods and Ratings
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis
Data Description:
Utility Source Data
Data needed includes Positive and zero sequence impedance data and system operating
at facility service entrance.

This data can be given by the utility/power company in a variety of ways including ohms,
Per unit impedance, amperes, and MVA

Example:
Utility contribution to a 3 phase fault is 485 MVA. X/R Ratio is 12. System Voltage is 13.8 kV
Convert this to per unit impedance:
Base MVA selected is 100 MVA
Per unit Z=Base MVA/SC MVA=100/485=0.2061856 per unit ohms
Based on an X/R of 12 we get the angle of 85.236 degrees
R=Cos(85.236)*Z=Cos(85.236)*0.2061856=0.01712 per unit ohms
X=Sin(85.236)*Z=Sin(85.236)*0.2061856=0.205473 per unit ohms

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Data Description:
Utility Source Data
Example:
So Z=0.2061856 per unit ohms
R=0.01712 per unit ohms
Voltage is 13.8 kV =1 per unit
Base MVA=100
SC MVA is 485

If SC MVA is 485 this translates to 485*1000/(1.732*13.8) Amperes


=20,291.52 Amperes.

From per unit impedance we get I pu= V pu/Z pu= 1/0.2061856 pu Amps=4.85 pu Amps
Base Amps= Base MVA*1000/(1.732*13.8)=4183.82 Amperes
Fault current in amperes = PU SC short current * Base Amps= 4.85*4183.82=20291.52 Amperes
Utility could provide the data as 20,291.52 amperes at 13.8 kV with X/R of 12. You can convert
Current to MVA and then get the impedance

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Data Description:
Motor Data
1. Location
2. Rated Voltage
3. Horse Power
4. Speed
5. Type-Induction or synchronous (if Synchronous we need PF)
6. Subtransient Reactance
7. X.R ratio

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Data Description:
Motor Data
Typical Reactances
Individual Induction motors usually above 600 V X”d=0.17
Group of motors each less than 50 HP usually 600V and below X”d=0.25
Synchronous motors (6 poles) X”d=0.15
Synchronous motors (8-14 poles) X”d=0.20
Synchronous motors (16 poles and more) X”d=0.28

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Data Description:
Typical X/R Ratio for Motors

Show Graph

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Data Description:
Generator Data
1. Location
2. Rated Voltage
3. KVA
4. Speed
5. X’d and X0
6. X.R ratio

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis

Generator Data
Typical Reactances
Turbine Generators
2 Poles X”d=0.09
4 Poles X”d=0.15
Salient Pole generator with damper windings
12 poles or less X”d=0.16
14 poles or more X”d=0.21

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis

Generator Data
Graph of X/R

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Data Description:
Cable Data
1. Location
2. Voltage rating
3. Single Conductor or three Conductor cable
4. Magnetic or non-magnetic conduit
5. Copper or Aluminum
6. Number of conductors per phase
7. Conductor size
8. Conductor length
9. Shielded or non shielded

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Data Description:
Transformer Data
1. Location
2. Primary and secondary voltage rating
3. kVA
4. Connection
5. Impedance
6. X/R ratio
7. Grounding method

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Data Description:
Transformer Data

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Data Description:
Transformer Data

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Data Description:
Transformer Data

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Data Description:
Transformer Data

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Data Description:
Bus Duct
1. Location
2. Ampacity
3. Type
4. Material
5. Length
6. Bus Bracing for short circuits

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Data Description:
Medium Voltage Circuit Breaker
1. Manufacturer
2. Type
3. Interrupting rating
4. Momentary or Close and Latch rating
5. Maximum rated Voltage
6. Minimum Voltage or K factor
7. Operating Voltage
8. Continuous Rating
9. Interrupting Time

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Data Description:
Medium Voltage Circuit Breaker

1200,2000 A and 3000A

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Data Description:
Medium Voltage Circuit Breaker

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Data Description:
Medium Voltage Circuit Breaker

1200-2000 A for 27 kV breakers

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Data Description:
High Voltage Circuit Breaker –Live Tank

1200-2000 A for 27 kV breakers

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Data Description:
High Voltage Circuit Breaker –Dead Tank

1200-2000 A for 27 kV breakers


Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis
Data Description:
Low Voltage Circuit Breaker
1. Manufacturer
2. Type
3. Trip rating
4. Frame size
5. Symmetrical Interrupting rating
6. Asymmetrical Interrupting rating
7. Operating Voltage
8. Time Current characteristics of the trip device

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Data Description:
Fuses
1. Manufacturer
2. Type
3. Ampere or size designation
4. Rated Voltage
5. Symmetrical Interrupting rating
6. Asymmetrical Interrupting rating
7. Operating Voltage
8. Time Current characteristics curve

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Data Description:
Switches
1. Manufacturer
2. Type
3. Continuous Rating
4. Momentary Rating
5. Fault Closing rating
6. Asymmetrical Interrupting rating
7. Operating Voltage
8. Time Current characteristics curve

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Data Description:
Panel Boards, Motor Control Centers and Switchgear Bus
1. Symmetrical short circuit rating
2. Asymmetrical short circuit rating
3. Continuous Rating

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Symmetrical Components

Balanced faults are very easy to calculate (three phase fault is balanced)

How about unbalanced faults (line to line, line to earth , etc.)

These cannot be calculated based on methods pointed out earlier.


We could make single phase representation and this simplifies solution.

For unbalanced faults we use a methodology called Symmetrical


Components.

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Symmetrical Components

Symmetrical Components was discovered in 1918 by


Charles Legeyt Fortescue.

He found that any set of unbalanced three phase quantities could


be expressed as a sum of three symmetrical sets of balanced
quantities.

Very useful for analyzing unbalanced faults where we have


unbalanced quantities.

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Symmetrical Components

For three phase faults:


Prefault Fault
Va=110 <0 Va=5 <0
Vb=110<-120 Vb=5<-120
Vc=110<120 Vc=5<120

Ia=10<-30 Ia=100<-30
Ib=10<-150 Ib=100<-150
Ic=10<90 Ic=100<90
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis
Symmetrical Components
Unbalanced
For line-earth faults:
Prefault Fault
Va=110 <0 Va=0 <0
Vb=110<-120 Vb=110<-120
Vc=110<120 Vc=110<120

Ia=10<-30 Ia=150<-30
Ib=10<-150 Ib=0<-150
Ic=10<90 Ic=0<90
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis
Symmetrical Components

We can breakdown Va into three symmetrical components


Va1, Va2, and Va0. Similarly, Vb and Vc can be broken down

Ia can be split into Ia1, Ia2, and Ia0. Similarly Ib and Ic can be
broken down as well into three components.

Three balanced components ----Positive, Negative and Zero.

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Symmetrical Components

c1 b2

120 120
120 a1 120 a2 a0

b0
120
120
c0
b1 c2

Zero Sequence
Positive Sequence Negative Sequence No sequence—all
Sequence ABC Sequence ACB In phase

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Symmetrical Components

Va=Va1+Va2+Va0 ------Va=Va1+Va2+Va0
Vb=Vb1+Vb2+Vb0 ------Vb=1<240 Va1+1<120Va2+Va0
Vc=Vc1+Vc2+Vc0 ------Vc=1<120 Va1+1<240Va2+Va0

Vc1 Vb2
Va0

Va1 Va2 Vb0

Vc0

Vb1 Vc2

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Symmetrical Components

Va=Va1+Va2+Va0 = V1+V2+Va0
Vb=1<240Va1+1<120Va1+Va0 = 1<240V1+1<120V2+Va0
Vc=1<120Va1+1<240Va2+Va0 = 1<120V1+1<240V2+Va0
1<120 V2
1<120 V1
V0

V1 V2 V0

V0

1<240 V2
1<240 V1

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Symmetrical Components
Operator a
a operates the vector by +120 degrees (1<120)
a2 operates the vector by +240 degrees (1<240)
a3 operates the vector by +360 degrees so is equal to 1<0
a4 operates the vector by +120 degrees so is equal to a
a V2
a V1

V1 V2 V0

a2 V1 a2 V2
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis
Symmetrical Components

Va= V1+V2+Va0 =V1+V2+V0


Vb= 1<240V1+1<120V2+Va0 =a2V1+aV2+V0
Vc= 1<120V1+1<240V2+Va0 =aV1+a2V2+V0
1<120 V2
1<120 V1

V1 V2 V0

1<240 V2
1<240 V1

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Symmetrical Components

Va = V1 + V2 + V0
Vb = a2 V1 + aV2 + V0
Vc = aV1 + a2 V2 + V0

Va+Vb+Vc = 0 + 0 + 3V0

V0=1/3(Va+Vb+Vc)
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis
Symmetrical Components

Va = V1 + V2 + V0
aVb = a3V1 + a2V2 + aV0
a2Vc = a3V1 + aV2 + a2V0

Va+aVb+a2Vc = 3V1 + 0 +0

V1=1/3(Va+aVb+a2 Vc)
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis
Symmetrical Components

Va = V1 + V2 + V0
a2Vb = a4V1 + a3V2 + a2V0
aVc = a2V1 + a3V2 + aV0

Va+a2Vb+aVc = 0 + 3V2 +0

V2=1/3(Va+a2Vb+a Vc)
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis
Symmetrical Components
Important Formulas
V1=1/3(Va+aVb+a2 Vc)
V2=1/3(Va+a2Vb+a Vc)
V0=1/3(Va+Vb+Vc)
Va= V1+V2+V0
Vb= a2V1+aV2+V0
Vc= aV1+a2V2+V0

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Symmetrical Components
Important Formulas
I1=1/3(Ia+a Ib+a2 Ic)
I2=1/3(Ia+a2Ib+a Ic)
I0=1/3(Ia+Ib+Ic)
Ia= I1+I2+I0
Ib= a2 I1+a I2+V0
Ic= a I1+a2 I2+V0

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Symmetrical Components
Example:
Following are the voltages in a three phase system
Va=60<0
Vb=87<-59
Vc=121 <100
Find positive, negative and zero sequence
Components (V1, V2, V0)

V1=1/3 *(Va+aVb+a2Vc)
V1=1/3* (60<0 +1<120*87<-59 + 1<240* 121<100)
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis
Symmetrical Components
Example:
Following are the voltages in a three phase system
Va=60<0
Vb=87<-59
Vc=121 <100
V1=1/3* (60<0 +1<120*87<-59 + 1<240* 121<100)
V1=1/3* (60<0 + 87<62 +121<340)
V1=1/3*(60+j0 +40.844+j76.82+113.70-j41.38)
V1=1/3*(214.54+j35.44)=71.51+j11.81

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Symmetrical Components
Example:
Following are the voltages in a three phase system
Va=60<0
Vb=87<-59
Vc=121 <100
V2=1/3* (60<0 +1<240*87<-59 + 1<120* 121<100)
V2=1/3* (60<0 + 87<181 +121<220)
V2=1/3*(60+j0 -86.986-j1.52-92.7-j77.77)
V2=1/3*(-119.68-j79.29)=-39.9-j26.43

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Symmetrical Components
Example:
Following are the voltages in a three phase system
Va=60<0
Vb=87<-59
Vc=121 <100
V0=1/3* (60<0 +87<-59 + 121<100)
V0=1/3* (60+j0 + 44.80-j74.57-21+j119.16)
V0=1/3*(83.80+j44.59)=27.93+j14.86

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Symmetrical Components
Example:
Following are the voltages in a three phase system
Va=60<0
Vb=87<-59
Vc=121 <100

V0=1/3*(83.80+j44.59)=27.93+j14.86=31.63<28
V1=1/3*(214.54+j35.44)=71.51+j11.81=72.48<9.37
V2=1/3*(-119.68-j79.29)=-39.9-j26.43=47.86<33.52
Va=V1+V2+V0=59.54+j0.24=59.54<0.23
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis
Symmetrical Components
Example:
Following are the voltages in a three phase system
V0=1/3*(83.80+j44.59)=27.93+j14.86=31.63<28
V1=1/3*(214.54+j35.44)=71.51+j11.81=72.48<9.37
V2=1/3*(-119.68-j79.29)=-39.9-j26.43=47.86<213.52
Vb=a2 V1+aV2+V0
=1<240*72.48<9.37+1<120*47.86<213.52+31.63<28
=72.48<249.37+47.86<333.52+31.63<28
=-25.537-j67.832+42.84-j21.34+27.93+j14.86
=45.233-j74.31=87<-58.7
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis
Symmetrical Components
Example:
Following are the voltages in a three phase system
V0=1/3*(83.80+j44.59)=27.93+j14.86=31.63<28
V1=1/3*(214.54+j35.44)=71.51+j11.81=72.48<9.37
V2=1/3*(-119.68-j79.29)=-39.9-j26.43=47.86<213.52
Vc=a V1+a2 V2+V0
=1<120*72.48<9.37+1<240*47.86<213.52+31.63<28
=72.48<129.37+47.86<93.52+31.63<28
=-45.97+-j56.032-2.938-j47.77+27.93+j14.86
=-20.98+j118.66=120.50<100
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis
Nature of Short Circuit
R
L
t=0
V(t)
I(t)

V(T)=Vmax*Sin(ωT+ α)
Total Current in the loop is given by Eqn. 1
I(T)=(Vmax/magZ)*[Sin(ωT+ α- θ)-eRT/L *Sin(α-θ)]
Where Mag Z= Square root of R2 + X2 and θ=Tan-1 (ωL/R)
α-=Angle on the voltage waveform at which the fault occurs (T=0)
T is time in seconds
ω is Frequency in radians
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis
Nature of Short Circuit
When the switch closes at T=0, total fault current
waveform can be shown as below
Total fault Degrees
current
90 180 270 360 450
0

Decaying dc
component

1 1 3/4
AC Component Cycles
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis
Nature of Short Circuit
EQ.1 has two parts:

AC Component is:
Total fault
(Vmax/Z mag)* Sin(ωT+ α-θ ) current

DC Component is:

e-(R/L)T *Sin(α-θ) Decaying dc


component AC Component

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Symmetrical Current

If α-ϴ = 0 or +/- π Then Sin(α-ϴ)=0


The DC component under such condition will be zero.
Only AC Component will be present

This will result in a symmetrical waveform given by:

I(T)=(Vmax/Z mag)*Sin ωT
where Zmag is the magnitude of short circuit impedance

Current
Short Circuit
Initiation Voltage
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis
Symmetrical Current
This condition of no dc component will be present
is the fault occurs at α= ϴ=Tan-1 (X/R)
If R=X (Totally reactive circuit) will mean α=Tan-1 (X/R)=90
Degrees.
Voltage
Current
Fault occurs at 90
degrees on Short Circuit
voltage Initiation

waveform
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis
Asymmetrical Current

If α= ϴ=+/-90 degrees then Sin(α- ϴ) is +/-1 and the


Dc component will be maximum.

The waveform is then represented by the following:


I(T)=(Vmax/magZ)*[Sin(ωT+/-90)-eRT/L *Sin(+/-90)]

This results in a fully offset waveform.


This is due to the term Sin(+/-90)

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Asymmetrical Current

The waveform is referred to asymmetrical since it is not


symmetrical about the x axis.
Isc
V

Fully Offset
Current Waveform

V
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis
Asymmetrical Current
Consider a totally reactive circuit and assume
α-ϴ=-90 and θ=90.
This means α=0
Isc

Short circuit V
initiated
Fully Offset
Current Waveform

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Asymmetrical Current

If the fault closing angle is somewhere between zero and


90 degrees on voltage waveform we get partially offset
waveform
Isc
Short circuit
initiated

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Asymmetrical Current

The DC component decays with time because of


resistance in the circuit. X/R ratio determines the rate at
which it decays. The larger the X/R ratio the longer is
is the delay.

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Asymmetrical Current

Total asymmetrical waveform

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Characteristics Power Co.
of short circuit
contributions

Syn Gen.
Syn Mtr.

2ms
Ind. Mtr.
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis
Characteristics Utility/Power Co.
of short circuit
contributions Syn. Generator

Syn. motor

Ind. motor

Total

From GE Industrial Power Systems Data Book


Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis
Wind-Turbine Generators
Wind turbine generators are induction machines
of various types.

Fault current simulates that of induction machines

Can be prolonged if reactive source is present to


sustain faults.

Manufacturer needs to be contacted to get exact profile


of short circuit
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis
Asymmetrical short circuit current is very
important factor because it increases the total
rms current.

Also:
Circuit breakers and fuses have to interrupt
asymmetrical current
 Bracing of electrical equipment is based on
asymmetrical current
Some Instantaneous relays respond to
asymmetrical current
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis

Main concern for equipment rating


is the 1//2 cycle for devices that operate
Instantaneously.

We also need to know what happens from time


2 to 8 cycles or so– Breakers interrupt in this time frame

Making current is tied to fist cycle

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis

Maximum value of the first half cycle current is calculated


Using the following equation:
Irms (1/2 cycle)=Isym Sq. root of 1+2e-2π/(x/r) rms Asymmetrical

Where X=inductive reactance


R=Resistance
Isym =symmetrical AC rms current at ½ cycle

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis

Making Duty

Current reaches maximum value during first half cycle after


fault is initiated.
This level of short circuit exerts tremendous mechanical
force on electrical equipment.

Force is directly proportional to the square of the current.

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis

Making Duty
Hence, this current rating is used to evaluate the mechanical
Capability of equipment such as:

Medium voltage breaker momentary/making/close


and latch ratings

Withstand rating of switches

Bus bracings
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis
Making Duty
Hence, this current rating is used to evaluate the mechanical
Capability of equipment such as:

Fuse breaking or interrupting rating is based on ½ cycle


magnitude

Molded case circuit breakers and low voltage power


circuit breaker may start interruption process within
first half cycle.

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Making Duty
Hence, this current rating is used to evaluate the mechanical
Capability of equipment such as:

Instantaneous overcurrent relays and low voltage breakers


with instantaneous trip feature respond to first half cycle
short circuit currents

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
How do we evaluate device SC capabilities
Load Break Switches

These switches interrupt load currents and do not interrupt


short circuit currents.

The switch must however withstand the short circuit currents


that flow through it.

It must be able to close into a fault.

This is based onCopyright


½ cycle fault currents.
© 2012, Quanta Technology, LLC Confidential and Proprietary
Fault Analysis
Medium Voltage Circuit breakers rated per ANSI

1200-2000 A for 27 kV breakers

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Medium Voltage Circuit breakers rated per IEC

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis
Medium Voltage Circuit breakers rated per ANSI

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary


Fault Analysis

Do not worry. Help is there

Software does all this evaluation for you


Both for ANSI rated and IEC rated breakers

Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary

Potrebbero piacerti anche