Sei sulla pagina 1di 1

NOTES

B C LEGEND: STRUCTURAL MEMBERS SCHEDULE LOADS (uls)


MVR
A B C A B C Existing wall
STEEL BEAMS kNm kN kN
1. THIS DRAWING IS TO BE READ IN CONJUNCTION
01 01 01
Existing loadbearing stud wall
Provide 9mm OSB/3 sheathing
B1 EXISTING MEMBER TO REMAIN 15 15 20 WITH THE ARCHITECTS DRAWINGS AND THE
both sides B2 EXISTING MEMBER TO REMAIN 30 55 55 PROJECT SPECIFICATION. DO NOT SCALE OFF THE
B2a 152x89x16 UB 10 10 10
New wall
B3 EXISTING MEMBER TO REMAIN 95 60 65
DRAWING.
New loadbearing stud wall B4 2No. 75x275dp C24 timber joists 5 10 10 2. ALL DIMENSIONS AND LEVELS TO BE CHECKED BY

A
New 20N/mm² masonry brick wall
B5 2No. 75x275dp C24 timber joists 15 15 15 THE BUILDER BEFORE ORDERING ANY STEELWORK.
B6 150x90x24 PFC (shape to suit) 15 20 20
02 02 02 Demolition B7 150x90x24 PFC 10 20 20
3. ALL STEELWORK IS TO BE GRADE S275, SHOT
B8 152x152x30 UC 40 45 45 BLASTED AND PAINTED WITH 2 COATS OF ZINC
Walls under
B9 152x152x30 UC 35 30 35 PHOSPHATE PRIMER OR RED OXIDE PRIMER
B10 200x100x8 RHS laid flat + bottom plate 20 25 25
New ceiling joists CJ1 above
All Ceiling joists CJ1 TBC on site B11 300x100x10 RHS laid flat + bottom plate 25 30 30 UNLESS NOTED ON DRAWING AS GALVANISED, OR
B12 FLITCH BEAM- 2No. 60x225dp C24 timber joists 20 20 40 CONCRETE CASED. ALL BOLTS ARE TO BE GRADE
Existing structure to remain + 1No. 10thk M.S plate bolted together using M12
bolts @400c/c
8.8. ALL FABRICATION IS TO BE DONE IN
Reinforced Existing structure
03 03 03 B13 203 x 203 x 86 UC + end plate 160 200 200 ACCORDANCE WITH BS5950.
New structural member B13a 203x133x30UB + end plate 55 100 100
B14 254x254x73 UC - splice connection 150 65 65
4. ALL NEW TIMBER IS TO BE C24 GRADE (UNLESS
ExJ
04 04 04
Existing Floor / Roof Joists
B15 EXISTING MEMBER TO REMAIN 35 30 30 NOTED AS C16 ON THE DRAWING) AND TANALISED.
New Floor / Ceiling / Roof Joists B16 EXISTING MEMBER TO REMAIN 10 25 25 PAINT ALL CUT ENDS WITH TIMBER PRESERVATIVE,
Blocking up existing B17 203x102x23 UB 20 30 30
window opening using
All joist sizes noted on the drawings are to B18 203x203x86UC 195 165 165
ON SITE. PLYWOOD MUST COMPLY WITH EN636,
B

B
matching bricks
be a minimum as specified on the B19 254x254x73 UC 180 100 140 CLASS 3.
L2 drawings, if the existing is less than shown
on the drawings they must be replaced to
B20 203x203x60 UC + 15thk bottom plate 35 40 40 5. ALL BRICKWORK TO BE 20.5 N/mm² IN 1:1:6 MORTAR.
05 05 suit the specified size B21 FLITCH BEAM- 2No. 70x200dp C24 timber joists 6. ALL CONCRETE (EXCEPT BLINDING CONCRETE) IS
+ 1No. 12thk M.S plate bolted together using M12 20 25 25
All studwalls parallel to the floor joists to TO BE MINIMUM 30 N/mm2 WITH 20 DIAMETER

50x200dp @350c/c
For joists support refer B21 bolts @400c/c
Joists arrangement to to drawing 2081-07 be supported using double up joists
u/s of Mezzanine Unit FR1 150x175 C24 Timber Posts + 150x225dp C24 AGGREGATE AND IS TO BE MECHANICALLY
34 tbc on site. Timber Beam as Timber Frame
PROVIDE FULL LENGTH BEARING ON
ALL PADSTONES FR2 2No.50x100 C16 + Ex. 80x100+Ex 80x100
VIBRATED, WHEN PLACED. ALL CONCRETE WORK
EXJ / 60x275dp
@350c/c
Timber Post + 2No. 80x100dp C16 Timber Header MUST COMPLY WITH BS 8110.
06 06 Contractor to check the existing timber COLUMNS
floor masonry supports 7. BEAMS SUPPORTING CAVITY WALLS TO HAVE 15THK
Provide min 100mm UNIT 34 C1 80x80x5 SHS + top and bottom plates
UNIT 34 bearing each end of C2 203x102x23 UB + top and bottom plate MM PLATE WELDED TO TOP, TO WIDTH OF WALL
B8 P1 B5 Contractor to provide lateral stability in
P1
Beam B2A Accordance with Approved Document A of C3 200x120x10 RHS + top and bottom plates 8. ALL EXTERNAL WALLS TO HAVE WALL STRAPS AT
Building Regulations. C4 80x80x5 SHS + top and bottom plates
New stairs
CJ1
Lateral restraint straps required to walls
2.0m c/c's HORIZONTALLY AND VERTICALY FOR THE
above C5 3No.72 x100 C24 studs

B4
up
by others FJ2 parallel to joists and timber roof spans. ROOF.

B6
EXJ / 60x275dp C6 4No.72 x100 C24 studs or 300x100x10 RHS

FJ4
Straps to be at maximum 1.2m c/c apart
@350c/c 9. TIMBER JOISTS WITH A SPAN OVER 2.5m TO HAVE

B7
and fixed to minimum of 3 No. joists. All C7 100 x100 C24 timber stud
07 07 07

FJ2
straps installed to BS5268 & BS8103. LINTELS ONE ROW OF NOGGINS AT THIRD SPAN. TIMBER
L1 2No. 50x200dp C24 timber joists, bolted
C1 Where Architects indicated storage area together using M12 bolts @400c/c NOGGINS CAN BE REPLACED WITH HERRINGBONE
below above, use CJ1 for 1.8m max span
P1 B9 C1 P1
New ceiling up P1
L2 CX 90/100 Catnic Lintel STRUTTING
joists CJ1 B2A L3 3No. 50x200dp C24 timber joists, bolted
above
**ALL EXISTING STRUCTURAL
MEMBERS TO REMAIN IF MEET THE together using M12 bolts @400c/c 10.ALL JOISTS ON WALLS TO BE CROSS NAILED
08 08 08 **B2
CRITERIA OF MINIMUM STRUCTURAL L4 100w x 140dp Precast Concrete Lintel 11.ALL STUDWALLS PARALLEL TO THE FLOOR JOISTS
C7 L1 (over) MEMBER SIZE REQUIRED SHOWN ON

(under)
C7 2No. 50x200dp C24 timber joists, bolted
L5 TO BE SUPPORTED USING DOUBLE JOISTS BOLTED
B

B
L1
under STRUCTURAL MEMBERS SCHEDULE. together using M12 bolts @400c/c
ALL EXISTING STRUCTURAL MEMBERS
TO BE REINFORCED OR REPLACED TO L6 2No. 100w x 140dp Prestressed Concrete Lintels TOGETHER USING M12 BOLTS WITH 50x50mm
C7
MEET THE REQUIRED STRUCTURAL L7 2No. 100w x 290dp Prestressed Concrete Lintels WASHERS @500mm c/c
UNIT 23 CJ1 MEMBER SIZE. L8 2No. 100w x 290dp Prestressed Concrete Lintels
12.ALL BEAMS TO BE LOADED CENTRALLY ON
Second Floor
Existing stud wall to remain

Existing stud wall and flitch


above L9 2No.50x100dp C24 timber joists
Mezzanine Plan Lintel L1
LINTELS
PADSTONES PADSTONES. BEAMS TO EXTEND TO END OF

beam under to remain


· For spans greater than 1200mm,
Scale 1:50 2No.50x200dp on UNIT 33 lintels should be adequately propped P1 440 x100wd x150dp Concrete Padstone PADSTONE.
100x100 C24 Timber
during construction at a maximum of P2 215 x215wd x150dp Concrete Padstone
CJ1 Post (C7 below) 1200mm centres. Props should not be
13.THE CONTRACTOR MUST PROVIDE FULL DETAILS OF

B1
above P3 750 x100wd x 215dp Concrete Padstone
CJ1 removed until the mortar has matured.
P4 440x 215wd x 150dp Concrete Padstone THEIR PROPOSED TEMPORARY WORKS, BEFORE
above · Lintel should be bedded on a level full
mortar bed each end. Min end bearing P5 660 x100wd x 150dp Concrete Padstone COMMENCING THE STRUCTURAL WORKS.
150mm P6 440 x215wd x 215dp Concrete Padstone
LBW1 LBW1 · No rebate must be formed/cut into A P7 450 x100wd x 150dp Concrete Padstone
09 09 PRESTRESSED lintels, or holes drilled
P8 960 x100wd x 215dp Concrete Padstone
for chemical anchors. Plugging and
CJ1 drilling is acceptable providing that the P9 880 x100wd x 215dp Concrete Padstone
above location of prestressing tendons is not P10 660x 215wd x 215dp Concrete Padstone
compromised. P11 330 x100wd x 150dp Concrete Padstone
CJ1 B3
10 above 10 FLOOR JOISTS
CJ1 ALL STEEL CONNECTIONS ARE TO BE
above FJ1 2No. 50x100dp C24 timber joists @250c/c 555
CJ1 DESIGNED BY SPECIALIST
above MANUFACTURER USING SPECIFIED FJ2 50x150dp C24 timber joists @400c/c 555
FACTORED LOADS (ULS) SHOWN ON FJ3 50x175dp C24 timber joists @400c/c 5 10 10
STRUCTURAL MEMBERS SCHEDULE CJ1/FJ4 50x100dp C24 timber joists @400c/c 111
Existing stud
LOADBEARING WALLS
wall to remain All Timber to timber connection are to
IMPERIUM ENGINEERING LIMITED
CJ1 LBW1 72x100 C24 timber studs @400c/c +OSB / 3
be on joist hangers. 20-22 Wenlock Road
above sheathing both sides
UNIT 22 UNIT 21 N1 7GU, London info@imperiumengineering.co.uk
EXJ / 60x275dp

Contractor to provide adequate joist


11 11 hangers using specified loads
LBW2 72x100 C24 timber studs @400c/c +OSB / 3 Tel. 020 3441 7606 www.imperiumengineering.co.uk

(factored) shown on Structural Members sheathing both sides


@350c/c

Schedule. If unsure, contact Structural ROOF BEAMS DRAWING TITLE:


EXJ / 75x280dp Engineer RB1 203x203x46 UC - splice connection 70 65 65
@350c/c *Contractor to use slope adjustable joist 25 30 30
hangers where required (Roof level)
RB2 203x102x23 UB PROPOSED STRUCTURAL
RB3 203x102x23 UB 20 25 25
RB4 254x254x73 UC - splice connection 160 65 105
SECOND FLOOR, SECOND FLOOR
When demolition, all walls to be made
good using matching bricks fully toothed RB5 254x254x73 UC - splice connection 160 65 105 MEZZANINE AND THIRD FLOOR PLAN
UNIT 32 UNIT 31 and bonded into existing RB6 203x203x46 UC - splice connection 60 35 35
RB7 203x203x46 UB under balustrade-spliced 40 30 30
· All Structural Elements to be measured
connection PROJECT:
on site prior to ordering. Imperium
Engineering is NOT responsible for beam FLAT ROOF JOISTS
12 12 length measurements RJ1 44x240dp C24 timber joists @400c/c 555
· Any alterations or amendments to be
ROOF TRIMMERS
approved in writing by Structural
Engineer prior to carrying out on site. TR1 2No. 44x240dp C24 timber joists bolted 555
· Imperium Engineering to be notified if together using M12 bolts @400c/c
joist spans and sizes noted on the GA TR2 3No. 44x240dp C24 timber joists bolted 10 10 10
drawing are any different prior to ordering together using M12 bolts @400c/c
of Steel Beams.
· All padstones on party walls are 100mm TR3 2No. 44x240dp C24 timber joists bolted 555 CLIENT:
wide. Contractor to inform Imperium together using M12 bolts @400c/c
Engineering if different. TR4 FLITCH BEAM- 2No. 75x280dp C24 timber joists 5 10 10
13 13 · All workmanship and materials to be in
+ 15thk M.S plate bolted together using M12
accordance with all current relevant
bolts @400c/c
Codes of Practice, British Standards and
Current CDM Regulations TR5 FLITCH BEAM- 2No. 75x280dp C24 timber joists 40 30 35
· Structural Elements to be installed in + 15thk M.S plate bolted together using M12 bolts
accordance with current CDM @400c/c
Regulations
TR6 3No. 44x240dp C24 timber joists bolted 10 15 15
together using M12 bolts @400c/c
All existing foundations are to be agreed
with Building Control. Contractor / TR7 3No. 44x240dp C24 timber joists bolted 5 15 15
Building Control to confirm capacity of together using M12 bolts @400c/c
existing foundation. If found inadequate
or unsure, contact Structural Engineer Loads (shown on Structural Member Schedule):
M - indicate max Moment (kNm)
V- indicate max Shear (kN)
14 14 R- indicate max Reaction (kN)
NOTE: Loads given in the Structural Members Schedule are to the
SITE BOUNDARY

SITE BOUNDARY

SITE BOUNDARY

SITE BOUNDARY
A

nearest value of 5. Please refer to Structural Calculation Pack if unsure.


Temporary Works Notes:
N° 73
N° 73

N° 69
N° 69

It is the responsibility of the main contractor to consider the need for temporary works - props, shores, bracing, needles
A B C A B C etc - to provide suitable temporary works where required;
Second Floor Plan Third Floor Plan Maintain the integrity of the existing structure and temporary support throughout the duration of the project and appoint
Scale 1:50 Scale 1:50 a temporary works Engineer if deemed necessary.

Potrebbero piacerti anche