What is SOTF Protection? Topics

Power System
Power System Protection
Electrical Machines
SOTF Protection stands for Switch On to Fault. This DC Machine
protection is provided for high speed clearance of detected Measurement and
fault immediately after Manual Closure of Circuit Breaker. Let Instrumentation
us suppose that a fault is existing and we gave a closing AC Circuit
command to Breaker, then in that case SOTF protection will Digital Electronics
immediately trip the Breaker. Electrical Drives
Power Electronics
EM Theory
Pegasus II Semi Power Standing
Wheelchair

Wheelchair88 Learn more


Latest Topics

Construction and Types of


Synchronous Machine
Short Circuit Ratio-Definition,
Calculation and Significance
Zero Power Factor
Characteristics and Potier
Triangle
Purpose of Compensating
SOTF Protection is helpful in the sense that while taking
Winding in DC Machine
maintenance on a Line, it may happen so that Earth Switch of
Construction of DC Motor
a particular Circuit Breaker is close. In that case if we give
Thevenin’s Theorem and Its
closing command to the Circuit Breaker, it will immediately
Application
trip on SOTF Protection. But it is normal to strike in your smart
Meaning of 1 Unit Electricity –
brain that how can we close a Breaker when a fault is already
Power Consumption
existing? Thing is that you can close the Breaker by
Calculation
bypassing all the required logics, so in that case SOTF will
Difference between
come into picture. Suppose while maintenance Earthing Rod
Instantaneous and Definite
was used for discharging a particular section but after
Time Overcurrent Relay
competition of maintenance the Earth Rod is still connected
Torque Equation of DC Motor
to that section. In such case there is nothing or no logic to
AC Generator – Definition,
prevent closing of Breaker and as soon as one closes the
Construction and Working
Circuit Breaker, it will trip on SOTF.

SOTF Protection gets enabled whenever all the three poles of


a Circuit Breaker is open for more than a settable time say
110s (This time can be changed and configured as per the
design.) Subscribe to our mailing list
and get interesting stuff

SOTF is enabled in two cases. They are mentioned below.


and updates to your email
Case1: If no Closing command to the Breaker is Present. inbox.

When all the three poles of Circuit Breaker is open for more
than a particular time say 110 s, as soon as we give a closing Your Email Please
command to the Circuit Breaker, the SOTF is enabled for 500
ms and then gets reset.
I consent to my
submitted data being
Case2: When an external closing command is present.
collected via this form*
Here external closing means closing the Circuit Breaker
either manually or remotely. The SOTF logic is activated
SUBSCRIBE NOW
immediately. As soon as all the poles are closed SOTF is
enable for 500 ms and then is reset.
we respect your privacy and
take protecting it seriously

During this SOTF time frame of 500 ms, individual distance


protection can be enabled or disabled. When a particular
distance zone say Zone-2 is enabled, Zone-2 will actuate
immediately without waiting for Zone-2 time delay if there
exists any fault in this zone.

How SOTF Relay Senses a Fault?

Basically there are two elements in relay providing SOTF


feature. They are Voltage Level Detector and Current Level
Detector. The purpose of Voltage Level Detector is to ensure
Dead Pole situation and Current Level Detector ensures that
a fault occurred i.e. Current Level Detector is used for
detection of fault. Therefore SOTF Relay element must have
two settings, one for Voltage Level Detector and another for
Current Level Detector. Typical setting for both the elements
are as follows:

Vph < 75% VN


 Iph > 5% IN

Here VNand IN are Nominal Voltage and Nominal Current


respectively. Thus if the phase voltages are normal and if
phase current increases from the setting then SOFT will
sense it a fault and will issue three phase trip command
provided all other conditions as mentioned in case1 and
case2 for SOTF are met.

 September 21, 2016  admin  Power System Protection  3 Comments

 SOTF Protection,  Transmission Line

«Broken Conductor Protection

Sag in Overhead Transmission Line and Its Calculation»


3 Thoughts On “What Is SOTF
Protection?”

— Priyanka

says:
March 2, 2018 at 9:19 pm
Is it measure the impedance variation (Vph/Iph)?

— siva

says:
June 5, 2018 at 8:53 am

really good answer i did practically as your written thank you so


much ur gaudiness

— admin

says:
June 5, 2018 at 9:23 am

That really sounds great! Thank you very much Siva.

Leave A Reply

Your email address will not be published. Required fields are marked *

 Comment

 Name *

 Email *
 Website

 Notify me when new comments are added.

Post Comment

This site uses Akismet to reduce spam. Learn how your comment data is
processed.

Electrical Concepts © 2018 | Theme: Optimize ↑

About Us | Contact Us | Privacy Policy |

Potrebbero piacerti anche