Sei sulla pagina 1di 11

ACI STRUCTURAL JOURNAL TECHNICAL PAPER

Title no. 106-S32

Cyclic Response of Exterior Beam-Column Joints with


Different Anchorage Methods
by Hung-Jen Lee and Si-Ying Yu

This paper presents the cyclic response of six exterior beam- head area ratio, Abrg/Ab, which is defined as the ratio of net
column joints with or without eccentricity to evaluate the use of head bearing area, Abrg, to the nominal bar area Ab. The
mechanical anchorages in place of hooked bar anchorages. In high larger the relative head area ratio, the greater the tensile stress
seismic zones, the hooked beam bars often cause steel congestion that can be developed near the head. A headed deformed bar
in a joint at building corners. From previous tests of beam-column with smaller relative head area plus an additional bonded
joints, the use of mechanical anchorages in place of hooked bar
anchorages provides a promising solution for steel congestion, but
length can also be used. It is typical that longitudinal bars
it has not been verified in eccentric beam-column joints. The terminated within a beam-column joint are deeply embedded.
presented experimental program demonstrates that eccentric Therefore, headed bars with a smaller relative head area can
beam-column joints with mechanical anchorages can exhibit be used by considering the head bearing component plus the
satisfactory performance and adequate anchorage capacity for a bond component within the joint. With a smaller relative head
limiting drift ratio. Extending ACI design methods to cover the use area, however, the possibility of side-face blowout and
of mechanical anchorages for eccentric beam-column joints is an concrete crushing at the head should be checked.
appropriate code modification. Test results also indicate that the In the early 1990s, Wallace et al.9 conducted cyclic
cyclic behavior of exterior beam-column joints can be significantly loading tests of isolated beam-column joints to address the
improved by attaching double mechanical devices on each beam
bar within the joint.

Keywords: anchorage; beam-column joint; connection; headed bar;


seismic design.

INTRODUCTION
Hooked bar anchorages are commonly used for longitudinal
beam flexural reinforcing bars terminating within a building
beam-column joint. To promote the development of a diagonal
compression strut within a beam-column joint under earthquake-
type loading, it is well accepted that hooked bars should be bent
into the joint with the hook embedded as far as possible from the
critical section. This requirement and the specified dimension of
standard hooks in ACI 318-08,1 however, often cause steel
congestion in an exterior or corner beam-column joint, as shown
in Fig. 1, thereby making fabrication and construction difficult. Fig. 1—Congestion of hooks in eccentric beam-column
To ease the congestion problem within the beam-column joint, connection during fabrication.
the use of headed bars in place of hooked bars is a viable option.
Headed bars are fabricated by attaching an anchor plate or
forged head onto the end of a reinforcing bar to provide
mechanical anchorage by head bearing. The pullout behavior
and anchorage capacity of headed bars have been extensively
studied at the Universities of Calgary,2 Kansas,3 and Texas at
Austin.4-8 Researchers4-6 used a simple and convenient
definition to distinguish shallowly-embedded headed bars
from deeply-embedded headed bars, from which embedment
depth to the bearing face of head was at least five times the
least cover dimension, as shown in Fig. 2. Concrete breakout
is the primary failure mechanism of shallowly-embedded
headed bars, similar to that of anchor bolts embedded into
concrete (ACI 318-08,1 Appendix D). For a deeply-embedded
Fig. 2—Shallow versus deep embedment for headed bars.
headed bar, the primary failure mechanism is side-face blowout
of cover concrete when the headed bar is close to a side face.
If headed bars are closely spaced, crushing of the concrete at ACI Structural Journal, V. 106, No. 3, May-June 2009.
the head may occur. MS No. S-2007-313.R2 received April 23, 2008, and reviewed under Institute
publication policies. Copyright © 2009, American Concrete Institute. All rights reserved,
Previous studies5-8 have shown that the anchorage including the making of copies unless permission is obtained from the copyright proprietors.
Pertinent discussion including author’s closure, if any, will be published in the March-
capacity of a headed bar is strongly related to the relative April 2010 ACI Structural Journal if the discussion is received by November 1, 2009.

ACI Structural Journal/May-June 2009 329


More recently, Chun et al.11 tested beam-column joints
ACI member Hung-Jen Lee is an Assistant Professor at the National Yunlin University
of Science and Technology, Yunlin, Taiwan. He received his BS from the National with large-diameter bars (22, 32, and 36 mm [No. 7, No. 10,
Taiwan University in 1995, and his MS and PhD from the National Taiwan University and No. 11]) and a relatively small head area ratio (between
of Science and Technology in 1997 and 2000, respectively. His research interests
include testing on structural concrete elements, behavior of beam-column connections,
3 and 4) because prior tests9 of beam-column joints used
and strut-and-tie models. small-diameter bars (16, 20, and 25 mm [0.63, 0.79, and
1.0 in.]) with a relatively large head area ratio between 4.0
Si-Ying Yu is a Supervision Engineer at the Wu Chang-Cheng Architect Business and 11.4. Five exterior and four roof corner joint specimens
Office, Taiwan. She received her BS and MS from the National Yunlin University of
Science and Technology in 2004 and 2006, respectively. were constructed with threaded headed bars and tested under
a cyclic loading up to 3.5% drift ratio or higher. The
researchers concluded that a relative head area ratio between
use of headed bars in high seismic zones. Two exterior joints 3 and 4 is sufficient to anchor the beam bars effectively
and three roof corner joints were constructed with threaded within exterior beam-column joints. Thus, the research
or friction-welded headed bars. Wallace et al.9 concluded extended the ACI 352R-0210 provisions to cover multiple
that the behavior of the specimens with headed bars was as layers of large-diameter bars with closely-spaced heads.
good as, or better than, that of similar specimens with The previous cyclic tests9,11 of headed bars were conducted
standard 90-degree hooks. Based on limited test data on exterior or roof corner beam-column joints without eccen-
available, Wallace et al.9 recommended a minimum tricity. In practice, eccentric beams are often used at the edge or
anchorage length of 12db and a minimum relative head area corner of a building frame. LaFave et al.12 noted that eccentric
ratio of 4. To date, the Joint ACI-ASCE Committee 352 connections had somewhat lower joint shear strengths than
report, “Recommendations for Design of Beam-Column similar concentric connections in most of the available studies.
Connections in Monolithic Reinforced Concrete Structures It is known that the existence of slabs and transverse beams
(ACI 352R-02),”10 adopted the recommendations of framing into the joint can reduce the effect of eccentric beams
researchers3,4,9 to allow the use of headed bars terminating on edge beam-column-slab connections.13,14 Due to the lack of
in beam-column joints. ACI 352R-02,10 Section 4.5.3, points slabs and beams confined on two opposite faces, however,
out that any headed bar meeting ASTM A970 specifications can corner beam-column joints are more vulnerable to deterioration
be used in a beam-column joint if its embedded length is not less than edge or interior joints under an earthquake-type loading.
than 8db, 150 mm (6 in.), or 3/4 of the development length for a The use of headed bars in place of hooked bars in eccentric
hooked bar. Although the minimum development length of a beam-column joints at building corners, therefore, need to be
headed bar is shorter than that of a hooked bar, either bar heads evaluated due to the possibility of side-face blowout at the heads
or hooks should be located within 50 mm (2 in.) from the back close to free surface. An experimental investigation was
of the confined core to promote a better force-transferring conducted to evaluate cyclic response of concentric and
mechanism. The embedded length, therefore, should be the eccentric beam-column joints with different anchorage
same for either headed or hooked bars; but fewer headed bars of methods. The connection parameters were designed to
larger diameter could be used because of the shorter development meet the requirements for special moment frames in high
length. This advantage can be used for easing the steel congestion seismic zones. This paper also evaluates the performance
in beam-column joints. of the beam-column joints with different anchorage
methods in compliance with ACI 374.1-05, 15 which
discusses the acceptance criteria for moment frames
based on structural testing.

RESEARCH SIGNIFICANCE
No available data exist showing that headed bars can be safely
used in eccentric beam-column joints. Cyclic loading tests of
exterior beam-column joints with concentric or eccentric beams
were conducted to evaluate the use of mechanical anchorage
devices in place of the standard 90-degree hooks on longitudinal
beam bars. The test results demonstrate that eccentric beam-
column joints with mechanical anchorage have satisfactory
performance with respect to modern seismic design. This paper
also presents an innovative arrangement of double mechanical
anchorages for longitudinal beam bars within the joints. The
double anchorage design improved the cyclic response of beam-
column joints significantly.

EXPERIMENTAL PROGRAM
This paper presents results from six exterior beam-column
joint specimens with different anchorage methods. The primary
test variables were the anchorage methods of longitudinal beam
bars and the eccentricity between the beam and column
centerlines. Figure 3 shows the designation and reinforcing
details for the test specimens. The first pair of joint specimens
(W0 and W150), which was selected from five specimens
tested by Lee and Ko,16 used standard 90-degree hooks for the
Fig. 3—Specimen designation and reinforcing details. beam bar anchorage. The next two pairs of joint specimens

330 ACI Structural Journal/May-June 2009


(W0-M1 and W150-M1, W0-M2 and W150-M2) used screw- where the summation term is applied on each side of the joint
deformed bars with mechanical anchorage devices in place where the column edge extends beyond the beam edge, and
of hooked bars in the joints. As shown in Fig. 4, a screw- the slope m is 0.3 when the eccentricity between beam and
deformed bar is a reinforcing bar with rolled-on ribs that are column centerlines is greater than bc /8; otherwise, m is 0.5.
spaced like screw threads. Therefore, a steel coupler or 3. To control joint deterioration during earthquake loading
anchor head can be screwed onto the bar as a flange nut. and displacement demands, a specified amount of transverse
Resin or nonshrink high-strength mortar is grouted into the reinforcement should be provided within the joint. For a tied
steel coupler or anchor head to avoid a loose condition. column with rectangular hoops and crossties, the total cross-
As shown in Fig. 3, the first character of the specimen sectional area in each direction of transverse reinforcement
designation, W, represents a west beam framing into the joint. within the joint should be at least equal to
The subsequent numerals (0 or 150) denote the eccentricity
between the beam and column centerlines in mm. The north fc ′ ⎛ Ag
faces of the beam and column were flush when the eccentricity - -------- – 1⎞
A sh = 0.3sb c″ ---- (4)
f yt ⎝ A ch ⎠
was 150 mm (5.9 in.); thus, the possibility of side-face blowout
of headed bars was increased. Finally, specimen designation
-M1 or -M2 denotes that each beam bar had a single or double but not less than 0.09sbc′′ fc′/fyt.
mechanical device within the joint, respectively. In general, the 4. The minimum development length of longitudinal beam
test specimens had conventional reinforcing details except for bars with standard hooks anchored in the joint is determined by
the use of mechanical anchorage.
fy db ⎛ fy db ⎞
Connection design parameters - N-mm ⎜ ---------------
l dh, 352 = ------------ - lb-in.⎟ (5)
ACI-352R-0210 recommendations define Type 1 and 5 fc ′ ⎝ 60 f c ′ ⎠
Type 2 connections as essentially nonseismic and seismic
design, respectively. The scope of this paper discusses the while the minimum development length of headed bars is
Type 2 connection for special moment frames. For an exterior 0.75ldh,352.
beam-column connection, ACI 352R-0210 addresses four Critical sections for the development of longitudinal beam
major design parameters, as follows: bars should be taken at the outside edge of the confined core
1. To produce flexural hinging in the beams rather than the for Type 2 connections as defined in ACI 352R-02,10
columns, the flexural strengths of the beams and columns Section 4.5.1. Either bar heads or hooks should be located
framing into a joint should satisfy within 50 mm (2 in.) from the back of the confined core,
where heads or hooks can be anchored within the diagonal
ΣM nc strut. In practice, the beam bars should be extended into the
- ≥ 1.2
M r = ------------ (1) joint as far as possible.
ΣM nb The provisions written in ACI 318-081 for the development of
hooked or headed bars are slightly different from ACI 352R-02.10
where ΣMnb and ΣMnc are the sum of nominal flexural Critical sections for the development of longitudinal beam
strengths of beams and columns, respectively, evaluated at bars could be taken at beam-column faces, and the minimum
the face of the joint. The beam hinging mechanism is much
preferred for building frames resisting earthquake forces.
2. To prevent joint shear failure before beam hinging, the
shear strength Vn computed on a horizontal plane within the
joint shall satisfy

φV n = φγ f c ′b j h c ≥ V u (2)

where φ is the strength reduction factor of 0.85 and γ f c ′


is the nominal joint shear stress of 1.0 f c ′ MPa (12 f c ′ psi) for
corner, interstory beam-column connections. For an exterior
joint without slabs, the design shear force can be estimated
by Vu = 1.25fyAs – Vcol, where the probable overstrength of
1.25fy is typical for Type 2 connections using ASTM A706
or equivalent reinforcement.
The effects of the column’s aspect ratio and joint eccentricity
are considered by limiting or reducing the effective joint
width as defined by

⎧ (b + b ) ⁄ 2
⎪ b c
⎪ mh
b j = the smaller of ⎨ b + Σ ---------c (3)
⎪ b 2
⎪ Fig. 4—Details of mechanical devices for test specimens
⎩ bc (plan view).

ACI Structural Journal/May-June 2009 331


development length for a hooked beam bar anchored in a Two sizes of reinforcement meeting ASTM A706 requirements
joint can be determined following ACI 318-081, Section 21.7.5.1 were used for longitudinal and transverse reinforcement.
Specimens W0 and W150 used traditional deformed bars
⎛ fy db ⎞ with standard 90-degree hooks within the joint, whereas the
fy db
- N-mm ⎜ ---------------
l dh, 318 = ---------------- - lb-in.⎟ (6) other four specimens used screw-deformed bars with
5.4 f c ′ ⎝ 65 f c ′ ⎠ mechanical devices for the anchorage of beam bars. Transverse
reinforcement used consistent properties for all specimens.
Headed bars are not mentioned in Chapter 21 of ACI 318-081 Table 1 shows the material properties measured at the date
for special moment frames, but new provisions for the of testing and the connection design parameters with respect
development of headed deformed bars in tension can be to the recommendations of ACI 352R-02.10 Flexural hinging
found in ACI 318-08,1 Section 12.6. Based on available in the beam was anticipated because the flexural strength
monotonic loading tests,5-7 ACI Committee 318 wrote that ratios Mr were much greater than the specified value of 1.2.
the minimum development length for a headed bar, Thus, the demand of the joint shear force Vu was dominated
measured from the critical section to the bearing face of the by the probable moment capacity of the beam, which had a
head, shall be determined by cross section of 300 x 450 mm (12 x 18 in.) and had four D22
(No. 7) longitudinal bars (steel ratio of 1.29%) at both the top
fy db ⎛ fy db ⎞ and bottom (Fig. 3). The relative head area ratio Abrg/Ab was
- N-mm ⎜ -------------------
l dt, 318 = ---------------- - lb-in.⎟ (7) equal to 5.14 for the D22 (No. 7) longitudinal bars terminated
5.2 f c ′ ⎝ 62.5 f c ′ ⎠ within the joints.
The values of Vu in Table 1 were computed based on
for headed deformed bars satisfying: (a) specified fy of 420 MPa 1.25fy (measured) and an internal lever arm of 0.875d in the
(60 ksi) or less; (b) bar size of 36 mm (No. 11) or smaller; (c) beam. Due to the eccentric beams, the nominal joint shear
normalweight concrete; (d) relative head area ratio Abrg/Ab capacities of eccentric beam-column joints were smaller
of 4 or more; (e) minimum clear cover of 2db for each bar; than those of concentric joints. Therefore, the joint shear
and (f) minimum clear spacing of 4db between bars. demand-to-capacity ratios of eccentric joints were greater
The length ldt,318 is longer (more conservative) than than those of concentric joints. Notably, all joint shear
0.75ldh,352, even though the effect of load reversals is not demand-to-capacity ratios were below 1.0, as listed in Table 1.
addressed in ACI 318-08,1 Section 12.6. In all cases, the The joint capacity should be sufficient for the development
aforementioned development lengths shall not be less of the adjacent beam hinging.
than the larger of 8db or 150 mm (6 in.).
To meet the minimum requirement of transverse reinforcement
in a joint and adjacent column end, D10 (No. 3) hoops with
Specimen design and reinforcing details seismic crossties at a spacing of 100 mm (4 in.) were
This experimental program was designed using a concrete
provided throughout the column (Fig. 3). As shown in Table 1,
compressive strength of 30 MPa (4.35 ksi) and a specified
the amount of provided transverse reinforcement was close
yield strength of 420 MPa (60.9 ksi) for reinforcing steel.
to the requirement given in Eq. (4) along both the N-S or
E-W directions. Thus, the joint is considered to be code-
Table 1—Material properties and connection compliant to sustain earthquake loading and inelastic
design parameters
displacement reversals.
Connection Conventional Mechanical anchorage In this experimental program, both headed and hooked
specimen ID
bars were extended into the joints as far as possible, with a
total embedment length of 330 mm (13 in.), or 14.9db was
Parameters W0 W150 W0-M1 W150-M1 W0-M2 W150-M2
used for all specimens, leaving a 70 mm (2.8 in.) back cover
Concrete strength 29.5 30.7 35.8 30.7 35.8
fc′, MPa (ksi) (4.28) (4.45) (5.19) (4.45) (5.19) behind the outside edge of heads or hooks. For hooked bars
Bar yield strength fy ,
in the test specimens, this embedded length of 14.9db was
455 (66) 473 (68.6) less than the development length of 16.7db determined using
MPa (ksi)
Bar tensile strength Eq. (5) plus cover thickness, but slightly greater than the
fu, MPa (ksi) 682 (99) 667 (96.7) development length of 14.2db determined using Eq. (6). For
Flexural strength the other specimens, the embedded length of a headed bar
3.11 3.11 3.19 3.19 3.19 3.19
ratio Mr* measured from the column face to the bearing face of the
Shear demand- head was equal to 14.5db, which was close to the development
capacity ratio Vu/Vn†
0.77 0.96 0.79 0.91 0.79 0.91 length of 14.7db per ACI 318-081 (Eq. (7)), but greater than
NS-dir confinement the 12.8db length per ACI 352R-02.10
Ash,provided/ 1.09 1.09 1.05 0.90 1.05 0.90 All longitudinal beam bars were closely spaced at a center-
Ash,required‡ to-center spacing of 2.2db, but the outer diameter of the
EW-dir confinement mechanical device was 2.48db. As shown in Fig. 4, staggering
Ash,provided/ 1.14 1.14 1.10 0.94 1.10 0.94 heads were used to prevent the overlapping of anchor heads.
Ash,required‡ Notably, the side cover dimension from the north face to the
*
Mr = (M top bottom
nc + M nc )/Mnb was computed with target column axial load of 0.1Agfc′. edge of extreme beam bars was only 3db for eccentric beam-

Joint shear demand Vu and nominal joint shear capacity Vn were computed using Eq. (2) column joint specimens. The headed bars, however, were not
and (3).

Measured yield strength of transverse reinforcement was 471 MPa (68.3 ksi).
restrained by additional transverse reinforcement for side-face
Note: All parameters are based on measured material properties at testing date. blowout failure.

332 ACI Structural Journal/May-June 2009


Test setup and loading procedure level, the test specimens had similar stiffness and strength
Following an earlier experimental program16 of eccentric because the anticipated beam hinging dominated the load-
beam-column joints, the same testing framework was used displacement response. After reaching maximum load at the
for specimens with mechanical anchorage. Each T-shaped 4% drift level or more, the load-displacement loops showed
one-way joint specimen was rotated 90 degrees to ease test pinching due to the beam bar slip from the joint and joint
setup, as shown in Fig. 5. The column was simply supported shear distress. The response of Specimens W0-M2 and
and anchored on the strong floor with four one-dimensional W150-M2 shows relatively more ductility and less pinching
rollers. This arrangement was used to simulate contraflection due to the contribution of double mechanical devices on each
points of zero moment as the column was subjected to lateral beam bar.
loads, and also to restrain the column for twisting about the As observed by Lee and Ko16 for Specimens W0 and W150,
column axis. Prior to applying lateral force, a manually the damage progression commenced with a beam flexural
controlled axial load of 0.1Agfc′ was applied along the yielding followed by joint cracking, the spalling of the column
column axis during testing. A displacement-controlled actuator concrete cover, crushing of the joint diagonal strut, and eventual
applied a lateral force at the beam centerline using a expansion and distortion of the joint region. It can be observed
predefined procedure consisting of three fully reversed cycles in Fig. 6 that the significant joint damage of Specimens W0 and
at gradually increasing drift ratios (0.25, 0.50, 0.75, 1.0, 1.5, W150 after 5% drift corresponds to significant degradation in
2, 3, 4, 5, 6, 7, and 8%). The predetermined target displacement load capacity from the first to third cycle of the 5% drift ratio.
at beam tip, Δ, was computed by target drift ratio The damage progressions of Specimens W0-M1 and W150-M1,
respectively, were very similar to those of W0 and W150,
Δ - except for the pushout of concrete on the east face of the
θ = ------------------------ (8) column. The failure mechanisms of Specimens W0-M1 and
L b + 0.5h c
W150-M1 were a complete loss of bond along the headed bars
into the joint and subsequent crushing of the joint diagonal
Note that the positive drift ratio corresponds to displacing the struts during the 5% drift cycles. As shown in Fig. 6, the load
beam tip to the right in Fig. 5, causing a positive bending capacity of Specimens W0-M1 and W150-M1 degraded from
moment at the column face. the first to the third cycle of the 5% drift ratio and subsequent
Using the testing method recommended by ACI 374.1-05,15 loops became very pinched. Notably, Specimens W0-M1 and
the initial drift ratio should be within an elastic range. Subsequent W150-M1 had smaller strength degradation in the post-peak
drift ratios should be between 1.25 and 1.50 times the previous range than Specimens W0 and W150, respectively. The use of
drift ratio, and testing should continue to a 3.5% drift ratio. The a single mechanical device in place of the 90-degree hook in the
loading procedure in this experimental program is relatively joint resulted in at least an equivalent or somewhat better
severe with respect to ACI 374.1-05.15 The presented tests performance under large displacement reversals.
continued up to an 8% drift ratio for observations of failure The use of double mechanical devices changed the failure
modes. The performance of test specimens should be evaluated mechanism and further improved the cyclic response of test
prior to 4% drift, however, because a drift ratio of 4 or 5% is too specimens. As shown in Fig. 6, the pushout of concrete on
large for well-designed moment frames. Figure 5 also shows a the east face of the column did not appear at the end of
typical instrumentation installed on a test specimen. One pair of testing for Specimens W0-M2 and W150-M2. It is evident
displacement transducers was used to measure the shear that double mechanical devices are very effective for beam
deformation on the north face of the joint, while another two bars subjected to cyclic loading. The most deeply embedded
pairs of displacement transducers were used to measure the mechanical device is effective for developing bars in
beam plastic hinge (PH) rotation and rotation from beam bar tension, but might not be as effective in compression because
slip and yield penetration. Furthermore, electrical resistance the concrete cover behind the head is weak. The intermediate
strain gauges attached to reinforcing bars at key positions and mechanical device was found to effectively transfer the
were used to monitor the strain histories of reinforcing bars. compression of the beam bar into the joint diagonal strut.
Thus, the pushout of concrete on the east face of the column
EVALUATION OF CYCLIC LOADING RESPONSE
Cyclic loading response and damage progression of
Specimens W0 and W150 has been presented by Lee and
Ko.16 The performance of four specimens with mechanical
anchorage are evaluated with respect to that of Specimens
W0 or W150, which are referred to as the benchmark
specimens in this paper.

Overall load-displacement response


All six specimens developed the anticipated beam
hinging and behaved in a ductile manner consistent with the
seismic design objectives. Figure 6 shows the measured
lateral load-displacement loops and final damage patterns
for test specimens. The lateral load P was normalized to the
nominal lateral resistance Pn determined using measured
material properties and a strain compatibility analysis for
the flexural strength of the beam section at the column face.
As shown in Fig. 6, the lateral displacement was also
converted to drift ratios by Eq. (8). Prior to the 4% drift Fig. 5—Test setup and loading procedure.

ACI Structural Journal/May-June 2009 333


can be prevented. As a result, Specimen W0-M2 could fully maximum joint shear forces Vj,max were computed based on
develop a beam PH with minimal joint damage, whereas Pmax by assuming an internal lever arm of 0.875d in the
Specimen W150-M2 had more visible joint damage on the beam section. When dividing Vj,max by the shear area with
east and north face of the column due to the joint eccentricity. different definitions of effective joint width, as listed in
Nevertheless, the resistance of both specimens was maintained Table 2, the imposed joint shear stresses were all kept below
up to 7 or 8% drift, which is more than enough for seismic the limit of 1.0 f c ′ MPa (12 f c ′ psi) set by ACI 352R-0210
design of buildings. for joints that are not confined on opposite faces.
It can be expected that the greater the imposed joint shear
Experimental joint shear stresses stress obtained by using effective joint area, the poorer the
Because all test specimens underwent beam hinging, the seismic performance of such a joint. Data in Fig. 6 show that
measured maximum resistance Pmax exceeded their nominal the cyclic loading responses of eccentric specimens were
resistances Pn, as shown in Fig. 6 and Table 2. The experimental very similar to those of concentric specimens within 4 or 5%

Fig. 6—Cyclic loading response and final damage patterns.

334 ACI Structural Journal/May-June 2009


drift, but the final damage on the north (flush) face of eccentric Performance evaluation at limiting drift ratio
specimens was obviously more than those of the concentric Table 3 summarizes the test results for comparison with
specimens. Minor damage for concentric specimens was the acceptance criteria in ACI 374.1-05.15 For acceptance,
attributed to that the effective joint width participating in test results of the third complete cycle to a limiting drift ratio
shear resistance was less than the column width bc. The not less than 3.5% should satisfy the following criteria: 1) the
width of severely damaged concrete in the concentric joints strength degradation shall not be greater than 1/4 of the
was approximately (bb + bc)/2, which is the basic definition maximum load resistance in the same loading direction;
of bj used by ACI 352R-0210 for concentric connections. 2) the relative energy dissipation ratio shall not be less
Accordingly, the experimental shear stresses determined than 1/8; and 3) the secant stiffness between drift ratios of –
using bj = (bb + bc)/2 for concentric specimens can be taken 1/10 and +1/10 of the limiting drift ratio shall not be less than
as baselines, and those for eccentric specimens should be 0.05 times the initial stiffness obtained from the first cycle.
somewhat higher. Table 2, however, shows that the basic In this experimental program, a conservative limiting drift
definition of bj = (bb + bc)/2 was not conservative for eccentric ratio of 4% is considered due to the lack of 3.5% drift cycles.
specimens, and the definition of b j = b b + 0.3h c/2 was Therefore, the characteristics of the third cycle of the 4% drift
conservative. According to Eq. (3), the effective joint width ratio for test specimens are listed in Table 3. Using the
for eccentric specimens should be determined by the definition of ACI 374.1-05 15 criteria, all specimens had satisfactory
bj = bb + Σmhc/2, where the slope m is reduced from 0.5 to performance, except Specimen W150, which had just
0.3 because the eccentricity is greater than bc/8. Neglecting acceptable performance. Relative to all the criteria, it can be
this restriction and assuming bj = bb + 0.5hc/2, the difference observed in Table 3 that the performance of an eccentric
of experimental joint shear stresses between concentric and beam-column joint with mechanical anchorages was superior
eccentric specimens becomes more rational (Table 2). to that of an eccentric beam-column joint with standard 90-degree
Previous researchers12-14 recommended that the simple hooks. Comparing the test results with the ACI 374.1-0515 criteria
definition of bj = (bb + bc)/2 can be used for the design of suggests that the use of mechanical devices in place of
eccentric beam-column connections, while it was also not hooks can improve the seismic behavior of an eccentric
conservative for available experimental results of eccentric beam-column connection.
connections without slabs. The simple definition of b j = Figure 7 compares the average dissipated energy of every
(bb + b c)/2, however, may be unrealistic for a narrow three loops at each target drift level. By focusing on the
beam framing into a wide column with large eccentricity, energy dissipation capacities prior to the limiting drift ratio
as were the eccentric specimens discussed in this paper. of 4%, the beam-column joints with mechanical anchorages

Table 2—Evaluation of imposed shear stresses on test joints


Connection Conventional Mechanical anchorage
specimen ID
Results W0 W150 W0-M1 W150-M1 W0-M2 W150-M2
Nominal resistance Pn, kN (kips) 147 (33.0) 147 (33.0) 151 (33.9) 152 (34.2) 151 (33.9) 152 (34.2)
Maximum resistance Pmax, kN (kips) 163 (36.6) 155 (34.8) 158 (35.6) 160 (35.9) 160 (35.6) 166 (35.9)
Over-strength factor Pmax/Pn 1.11 1.05 1.05 1.05 1.06 1.09
Maximum joint shear Vj,max,* kN (kips) 778 (175) 739 (166) 756 (170) 763 (172) 765 (172) 792 (178)

b j = ⎛ ---------------
b b + b c⎞ 0.80 0.76 0.76 0.71 0.77 0.74
-
⎝ 2 ⎠
V j, max †
---------------------
-
γ f c ′b j h c b j = ( b b + 0.5h c ⁄ 2 ) — 0.85 — 0.80 — 0.83
b j = ( b b + 0.3h c ⁄ 2 ) — 0.94 — 0.89 — 0.92
( L + 0.5h )
Vj,max = P max ⎛ -----b – ----------------------------
c ⎞
* L b
- where jd = 0.875d is assumed.
⎝ jd Lc ⎠
†γ f c ′ is nominal joint shear stress of 1.0 f c ′ MPa ( 12 f c ′ psi) for test joints.

Table 3—Test results for comparison with acceptance criteria in ACI 374.1-05
Connection Conventional Mechanical anchorage
specimen ID
Parameters W0 W150 W0-M1 W150-M1 W0-M2 W150-M2
Initial stiffness for first cycle of 0.25% drift, Positive 9.16 (52.3) 9.01 (51.4) 9.19 (52.5) 9.03 (51.5) 9.47 (54.1) 9.71 (55.4)
kN/mm (kips/in.) Negative 8.97 (51.2) 8.18 (46.7) 8.94 (51.0) 9.53 (54.4) 8.97 (51.2) 8.60 (49.1)
Percentage degradation in load capacity from Positive 4% 11% 3% 4% 2% 1%
first to third cycle
of 4% drift Negative 5% 20% 5% 5% 3% 2%

Relative energy dissipation ratio* 0.31 0.22 0.33 0.29 0.32 0.35

Ratio of secant stiffness† around zero drift to Positive 0.17 0.08 0.16 0.15 0.20 0.21
initial stiffness Negative 0.16 0.07 0.14 0.12 0.20 0.21
*
Relative energy dissipation ratio is energy-dissipated in third complete cycle of 4% drift ratio divided by idealized elastoplastic energy. Elastoplastic energy was calculated for
positive and negative loading direction using initial stiffness in first cycle of 0.25% drift ratio and peak load resistances in third complete cycle of 4% drift ratio.

Secant stiffness around zero drift was obtained for positive and negative loading direction between –0.4% and +0.4% drift ratios in third compete cycle of 4% drift ratio.

ACI Structural Journal/May-June 2009 335


performed as good as, or even better than, those joints with of the total drift angle, whereas that of beam PH rotation was
90-degree hooks. Figure 7 implies that the use of a single approximately 30% of the total drift angle. Beyond this drift
mechanical device in place of the 90-degree hook is good level for Specimens W150 and W150-M1, the percent of
enough for a drift ratio of 4%. The use of double mechanical beam bar slip and yield penetration increased rapidly and
devices further enhanced the energy dissipation capacities that of beam PH rotation decreased simultaneously. These
up to an unrealistic drift level of 7%. Nevertheless, this readings are consistent with the damage observations on
innovative detailing of double mechanical devices can be a both Specimens W150 and W150-M1. As the joint degraded
possible option to improve the cyclic loading behavior of due to the crushing of joint concrete initiated at 5% drift, the
headed bars. Further tests for improving bond performance beam bars lost bond transfers for tension and compression. This
of beam bars passing through interior joints with double resulted in large slip deformations within the joint and extensive
mechanical devices are under investigation by Lee et al.17 pushout cracking behind the joint. Consequently, a greater
Fabrication of double mechanical devices is easy for screw- portion of the rotation was concentrated between the column
deformed bars. Doubling the costs of mechanical devices face and beam end. The joint shear deformations shown in Fig. 9
may be the only drawback. were measured on the north face (eccentric side) of the joint.
Beyond 5% drift for Specimen W150 and 6% for Specimens
Drift contributions W150-M1 and W150-M2, the expansion and spalling of joint
The external instrumentation of this experimental program concrete made the readings inaccurate.
measured the major drift components, illustrated in Fig. 8. For Specimen W150-M2 at 5 or 6% drift, the contribution of
The three drift components were: 1) rotation from beam bar beam bar slip and yield penetration was below 50%, and that of
slip and yield penetration at the beam end; 2) rotation in the beam PH rotation remained at 30% of the total drift angle. It is
anticipated beam PH zone within an effective depth of the evident that the joint maintained its integrity to support the
beam; and 3) shear deformation measured on the north face complete formation of an adjacent beam PH up to 6% drift. It
of the joint. Other drift components such as elastic flexural seems that the intermediate mechanical device was effective not
and shear deformation in the beam and columns were minor only for transferring compression force of the beam bar, but also
and not relevant in this experimental program. for reducing the slip and yield penetration of the beam bar in
As shown in Fig. 9, rotation from beam bar slip and yield tension. The beam bar slip, yield penetration, and PH components
penetration contributed most to the total drift angle for three of Specimens W0, W0-M1, and W0-M2 were, respectively,
eccentric connections. At 4% drift, the contribution of beam similar to those shown in Fig. 9. The shear deformation
bar slip and yield penetration was approximately 40 to 45% component measured on the joint face of Specimens W0,
W0-M1, and W0-M2, however, was minimal due to the
distance between the beam and column faces.

EVALUATION OF ANCHORAGE CAPACITY


Anchorage behavior
Strains along one bottom beam bar adjacent to the north
face (eccentric side) were measured and converted to tensile
stress at peak drift ratios by assuming an elastoplastic stress-
strain relationship. Figure 10 compares the bar tensile
stresses fs1 measured at the column face and fs2 measured at

Fig. 8—Major drift components to total drift angle for test


specimens.

Fig. 7—Average dissipated energy of three cycles at each Fig. 9—Contributions to total drift after beam yielding for
drift level. eccentric specimens.

336 ACI Structural Journal/May-June 2009


0.5hc along the beam bar into the column. The measured gauge was damaged in the first cycle of 5% drift. It is evident
strain readings show that all beam bars were adequately that the use of an intermediate mechanical device enhanced
anchored to reach the yield strength at a drift ratio of 1.5% or the bond condition under cyclic loading and delayed the
more. Before the bar yielded at the column face, the strain yield penetration along the beam bars into the joint. This
readings showed that 50% of the bar tensile stress was transferred enhancement resulted in Specimens W0-M2 and W150-M2,
by the hook or head bearing component plus some bond of sustaining the joint shear forces up to the 8% drift ratio with
the straight portion in the back 0.5hc, while the remainder limited joint damage (Fig. 6).
was transferred by the bond component of the straight On the other hand, the side cover of the north face beam
portion in the front 0.5hc. After the bar yielded at the column bars was only 3db for Specimens W150-M1 and W150-M2.
face, the bond component in the front 0.5hc deteriorated and The anticipated side-face blowout failure, however, was not
vanished at the 4% drift level except for Specimens W0-M2 observed during testing. The provided joint hoops and crossties
and W150-M2. This shows that Specimens W0 and W150 as were apparently effective in restraining the headed bars.
well as W0-M1 and W150-M1 underwent significant bond Section 4.5.3.3 of ACI 352R-0210 refers to prior knee joints
deterioration along the straight portion of the beam bar tested by Wallace et al.9 and conservatively recommends
because of the adjacent beam PH. Beyond the 4% drift level, providing some U-shaped reinforcement for restraining
the bond along the straight portion of the beam bar was headed bars adjacent to a free face. Notably, there is a top
almost lost and the entire bar tensile force was transferred by layer of beam bars adjacent to a free face in a knee joint. For
end anchorage. eccentric beam-column joints with a continuous column,
The strain histories of Specimens W150-M1 and W150-M2 only one of the top or bottom beam bars is adjacent to the
are compared in Fig. 11. The strain gauge was attached at 0.5hc eccentric joint face. The side-face blowout failure of one of
along the beam bar into the column. The strain history of the beam the heads does not result in the loss of anchorage of all
bar with a single mechanical device in Specimen W150-M1 was headed bars. Therefore, the additional restraining reinforcement
very similar to that of the hooked bar in Specimen W150, could be unnecessary.
as reported by Lee and Ko. 16 The strain readings for
Specimen W150-M1 remained elastic in the 3% drift cycles Comparison of test results with model combining
but went into a yielding plateau in the first cycle of 4% drift. bond and head bearing
Due to yield penetration and bond deterioration, the shear- Thompson et al.8 reviewed numerous test results of
resisting mechanisms changed and the joint shear capacity headed bars and proposed a refined model for determining
decreased as the drift ratio increased. The degradation of the the anchorage capacity of headed bars by a combination of
joint shear capacity can be delayed if good bond is maintained head bearing and bond. The following equations based on
along the bonded length of beam bars. As shown in Fig. 11, the research4-8 at the University of Texas at Austin can be
the strain readings for the beam bar with double mechanical taken to represent the state of the art of headed bar
devices in Specimen W150-M2 remained elastic until the anchorage. First, the anchorage capacity provided by head
bearing can be estimated by

f s, head c A brg f c ′
-------------- = n 5% 2 ⎛ ----b-⎞ ---------
- Ψ ----- (9)
fy ⎝ d b⎠ A b f y

Fig. 10—Bar tensile stresses measured at beam-column Fig. 11—Bar strain histories measured at half column depth into
interface and half column depth into test joints. joint: (a) Specimen W150-M1; and (b) Specimen W150-M2.

ACI Structural Journal/May-June 2009 337


where n5% is equal to 0.7 for the 5% fractile value for design tests on the use of staggered headed bars and multiple
purposes. Without the n5% term, Eq. (9) estimates the mean layers of headed bars are recommended to refine the model
capacity of head bearing. for their development.
For the mechanical devices used in Fig. 4, the relative head
area ratio Abrg/Ab is equal to 5.14 and the minimum cover CONCLUSIONS
dimension cb is equal to 1/2 the center-to-center spacing of Based on the results of this experimental program, the
bars being developed. The radial disturbance factor Ψ is a following conclusions are drawn:
modification factor for stress disturbance caused by the 1. The use of a single mechanical anchorage device in place
proximity of a bar to a corner. Thompson et al.8 recommended of the 90-degree hook terminating in the joint resulted in an
that the Ψ factor equals 0.6 + 0.4(c2/cb) but is not greater equivalent or better performance under large inelastic
than 2.0, where c2 is the minimum cover dimension displacement reversals. Comparing the test results with the
measured in the direction orthogonal to cb. For connections acceptance criteria given in ACI 374.1-0515 suggested that the
with a continuous column, as shown in Fig. 3, the c2 value is use of mechanical anchorages in place of hooked anchorages
much greater than cb. Thus, the Ψ factor can be taken as 2.0. is appropriate, or even better;
Substituting forgoing parameters except the n5% term 2. Attaching double mechanical anchorage devices on
into Eq. (9), the predicted head bearing capacity of a each beam bar within the joint can enhance the anchorage
headed bar was 0.65fy and 0.76fy for Specimens W0-M1 and further improve the cyclic behavior of beam-column
and W150-M1, respectively. connections. The experimental data showed that double
Secondly, Thompson et al.8 proposed that the bar stress mechanical devices could prevent pushout on the back of the
contributed from bond be calculated using the ratio of available joint and reduce the yield penetration and bond deterioration
bonded length la to development length ld for straight along the beam bar into the joint. Therefore, the degradation
deformed bars in tension, assuming that the distribution of of potential joint shear capacity could be delayed beyond the
bar stress is linear over ld. Thompson et al.8 observed a limiting drift ratio of 4%;
certain degree of bond deterioration when the head bearing 3. For the presented eccentric beam-column joint specimens,
component achieved peak capacity in their tests of headed the evaluation of the experimental joint shear stresses
bars. Thus, a reduction factor χ for considering the reduced showed that the definition of bj = (bb + bc)/2 for computing
bond was also recommended. the shear area of the joint were not conservative, whereas the
ACI 352R-0210 effective joint width was conservative and
could be further widened;
f s, bond l A brg ⁄ A b⎞
--------------- = χ ---a- where χ = 1 – 0.7 ⎛ -------------------
- ≥ 0.3 (10) 4. The side-face blowout failure was not observed during
fy ld ⎝ 5 ⎠ tests of eccentric beam-column joints with mechanical
anchorage, even though there was only 3db side cover for the
The development length ld = 46db was determined using extreme headed bar without any additional restraining
ACI 318-08,1 Section 12.1 for the bars used in the test stirrups; and
specimens. The additional bonded length for the headed bars 5. The available head bearing model derived from monotonic
in the back 0.5hc is equal to 74 mm (2.9 in.) or 3.3db (Fig. 4). loading tests of headed bars underestimates the anchorage
Substituting ld = 46db and la = 3.3db into Eq. (10), the bar capacity of closely-spaced headed bars used in this cyclic
stress contributed from this bonded length is only 0.02fy. loading test. It is concluded that the minimum clear spacing
Finally, the summation of the head bearing capacity and of 4db between headed bars could be further reduced for
bond capacity from the bonded length in the back 0.5hc longitudinal beam bars terminated within a continuous
ranged between 0.67fy and 0.78fy for Specimens W0-M1 and column. Due to a limited number of test results, further
W150-M1, respectively, but the measured stress fs2 achieved investigation of single or multiple layers of closely-spaced
1.0fy in all test specimens (Fig. 10). It is concluded that Eq. (9) headed bars is recommended.
underestimates the head bearing capacity for closely-spaced
headed bars used in this experimental program. This is ACKNOWLEDGMENTS
The authors are grateful to the National Science Council in Taiwan for
attributable to the fact that the smaller cb = 1.1db, as half of funding this project (No. NSC 94-2211-E-224 -014). The Fu-Sheng Co. Ltd.
the center-to-center spacing between bars shown in Fig. 4, is in Taiwan is also acknowledged for donating screw-deformed bars and
a conservative assumption recommended by Thompson et al.8 mechanical anchorage devices.
due to no available test data for anchorage capacity of
multiple headed bars. NOTATION
In fact, the lower limit of cb used in previous tests5-7 on Ab = nominal bar area, mm2 (in.2)
headed bars to derive the head bearing model was 2.5db. This Abrg = net bearing area of headed bar, gross head area minus bar area,
mm2 (in.2)
lower limit is also incorporated in ACI 318-08,1 Section 12.6.1 Ach = cross-sectional area of column core, measured to outside edges
as a restriction for the use of the development length equation: of hoops, mm2 (in.2)
(a) minimum clear cover for a headed bar should not be less Ag = gross area of column section, mm2 (in.2)
than 2db; and (b) clear spacing between headed bars should As = area of longitudinal tension reinforcement in beam section,
mm2 (in.2)
not be less than 4db. The test specimens shown in Fig. 4 did
Ash = total cross-sectional area of transverse reinforcement (including
not meet the latter restriction but did demonstrate adequate crossties) within spacing s and perpendicular to column core
anchorage capacities by the staggering heads. The heads of dimension bc′′, mm2 (in.2)
longitudinal beam bars were anchored within the column bb = beam width, mm (in.)
core, which was confined by lateral reinforcement and the bc = column width transverse to direction of shear, mm (in.)
bc′′ = column core dimension, measured to outside edges of hoops,
column axial load. Both helped the anchorage of headed bars mm (in.)
in exterior beam-column joints. These parameters, however, bj = effective joint width transverse to direction of joint shear,
have not been considered in available models or codes. More mm (in.)

338 ACI Structural Journal/May-June 2009


c2 = minimum cover dimension, measured in direction orthogonal to 3. Wright, J. L., and McCabe, S. L., “The Development Length and
cb, mm (in.) Anchorage Behavior of Headed Reinforcing Bars,” SM Report No. 44,
cb = relative concrete cover dimension, smaller of: (a) distance from Structural Engineering and Materials, University of Kansas, Center for
bar center to nearest free surface; and (b) one-half of center-to- Research, Lawrence, KS, Sept. 1997, 147 pp.
center spacing between bars, mm (in.) 4. DeVries, R. A.; Jirsa, J. O.; and Bashandy, T., “Anchorage Capacity in
d = effective depth of beam section, mm (in.) Concrete of Headed Reinforcement with Shallow Embedments,” ACI Structural
db = nominal bar diameter, mm (in.) Journal, V. 96, No. 5, Sept.-Oct. 1999, pp. 522-530.
fc′ = concrete compressive strength, MPa (psi)
5. Thompson, M. K.; Ziehl, M. J.; Jirsa, J. O.; and Breen, J. E., “CCT Nodes
fs1 = measured bar tensile stress at beam-column interface, MPa (psi)
Anchored by Headed Bars—Part 1: Behavior of Nodes,” ACI Structural
fs2 = measured bar tensile stress at 0.5hc along bar into joint, MPa (psi)
Journal, V. 102, No. 6, Nov.-Dec. 2005, pp. 808-815.
fs,bond = bar stress provided by bond, MPa (psi)
fs,head = bar stress provided by head bearing, MPa (psi) 6. Thompson, M. K.; Jirsa, J. O.; and Breen, J. E., “CCT Nodes Anchored by
fu = ultimate strength of reinforcement, MPa (psi) Headed Bars—Part 2: Capacity of Nodes,” ACI Structural Journal, V. 103,
fy = yield strength of longitudinal reinforcement, MPa (psi) No. 1, Jan.-Feb. 2006, pp. 65-73.
fyt = yield strength of transverse reinforcement, MPa (psi) 7. Thompson, M. K.; Ledesma, A.; Jirsa, J. O.; and Breen, J. E., “Lap Splices
hc = column depth parallel to direction of joint shear, mm (in.) Anchored by Headed Bars,” ACI Structural Journal, V. 103, No. 2, Mar.-Apr.
Lb = vertical distance from column face to actuator centerline, 1950 2006, pp. 271-279.
mm (76.8 in.) 8. Thompson, M. K.; Jirsa, J. O.; and Breen, J. E., “Behavior and Capacity of
Lc = horizontal distance between roller supports at column ends, Headed Reinforcement,” ACI Structural Journal, V. 103, No. 4, July-Aug. 2006,
2700 mm (106.3 in.) pp. 522-530.
la = additional anchorage length, mm (in.)
9. Wallace, J. W.; McConnell, S. W.; Gupta, P.; and Cote, P. A., “Use of
ld = development length for straight deformed bar in tension, mm (in.)
Headed Reinforcement in Beam-Column Joints Subjected to Earthquake
ldh = minimum development length for hooked bar, mm (in.)
Loads,” ACI Structural Journal, V. 95, No. 5, Sept.-Oct. 1998, pp. 590-606.
ldt = minimum development length for headed bar, mm (in.)
Mnb = nominal flexural strength of beam framing into joint, kN-m (ft-kips) 10. Joint ACI-ASCE Committee 352, “Recommendations for Design of
Mnc = nominal flexural strength of column framing into joint, kN-m Beam-Column Connections in Monolithic Reinforced Concrete Structures (ACI
(ft-kips) 352R-02),” American Concrete Institute, Farmington Hills, MI, 2002, 37 pp.
Mr = column-to-beam flexural strength ratio 11. Chun, S. C.; Lee, S. H.; Kang, T. H.-K.; Oh, B.; and Wallace, J. W.,
m = slope to define effective width of joint “Mechanical Anchorage in Exterior Beam-Column Joints Subjected to Cyclic
n5% = 5% fractile coefficient Loading,” ACI Structural Journal, V. 104, No. 1, Jan.-Feb. 2007, pp. 102-112.
Pmax = maximum lateral resistance of test specimen, kN (kips) 12. LaFave, J. M.; Bonacci, J. F.; Burak, B.; and Shin M., “Eccentric
Pn = Mnb /Lb, nominal lateral resistance of test specimen, kN (kips) Beam-Column Connections,” Concrete International, V. 27, No. 9,
Vcol = column shear calculated based on probable beam moment at Sept. 2005, pp. 58-62.
column face, kN (kips) 13. Shin, M., and LaFave, J. M., “Seismic Performance of Reinforced
Vj,max = experimental maximum joint shear force, calculated based on
Concrete Eccentric Beam-Column Connections with Floor Slabs,” ACI
Pmax, kN (kips)
Structural Journal, V. 101, No. 3, May-June 2004, pp. 403-412.
Vn = nominal shear strength of joint, kN (kips)
Vu = design shear force acting on horizontal plane within joint, kN (kips) 14. Canbolat, B. B., and Wight, J. K., “Experimental Investigation on Seismic
χ = bond reduction factor for headed deformed bars Behavior of Eccentric Reinforced Concrete Beam-Column-Slab Connections,”
Δ = beam tip displacement, mm (in.) ACI Structural Journal, V. 105, No. 2, Mar.-Apr. 2008, pp. 154-162.
θ = target drift ratio, or angular rotation of beam chord with respect 15. ACI Committee 374, “Acceptance Criteria for Moment Frames Based on
to column chord Structural Testing and Commentary (ACI 374.1-05),” American
Ψ = radial disturbance factor, 0.6 + 0.4(c2/cb) ≤ 2.0 Concrete Institute, Farmington Hills, MI, 2005, 9 pp.
16. Lee, H. J., and Ko, J. W., “Eccentric Reinforced Concrete Beam-Column
REFERENCES Connections Subjected to Cyclic Loading in Principal Directions,” ACI
1. ACI Committee 318, “Building Code Requirements for Structural Structural Journal, V. 104, No. 4, July-Aug. 2007, pp. 459-467.
Concrete (ACI 318-08) and Commentary,” American Concrete Institute, 17. Lee, H. J.; Kang, J. Y.; and Lin, Y. J., “Improving Seismic Behavior of RC
Farmington Hills, MI, 2008, 465 pp. Interior Beam-Column Connections with Headed Reinforcement,” Proceedings
2. Ghali, A., and Youakim, S. A., “Headed Studs in Concrete: State of the of the 9th Korea-Japan-Taiwan Joint Seminar on Earthquake Engineering for
Art,” ACI Structural Journal, V. 102, No. 5, Sept.-Oct. 2005, pp. 657-667. Building Structures (SEEBUS 2007), Hsinchu, Taiwan, 2007, pp. 103-112.

ACI Structural Journal/May-June 2009 339

Potrebbero piacerti anche