665/18-19
1
Spec. No. CED/CSR/E.665/18-19
REGISTRATION
1) Bidders are required to enroll on the e-Procurement module of the Central
Public Procurement Portal (URL: https://eprocure.gov.in/eprocure/app) by
clicking on the link “Online bidder Enrollment” on the CPP Portal which
is free of charge.
2) As part of the enrolment process, the bidders will be required to choose a
unique username and assign a password for their accounts.
3) Bidders are advised to register their valid email address and mobile
numbers as part of the registration process. These would be used for any
communication from the CPP Portal.
4) Upon enrolment, the bidders will be required to register their valid Digital
Signature Certificate (Class II or Class III Certificates with signing key
usage) issued by any Certifying Authority recognized by CCA India (e.g.
Sify / nCode / eMudhra etc.), with their profile.
5) Only one valid DSC should be registered by a bidder. Please note that the
bidders are responsible to ensure that they do not lend their DSC’s to
others which may lead to misuse.
6) Bidder then logs in to the site through the secured log-in by entering their
user ID / password and the password of the DSC / e-Token.
2
Spec. No. CED/CSR/E.665/18-19
3) The bidder should make a note of the unique Tender ID assigned to each
tender, in case they want to obtain any clarification / help from the
Helpdesk.
PREPARATION OF BIDS
1) Bidder should take into account any corrigendum published on the tender
document before submitting their bids.
2) Please go through the tender advertisement and the tender document
carefully to understand the documents required to be submitted as part of
the bid. Please note the number of covers in which the bid documents have
to be submitted, the number of documents - including the names and
content of each of the document that need to be submitted. Any deviations
from these may lead to rejection of the bid.
3) Bidder, in advance, should get ready the bid documents to be submitted as
indicated in the tender document / schedule and generally, they can be in
PDF / XLS / RAR / DWF/JPG formats. Bid documents may be scanned with
100 dpi with black and white option which helps in reducing size of the
scanned document.
4) To avoid the time and effort required in uploading the same set of standard
documents which are required to be submitted as a part of every bid, a
provision of uploading such standard documents (e.g. PAN card copy,
annual reports, auditor certificates etc.) has been provided to the bidders.
Bidders can use “My Space” or ‘’Other Important Documents’’ area
available to them to upload such documents. These documents may be
directly submitted from the “My Space” area while submitting a bid, and
need not be uploaded again and again. This will lead to a reduction in the
time required for bid submission process.
SUBMISSION OF BIDS
1) Bidder should log into the site well in advance for bid submission so that
they can upload the bid in time i.e. on or before the bid submission time.
Bidder will be responsible for any delay due to other issues.
2) The bidder has to digitally sign and upload the required bid documents one
by one as indicated in the tender document.
3) Bidder has to select the payment option as “offline” to pay the tender fee /
EMD as applicable and enter details of the instrument.
4) Bidder should prepare the EMD as per the instructions specified in the
tender document. The original should be posted/couriered/given in person
to the concerned official, latest by the last date of bid submission or as
specified in the tender documents. The details of the DD/any other
accepted instrument, physically sent, should tally with the details available
in the scanned copy and the data entered during bid submission time.
Otherwise the uploaded bid will be rejected.
3
Spec. No. CED/CSR/E.665/18-19
5) Bidders are requested to note that they should necessarily submit their
financial bids in the format provided and no other format is acceptable. If
the price bid has been given as a standard BoQ format with the tender
document, then the same is to be downloaded and to be filled by all the
bidders. Bidders are required to download the BoQ file, open it and
complete the white coloured (unprotected) cells with their respective
financial quotes and other details (such as name of the bidder). No other
cells should be changed. Once the details have been completed, the bidder
should save it and submit it online, without changing the filename. If the
BoQ file is found to be modified by the bidder, the bid will be rejected.
6) The server time (which is displayed on the bidders’ dashboard) will be
considered as the standard time for referencing the deadlines for
submission of the bids by the bidders, opening of bids etc. The bidders
should follow this time during bid submission.
7) All the documents being submitted by the bidders would be encrypted
using PKI encryption techniques to ensure the secrecy of the data. The
data entered cannot be viewed by unauthorized persons until the time of
bid opening. The confidentiality of the bids is maintained using the secured
Socket Layer 128 bit encryption technology. Data storage encryption of
sensitive fields is done. Any bid document that is uploaded to the server is
subjected to symmetric encryption using a system generated symmetric
key. Further this key is subjected to asymmetric encryption using
buyers/bid openers public keys. Overall, the uploaded tender documents
become readable only after the tender opening by the authorized bid
openers.
7) The uploaded tender documents become readable only after the tender
opening by the authorized bid openers.
8) Upon the successful and timely submission of bids (ie after Clicking “Freeze
Bid Submission” in the portal), the portal will give a successful bid
submission message & a bid summary will be displayed with the bid no.
and the date & time of submission of the bid with all other relevant details.
9) The bid summary has to be printed and kept as an acknowledgement of
the submission of the bid. This acknowledgement may be used as an entry
pass for any bid opening meetings.
ASSISTANCE TO BIDDERS
1) Any queries relating to the tender document and the terms and conditions
contained therein should be addressed to the Tender Inviting Authority for
a tender or the relevant contact person indicated in the tender.
2) Any queries relating to the process of online bid submission or queries
relating to CPP Portal in general may be directed to the 24x7 CPP Portal
Helpdesk.
****
4
Spec. No. CED/CSR/E.665/18-19
INDEX
SECTION - V : COMMERCIAL
SECTION – VI : TECHNICAL
6
Spec. No. CED/CSR/E.665/18-19
SECTION – I
4) The Tenderers who are having valid Permanent EMD with TNEB/TANGEDCO
for an amount of Rs.10,00,000/- (Rupees Ten lakhs only) and above are
exempted from payment of Earnest Money Deposit and are eligible to
participate in the tender.
The existing PEMD holder for Rs.10,00,000/- are eligible to participate in the
tender only for the value of tenders not exceeding Rs.10 Crores. The existing
PEMD holder for Rs.5,00,000/- are not eligible for participating in the tender
unless they pay the differential amount for the new PEMD slab.
6) Cheques will not be accepted towards EMD and the tenders shall be
rejected if EMD is not paid in the prescribed manner.
7) (i) The following categories of Industries are exempted from payment of EMD:
a) The Small Scale Industrial Units located within the State and Registered with
the Tamil Nadu Small Industries Development Corporation.
b) The Small Scale Industrial Units Registered with the National Small Industries
Corporation.
7
Spec. No. CED/CSR/E.665/18-19
7) (ii) SSI units having provisional registration certificate are not eligible for
exemption.
8) Those tenderers who are exempted from payment of EMD shall upload in lieu
of EMD an undertaking in a non-judicial Stamp paper of value not less than
Rs.80/- (Rupees Eighty only) in the form as per Annexure-I to the effect to
pay as penalty an amount equivalent to EMD in the event of non-fulfillment or
non-observance of any of the conditions stipulated in the contract consequent
to such breach of contract. The State Government, Public Sector
Undertakings who are exempted from payment of EMD/Security Deposit
should also pay as penalty an amount equivalent to the amount fixed as
Security Deposit in the event of non-fulfillment or non-observance of any of
the conditions stipulated in the contract.
10) Small Scale Industries registered with the Tamil Nadu small Industries
Development Corporation or with National Small Industries Corporation or
holding Enterpreneur Memorandum Part-II or acknowledgement for
the Enterpreneur Memorandum Part-II issued by DIC, for small scale
industrial unit for subject materials specifying capacity for which they are
permitted to manufacture and the period of validity of the certificate shall
upload attested Photo copy of Registration Certificate/ Acknowledgement as
proof of eligibility for exemption from payment of EMD.
11) Others viz. Central and other State Government Departments/ Undertakings
and Corporations other than those in Tamil Nadu shall have to pay Earnest
Money Deposit and Security Deposit.
8
Spec. No. CED/CSR/E.665/18-19
12) The tenderers shall upload the audited attested copy of Profit and Loss
account/ Balance Sheet along with the proof for exemption from payment of
EMD in order to ensure the SSI status of the firm based on the investment
held in Plant and Machinery for extending exemption from paying EMD.
In case the investment held by them in Plant and Machinery as per
their financial statement of Accounts exceeds Rs.5 Crores, the General
Manager, District Industries Centre concerned will be requested to verify the
SSI status of the firm. Till receipt of confirmation from General Manager /
District Industries Centre concerned, the exemption from paying EMD for SSI
Units shall not be extended.
************************
9
Spec. No. CED/CSR/E.665/18-19
SECTION – II
BID QUALIFICATION REQUIREMENTS (BQR)
The Bidders shall become eligible to bid on satisfying the following Bid
Qualification Requirements and uploading of the required documentary
evidences.
The Tenderers shall furnish the details of various purchase orders for
(iv) tendered materials or higher size placed on them by S.E.B./ DISCOMs/
Government undertakings and executed during the preceding ten
years as on the date of tender opening along with the tender. Copies
of such orders shall be enclosed along with the tender.
3 nos. of the 11KV indoor Vacuum Circuit Breakers or 33KV indoor Vacuum
circuit Breakers shall be in satisfactory operation for a continuous period of
two years
The bidder should furnish the documentary evidence and the Performance
certificate from the end users in support of the above Bid Qualification
Requirement along with the bid documents.
(v) The Annual turnover of the tenderer shall be more than Rs.33 Lakhs
during any one of the last three years (ie. 2014-15,2015-16,2016-17).
Proof for the same should be enclosed in the tender (i.e) attested copy of
Balance Sheet and Profit & loss statement/ NSIC enlistment certificate
/STCC/Income Tax return filed by the bidder etc., containing turnover
details of the bidder for the respective period.
(vi) The main contractor shall only be considered for satisfying the experience
criteria specified in Bid Qualification Requirement. The experience as a
Sub-Contractor shall not be considered for qualifying the experience
10
Spec. No. CED/CSR/E.665/18-19
criteria specified in the Bid Qualification Requirement and the offer of such
tenderers shall be summarily rejected.
The offers of Tenderers not satisfying above ‘BQR’ will be summarily
rejected.
Note : If the bids are received through consortium, the same will
not be considered and the bids will be rejected. Tenders received
from Agents / Dealers will not be considered.
11
Spec. No. CED/CSR/E.665/18-19
SECTION – III
REJECTION OF TENDERS
1.0 REJECTION OF TENDERS
12
Spec. No. CED/CSR/E.665/18-19
SECTION – IV
INSTRUCTION TO TENDERERS
1.0 Tenders in two part System (a) Technical Bid with commercial terms
but without Price Bid and (b) Price Bid, will be received through e-tender
for and on behalf of TANGEDCO herein after referred as TANGEDCO so as
to reach on or before the due date prescribed. All the tenders shall be
prepared and submitted strictly in accordance with the Instructions set forth
herein.
1.1 This tender will be processed as per the provision in the Tamil Nadu
Transparency in Tender Act 1998 and Tamil Nadu Transparency in Tenders
Rules 2000.
Tamil Nadu Transparency in Tenders Act 1998 and the Tamil Nadu
Transparency in Tender Rules 2000 and subsequent amendments
thereof are applicable to this Tender.
4.1.2. In the event of tender being submitted by other than a firm, it must be
signed by a partner (copy of partnership deed should be enclosed) and in
the event of the absence of any Partner, it shall be signed on his behalf by
a person holding a Power of Attorney authorising him to do so, Certified
copies of which shall be enclosed.
4.2.1. At any time after the commencement of e-Tender and before the closing of
the event, TANGEDCO may make any changes, modifications or
amendments to the tender documents and same will be intimated to the
concerned Vendors through corrigendum which can be downloaded from the
Vendor login .
4.2.2. In case any tenderer asks for a clarification to the tender documents before
48 hours of opening of tenders, the Chief Engineer/Distribution / Chennai
South Region/ TANGEDCO, Electricity Avenue, 5A block, 802 Anna Salai,
Chennai -600 002 will clarify the same.
4.2.3. If any tenderer raises clarifications after the opening of the tender, the
clarified reply issued by the Chief Engineer/ Distribution / Chennai South
Region, TANGEDCO, Chennai- 600 002 on the clarifications will be final and
binding on the Tender.
4.3. All tender offers shall be prepared by typing or printing in the formats
enclosed with this specification.
4.4. All information in the tender offer shall be in ENGLISH only. It shall not
contain interlineations, erasures or overwritings except as necessary to
correct errors made by the tenderer. Such erasures or other changes in the
tender documents shall be attested by the persons signing the tender offer.
14
Spec. No. CED/CSR/E.665/18-19
4.5.2. Offers giving lumpsum price, without giving their breakup as per details
required in the attached Price Schedule-A shall be liable for rejection.
4.6. PRINTED TERMS AND CONDITIONS IN TENDERS:
Supplier's printed terms and conditions will not be considered as forming
part of the tender under any circumstances.
4.10. Tenderers shall bear all costs associated with the participation in the e-
Tender and the purchaser will in no case be responsible or liable for these
costs.
4.11. No offer shall be withdrawn by the Tenderer in the interval between the
deadline for submission and the expiry of the period of validity specified /
extended validity of the tender offer.
The Tenderers are requested to furnish the exact location of their factories
with detailed postal address and pin code, telephone and Fax Nos. etc in their
tenders so as to arrange inspection by the TANGEDCO, if considered necessary.
The tenderers are requested to furnish the GST REGISTRATION
Nos. in their offer.
15
Spec. No. CED/CSR/E.665/18-19
15.30 Hrs. on the date notified at the Office of the Chief Engineer
/ Distribution / Chennai South Region, TANGEDCO, 5A block, 802
Anna Salai, Chennai - 600 002, through https://tntenders.gov.in
6.2. The TANGEDCO will examine the tender offers to determine whether they
are complete, whether any computational errors have been made, whether
required sureties have been furnished, whether the documents have been
properly signed and whether the offers are generally in order.
6.5 Mere submission of any Tender offer connected with these documents and
Specification shall not constitute any agreement. The tenderer shall have no
cause of action or claim, against the TANGEDCO for rejection of his offer,
except as mentioned in Clause-4.19 of Section-IV. The TANGEDCO shall
always be at liberty to reject or accept any offer or offers at its sole
discretion and any such action will not be called into question and the
Tenderer shall have no claim in that regard against the TANGEDCO.
7.2. The tender offers received will be examined to determine whether they are
16
Spec. No. CED/CSR/E.665/18-19
in complete shape, all required Data have been furnished, properly signed
and generally in order and conforms to all the terms and conditions of the
Specification without any deviation.
7.3. For the purpose of evaluation of tender offers, the following factors will be
taken into account for arriving the evaluated price:
The quoted price will be corrected for arithmetical errors.
In case of discrepancy between the price quoted in words and
figures lowest of the two will be considered.
The rate of CGST, SGST, and IGST as applicable both in
percentage and amount shall be indicated in the offer along with
HSN code.
The evaluated price shall be arrived in compliance with the
provisions of GST on the Transaction value i.e. (Ex works price
+ P&F+ Freight and Insurance) + GST. In case of import of
goods would be treated as inter state supplies and would be
subject to IGST in addition to applicable customs duty.
Since GST is enacted wherein all taxes & duties are subsumed,
price evaluation shall be inclusive of applicable GST in all cases,
i.e. even if the bidders are only within the State or bidders are
within the State and outside TN.
7.4 Evaluation for the capacity of material /equipment will be done
separately.
7.5 The rates quoted by the eligible lowest tenderer in the open tender Rate
Contract Scheme shall be compared with the prevailing market rate and
the rates of previous period and if the Tender Accepting Authority is of the
view that the quoted rates are too high, the rates will be negotiated and
the rate will be determined. All eligible bidders who accept the rate shall be
enlisted.
7.6 Evaluation will be done for the whole package.
7.7 The tenderers shall mention the quantity in Questionnaire - A. The tenderers
shall quote the minimum quantity of 10% of tendered quantity. The offer of
the bidders who have quoted for lesser quantity than the minimum quantity
prescribed shall be summarily rejected.
In the event of procurement of more items of similar materials of various
sizes or ratio etc. the cumulative 10% of the aggregate quantity of various
items will be considered for arriving at minimum quantity.
8.0. VALIDITY:
8.1. The tender offer shall be kept valid for acceptance for period of 180 days
from the date of opening of offers. The offers with lower validity period are
liable for rejection.
8.2. Further, the tenderer shall agree to extend the validity of the Bids without
altering the substance and prices of their Bid for further periods, if any,
required by the TANGEDCO.
a) to vary the quantity finally ordered to the extent of 25% indicated in the
Tender document.
b) to split the Tendered Quantity and place orders on one or more than
one firm as per the Tamil Nadu Transparency in Tender Rules 2000
since the tendered material is so vital in nature and the failure in supply
would affect the public interest.
c) to recover losses , if any, sustained by TANGEDCO, from the supplier
who pleads his inability to supply and backs out of his obligation after
award of contract. The security deposit paid shall, be forfeited.
d) to cancel the orders for not keeping up the delivery schedule.
e) to vary the delivery period based on the requirement and contingencies
at the time of placing the Rate contract.
f) to accept the lowest eligible tender.
g) to reject any or all the tenders or cancel without assigning any reasons
therefor.
h) to relax or waive or amend any of the conditions stipulated in the tender
Specification wherever deemed necessary in the best interest of the
TANGEDCO.
9.2. The purchaser reserves the right to request for any additional information
and also reserves the right to reject or accept the proposal of any tenderer,
if in the opinion of the purchaser, the qualification data is incomplete or in
the opinion of the TANGEDCO the bidder is found not qualified to
satisfactorily perform the contract.
10.0. DEVIATIONS:
10.1 The tenderer shall furnish, any deviations in the technical/commercial terms
in schedule-B1/B2 annexed. If no deviations are furnished it will be construed that
the tenderer is accepting the technical specification and commercial terms.
Similarly if any deviations are furnished in the specified form it will be construed
that these are the only deviations and the tenderer is accepting all other terms of
the specification and the offer will be taken for evaluation accordingly.
10.2 The offers of the Tenderers with Deviations in Commercial terms and
Technical Terms of the Tender Document are liable for rejection.
18
Spec. No. CED/CSR/E.665/18-19
SECTION - V
COMMERCIAL
1.0. SCOPE:
1.1. The scope of supply of the material includes for design, manufacture,
inspection, testing, packing, forwarding and delivery of the materials
detailed herein, at our stores/yards anywhere in Chennai Region.
2) PLACING OF ORDERS:
2.0 It is not binding on the Board to accept the lowest or any tender.
TANGEDCO reserves the right to split and place orders for the items with different
tenderers and for revising the quantities at the time of placing the orders. The
TANGEDCO reserves the right to vary the quantity finally ordered to the extent of
25% either way of the requirement indicated in the tender documents.
2.1The award of contract will be issued to the successful tenderer with all
TANGEDCO's terms and conditions, duly indicating the approved unit rates and the
quantity allotted to them.
3.0 PRICE:
3.1The Tenderers are requested to quote FIRM price only.
4.2 The tenderer should quote their rates taking into account the (Input
Tax Credit (ITC) relief available to them on account of GST already paid. A
certificate to this effect may be furnished along with the tender.
19
Spec. No. CED/CSR/E.665/18-19
i. Goods and Services Tax [GST] as a modern law, has been brought
after Article 366(12A) of the Constitution as amended by 101 st
Constitutional Amendment Act, 2016. GST is an indirect tax system,
commonly used by both the Central Government and the State/UT to
final consumption with credit of taxes paid at previous stages
available as set off. In a nutshell, only value addition will be taxed
and burden of tax Governments on goods and services. GST is a
destination based tax on consumption of goods and services. It is
proposed to be levied at all stages right from manufacture up is to be
borne by the final consumer. GST has been rolled out w.e.f.
01.07.2017, across India.
ii. The GST to be levied by the Centre on intra-State supply of goods
and / or services would be called the Central GST (CGST) and that
to be levied by the States/ Union territory would be called the
State GST (SGST)/ UTGST. Similarly, Integrated GST (IGST) will
be levied and administered by Centre on every inter-state supply of
goods and services.
iii. Any supplier of goods and service Provider of services who makes
a taxable supply with an aggregate turnover of over Rs.20 lakhs
in a financial year is required to obtain GST registration. In special
category states, the aggregate turnover criteria are set at Rs.10
lakhs. In simple words every business whose taxable supply of
goods or services under GST (Goods and Service Tax) and whose
turnover exceeds the threshold limit of Rs. 20 lakhs / 10 Lakhs as
applicable will be required to register as a normal taxable person.
iv. GST Registration Number: TANGEDCO has migrated into GST regime
on 15.06.2017 by duly uploading various mandatory data as required
by the GST portal. The provisional ID issued to TANGEDCO is
33AADCT4784E1ZC. The details are also posted in TANGEDCO web
portal.
v. GST Registration Number or GSTIN is 15 Digit identification
number which is allotted to each applicant who applied for GST
Registration. GST Number is completely based on the Pan
Number and State code. First two digits represent the state code
and another 10 digit represent the PAN number of the client, one
digit represent the entity code (Like proprietorship or partnership
etc), one digit is blank and last one is representing check digit.
vi. Transaction Value: The value of supply of goods or services or
both shall be the transaction value, which is the price actually paid or
payable for the said supply of goods or services or both where the
supplier and the recipient of the supply are not related and the price
is the sole consideration for the supply. Sec 15(1) states that value
of supply of goods and service shall be the transaction value i.e. the
price actually paid or payable.
20
Spec. No. CED/CSR/E.665/18-19
6.0 INSURANCE:
Contracting firms shall arrange insurance for the equipment and all its
accessories being supplied by them, through any of the Nationalised Insurance
Companies. The equipment shall be insured to cover transport (from Warehouse)
and 60 days storage risk at site. The damages, if any, during transit will be
reported within 30 days of receipt of materials. It will be the responsibility of the
supplier to replace the defective/damaged materials and make good the shortages
and other losses in transit, free of cost, lodge and recover claim from
Insurance, Under-writers/Carriers.
22
Spec. No. CED/CSR/E.665/18-19
The equipment and all its accessories shall be securely packed and despatched,
freight paid, duly insured, at supplier’s risk and cost. The packing may be in
accordance with the manufacturer's standard practice. The supplier is responsible
for ascertaining the facilities that exist for Road Transport to site. Each package
shall be clearly marked and contain detailed packing list, such as gross weight,
net weight etc., the supplier is solely responsible for any loss or damage during
transport. The despatch of materials shall be only after the approval of test
certificates by the Board. The Equipments/Materials shall be unloaded at
destination store/ site by the supplier at free of cost.
The supplier shall ensure that the bill of material is approved by the purchaser
before despatch.
The supplier is responsible to make sure about the facilities that exist for
Road and Rail transport to site, the maximum packages which can be
conveyed by the railways and crane lift available at the destination railway
station. The supplier is also responsible for any loss or damage during transport
and storage for 60 days.
8.0 PAYMENT:
8.1 Payment for the supplies will be made by E-banking on any one of the
Nationalised Banks/ Scheduled Banks approved by Reserve Bank of India in
Tamil Nadu. The Bank charges involved in making the payment will be to the
account of the Tenderer.
8.2 Payment to the suppliers will be made through public fund management
system (PFMS) portal from the dedicated account maintained with a nationalized
bank, by Head quarters, TANGEDCO. The bank charges if any involved in making
then payment will be on the account of tenderer.
The tenderer has to furnish the following details of the bank account to
which the payment be credited:
1. Name of the account holder
2. Name of the bank
3. Branch
4. Account Number
5. IFSC code of the branch
23
Spec. No. CED/CSR/E.665/18-19
8.3 Payments will not be made for materials damaged during transit. All
defective materials shall be replaced by the supplier free of charge.
(a) For the materials delivered within the contractual delivery period:
100% of the All-inclusive price (including GST Tax) of the materials of each
consignment will be paid within a reasonable time after receipt of materials
and submission of bills with required documents after deducting recoveries,
if any.
(b) For the materials delivered beyond the the contractual delivery period if
accepted by the purchaser..
100% of the all-inclusive price (including GST) of the materials after
deducting the appropriate amount of LD of each consignment will be paid
within a reasonable time after receipt of materials and submission of bills
with required documents after deducting recoveries, if any.
8.4 For the delayed payments, if any, TANGEDCO will not pay any interest on
any account.
8.5 In cases of delayed supply, the materials will be accepted subject to the
following conditions.
a) There should be no declining trend in prices.
b) Payment will be released as per the recent purchase order rates or lowest
rates obtained during the recent tenders opened subject to levy of liquidated
damages for belated supplies
c) TANGEDCO reserves the right to accept or reject the delayed supplies
without assigning any reason there for and take action as per the other
terms and conditions of this specification.
8.6 The bills for payment will be passed only after the approval / acceptance of
the following:
i) Security Deposit cum Performance Guarantee for 5% value of the
order.
ii) Test Certificate.
iii) Undertaking towards jurisdiction for legal proceedings.
iv) Guarantee Certificate.
v) Supply of approved drawings, Instruction manuals etc, as per section
VII Technical of this specification.
8.7 The supplier should despatch only after getting despatch instructions from
the Chief Engineer/ Distribution/Chennai South. If the supplier despatches
the materials without the prior approval of the purchaser, then the
purchaser shall not be responsible for any demurrage or wharfage or both
and only the supplier should bear any expenditure arising out of such
unapproved despatches.
24
Spec. No. CED/CSR/E.665/18-19
9.1 The Successful tenderer will have to furnish 5% of order value (All-inclusive
price) of as Security Deposit cum Performance Guarantee (including Earnest
Money Deposit remitted) in the form of DD / Banker's Cheque / irrevocable
Bank Guarantee.
9.2 The successful tenderer will have to furnish the Security Deposit cum
Performance Guarantee within 15 days from the date of receipt of award of
Rate Contract Order. The security deposit Cum Performance Guarantee will
not carry any interest. The TANGEDCO also reserves the right to accept the
belated payment of security deposit Cum Performance Guarantee by levying
penal interest at the rate of 22% p.a. from the date of expiry of 15 days
time limit till the date of actual payment of Security Deposit cum
Performance Guarantee. The same will be recovered from supplier’s first bill.
9.3 Failure to comply with the terms regarding Security Deposit Cum
Performance Guarantee set out in the contract order within the stipulated
time by the successful tenderer will entail in the cancellation of the contract
without any further reference to the supplier.
9.4 The Security Deposit Cum Performance Guarantee will be refunded to the
supplier after the expiry of the guarantee period ensuring that defects/
damages during the guarantee period are rectified /replaced. If the
purchaser incurs any loss or damages on account of breach of any of the
clauses or any other amount arising out of the contract becomes payable by
the supplier to the purchaser, then the purchaser will in addition to such
other dues that he shall have under law, appropriate the whole or part of
the security deposit and such amount that is appropriated will not be
refunded to the supplier.
9.5 In case of delay in supply, the BG should be extended suitably. The Bank
Guarantee should be a single Bank Guarantee and should be furnished
within 15 days from the date of receipt of purchase order.
9.6 The Bank guarantee shall be extended for its validity without break in
period till completion of project.
10.0 DELIVERY:
“The drawing should be submitted within 15 days from the date of receipt of
purchase order. The entire ordered quantity supply shall be supplied within 3
months from the date of receipt of drawing approval”.
If the guaranteed delivery period is not kept up, the liquidated damages
specified in Clause - 12 will be enforced.
10.1 TANGEDCO reserves the right to cancel the quantities not supplied as per
delivery schedule.
25
Spec. No. CED/CSR/E.665/18-19
10.1 TANGEDCO also reserves the right to cancel the order if the delivery
schedule is not kept up, without any further notice to the supplier.
10.4 The actual date of receipt of each material with all accessories will be
reckoned as the date of delivery for the purpose of calculation of liquidated
damages in respect of that material.
10.5 It is the responsibility of the supplier to give 15 days advance information
for inspection, despatch of materials and other obligations under the terms
and conditions of this contract in order to deliver the materials within the
contractual delivery period quoted /agreed.
10.6 The delivery period will not normally be extended. Hence all efforts shall be
taken to deliver the materials within the contractual delivery period.
11 INSPECTION:
11.1 The authorised representatives of the purchaser with REC officials shall have
access to the supplier's works at any time during working hours, for the
purpose of inspecting the manufacture of the materials and for testing the
selected samples from the materials covered by the specification. The
suppliers shall provide necessary facilities for such inspection. The entire
cost of inspection shall be borne by the supplier.
11.2 Tenderers are requested to furnish in their tenders the exact location of their
factory with detailed address to enable inspection by TANGEDCO Officers.
11.3 Not less than 15 days advance intimation shall be given about the quantity of
materials that will be ready for inspection by the TANGEDCO's officers/ Third Party
Agency authorised by the TANGEDCO. The arrangement for inspection shall be
made by suppliers in such a way that the delivery schedule is kept up. The
materials shall not be despatched without instruction from TANGEDCO.
11.4. The materials supplied for DDUGJY will be inspected by the authorised
representatives of the purchaser with REC officials to the supplier's works at
any time during working hours, for the purpose of inspecting the manufacture of
the materials and for testing the selected samples from the materials covered by
the specification. Inspection is to be carried out the scheduled date and time as
finalised by PIA(Project implementation Agency) No Variation in quantity, date and
venue shall be allowed. If the material is not ready on the scheduled date of
inspection then the inspection call shall be treated as fake call and penalty of Rs
50,000 /= shall be imposed on the contractor towards deployment of inspector.
26
Spec. No. CED/CSR/E.665/18-19
12 LIQUIDATED DAMAGES:
12.1 The delivery as specified should be guaranteed by the supplier under the
Liquidated Damages Clauses given below:
12.2 If the supplier fails to deliver the materials within the time specified in the
indent or any extension thereof, the purchaser shall recover from the
supplier as liquidated damages, a sum of half a percent (0.5%) of the All-
inclusive price of the undelivered Materials for each completed week of
delay. The total liquidated damages shall not exceed ten percent (10%) of
the All-inclusive price of the materials so delayed. The actual date of delivery
of materials with all its accessories at destination stores will be reckoned as
date of delivery for this purpose. Liquidated damages will also be recovered
for the quantity not supplied as is done for the belated supply. It is the
responsibility of the suppliers to arrange for inspection, despatch etc. in time
to keep up the delivery schedule.
12.3 If supplies to be rendered against the Rate Contract Order are made by the
supplier beyond the period of delivery stipulated in the indent and if they are
accepted by the TANGEDCO, such acceptance is without prejudice to the
TANGEDCO's rights to levy liquidated damages for the delay in supply.
12.4 The TANGEDCO will also be at liberty to cancel the order if the supply is not
made as per the delivery schedule specified in the indent, notwithstanding
its rights to claim liquidated damages for the belated supplies and quantity
outstanding to be supplied as on the date of cancellation.
12.5 The suppliers are liable to pay the amount of loss sustained by the
TANGEDCO in the event of non-execution of orders, if any placed on them
either in full or part to the satisfaction of the TANGEDCO under the terms
and conditions of contract and in the event of placing orders for such
quantities on some others at a higher price.
12.6 Tenderers not giving clear and specific acceptance to the above clauses are
liable for rejection.
12.7 If there is any downward trend in prices on account of belated supplies, the
tenderers have to accept the same with the levy of liquidated damages, for
belated supplies.
12.8 The defaulting contractors will be liable to pay to the TANGEDCO in addition
to Liquidated Damages for delay, the actual difference in price wherever
TANGEDCO orders the delayed quantity to be supplied by other agencies at
a higher cost.
12.9 Equipment/materials will be deemed to have been delivered only when all its
component and its accessories are also delivered. If certain components
and accessories are not delivered in time the whole equipment will be
considered as delayed unless, the missing parts are delivered. The
27
Spec. No. CED/CSR/E.665/18-19
Liquidated damages will also be levied for the quantity not supplied
as is done for the delay supplies. If supplies effected in part which
could not be beneficially used to the TANGEDCO (due to such
incomplete supply), liquidated damage will be worked out on the
basis of entire contract price of such materials which could not be
beneficially used and not on the value of delayed portion only.
12.10 If the ordered materials are not delivered, the purchaser shall recover from
the supplier, as liquidated damages a sum of TEN PERCENT (10%) of the
contract price of the equipments/materials undelivered besides forfeiture of
security deposit.
13 FORCE MAJEURE:
13.1 The supplier shall not be liable for delay in performing his obligations
resulting directly or from any force majeure conditions herein defined as:
(a) Any cause which is beyond the reasonable control of the supplier or
purchaser as the case may be
(b) Natural phenomena, such as floods, drought, earthquakes and epidemics.
(c) Act of any Govt. Authority, domestic or foreign, such as wars declared or
undeclared quarantines, embargoes licensing control on production or
distribution restrictions.
(d) Accident and disruptions such as fire, explosion, increase in power cut with
respect to date of tender opening, break down of essential machinery or
equipments etc.
(e) Strikes, slow down, and lockouts.
(f) Failure or delay in the supplier's source of supply due to force majeure
causes enumerated at 'b' to 'e' above shall be considered, provided the
supplier produces documentary evidence to show that there were no other
alternative source of supply available to him or if available the lead time
required was likely to be longer than the duration of the force majeure at
the normal source of supply. All the provisions of this clause shall apply
whether the disruption cause is total or partial in its effect upon the ability of
the supplier to perform.
NOTE: The cause of force majeure condition will be taken into consideration only if
the supplier notifies within 15 days from the occurrence of such
eventualities. The purchaser shall verify the facts and grant such extension
as the facts justify. For extension due to force majeure conditions, the
supplier shall submit his representation with documentary evidence for
scrutiny by the purchaser and decision of the purchaser shall be binding on
the firm.
13.2 Provided that if the performance in whole or part by the supplier on any
obligation under this contract is prevented or delayed by reasons of any
eventuality for a period exceeding 60 days, the TANGEDCO may at its option
terminate the contract by a notice in writing.
28
Spec. No. CED/CSR/E.665/18-19
13.3 The Power cut shall not be considered under force majeure condition. The
period of extension shall be decided only by the authority who placed the
order, after verifying the evidence for the cause of delay.
14.0 GUARANTEE:
The entire equipments should be guaranteed for satisfactory operation and good
workmanship at least for a period of 36 (Thirty six) months from the date of
receipt of materials at site in good condition.
Any defects noticed during this period shall be rectified free of cost to the
TANGEDCO within 2 (Two) months from the date of intimation of defect/failure.
Irrespective of number of failures and repairs, the suppliers are responsible for
free replacement of the defective materials. Such replaced components shall
serve for a continuous period of 12 months from the date of re-commissioning
and this shall be in addition to the guarantee provided for the equipment.
The incidental expenses, transport and freight charges for the replacement of
defective materials within the guarantee period shall also be borne by the supplier
till such time it serves a continuous period of 12 (Twelve) months as said above.
The Supplier shall guarantee among other things, the following:
(i) Quality and strength of materials used.
(ii) Safe electrical and mechanical stresses on all parts of the equipments
under all specified conditions.
(iii) Performance figures given by the tenderers in the Schedule of
Guaranteed technical particulars
The supplier should despatch the materials only after getting dispatch
Instruction from the Chief Engineer/ Distribution/Chennai South .If the supplier
despatches the materials without the prior approval of the purchaser, then the
purchaser shall not be responsible for any demurrage or wharfage or both and
only the supplier should bear any expenditure arising out of such unapproved
despatches.
the receipt of the materials. Internal defects, damages or shortages of any integral
parts which cannot ordinarily be detected on a superficial visual examination
caused by bad handling in transit or defective packing would be indicated after
inspection on receipt of the materials at stores. In either case, the damaged or
defective materials should be replaced free of cost to the TANGEDCO within 60
days.
16.2 If during the period of supply, it is found that goods already supplied are
defective in material or workmanship or do not conform to specification or
unsuitable for the purpose for which they are purchased, then it will be open
to the purchaser either to reject the goods or repudiate the entire contract
and claim such loss that the purchaser may suffer on that account require
the supplier to replace the defective goods, free of cost.
16.3 Similarly, if during the guarantee period any of the goods found to be
defective in materials or workmanship or do not conform to specification or
are unsuitable for the purpose for which they are purchased, it will be open
to the purchaser either to repudiate the entire contract and claim damages
or accept such parts of the goods that are satisfactory and require the
supplier to replace the balance or to claim compensation for the entire loss
sustained by the purchaser on that account.
16.4 In the event of supplies being received damaged or any shortages at the
destination stations, the cost of such materials, Excise duty and VAT (if
payable) and other charges payable thereof will be paid only proportionate
to the value of materials received in good condition, unless the damaged
goods or short supplies are made good free of cost by the suppliers.
16.5 For all legal purposes, the materials shall be deemed to pass into the
TANGEDCO’s ownership at the destination Stores, where they are delivered
and accepted.
18.0 RESPONSIBILITY:
The tenderer is responsible for safe delivery of the materials at the destination
stores. The tenderer should include and provide for packing and secured
protection of the materials so as to avoid damages or loss in transit.
20.0 NON-ASSIGNMENT:
20.1 The supplier shall not assign or transfer the contract or any part thereof
without the prior approval of the Purchaser.
31
Spec. No. CED/CSR/E.665/18-19
27.2 The details furnished by the tenderers shall be in complete shape and if it is
found that any information is found omitted, suppressed, incomplete or
incorrect, the same will be taken note of while dealing with the tenders in
future.
29.1 No suit or any proceedings in regard to any matter arising in respect of this
contract shall be instituted in any court, save in the High Court, Madras, City
Civil Court at Chennai or at the Court of small causes at Chennai. It is agreed
that no other court shall have jurisdiction to entertain any suit or proceedings
even though, part of the cause of action might arise within their jurisdiction. In
case any part of the cause of action might arise within the jurisdiction of any
other Courts in Tamil Nadu and rest within the jurisdiction of courts outside the
Tamil Nadu, then it is agreed to between the parties that such suits or
32
Spec. No. CED/CSR/E.665/18-19
proceedings shall be instituted in a Court within the State of Tamil Nadu and
no other court outside the State of Tamil Nadu shall have jurisdiction even
though any part of the cause of action might arise within the jurisdiction of
such courts. The successful Tenderer shall furnish an undertaking as per
Annexure-II in a non judicial stamp paper of Rs.80/-agreeing to the above
condition.
Performance Guarantee will be released on expiry of guarantee period
after ensuring that defects/damages during the guarantee period are
rectified/replaced.
30.1 All materials, equipments and spare parts thereof shall be new, unused and
originally coming from manufacturers’ plant to the destination stores. Those
including used, rebuilt or overhauled materials/equipments will not be
accepted.
30.2 All the materials shall be of best class and capable of satisfactory operation
in the tropics with humid atmospheric condition. Unless otherwise specified,
they shall conform to the requirements of appropriate Indian Standards.
Where these are not available, IEC and American / British Standards shall be
followed.
30.3 The design shall incorporate every reasonable precautions and provisions for
the safety of all those concerned in the operation and maintenance of
equipment/ materials.
30.4 The materials should be designed to facilitate inspection and repair and to
ensure satisfactory operation under atmospheric conditions prevailing at site
and under sudden variations of load and voltages as may be met with under
working conditions in the system including those due to faulty synchronizing
and short circuits within the rating of the apparatus.
30.5 All the equipments should operate without undue vibration and with the
least practicable amount of noise.
33
Spec. No. CED/CSR/E.665/18-19
34
Spec. No. CED/CSR/E.665/18-19
Sd/-
CHIEF ENGINEER/DISTRIBUTION
CHENNAI SOUTH REGION
35
Spec. No. CED/CSR/E.665/18-19
SECTION –VI
1.0. SCOPE
1.1 The scope of bid envisages the Design, Engineering, Manufacture, Stage
testing, Final Inspection and testing before supply, Supply and Delivery at site, so
as to be a protected switch gear, feasible to be integratable towards remote
monitoring and control using local HMI SCADA and also to be compatible to the
existing/proposed SCADA in TANGEDCO. The system will transmit data to
Chennai DCC SCADA system on real time with IEC 60870-5-101 protocol. Sub-
station equipments like energy meters, relays etc which may have MODBUS, DNP
3.0, IEC 61850 protocols with Optical/RS485 port. Station Controller shall also
support ABB’s RP570 protocol and IEC 61850 to communicate with Master
Station. This specification also provides for packing and delivery F.O.R.
(Destination) of 11 KV Single Bus 25 KA, 1250 Amps, Indoor Vacuum Circuit
Breaker (VCB) panels suitable for Feeder, Transformer and Bus coupler control
with all accessories and auxiliary equipments and mandatory spares described
herein and required for the satisfactory operation at any location in and around
Chennai city and also other places in TAMILNADU for TANGEDCO/TANTRANSCO.
1.2 The Switchgear Panel shall conform in all respects to high standards of
engineering design, workmanship and latest revisions of relevant standards at
the time of offer. The purchaser shall have the right to reject any work or
material which in his judgment is not in full accordance therewith.
1.3 The breakers should be as per the guaranteed technical particulars furnished
in annexure.
2.0. STANDARDS:
The Breakers and Instrument Transformers shall conform to the latest revisions
and amendments thereof of the following standards.
1. IEC-62271-100 Specification for alternating current circuit Breakers.
& 200
2. IEC-60298 Metal Enclosed Switchgear and Control Gear for
Rated Voltages up to and including 36 KV
3. IEC 2331 High voltage porcelain bushings
4. IEC-60 High voltage test techniques
5. IEC-71 Insulation co-ordination
6. IEC-270 Partial discharge measurement
7. IS-3427 Specification for metal clad high voltage switchgear
36
Spec. No. CED/CSR/E.665/18-19
The H.T. switchgears shall be suitable for operation on three phase, three
wire, 11 KV, 50 cycles, A.C. System. Every current-carrying part of the switchgear
including Circuit Breaker, current transformers, conductors, bus bars & bus
raisers in case of transformer control panel shall be capable of carrying its
specified rated normal current of 2000 A continuously, connections and joints
shall be capable of carrying its specified rated normal current of 1250 A
continuously and in no part shall the temperature rise exceed the values specified
in relevant IEC Standards at ambient temperature. Assistance from any forced
cooling to maintain IEC rating is not allowed. Every part of the switchgear shall
also withstand, without mechanical or thermal damage the instantaneous peak
currents and rated short-time current of 25 KA (3 sec.) pertaining to the rated
breaking capacity of the circuit breaker.
37
Spec. No. CED/CSR/E.665/18-19
The Indoor VCB panels should be suitable for operation on the following
auxiliary supply systems.
a) Power Devices like drive Motors 415V, 3 Phase 4 Wire 50Hz, AC
of rating 1 KW and above neutral grounded
b) Alarm, Lighting, space heaters and 240V single phase, 50Hz, AC
fractional KW motor neutral grounded
The above supply voltage may vary as below and all devices shall be suitable for
continuous operation over entire range of voltage.
Sl No Item Requirement
38
Spec. No. CED/CSR/E.665/18-19
capability
27 Rating of auxiliary contacts 15 A (110V/30V DC) Shall be 4A at 110V
DC & 8A at 30V DC may be accepted.
28 Breaking capacity of auxiliary 2 A DC with the circuit constant less
contacts than 20ms at the rated voltage.
29 Noise level at base and upto 50 140 dB (max.)
metres
30 Seismic acceleration 0.3 g
31 Protection IP 4 X for HV compartment & IP 5 X for
LV compartment
7.1. All similar materials and removable parts of identical equipments shall be
interchangeable with each other. The VCB truck in particular should easily be
interchangeable.
7.2. The panels should be suitable for easy extension on both sides by addition of
panels of same make.
41
Spec. No. CED/CSR/E.665/18-19
a) Ratio : 900-600/1-1-1A
42
Spec. No. CED/CSR/E.665/18-19
The CT protection accuracy should take care of the fault current and fault MVA or
whichever is higher.
v) 3 nos 11 KV single phase indoor resin cast PTs: Shall be of draw out type PT
on line side (Preferably truck mounted draw out from front side). Mounted on
rear side of panel inside cable compartment may be accepted 1) based on the
position of CT so that panels can be erected in the existing substations without
modification of cable duct. 2) If floor mounted, trolley for easy transportation is
to be given.
The compatibility of PT and its burden shall be ensured for all the measuring/
protection devices.
a) Protection fuses to be provided for LT
b) PTs shall conform to IEC-60044-2 / IS 3156 of the latest issue
c) For the PT Primary HRC fuse shall be provided
The PTs shall have isolating features, current resistors etc. with indicating lamps
for each phase. The primary of the potential transformer should be connected
with the main supply through a plug type arrangement. The PT shall be of draw
43
Spec. No. CED/CSR/E.665/18-19
out type with self locking arrangement with HRC fuse on HV and LV side and
shall be of plug in type. The potential transformer supply should not be disturbed
by jerking of the PT. Neutral of the potential transformers should be brought out
externally and earthed separately to facilitate isolation during testing at site.
Wiring shall be done from cable termination for voltage indication and voltmeter
reading so that phase voltage is read when the power transformer is energized.
vi) Voltmeter : 1 No. To read: 0-16 KV
vii) Voltmeter selector switch: 1 No. 7 position
x) The power consumption of tripping coil & closing coil shall be 250 ± 25 W.
x) 3 nos. 11 KV resin cast insulated solid round copper bus bar suitable for
highest system voltage is preferred. Panels with equally insulated rectangular bus
bars may also be offered. The area of cross section of the bus bar shall be such
way to carry the rated current of 2000 A with a current density of 1.6 amps per
sq.mm. No tolerance shall be permitted. The bus bars and jumpers shall be
housed in a totally enclosed compartment without barriers between the adjacent
panels. The bus bars shall be supported on specially designed cast resin
insulators at short intervals keeping adequate clearance between bus bars and
earth. The bus bar chamber is to be located on the back side of the circuit
breaker chamber. The bus bar chamber shall be provided with inspection covers
and bus bar shutters. Provision shall be made for future extension of bus bar and
switch board. The busbar joints shall be insulated by preformed insulation and
shall be detachable type suitable for inspection of bolt tightness at joints. The
insulating material used shall be capable of withstanding the heating effects of
the rated short time current without permanent deformation or deterioration.
Provision shall be made for future extension of bus bar and switch board.
44
Spec. No. CED/CSR/E.665/18-19
xi) Spring charge mechanism for charged position indication. 2 Nos. spare contact
wired upto (SCADA) terminal block.
xii) Local/Remote switch with separate contact for indicating the position to
SCADA wired upto terminal block.
xiv) Stud type terminal block for controls and disconnecting link type terminals
for CT leads.
xv) Static Tri-vector meter with specification as set out in clause 10.7.
ii) 3 Nos. of 11 KV window/ring type or bar primary indoor resin cast, two core
Current Transformers with the following specifications.
a) Ratio : 300/1-1Amps
b) Burden : 5VA for Core I and 30 VA for core II
c) Accuracy : Core I – Class 0.2S (metering)
Core – II – 5P20 (Protection)
The CTs shall have 2 cores on secondary with following specifications. Metering -
0. 2S accuracy class with 5 VA burden, protection - 5P20 with 30 VA burden.
(Core II of CT with burden > 7.5VA may be accepted provided the CT is not
saturated due to heavy fault current. For that, magnetizing current shall be
<40mA (Vk/2)) and PS class. The magnetising current and the knee point voltage
(Vk) shall be as per the requirement of the relay manufacturer.
45
Spec. No. CED/CSR/E.665/18-19
The CT protection accuracy should take care of the fault current and fault MVA or
whichever is higher.
The feeder panel shall be provided with line indicators using capacitor divider
circuit along with provision for checking phase sequence. PT selection switch for
energy meter reading with phase sequence indication shall be provided such that
in case of failure of one of the PT supply to all energy meters are extended
without interruption. The above selection shall be manual.
Additional Disconnecting terminal Block for R,Y,B Currents with loops may be
Provided to connect External Transducers to be provided by TANGEDCO.
viii) All the relays and accept/reset push buttons shall be situated at height
approximately 5 feet for smooth and easy operation for the operator. More than
5½ feet is not acceptable.
ix) The power consumption of tripping coil & closing coil shall be 250 ± 25 W.
vii) 3 nos. 11 KV resin cast insulated solid round copper bus bar suitable for
highest system voltage is preferred. Panels with equally insulated rectangular bus
bars may also be offered. The area of cross section of the bus bar shall be such
way to carry the rated current of 2000 A with a current density of 1.6 amps per
sq.mm. No tolerance shall be permitted. The bus bars and jumpers shall be
housed in a totally enclosed compartment without barriers between the adjacent
panels. The bus bars shall be supported on specially designed cast resin
insulators at short intervals keeping adequate clearance between bus bars and
earth. The bus bar chamber is to be located on the back side of the circuit
breaker chamber. The bus bar chamber shall be provided with inspection covers
46
Spec. No. CED/CSR/E.665/18-19
and bus bar shutters. Provision shall be made for future extension of bus bar and
switch board. The busbar joints shall be insulated by preformed insulation and
shall be detachable type suitable for inspection of bolt tightness at joints. The
insulating material used shall be capable of withstanding the heating effects of
the rated short time current without permanent deformation or deterioration.
Provision shall be made for future extension of bus bar and switch board.
ix) Spring charge mechanism for charged position indication. 2 Nos. spare contact
wired upto (SCADA) terminal block.
xii) Stud type terminal block for controls and disconnecting link type terminals for
CT leads.
xiii) Static Tri-vector meter with specification as set out in clause 10.7.
i) 1 No. 11 KV, 25KA, 1250 Amps triple pole, Indoor VCB with provision for both
manual operation and motor spring closing mechanism with suitable adaptor for
separating different feeders and transformers.
ii) 3 Nos. 11KV window/ring type or bar primary indoor resin cast, three core
Current Transformers, with the following specifications.
a) Ratio : 900-600/1-1-1A
b) Burden : 5VA for Core I and 30VA for core II
c) Accuracy : Core - I – Class 0.2S (metering)
: Core - II – 5P20 (Protection)
: Core –III– PS Class (Protection)
The CTs shall have 3 cores on secondary with following specifications. Metering -
0.2S accuracy class with 5 VA burden, protection - 5P20 with 30 VA burden. (>
7.5VA may be accepted provided the CT is not saturated due to heavy fault
current. For that, magnetizing current shall be <40mA (Vk/2)) and PS class. The
magnetising current and the knee point voltage (Vk) shall be as per the
requirement of the relay manufacturer.
47
Spec. No. CED/CSR/E.665/18-19
The CT protection accuracy should take care of the fault current and fault MVA or
whichever is higher.
d) Short time current rating : 25 KA for 3 Seconds
e) Insulation level : 28 KV /75 KV peak.
Additional Disconnecting terminal Block for R,Y,B Currents with loops may
be Provided to connect External Transducers to be provided by TANGEDCO.
v) Relays: As per clause 10.6
vi) All the relays and accept/reset push buttons shall be situated at height
approximately 5 feet for smooth and easy operation for the operator. More than
5½ feet is not acceptable.
vii) The power consumption of tripping coil & closing coil shall be 250 ± 25 W.
vii) 3 nos. 11 KV resin cast insulated solid round copper bus bar suitable for
highest system voltage is preferred. Panels with equally insulated rectangular bus
bars may also be offered. The area of cross section of the bus bar shall be such
way to carry the rated current of 2000 A with a current density of 1.6 amps per
sq.mm. No tolerance shall be permitted. The bus bars and jumpers shall be
housed in a totally enclosed compartment without barriers between the adjacent
panels. The bus bars shall be supported on specially designed cast resin
insulators at short intervals keeping adequate clearance between bus bars and
earth. The bus bar chamber is to be located on the back side of the circuit
breaker chamber. The bus bar chamber shall be provided with inspection covers
and bus bar shutters. Provision shall be made for future extension of bus bar and
switch board. The busbar joints shall be insulated by preformed insulation and
shall be detachable type suitable for inspection of bolt tightness at joints. The
insulating material used shall be capable of withstanding the heating effects of
the rated short time current without permanent deformation or deterioration.
Provision shall be made for future extension of bus bar and switch board.
48
Spec. No. CED/CSR/E.665/18-19
viii) Spring charge mechanism for charged position indication. 2 Nos spare
contact wired up to (SCADA) terminal block.
ix) Local/Remote switch with separate contact for indicating the position to
SCADA wired up to terminal block.
xi) Stud type terminal block for controls and disconnecting link type terminals for
CT leads.
10.0. GENERAL:
a) Each VCB Panel shall be housed in a fabricated housing made of bolted/ CRCA
sheet steel or Aluminum-Zinc sheet of thickness not less than 2.5 mm for all load
bearing members and 2 mm for non load bearing members. Non load bearing
member shall be 2mm thick (with Aluminum – Zinc steel cubicle for load bearing
member, the sheet steel is so formed that the total steel thickness shall be 4mm
(2mm + 2mm) suitable reinforcement is also acceptable). Adequate stiffeners
shall be provided for top cover so that minimum two persons could walk on top
of the panels simultaneously. Minimum four number lifting hooks shall be
provided at the top to lift the panel with the VCB truck inside using crane during
transport and erection. Floor mounted type breakers are preferred. If trolley
mounted VCB truck is offered the supplier shall supply adequate number of
trolleys as requested by TANGEDCO.
b) Each VCB panels shall be supplied with 3 nos. 11 KV resin cast insulated solid
round copper bus bar suitable for highest system voltage is preferred. Panels
with equally insulated rectangular bus bars may also be offered. The area of
cross section of the bus bar shall be such way to carry the rated current of 2000
A with a current density of 1.6 amps per sq.mm. No tolerance shall be permitted.
The bus bars and jumpers shall be housed in a totally enclosed compartment
without barriers between the adjacent panels. The bus bars shall be supported
on specially designed cast resin insulators at short intervals keeping adequate
clearance between bus bars and earth. The bus bar chamber is to be located on
the back side of the circuit breaker chamber. The bus bar chamber shall be
provided with inspection covers and bus bar shutters. Provision shall be made for
future extension of bus bar and switch board. The busbar joints shall be insulated
49
Spec. No. CED/CSR/E.665/18-19
6 Nos Isolating plugs – 3 Nos. for the Buses and 3 Nos. for the line with
necessary sockets along with automatic safety shutters, bus bar jumpers, etc. are
to be provided in each panel. The bus bars shall be of 99.9% electrolytic copper.
c) The flower/jaw contacts are to be provided on the truck side and free from
atmospheric effects.
e) The maximum temperature in any part of the equipment shall not exceed the
permissible limits as stipulated in the relevant standards.
f) The L.V equipments like relays, meters, indication lamps, switches and
accept/reset push buttons shall be mounted in the L.V. chamber at the panel
front, at a height not more than 5 feet so that they can be operated easily
without any steps. More than 5½ feet is not acceptable.
g) The VCB preferably of floor mounted type, with isolating main contacts for
isolating the VCB. The Circuit Breaker compartment shall be suitable for
accommodating the VCB truck. The breaker compartment is to be separated
from the bus bar and cable compartment by Fiber Glass reinforced epoxy
plate/MS plate. The shutters are to be operated smoothly and automatically by
the movement of truck and the shutters shall be of solid closing type that close
automatically when the truck is withdrawn and the shutters cannot be pushed
open inadvertently when the truck is removed. The breaker is to be operated
both Manual/Motor spring charging mechanism. In case, the breaker truck is
withdrawn, there shall be a cover supplied to make it vermin proof if doors are
not provided.
All panels shall have suitable surge protection for DC controls at the source point.
(If any other scheme is proposed the same shall be got approved from
50
Spec. No. CED/CSR/E.665/18-19
TANGEDCO). Provision shall be given to isolate the DC load of the SCADA system
at a single point.
The individual compartments are to be provided with explosion vents at the top
of panels to let out gases under pressure generated during unlikely event of fault
inside the panel.
When the breaker is in service position, without closing the door the breaker
should not be closed.
Window/ring type CT shall be mounted such a way that while replacing the cable
termination or terminating the cable there should not be any need to remove the
CT and its associated wiring. The CTs shall be of draw out only.LV and Bus
coupler the ratio shall be 900-600/1-1-1A.
The Panel illumination with 3 no 14 W CFLs is to be provided in the Bus bar, L.V.
chamber and cable compartments.
The offer should include provision for wiring of annunciation equipment like
hooter, bell, and reset push buttons for the Sub Station.
The distance between the cable termination to CT (the termination lug) and cable
clamping shall be 700 mm. To obtain this cable pan of maximum depth up to
400mm may be used.
Adequate accessories required for fixing the panel such as foundation bolts and
nuts as well as attachment bolts and nuts shall be provided along with panel. For
every 2 Nos. of breakers, breaker operating rod, door opening key, interlock key,
spring charge rod etc., shall be given.
Separate entry for control cable (open with cover) shall be provided preferably in
the rear side bottom separated from the power cable entry for Transformer and
Feeder panels.
Trip circuit healthiness indication, auto trip indication and breaker ON/OFF
indication shall be in DC supply. All other indications shall be in AC supply ONLY.
Copper Bus bar joints should be covered with 11 kV class FRP shrouds without
any gap or any other flexible material.
There shall be suitable MS channel with adequate holes for cable clamping
arrangement in all Feeders and Transformer panels. Transformer panel shall have
provision to connect 2 X 3 runs of 1 X 630 sq. mm. aluminum UG cable per phase
and the feeder panel shall have provision to connect 3 X 300 sq. mm. cable.
51
Spec. No. CED/CSR/E.665/18-19
In all the panels, the accept/reset push button shall be provided and the
annunciation shall be extended from the common alarm.
Each VCB shall be housed in a fabricated sheet steel enclosure with the following:
(a) Vertical or horizontal isolation, horizontal draw out circuit Breaker truck with
VCB, its mechanism, auxiliary contacts and interlocks.
(b) 11 KV, single phase, twin core/triple core, resin cast window/ring or bar
primary type indoor CTs.
(c) 11KV, single phase, resin cast, truck mounted type PT to be provided for
Transformer panel.
(d) Air insulated Bus bar chamber fixed main contacts, automatic safety shutters,
bus bar, jumpers etc.
(f) The breakers shall have provision for terminating required no of cables along
with aluminum gland plate, suitable housing heaters (PTC type), indicating lamps
and illuminating lamps etc.
(g) 1 No. fabricated housing made of bolted steel/Aluminum-Zinc sheet not less
than 2.5 mm for load bearing with 4 lifting hooks at the top to lift the panel along
with VCB truck by a crane during transport and erection.
(h) One set of mechanical interlocks to prevent moving of the switch gear truck
unless the circuit breaker is in the open position.
(i) One set of mechanical interlocks to prevent the movement of the breaker from
service position of the Breaker, when the breaker is in service position and in
closed condition.
(j) One set of mechanical/electrical interlock to prevent the closing of the Breaker
when the Breaker is in service position and the control cable plug is not inserted
in the VCB truck
Following interlocks apart from the already given above shall be ensured.
52
Spec. No. CED/CSR/E.665/18-19
Provision shall be given to isolate the DC load of the SCADA system at a single
point.
All indication lamps shall be of LED cluster type. Lamps must be replaced from
the front end instead of the rear end.
All the VCB panels should be suitable for easy extension on both sides by addition
of similar panels. Bus bar end covers shall be supplied as required by
TANGEDCO. End covers to cover bus bar chamber (both right hand side and left
hand side) shall be supplied as required by CDC wing of TANGEDCO.
10.2. Switchgear Truck:
The breaker truck is to be horizontally drawn out and shall be preferably of floor
mounted type. If trolley mounted VCB truck is offered the supplier shall supply
adequate number of trolleys as requested by TANGEDCO. The service and test
positions shall be distinctly marked. In the service position, the isolating contacts
should fully engage each other. The breaker should lock out after the flower/jaw
contacts have made full contact with the bus. The control wiring from the breaker
to the control equipments on the L.V. Chamber shall be made through minimum
24 way plug and socket arrangement. The plug is to be interlocked in such a way
that the breaker truck cannot be pushed into service position until and unless the
control plug is inserted in the correct place. The full isolated position is to be
achieved in the test position by removal of the control plug. The insulated fiber
glass connecting rods wherever used shall be sturdy and shall not break during
the entire life period of the breaker. The shunt close/ trip coils shall be fed from
110/30 Volts station battery for closing/ tripping purposes and shall consume 250
± 25 watts. The current taken by the coils shall be limited to 3/10 amps.
53
Spec. No. CED/CSR/E.665/18-19
All the equipments should operate without undue vibration and with the
least practicable amount of noise. The breaker truck should be inter-changeable.
This should be ensured. Operating handle, circuit breaker drawal handles are to
be supplied at the rate of one set each for two panels supplied. Wherever the
panels will be erected as single unit with other make panels, additional set has
to be supplied at free of cost , as and when required by the TANGEDCO based on
the site condition.
All mating contacts shall be of flower/jaw type only and free from
atmospheric effects. Any other type of mating contacts shall not be accepted.
They shall be mounted on the truck side only. Contacts shall be designed to have
adequate thermal and current carrying capacity for the duty specified and to
have a life expectancy so that frequent replacements due to excessive burning
shall not be necessary. Provision shall be made for rapid dissipation of heat
generated by the arc on opening. If arcing contacts are used they shall be first to
close and last to open. Tips of arcing contacts and main contacts shall be silver
plated or made of superior material like graphite/tungsten copper/copper
chromium. Breakers shall be so designed that when operated within their
specified rating, the temperature of each part will be limited to values consistent
with long life of the materials used. The temperature shall not exceed that
indicated in latest IEC under specified ambient conditions.
10.3 Interlocks:
10.3.1. The movement of the switchgear truck should be defeated when Breaker
is in service position and is in ON position.
10. 3.3. The closing of the breaker either electrically or mechanically should be
defeated if the breaker is not locked in the service position fully.
10.3.4. Secondary Plug (Truck Plug) and socket interlock shall be provided.
10.3.5. Limit switch shall be given in such a way that after spring charging only
the closing pulse can be given to the breaker.
10.3.6. One set of mechanical interlock to prevent moving of the switchgear truck
unless the circuit breaker is in the open position.
10.3.8. Movement of the switchgear truck from service to test position shall be
possible only when the breaker is in OFF position.
10.3.9. Front door of the switchgear compartment shall not be opened unless
breaker is tripped and brought to test position.
10.3.10 Auxiliary plug and socket shall not be opened unless VCB is brought to
test position.
10.3.11. Rear cable chamber cover shall not be opened unless and otherwise the
breaker if OFF and in test position. (Rear cover shall be box type with mesh
protection)
10.3.13. The movement of the switchgear truck should be defeated when the
rear covers are not closed.
Current transformers shall be located on the feeder side of the circuit breaker
and on both sides for bus section Bus coupler breaker and shall be part of panel
assembly. CTs shall be encapsulated and protected from the adverse effect of
atmospheric conditions. Generally, the cores for measuring instruments shall
have accuracy class of 0.2S or better and saturation factors below five (5). Cores
for relay shall have accuracy class of 5P as required. For unit protection schemes,
the C.Ts shall have class PS accuracy class according to IEC 60044-1. The C.Ts
55
Spec. No. CED/CSR/E.665/18-19
shall have the same short-circuit ratings as that of the switchgear. All secondary
shall be wired to terminal block in LV compartment to facilitate easy ratio
changing. Adequate interposing CT’s are to be provided in case protection/
measurement/SCADA are fed from the same CT core.
whether they are connected to the circuit side or the busbar side the circuit
breaker. The Voltage transformer truck, if provided for draw out type, shall be
earthed separately. All voltage transformers shall have windings of required (but
with min. specified) VA output, 50 VA. The neutral point of the Primary star
connected windings shall be solidly earthed in an accessible position and shall be
easily isolated for insulation testing. The neutral point of the secondary star
connected windings shall be earthed separately via approved removable links
mounted in accessible positions. Voltage transformers shall have a rated voltage
factor of 1.2 continuous and 1.5 for 30 seconds. Labels of approved type shall be
provided showing make, serial no., type, ratio, accuracy class, output, maximum
continuous thermal current. Suitable measures shall be provided to ensure
protection against ferroresonance effects. Facility and accessories, if any, shall be
provided for easy disconnection of voltage transformers during HV DC testing of
the cables. It shall be arranged that replacement of one or all the voltage
transformers can be carried out in situ, without complications. If, any handling
devices or fixtures are required for this purpose, then one set shall be supplied
within the quoted price of the switchgear.
iv) Shall have independent protection characteristics (IDMTL and Transient free
High set) for each phase. The IDMTL characteristic of the relay shall be 1.3 secs
at 10 times set value of the current with time set at unity.
v) The following characteristics should be able to be set at the site.
IDMTL – 5% to 200% for OC.
2% to 80% for E/F.
High Set – 50 % to 2000 % for OC
20 % to 800 % for E/F.
Selection of curve shall be 1.3 secs. Instantaneous setting for O/L shall be 20.
For E/L it shall be 8.
vi) The Time Multiplier setting shall be 0 to unity continuously in steps of 0.01,
variable for each phase and for both IDMTL and high set separately.
1. To store minimum of last ten fault data with date, time and current.
2. Alpha – Numeric LED display of minimum 12 mm backlit.
3. HMI for programming the relay.
4. Shall have self diagnostic features.
5. Shall have one set of NO and 1 set of NC potential free contacts.
6. The relay should operate satisfactorily at ambient air temperature ranging
from 10°C to 50°C.
ix) The relay should have communication port (RS 485) compatible for IEC
61850 Protocol. The relay should have communication port (Ethernet) or FO
port compatible for IEC 61850 protocol. Acceptable provided the relay has
communication port to connect a Laptop enabling MRT to down load later.
xi) The relay shall have suitable provision to take care of surges and inadvertent
high voltage due to fault.
2 no tripping relays one for transformer protection and another for overload and
earth fault protection shall be provided for transformer panel. The contacts of the
relay shall be wired up to the terminal block for SCADA. Provision should be
made for connecting up the transformer differential relay in one of the protection
core of the CT.
58
Spec. No. CED/CSR/E.665/18-19
Upon TSR (trip circuit supervision relay) activation, there should be an alarm. The
permissive command to close the breaker should be disabled (i.e.) the breaker
should not be closed when the trip circuit is unhealthy.
10.7.1 3 Phase 4 wire 110V 1A 0.2S Accuracy class CT/PT operated fully Static
and AMR compatible Trivector Meter with automatic and manual scrolling facility
to read KWHr, RKVAHr, Voltage, Current, Power factor and instantaneous KW
with optical port for downloading the load survey for 35 days and with MD reset
push button and test block (link type terminal block) preferably below the meters
for isolation during testing. The meter should be compatible with the trivector
meters used by TNEB for HT metering. Necessary software compatible with
SANDS CMRI for the same shall also be included in the scope of supply. Only
Elster, Secure, L&T and Lyandis Gear make of the meter shall be accepted. Any
other type of the meter intended to be used by the supplier shall have to be
accepted by the MRT wing. RS 485 port compatible for MODBUS/IEC/D NP 3
protocol shall be provided. Opto coupler or one set potential free contact to
translate the energy transmitted through the feeder to SCADA shall be provided.
59
Spec. No. CED/CSR/E.665/18-19
60
Spec. No. CED/CSR/E.665/18-19
In addition to above the meter shall also record the Name plate details,
programmable parameters (readable as profile), occurrence and restoration of
tamper events along with the parameters.
Minimum 200 numbers of events (occurrences & restoration with date &
time) should be available in the meter memory.
Each control and relay panel shall be provided with necessary arrangements for
receiving, distributing and isolating of A.C and D.C supplies for control, signaling,
lighting and heating purposes. The incoming and sub-circuits shall be separately
provided with switch fuse units/MCBs. Fuses provided in the potential circuits
shall protect metering.
61
Spec. No. CED/CSR/E.665/18-19
All fuses shall be of HRC cartridge type confirming to IS2203 mounted on the
plug in type fuse base. Fuses shall have fusing indication and the fuse base shall
have imprints of fuse rating and voltage. All fuses and links shall be mounted
with sufficient space between each row of fuses and rows upper or below and
should have a minimum of 2 cms space between live terminal of the fuse/links
and metal parts.
Separate fuse control shall be given for close, trip and indication in DC Circuit and
for spring charging motor, annunciation and heater for A.C. Only Universal AC
spring charge motor shall be accepted. DC motor with rectifiers will be summarily
rejected.
10. 10. Panel Wirings:
The wiring should be as per IS 5578/1984 and amendments thereof. The wiring
shall be of high standard and should be able to withstand the tropical weather
conditions. All wiring shall be provided with 1100 volt Grade single core
multistranded copper conductor wires with P.V.C insulation and shall be flame
retardant low smoke type. The minimum size of the stranded copper wire shall
be 1.5 Sq.mm
The wiring shall be carried out using 4.0 Sq.mm. PVC insulated multi-strand FRLS
copper wire of 1100V Grade for entire CT circuits, 2.5 Sq.mm. PVC insulated
multi-strand FRLS copper wire of 1100V Grade for entire PT circuits, AC Power &
DC Control. Suitable coloured wires shall be used for phase identification and
interlocking type ferrules shall be provided at both ends of the wires for wire
identification. Terminal should be suitably protected to eliminate sulphating.
Connections and terminal should be able to withstand vibrations. The terminal
blocks should be stud type with suitable spring washer and lock nuts. The studs
shall be minimum 4 mm dia and made up of brass.
Flexible wires shall be used for wiring of devices on moving parts such as
swinging panels or panel doors. Panel wiring shall be securely supported, neatly
arranged readily accessible and connected to equipment terminals, terminal
blocks and wiring gutters. The cables shall be uniformly bunched and tied by
means of PVC belts and carried in a PVC carrying trough.
All front and internally mounted items including MCBs shall be provided with
individual identification labels. Labels shall be mounted directly below the
respective equipment.
24 Pin type socket shall be given in all the breakers irrespective of the type of
breaker with identical type of wiring for the purpose of interchangeability.
62
Spec. No. CED/CSR/E.665/18-19
The position of PVC carrying trough and wires should not give any hindrance for
fixing or removing relay casing, switches etc., Wire termination shall be made
with solder less crimping type of tinned copper lugs. Core identification plastic
ferrules marked to correspond with panel wiring diagram shall be fitted with both
ends of each wire. Ferrules shall fit tightly on the wire when disconnected. The
wire number shown on the wiring shall be in accordance with the IS.375.
All wires directly connected to trip circuits of breaker or devices shall be
distinguished by addition of a red color unlettered ferrule. Inter-connections to
adjacent panels shall be brought out to a separate set of Terminal blocks located
near the slots or holes to be provided at the top portion of the panel.
Arrangements shall be made for easy connections to adjacent panels at site and
wires for this purpose shall be provided and bunched inside the panel. The bus
wire shall run at the top of the panel. Terminal block with isolating links should
be provided for bus wire. Bus wire for voltage from the bus PT shall be provided
with wiring diagram. At least 20% of total terminals shall be provided as spare
for further connections. Wiring shall be done for all the contacts available in the
relay and other equipment and brought out to the terminal blocks for spare
contacts. Color code for wiring is preferable in the following colours.
PT supply Red, Yellow, Blue for phase and Black for neutral
CT circuits Similar to the above
DC circuits Grey for both positive and negative
250V AC circuits Black for both phase and neutral
Earthing Green
The terminal shall hold the wires in the tight position by bolts and nuts with lock
washers. The terminal blocks shall be arranged in vertical formation at an inclined
angle with sufficient space between terminal blocks for easy wiring. The lowest
terminal shall be atleast 450 mm above ground level. Steel plate shall be
provided 150 mm below the lowest terminal block to fix the cable glands.
In all the breakers, the reset push button shall be provided and the annunciation
shall be extended from the common alarm.
63
Spec. No. CED/CSR/E.665/18-19
Cable pan shall have suitable MS channel for cable clamping arrangement for all
Feeders and Transformer panels. Cable Termination should be provided with
support Insulators.
Each feeder panel shall be supplied with 1 No. termination kit suitable for 11 KV
3x300 sq.mm XLPE Aluminium cable. Each transformer panel shall be supplied
with 12 Nos. termination kits suitable for 11 KV 1x630 sq.mm XLPE Aluminium
cable.
10.12. Heaters:
There shall be 3 push buttons with one lamp to test the healthiness. Wiring shall
be separate. No looping is permitted.
10.13. Earthing:
All panels shall be equipped with an earth bus securely fixed along the base of
the panels. When several panels are mounted adjoining to each other, the earth
bus shall be made continuous and necessary connectors and clamps for this
purpose shall be included in the scope of supply. The size of the earth bus shall
be of 25mm x 6mm tinned copper flat. Individual earthing may be 25 mm X 3
mm tinned copper flat. Provision shall be made on end panels for connecting the
earth bus to the earth grid. Necessary terminal clamps and connectors shall be
included in the scope of supply. All metallic cases of the relays, instruments and
other panel mounted equipment’s shall be connected to the earth bus by
independent copper wires of size not less than 4.0 sq.mm.
The color code of earth wire shall be green. Earth wires shall be connected on
the terminals with suitable clamp connectors and soldering shall not be
permitted.
64
Spec. No. CED/CSR/E.665/18-19
10.14. Labels:
All fronts mounted equipment as well as equipment mounted inside the panels
shall be provided with individual labels with equipment designation engraved.
Labels shall be made of non-rusting metal or 3 ply lanced. Labels shall have
white letters on black or dark batch ground. The size of the labels shall be
width- 1.5 cms and length - as per the length of the inscription and the letter size
shall be 0.75 cm.
11.0. TESTS:
11.1. Acceptance and Routine Tests:
All acceptance and routine tests as stipulated in the latest IEC- shall be carried
out by the supplier in the presence of purchaser’s representative. Only on getting
the inspection report to the effect that the inspection was carried out
satisfactorily, dispatch clearance shall be issued. The supplier shall give minimum
10 days advance intimation to the PURCHASER to enable them to depute their
representatives for witnessing the tests. All assistance shall be given to the
inspection team to carry out the inspection.
65
Spec. No. CED/CSR/E.665/18-19
unless the material has been satisfactorily inspected and tested /unless the same
is waived by the purchaser in writing.
13.0. DOCUMENTATION:
The tenderer shall invariably furnish following information alongwith his offer,
failing which his offer shall be liable for rejection. Information shall be separately
given for individual type and current rating of circuit breaker/CTs/ PTs/Panel
mounting & accessories.
a. Vacuum Interrupter.
b. Insulators
c. Bus Bar Material
d. Instrument transformers.
e. Terminal connectors
iii. List of areas in manufacturing process, where stage inspection are normally
carried out by the tenderer for quality control and details of such tests and
inspections.
iv. List of testing equipment available with the tenderer for final testing of
breakers visa-vis the type, special, acceptance and routine tests specified herein.
The limitations in testing facilities shall be very clearly brought out in Schedule-E
i.e. schedule of deviation from specified test requirements.
The successful tenderer shall submit the routine test certificates of bought
out accessories at the time of routine testing of the fully assembled breaker for
the goods manufactured within purchaser's country. The supplier shall also
submit the central excise passes for the raw material at the time of routine
testing of the fully assembled breaker.
Following Type tests as per latest IEC must have been performed and the
certified copies of test reports shall be enclosed along with technical bid. All the
tests should have been conducted within five years from the date of opening of
technical bid.
66
Spec. No. CED/CSR/E.665/18-19
i) Instruction manuals
ii) Catalogues of spares recommended with drawing to indicate each item
iii) List of spares and special tools recommended by the supplier.
iv) Type Test Certificates as per ISS
67
Spec. No. CED/CSR/E.665/18-19
The spares for the breakers ordered under scope of the contract should
also be supplied along with the initial supply of breakers. It should be noted that
if the above conditions are not fulfilled, the payment will not be released.
All the materials shall be of the best class and capable of satisfactory
operation in the tropics with humid atmosphere conditions. Unless otherwise
specified, they shall conform to the requirements of the appropriate ISS/IEC.
The workmanship shall be of the best grade and the entire construction in
accordance with the best modern practice.
68
Spec. No. CED/CSR/E.665/18-19
All the equipments should operate without undue vibration and with the
least practicable amount of noise.
69
Spec. No. CED/CSR/E.665/18-19
SCHEDULE-A
PRICE SCHEDULE
Quantity tendered:
Name of Material Quantity Ex- Freight & Packing & GST All
offered works Insurance Forwarding amount inclusive
in Nos. price charges charges and price
per
per No. per No. percentage per No.
Rs.p No.
Rs.p Rs.p Rs.p Rs.p Rs.p
11 KV,1250 A,
25 KA Indoor
Vacuum Circuit
Breaker suitable
for feeder.
SPECIAL NOTE: The bidders are requested to quote the rates as per
BOQ .
70
Spec. No. CED/CSR/E.665/18-19
SCHEDULE – B1
DEVIATION FROM TECHNICAL SPECIFICATION
All technical deviations from the specification shall be filled in by the Tenderer,
Clause by clause, in the Schedule.
The Tenderer hereby certifies that the above mentioned are the only
deviations from the TECHNICAL Specification and the tender confirms
to the specification in all other respects.
DESIGNATION :
COMPANY :
DATE :
71
Spec. No. CED/CSR/E.665/18-19
SCHEDULE – B2
DEVIATION FROM COMMERCIAL TERMS
All deviations from the commercial terms shall be filled in by the Tenderer, Clause
by clause, in the Schedule.
The Tenderer hereby certifies that the above mentioned are the only
deviations from the Commercial terms of the Specification.
DESIGNATION :
COMPANY :
DATE :
72
Spec. No. CED/CSR/E.665/18-19
SCHEDULE-C
Sl Name & Address of Name of the P.O. No. Qty. Value of Scheduled Actual
No. the Organisation material & Date In order in Date of Date of
Nos Rs. completion completion
Lakhs of order of order
1 2 3 4 5 6 7 8
DESIGNATION :
COMPANY :
DATE :
73
Spec. No. CED/CSR/E.665/18-19
SCHEDULE - D
DECLARATION FORM
Dear Sir,
Having examined the above specification together with the accompanying
schedules etc., we hereby offer to manufacture and supply the equipments/
materials covered in this Specification at the rates entered in the attached schedule
of prices.
PLACE : SIGNATURE :
DATE : DESIGNATION :
COMPANY SEAL : COMPANY :
74
Spec. No. CED/CSR/E.665/18-19
SCHEDULE - E
GUARANTEED TECHNICAL PARTICULARS.
offered by
Sl.No Description
tenderer
Manufacturer’s Name and Country of
1
origin (*)
2 Manufacturer’s Design / type Ref
3 Frequency
4 Rated Voltage
5 Highest system voltage
6 Rated current
Short Circuit current rating with
7
duration
Certificate or report of short circuit type
8
test
9 Rated operating duty cycle
10 Short Circuit Breaking Current :
(a) Symmetrical
(b) Symmetrical at rated voltage
(c) Asymmetrical at rated voltage
(i) Per Phase
(ii) Average
(iii) D.C. Component
Arcing time (at rated breaking current)
11
in ms.
12 Opening time
13 Total break time in milli sec.
(a) At 10% rated interrupting capacity
14 Breaking Current
(a) Rated out of phase current
(b) Rated cable charging current
(c) Rated kilometric fault level
(d) Rated capacitor breaking current
75
Spec. No. CED/CSR/E.665/18-19
76
Spec. No. CED/CSR/E.665/18-19
77
Spec. No. CED/CSR/E.665/18-19
3 Applicable Standards
4 Type
7 Rated frequency
8 Transformation ratios
9 Number of cores
10 Rated output
11 Class of insulation
12 Class of accuracy
78
Spec. No. CED/CSR/E.665/18-19
PLACE : SIGNATURE :
DATE : DESIGNATION :
COMPANY SEAL : COMPANY
79
Spec. No. CED/CSR/E.665/18-19
3 Applicable Standards
4 Type
5 Ratio
8 Rated frequency
9 Class of accuracy
11 Burden
14 Class of insulation
15 Insulation level
80
Spec. No. CED/CSR/E.665/18-19
PLACE : SIGNATURE :
DATE : DESIGNATION :
COMPANY SEAL : COMPANY
81
Spec. No. CED/CSR/E.665/18-19
offered by
Sl.No Description
tenderer
Manufacturer’s Name and Country of
1
origin (*)
2 Manufacturer’s design Ref / Type
3 Applicable Standards
(a)Over current
IDMTL
Instantaneous
IDMTL
Instantaneous
82
Spec. No. CED/CSR/E.665/18-19
18 Types of case
19 Reset time
20 Burden of relay
Maximum and Minimum operating
21
ambient air temperature
Whether technical literature pamphlets
22
offered. for the Relay
PLACE : SIGNATURE :
DATE : DESIGNATION :
COMPANY SEAL : COMPANY
83
Spec. No. CED/CSR/E.665/18-19
SCHEDULE-F
QUESTIONNAIRE-A
INSTRUCTIONS:
(a) Strike off, whichever is not applicable.
(b) Separate sheets should be used, wherever necessary:
PLACE: NAME :
85
Spec. No. CED/CSR/E.665/18-19
5. Quantity offered.
86
Spec. No. CED/CSR/E.665/18-19
SCHEDULE-F
QUESTIONNAIRE-B
PLACE: NAME :
87
Spec. No. CED/CSR/E.665/18-19
SCHEDULE – G
STATEMENT OF TYPE TEST PARTICULARS
(To be filled in by the Tenderer)
Sl.
Name of Test Name of Lab Date of Test
No.
01. Short time current withstand
test and peak current withstand
test.
02. Lightning Impulse voltage with-
stand test
03. Short Circuit current making and
breaking tests
04. Power frequency voltage
withstand test (dry)
05. Temperature rise test for 2500A
06. Mechanical Endurance Test
confirming to class M2 of IEC /
62271 – 100
07. Capacitive current switching test
confirming to class C2 of IEC
62271-100
08. Measurement of the resistance
of the main circuit.
09 Internal arc fault withstand test
on cable, main bus and breaker
chambers.
Yours faithfully,
COMPANY :
DATE :
NOTE :
The type test certificates for the above type tests should have been
conducted in a Government/Government recognized Laboratory or NABL accredited
Laboratory and dated within five (5) years as on the date of Tender Opening as
per latest IEC.
88
Spec. No. CED/CSR/E.665/18-19
ANNEXURE-I
(To be furnished in non-judicial stamp paper of value not less than Rs.80/-)
(1) Withdrawing his tender before the expiry of the validity period, OR
(3) Violating any of the conditions of the tender issued by the competent
authority;
89
Spec. No. CED/CSR/E.665/18-19
(i) Withdrawing his tender before the expiry of the validity period.
(iii) Violating any of the conditions of the tender issued by the competent authority.
NOW THE CONDITION OF THE above written undertaking is such that if the
tenderer shall duly and faithfully observe and perform the conditions specified as
above, then the above written undertaking shall be void, otherwise it shall remain
in full force.
The tenderer undertakes not to revoke this guarantee till the contract is completed
under the terms of contract.
The expression, `tenderer’ and the ` TANGEDCO’ hereinafter before used shall
include their respective successors and assign in office.
SIGNATURE
1. Signature
90
Spec. No. CED/CSR/E.665/18-19
ANNEXURE –II
UNDERTAKING TOWARDS JURISDICTION OF LEGAL PROCEEDINGS
....................................
This undertaking executed at ......on this
(Date).........
.............................. ..................
................. ......... (Month) Two Thousand
and seventeen by M/s.
............................................. Registered under Companies Act, 1956
having its registered office at
.......................................... hereinafter called the contractor
(which expression shall where the context so admits mean and include its successors in
office and assigns) with the TANGEDCO a statutory authority, a body corporate constituted
as per provision of G.O.MS.No.100, dt.9.10.2010, having its registered Office at No.144,
Anna Salai, NPKRR Maaligai, Chennai - 600 002 herein after called the purchaser (Which
expression shall where the context so admits means and includes its successors in Office
and assigns.)
WHEREAS the contract is for the supply of ............................of terms of the Rate
Contract Order No......... dated ....................................
ofthe above said P.O. certain
AND WHEREAS in accordance with Clause .............. terms
were stipulated for the above supply.
AND WHEREAS in accordance with Clause........ of the above mentioned Rate Contract
Order the contractor has to furnish an undertaking that no suit or any proceedings in
regard to any matter arising in any respect under this contract shall be instituted in any
court other than in the High Court, Chennai City Civil Court of Chennai or other Court of
small causes at Chennai, as the case may be.
91
Spec. No. CED/CSR/E.665/18-19
ANNEXURE - III
CERTIFICATE
To
(Name and address of the
selling Dealer)
…………………………………………………….
……………………………………………………..
TNGST NO.
(Rupees only).
Place : Date :
(SIGNATURE)
Name :
Status :
Seal of Office :
92
Spec. No. CED/CSR/E.665/18-19
ANNEXURE IV
DECLARATION FORM
To,
----------------------------------
Dear Sir,
1. I/We have downloaded / obtained the tender document(s) for the above
mentioned ‘Tender/Work’ from the web site(s) namely:
---------------------------------------------------------------------------------------------------
2. I/We hereby certify that I/We have read the entire terms and conditions
of the tender documents from page No.------ to --------(including all documents like
annexure(s), schedule(s), etc.,) which form part of the contract agreement and
I/We shall abide hereby the terms / conditions / clauses contained therein.
5. In case any provisions of this tender are found violated, then your
department/organization shall without prejudice to any other right or remedy be at
liberty to reject this tender/bid including the forfeiture of the full said earnest money
deposit absolutely.
Yours Faithfully,