The document contains calculations to determine short circuit fault currents at different points in an electrical system for a printing press. It first calculates the short circuit current from the transformer primary to be 39,550 amps. It then calculates the fault current from the transformer to a downstream point to be 34,357 amps, taking into account cable impedance factors. Finally, it calculates the fault current from that point to another point further downstream to be 20,991 amps, and notes a motor adds an additional 3,464 amps of current.
The document contains calculations to determine short circuit fault currents at different points in an electrical system for a printing press. It first calculates the short circuit current from the transformer primary to be 39,550 amps. It then calculates the fault current from the transformer to a downstream point to be 34,357 amps, taking into account cable impedance factors. Finally, it calculates the fault current from that point to another point further downstream to be 20,991 amps, and notes a motor adds an additional 3,464 amps of current.
The document contains calculations to determine short circuit fault currents at different points in an electrical system for a printing press. It first calculates the short circuit current from the transformer primary to be 39,550 amps. It then calculates the fault current from the transformer to a downstream point to be 34,357 amps, taking into account cable impedance factors. Finally, it calculates the fault current from that point to another point further downstream to be 20,991 amps, and notes a motor adds an additional 3,464 amps of current.
Short Circuit Current Calculation : Kilo-10, Printing Press
3-phase Transformer Fault Current
Primary Fault (Isca(P)) in kA *if unknown = "x" x
Primary Voltage (V) 13800 Trans. Size (kVA) 1500 Impedance (%Z) 6.00 Secondary Voltage (V) 400.00 I = kVA x 1000 = Trans. FLA IS (Current) (A) 2,165 V x 1.732 Isca(s) = trans. FLA x 100 Isca(s) (A) 39,550 transformer Z *Isca = ampere short-circuit current RMS symmetrical kA
Fault Current from Transformer to Point
Primary Fault (Isca(P)) in kA *if unknown = "x" x Primary Voltage (kV) 13800 Trans. Size (kVA) 1500 Impedance (%Z) 6 Secondary Voltage (V) 400 Fault Transformer Isca (A) 36,085 Sizing Standard Metric Voltage (V) 400 Single or Multi-Wire ? 3 Conductor Cable Phase Conductor Wire Size # Conductors per 300 mm2 8 (mm2 or AWG/kcmil) phase (n) Length - L (ft or m) 80 Conductor Type Copper Cable Voltage Rating (V) 600 Conduit Type Non-Magnetic C Value (Metric) 9296 M = 1 / (1 + f) C Value (AWG) N/A 3 phase faults f = 1.73 x L x IL-L-L f Factor 0.1681 VL-L x C x n M Factor 0.8561 1 phase faults f = 2 x L x IL-L VL-L x C x n Isca x M = fault current L-L = 34,357
Calculation does not include motor contribution
Fault Current from Point-to-Point
Isca at Fault #1 (A) 34,357 Sizing Standard Metric
Fault #1 Voltage (V) 400 Single or Multi-Wire ? 3 Conductor Cable Phase Conductor Wire Size # Conductors per 300 mm2 1 (mm2 or AWG/kcmil) phase (n) Length - L (ft or m) 60 Conductor Type Copper Cable Voltage Rating (V) 600 Conduit Type Non-Magnetic C Value (Metric) 9296 Fault #2 C Value (AWG) N/A f Factor 0.9602 M Factor 0.5101 Branch Circuit Panel
Isca x M = fault current L-L = Isca at Fault #2 (A) 20,991
Calculation does not include motor contribution
Fault Current Contribution from Motor
Total Motor HP 600 Motor Voltage (V) 400 Motor Contribution Isca (A) 3464