Sei sulla pagina 1di 11

3440 TABLE 1: Screen 5 : Neutral current ( for 4W only ) ,

Frequency, Sys. Power Factor


Screen 6 : System Power
( Reactive, Apparent, Active)
Screen 17 : Phase Power (B)
Reactive/ Apparent /Active
( for 4W only )
Screen 18: Phase Angle
(Phase R / Y / B) ( for 4W only )
Measured Parameters Units of measurement
System Voltage Volts V x1000
V x1000 V x1000 V x1000

3440 - Three Phase (3W/4W) Amps VRY IN


System Current VRY
KVAr
IN
KVArh
VRY
KVAr
IN
KVArh
KVAr KVArh VRY
KVAr
IN
KVArh
Sys Ph R
Sys Ph R
Voltage VL1-N(4wire only) Volts Sys Ph R
KAh KAh
KAh Sys Ph R
KAh

Three Phase Multi-function Digital Meter Voltage VL2-N(4wire only) Volts A


VYB
x1000
Hz
A
VYB
x1000
Hz
A
VYB
KVA
x1000
Hz A
VYB
x1000
Hz
KVA KVAh
KVAh
Voltage VL3-N(4wire only) Volts KVA KVAh Min Ph Y
KVA KVAh
Installation & Operating Instructions Min Ph Y
%THD
Min Ph Y
%THD
%THD
Min Ph Y
%THD
Voltage VL1-L2 Volts x1000 KW x1000
KW x1000 KW KW x1000
Section Contents Voltage VL2-L3 Volts VBR P.F. VBR
Angle
P.F.
KWh
VBR
Angle
P.F.
KWh VBR P.F.
Angle KWh Max Angle KWh
Max Ph B
Ph B
1. Introduction Voltage VL3-L1 Volts Max Ph B
Demand Demand
Demand
Max Ph B
Demand

2. Measurement Reading Screens Current L1 Amps


3. Programming Current L2 Amps
Current L3 Amps
3.1 Password Protection
3.2 Menu selection Neutral Current ( 4 wire only ) Amps
3.2.1 System Parameter selection screen Frequency Hz Screen 19 : Phase Power Factor
Active Power (System / Phase (4 wire only) ) Kwatts Screen 7 : Active Energy(Import) Screen 8 : Active Energy (Export) (Phase R / Y / B) ( for 4W only ) Screen 20 : Current Demand
3.2.1.1 System type
3.2.1.2 Potential transformer Primary value Reactive Power (System / Phase (4 wire only)) KVAr
3.2.1.3 Potential transformer secondary value Apparent Power (System / Phase (4 wire only)) KVA V x1000 V x1000 V x1000 V x1000

3.2.1.4 Current transformer Primary value Power Factor (System / Phase (4 wire only)) VRY
KVAr
IN
KVArh
VRY
KVAr
IN
KVArh
VRY
KVAr
IN
KVArh
VRY
KVAr
IN
KVArh
Sys Ph R Sys Ph R Sys Ph R Sys
3.2.1.5 Current transformer Secondary value Phase Angle ( Phase(4 wire only)) Degree KAh KAh KAh
Ph R
KAh

3.2.1.6 Demand integration time Active Import Energy (8 Digit resolution) kWh A
VYB
x1000
Hz
A
VYB
x1000
Hz
A
VYB
x1000
Hz
A
VYB
x1000
Hz
KVA KVAh KVA KVAh KVA KVAh
3.2.1.7 Auto Scrolling Active Export Energy (8 Digit resolution) kWh Min Ph Y Min Ph Y Min Ph Y
KVA
Min
KVAh
Ph Y
%THD %THD %THD %THD
3.2.1.8 Low current noise cutoff Reactive Import Energy (8 Digit resolution) kVArh KW x1000
KW x1000 KW x1000 KW x1000
3.2.1.9 Energy Display on modbus Reactive Export Energy (8 Digit resolution) kVArh VBR
Angle
P.F.
KWh
VBR
Angle
P.F.
KWh
VBR P.F. VBR P.F.
Angle KWh Angle KWh
3.2.1.10 Energy Digit reset count. Apparent Energy (8 Digit resolution) kVAh
Max Ph B
Demand
Max Ph B
Demand
Max Ph B Max Ph B
Demand Demand
3.2.2 Communication Parameter selection screen Ampere Hour (8 Digit resolution) KAh
3.2.2.1 Address Setting Current Demand Amps
3.2.2.2 RS 485 Baud rate
KVA Demand KVA
3.2.2.3 RS 485 Parity selection
KW Import Demand KW
3.2.3 Reset Parameter selection screen
KW Export Demand KW Screen 10 : Reactive Energy(Export)
3.2.3.1 Resetting Parameter Screen 9 : Reactive Energy(Import) Screen 21 : Max Current
Max Current Demand Amps
3.2.4 Output Option selection screen (menu) Demand Screen 22 : kVA Demand
Max kVA Demand KVA
3.2.4.1 Configuration of Output Max KW Import Demand KW V x1000 V x1000
IN
3.2.4.1.1 Relay 1 output selection menu Max KW Export Demand KW
VRY
KVAr KVArh
VRY
KVAr
IN
KVArh
V x1000
IN
V x1000
Sys Ph R VRY VRY IN
Sys Ph R
3.2.4.1.1.1 Pulse output Run Hour Hours KAh KAh
KVAr
Sys
KVArh
Ph R
KVAr
Sys
KVArh
Ph R
3.2.4.1.1.1.1 Assignment of Energy to Pulse (Relay 1) On Hour Hours
A
VYB
x1000
Hz
A
VYB
x1000
Hz
KAh KAh
A x1000
3.2.4.1.1.1.2 Pulse Duration Selection Number of Interruptions Counts
KVA
Min
KVAh
Ph Y
KVA
Min
KVAh
Ph Y
VYB Hz
A
VYB
x1000
Hz
KVA KVAh KVA KVAh
%THD
3.2.4.1.1.1.3 Pulse Rate %THD Min Ph Y Min Ph Y
Phase Reversal Indication KW x1000 KW x1000
%THD Demand
%THD
3.2.4.1.1.2 Limit output VBR P.F. VBR P.F.
V1 THD % Angle KWh Angle KWh
KW x1000
KW x1000
3.2.4.1.1.2.1 Assignment of Limit Output1 to Parameter Max Ph B Max Ph B
VBR P.F. VBR P.F.
V2 THD % Demand Demand
Angle
Max
KWh Angle KWh
3.2.4.1.1.2.2 Limit Configuration Ph B
Demand
Max Ph B

3.2.4.1.1.2.3 Trip point selection V3 THD %


Max Demand
Demand

3.2.4.1.1.2.4 Hysteresis selection I1 THD %


3.2.4.1.1.2.5 Energizing delay time I2 THD %
3.2.4.1.1.2.6 De-energizing delay time I3 THD %
3.2.4.1.2 Relay 2 output selection menu System Voltage THD %
Screen 11 : Apparent Energy Screen 12 : Ampere Hour
3.2.4.1.3 Analog output System Current THD % Screen 23 : Max kVA Demand Screen 24 : Import kW Demand
3.2.4.1.3.1 Parameter setting for Analog Output-1
3.2.4.1.3.2 Parameter setting for Analog Output-2 V x1000
V x1000 V
VRY IN x1000
VRY IN
3.2.5 Quit screen KVAr
Sys
KVArh
Ph R
KVAr KVArh V x1000 VRY
KVAr
IN
KVArh
Sys Ph R VRY IN
KAh Sys Ph R
4. Phase Rotation Error screen. 2. Measurement Reading Screens A x1000
A
KAh

x1000
KVAr
Sys
KVArh
Ph R
KAh
KAh

5. Run - Hour. VYB


KVA
Hz
KVAh
VYB
KVA
Hz
KVAh A x1000
A
VYB
x1000
Hz

6. On - Hour. In normal operation the user is presented with one of the measurement reading Min Ph Y
%THD
Min Ph Y
VYB
KVA
Hz
KVAh
KVA
Min
KVAh
Ph Y
%THD
7. Number of Interruption screens out of several screens. These screens may be scrolled through one at a KW x1000
Min Ph Y
Demand
%THD
%THD
Demand

KW x1000 x1000
P.F. KW
8. Analog Output time in incremental order by pressing the “ Up key” and in decremental order VBR
Angle KWh
VBR P.F.
KWh KW x1000 VBR P.F.
Angle
9. Relay Output by pressing “ Down key”.
Max Ph B
Demand
Max Ph B VBR
Angle
P.F.
KWh
Angle
Max
KWh
Ph B
Demand Max Demand
Max Ph B Demand
9.1 Pulse output Max Demand
Demand

9.2 Limit Switch


10. RS 485 ( ModBus ) Screen 1 : System screen
10.1 User Assignable Modbus Register (System Voltage, System Current, Screen 2 : Line to Neutral Voltages
(for 4 wire only)
11. Phaser Diagram System Active Power)
Screen 13 : Min System Voltage
12. Installation Screen 14 : Max System Voltage Screen 25 : Max Import kW
& Current & Current Screen 26 :Export kW Demand
12.1 EMC Installation Requirements V x1000
Demand
VRY IN V x1000
12.2 Case Dimensions and Panel Cut-out KVAr KVArh VRY
KVAr
IN
KVArh
Sys Ph R V x1000
12.3 Wiring KAh Sys Ph R
KAh
VRY IN
V
VRY
x1000
IN
V
VRY
x1000
IN
KVAr KVArh V x1000
12.4 Auxiliary Supply A
VYB
x1000
Hz
A x1000
Sys Ph R
KAh
VRY IN
KVAr
Sys
KVArh
Ph R
KVAr
Sys
KVArh
Ph R
VYB Hz KVAr KVArh KAh KAh
12.5 Fusing KVA
Min
KVAh
Ph Y
KVA
Min
KVAh A x1000
Sys Ph R
KAh A x1000
Ph Y VYB Hz A x1000
12.6 Earth / Ground Connections %THD
%THD KVA KVAh A x1000
VYB
KVA
Hz
KVAh
VYB
KVA
Hz
KVAh
Min Ph Y VYB Hz
x1000 Min
13. Connection Diagrams KW
VBR P.F.
KW
VBR
x1000
P.F.
%THD KVA
Min
KVAh
Ph Y
%THD
Demand
Min Ph Y
Demand
%THD
Angle KWh Ph Y
Angle KWh x1000
14. Specification Max Ph B Max Ph B
KW
VBR P.F.
%THD
KW x1000 KW x1000
Demand Demand VBR P.F. VBR P.F.
Angle KWh KW x1000
15. Connection for Optional Pulse output / RS 485 /Analog Ouput Max Ph B VBR P.F.
Angle
Max
KWh
Ph B
Angle
Max
KWh
Ph B
Demand Angle KWh
Max Demand
Demand Max Demand
Demand
Max Ph B
15000889_Rev.D - 7/2012 Demand

1. Introduction
The 3440 is a panel mounted 96 x 96mm DIN Quadratic Digital metering
system for the measurement important electrical parameters like AC voltage, Screen 15 : Phase Power (R) Screen 16 : Phase Power (Y)
AC Current, Frequency, Power, Energy(Active / Reactive / Apparent) . Screen 3 : Line to Line Voltages Screen 4 : Line Currents Reactive/ Apparent /Active Reactive/ Apparent /Active
The instrument integrates accurate measurement technology (All Voltages & ( for 4W only ) ( for 4W only ) Screen 27 :Max Export kW
Current measurements are True RMS upto 15th Harmonic) with 3 line 4 digits V
Demand Screen 28 :Run Hour
x1000 V x1000
Ultra high brightness LED display. VRY
KVAr
IN
KVArh
VRY
KVAr
IN
KVArh V x1000 V x1000
Sys Ph R Sys Ph R VRY IN VRY IN
KAh KAh KVAr KVArh KVAr KVArh V x1000
Sys V x1000
Sys Ph R Ph R VRY IN

V x1000
3440 can be configured and programmed A
VYB
x1000
Hz
A
VYB
x1000
Hz
KAh KAh KVAr
Sys
KVArh
Ph R
VRY
KVAr
IN
KVArh
Sys Ph R
VRY
KVAr
IN
KVArh
at site for the following : KVA
Min
KVAh
Ph Y
KVA
Min
KVAh
Ph Y
A
VYB
x1000
Hz
A
VYB
x1000
Hz
KAh
KAh
Sys Ph R %THD KVA KVA KVAh A x1000
KAh PT Primary, PT Secondary, CT Primary, %THD
Min
KVAh
Ph Y Min Ph Y VYB Hz A
VYB
x1000
Hz
KW x1000 KW x1000 %THD %THD KVA KVAh
A x1000 CT Secondary (5A or1A) and 3 phase 3W VBR P.F. VBR P.F. Min Ph Y
KVA
Min
KVAh
Ph Y
VYB Angle KWh KW x1000 KW x1000 Demand
%THD
KVA
Hz
KVAh or 3 Phase 4W system. Max Ph B
Angle
Max
KWh
Ph B VBR P.F. VBR P.F.
%THD
Min Ph Y Demand Angle KWh Angle KWh KW x1000
Demand KW x1000
%THD Max Ph B Max Ph B VBR P.F.
VBR P.F.

KW x1000
The front panel has two push buttons through Demand Demand Angle
Max
KWh
Ph B Angle KWh
Max Ph B
Max Demand
Demand
VBR
Angle
P.F.
KWh
which the user may scroll through the Demand

Max Ph B
Demand
available measurement readings, reset the
energy (Import/Export) Min/Max (System Voltage
and System Current) and configure the product. 1
2

Down Up
Screen 32 :Voltage %THD
Screen 29 :On Hour Screen 30 :Number of Interruptions (for 4 wire only) (for 3 wire only)
3. Programming
Password confirmed.
V x1000 V x1000 V x1000 V x1000
The following sections comprise step by step procedures for configuring the V x1000
VRY IN
VRY
KVAr
IN
KVArh
VRY
KVAr
IN VRY
KVAr
IN
KVArh
VRY
KVAr
IN
KVArh
3440 for individual user requirements. KVAr
Sys
KVArh
KVArh Ph R
Sys
Sys Ph R
KAh
Sys Ph R
KAh
Ph R
KAh
Sys Ph R
KAh To access the set-up screens press and hold the “ Down” and “ Up” KAh
Pressing “ Down” key will advance to the “New /
A x1000 A x1000 A x1000 A x1000 Key simultaneously for 5 seconds. This will take the User into the Password A
VYB
x1000
Hz
change Password” entry stage.
VYB Hz VYB Hz VYB Hz VYB Hz KVA KVAh
KVA KVAh KVA KVAh KVA
Min
KVAh KVA KVAh Protection Entry Stage (Section 3.1). Min Ph Y Pressing the “ Up” key will advance to the Menu selection
Min Ph Y Min Ph Y Ph Y Min Ph Y %THD
%THD %THD %THD %THD
KW x1000
KW x1000 KW x1000 KW x1000 KW x1000 P.F.
VBR
VBR
Angle
P.F.
KWh
VBR P.F. VBR
Angle
P.F.
KWh
VBR
Angle
P.F.
KWh
3.1. Password Protection Angle KWh

Max Ph B
Angle
Max
KWh
Ph B Max Ph B Max Ph B
Max Ph B
Demand
screen. (See section 3.2).
Demand Demand Demand Demand Password protection can be enabled to prevent unauthorised access to set-up
screens, by default password protection is not enabled.

Password protection is enabled by selecting a four digit number other than 0000,
setting a password of 0000 disables the password protection.
Screen 34 : System Voltage & Password Incorrect.
Screen 31 :Correct Phase sequence Phase sequence error Screen 33 :Current %THD System Current %THD V
VRY
x1000
IN
V x1000 KVAr KVArh
VRY IN Sys Ph R The unit has not accepted the
KVAr KVArh KAh
Sys Ph R Password entered.
V x1000 V x1000 V KAh A x1000
V x1000 x1000
IN VRY IN VYB Hz
VRY VRY IN VRY IN
KVAr KVArh KVAr KVArh A x1000 KVA KVAh
KVAr KVArh KVAr KVArh
Sys Ph R
KAh
Sys Ph R
Sys Ph R
KAh
Sys Ph R
VYB
KVA
Hz
KVAh
Min Ph Y
%THD
Pressing the " Down" key will return to
KAh KAh

A x1000 A x1000 A x1000


Min Ph Y
%THD KW x1000
the Enter Password stage.
A x1000
VYB Hz VYB Hz VYB Hz VBR P.F.
VYB Hz
KVA KVAh KVA KVAh KVA KVAh KW x1000 Angle KWh
KVA KVAh
Min Ph Y Min Ph Y Min VBR P.F. Max Ph B
Min Ph Y
%THD
Ph Y
%THD
%THD %THD Angle KWh Demand Pressing the “ Up” key exits the
Max Ph B
KW x1000 KW x1000 KW x1000 KW x1000 Demand Password menu and returns operation
VBR P.F. VBR P.F.
Angle KWh
VBR
Angle
P.F.
KWh Angle KWh
VBR
Angle
P.F.
KWh to the measurement reading mode.
Max Ph B Max Ph B Max Ph B
Max Ph B
Demand Demand Demand
Demand

New / Change Password


V x1000
VRY IN
KVAr KVArh
V x1000
Sys Ph R
KAh
(*Decimal point indicates that this will be flashing).
VRY IN
KVAr KVArh A x1000
Sys Ph R VYB Hz
KAh KVA
Min
KVAh
Ph Y
Pressing the “ Down” key will scroll the value of the
A x1000
VYB Hz
%THD first digit from 0 through to 9, the value will wrap from 9
KVA KVAh
Min Ph Y KW
VBR
x1000
P.F.
round to 0.
%THD
Angle KWh
KW x1000 Max Ph B
VBR P.F. Demand
Pressing the “ Up” key to advance the operation to
3440 Setup Parameter Screen Angle
Max
KWh
Ph B
the next digit and sets the first digit, in this case to “2”
Demand

codE (PassWord) Exit from setup Parameter to Main Display

SEL (Select)
V x1000 New / Change Password, first digit entered, prompting for
VRY IN
KVAr KVArh second digit. (*Decimal point indicates that this will be
Sys Ph R
KAh flashing).
SYS PArA Ser PArA rSEt Out PArA
quit Enter Password, second digit entered, prompt for third A x1000
A (System Parameter) (Serial Comm.Parameter) (Reset Parameter) (Output Parameter) A V x1000
digit. VYB Hz
(Exit Menu) VRY IN KVA KVAh
(Sec 3.2.1) (Sec 3.2.2) (Sec 3.2.3) (Sec 3.2.4) (Sec 3.2.5) KVAr
Sys
KVArh
Ph R (* Denotes that decimal point will be flashing). Min Ph Y Pressing the “ Down” key will scroll the value of the
%THD
KAh second digit from 0 through to 9, the value will wrap from
KW x1000
A
VYB
x1000 VBR P.F. 9 round to 0.
KVA
Hz
KVAh Use the “ Down” key to scroll the value of the third Angle KWh
SYS Addr none (No Parameter), Max Ph B
(System Type / Network)
Min Ph Y
%THD digit from 0 through to 9, the value will wrap from 9 Demand
(Modbus Address) ALL (All Parameter),
(Sec 3.2.1.1) (Sec 3.2.2.1) d (Demand), rL1 & rL2 x1000
round to 0. Pressing the “ Up” key to advance the operation to the
B AnL Out quit KW

E (Energy), (Relay 1 & 2) (Analog Output) (Exit Menu)


VBR
Angle
P.F.
KWh
next digit and sets the second digit, in this case to “1”
hi (Max values), (Sec 3.2.4.1.1) (Sec 3.2.4)
Max Ph B
(Sec 3.2.4.1.3) Demand

UP Lo (Min values),
hr (Run Hour & On Hour), Press the “ Up” key to advance to next digit.
(PT Primary) br
(Sec 3.2.1.2) (Baud Rate) Intr (No. of Interrupts)
(Sec 3.2.2.2) Select any one option using
“Down” key . B New / Change Password, second digit entered,
PUL Lt AnL1 V x1000
prompting for third digit. (*decimal point indicates that
(Pulse Output) (Limit Output) (Analog1 parameter VRY IN
US (Sec 3.2.4.1.1.1) (Sec 3.2.4.1.1.2) selection)
KVAr
Sys
KVArh
Ph R this will be flashing).
(PT Secondary) Pr (Acc. To Table) KAh

(Sec 3.2.1.3) (Parity Bits) (Sec 3.2.4.1.3.1) Enter Password, third digit entered, prompt for fourth A
VYB
x1000
Hz
(Sec 3.2.2.3)
V
VRY
x1000
IN digit. KVA KVAh Pressing the “ Down” key will scroll the value of the
Min
Para. Selection Para. Selection
KVAr
Sys
KVArh
Ph R (* Denotes that decimal point will be flashing).
Ph Y
%THD third digit from 0 through to 9, the value will wrap from 9
(i-E, E-E, i-rE, E-rE, (Acc. To Table) KAh
round to 0.
AP KW x1000
A-E, A-H) (Sec 3.2.4.1.1.2.1) A x1000 P.F.
(CT Primary) (Sec 3.2.4.1.1.1.1)
VBR

(Sec 3.2.1.4) AnL2 VYB


KVA
Hz
KVAh
Use the “ Down” key to scroll the value of the fourth Angle
Max
KWh
Ph B
(Analog 2 parameter Min Ph Y digit from 0 through to 9, the value will wrap from 9 Demand
selection) %THD Pressing the “ Up” key to advance the operation to
(Acc. To Table ) round to 0. the next digit and sets the third digit, in this case to “5”
Limit Config. KW x1000

AS dur (Sec 3.2.4.2.3.2) VBR P.F.

(Pulse Duration) Selection Angle KWh


(CT Secondary) (Hi-E, Hi-d, Max Ph B

(Sec 3.2.1.5) 60,100,200 Lo-E, Lo-d) Demand


Press the “ Up” key to advance to verification of the
(Sec 3.2.4.1.1.1.2) (Sec 3.2.4.1.1.2.2)
password.
New / Change Password, third digit entered, prompting
dit V x1000
for fourth digit. (* denotes that decimal point will be
(Demand Integ.Time) rAt trip (Trip Point) VRY IN
flashing).
KVAr KVArh
(Sec 3.2.1.6) (Pulse Divisor Rate) 10% to 100% Sys Ph R
1, 10, 100, 1000 (Sec 3.2.4.1.1.2.3) KAh
(Sec 3.2.4.1.1.1.3) A
VYB
x1000
Hz
Pressing the “ Down” key will scroll the value of the
Auto V x1000 Enter Password, fourth digit entered, awaiting
KVA
Min
KVAh
Ph Y
fourth digit from 0 through to 9, the value will wrap from
(Auto Scrolling) HYS (Hysterisy s) VRY IN %THD 9 round to 0.
0.5% to 50%
KVAr KVArh verification of the password.
(Sec 3.2.1.7) Sys Ph R KW x1000
B (Sec 3.2.4.1.1.2.4)
KAh VBR P.F.
Angle KWh
A
VYB
x1000
Hz
Max Ph B Pressing the “ Up” key to advance the operation to
KVA KVAh
Demand
the “New Password Confirmed” and sets the fourth digit,
nC Min Ph Y
(Noise Current Cut-off) %THD in this case to “3”.
En-d : UP KEY
(Sec 3.2.1.8) KW x1000
(Energizing Delay time) VBR P.F.
1s to 10s Angle KWh
Max Ph B
(Sec 3.2.4.1.1.2.5)
: DOWN KEY Demand

A
dE-d
B (De-energizing Delay time) 1s
to 10s
(Sec 3.2.4.1.1.2.6)

3 4
3.2.1 System parameters Selection 3.2.1.5 Current Transformer Secondary Value
New Password confirmed.
V
VRY
x1000
IN 3.2.1.3 Potential Transformer secondary Value
KVAr
Sys
KVArh
Ph R 3.2.1.1 System Type This screen is used to set the secondary value for
KAh
Pressing the “ Down” key will return to the The value must be set to the nominal full scale secondary voltage which will be obtained from the V Current Transformer. Secondary value “5” for 5A or
x1000
A
VYB
x1000
Hz
“New/Change Password”. This screen is used to set the system type . Transformer when the potential transformer(PT)primary is supplied with the voltage defined in 3.2.1.2 VRY IN
“1” for 1A can be selected. Pressing “ Up” key
KVA KVAr KVArh
KVAh
Min Ph Y V x1000 System type ”3” for 3 phase 3 wire & “4” for 3 phase potential transformer primary voltage.The ratio of full scale primary to full scale secondary is defined Sys Ph R
KAh accepts the present value and advances to the
%THD VRY IN
KVAr
Sys
KVArh
Ph R
4 wire system. as the transformer ratio. A x1000
Demand integration Time (See Section 3.2.1.6)
KW x1000
VBR P.F. Pressing the “ Up” key will advances to the KAh
VYB Hz

Angle KWh Pressing the “ Up” key accepts the present KVA KVAh

Max Ph B Menu selection screen.(see section 3.2). A x1000


Pressing the “ Up” key accepts the present value Min Ph Y
Pressing the “ Down” key will enter the CT
Demand
VYB
KVA
Hz
KVAh
value and advances to the “Potential transformer %THD

Min Ph Y
primary value Edit” menu (see section 3.2.1.2) and advances to the “Current Transformer Primary KW x1000
Secondary value edit mode and scroll the value
%THD V x1000 VBR P.F.
VRY IN Value edit” menu. (See Section 3.2.1.4) Angle KWh
through the values available.
KW x1000
P.F.
Pressing the “ Down” key will enter the system type KVAr
Sys
KVArh
Ph R
Max Ph B
Demand
VBR
Angle KWh
edit mode and scroll the values through values available . KAh Note that the range of instrument is from 240 to 480V
Max Ph B
A x1000 for 415 VL-L. Please refer the table below for different ranges. Pressing the “ Up” key will advance to the CT
Demand VYB Hz

Pressing the “ Up” key advances to the system KVA KVAh Secondary value confirmation.
3.2 Menu selection. Min Ph Y
%THD
Pressing the “ Down” key will enter the “Potential
type confirmation menu. Transformer Secondary Value Edit” mode.
KW x1000
CT Secondary value confirmation
3.2.1 System Parameter selection screen. VBR
Angle
P.F.
KWh
Down” key will scroll the value of the most significant digit
V x1000
Max Ph B
Demand
From available range of PT secondary value VRY
KVAr
IN
KVArh This screen will only appears following an edit of CT
Sys Ph R
System Type Confirmation Pressing the “ Up” key accepts the present value KAh secondary value .
V x1000
This screen is used to select the different system
VRY IN at the cursor position and advances the cursor to the A x1000

KVAr KVArh Parameter like “system type,””CT Ratio”,”PT Ratio”, VYB


KVA
Hz
KVAh If secondary value shown is not correct, pressing the
Sys Ph R
This screen will only appear following the edit of next less significant digit. Min Ph Y
KAh
Pressing the “ Up” key allows the user to set
V x1000 %THD Down key will return to CT secondary edit stage by
VRY IN
A
VYB
x1000
Hz
KVAr KVArh system type. If system type is to be Downed again, Potential Transformer secondary ranges for various Input Voltages KW x1000
blanking the bottom line of the display.
KVA
Min
KVAh Different system parameters. Sys Ph R
KAh
VBR
Angle
P.F.
KWh
Ph Y
%THD
(see section 3.2.1.1 to 3.2.1.8) A x1000
110V L-L (63.5V L-N) 100 - 120V L-L (57.73V - 69.28V L-N) Max Ph B
Demand Pressing “ Up” key sets the displayed value and
KW x1000
VYB Hz
Pressing the “ Up” key sets the displayed value and 230V L-L (133.0V L-N) 121 - 239V L-L (69.86V - 138V L-N)
VBR P.F.
KVA
Min
KVAh
will advance to Demand integration Time Edit menu.
Angle KWh
Ph Y
%THD will advance to “Potential Transformer Primary Value 415V L-L (239.6V L-N) 240 - 480V L-L (138.56V - 277.12V L-N) (See Section 3.2.1.6)
Max Ph B
Demand
Pressing the “ down” key will advance to KW x1000 Edit” menu. (See section 3.2.1.2)
VBR P.F.
Communication selection screen (see section 3.2.2) Angle KWh
Max Ph B Note : the flashing decimal point indicates the cursor position, a steady decimal point will be present
Demand
to identify the scaling of the number until the cursor position coincides with the steady decimal point 3.2.1.6 Demand Integration Time
Pressing the “ Down” key will return to the system type
edit stage by blanking the bottom line of the display position. At this stage the decimal point will flash.
When the least significant digit has been set pressing the “ Up” key will advance to the V x1000
This screen is used to set the period over which
VRY IN
“Potential Transformer secondary Value Confirmation” stage. KVAr KVArh current and power readings are to be integrated
Sys Ph R
3.2.2 Communication Parameter selection screen. KAh
The Unit of displayed Readings is minutes.
Potential Transformer Secondary Value Confirmation A
VYB
x1000
Hz

This screen is used to select the different communication 3.2.1.2 Potential Transformer Primary Value V x1000
KVA
Min
KVAh
Ph Y
P. ressing the “ Down” key will scroll through the
V x1000
parameters like “Address selection”,”RS485 Parity selection”,
VRY
KVAr
IN This screen will only appear following an edit of the %THD
Folliowing Options 8,15,20,30.
VRY
KVAr
IN
KVArh The nominal full scale voltage which will be displayed as the Line to Line voltages for all system types. Sys
KVArh
Ph R
Potential Transformer Secondary Value. KW x1000
Sys Ph R
”Rs485 baud rate” The values displayed represent the voltage in kilovolts (note the x1000 enunciator). KAh VBR P.F.
KAh
A x1000
Angle
Max
KWh
Ph B Pressing the “ Up” key will advance to Demand
A
VYB
x1000
Hz
VYB
KVA
Hz
KVAh
If the scaling is not correct, pressing the “ Down” Demand
Integration confirmation screen.
KVA
Min
KVAh Pressing the “ Up” key allows the user to set different Min Ph Y
%THD key will return to the “Potential Transformer Secondary
Ph Y
%THD
Communication parameters KW x1000 Value Edit”
KW
VBR
x1000
P.F.
(see section 3.2.2.1 to 3.2.2.3) Pressing the “ Up” key accepts the present value VBR
Angle
P.F.
KWh
Max
Angle
Max
KWh
Ph B and advances to the “potential Transformer secondary Ph B
Demand Pressing the “ Up” key sets the displayed value Demand Integration Time value confirmation
Demand
Pressing the “ down key will advance to Reset parameter Value edit” menu. (See Section 3.2.1.3) and will advance to the current Transformer Primary V x1000
Pressing “ Up” key sets the displayed value and
VRY IN

Screen. (see section 3.2.3) V x1000 Value (See Section 3.2.1.4) KVAr
Sys
KVArh
Ph R will advance to scroll screen.
VRY
KVAr
IN
KVArh Pressing the “ Down” key will enter the “Potential KAh
Sys Ph R
KAh Transformer Primary Value Edit” mode. A x1000
(See Section 3.2.1.7)
VYB Hz
A x1000 KVA KVAh
VYB Hz Min Ph Y
KVA KVAh Initially the “multiplier must be selected, pressing the “ %THD

3.2.1.4 Current Transformer Primary Value


Min Ph Y
%THD Down” key will move the decimal point position to the KW
VBR
x1000
P.F.
KW x1000
right until it reaches # # # .# after which it will return to Angle KWh
3.2.3 Reset Parameter selection screen. VBR P.F.
The nominal Full Scale Current that will be displayed as the Line currents. This screen enables the
Max Ph B
Angle
Max
KWh
Ph B
#. # # #. Demand

Demand user to display the Line currents inclusive of any transformer ratios, the values displayed represent
V x1000
This screen is used to Reset the different parameters . Pressing the “ Up” key accepts the present the Current in Amps.
VRY
KVAr
IN
KVArh
multiplier (decimal point position) and advances to the
Sys Ph R
KAh “potential Transformer primary Digit Edit” mode. Pressing the “ Up” key accepts the present value and advances to the Current Transformer
A x1000 Pressing the “ Up” key allows the user to Reset different Secondary Value (See Section 3.2.1.5) 3.2.1.7 Auto Scrolling :
VYB Hz
KVA KVAh
Min Ph Y system parameters (see section 3.2.3.1)
%THD Potential Transformer primary Digit Edit Pressing the “ Down” key will enter the “Current
V x1000 This screen allows user to enable screen scrolling.
KW x1000 Transformer Primary Value Edit” mode. This will scroll the VRY IN
VBR P.F. V x1000
Pressing the “ Down” key will scroll the value of KVAr KVArh
Angle KWh VRY IN V x1000 value of the most significant digit from 0 through to 9, Sys Ph R
Auto scrolling Edit.
Max Ph B KVAr
Sys
KVArh
Ph R the most significant digit from 0 through to 9 unless VRY IN KAh
Demand
Pressing the “ down key ” will advance to Output KAh
KVAr KVArh unless the presently displayed Current Transformer A x1000
the presently displayed Potential Transformer Primary Sys Ph R
VYB Hz
Pressing “ Up” key accepts the present status and
A x1000
KAh
Primary Value together with the Potential Transformer KVA KVAh
Option selection screen (see section 3.2.4). VYB Hz Value together with the Current Transformer Primary A x1000 Min Ph Y
advance to the Low Current noise cutoff
KVA KVAh VYB Hz Primary Value results in a maximum power of greater %THD
Min Ph Y Value, previously set, would result in a maximum power KVA KVAh
(See Section 3.2.1.8).
%THD Min Ph Y than 666.6 MVA in which case the digit range will be KW x1000

x1000 of greater than 666.6 MVA per phase in which case %THD VBR P.F.
KW
VBR P.F. restricted, the value will wrap. Example: If primary value Angle KWh

Angle KWh the digit range will be restricted. KW x1000 Max Ph B

Max Ph B
VBR
Angle
P.F.
KWh
of PT is set as 692.8kV L-L (max value) then primary value of Demand

Demand
Pressing the “ Up” key accepts the present value Max Ph B
Demand
Current is restricted to 1157A.
3.2.4 Output Option selection screen. at the cursor position and advances the cursor to the
next less significant digit. Pressing the “ Up” key will advance to the next less
significant digit. (* Denotes that decimal point will be
This screen will allow the user to select different
V x1000 The PT Primary value can be set from 100V L-L to 692.8 kV L-L. flashing).
VRY IN Output options Like “Relay1”,”Relay2”,”Analog” Output. V x1000 Pressing the “ Down” key will enter the “Auto Screen
KVAr KVArh
Sys Ph R
KAh
Note : the flashing decimal point indicates the cursor position, a steady decimal point will be present The “Maximum Power” restriction of 666.6 MVA refers to 120% of nominal current and 120% of
VRY
KVAr
IN
KVArh Scrolling Edit” and toggle the status ‘Yes’ and ‘No’.
Sys Ph R
A x1000
to identify the scaling of the number until the cursor position coincides with the steady decimal point nominal voltage, i.e, 462.96 MVA nominal power per phase. KAh
VYB Hz Pressing the “ Up” key allows the user to select & position. At this stage the decimal point will flash. A x1000
KVA KVAh VYB Hz
Min Ph Y
%THD
Configuare the output option (see section 3.2.4.1) When the least significant digit had been set, pressing the “ Up” key will advance to the KVA
Min
KVAh
Ph Y Pressing the “ Up” key will select the status displayed
KW x1000 “Current Transformer Primary Value Confirmation” stage. %THD
and advance to the Low Current noise cutoff
VBR P.F. x1000
KW
Angle KWh VBR P.F. (See Section 3.2.1.8)
Max Ph B When the least significant digit has been set pressing the “ Up” key will advance to the The minimum value allowed is 1, the value will be forced to 1 if the display contains zero when the Angle KWh
Demand
Pressing the “ down key will advance to Quit screen. “Potential Transformer Primary Value Confirmation” stage.
Max Ph B
“ Up” key is pressed. Demand

(see section 3.2.5)


Screen showing display of 0.120 kV i.e. 120 Volts indicating steady decimal point and cursor Current Transformer Primary Value Confirmation.
flashing at the “hundreds of volts” position.
This screen will only appear following an edit of the Current
Potential Transformer Primary Value Confirmation V x1000 Transformer Primary Value . 3.2.1.8 Low Current noise cutoff.
V x1000
VRY
KVAr
IN
KVArh
This screen allows the user to set Low noise current cutoff in mA.
3.2.5 Quit screen. VRY
KVAr
IN
KVArh
This screen will only appear following an edit of the Sys Ph R
KAh
If the scaling is not correct, Pressing the “ Down” key Low current cutoff Edit.
Sys Ph R
KAh Potential Transformer Primary Value. A x1000 will return to the “ Current Transformer Primary Value Edit”
VYB Hz V x1000
A x1000 KVA KVAh stage with the most significant digit highlighted (associated VRY IN
VYB Hz
If the scaling is not correct, pressing the “ Down” Min Ph Y KVAr KVArh Pressing
. “ Up” key accepts the present value and
V x1000 KVA KVAh %THD decimal point flashing) and the bottom line of the display Sys Ph R
VRY IN Min Ph Y
key will return to the “Potential Transformer Primary KAh advance to Energy output Selection.
KVAr KVArh
Pressing the “ Up” key will allow the user to Quit from menu %THD KW x1000
will be blanked.
Sys Ph R
KAh x1000 Value Edit” stage.
VBR P.F. A x1000 (See section 3.2.1.9)
& return to measurement screen. KW
VBR P.F.
Angle
Max
KWh
Ph B
VYB
KVA
Hz
KVAh
A x1000 Min
Angle KWh Demand Ph Y
VYB
KVA
Hz
KVAh
Max Ph B Pressing the “ Up” key sets the displayed value and %THD
Demand
Min Ph Y
%THD will advance to the “Current Transformer Secondary Value KW x1000
P.F.
Pressing the “ Down” key will enter the “Low current
VBR
x1000 Edit” menu. (See Section 3.2.1.5) Angle KWh noise cutoff Edit” mode and scroll the “Value” through 0 & 30
KW
Pressing the “ Up” key sets the displayed value Max Ph B
VBR
Angle
P.F.
KWh Demand and wrapping back to 0. Setting 30 will display measured
Max Ph B and will advance to the Potential Transformer secondary currents as 0 below 30 mA.
Demand Note : 0.120 kV i.e. 120 VL-L Value (See Section 3.2.1.3)

5 6
5
Low current noise cutoff Confirmation. V x1000
Enter Address, second digit entered, prompt for third digit
VRY IN
V
VRY
x1000
IN
KVAr
Sys
KVArh (* Denotes that decimal point will be flashing).
Ph R
KVAr KVArh KAh
Sys Ph R Reset option select, (Resets ALL resettable parameter) Reset hI (Max) Confirmation.
KAh
pressing the “ Down” key will re-enter the “Low current A x1000
V x1000 V x1000
VYB Hz Use the “ Down” key to scroll the value of the third digit VRY IN IN
A
VYB
x1000
Hz Noise cutoff Edit” mode. KVA
Min
KVAh
Ph Y
KVAr KVArh
The user has scrolled through to the “ALL” .
VRY
KVAr KVArh
KVA
Min
KVAh %THD
Sys Ph R
KAh
Sys Ph R
KAh
Pressing the “ Down” key will re-enter the
Ph Y
%THD
KW x1000 A x1000 A x1000
“Reset option Select mode.
KW x1000
VBR P.F. VYB Hz Pressing “ Up” key will select the value and VYB Hz
VBR P.F. Pressing “ Up” key set displayed value and Angle
Max
KWh
Ph B
KVA
Min
KVAh
Ph Y advance to the “Reset ALL Confirmation” Mode &.
KVA
Min
KVAh
Angle KWh Ph Y
Max Ph B Advance to the energy output selection Demand %THD
Will reset all resettable parameter.
%THD
Demand
Pressing “ Up” key will jump back to the
Demand
(See section 3.2.1.9) KW
VBR
x1000
P.F.
KW
VBR
x1000
P.F. Reset Parameter selection screen (see section 3.2.3).
Angle KWh Angle KWh
Max Ph B Max Ph B
Demand Max Demand
Demand
7

3.2.1.9. Energy Display on modbus V x1000 Address confirmation Screen.


VRY IN
KVAr KVArh
Sys Ph R
This screen enable user to set energy in terms of Wh / KWh / MWh on RS 485 Output depending as per the KAh
This Screen confirms the Address set by user .
requirement .Same applicable for all types of energy. A x1000
VYB
KVA
Hz
KVAh Press the “ Up” key to advance to next Screen Reset ALL Confirmation. Reset option select, (Reset Lo)
Pressing “ Up” key accepts the presents value Min Ph Y
%THD “Rs485 Baud Rate” (See Section 3.2.2.2)
V
VRY
x1000
IN
V x1000
IN
VRY
KVAr
V x1000 and advances to the “Energy digit reset count”menu KW x1000 Sys
KVArh
Ph R Pressing the “ Down” key will re-enter the KVAr
Sys
KVArh
Ph R The user has scrolled through to the “Lo” (Min)
VRY IN KAh
VBR P.F.
KVAr KVArh (See section 3.2.1.10). Angle KWh Reset option Select mode. KAh

Sys Ph R Max Ph B Pressing the “ Down” key will reenter the “Address A x1000 A x1000
Pressing the “ Down” key will enter the “Energy Display Demand
Edit” mode.
VYB
KVA
Hz
KVAh
VYB
KVA
Hz
KVAh
Pressing “ Up” key will select the value and
A x1000
VYB Hz
On Modbus Edit” mode and scroll the value through the values
Min Ph Y
%THD
Pressing “ Up” key will jump back to the Min Ph Y advance to the “Reset Lo Confirmation” Mode &
%THD
KVA
Min
KVAh
Ph Y 1,2 & 3 wrapping back to 1 KW x1000
Reset Parameter selection screen (see section 3.2.3). x1000
Will reset minimum values of Voltage & Current Avg.
KW
%THD VBR P.F.
VBR P.F. appeared at Input.
KW x1000
1 : Energy In Wh Angle
Max
KWh
Ph B
Angle
Max
KWh
Ph B
VBR P.F. 2 : Energy in KWh 3.2.2.2 RS 485 Baud Rate : Demand
Demand
Angle KWh
Max Ph B 3: Energy in MWh.
Pressing the “ Up” key advances to the “Energy Display This screen allows the user to set Baud Rate of RS 485 port.
On Modbus Confirmation” menu. V x1000 The values displayed on screen are in kbaud ..
VRY IN
KVAr KVArh
Sys Ph R

Energy Display On Modbus Confirmation.


KAh
Pressing “ Up” key accepts the present value and V x1000
Reset option select, (Reset A Demand, KVA Demand Reset Lo Confirmation
A x1000
V x1000 VYB Hz advance to the Parity Selection (See Section 3.2.2.3) VRY
KVAr
IN
KVArh
Parameters KW demand (Import/Export)) V
VRY
x1000
IN
VRY IN KVA KVAh KVAr KVArh
KVAr KVArh This screen will only appear following an edit of the Min Ph Y
%THD
Sys Ph R
KAh Sys Ph R Pressing the “ Down” key will re-enter the
Sys Ph R KAh
Energy Display On Modbus. KW x1000
A x1000 The user has scrolled through to the “d” . “Reset option Select mode.
A x1000
VBR P.F. Pressing the “ Down” key will enter the “Baud Rate VYB
KVA
Hz
KVAh
A
VYB
x1000
Hz
VYB Hz
Pressing the “ Down” key will enter the “Energy Display Angle KWh
Edit” mode and scroll the value through 2.4, 4.8, 9.6 , 19.2 Min Ph Y KVA KVAh
KVA
Min
KVAh
Ph Y On Modbus Edit” Edit” stage by blanking the bottom line of the
Max Ph B
Demand
%THD Pressing “ Up” key will select the value and Min Ph Y
%THD Pressing “ Up” key will jump back to the
%THD and back to 2.4 resets all Demand parameters.
display.
KW
VBR
x1000
P.F. KW x1000 Reset Parameter selection screen (see section 3.2.3).
KW x1000 Angle KWh VBR P.F.
VBR P.F. Max Ph B Angle KWh
Angle KWh Pressing “ Up” key sets the displayed value and Demand
Max Ph B
Demand
Max Ph B
will advance to the “Energy digit reset count” menu.
RS 485 Baud Rate confirmation :
(See section 3.2.1.10) V x1000
VRY IN
KVAr
Sys
KVArh
Ph R Pressing “ Down” key will be re-enter into the.
KAh
Baud Rate Edit mode
Note : Default value is set to ‘1’ i.e. Energy on Modbus will be in A x1000
Reset Demand parameters Confirmation.
terms of Wh/VArh/VAh/Ah resp. VYB
KVA
Hz
KVAh Reset option select, hr (ON Hour & Run Hour)
Min Ph Y
%THD
Pressing the “ Up” key will select the value and advances V
VRY
x1000
IN
V
VRY
x1000
IN
to the Parity Selection (See Section 3.2.2.3). KVAr KVArh Pressing the “ Down” key will re-enter the KVAr KVArh
3.2.1.10 Energy Digit reset count : KW
VBR
x1000
P.F.
Sys Ph R
KAh “Reset option Select mode.
Sys Ph R
KAh The user has scrolled through to the “hr”
Angle KWh
A x1000 A x1000
Max Ph B
VYB Hz VYB Hz
Demand KVA KVAh KVA KVAh Pressing “ Up” key will select the value and
This screen enables user for setting maximum energy count after Min Ph Y
Pressing “ Up” key will jump back to the Min Ph Y
%THD %THD
Demand advance to the “Reset hr Confirmation” Mode &
V x1000 which energy will rollback to zero depends upon setting of Wh,KWh, Reset Parameter selection screen (see section 3.2.3).
VRY IN
KVArh & MWh.
KW
VBR
x1000
P.F.
KW
VBR
x1000
P.F.
Will reset On hour & Run Hour both.
KVAr
Sys Ph R Angle KWh Angle KWh
Pressing the “ Up” key sets the displayed value and will jump Max Ph B Max Ph B
A x1000 Demand Max Demand
Demand
VYB Hz
KVAh
back to the system parameter selection (See Section 3.2.1) 3.2.2.3 RS 485 Parity Selection :
KVA
Min Ph Y
%THD
Pressing the “ Down” key will enter the Energy digit reset This screen allows the user to set Parity & number of stop bits of RS 485 port.
KW x1000
count edit mode. This will scroll the value of reset count from
VBR P.F. 7 to 14 for Wh,from 7 to 12 for KWh & from 7 to 9 for MWh. Pressing “ Up” key accepts the present value and
Angle KWh
Max Ph B
Ex. If energy display on modbus is set Wh & It will set Energy digit V x1000 advance to Menu selection (see section 3.2).
VRY
KVAr
IN Reset option select, (Resets all Energies) Reset hr Confirmation
count to 10 then energy will reset after “9,999,999,999” & then will Sys
KVArh
Ph R V x1000
V x1000
VRY IN
rollback to zero. KAh
Pressing the “ Down” key will enter the “Parity & stop bit VRY
KVAr
IN
KVArh The user has scrolled through to the “E” Energy KVAr
Sys
KVArh
Pressing the “ Down” key will re-enter the
A x1000 Sys Ph R Ph R
VYB Hz Edit” mode and scroll the value through KAh
value. KAh
“Reset option Select mode.
Pressing “ Up key “ will advance to Energy digit reset count confirmation screen. KVA KVAh
A x1000
Min Ph Y A x1000
Pressing the “ Down” key will re-enter Energy digit reset count edit mode. %THD VYB Hz
VYB Hz

odd : odd parity with one stop bit KVA KVAh


Pressing “ Up” key will select the value and
KVA
Min
KVAh
Ph Y Pressing “ Up” key will jump back to the
Pressing the “ Up” key sets the displayed value and will jump back to the system parameter selection KW x1000 Min Ph Y
%THD
Demand
no 1 : no parity with one stop bit
%THD
(See Section 3.2.1)
VBR
Angle
P.F.
KWh advance to the “Reset Energy Confirmation” Mode. x1000
Reset Parameter selection screen (see section 3.2.3).
KW x1000 KW
Max Ph B
no 2 : no parity with two stop bit & resets all Energies (Import Enegy, Export Energy VBR P.F.
Note : 1) Default value is set to “14” i.e if energy count crosses 14 digit it will rollback to zero. Demand VBR P.F.
KWh Angle KWh
Angle
Import reactive, Export reactive, Apparent Energy
E : even parity with one stop bit
Max Ph B
2) Energy displays on modbus is set to (2) & energy digit reset count is set to 12.Energy screen
Max Ph B
Max Demand
Demand
Demand

on display will show “-------” i.e Energy overflow .when energy crosses the 11 digit count. Ampere Hour)
3) Energy displays on modbus is set to (3) & energy digit reset count is set to 9.Energy screen
on display will show “-------” i.e Energy overflow .when energy crosses the 8 digit count.
3.2.2 Communication Parameter Selection : V x1000 RS 485 Parity confirmation :
VRY IN
KVAr KVArh

3.2.2.1 Address Setting : This screen applies to the RS 485 output only. Sys Ph R
Pressing “ Down” key will be re-enter into Parity Edit mode . Reset option select, (Reset Number of Interrupt)
KAh Reset Energy Confirmation. V x1000
V x1000
This screen allows the user to set Rs485 parameter for instruments A x1000 VRY IN VRY IN
VYB
KVA
Hz
KVAh
KVAr
Sys
KVArh
Ph R Pressing the “ Down” key will re-enter the “Reset
KVAr
Sys
KVArh
Ph R
The user has scrolled through to the “intr”
Min Ph Y Pressing the “ Up” key will set the value. KAh KAh
%THD option” mode.
V x1000
The range of allowable address is 1 to 247 . KW x1000
A
VYB
x1000
Hz
A
VYB
x1000
Hz Pressing “ Up” key will select the value and
VRY IN KVA KVAh
KVAr KVArh
VBR
Angle
P.F.
KWh Pressing the “ Up” key again will jump back to the
KVA
Min
KVAh
Ph Y
Min Ph Y advance to the “reset Interrupt Confirmation” Mode &
Sys Ph R Max Ph B %THD Pressing “ Up” key will jump back to the %THD
Demand
Will reset number of Auxiliary supply interruption count.
KAh Enter Address, prompt for first digit. Demand communication parameter selection menu (see section 3.2.2).
A x1000
KW x1000 Reset Parameter selection screen (see section 3.2.3). KW
VBR
x1000
P.F.
VYB Hz (* Denotes that decimal point will be flashing). VBR
Angle
P.F.
KWh Angle KWh
KVA KVAh Max Ph B
Max Ph B
Min Ph Y
Demand Max Demand
Demand
%THD

KW
VBR
x1000
P.F. Press the “ Down” key to scroll the value of the first digit 3.2.3 Reset Parameter Selection :
Angle KWh
Max Ph B
Demand
3.2.3.1 Resetting Parameter
Press the “ Up” key to advance to next digit. The following screens allow the users to reset the all Energy , Lo(Min), hi(Max),Demand,Run hour, .
On hour, No.of Interrupts Reset option select, (Reset Hi)
V x1000 V x1000
Reset Interrupt Confirmation
Reset (None) VRY IN VRY IN
KVAr KVArh The user has scrolled through to the “Hi” (Max) KVAr KVArh

V
Enter Address, first digit entered, prompt for second digit V
VRY
x1000
IN
Sys Ph R
KAh
Sys Ph R
KAh Pressing the “ Down” key will re-enter the
x1000
VRY IN
(* Denotes that decimal point will be flashing).
KVAr KVArh
Pressing “ Up” key advances to Reset Parameter A “Reset parameter Selection”(see section 3.2.3).
KVAr KVArh
Sys Ph R A
VYB
x1000
Hz Pressing “ Up” key will select the value and VYB
x1000
Hz
Sys Ph R
KAh
selection screen (see section 3.2.3) KVA KVAh KVA KVAh
KAh
A x1000 Min Ph Y advance to the “Reset Hi Confirmation” Mode
Mode.& Min Ph Y
VYB Hz %THD
Demand %THD
Demand
A x1000
KVA KVAh Will reset Maximum (Hi) values of Voltage & Current Avg.
VYB Hz
Min Ph Y Pressing the “ Down” key will enter the “Reset KW x1000 KW x1000 Pressing “ Up” key will jump back to the
KVA KVAh
Use the “ Down” key to scroll the value of the second digit %THD VBR P.F. appeared at input. VBR P.F.
Min Ph Y
%THD option” mode and scroll through Parameter Angle KWh Angle KWh Reset Parameter selection screen (see section 3.2.3).
KW x1000 Max Ph B Max Ph B
KW x1000 VBR
Angle
P.F.
KWh
and wrapping back to None. Max Demand
Demand Max Demand
Demand
VBR P.F.
Max Ph B
Angle KWh
Max Ph B Demand
Demand Press the “ Up” key to advance to next digit.

8
3.2.4.1.1.2.1 Assignment of Limit output (for Relay1) to parameter.
3.2.4. Output Option selection menu 3.2.4.1.1.1.1 Assignment of Energy to pulse output (Relay 1) :
This screen is for Limit output mode selection. It allows the user to set Limit output corresponding measured
3.2.4.1 Configuration of Output This screen allows the user to assign pulse output to energy (for Relay 1) value . Refer Table 2“ Parameter for Analog & Limit output “ for assignment.
The second digit entered, prompt for third digit
This screen applies to the Relay1 Output option Selection . Pressing “ Up” key accepts the present setting V x1000

V x1000 Pressing “ Up” key accepts the present value and VRY IN
(* Denotes that decimal point will be flashing).
VRY IN and advance to “Pulse duration selection” V x1000
KVAr
Sys
KVArh
Ph R
KVAr KVArh Pressing “ Up” key will select the V
VRY
x1000
IN (see section 3.2.4.1.1.1.2).
VRY
KVAr
IN
KVArh
advance to the Limit1 configuration select screen. KAh
Sys Ph R
KAh
KVAr
Sys
KVArh
Ph R
Sys Ph R
KAh
(see section 3.2.4.1.1.2.2 ). A x1000

A x1000 Relay1 output selection menu(See section 3.2.4.1.1) KAh Pressing the “ Down” key will enter into edit mode VYB
KVA
Hz
KVAh
VYB Hz A x1000 Min Ph Y
KVA KVAh
pressing the “ Down” key will advance
A
VYB
x1000
Hz
and scroll through the energy setting VYB
KVA
Hz
KVAh Pressing the “ Down” key will enter the “ Limit1 output Edit” Demand
%THD Use the “ Down” key to scroll the value of the third digit
Min Ph Y KVA KVAh Min Ph Y
Demand
%THD Min Ph Y mode and scroll the values, as per Table 2, KW x1000
A - E : Apparent Energy
%THD
Demand
KW x1000 Relay2 output option below. %THD
x1000 “ Parameter for Analog & Limit Output”
VBR
Angle
P.F.
KWh
I - E : Import Energy ( Active )
VBR P.F. KW
KW x1000 Max Ph B
VBR P.F.
Angle KWh P.F. Max Demand
Demand
VBR Angle KWh
Max Ph B
Max Demand
Demand
Angle
Max
KWh
Ph B
E - E : Export Energy ( Active ) Max Ph B
Demand
Max Demand
Demand
I - rE : Import Reactive Energy Pressing the “ Up” key advance to the Limit1 output
E - rE : Export Reactive Energy confirmation screen .
A - H : Ampere Hour

This screen applies to the Relay2 Output option Selection . Limit1 output Confirmation :
Pulse output (for Relay 1) confirmation : V x1000
V
VRY
x1000
IN
Entered the value for third digit .
V x1000 V x1000 VRY IN
KVAr KVArh
KVAr
VRY
KVAr
IN
KVArh
VRY
KVAr
IN
KVArh Sys
KVArh
Ph R Pressing the “ Down” key will re-enter the “ Limit1 output Edit” Sys Ph R
Sys Ph R
KAh Pressing “ Up” key will advance to the select Sys Ph R
KAh
Pressing “ Down” key will be re-enter into edit mode . KAh
KAh

A x1000
A x1000
A x1000 A x1000 VYB Hz
VYB
KVA
Hz
Press the “ Up” key to advance to trip point
VYB
KVA
Hz
KVAh
Relay 2 output selection menu. (See section 3.2.4.1.2) VYB
KVA
Hz
KVAh
KVA
Min
KVAh
Ph Y
Pressing the “ Up” key sets the displayed value and will Min
KVAh
Ph Y confirmation Screen.
%THD
Demand
Min Ph Y
%THD
Demand
Min Ph Y
%THD
Pressing the “ Up” key will set the value and advances %THD
Demand advance to the Limit1 Configuration select screen
KW x1000
KW x1000 KW x1000
to the “ Pulse duration selection ”(see section 3.2.4.1.1.1.2). KW
VBR
x1000
P.F.
( see section 3.2.4.1.1.2.2 ) VBR P.F.
Angle KWh
VBR P.F. VBR P.F. Angle KWh
Max Ph B
Angle
Max
KWh
Ph B
pressing the “ Down” key will advance to Angle
Max
KWh
Ph B
Max Ph B
Max Demand
Demand
Max Demand
Demand
Max Demand
Demand Demand
Analog output option below.

3.2.4.1.1.2.2 Limit1 Configuration select


3.2.4.1.1.1.2 Pulse Duration Selection:
This screen is used to set the Limit1 Configuration, four different types of configuration can be selected V x1000
Value confirmation Screen.
This screen applies to the Analog Output Selection. VRY IN
V x1000 This screen applies only to the Pulsed output mode of both the relay H i - E (High Alarm & Energized Relay) KVAr
Sys
KVArh
Ph R
VRY IN
KVAr KVArh This screen allows the user to set Relay energisation time in milliseconds. H i - d (High Alarm & De-Energized Relay) KAh This Screen confirms the value set by user .
Sys Ph R
KAh Pressing “ Up” key will Select the Analog output V x1000 L o - E (Low Alarm & Energized Relay)
A
VYB
x1000
Hz
VRY IN KVA KVAh
A
VYB
x1000
Hz
selection menu (See section 3.2.4.3) KVAr KVArh L o - d (Low Alarm & De-Energized Relay) Min Ph Y
Press the “ Up” key to advance to next Screen
KVA KVAh Pulse Duration Edit. Sys Ph R
KAh (For detail refer to section 9.2)
%THD
Demand
Min Ph Y V x1000 KW x1000
%THD
Demand
VRY IN A x1000 VBR P.F.
KW x1000
KVAr
Sys
KVArh
Ph R
Pressing “ Up” key accepts the present value and VYB
KVA
Hz
KVAh
Pressing the “ Up” key accepts the present value and Angle KWh “Hysteresis selection” ( see section 3.2.4.1.1.2.4)
Max Ph B
VBR
Angle
P.F.
KWh
Pressing the “ Down” key will advance to Quit screen. KAh
advance to pulse rate selection menu (see section 3.2.4.1.1.1.3). Min Ph Y advances to the “Trip point selection”screen Max Demand
Demand
%THD
Demand
Max Ph B
Max Demand
Demand
A
VYB
x1000
Hz
(see section 3.2.4.1.1.2.3) Pressing the “ Down” key will return in edit mode
KW x1000
KVA KVAh
Min Ph Y Pressing the “ Down” key will enter the “Pulse Duration VBR
Angle
P.F.
KWh
Pressing the “ Down” key will enter the Limit1 configuration
%THD
Edit” mode and scroll the value through 60, 100, 200 and Max Ph B
Max Demand
Demand
edit mode and scroll through the Modes available .
KW x1000
VBR P.F. wrapping back to 60. Pressing the “ Up” key advances to the
Angle KWh
Max Ph B
Demand
Limit1 configuration type confirmation menu.
Pressing the “ Up” key will select the value and advances
to “Pulse Duration Confirmation”.
This screen allows the user to quit the output option 3.2.4.1.1.2.4 Hysteresis selection :
V x1000
VRY IN Limit1 Configuration Confirmation This screen applies to the Hysteresis selection.
KVAr KVArh
Sys Ph R
KAh
Pressing “ Up” key will advance to the
A x1000 Output Parameter selection (See section 3.2.4)
VYB Hz Pulse Duration Confirmation. This screen allows the user to set Hysteresis
KVA KVAh
V x1000
This screen will only appear following the edit of V x1000
Min Ph Y
VRY
KVAr
IN
KVArh
V x1000
VRY IN for relay1 output
%THD Sys Ph R This screen will only appear following an edit of the
VRY
KVAr
IN
KVArh
system type. If system type is to be changed again, KVAr KVArh
KAh Sys Ph R
Sys Ph R
KW x1000 KAh
VBR P.F. Pressing the “ Down” key will go back to A x1000 Pulse duration. KAh
The allowable range is 0.5% to 50 % of
Angle
Max
KWh
Ph B Relay1 output option (See section 3.2.4.1).
VYB
KVA
Hz
KVAh
A
VYB
x1000
Hz
pressing the “ Down” key will return to the Limit1configuration A
VYB
x1000
Hz Trip point .
Min KVA KVAh
Demand Ph Y
%THD pressing the “ Down” key will re-enter the “Pulse KVA
Min
KVAh
Ph Y
Type edit stage by blanking the bottom line of the display Min Ph Y Enter value, prompt for first digit.
%THD
Demand
KW x1000 Duration Edit” mode. Demand
%THD
(* Denotes that decimal point will be flashing).
VBR P.F. KW x1000
KW x1000
Angle KWh VBR P.F. Pressing the “ Up” key sets the displayed value and VBR
Angle
P.F.
KWh
Max Ph B Angle KWh
Demand Pressing “ Up” key set displayed value and Max Ph B will advance to “Trip point selection” Screen Max Ph B
Demand
Press the “ Down” key to scroll the value of
Max Demand
Will advance to pulse rate selection menu Max Demand
Demand
(See section 3.2.4.1.1.2.3 ) the first digit.
(See section 3.2.4.1.1.1.3) Press the “ Up” key to advance to next digit.

3.2.4.1.1 Relay1 output Selection menu :


3.2.4.1.1.1 Pulse output :
3.2.4.1.1.2.3 Trip point selection :
3.2.4.1.1.1.3 Pulse Rate
This screen is used to assign Relay1 in Pulse This screen applies to the Trip point selection. The first digit entered, prompt for second digit
This screen applies to the Relay Output option only. The screen allows user to set the energy V x1000
V x1000
output mode This screen allows the user to set Trip point for instruments VRY IN
(* Denotes that decimal point will be flashing).
VRY
KVAr
IN
KVArh
pulse rate divisor. Divisor values can be selected through 1,10,100,1000 in Wh. KVAr
Sys
KVArh
Ph R
Sys Ph R KAh
KAh
Pressing “ Up” key will advance to the The allowable range is 10% to 120% for High Alarm . A x1000
A x1000 VYB Hz
VYB
KVA
Hz
KVAh
Pulse (for Relay1) output configuration Pressing “ Up” key accepts the presents value V
The allowable range is 10% to 100% for Low Alarm . KVA KVAh Use the “ Down” key to scroll the value of
V x1000 x1000 Min Ph Y
Min Ph Y
%THD
Demand
(See section 3.2.4.1.1.1.1) VRY
KVAr
IN
KVArh and advances to the “Configuration of Output” VRY
KVAr
IN
KVArh
Demand
%THD the second digit
Sys Ph R Sys Ph R x1000
KW x1000 KAh (See section 3.2.4.1). KAh
Enter value, prompt for first digit.
KW
VBR P.F.
VBR
Angle
P.F.
KWh
Pressing “ Down” key will show “Limit”output option A x1000 A x1000
(* Denotes that decimal point will be flashing).
Angle KWh

Max Ph B VYB Hz VYB Hz


Max Ph B
Press the “ Up” key to advance to next digit.
Max Demand
Demand (See section 3.2.4.1.1.2) KVA KVAh Pressing the “ Down” key will enter the “Pulse rate divisor KVA
Min
KVAh Max Demand
Demand
Min Ph Y Ph Y
%THD Edit” mode and scroll the value through the values 1,10,100, %THD
Demand
Press the “ Down” key to scroll the values of the first digit
KW
VBR
x1000
P.F.
1000 wrapping back to 1 in Wh but in KWh & MWh pulse rate KW
VBR
x1000
P.F.
Angle
Max
KWh
Ph B
divisor is only 1 .. Angle
Max
KWh
Ph B Press the “ Up” key to advance to next digit.
Demand Pressing the “ Up” key advances to the “Pulse rate Max Demand
Demand

3.2.4.1.1.2 Limit output : Divisor Confirmation” menu.


For setting divisior value refer table 3.

This screen is used to assign Relay1 in limit output mode.


V x1000 Pulse Rate Divisor Confirmation. V x1000 The second digit entered, prompt for third digit
VRY IN VRY IN
KVAr KVArh The first digit entered, prompt for second digit KVAr KVArh
(* Denotes that decimal point will be flashing).
Sys Ph R Pressing “ Up” key will assign This screen will only appear following an edit of the
V
VRY
x1000
IN
Sys Ph R
KAh V x1000
KVAr KVArh (* Denotes that decimal point will be flashing). KAh

A x1000 Limit (for Relay1) output mode.(See section 3.2.4.1.1.2.1) VRY


KVAr
IN
KVArh Pulse rate divisor. Sys Ph R A x1000
VYB Hz Sys KAh VYB Hz
Ph R
KVA KVAh KAh KVA KVAh
Min A x1000 Min
Ph Y Ph Y
Demand
%THD
Pressing “ Down” key wil go back to the pulse option A x1000 If the Pulse rate shown is not correct, pressing the VYB Hz Use the “ Down” key to scroll the value of the second digit %THD
Demand
VYB Hz
KVA KVAh
Use the “ Down” key to scroll the value of
KW x1000 KVA KVAh “ Down” key will return to the “Pulse rate divisor Min Ph Y
KW x1000
VBR P.F. (For Relay 1) screen.(See section 3.2.4.1.1.1) Min Ph Y
%THD
Demand
VBR P.F. the third digit
Angle
Max
KWh
Ph B
%THD
Edit” stage by blanking the bottom line of the KW x1000
Press the “ Up” key to advance to next digit.
Angle
Max
KWh
Ph B
VBR P.F.
Max Demand
Demand KW
VBR
x1000
P.F. display. Angle KWh Max Demand
Demand
Max Ph B
Angle KWh
Max Ph B Max Demand
Demand
Demand Pressing “ Up” key sets the displayed value and
will advance to the “Configuration of output”.
(See section 3.2.4.1)
9 10
3.2.4.1.2 Relay 2 Output Selection : 4.Phase Rotation Error screen : 8. Analog Output ( optional ) :
Entered value for third digit .
V
VRY
x1000
IN
Configuration of Relay 2 for Pulse or Limit Output is same as Relay 1. If you Select the Pulse output Meter shows phase rotation error if the phase sequence R-Y-B (L1-L2-L3) is not maintained
KVAr KVArh option for Relay 1 same setting will be applicable for Relay 2 except assignment of energy to Pulse This module provides two d.c. isolated outputs .There are two output options
Sys Ph R
KAh
Press the “ Up” key to advance to Hysteresis output (i.e. Energy assignment of both relay can be different.)
A
VYB
x1000 1) Two 0 - 1mA outputs , internally powered .
KVA
Hz
KVAh confirmation Screen. 2) Two 4 - 20mA outputs , internally powered .
Min Ph Y
%THD
Demand
V
VRY
x1000
IN
This screen indicates that Phase sequence is incorrect.
KW x1000
P.F.
KVAr
Sys
KVArh
Ph R The 0 -1mA output module has an 0V return on each end of the 4 way connector
VBR
KAh
Angle
Max
KWh ( Please refer section 15 for connection details )
Ph B A x1000
Max Demand
Demand VYB Hz
KVA KVAh User must check this screen in order to get correct readings
Min Ph Y
%THD When meter is connected. On both modules the output signals are present on pins A1(Anolog Output 1) &
KW x1000
VBR P.F. A2 (Analog Output 2)
3.2.4.1.3 Analog Output Angle
Max
KWh
Ph B
Demand
These outputs can be individually assigned to represent any one of the measured and displayed
3.2.4.1.3.1 Parameter setting for Analog Output 1 ( Optional ) Parameters.
Hysteresis confirmation Screen. This screen is for analog output 1 only . It allows the user to set analog output 1 to corresponding measured
V
VRY
x1000
IN
All settlings are user configurable via the user interface screen. See Analog o/p selection
KVAr
Sys
KVArh This Screen confirms the percentage value set by user . parameter . Refer table2 “ Parameter for Analog & Limit output “. ( section 3.2.4.1.3 ) for details .
Ph R
KAh & Screen will appear only after edit mode of Hysteresis.
A
VYB
KVA
x1000
Hz Correct Phase sequence : * Note : Refer diagrams 1 & 2
Min
KVAh
Ph Y Press the “ Up” key to advance to next Screen V x1000
Pressing “ Up” key accepts the present value and V
VRY
x1000
IN
Demand
%THD
VRY
KVAr
IN advance to the Analog output 2 selection (see section 3.2.4.1.3.2 ). KVAr
Sys
KVArh
Ph R
KW
VBR
x1000
P.F.
Sys
KVArh
Ph R KAh This Screen indicates the phase sequence connected to
KAh
Angle KWh “Energizing delay time” ( 3.2.4.1.1.2.5 ) A
VYB
x1000
Hz meter is correct. If phase sequence is wrong this screen is useful
Max Ph B
Max Demand
Demand
A
VYB
x1000
Hz
Pressing the “ Down” key will enter the “ Analog output 1 Edit” KVA KVAh
KVA KVAh
mode and scroll the values, as per Table 2
Min Ph Y
%THD
to get correct phase sequence by interchanging connection &
Min Ph Y
%THD
“ Parameter for Analog & Limit output” KW x1000
verifying it with screen.
KW x1000 VBR P.F.
VBR P.F. Angle KWh
Max Ph B
Angle
Max
KWh
Ph B Pressing the “ Up” key advance to the Analog output 1 Demand
Demand
confirmation screen .

3.2.4.1.1.2.5 Energizing Delay time.


Diagram 1 : ( 4 -20 mA )
This screen allows the user to set Energizing Delay time for Relay 1 Limit Assigned Parameters .
0 0 ( 12 mA)
V x1000
VRY
KVAr
IN
KVArh
This Screen indicates that all three phases (Voltages) are absent.
V
VRY
x1000
IN
Pressing “ Up” key accepts the present value and Sys Ph R
KAh
KVAr
Sys
KVArh
Ph R
advance to De-energizing delay screen A x1000
KAh . VYB
KVA
Hz
KVAh
A x1000 Analog output 1 Confirmation : Min Ph Y
%THD
VYB
KVA
Hz
KVAh
Pressing the “ Down” key will enter the V
VRY
x1000
IN
KW x1000
Min Ph Y
Demand
%THD
“Energizing Delay” Edit mode and KVAr
Sys
KVArh
Ph R
This Screen will appear only after edit mode of Analog output 1 VBR P.F.
Angle KWh
KW x1000 scroll the “Value” through 1 to10 KAh
Parameter. Max Ph B
VBR P.F. A x1000 Demand
VYB Hz
270 0 ( 8 mA) 90 0 ( 16 mA)
Angle KWh
Max Ph B KVA KVAh
Max Demand
Demand Min Ph Y
%THD Pressing the “ Down” key will re-enter the “ Analog output 1 Edit”
KW x1000
VBR P.F.
Angle KWh
Max Ph B
Demand Pressing the “ Up” key sets the displayed value and will advance
to the Analog output 2 selection screen ( see section 3.2.4.1.3.2 )
Energizing delay time Confirmation. 5. Run Hour 181 0 ( 4 mA)
V
VRY
x1000
IN
This screen will appear only after edit mode of
KVAr
Sys
KVArh
Ph R
Energizing delay time V x1000 This Screen shows the total no. of hours the load is connected
KAh VRY IN

A x1000
KVAr KVArh Even if the Auxiliary supply is interrupted count of Run hour will be
VYB Hz pressing the “ Down” key will re-enter the “Energizing Sys Ph R
KAh
maintained in internal memory & displayed in the format “hours. min”.
KVA KVAh
Min Ph Y delay Edit” mode. A x1000
%THD
Demand VYB Hz For example if Displayed count is 105000.10 r-H it indicates 180 0 ( 20 mA)
KVA KVAh
KW
VBR
x1000
P.F.
Min Ph Y
%THD
105000 hours & 10 minutes.
Angle
Max
KWh
Ph B Pressing “ Up” key set displayed value and KW x1000
After 999999.59 run hours display will restart from zero.
Max Demand
Demand
will advance to Assignment of De-energizing delay time.
VBR
Angle
P.F.
KWh
To reset run hour manually see section Resetting Parameter 3.2.3.1
(See section 3.2.4.1.1.2.6 ) 3.2.4.1.3.2 Parameter setting Analog Output 2 ( Optional ) Max Ph B
Demand

This screen is for analog output 2 only . It allows the user to set analog output 2 to corresponding measured
parameter . Refer table2 “ Parameter for Analog & Limit output “.
Diagram 2 : ( 0 - 1 mA )
3.2.4.1.1.2.6 De-Energizing Delay time. Pressing “ Up” key accepts the present value and 0 0 ( 0.5 mA)
V x1000 advance to Analog output selection screen (see section 3.2.4.1 ). 6. On Hour
This screen allows the user to set De-Energizing Delay time for Relay 1 Limit Assigned Parameters . VRY IN
KVAr KVArh
Sys Ph R
KAh
Pressing the “ Down” key will enter the “ Analog output 2 Edit” V
This Screen shows the total no. of hours the Axillary Supply is ON.
A x1000 x1000
Pressing
. “ Up” key accepts the present value and VYB Hz
mode and scroll the values, as per Table 2. VRY
KVAr
IN Even if the Auxiliary supply is interrupted count of On hour will be
V x1000 KVA KVAh KVArh
VRY IN advance to Configuration of Output. Min Ph Y
“ Parameter for Analog output” Sys Ph R
KAh
maintained in internal memory & displayed in the format “hours. min”.
KVAr KVArh %THD
Sys Ph R (See section 3.2.4.1 ) A x1000 For example if Displayed count is 005000.10 On-H it indicates
KAh KW x1000
VYB Hz
A x1000
VBR
Angle
P.F.
KWh Pressing the “ Up” key advance to the Analog output 2 KVA KVAh 005000 hours & 10 minutes.
VYB Hz Pressing the “ Down” key will enter the Max Ph B
Min Ph Y
KVA KVAh Demand confirmation screen . %THD After 999999.59 On hours display will restart from zero.
Min Ph Y “De-Energizing Delay” Edit mode and
%THD
Demand KW x1000
To reset On hour manually see section Resetting Parameter 3.2.3.1 270 0 ( 0.25 mA) 90 0 ( 0.75 mA)
KW x1000
scroll the “Value” through 1 to10 VBR
Angle
P.F.
KWh
VBR P.F. Max Ph B
Angle KWh Demand
Max Ph B
Max Demand
Demand

181 0 ( 0 mA)
7. Number of Interruption :
De-Energizing delay time Confirmation. Analog output 2 Confirmation :
V x1000
VRY IN
V x1000
KVAr KVArh This Screen Displays the total no. of times the Axillary Supply was
VRY IN This screen will appear only after edit mode of Sys Ph R This Screen will appear only after edit mode of Analog output 2
V x1000
KVAr
Sys
KVArh
Ph R
KAh
VRY
KVAr
IN
KVArh
Interrupted. Even if the Auxiliary supply is interrupted count will be
KAh De-energizing delay time. A x1000 Parameter. Sys Ph R
KAh maintained in internal memory 180 0 ( 1 mA)
VYB Hz
A x1000
VYB Hz
KVA
Min
KVAh
Ph Y
A
VYB
x1000
Hz
To reset No of Interruption manually see section
KVA KVAh
Min Ph Y pressing the “ Down” key will re-enter the %THD KVA KVAh
Resetting Parameter 3.2.3.1
Demand
%THD Pressing the “ Down” key will re-enter the “ Analog output 2 Edit” Min Ph Y
“De-energizing delay Edit” mode. KW
VBR
x1000
P.F.
%THD
KW x1000
P.F. Angle KWh KW x1000
VBR
Max Ph B VBR P.F.
Angle KWh
Max Ph B Demand Angle KWh
Max Demand
Demand Pressing “ Up” key set displayed value and Pressing the “ Up” key sets the displayed value and will advance Max Ph B
Demand
will advance to Configuration of Output. to the Analog output selection screen (see section 3.2.4.1 ).
(See section 3.2.4.1 )

11 12
8. Analog Output ( optional ) : Accessing 3 X register for reading measured values:
TABLE 2 : Parameter for Analog & Limit output TABLE 3 : Energy Pulse Rate Divisor Two consecutive 16 bit registers represent one parameter. Refer table 4 for the addresses
of 3X registers (Parameters measured by the instruments).
1.For Energy Output in Wh Example of different configuration. Each parameter is held in the 3X registers. Modbus Code 04 is used to access all parameters.
Parameter No. Parameter 3P 4W 3P 3W Range Parameter No: 4 (Current 1)
Pulse rate
Trip Point = 50%
0 None Divisor Pulse System Power* Example :
Hysteresis = 50% of trip point
To read parameter ,
1 1per Whr Up to 3600W Energising Delay: 2s
1 Volts 1 0 - 100 % Volts 3 : Start address= 04 (Hex) Number of registers = 02
1per kWhr Up to 3600kW De-energising Delay: 2s

2 Volts 2 0 - 100 % 1per MWhr Above 3600kW Note : Number of registers = Number of parameters x 2
1) Hi alarm & Energised relay 2) Hi alarm & De-energised relay
10 1per 10Whr Up to 3600W Each Query for reading the data must be restricted to 20 parameters or less. Exceeding the 20 parameter
3 Volts 3 0 - 100 % 1per 10kWhr Up to 3600kW Relay Energise Relay De-energise limit will cause a ModBus exception code to be returned.
1per 10MWhr Above 3600kW Input Relay De-energise Input Relay Energise
4 IL1 0 - 100 % Query :
100 1per 100Whr Up to 3600W
5 IL2 0 - 100 % 1per 100kWhr Up to 3600kW
50% Trip point 50% Trip point
1per 100MWhr Above 3600kW
01 (Hex) 04 (Hex) 00 (Hex) 04(Hex) 00 (Hex) 02(Hex) 30 (Hex) 0A (Hex)
6 IL3 0 - 100 % 1000 1 per 1000Whr Up to 3600W 25% Hysterisis point 25% Hysterisis point
1 per 1000kWhr Up to 3600kW
7 W1 X 0 - 120 % Device Function Start Address Start Address Number of Number of CRC CRC
1per 1000MWhr Above 3600kW Time Time
Address Code High Low Registers Hi Registers Lo Low High
8 W2 X 0 - 120 % Pulse Duration 60 ms,100 ms or 200 ms 2s 2s 2s 2s
Start Address High : Most significant 8 bits of starting address of the parameter requested.
9 W3 X 0 - 120 % 2. For Energy Output in KWh 3. For Energy Output in MWh Start Address low :Least significant 8 bits of starting address of the parameter requested.
3) Lo alarm & Energised relay 4) Lo alarm & De-energised relay
10 VA1 X 0 - 120 % Pulse rate Pulse rate Number of register Hi : Most significant 8 bits of Number of registers requested.
Divisor Pulse System Power* Divisor Pulse System Power* Relay De-energise Relay Energise Number of register Lo : Least significant 8 bits of Number of registers requested.
11 VA2 X 0 - 120 % 1 per KWhr Input Relay Energise Input Relay De-energise (Note : Two consecutive 16 bit register represent one parameter.)
1 Up to 3600W 1 1per MWhr Up to 3600W
12 VA3 X 1 per 1000KWhr Up to 3600kW 1per 1000MWhr Up to 3600kW
0 - 120 %
1per 1000MWhr Above 3600kW 1per 1000GWhr Above 3600kW 75% Hysterisis point 75% Hysterisis point Response: Volt3 (219.25V)
13 VAr1 X 0 - 120 %
50% Trip point 50% Trip point
14 VAr2 X 0 - 120 % 01 (Hex) 04 (Hex) 04 (Hex) 43 (Hex) 5B (Hex) 41 (Hex) 21 (Hex) 6F (Hex) 9B (Hex)
Above options are also applicable for Apparent and Reactive Energy.
Time Time
15 VAr3 X 0 - 120 % * System power = 3 x CT(Primary) x PT(Primary)L-N for 3 Phase 4 Wire Device Function Byte Data Register1 Data Register1 Data Register2 Data Register2 CRC CRC
System power = Root3 x CT(Primary) x PT(Primary)L-L for 3 Phase 3 Wire 2s 2s 2s 2s Address Code Count High Byte Low Byte High Byte Low Byte Low High
16 * PF1 X 180 / 0 / -180
Ampere Hour: Byte Count : Total number of data bytes received.
17 * PF2 X 180 / 0 / -180
Data register 1 High Byte : Most significant 8 bits of Data register 1 of the parameter requested.
18 * PF3 X 180 / 0 / -180 Divisor 1(Default) Data register 1 Low Byte : Least significant 8 bits of Data register 1 of the parameter requested.
CT secondary = 1A Max pulse rate 3600 pulses per Ah ** 10. RS 485 ( ModBus ) Output :
Data register 2 High Byte : Most significant 8 bits of Data register 2 of the parameter requested.
19 * PA1 X 180 / 0 / -180 CT secondary = 5A Max pulse rate 720 pulses per Ah **
3440 supports MODBUS (RS485) RTU protocol( 2-wire ) . Data register 2 Low Byte : Least significant 8 bits of Data register 2 of the parameter requested.
20 * PA2 X 180 / 0 / -180 Divisors 10 Connection should be made using twisted pair shielded cable. All "A" and "B" connections are daisy chained (Note : Two consecutive 16 bit register represent one parameter.)
CT secondary = 1A Max pulse rate 3600 pulses per 10Ah ** together. The screens should also be connected to the “Gnd” terminal. To avoid the possibility of loop currents,
21 * PA3 X 180 / 0 / -180 CT secondary = 5A Max pulse rate 720 pulses per 10Ah ** an Earth connection should be made at one point on the network.Loop (ring) topology does not require any Table 4 : 3 X register addresses (measured parameters)
termination load. Line topology may or may not require terminating loads depending on the type and length
22 Volts Ave. 0 - 100 % Divisors 100 of cable used. The impedance of the termination load should match the impedance of the cable and be at both
CT secondary = 1A Max pulse rate 3600 pulses per 100Ah ** ends of the line. The cable should be terminated at each end with a 120 ohm (1/4 Watt min.) resistor. Address Parameter Parameter Modbus Start Address Hex
24 Current Ave. 0 - 100 % CT secondary = 5A Max pulse rate 720 pulses per 100Ah ** High Byte 3P 4W 3P 3W
RS 485 network supports maximum length of 1.2km. Including the Master, a maximum of 32 instruments (Register) No. Low Byte
27 Watts sum 0 - 120 % can be connected in Rs485 network.The permissible address range for 3440 is between 1 and 247 for 30001 1 Volts 1 00 0
Divisors 1000
32 instruments. Broadcast Mode (address 0) is not allowed. 30003 2 Volts 2 00 2
CT secondary = 1A Max pulse rate 3600 pulses per 1000Ah **
29 VA sum 0 - 120 % 30005 3 Volts 3 00 4
CT secondary = 5A Max pulse rate 720 pulses per 1000Ah ** The maximum latency time of an 3440 is 200ms i.e. this is the amount of time that can pass before the
30007 4 Current 1 00 6
31 VAr sum 0 - 120 % first response character is output.
Pulse duration 60 ms, 100 ms or 200 ms 30009 5 Current 2 00 8
* PF Ave. 180 / 0 / -180 **No. of Pulses per Ampere hour = Maximum Pulses / CT Ratio After sending any query through software ( of the Master) , it must allow 200ms of time to elapse before 30011 6 Current 3 00 A
32
Where, CT Ratio = (CT primary/ CT Secondary) assuming that the 3440 is not going to respond. If slave does not respond within 200 ms, Master can 30013 7 W1 00 C X
34 * PA Ave. 180 / 0 / -180 ignore the previous query and can issue fresh query to the slave.
30015 8 W2 00 E X
30017 9 W3 00 10 X
36 Freq. 45 to 66 Hz
9.2 Limit Switch : 30019 10 VA1 00 12 X
The each byte in RTU mode has following format:
43 Watt Demand Imp. 0 - 120 % Limit switch can be used to monitor the measured parameter ( Ref.Table:2 )in relation 30021 11 VA2 00 14 X
with to a set limit. 8-bit binary, hexadecimal 0-9, A-F 30023 12 VA3 00 16 X
44 Watt Max Demand Imp. 0 - 120 % The limit switch can be configured in one of the four mode given below:- 2 hexadecimal characters contained in each 8-bit field of 30025 13 VAR1 00 18 X
1) Hi alarm & Relay Energized Relay.. the message 30027 14 VAR2 00 1A X
45 Watt Demand Exp 0 - 120 %
2) Hi alarm & De-Energized Relay. 30029 15 VAR3 00 1C X
3) Lo alarm & Energized Relay. Format of Data Bytes 4 bytes (32 bits) per parameter.
46 Watt Demand Max Exp 0 - 120 % Floating point format ( to IEEE 754) 30031 16 PF1 00 1E X
4) Lo alarm & De-Energized Relay.
Most significant byte first (Alternative least significant byte first) 30033 17 PF2 00 20 X
51 VA Demand 0 - 120 % 30035 18 PF3 00 X
Hi Alarm:
22
52 VA Max Demand. 0 - 120 % If Hi-Alarm Energized or Hi Alarm De-Energized option is selected then relay will get energized Error Checking Bytes 2 byte Cyclical Redundancy Check (CRC) 30037 19 Phase Angle 1 00 24 X
or De-energized,if selected parameter is greater than or equal to trip point. 30039 20 Phase Angle 2 00 26 X
53 Current Demand. 0 - 100 % Byte format 1 start bit, 30041 21 Phase Angle 3 00 28 X
Lo Alarm: 8 data bits, least significant bit sent first
30043 22 Volts Ave 00 2A
54 Current Max Demand. 0 - 100 % If Lo-Alarm Energized or Lo Alarm De-Energized option is selected then relay will get energized 1 bit for even/odd parity
1 stop bit if parity is used; 1 or 2 bits if no parity 30045 23 Volts Sum 00 2C
or De-energized,if selected parameter is less than or equal to trip point. 30047 24 Current Ave
101 VRY X 0 - 100 % 00 2E
Trip point: Communication Baud Rate is user selectable from the front panel between 2400, 4800, 9600, 19200 bps. 30049 25 Current Sum 00 30
102 VYB X 0 - 100 % Trip point can be set in the range of 10% to 120 % of nominal value for Hi-Alarm & 30051 26 Watts Ave 00 32
10% to 100 % of nominal value for Lo-Alarm. Function code : 30053 27 Watts Sum 00 34
103 VBR X 0 - 100 %
30055 28 VA Ave 00 36
I Neutral X 0 - 100 % Hysteresis: 03 Read Holding Registers Read content of read /write location ( 4X ) 30057 29 VA Sum 00 38
113
Hysteresis can be set in the range of 0.05% to 50 % of set trip point . 04 Read input Registers Read content of read only location ( 3X ) 30059 30 VAr Ave 00 3A
If Hi-alarm Energized or Hi-alarm De-energized is selected then relay will get 30061 31 VAr Sum 00 3C
Note : Parameters 1,2,3 are L-N Voltage for 3P 4W & L-L Voltage for 3P 3W . De-energized or Energized respectively, if set parameter value is less than Hysteresis 16 Presets Multiple Registers Set the content of read / write locations ( 4X ) 30063 32 PF Ave 00 3E
Similarly if Lo-alarm Energized or Lo-alarm De-Energized. 30065 33 PF Sum 00 40 X
9. Relay output (Optional) :
Energizing Delay: Exception Cases : An exception code will be generated when 3440 receives ModBus query with valid 30067 34 Phase Angle Ave 00 42
3440 is provided with either 1 or 2 relay for pulse output as well as for limit switch The energizing delay can be set in the range from1 to 10 sec. parity & error check but which contains some other error ( e.g. Attempt to set floating point variable to 30069 35 Phase Angle Sum 00 44 X
an invalid value ) The response generated will be “Function code” ORed with HEX (80H ). 30071 36 Freq 00 46
9.1 Pulse Output : De-Energizing Delay: The exception codes are listed below 30073 37 Wh Import 00 48
Pulse output is the potential free, very fast acting relay contact which can be used to drive an external The De-energizing delay can be set in the range from1 to 10 sec. 30075 38 Wh Export 00
Illegal function The function code is not supported by 3440 4A
mechanical counter for energy measurement. 01
3440 pulse output can be configured to any of the following parameter through setup parameter screen Note : In case of lo alarm if trip point is set at 100% then maximum 20% 30077 39 VARh Import 00 4C
Hysterisis can be set.. 02 Illegal Data Attempt to access an invalid address or an attempt to read 30079 40 VARh Export 00 4E
Address or write part of a floating point value 30081 41 VAh 00 50
1) Active Energy (Import)
2) Active Energy (Export) 03 Illegal Data Attempt to set a floating point variable to an invalid value 30083 42 Ah 00 52
3)Reactive Energy (Import) Value
4)Reactive Energy (Export)
5)Apparent Energy
6)Ampere hour

13 14
Table 4 : Continued...

Address Parameter Parameter Modbus Start Address Hex


High Byte 3P 4W 3P 3W Table 5 : 4 X register addresses
(Register) No. Low Byte Byte Count : Total number of data bytes received. Address Parameter Description
30085 43 W Demand (Import) 00 54 Data register 1 High Byte : Most significant 8 bits of Data register 1 of the parameter requested. Address Parameter Parameter Read / Write Modbus Start Address Hex 40025 Min - Reset This address is used to reset the Min parameters value.
30087 44 W Max Demand (Import) 00 56 High Byte Low Byte
Data register 1 Low Byte : Least significant 8 bits of Data register 1 of the parameter requested. (Register) No. Write Zero value to this register to reset the Min parameters.
30089 45 W Demand (Export) 00 58 Data register 2 High Byte : Most significant 8 bits of Data register 2 of the parameter requested. 1
40001 Demand Time R/Wp 00 00 Writing any other value will return an error.
30091 46 W Max Demand (Export) 00 5A Data register 2 Low Byte : Least significant 8 bits of Data register 2 of the parameter requested. 40003 2 Demand Period R
R/Wp 00 02
30093 47 - - - - - 40027 Max - Reset This address is used to reset the Max parameters value.
(Note : Two consecutive 16 bit register represent one parameter.) 40005 3 Energy display on Modbus R/Wp 00 04 Write Zero value to this register to reset the Max parameters.
30095 48 - - - - -
40007 4 Sys Voltage R 00 06 Writing any other value will return an error.
30097 49 - - - - -
- 40009 5 Sys Current R 00 08 40029 Analog Out 1- This address is used to set the parameter for Analog Output 1.
30099 50 - 00 - -
51 VA Demand 00 40011 6 Sys Type R/Wp 00 0A Para Set Write one of the parameter no. As per the options given in
30101 64
30103 52 VA Max Demand 00 66 Example : Writing System type 40013 7 Pulse Width R/Wp 00 0C Table 2 for Analog & Limit Output Parameters.
40015 8 Energy Reset Wp
W 00 0E Writing any other value will return an error.
30105 53 A Demand 00 68
System type : Start address= 0A (Hex) Number of registers = 02 40017 9 Run/On Hour & Interruption Reset Wp 00 10 40031 Analog Out 2- This address is used to set the parameter for Analog Output 2..
30107 54 A Max Demand 00 6A
40019 10 RS 485 Set-up Code R/Wp 00 12 Para Set Write one of the parameter no. As per the options given in
30133 67 Volts Ave Max 00 84
Query:( Change System type to 3phase 3wire = 2 ) 40021 11 .Node Address. R/Wp 00 14 Table 2 for Analog & Limit Output Parameters.
30135 68 Volts Ave Min 00 86 Writing any other value will return an error.
30141 71 Current Ave Max 40023 12 Pulse Divisor R/Wp 00 16
00 8C 40033 PT Primary This address allows the user to set PT Primary value.
30143 72 Current Ave Min Device Address 01 (Hex) 40025 13 Min Reset Wp 00 18
00 8E The maximum settable value is 692.8kV L-L
101 40027 14 Max Reset Wp 00 1A depends on the per phase 666.6MVA Restriction of power
30201 VL 1 - 2 ( Calculated ) 00 C8 X
102 Function Code 10 (Hex) 40029 15 Analog Out 1- Para Sel R/Wp 00 1C combined with CT primary
30203 VL 2 - 3 ( Calculated ) 00 CA X
103 40031 16 Analog Out 2- Para Sel R/Wp 00 1E
30205 VL 3 - 1 ( Calculated ) 00 CC X This address allows the user to set CT Primary value.
104 Starting Address Hi 00 (Hex) 40033 17 PT Primary R/Wp 00 20 40035 CT Pimary
30207 V1 THD( % ) 00 CE The maximum settable value is 9999 & also depends on the
30209 105 V2 THD( % ) 40035 18 CT Primary R/Wp 00 22 per phase 666.6MVA Restriction of power combined with PT primary
00 D0
106 Starting Address Lo 0A(Hex) 40037 19 System Power R 00 24
30211 V3 THD( % ) 00 D2 40037
40039 20 Energy digit reset count R/Wp 00 26 Sys Power System Power (Read Only) is the Nominal system power based on
30213 107 I1 THD( % ) 00 D4 the values of Nominal system volts and Nominal system current.
Number of Registers Hi 00 (Hex) 40041 21 Register Order/Word Order R/Wp 00 28
30215 108 I2 THD( % ) 00 D6
109 40043 22 CT Secondary R/Wp 00 2A This address is used to setting maximum energy count after
30217 I3 THD( % ) 00 D8 40039 Energy digit
110 Number of Registers Lo 02(Hex) 40045 23 PT Secondary R/Wp 00 2C which energy will rollback to zero depends upon setting of Wh,KWh,
30219 System Voltage THD( % ) 00 DA Reset Count
111 40047 24 Relay1 output select R/Wp 00 2E & MWh.If Energy display on modbus in Wh count will be set in
30221 System Current THD( % ) 00 DC
Byte Count 04 (Hex) 40049 25 Pulse1/Limit1 Parameter select R/Wp 00 30 between 7 to 14 or In KWh set in between 7 to 12 & In MWh set in
30225 113 I neutral 00 E0 X between 7 to 9.
30227 114 Run Hour 40051 26 Limit1 Trip point R/Wp 00 32
00 E2
30229 115 On Hour Data Register-1High Byte 40 (Hex) 40053 27 Hysteresis(Limit1) R/Wp 00 34
00 E4 40041
40055 28 Limit1 delay(On) R/Wp 00 Word Order Word Order controls the order in which 3440 receives or sends
30231 116 No. Of Interrupts 00 E6 36
Data Register-1 Low Byte 29 R/Wp floating - point numbers:- normal or reversed register order .
00(Hex) 40057 Limit1 delay(Off) 00 38 In normal mode, the two registers that make up a floating
40059 30 Relay2 output select R/Wp 00 3A point numbers are sent most significant bytes first.
Note : Parameters 1,2,3 are L-N Voltage for 3P 4W & L-L Voltage for 3P 3W . Data Register-2 High Byte 00(Hex) 40061 31 Pulse2/Limit2 Parameter select R/Wp 00 3C In reversed register mode , the two registers that make up
40063 32 Limit2 Trip point R/Wp 00 3E a floating point numbers are sent least significant bytes first.
Accessing 4 X register for Reading & Writing : Data Register-2 Low Byte 00(Hex) 40065 33 Hysteresis(Limit2) R/Wp 00 40 To set the mode, write the value ‘2141.0’ into this register-
40067 34 Limit2 Delay(On) R/Wp 00 42 the instrument will detect the order used to send this value and
CRC Low 66 (Hex) 40069 35 Limit2 Delay(Off) R/Wp set that order for all ModBus transaction involving floating point
Each setting is held in the 4X registers .ModBus code 03 is used to read the current setting and code 16 00 44
numbers.
is used to write/change the setting. Refer Table 5 for 4 X Register addresses. 40071 36 Password R/W 00 46
CRC High 10 (Hex) 40073 37 Limit1 Configuration select R/Wp 00 48 40043 CT secondary This address is used to read and write the CT secondary value
Example : Reading System type write one of the following values to this address.
40075 38 Limit2 Configuration select R/Wp 00 4A 1=1A CT secondary
System type : Start address= 0A (Hex) Number of registers = 02 40077 39 Auto scroll R/Wp 00
Byte Count : Total number of data bytes received. 4C 5=5A CT secondary
Note :Number of registers = Number of Parameters x 2
Data register 1 High Byte : Most significant 8 bits of Data register 1 of the parameter requested. 40079 40 30mA Noise Current Elimination R/Wp 00 4E writing any other value will return an error.
Query : Data register 1 Low Byte : Least significant 8 bits of Data register 1 of the parameter requested. 40045 PT secondary This address is used to read and write the PT secondary value.
Data register 2 High Byte : Most significant 8 bits of Data register 2 of the parameter requested. Ref Table for the range of PT secondary settable values in
Explanation for 4 X register : Section 3.2.1.3
Data register 2 Low Byte : Least significant 8 bits of Data register 2 of the parameter requested.
Device Address 01 (Hex)
(Note : Two consecutive 16 bit register represent one parameter.) Address Parameter Description 40047 Relay1 output This address is used to select the Relay 1 operation as pulse or
select Limit.
Function Code 03 (Hex) 40001 Demand Reset Demand Reset is used to reset the Demand parameter. A value write one of the following values to this address.
of zero must be Written to this register to reset the Demand 0 = Pulse output on Relay 1
40005 128 (Decimal) = Limit output on Relay 1
Start Address High 00 (Hex) period. Writing any other value will return an error.
writing any other value will return an error.
40003 Demand Demand period represents demand time in minutes. The
0A (Hex) Period applicable values are 8,15,20 or 30. Writing any other value will 40049 Pulse 1 /Limit 1 This address is used to assign the Parameter to Relay1
Start Address Low Response: parameter If Limit option is selected refer table 2 for parameter number
return an error.
select & if Pulse option is selected then refer table 7.
00 (Hex) 40005 Energy display This address is used to set energy display on modbus in Wh,KWh
Number of Registers Hi & MWh.Write one of the following value to this address. 40051 Limit1 This address is used to set the trip point in %. Any value between
Device Address 01 (Hex) on Modbus 1 = Energy in Wh. 2 = Energy in KWh. 10 to 100 for Lo- alarm & 10 to120 for Hi-alarm can be written to
Trip Point
02 (Hex) 3 = Energy in MWh. this address. Writing any other value will return an error.
Number of Registers Lo
Function Code 10 (Hex) 40007 System This address is read only and displays System Voltage 40053 Hysteresis This address is used to set the hysteresis between
Voltage (Limit 1) 0.5 to 50 . Writting any other value will return an error.
CRC Low E4 (Hex)
Start Address High 00 (Hex)
40009 System This address is read only and displays System Current 40055 Limit1 This address is used to set the Energizing delay between
Current Energizing 1 to 10 . Writting any other value will return an error.
CRC High 09 (Hex) 0A(Hex)
Start Address Low System This address is used to set the System type. Delay
40011
Type Write one of the following value to this address. 40057 Limit1 This address is used to set the De-Energizing delay between
Start Address High : Most significant 8 bits of starting address of the parameter requested. 00 (Hex) 2 = 3 Phase 3 Wire de-energizing 1 to 10 . Writting any other value will return an error.
Number of Registers Hi
Start Address low :Least significant 8 bits of starting address of the parameter requested. 3 = 3 Phase 4 Wire. Delay
Number of register Hi : Most significant 8 bits of Number of registers requested. 02(Hex)
Writing any other value will return error . 40059 Relay 2 This address is used to select the Relay 2 operation as pulse or
Number of Registers Lo
Number of register Lo : Least significant 8 bits of Number of registers requested. 40013 Pulse Width This address is used to set pulse width of the Pulse output. output select Limit.
(Note : Two consecutive 16 bit register represent one parameter.) of Relay Write one of the following values to this address: write one of the following values to this address.
CRC Low 61 (Hex) 60 : 60 ms 0 = Pulse output on Relay 2
100 : 100 ms 128 (decimal) = Limit output on Relay 2
Response: System Type ( 3phase 4 wire = 3 )
CRC High 200 : 200 ms writing any other value will return an error.
CA (Hex)
Writing any other value will return error .
40061 Pulse 2/Limit 2 This address is used to assign the Parameter to Relay2
Device Address 01 (Hex) 40015 Reset Energy This address is used to reset the Energy Counter. Parameter If Limit option is selected refer table 2 for parameter number
Counter Write zero value to this register to reset the energy counter. select & if Pulse option is selected then refer table 7.
Function Code 03 (Hex) Start Address High : Most significant 8 bits of starting address of the parameter requested. Writing any other value will return an error. This address is used to set the trip point in %. Any value between
40063 Limit 2
Start Address low :Least significant 8 bits of starting address of the parameter requested. 40017 Run/On Hour & This address is used to reset the Run/On hour & number Trip point 10 to 100 for Lo- alarm & 10 to120 for Hi-alarm can be written to
Byte Count 04 (Hex) Number of register Hi : Most significant 8 bits of Number of registers requested. Interruption of Interruption . Write zero value to this register to reset this address. Writing any other value will return an error.
Number of register Lo : Least significant 8 bits of Number of registers requested. reset the Run/On hour & number of Interruption. Hysteresis
40 (Hex) 40065 This address is used to set the hysteresis between
(Note : Two consecutive 16 bit register represent one parameter.) Writing any other value will return an error. (Limit 2)
Data Register1 High Byte 0.5 to 50 . Writting any other value will return an error.
40019 Rs485 Set-up This address is used to set the baud rate, Parity, Number of Limit 2
40 (Hex) Code stop bits. Refer to Table 6 for details. 40067 This address is used to set the Energizing delay between
Data Register1Low Byte Energizing 1 to 10 . Writting any other value will return an error.
40021 Node This register address is used to set Device address delay
Data Register2 High Byte 00 (Hex) Address between 1 to 247 . Limit 2 This address is used to set the De-Energizing delay between
40069
40023 Pulse Divisor This address is used to set pulse divisor of the Pulse output. De-Energizing 1 to 10 . Writting any other value will return an error.
Data Register2 Low Byte Write one of the following values to this address for Wh: delay
00(Hex) 1: Divisor 1
10 : Divisor 10
CRC Low EE (Hex) 100 : Divisor 100
1000 : Divisor 1000 & In KWH or MWh divisior will be 1 default.
CRC High 27 (Hex) Writing any other value will return an error.
15 16
Address Parameter Description 10.1 User Assignable Modbus Registers: User Assignable mapping Registers User Assignable Data Registers
Response : (Starting Address) ( 4X Registers Table10 ) (Starting Address) ( 3X Registers Table 9 )
40071 Password This address is used to set & reset the password. The 3440 contains the 20 user assignable registers in the address range of 0x200 (30513) to
Valid Range of Password can be set is 0000 - 9999 . 0x226 (30551) (see Table 9). 0x200 Voltage 2 (0x0002) 0x200 0x200 0x201
Device Address 01 (Hex) (16 bit) (16 bit)
1) If password lock is present & if this location is read it will Any of the parameter addresses ( 3X register addresses Table 4)) accessible in the instrument
return zero. can be mapped to these 20 user assignable registers. 10 (Hex) 0x201 Power Factor 1 (0x001E) 0x202 0x202 0x203
Function Code
2) If Password lock is absent & if this location is read it will Parameters (3X registers addresses ) that resides in different locations may be accessed by (16 bit) (16 bit)

return One. the single request by re-mapping them to adjacent address in the user assignable registers area.
Start Address High 02 (Hex) 0x202 Wh Import (0x0048) 0x204 0x204 0x205
3) If password lock is present & to disable this lock The actual address of the parameters ( 3X registers addresses) which are to be assessed via (16 bit) (16 bit)
first send valid password to this location then write “0000” address 0x200 to 0x226 are specified in 4x Register 0x200 to 0x213 (see Table 10).
to this location 00 (Hex) 0x203 0x206 0x206 0x207
Start Address Low Frequency (0x0046) (16 bit) (16 bit)
4) If password lock is present & to modify 4X parameter Table 9 : User Assignable 3X Data Registers
first send valid password to this location so that 4X parameter Address Parameter Modbus Start Address (Hex)
Assignable Register Number of Registers Hi 00 (Hex)
will be accessible for modification. (Register) Number. High Byte Low Byte
5) If for in any of the above case invalid password is send then 30513 257 Assignable Reg 1 02 00
meter will return exceptional error 2. 30515 Number of Registers Lo 02 (Hex)
258 Assignable Reg 2 02 02
40073 Limit1 This address is used to set the Configuration for relay 1 30517 259 Assignable Reg 3 02 04
Configuration see table 8 . Writting any other value will return an error. 30519 260 Assignable Reg 4 02 06 CRC Low 40 (Hex) 0x212 Current 1 (0x0006) 0x224 0x224 0x225
(16 bit) (16 bit)
Select 30521 261 Assignable Reg 5 02 08
Limit2 30523 262 Assignable Reg 6 02 0A CRC High 0x213 VAh (0x0050) 0x226 0x226 0x227
40075 This address is used to set the Configuration for relay 2 70 (Hex) (16 bit) (16 bit)
Configuration see table 8 . Writting any other value will return an error. 30525 263 Assignable Reg 7 02 0C
Select 30527 264 Assignable Reg 8 02 0E
Auto scroll This address is used to activate or de-activatethe auto scrolling write 30529 265 Assignable Reg 9 02 10 To get the data through User assignable Register use following steps:
40077
0-Deactivate 30531 266 Assignable Reg 10 02 12 Reading Parameter data through User Assignable Registers: 1) Assign starting addresses(Table3) of parameters of interest to a
1-Activate 30533 267 Assignable Reg 11 02 14 “User assignable mapping registers” in a sequence in which they are to be accessed
Writing any other value will return an error. 30535 268 Assignable Reg 12 02 16 In assigning query Voltage2 and Power Factor1 parameters were assigned to 0x 200 and (see section “Assigning parameter to user assignable registers”)
30537 269 Assignable Reg 13 02 0x201(Table10) which will point to user assignable 3xregisters 0x200 and 0x202 (table9). So to read
30mA Noise This address is used to activate or de-activatethe 30 mA noise 18
40079 Voltage2 and PowerFactor1 data reading query should be as below.
current current elimination write 30539 270 Assignable Reg 14 02 1A 2) Once the parameters are mapped data can be acquired by using
Elimination 0-Deactivate 30541 271 Assignable Reg 15 02 1C “User assignable data register “ Starting address . i.e to access data of Voltage2,
Query:
30 (Decimal)-Activate 30543 272 Assignable Reg 16 02 1E Power factor1,Wh import, Frequency send query with starting address 0x200
Writing any other value will return an error. 30545 273 Assignable Reg 17 02 20 with number of register 8 or individually parameters can be accessed
30547 274 Assignable Reg 18 02 22 Device Address 01 (Hex)
for example if current1 to be accessed use starting address 0x212.
30549 275 Assignable Reg 19 02 24 (See section Reading Parameter data through User Assignable Registers)
30551 276 Assignable Reg 20 02 26 Function Code 04 (Hex)

11. Phaser Diagram :


Start Address High 02 (Hex)
Table 6 : RS 485 Set-up Code Table 10 : User Assignable mapping register ( 4X registers)
Address Parameter Modbus Start Address (Hex) 00 (Hex)
Mapping Register Start Address Low
(Register) Number. High Byte Low Byte
Baud Rate Parity Stop Bit Decimal value 40513 257 Mapped Add for register #0x0200 02 00
Number of Registers Hi 00 (Hex)
40514 258 Mapped Add for register #0x0202 02 01
19200 NONE 01 12 Capacitive Inductive
40515 259 Mapped Add for register #0x0204 02 02
19200 NONE 02 13 04 (Hex) **
40516 260 Mapped Add for register #0x0206 02 03 Number of Registers Lo
19200 EVEN 01 14
19200 ODD 15 40517 261 Mapped Add for register #0x0208 02 04
01
9600 01 40518 262 Mapped Add for register #0x020A 02 05 CRC Low F0 (Hex)
NONE 08
9600 NONE 02 09 40519 263 Mapped Add for register #0x020C 02 06
EVEN 01 10 40520 264 Mapped Add for register #0x020E 02 07 CRC High
9600 71 (Hex)
9600 ODD 01 11 40521 265 Mapped Add for register #0x0210 02 08
4800 NONE 01 04 40522 266 Mapped Add for register #0x0212 02 09
Start Address High : Most significant 8 bits of starting address of User assignable register.
4800 NONE 02 05 40523 267 Mapped Add for register #0x0214 02 0A
Start Address low :Least significant 8 bits of starting address of User assignable register.
4800 EVEN 01 06 40524 268 Mapped Add for register #0x0216 02 0B
Number of register Hi : Most significant 8 bits of Number of registers requested.
4800 ODD 01 07 40527 269 Mapped Add for register #0x0218 02 0C
40528 270 Mapped Add for register #0x021A Number of register Lo : Least significant 8 bits of Number of registers requested.
2400 NONE 01 00 02 0D
2400 NONE 02 01 40529 271 Mapped Add for register #0x021C 02 0E **Note : Two consecutive 16 bit register represent one parameter.
2400 01 40530 272 Mapped Add for register #0x021E 02 0F Since two parameters are requested four registers are required
EVEN 02
Capacitive
2400 ODD 01 03 40531 273 Mapped Add for register #0x0220 02 10 Inductive
40532 274 Mapped Add for register #0x0222 02 11
Response : (Volt2 = 219.30 / Power Factor1 = 1.0) Sign of Sign of Sign of Inductive /
NOTE : 40533 275 Mapped Add for register #0x0224 02 12 Connections Quadrant Active Reactive Power Capacitive
Codes not listed in the table above may give rise to unpredictable results including loss of 40534 276 Mapped Add for register #0x0226 02 13 Power ( P ) Power ( Q ) Factor ( PF )
communication. Excise caution when attempting to change mode via direct Modbus writes. Device Address 01 (Hex)
Example : Import 1 +P +Q + L
Assigning parameter to user assignable registers Function Code 04 (Hex) Import 4 +P -Q + C
To access the voltage2 (3X address 0x0002) and Power Factor1 (3X address 0x001E) through user Export 2 -P +Q - C
assignable register assign these addresses to 4x register (Table 10 ) 0x0200 and 0x0201 respectively . Byte count 08 (Hex)
Table 7 : Pulse1 & Pulse2 Configuration select Export 3 -P -Q - L
Assigning Query:

}
Data Register-1High Byte 43 (Hex) Inductive means Current lags Voltage
Code Configuration Capacitive means Current leads Voltage
0 Import Active Energy Data Register-1 Low Byte 5B (Hex)
Device Address 01 (Hex)
1 Export Active Energy Voltage 2 Data When 3440 displays Active power ( P )with “ + ” ( positive sign ) ,
2 Import Reactive Energy Data Register-2 High Byte 4E (Hex)
Function Code 10 (Hex) the connection is “ Import ” .
3 Export Reactive Energy
4 Apparent Energy Data Register-2 Low Byte 04 (Hex) When 3440 displays Active power ( P )with “ - ” ( negative sign ) ,
Starting Address Hi 02 (Hex) the connection is “ Export ” .

}
Data Register-3 High Byte 3F (Hex)
Starting Address Lo 00 (Hex)
12. Installation
Data Register-3 Low Byte 80 (Hex)
Table 8 :Limit1 & Limit2 Configuration select Number of Registers Hi 00 (Hex)* Power Factor 1Data Mounting is by four side clamps, slide the side clamps through side slot till side clamp
gets firmly locked in a groove (Refer fig.) Consideration should be given to the space
Data Register-4 High Byte 00 (Hex) required behind the instrument to allow for bends in the connection cables.
Code Configuration Number of Registers Lo 02(Hex)*
0 Hi- alarm & Energized relay
Data Register-4 Low Byte 00 (Hex) PANEL
1 Hi- alarm & De-energized relay Byte Count 04 (Hex) SLIDE IN THIS DIRECTION AND LOCK
2 Lo- alarm & Energized relay CRC Low

}
79 (Hex)
3 Lo- alarm & De-energized relay Data Register-1High Byte 00 (Hex)
Voltage 2 *
CRC High
Data Register-1 Low Byte
(3X Address 0x0002) 3F (Hex)
02 (Hex)
3440

Data Register-2 High Byte

Data Register-2 Low Byte


00 (Hex)

1E (Hex) } Power Factor 1 *


(3X Address 0x001E)

CRC Low CB (Hex)

CRC High 07 (Hex)

* Note : Parameters should be assigned in Multiple of two i.e. 2,4,6,8.......20.


17 18
As the front of the enclosure conforms to IP54 it is protected from water spray Accuracy
from all directions, additional protection to the panel may be obtained by the 13. Connection Diagrams
use of an optional panel gasket. The terminals at the rear of the product Accuracy 1:
should be protected from liquids. Power Factor / Phase Angle 40... 100% of Nominal Current &
Voltage + 0.5 % of range
50... 100% of Nominal Voltage.
The 3440 should be mounted in a reasonably stable ambient 3-PHASE 3-WIRE UNBALANCED LOAD + 0.5 % of range
temperature and where the operating temperature is within the range DIGITAL METERING SYSTEM
Current
0
-10 to 55 C . Vibration should be kept to a minimum and the product should 2 5 8 3 4 6 7 9 Frequency 0.15% of mid frequency
not be mounted where it will be subjected to excessive direct sunlight. Nominal range of use of influence quantities for measurands
Active Power + 0.5 % of range
Re- Active Power + 0.5 % of range Voltage 50 .. 120 % of Rated Value

Apparent Power + 0.5 % of range Current 10 .. 120 % of Rated Value


L N
Caution AUX Active Energy + 1.0 % of range Input frequency Rated Value + 10 %
SUPPLY
1. In the interest of safety and functionality this product must be installed by + 1.0 % of range
Re - Active Energy Temperature
0
a qualified engineer, abiding by any local regulations. L1
P1 S1 0 to 50 C
L
L2 O Apparant Energy + 1.0 % of range
2. Voltages dangerous to human life are present at some of the terminal L3
P1 S1 A Auxiliary supply voltage Rated Value + 10 %
connections of this unit. Ensure that all supplies are de-energised before D
N + 1 % of Unity
attempting any connection or disconnection. Power Factor Auxiliary supply frequency Rated Value + 10 %
3. These products do not have internal fuses therefore external fuses must Angle + 1 % of range 0
Temperature Coefficient 0.025% / C for Voltage (50..120% of Rated Value)
be used to ensure safety under fault conditions. (For Rated value range of use
0
Analog Output + 1 % of Output end value 0
0.05% / C for Current ( 10..120% of Rated Value )
0... 50 C )
3-PHASE 4-WIRE UNBALANCED LOAD Total Harmonic Distortion +1%
12.1 EMC Installation Requirements DIGITAL METERING SYSTEM
+ 4 % of range. Error change due to variation of an 2 * Error allowed for the reference
Neutral Current influence quantity condition applied in the test.
2 5 8 11 1 3 4 6 7 9 13 14
This product has been designed to meet the certification of the EU directives Accuracy 0.5:
when installed to a good code of practice for EMC in industrial environments, Voltage + 0.5 % of range
e.g.
Current + 0.5 % of range

1. Screened output and low signal input leads or have provision for fitting L N Frequency 0.15% of mid frequency Display
RF suppression components, such as ferrite absorbers, line filters etc., in AUX LED 3 line 4 digits . Digit height 11mm
SUPPLY Active Power + 0.5 % of range
the event that RF fields cause problems.
P1 S1
L1 Re- Active Power + 0.5 % of range
P1 S1 L Update Approx. 1 seconds
Note: It is good practice to install sensitive electronic instruments that are L2
P1 S1
O
performing critical functions, in EMC enclosures that protect against electrical L3 A Apparent Power + 0.5 % of range
D
interference which could cause a disturbance in function. N
Active Energy + 0.5 % of range Controls
2. Avoid routing leads alongside cables and products that are, or could be, a Re - Active Energy + 0.5 % of range User Interface Two push buttons
source of interference.
Apparant Energy + 0.5 % of range
14. Specification :
3. To protect the product against permanent damage, surge transients must
be limited to 2kV pk. It is good EMC practice to suppress differential System Power Factor + 1 % of Unity
surges to 2kV at the source. The unit has been designed to automatically Standards
recover in the event of a high level of transients. In extreme Angle + 1 % of range
3 Phase 3 Wire / 4 Wire programmable at site
circumstances it may be necessary to temporarily disconnect the + 1 % of Output end value EMC Immunity IEC 61326
Analog Output
auxiliary supply for a period of greater than 5 seconds to restore correct
operation. 10V/m min-Level 3 industrial low level
Total Harmonic Distortion +1%
Inputs electromagnetic radiation environment
The Current inputs of these products are designed for connection in to
systems via Current Transformers only, where one side is grounded. Neutral Current + 4 % of range
Nominal input voltage 57.7 VL-N to 277V L-N (100VL-L to 480 V L-L) IEC 61000-4-3.
(Three wire and Four wire) Accuracy 0.2:
4. ESD precautions must be taken at all times when handling this product. Safety IEC 61010-1 , Year 2001
Voltage + 0.2 % of range
Max continuous input 120% of Rated Value IP for water & dust IEC 60529
Current + 0.2 % of range
voltage
12.2 Case Dimension and Panel Cut Out Frequency 0.15% of mid frequency
Max short duration input 2 x Rated Value
voltage (1s application repeated 10 times Active Power + 0.2 % of range Isolation
3.78” 3.15” 3.62” at 10s intervals) Re- Active Power + 0.2 % of range Dielectric voltage withstand 2.2 kV RMS 50 Hz for 1 minute
96mm 80mm 92mm test between circuits and between all electrical circuits
Nominal input voltage burden 0.2VA approx. per phase Apparent Power + 0.2 % of range accessible surfaces

Active Energy + 0.2 % of range


3.62”
Nominal input current 1A / 5A AC rms programmable at site
3.78” Re - Active Energy + 0.2 % of range
96mm FRONT DISPLAY PANEL CUTOUT 92mm
AREA Max continuous input current 120% of Rated Value
Apparant Energy + 0.2 % of range
Nominal input current burden 0.6VA approx. per phase
Power Factor + 1 % of Unity Environmental
Max short duration current input 20 x Rated Value (1s application repeated Operating temperature -10 to 55 0 C
Angle + 1 % of range
5 times at 5 min. intervals)
MAX PANEL THICKNESS 0.18”,5mm Storage temperature -20 to +65 C
0

Analog Output + 1 % of Output end value


System CT primary values Std. Values from 1 to 9999A (1 or 5 Amp secondaries)
Total Harmonic Distortion +1% Relative humidity 0 .. 90 % RH

12.3 Wiring Neutral Current + 4 % of range Warm up time 3 minute (minimum)


Auxiliary
Input connections are made directly to screw-type terminals with indirect
Reference conditions for Accuracy : Shock 15g in 3 planes
wire pressure. Numbering is clearly marked in the plastic moulding. Choice of Standard nominal Auxillary 110V AC/50 Hz , 230V AC/50 Hz ,380V AC/50 Hz ,
cable should meet local regulations. Terminal for both Current and Voltage supply voltages & Frequency 100 - 250V AC- DC (45-66Hz), Reference temperature 0 0
23 C + 2 C Vibration 10 .. 55 Hz, 0.15mm amplitude
2
inputs will accept upto 3mm x 2 diameter cables. 12 - 48V DC
Input frequency 50 or 60Hz + 2% Enclosure ( front only ) IP 54 as per IEC 60529
Note : It is recommended to use wire with lug for a.c. supply voltage tolerance +20 % / -15 % of Rated Value
Input waveform Sinusoidal (distortion factor 0.005)
connection with meter. a.c. supply frequency range 45 to 66 Hz
Auxiliary supply voltage Rated Value + 1 % Enclosure
a.c. supply burden 4.5V A
12.4 Auxiliary Supply Auxiliary supply frequency Rated Value + 1 % Style 96mm x 96mm DIN Quadratic
d.c. supply burden 3W
3440 should ideally be powered from a dedicated supply, however it may be Voltage Range 50... 100% of Nominal Value. Material Polycarbonate Housing ,
powered from the signal source, provided the source remains within the limits 60... 100% of Nominal Value for THD. Self extinguish & non dripping as per UL 94 V-0
of the chosen auxiliary voltage. Operating Measuring Ranges Current Range 10... 100% of Nominal Value. Terminals Screw-type terminals
20... 100% of Nominal Value for THD.
12.5 Fusing Voltage 5 .. 120 % of Rated Value Depth
Power cosØ / sinØ = 1 < 80 mm
It is recommended that all voltage lines are fitted with 1 amp HRC fuses. Current 5 .. 120 % of Rated Value For Active / Reactive Power & Energy
Weight 0.620 kg Approx.
10... 100% of Nominal Current &
Frequency 40 .. 70 Hz 50... 100% of Nominal Voltage.
12.6 Earth/Ground Connections
For safety reasons, CT secondary connections should be grounded in Power Factor 0.5 Lag ... 1 ... 0.8 Lead
accordance with local regulations.

19 20
15. Connection for Optional Pulse Output / RS 485
Pulse output Option ( 1 or 2 Relay ) : 7. RS 485 + Two Analog Output
/ Analog Output ( rear view of 3440 ) :
Relay 1NO + 1NC

Switching Voltage & Current 240VDC , 5Amp. 1. One Pulse Output (One Limit Output)
Default Pulse rate Divisor 1 per Wh (up to 3600W),
1 per kWh (up to 3600kW),
Gnd A1 A2 Gnd B A Gnd
1 per MWh (above 3600 kW)
4 -20 mA RS 485
Pulse rate Divisors Programmable on site

10 1 per 10Wh (up to 3600W), N/O N/C COM


1 per 10kWh (up to 3600kW),
Relay 1
1 per 10MWh (above 3600 kW)
100 1 per 100Wh (up to 3600W),
1 per 100kWh (up to 3600kW),
1 per 100MWh (above 3600 kW)
8. RS 485 Output + One Pulse (One Limit) + Two Analog Output
1000 1 per 1000Wh (up to 3600W), 2. Two Pulse Output ( Two Limit Output)
1 per 1000kWh (up to 3600kW),
1 per 1000MWh (above 3600 kW)

Pulse Duration 60ms , 100ms or 200ms

Gnd A1 A2 Gnd N/O N/C COM B A Gnd


Note : Above conditions are also applicable for Reactive & Apparent Energy . N/O N/C COM N/O N/C COM
0 - 1mA Relay 2 RS 485
Relay 1 Relay 2

ModBus ( RS 485 ) Option :

Protocol ModBus ( RS 485 )


3. RS 485 Output
Baud Rate 19200 , 9600 , 4800 or 2400
( Programmable ) 9. Two Pulse (Two Limit) + RS 485 Output
Parity Odd or Even, with 1 stop bit,
Or None with 1 or 2 stop bits

B A Gnd
RS 485
Analog Output Option :

N/O N/C COM N/O N/C COM B A Gnd


Linear 0 ... 1mA dc into 0 - 2 kohm
Relay 1 Relay 2 RS 485
Uni-directional, internally powered .

4 ... 20mA dc into 0 - 500 ohm


Uni-directional, internally powered. 4. Two Analog Output

Gnd A1 A2 Gnd
4 -20 mA

5. One Pulse (One Limit) + RS 485 Output

N/O N/C COM B A Gnd


Relay 2 RS 485

6. One Pulse (One Limit) + Two Analog Output

Gnd A1 A2 Gnd N/O N/C COM The Information contained in these installation instructions is for use only by installers trained to make electrical power installations and
is intended to describe the correct method of installation for this product.
0 - 1mA Relay 2
It is the user's responsibility to determine the suitability of the installation method in the user's field conditions.

21

Potrebbero piacerti anche