Sei sulla pagina 1di 1

A

ACOUSTIC DOWNDUCT
CALCULATION SHEET

JOB NAME: JOB. NO.


BY: PAGE NO. 1 OF 1
SYSTEM: DATE 6/23/2019
Link to MDA Down Duct Manual

FAN DETAILS Room/Area Served


FAN DUTY SWL 63 125 250 500 1K 2K 4K 8K
Spectrum
DUCT ATTENUATION Length (m)

End Reflection Loss


SOUND POWER LEAVING 0 0 0 0 0 0 0 0
Sound Power to Room % 0 0 0 0 0 0 0 0
Room Size m3 0 0 0 0 0 0 0 0
Reverberation Time secs 0 0 0 0 0 0 0 0
Number of Systems.
REVERBERANT SPL 0 0 0 0 0 0 0 0
Sound Power to Outlet % 0 0 0 0 0 0 0 0
Distance to Listener m 0 0 0 0 0 0 0 0
Directivity Factor m2
DIRECT SPL 0 0 0 0 0 0 0 0
RESULTANT SPL 3 3 3 3 3 3 3 3
dBA Correction
PNC Level 0
Required PNC Level PNC40
7 59 54 50 45 40 36 33 33
Attenuation Required
80
PNC65 76 73 70 67 64 61 58 58
PNC60 73 69 66 63 59 56 53 53
70
PNC55 70 66 62 59 55 51 48 48
60 PNC50 66 62 58 54 50 46 43 43
PNC45 63 58 54 50 45 41 38 38
50 PNC43 61.4 56.4 52.4 48 43 39 36 36
PNC40 59 54 50 45 40 36 33 33
40
PNC38 57.4 52.4 48 43 38 33.6 31 31
PNC37 56.6 51.6 47 42 37 32.4 30 30
30
PNC35 55 50 45 40 35 30 28 28
20 PNC32 53.2 47.6 42.6 37 32 27 25 25
PNC30 52 46 41 35 30 25 23 23
10 PNC25 49 43 37 31 25 20 18 18
PNC20 46 39 32 26 20 15 13 13
0
PNC15 43 35 28 21 15 10 8 8
63 125 250 500 1K 2K 4K 8K

Recommended maximum ductwork air velocities (m/s)


Main Main Branch Runout duct
Criteria riser duct duct Metal Flexible
PNC40 13 8.5 6.5 5 3.5

Downduct Revision 06/23/201908:31:04


425210658.xls