Cooling and Dehumidifying Heat Loa

Estmated By HENRY
Date MARCH 19,2017
Coustomer TONG LUNG
Location SUBIC
Room LINE 1
Classification PRODUCTION
Room Sensible Heat
Item Sun gain Factor
Solar gain glass
North 0.0 39 0.56
South 0.0 14 0.56
West 70.6 158 0.56
East 0.0 158 0.56
NW 0.0 148 0.56
NE 0.0 148 0.56
SW 0.0 66 0.56
SunSEGain 0.0 66 0.56
T19 pg 62, 60lb/sqft Wall Solar and trans gain-walls&roof
Factor
North 605.3 12.0 0.36
T21,22,23,24
South or 25 pp 66-69 0.0 26.0 0.36
UseWest
Hollow Block, 80lb, 8in thick 413.6 41.0 0.36
.24East
Btu/hr sqft degF Temp Dif 0.0 31.0 0.36
NW 0.0 32.0 0.36
NE 0.0 24.0 0.36
SW 0.0 36.0 0.36
SE 0.0 28.0 0.36
Roof -Sun 322.8 46.0 0.480
Roof -Sun-Insulated 42.0 0.20
Roof -Shaded 14.0 0.48
Transmission gain-except walls & roof
All glass 70.6 17.0 1.13
Partition 0.0 12.0 0.36
Ceiling 322.8 12.0 0.36
Floor 322.8 4.8 0.42
Infiltration 20.0 1.08
Internal Heat
People 48 230 1
Power
Lights 484 1 3.413
### Equipment 1.00 1 3413
### Additional Heat Gain, T54-57pg107-109
Room Sensible Heat-Sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Outdoor Air 726 17.0 1.08
EFFECTIVE ROOM SENSIBLE HEAT- Total
Room Latent Heat
Infiltration
People 48 190 1
Steam
Appliances
Additional Heat Gain
Vap.Trans 1,059 0.029
Sub-Total
Safety Factor, pg113 5%
Room Latent Heat
Duct leakage& R.A.Heat Regain + Safety
Outdoor Air 727 73.0 0.68
EFFECTIVE ROOM LATENT HEAT

EFFECTIVE ROOM TOTAL HEAT


OUTDOOR AIR HEAT
Cfm temp diff const
Sensible 726 17.0 1.08
hum diff const
Latent 726 73.0 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)

cfm
0.70

33
nd Dehumidifying Heat Load Estimate for GYMNASIUM IN PASIG
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 78.0
DIFFERENCE 17.0
JULY & MAY 10DEG
AHU Tag No GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH 605.3
SOUTH
- WEST 70.6 413.6
EAST
NW 0.0
NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 322.80 sft
&roof ROOF HEIGHT 10 ft
2,615 FALSE CEILING HT. 10 ft
- NO OF F.A.CHANGES 5 PER HR.
6,105 NO. OF PEOPLE 48 0.15
- Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
7,127 EQUIPMENT LOAD 100.0 KW
- DIVERSITY FACTOR 1.0
- SH PER PERSON 230 Btu/hr
lls & roof LH PER PERSON 190 Btu/hr
BPF 0.1
- CFM/PERSON 10
1,394 EXHAUST 0
657 FLOOR GAIN 0 (1 if fl. gain exists else 0)
- ROOF(0)/CEILING(1) 1
ROOF (1 if Roof provided Insulat
11,137 PARTITIONS (1 if Mod.Partitions exists
CEILING 323 (1 if Mod.Ceiling Panels ex
1,653 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists
3,413 ADP&SHR 0 (1 if ADP & SHR revised e
- Motor bkw IF ADP & SHR RE
34,101 SHR 0.70 REV. ESHR
10.0% 3,410 ADP 55.00 REV. ADP
0.10 1,333 TR 8.76 REV. TR
38,844 Dehumd. CFM 1738 REV. AIR QTY CFM
Reheat,KW N/A RE- HEAT IN KWTO INCREA
-
9,200 FRESH AIR REQUIREMENT
NOS CFM/PER
- PEOPLE 48
EXHAUST
2,242 NO. OF A/CHANGES 323
11,442 Ventilation cfm/ft2 323 0.10
572 TOTAL FRESH AIR
12,014 PRE-COOLING COIL
10% 1,201 DB 'F WB 'F
0.10 3,608 LEV. COND 56.0 55.9
16,824 INSIDE 69.0 58.9

55,668 DIFF. -13.0


T
1 - bf 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
0.90 12,001 Trm-( RSH/(1.08 x (De. CFM+CFMoa))
* If above is too high. Determine supply CFM
0.90 32,448 for desired dif. By supply air qty. formula
100,118 2. ENTERING DRY BULB TEMPERATURE
5% 5,006 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
N/A 3. ENTERING AIR MOISTURE CONTENT
105,123 (CFM oa*Woa+CFM ra*Wrm)/CFM da
10.95 9 4. LEAVING DRY BULB TEMPERATURE
0.70 ( Tadp + (BF(Tedb - T adp)))
55 5. SUPPLY AIR CFM
55 ( RSH/1.08 X (Trm-Tsa)
21 From psychrometric chart
1,738
# when bypassing a mixture of OA & RA use supply CFM, when
198.34 bypassing RA only, use deh. CFM
281.31
4
105.12
RH TH GR/LB DB 'F RH GR/LB
58% 138.0 95.0 58% 138.0
50% 65.0 77.0 50% 70.0
0.0 73.0 75 50 65
http://www.hvac-calculator.net/index.php?v=2
REAS (ft2) U' FACTORS
PARTNS WALL 0.360
GLASS 0.560
ALL GLASS 1.130
PARTITION 0.360
M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
0.0
The ADP Table
FOR 75.0 & 50%RH
SHR ADP
1 55.2 0.00
0.92 54 0.00
0.84 52 0.00
0.78 50 0.00
0.74 48 0.00
0.71 46 44.78
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00
UIREMENT
ACH NET (CFM)
15 726
-
-
1
727
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

63.41 0F
14.59

83.01 0F

149.92 Gr./lb

56.96 0F

2464.37 cfm

T ewb = F
0

T lwb = F
0

pply CFM, when


Cooling and Dehumidifying Heat Loa
Estmated By HENRY
Date MARCH 19,2017
Coustomer TONG LUNG
Location SUBIC
Room LINE 1
Classification PRODUCTION
Room Sensible Heat
Item Sun gain Factor
Solar gain glass
North 0.0 39 0.56
South 0.0 14 0.56
West 70.6 158 0.56
East 0.0 158 0.56
NW 0.0 148 0.56
NE 0.0 148 0.56
SW 0.0 66 0.56
SunSEGain 0.0 66 0.56
T19 pg 62, 60lb/sqft Wall Solar and trans gain-walls&roof
Factor
North 605.3 12.0 0.36
T21,22,23,24
South or 25 pp 66-69 0.0 26.0 0.36
UseWest
Hollow Block, 80lb, 8in thick 413.6 41.0 0.36
.24East
Btu/hr sqft degF Temp Dif 0.0 31.0 0.36
NW 0.0 32.0 0.36
NE 0.0 24.0 0.36
SW 0.0 36.0 0.36
SE 0.0 28.0 0.36
Roof -Sun 322.8 46.0 0.480
Roof -Sun-Insulated 42.0 0.20
Roof -Shaded 14.0 0.48
Transmission gain-except walls & roof
All glass 70.6 17.0 1.13
Partition 0.0 12.0 0.36
Ceiling 322.8 12.0 0.36
Floor 322.8 4.8 0.42
Infiltration 20.0 1.08
Internal Heat
People 48 230 1
Power
Lights 484 1 3.413
### Equipment 1.00 1 3413
### Additional Heat Gain, T54-57pg107-109
Room Sensible Heat-Sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Outdoor Air 726 17.0 1.08
EFFECTIVE ROOM SENSIBLE HEAT- Total
Room Latent Heat
Infiltration
People 48 190 1
Steam
Appliances
Additional Heat Gain
Vap.Trans 1,059 0.029
Sub-Total
Safety Factor, pg113 5%
Room Latent Heat
Duct leakage& R.A.Heat Regain + Safety
Outdoor Air 727 73.0 0.68
EFFECTIVE ROOM LATENT HEAT

EFFECTIVE ROOM TOTAL HEAT


OUTDOOR AIR HEAT
Cfm temp diff const
Sensible 726 17.0 1.08
hum diff const
Latent 726 73.0 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)

cfm
0.70

33
nd Dehumidifying Heat Load Estimate for GYMNASIUM IN PASIG
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 78.0
DIFFERENCE 17.0
JULY & MAY 10DEG
AHU Tag No GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH 605.3
SOUTH
- WEST 70.6 413.6
EAST
NW 0.0
NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 322.80 sft
&roof ROOF HEIGHT 10 ft
2,615 FALSE CEILING HT. 10 ft
- NO OF F.A.CHANGES 5 PER HR.
6,105 NO. OF PEOPLE 48 0.15
- Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
7,127 EQUIPMENT LOAD 100.0 KW
- DIVERSITY FACTOR 1.0
- SH PER PERSON 230 Btu/hr
lls & roof LH PER PERSON 190 Btu/hr
BPF 0.1
- CFM/PERSON 10
1,394 EXHAUST 0
657 FLOOR GAIN 0 (1 if fl. gain exists else 0)
- ROOF(0)/CEILING(1) 1
ROOF (1 if Roof provided Insulat
11,137 PARTITIONS (1 if Mod.Partitions exists
CEILING 323 (1 if Mod.Ceiling Panels ex
1,653 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists
3,413 ADP&SHR 0 (1 if ADP & SHR revised e
- Motor bkw IF ADP & SHR RE
34,101 SHR 0.70 REV. ESHR
10.0% 3,410 ADP 55.00 REV. ADP
0.10 1,333 TR 8.76 REV. TR
38,844 Dehumd. CFM 1738 REV. AIR QTY CFM
Reheat,KW N/A RE- HEAT IN KWTO INCREA
-
9,200 FRESH AIR REQUIREMENT
NOS CFM/PER
- PEOPLE 48
EXHAUST
2,242 NO. OF A/CHANGES 323
11,442 Ventilation cfm/ft2 323 0.10
572 TOTAL FRESH AIR
12,014 PRE-COOLING COIL
10% 1,201 DB 'F WB 'F
0.10 3,608 LEV. COND 56.0 55.9
16,824 INSIDE 69.0 58.9

55,668 DIFF. -13.0


T
1 - bf 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
0.90 12,001 Trm-( RSH/(1.08 x (De. CFM+CFMoa))
* If above is too high. Determine supply CFM
0.90 32,448 for desired dif. By supply air qty. formula
100,118 2. ENTERING DRY BULB TEMPERATURE
5% 5,006 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
N/A 3. ENTERING AIR MOISTURE CONTENT
105,123 (CFM oa*Woa+CFM ra*Wrm)/CFM da
10.95 9 4. LEAVING DRY BULB TEMPERATURE
0.70 ( Tadp + (BF(Tedb - T adp)))
55 5. SUPPLY AIR CFM
55 ( RSH/1.08 X (Trm-Tsa)
21 From psychrometric chart
1,738
# when bypassing a mixture of OA & RA use supply CFM, when
198.34 bypassing RA only, use deh. CFM
281.31
4
105.12
RH TH GR/LB DB 'F RH GR/LB
58% 138.0 95.0 58% 138.0
50% 65.0 77.0 50% 70.0
0.0 73.0 75 50 65
http://www.hvac-calculator.net/index.php?v=2
REAS (ft2) U' FACTORS
PARTNS WALL 0.360
GLASS 0.560
ALL GLASS 1.130
PARTITION 0.360
M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
0.0
The ADP Table
FOR 75.0 & 50%RH
SHR ADP
1 55.2 0.00
0.92 54 0.00
0.84 52 0.00
0.78 50 0.00
0.74 48 0.00
0.71 46 44.78
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00
UIREMENT
ACH NET (CFM)
15 726
-
-
1
727
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

63.41 0F
14.59

83.01 0F

149.92 Gr./lb

56.96 0F

2464.37 cfm

T ewb = F
0

T lwb = F
0

pply CFM, when


Cooling and Dehumidifying Heat Loa
Estmated By HENRY
Date MARCH 19,2017
Coustomer TONG LUNG
Location SUBIC
Room LINE 1
Classification PRODUCTION
Room Sensible Heat
Item Sun gain Factor
Solar gain glass
North 0.0 39 0.56
South 0.0 14 0.56
West 0.0 158 0.56
East 0.0 158 0.56
NW 0.0 148 0.56
NE 0.0 148 0.56
SW 0.0 66 0.56
SunSEGain 0.0 66 0.56
T19 pg 62, 60lb/sqft Wall Solar and trans gain-walls&roof
Factor
North 0.0 12.0 0.36
T21,22,23,24
South or 25 pp 66-69 0.0 26.0 0.36
UseWest
Hollow Block, 80lb, 8in thick 0.0 41.0 0.36
.24East
Btu/hr sqft degF Temp Dif 0.0 31.0 0.36
NW 0.0 32.0 0.36
NE 0.0 24.0 0.36
SW 0.0 36.0 0.36
SE 0.0 28.0 0.36
Roof -Sun 46.0 0.480
Roof -Sun-Insulated 269.0 42.0 0.20
Roof -Shaded 14.0 0.48
Transmission gain-except walls & roof
All glass 0.0 17.0 1.13
Partition 633.6 12.0 0.36
Ceiling 269.0 12.0 0.36
Floor 269.0 4.8 0.42
Infiltration 20.0 1.08
Internal Heat
People 11 230 1
Power
Lights 404 1 3.413
### Equipment 2.00 1 3413
### Additional Heat Gain, T54-57pg107-109
Room Sensible Heat-Sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Outdoor Air 161 17.0 1.08
EFFECTIVE ROOM SENSIBLE HEAT- Total
Room Latent Heat
Infiltration
People 11 190 1
Steam
Appliances
Additional Heat Gain
Vap.Trans 538 0.029
Sub-Total
Safety Factor, pg113 5%
Room Latent Heat
Duct leakage& R.A.Heat Regain + Safety
Outdoor Air 162 73.0 0.68
EFFECTIVE ROOM LATENT HEAT

EFFECTIVE ROOM TOTAL HEAT


OUTDOOR AIR HEAT
Cfm temp diff const
Sensible 161 17.0 1.08
hum diff const
Latent 161 73.0 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)

cfm
0.81

33
nd Dehumidifying Heat Load Estimate for GYMNASIUM IN PASIG
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 78.0
DIFFERENCE 17.0
JULY & MAY 10DEG
AHU Tag No GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH
SOUTH
- WEST
EAST
NW 0.0
NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 269.00 sft
&roof ROOF HEIGHT 10 ft
- FALSE CEILING HT. 10 ft
- NO OF F.A.CHANGES 5 PER HR.
- NO. OF PEOPLE 11 0.04
- Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
- EQUIPMENT LOAD 100.0 KW
2,260 DIVERSITY FACTOR 1.0
- SH PER PERSON 230 Btu/hr
lls & roof LH PER PERSON 190 Btu/hr
BPF 0.1
2,737 CFM/PERSON 10
1,162 EXHAUST 0
547 FLOOR GAIN 0 (1 if fl. gain exists else 0)
- ROOF(0)/CEILING(1) 1
ROOF (1 if Roof provided Insulat
2,475 PARTITIONS (1 if Mod.Partitions exists
CEILING 269 (1 if Mod.Ceiling Panels ex
1,377 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists
6,826 ADP&SHR 0 (1 if ADP & SHR revised e
- Motor bkw IF ADP & SHR RE
17,384 SHR 0.81 REV. ESHR
10.0% 1,738 ADP 55.00 REV. ADP
0.10 296 TR 2.96 REV. TR
19,419 Dehumd. CFM 869 REV. AIR QTY CFM
Reheat,KW N/A RE- HEAT IN KWTO INCREA
-
2,044 FRESH AIR REQUIREMENT
NOS CFM/PER
- PEOPLE 11
EXHAUST
1,139 NO. OF A/CHANGES 269
3,183 Ventilation cfm/ft2 269 0.10
159 TOTAL FRESH AIR
3,343 PRE-COOLING COIL
10% 334 DB 'F WB 'F
0.10 803 LEV. COND 56.0 55.9
4,480 INSIDE 69.0 58.9

23,899 DIFF. -13.0


T
1 - bf 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
0.90 2,667 Trm-( RSH/(1.08 x (De. CFM+CFMoa))
* If above is too high. Determine supply CFM
0.90 7,211 for desired dif. By supply air qty. formula
33,777 2. ENTERING DRY BULB TEMPERATURE
5% 1,689 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
N/A 3. ENTERING AIR MOISTURE CONTENT
35,466 (CFM oa*Woa+CFM ra*Wrm)/CFM da
3.69 3 4. LEAVING DRY BULB TEMPERATURE
0.81 ( Tadp + (BF(Tedb - T adp)))
55 5. SUPPLY AIR CFM
55 ( RSH/1.08 X (Trm-Tsa)
21 From psychrometric chart
869
# when bypassing a mixture of OA & RA use supply CFM, when
293.90 bypassing RA only, use deh. CFM
348.67
2
35.47
RH TH GR/LB DB 'F RH GR/LB
58% 138.0 95.0 58% 138.0
50% 65.0 77.0 50% 70.0
0.0 73.0 75 50 65
http://www.hvac-calculator.net/index.php?v=2
REAS (ft2) U' FACTORS
PARTNS WALL 0.360
158.4 GLASS 0.560
158.4 ALL GLASS 1.130
158.4 PARTITION 0.360
158.4 M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
633.6
The ADP Table
FOR 75.0 & 50%RH
SHR ADP
1 55.2 0.00
0.92 54 0.00
0.84 52 51.08
0.78 50 0.00
0.74 48 0.00
0.71 46 0.00
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00
UIREMENT
ACH NET (CFM)
15 161
-
-
0
162
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

60.55 0F
17.45

80.67 0F

102.82 Gr./lb

57.01 0F

1030.47 cfm

T ewb = F
0

T lwb = F
0

pply CFM, when


Cooling and Dehumidifying Heat Loa
Estmated By HENRY
Date MARCH 19,2017
Coustomer TONG LUNG
Location SUBIC
Room LINE 1
Classification PRODUCTION
Room Sensible Heat
Item Sun gain Factor
Solar gain glass
North 0.0 39 0.56
South 0.0 14 0.56
West 0.0 158 0.56
East 0.0 158 0.56
NW 0.0 148 0.56
NE 0.0 148 0.56
SW 0.0 66 0.56
SunSEGain 0.0 66 0.56
T19 pg 62, 60lb/sqft Wall Solar and trans gain-walls&roof
Factor
North 0.0 12.0 0.36
T21,22,23,24
South or 25 pp 66-69 0.0 26.0 0.36
UseWest
Hollow Block, 80lb, 8in thick 0.0 41.0 0.36
.24East
Btu/hr sqft degF Temp Dif 0.0 31.0 0.36
NW 0.0 32.0 0.36
NE 0.0 24.0 0.36
SW 0.0 36.0 0.36
SE 0.0 28.0 0.36
Roof -Sun 46.0 0.480
Roof -Sun-Insulated 269.0 42.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 0.0 20.0 1.13
Partition 633.6 15.0 0.36
Ceiling 269.0 15.0 0.36
Floor 269.0 4.8 0.42
Infiltration 20.0 1.08
Internal Heat
People 8 230 1
Power
Lights 404 1 3.413
### Equipment 2.00 1 3413
### Additional Heat Gain, T54-57pg107-109
Room Sensible Heat-Sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Outdoor Air 121 20.0 1.08
EFFECTIVE ROOM SENSIBLE HEAT- Total
Room Latent Heat
Infiltration
People 8 190 1
Steam
Appliances
Additional Heat Gain
Vap.Trans 538 0.029
Sub-Total
Safety Factor, pg113 5%
Room Latent Heat
Duct leakage& R.A.Heat Regain + Safety
Outdoor Air 121 73.0 0.68
EFFECTIVE ROOM LATENT HEAT

EFFECTIVE ROOM TOTAL HEAT


OUTDOOR AIR HEAT
Cfm temp diff const
Sensible 121 20.0 1.08
hum diff const
Latent 121 73.0 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)

cfm
0.84

33
nd Dehumidifying Heat Load Estimate for GYMNASIUM IN PASIG
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 75.0
DIFFERENCE 20.0
JULY & MAY 10DEG
AHU Tag No GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH
SOUTH
- WEST
EAST
NW 0.0
NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 269.00 sft
&roof ROOF HEIGHT 10 ft
- FALSE CEILING HT. 10 ft
- NO OF F.A.CHANGES 5 PER HR.
- NO. OF PEOPLE 8 0.03
- Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
- EQUIPMENT LOAD 100.0 KW
2,260 DIVERSITY FACTOR 1.0
- SH PER PERSON 230 Btu/hr
lls & roof LH PER PERSON 190 Btu/hr
BPF 0.1
3,421 CFM/PERSON 10
1,453 EXHAUST 0
547 FLOOR GAIN 0 (1 if fl. gain exists else 0)
- ROOF(0)/CEILING(1) 1
ROOF (1 if Roof provided Insulat
1,856 PARTITIONS (1 if Mod.Partitions exists
CEILING 269 (1 if Mod.Ceiling Panels ex
1,377 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists
6,826 ADP&SHR 0 (1 if ADP & SHR revised e
- Motor bkw IF ADP & SHR RE
17,740 SHR 0.84 REV. ESHR
10.0% 1,774 ADP 55.00 REV. ADP
0.10 261 TR 2.73 REV. TR
19,776 Dehumd. CFM 1017 REV. AIR QTY CFM
Reheat,KW N/A RE- HEAT IN KWTO INCREA
-
1,533 FRESH AIR REQUIREMENT
NOS CFM/PER
- PEOPLE 8
EXHAUST
1,139 NO. OF A/CHANGES 269
2,672 Ventilation cfm/ft2 269 0.10
134 TOTAL FRESH AIR
2,806 PRE-COOLING COIL
10% 281 DB 'F WB 'F
0.10 603 LEV. COND 56.0 55.9
3,690 INSIDE 69.0 58.9

23,465 DIFF. -13.0


T
1 - bf 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
0.90 2,353 Trm-( RSH/(1.08 x (De. CFM+CFMoa))
* If above is too high. Determine supply CFM
0.90 5,408 for desired dif. By supply air qty. formula
31,227 2. ENTERING DRY BULB TEMPERATURE
5% 1,561 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
N/A 3. ENTERING AIR MOISTURE CONTENT
32,788 (CFM oa*Woa+CFM ra*Wrm)/CFM da
3.42 3 4. LEAVING DRY BULB TEMPERATURE
0.84 ( Tadp + (BF(Tedb - T adp)))
55 5. SUPPLY AIR CFM
55 ( RSH/1.08 X (Trm-Tsa)
18 From psychrometric chart
1,017
# when bypassing a mixture of OA & RA use supply CFM, when
372.31 bypassing RA only, use deh. CFM
416.78
3
32.79
RH TH GR/LB DB 'F RH GR/LB
58% 138.0 95.0 58% 138.0
50% 65.0 77.0 50% 70.0
0.0 73.0 75 50 65
http://www.hvac-calculator.net/index.php?v=2
REAS (ft2) U' FACTORS
PARTNS WALL 0.360
158.4 GLASS 0.560
158.4 ALL GLASS 1.130
158.4 PARTITION 0.360
158.4 M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
633.6
The ADP Table
FOR 75.0 & 50%RH
SHR ADP
1 55.2 0.00
0.92 54 52.07
0.84 52 0.00
0.78 50 0.00
0.74 48 0.00
0.71 46 0.00
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00
UIREMENT
ACH NET (CFM)
15 121
-
-
0
121
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

58.92 0F
16.08

77.13 0F

89.25 Gr./lb

56.82 0F

1138.77 cfm

T ewb = F
0

T lwb = F
0

pply CFM, when


Cooling and Dehumidifying Heat Loa
Estmated By HENRY
Date MARCH 19,2017
Coustomer TONG LUNG
Location SUBIC
Room LINE 1
Classification PRODUCTION
Room Sensible Heat
Item Sun gain Factor
Solar gain glass
North 0.0 39 0.56
South 0.0 14 0.56
West 70.6 158 0.56
East 0.0 158 0.56
NW 0.0 148 0.56
NE 0.0 148 0.56
SW 0.0 66 0.56
SunSEGain 0.0 66 0.56
T19 pg 62, 60lb/sqft Wall Solar and trans gain-walls&roof
Factor
North 605.3 12.0 0.36
T21,22,23,24
South or 25 pp 66-69 0.0 26.0 0.36
UseWest
Hollow Block, 80lb, 8in thick 413.6 41.0 0.36
.24East
Btu/hr sqft degF Temp Dif 0.0 31.0 0.36
NW 0.0 32.0 0.36
NE 0.0 24.0 0.36
SW 0.0 36.0 0.36
SE 0.0 28.0 0.36
Roof -Sun 322.8 46.0 0.480
Roof -Sun-Insulated 42.0 0.20
Roof -Shaded 14.0 0.48
Transmission gain-except walls & roof
All glass 70.6 17.0 1.13
Partition 0.0 12.0 0.36
Ceiling 322.8 12.0 0.36
Floor 322.8 4.8 0.42
Infiltration 20.0 1.08
Internal Heat
People 48 230 1
Power
Lights 484 1 3.413
### Equipment 5.00 1 3413
### Additional Heat Gain, T54-57pg107-109
Room Sensible Heat-Sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Outdoor Air 726 17.0 1.08
EFFECTIVE ROOM SENSIBLE HEAT- Total
Room Latent Heat
Infiltration
People 48 190 1
Steam
Appliances
Additional Heat Gain
Vap.Trans 1,059 0.029
Sub-Total
Safety Factor, pg113 5%
Room Latent Heat
Duct leakage& R.A.Heat Regain + Safety
Outdoor Air 727 73.0 0.68
EFFECTIVE ROOM LATENT HEAT

EFFECTIVE ROOM TOTAL HEAT


OUTDOOR AIR HEAT
Cfm temp diff const
Sensible 726 17.0 1.08
hum diff const
Latent 726 73.0 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)

cfm
0.76

33
nd Dehumidifying Heat Load Estimate for GYMNASIUM IN PASIG
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 78.0
DIFFERENCE 17.0
JULY & MAY 10DEG
AHU Tag No GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH 605.3
SOUTH
- WEST 70.6 413.6
EAST
NW 0.0
NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 322.80 sft
&roof ROOF HEIGHT 10 ft
2,615 FALSE CEILING HT. 10 ft
- NO OF F.A.CHANGES 5 PER HR.
6,105 NO. OF PEOPLE 48 0.15
- Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
7,127 EQUIPMENT LOAD 100.0 KW
- DIVERSITY FACTOR 1.0
- SH PER PERSON 230 Btu/hr
lls & roof LH PER PERSON 190 Btu/hr
BPF 0.1
- CFM/PERSON 10
1,394 EXHAUST 0
657 FLOOR GAIN 0 (1 if fl. gain exists else 0)
- ROOF(0)/CEILING(1) 1
ROOF (1 if Roof provided Insulat
11,137 PARTITIONS (1 if Mod.Partitions exists
CEILING 323 (1 if Mod.Ceiling Panels ex
1,653 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists
17,065 ADP&SHR 0 (1 if ADP & SHR revised e
- Motor bkw IF ADP & SHR RE
47,753 SHR 0.76 REV. ESHR
10.0% 4,775 ADP 55.00 REV. ADP
0.10 1,333 TR 10.07 REV. TR
53,861 Dehumd. CFM 2409 REV. AIR QTY CFM
Reheat,KW N/A RE- HEAT IN KWTO INCREA
-
9,200 FRESH AIR REQUIREMENT
NOS CFM/PER
- PEOPLE 48
EXHAUST
2,242 NO. OF A/CHANGES 323
11,442 Ventilation cfm/ft2 323 0.10
572 TOTAL FRESH AIR
12,014 PRE-COOLING COIL
10% 1,201 DB 'F WB 'F
0.10 3,608 LEV. COND 56.0 55.9
16,824 INSIDE 69.0 58.9

70,685 DIFF. -13.0


T
1 - bf 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
0.90 12,001 Trm-( RSH/(1.08 x (De. CFM+CFMoa))
* If above is too high. Determine supply CFM
0.90 32,448 for desired dif. By supply air qty. formula
115,135 2. ENTERING DRY BULB TEMPERATURE
5% 5,757 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
N/A 3. ENTERING AIR MOISTURE CONTENT
120,891 (CFM oa*Woa+CFM ra*Wrm)/CFM da
12.59 10 4. LEAVING DRY BULB TEMPERATURE
0.76 ( Tadp + (BF(Tedb - T adp)))
55 5. SUPPLY AIR CFM
55 ( RSH/1.08 X (Trm-Tsa)
21 From psychrometric chart
2,409
# when bypassing a mixture of OA & RA use supply CFM, when
239.15 bypassing RA only, use deh. CFM
311.30
6
120.89
RH TH GR/LB DB 'F RH GR/LB
58% 138.0 95.0 58% 138.0
50% 65.0 77.0 50% 70.0
0.0 73.0 75 50 65
http://www.hvac-calculator.net/index.php?v=2
REAS (ft2) U' FACTORS
PARTNS WALL 0.360
GLASS 0.560
ALL GLASS 1.130
PARTITION 0.360
M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
0.0
The ADP Table
FOR 75.0 & 50%RH
SHR ADP
1 55.2 0.00
0.92 54 0.00
0.84 52 0.00
0.78 50 49.10
0.74 48 0.00
0.71 46 0.00
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00
UIREMENT
ACH NET (CFM)
15 726
-
-
1
727
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

62.10 0F
15.90

81.94 0F

126.24 Gr./lb

56.98 0F

3136.10 cfm

T ewb = F
0

T lwb = F
0

pply CFM, when


Cooling and Dehumidifying Heat Loa
Estmated By HENRY
Date MARCH 19,2017
Coustomer TONG LUNG
Location SUBIC
Room LINE 1
Classification PRODUCTION
Room Sensible Heat
Item Sun gain Factor
Solar gain glass
North 0.0 39 0.56
South 0.0 14 0.56
West 70.6 158 0.56
East 0.0 158 0.56
NW 0.0 148 0.56
NE 0.0 148 0.56
SW 0.0 66 0.56
SunSEGain 0.0 66 0.56
T19 pg 62, 60lb/sqft Wall Solar and trans gain-walls&roof
Factor
North 0.0 12.0 0.36
T21,22,23,24
South or 25 pp 66-69 0.0 26.0 0.36
UseWest
Hollow Block, 80lb, 8in thick 413.6 41.0 0.36
.24East
Btu/hr sqft degF Temp Dif 0.0 31.0 0.36
NW 0.0 32.0 0.36
NE 0.0 24.0 0.36
SW 0.0 36.0 0.36
SE 0.0 28.0 0.36
Roof -Sun 322.8 46.0 0.480
Roof -Sun-Insulated 42.0 0.20
Roof -Shaded 14.0 0.48
Transmission gain-except walls & roof
All glass 70.6 17.0 1.13
Partition 0.0 12.0 0.36
Ceiling 322.8 12.0 0.36
Floor 322.8 4.8 0.42
Infiltration 20.0 1.08
Internal Heat
People 24 230 1
Power
Lights 484 1 3.413
### Equipment 12.00 1 3413
### Additional Heat Gain, T54-57pg107-109
Room Sensible Heat-Sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Outdoor Air 363 17.0 1.08
EFFECTIVE ROOM SENSIBLE HEAT- Total
Room Latent Heat
Infiltration
People 24 190 1
Steam
Appliances
Additional Heat Gain
Vap.Trans 1,059 0.029
Sub-Total
Safety Factor, pg113 5%
Room Latent Heat
Duct leakage& R.A.Heat Regain + Safety
Outdoor Air 364 73.0 0.68
EFFECTIVE ROOM LATENT HEAT

EFFECTIVE ROOM TOTAL HEAT


OUTDOOR AIR HEAT
Cfm temp diff const
Sensible 363 17.0 1.08
hum diff const
Latent 363 73.0 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)

cfm
0.88

33
nd Dehumidifying Heat Load Estimate for GYMNASIUM IN PASIG
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 78.0
DIFFERENCE 17.0
JULY & MAY 10DEG
AHU Tag No GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH
SOUTH
- WEST 70.6 413.6
EAST
NW 0.0
NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 322.80 sft
&roof ROOF HEIGHT 10 ft
- FALSE CEILING HT. 10 ft
- NO OF F.A.CHANGES 5 PER HR.
6,105 NO. OF PEOPLE 24 0.15
- Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
7,127 EQUIPMENT LOAD 100.0 KW
- DIVERSITY FACTOR 1.0
- SH PER PERSON 230 Btu/hr
lls & roof LH PER PERSON 190 Btu/hr
BPF 0.1
- CFM/PERSON 10
1,394 EXHAUST 0
657 FLOOR GAIN 0 (1 if fl. gain exists else 0)
- ROOF(0)/CEILING(1) 1
ROOF (1 if Roof provided Insulat
5,568 PARTITIONS (1 if Mod.Partitions exists
CEILING 323 (1 if Mod.Ceiling Panels ex
1,653 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists
40,956 ADP&SHR 0 (1 if ADP & SHR revised e
- Motor bkw IF ADP & SHR RE
63,461 SHR 0.88 REV. ESHR
10.0% 6,346 ADP 55.00 REV. ADP
0.10 667 TR 8.96 REV. TR
70,474 Dehumd. CFM 3152 REV. AIR QTY CFM
Reheat,KW N/A RE- HEAT IN KWTO INCREA
-
4,600 FRESH AIR REQUIREMENT
NOS CFM/PER
- PEOPLE 24
EXHAUST
2,242 NO. OF A/CHANGES 323
6,842 Ventilation cfm/ft2 323 0.10
342 TOTAL FRESH AIR
7,184 PRE-COOLING COIL
10% 718 DB 'F WB 'F
0.10 1,805 LEV. COND 56.0 55.9
9,708 INSIDE 69.0 58.9

80,182 DIFF. -13.0


T
1 - bf 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
0.90 6,001 Trm-( RSH/(1.08 x (De. CFM+CFMoa))
* If above is too high. Determine supply CFM
0.90 16,224 for desired dif. By supply air qty. formula
102,406 2. ENTERING DRY BULB TEMPERATURE
5% 5,120 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
N/A 3. ENTERING AIR MOISTURE CONTENT
107,527 (CFM oa*Woa+CFM ra*Wrm)/CFM da
11.20 9 4. LEAVING DRY BULB TEMPERATURE
0.88 ( Tadp + (BF(Tedb - T adp)))
55 5. SUPPLY AIR CFM
55 ( RSH/1.08 X (Trm-Tsa)
21 From psychrometric chart
3,152
# when bypassing a mixture of OA & RA use supply CFM, when
351.80 bypassing RA only, use deh. CFM
392.39
8
107.53
RH TH GR/LB DB 'F RH GR/LB
58% 138.0 95.0 58% 138.0
50% 65.0 77.0 50% 70.0
0.0 73.0 75 50 65
http://www.hvac-calculator.net/index.php?v=2
REAS (ft2) U' FACTORS
PARTNS WALL 0.360
GLASS 0.560
ALL GLASS 1.130
PARTITION 0.360
M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
0.0
The ADP Table
FOR 75.0 & 50%RH
SHR ADP
1 55.2 0.00
0.92 54 52.97
0.84 52 0.00
0.78 50 0.00
0.74 48 0.00
0.71 46 0.00
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00
UIREMENT
ACH NET (CFM)
15 363
-
-
1
364
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

59.44 0F
18.56

79.76 0F

88.42 Gr./lb

57.03 0F

3516.02 cfm

T ewb = F
0

T lwb = F
0

pply CFM, when


Cooling and Dehumidifying Heat Loa
Estmated By HENRY
Date MARCH 19,2017
Coustomer TONG LUNG
Location SUBIC
Room LINE 1
Classification PRODUCTION
Room Sensible Heat
Item Sun gain Factor
Solar gain glass
North 0.0 39 0.56
South 0.0 14 0.56
West 70.6 158 0.56
East 70.6 158 0.56
NW 0.0 148 0.56
NE 0.0 148 0.56
SW 0.0 66 0.56
SunSEGain 0.0 66 0.56
T19 pg 62, 60lb/sqft Wall Solar and trans gain-walls&roof
Factor
North 605.3 12.0 0.36
T21,22,23,24
South or 25 pp 66-69 605.3 26.0 0.36
UseWest
Hollow Block, 80lb, 8in thick 413.6 41.0 0.36
.24East
Btu/hr sqft degF Temp Dif 413.6 31.0 0.36
NW 0.0 32.0 0.36
NE 0.0 24.0 0.36
SW 0.0 36.0 0.36
SE 0.0 28.0 0.36
Roof -Sun 484.2 46.0 0.480
Roof -Sun-Insulated 42.0 0.20
Roof -Shaded 14.0 0.48
Transmission gain-except walls & roof
All glass 141.2 17.0 1.13
Partition 0.0 12.0 0.36
Ceiling 484.2 12.0 0.36
Floor 484.2 4.8 0.42
Infiltration 20.0 1.08
Internal Heat
People 36 230 1
Power
Lights 726 1 3.413
### Equipment 12.00 1 3413
### Additional Heat Gain, T54-57pg107-109
Room Sensible Heat-Sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Outdoor Air 545 17.0 1.08
EFFECTIVE ROOM SENSIBLE HEAT- Total
Room Latent Heat
Infiltration
People 36 190 1
Steam
Appliances
Additional Heat Gain
Vap.Trans 1,382 0.029
Sub-Total
Safety Factor, pg113 5%
Room Latent Heat
Duct leakage& R.A.Heat Regain + Safety
Outdoor Air 546 73.0 0.68
EFFECTIVE ROOM LATENT HEAT

EFFECTIVE ROOM TOTAL HEAT


OUTDOOR AIR HEAT
Cfm temp diff const
Sensible 545 17.0 1.08
hum diff const
Latent 545 73.0 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)

cfm
0.87

33
nd Dehumidifying Heat Load Estimate for GYMNASIUM IN PASIG
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 78.0
DIFFERENCE 17.0
JULY & MAY 10DEG
AHU Tag No GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH 605.3
SOUTH 605.3
- WEST 70.6 413.6
EAST 70.6 413.6
NW 0.0
NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 484.20 sft
&roof ROOF HEIGHT 23 ft
2,615 FALSE CEILING HT. 20 ft
5,665 NO OF F.A.CHANGES 5 PER HR.
6,105 NO. OF PEOPLE 36 0.15
4,616 Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
10,691 EQUIPMENT LOAD 100.0 KW
- DIVERSITY FACTOR 1.0
- SH PER PERSON 230 Btu/hr
lls & roof LH PER PERSON 190 Btu/hr
BPF 0.1
- CFM/PERSON 10
2,092 EXHAUST 0
985 FLOOR GAIN 0 (1 if fl. gain exists else 0)
- ROOF(0)/CEILING(1) 1
ROOF (1 if Roof provided Insulat
8,352 PARTITIONS (1 if Mod.Partitions exists
CEILING 484 (1 if Mod.Ceiling Panels ex
2,479 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists
40,956 ADP&SHR 0 (1 if ADP & SHR revised e
- Motor bkw IF ADP & SHR RE
84,556 SHR 0.87 REV. ESHR
10.0% 8,456 ADP 55.00 REV. ADP
0.10 1,000 TR 12.37 REV. TR
94,012 Dehumd. CFM 4205 REV. AIR QTY CFM
Reheat,KW N/A RE- HEAT IN KWTO INCREA
-
6,900 FRESH AIR REQUIREMENT
NOS CFM/PER
- PEOPLE 36
EXHAUST
2,926 NO. OF A/CHANGES 484
9,826 Ventilation cfm/ft2 484 0.10
491 TOTAL FRESH AIR
10,317 PRE-COOLING COIL
10% 1,032 DB 'F WB 'F
0.10 2,708 LEV. COND 56.0 55.9
14,057 INSIDE 69.0 58.9

108,069 DIFF. -13.0


T
1 - bf 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
0.90 9,001 Trm-( RSH/(1.08 x (De. CFM+CFMoa))
* If above is too high. Determine supply CFM
0.90 24,336 for desired dif. By supply air qty. formula
141,406 2. ENTERING DRY BULB TEMPERATURE
5% 7,070 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
N/A 3. ENTERING AIR MOISTURE CONTENT
148,476 (CFM oa*Woa+CFM ra*Wrm)/CFM da
15.47 12 4. LEAVING DRY BULB TEMPERATURE
0.87 ( Tadp + (BF(Tedb - T adp)))
55 5. SUPPLY AIR CFM
55 ( RSH/1.08 X (Trm-Tsa)
21 From psychrometric chart
4,205
# when bypassing a mixture of OA & RA use supply CFM, when
339.87 bypassing RA only, use deh. CFM
383.96
11
148.48
RH TH GR/LB DB 'F RH GR/LB
58% 138.0 95.0 58% 138.0
50% 65.0 77.0 50% 70.0
0.0 73.0 75 50 65
http://www.hvac-calculator.net/index.php?v=2
REAS (ft2) U' FACTORS
PARTNS WALL 0.360
GLASS 0.560
ALL GLASS 1.130
PARTITION 0.360
M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
0.0
The ADP Table
FOR 75.0 & 50%RH
SHR ADP
1 55.2 0.00
0.92 54 52.75
0.84 52 0.00
0.78 50 0.00
0.74 48 0.00
0.71 46 0.00
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00
UIREMENT
ACH NET (CFM)
15 545
-
-
1
546
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

59.68 0F
18.32

79.95 0F

91.33 Gr./lb

57.03 0F

4750.76 cfm

T ewb = F
0

T lwb = F
0

pply CFM, when


Name of Project: INDIRA GANDHI INSTITUTE
Address: GOREGAON
Space used for: SEMINAR HALL No 1
Area in sq.ft = 935 Length in Ft. Height in ft.=
Volume in cu.ft 20570 Width in Ft. Contact factor :
Bypass factor : 0.12 Btu/hour
Area x Temp.diffFactor Sensible Load
SOLAR GAIN-GLASS
Glass (N) 0 11 0.56 0
Glass (E) 38 11 0.56 231
Glass (S) 0 11 0.56 0
Glass (W) 0 165 0.56 0
Glass (NE) 0 11 0.56 0
Glass (SW) 0 113 0.56 0
Glass (NW) 0 118 0.56 0
Glass (SE) 0 11 0.56 0
SOLAR & TRANSMISSION GAIN-WALLS & ROOF
Wall (N) 585.2 14 0.35 2867
Wall (E) 1326.5 28 0.35 13000
Wall (S) 0 26 0.35 0
Wall (W) 0 22 0.35 0
Wall (NE) 0 20 0.35 0
Wall (SW) 0 24 0.35 0
Wall (NW) 0 16 0.35 0
Wall (SE) 0 28 0.35 0
Exposed Roof 935 45 0.48 20196
TRANSMISSION GAIN-EXCEPT WALLS & ROOF
All Glass 38 22 1.13 932
Partition Wall 0 17 0.40 0
Partition Glass 0 17 0.43 0
Ceiling 0 17 0.48 0
Floor 0 17 0.48 0
INTERNAL HEAT
People 90 276 224 24840
Lights (I) - W 1870 3.41 1.0 6377
Lights (F) - W 0 3.41 1.25 0
Equip.Load -W 750 3.41 1.0 2558
-do- in HP 0 2545 1.0 0
Others 0
Subtotals 71001
Safety Factors (12.5% & 5% respectively) 8875
Room Sensible & Latent Loads 79876

Outdoor Air cfm = 506.1 1443


Effective Room Sensible Heat (ERSH) 81319
Effective Room Latent Heat (ERLH) -
Effective Room Total Heat (ERTH) 105873
OUTDOOR AIR (O.A.)
Sensible Load 10582
Latent Load -
Effective Room Total Heat + O.A Heat 141289
Other Heat Gains @ 3% 4239
GRAND TOTAL HEAT 145527
TR 12.13
Job ref./ Enquiry No.:
Estimated by: GDK Heat load for:
Peak load at: 4.00 PM
22.0 DESIGN CONDITIONS
0.88 (British Units) DBT % RH WBT
Outside 95 60 83
Latent Load Inside 73 55 62
Difference 22 xxxx xxxx
- Eq. Temp.correction factor 10
- OUTDOOR AIR (CFM)
- 90 People x 5.6233333333 CFM/Person =
- 1 No. of air changes/hr =
- Selected Outdoor Air CFM = 506.1
-
- APPARATUS DEW POINT
-
Effective Sens. Heat Factor (ESHF) = ERSH/ERTH =
-
- INDICATED ADP = 55 SELECT.ADP=
-
- DEHUMIDIFIED AIR QUANTITY
-
- Dehum. Rise = Contact Factor x (Rm Temp. - ADP)=
- Dehum. CFM = ERSH/1.08/Dehum. Rise =
- Dehum CFM /400 =
- U-factors: Roof Insl
ROOF Exposed Walls 0.35 Roof Non Insl
- Partition Walls 0.40 Ceiling
Partition Glass 0.43 Floor
- Factors for Glass: Solar gain
- Transm. Gain
- Some typical inside design conditions:
DBT % RH WBT
20160 70 50 58.5
- 70 55 59.7
- 72 50 60.1
DITIONS
DESIGN CONDITIONS
- 72 55 61.4
- 74 50 61.8
0 74 55 63.0
20160 75 50 62.6
1008 75 55 64.0
21168 76 55 64.9
77 55 65.6
3386 90 88 86
- 104 45 83
24554 105 40 83
105873 110 25 78

- Air on Coil in deg F: Check figures:


24834 DBT : 75 sq.ft/TR =
141289 WBT : 64 cfm/sq.ft =
4239 cfm/TR =
145527 TMBH = 145.5
12.13 SMBH = 91.9 Sheet No.
Summer

Gr/lb
151
69
82

506.1
342.8333
506.1

0.77

55

15.8
4753
11.88
0.12
0.48
0.48
0.48
0.56
1.13

Gr/lb
54.8
60.1
58.8
64.4
62.0
68.0
65.0
71.5
74.0
76.6
184.0
138.0
136.0
94.0

gures:
77
5.1
392