PROJECT NAME: PROJECT NUMBER:

C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019


C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

CRESSMAN DINING FACILITY EXPANSION GAFB Project #: 1030643


BUILDING 3220
OKLAHOMA CITY, OK 73112 405.416.8100

SAN ANGELO, TEXAS

[Circle the appropriate ACM/LBP and place an "X" in the appropriate boxes]
AND LEAD BASED PAINT [LBP] STATEMENT
ASBESTOS CONTAINING MATERIAL [ACM]

X
C.H. GUERNSEY & COMPANY

This facility contains ACM/LBP materials that will be removed

This facility contains ACM/LBP materials that will be removed

This facility contains ACM/LBP materials that will be removed


This facility contains ACM/LBP materials that will be left in
This facility does not contain ACM/LBP materials:
5555 N. GRAND BLVD.

This facility contains ACM/LBP materials:


87 208
DATE SIGNATURE

by an ACM/LBP removal contractor:


180 277
180 RECOMMENDED (BCE)

NORTH GATE
NATURAL GAS
ENTRY STATION

180

place for this project:

under this contract:


PE RIM CO NS

[325-654-3528]
TRUC

by the Air Force:


ETE R

CIVIL ENGINEER
RO AD TIO N
NORT
H
GA TE
SUBMITTED (CHIEF ENGINEER)
87
84

BUILDING 3511
PA INT
RO CK

FT. McKAVETT RD.


x x
x x

x
RO A D
x x
x

x
x
x
x
x
FIRE CHIEF

x
x

x
[325-644-3501]

x
x x x x x
x x x

20

FT. LANCASTER AVE


349 CALL BOX

FT. GRIFFIN AVE


PE RIM K ROAD #3
ETER
RO PAINT ROC
AD NO x x x x x x x x

RT H

x
x

x
x
ABILENE

x
x
385

x
DETENTION POND

x
x
SAFETY
x x

x
x x x

GV
x x x

OL ROAD

x
E. NORTH PATR
x

x
GV

x
SABER

x
x
x

x
x
x x x x x x x x

BIG SPRING

Appr
20
x x x x x x x x x x x x x x

x
x
x
533
ENVIRONMENTAL

x
KIOWA TRAIL
3521

x
X

510 3520 3535

x
x
x
X
3510

x
x
3533

x
x
3531

x
x
208

Date
x
X
3530 3530A

x
ELEC.

x
3530B

x
SUB

x
ND

X
STA. 3530D
TION PO

x
BIO-ENVIRONMENTAL OFFICER
x x x x x x x x

508
DET EN

x
538
3530E 50214

x
X

x
x
3530F

x
530 3519
83

x
3511

x
x
84
x x x x x x x x

MIDLAND

531
X
535
158

REVISIONS
277

516
X
CANBERRA STREET E 3527

ODESSA SECURITY FORCES


X X

509
ELEC.
SWITCH 3525
STA.

X
87 X

W. CANBERRA STREET 3445


3448

512
504
X
527 528
67

498
COMMUNICATIONS

Description
3447
JOINT FORCES
3446 OBSTACLE COURSE
385

APACHE TRAIL
521
523

500
JUMANOS TRAIL
3420 3490
525
TEAMWORK

499
LP FUEL TANKS 3478(4)
522 LP FUEL TANK DEVELOPMENT

FT. McKAVETT RD.


CHIEF OF OPERATIONS

520
COURSE
GOODFELLOW

511
505
3460
JOINER AVE.

SAN ANGELO AIR FORCE BASE 3473

TROOPWALK

KEARNEY BLVD
3456

X
3443(5)
3443(2)
3443(1)

X
519 3442
3428

BASE CONTRACTING
501
BASE DEVELOPMENT
X
518
3444
3478(1)
GOODFELLOW REC CAMP

X
503

X
BUILDING 707
3443(3)

FIRE PROTECTION
3443(4)

34
FT. GRIFFIN TROOPWALK

41
517 3475

435
3478(2)

34
434

40
MARAUDER STREET
CHIEF OF DESIGN

X
3488

[325-654-5174]

I.E.D.
AREA

Symbol
CO
67

443

3458
X

X
BUILDING 3321

MA
NC
87 RAPPELLING

H
436
CONC. WALL 447

ET

IN G
TOWER

AIN IN T
RA

JO
CHALLENGER AVE
PED.

IL
449 3478(3)
GATE MARAUDER STREET

FT. LANCASTER AVE

34
TROOPWALK

54

TR
448

[325-654-3539]
604 603 602 URBAN
601
SEARCH & RESCUE
PROJECT MANAGER

34
431 CAMP SENTINAL

39
TRAINING AREA x x x x x x x x x x x x x x x x x x x x x x x x x x

CARSWELL ST. VERIZON


3453
425 GRIFFIN STREET 3405
277 83 605 606 607 608

423
SCHERZ BLVD
CONC. WALL POWELL STREET
3324
PERIMETER ROAD NW 3329
GRIFFIN STREET T
LO

TROOPWALK

33
190 USING AGENCY

49
E
AG
612 611 610 609 416 OR
3322 GV G E ST
LA RV

FT. RICHARDSON AVE

410
3321 3341 VIL JOINT FORCES

3323
VANCE CIRCLE 3368 UT

414
420 MO

60245
3340
FIELD TRAINING AREA

422
W. VANCE ST

613
430
VANCE ST. E
RETENTION POND

10 VANCE CIRCLE 409 USING AGENCY


614 616 617

TROOPWALK

TROOPWALK
R
401 47
33
621 620 619 VANC MOUT VILLAGE
618 TROOPWALK

T
U E ST .
C E
NUCHOLS STREET
MATHIS ST.
AIL
TR
622 O
623 624 625 340 3311 PO
KA

PERIMETER ROAD EAST


358
KIC

PB3311
PARTIAL TEXAS STATE MAP
GV

AD
3305

RO AD
FARROW

TROOPWALK
TROL RO

356
ST RE

TO VAL
1009 ET 337 3327

PA

B. McCOMBS
1002 3342

CHRIS
1007 700

WEST
( DISPLAYS )

S. SPRAGUE
1005
TROOPWALK WILDLAND FIRE

J. MORGAN
3303 TRAINING AREA
FARROW STREET

Submitted by:
362 3307

Reviewed by:
2
1

89 1 1 3
0 2

4 5
7

6
6
701

Designed by:
1004 709
711

J. LOPEZ
1001

330
331
SECURITY FORCES
702
336

KEA RN

Drawn by:
703

FT. GRIFFIN AVE


334

SCHERZ BLVD

EY
360

704

BL VD
320

FLIGHTLINE AVE
707 335
705

BUILDING 3323
1003 319
POLLARD STREET

310
3220

TROOPWALK
361

DETENTION POND
BUILDING 3323

712

FT. PHANTOM HILL AVE


1022 723 INCOMING VEHICLE

F.M. HWY. 2105

RT
U.S 87

INSPECTION STATION

F.M. HWY. 2105

U
718

CO
500'

246
3209 EXPLOSIVE
U.S. HWY.

719
716 303 CLEAR ZONE
N
DS O 300
. HW

259 KAYDET STREET


FT. RICH AR 742 x x x x

245

x
x
KAYDET STREET 3208

x
ARMSTRONG ST. S.H. 208

x
N GAT E

x x x x x

744 3210
277

SAN ANGELO

258
747 243 223 '
741 750 Z ON E
RUC TIO

CO
1024 TY
Y.

MA
745 FE
SA

NC
CO NST

743

H
244

ET
727

COLISEUM

256

RA
PERIMETER ROAD SW 746

TROOP WALK
257

IL
738
CONC. WALL

241

242
CALL BOX

736

3206
254 #2

752
750 3298

255
32
222 2 7
HORNET STREET 213 1250'
QUANTITY DISTANCE

252
EXPLOSIVE CLEAR ZONE

B.B.C.
3276
222 1250'

FT. LANCASTER AVE


800 3201 QUANTITY DISTANCE
250 EXPLOSIVE CLEAR ZONE

238
221

240
251

CRESSMAN DINING FACILITY EXPANSION


TROOPWALK

GOODFELLOW AIR FORCE BASE, TEXAS


V.B.

.
WY

FT. GRIFFIN AVE


239

V.B.
818

H
U.S. HWY. 67
CHA

'
750 ON E

R GOODFELLOW DRIVE
164 TY
Z

GE
3139 FE
SE SA
UR
CO

LIN
DBO

( 6
1
g
.a
,ln
v
id
ze
u
o
c d
p
e
)ta
'0
o
1
(.c
n
3

812

L PA
R

O.C. FISHER LAKE A


PROJECT LOCATION
RR

DB
VALIANT STREET E
URN

U.S W. VALIANT STREET

OL
145

FT. STOCKTON AVE


811 146

.H

PB136
ES

144

WY B3220 CRESSMAN DINING FACILITY

137
&2 .

142

APACHE TRAIL
67 HWY

139
HAUL ROUTE

TROOP WALK
. 87

136
BF #2
T.

77

809

NORT

138
808 PB3198A

WY
130

H
.

KEARNEY BLVD.
19th HUGHES ST.
3198

T
EAS
U.S

3197
MULTI-PURPOSE FIELD
XP

135

116
134
PB3198

FLIGHTLINE AVE
810
ST

TEXAN STREET CROSS COUNTRY


CO

123
TRAILS
.

124

17th TRAINING WING


900 109
NC

HARTE AIL
901

N 121 TR
RR

NATURE OF WORK:
OO

STO
P
KA CAMP RAIDER

112
KIC

113
CONTINGENCY OPS

HOU
140
OH

125 126
910 903 111 TRAINING AREA

. MITCHELL STREET 3160


MITCHELL STREET

B.B.C.
3012

B.B.C.

TC #4

TC #1
TC #6

TC #3

TC #2
V.B.
V.B.
3070

ER TRUE NORTH 92
0 915

F.M R IV
.

30
05

PE
RIVER

R
50104
.

IM E
50105
924

TE
. GV

R
922

228 HWY

RO
U.S. P 306

P.T. Pad

AD
906

S
LOO

SCHERZ BLVD

E
Y 929

30
08
8 . XPW
104

ST.
EDGEWOOD DRIVE

FT. CONCHO DRIVE


Running Track
PERIMETER ROAD S
HWY

ARD
BELL STREET

RTE G

BER
BF #1

M
HA URE BF LL
927 100 Football Field
50110
3004
CALL BOX
.

BEA
#1

MAIN CONC
930 3015

F.M. STON
HOU
102 3020

HWY. HO BERM
GV
BERM

OLD EOLA ROAD


CHAD BOURNE

853 SOUTH CHADBOURNE STREET


CONST. GATE PERIMETE R ROAD SE

Y
MAG DEC

WA VISITOR CONTROL CENTER


C:\Work\Projects\R18_70374-000_A_SSnyderOKC.rvt

ARDEN RD.
.

OOD AVE. N RD.


ER
W PAINT ROCK F.M.
SH
ANGELO RIV
ER HWY. [325-654-4122]
#388
JACOBSON GATE
BRYANT BLVD.
(U.S. HWY. 87)

STATE UNIV. .
RD GOOD-
[325-654-3529]
ST.

R FELLOW MAGNETIC DECLINATION: 6° 19' EAST (2009)


. 67 KE
WY OC
U.S. HWY.
LOOP 306

B AIR ANNUAL RATE OF CHANGE: 7' WEST/YEAR


. H R
U.S U.S.
H CKE FORCE SOURCE: http://www.ngdc.noaa.gov/cgi-bin/seg/gmag/fldsnth1.pl
LOO WY. KN
I

RR
P 30
6 U.S.
H NC
HO
BASE
300 0 300 600 GOODFELLOW AIR FORCE BASE
LOO WY. CO

PROJECT TITLE
F.M

P 30
6
SAN ANGELO, TEXAS
.H

SCALE IN FEET
WY
. 12
23
H
UT
SO

GENERAL NOTES: PROJECT NOTES:


U.S. HWY. 87 & LOOP 306 1. THE CONTRACTOR SHALL INITIATE AND PROCESS FOR APPROVAL AF FORM
LAKE #103 "WORK CLEARANCE REQUEST" FOR THE CONTRACTING OFFICER PRIOR TO
NASWORTHY Project Number:
PERFORMANCE OF ON-SITE WORK.
U.S. HWY. 277

2. LOCATIONS OF EXISTING UTILITIES ARE APPROXIMATE. THE CONTRACTOR SHALL


OK70374-000
FIELD VERIFY EXACT LOCATIONS PRIOR TO EXCAVATION OR TRENCHING. IT
RO CKE ER

MATHIS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO LOCATE SERVICE SHEET TITLE
AD R
BO NICK

FIELD N LINES AS REQUIRED FOR CONSTRUCTION FOR THIS PROJECT.


K

COVER SHEET
MUNICIPAL 3. THE CONTRACTOR SHALL HAND DIG WITHIN (2) FEET EITHER SIDE OF UTILITY
TWIN BUTTES
RESERVOIR

AIRPORT CROSSING UNTIL THE UTILITY IS PHYSICALLY EXPOSED, PRIOR TO PERFORMING


7/12/2018 11:11:49 AM

MECHANICAL TRENCHING OR EXCAVATING. PROVIDE NEW TOPSOIL AND Date:


RIVE HO
CONCTH

HYDROMULCHING IN ALL AREAS WHERE DISTURBED OR DAMAGED BY 12 JUL 2018


R.M 584

R
SOU

S A N A N
F G
O
E
L
O ,
Y

W E
C I T

CONSTRUCTION ACTIVITIES.
. HW

TE X A
E
T H

* *
P
S

U K
B L R
I C W O

4. THE CONTRACTOR SHALL COORDINATE ALL COMMUNICATIONS WORK WITH THE


Y.

S
ENGINEERING SECTION MANAGER AT FRONTIER AT 325-944-5511; WITH THE
INSTALLATION OFFICE, SUDDEN-LINK CABLE AT 325-486-4155 AND THE SEQ. SHEET OF
GOODFELLOW AFB COMMUNICATIONS SQUADRON AT 325-654-3010.
0'

THE CITY OF SAN ANGELO, TEXAS


SCALE IN FEET
G-001
A. GENERAL NOTES J. MAINTENANCE OF STORAGE AREA SHEET INDEX
1. CONSTRUCTION ACCESS TO THE SITE SHALL BE THROUGH THE EXISTING GATE LOCATED ON SOUTH CHADBOURNE STREET. ALL 1. THE CONTRACTOR SHALL AT ALL TIMES KEEP THE CONSTRUCTION SITE, CONSTRUCTION TRAILER(S)/BUILDING(S), AND STORAGE AREA(S) SHEET NUMBER SHEET TITLE
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
CONSTRUCTION TRAFFIC ENTERING THE BASE IS REQUIRED TO PASS THROUGH THE COMMERCIAL VEHICLE SEARCH AREA IN A CLEAN, NEAT, WORKMAN LIKE CONDITION, FREE FROM ACCUMULATION OF WASTE, RUBBISH, WEEDS, OVERGROWN GRASS, OR 1000 - GENERAL
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
LOCATED TO THE EAST OF KEARNEY BOULEVARD. HOURS OF OPERATION ARE FROM 6:00 A.M. TO 6:00 P.M. MONDAY THROUGH CONSTRUCTION DEBRIS, TO THE SATISFACTION OF THE CONTRACTING OFFICER. ALL LOOSE OR LIGHT WEIGHT MATERIALS SHALL BE G-001 COVER SHEET
FRIDAY. SECURED TO PREVENT BLOWING OR SCATTERING. THE BURNING OF TRASH OR CONSTRUCTION DEBRIS IS STRICTLY PROHIBITED ON G-002 SHEET INDEX & CONVENTIONS
GOODFELLOW AFB. PRIOR TO FINAL INSPECTION, THE CONTRACTOR SHALL REMOVE ALL CONSTRUCTION DEBRIS, TOOLS, EQUIPMENT,
G-003 LIFE SAFETY CODE NARRATIVE
2. CONTRACTORS SHALL KEEP ALL PUBLIC ROADS AND STREETS CLEAN OF CONSTRUCTION DEBRIS, MUD, ETC. AT ALL TIMES. AND MATERIALS NOT THE PROPERTY OF THE GOVERNMENT. UPON COMPLETION OF THE WORK, THE CONTRACTOR SHALL LEAVE THE
CONTRACTOR SHALL PROVIDE EQUIPMENT AND PERSONNEL TO CLEAN ANY STREETS AS REQUESTED BY 17CES. WORK SITE AND STORAGE AREA(S) IN A CLEAN, NEAT, AND WORKMANLIKE CONDITION SATISFACTORY TO THE CONTRACTING OFFICER. G-004 LIFE SAFETY CODE NARRATIVE
CONTRACTOR IS RESPONSIBLE FOR ALL REPAIRS TO STREETS, PARKING AREAS AND BASE OR GOVERNMENT PROPERTY REFER TO SECTION 01400 - ENVIRONMENTAL PROTECTION FOR GOODFELLOW AFB, PARAGRAPH 2.4.6, POST-CONSTRUCTION CLEANUP. G-005 LIFE SAFETY FLOOR PLAN
DAMAGED FROM THEIR CONSTRUCTION ACTIVITIES. 5000 - CIVIL
DRAFTING CONVENTIONS
OKLAHOMA CITY, OK 73112 405.416.8100

2. THE CONTRACTOR SHALL KEEP FENCING IN A STATE OF GOOD REPAIR AND PROPER ALIGNMENT. GRASSED OR UNPAVED AREAS, WHICH C-001 CIVIL LEGEND
3. CONTRACTORS SHALL MAINTAIN A CONSTRUCTION SITE NEAT AND CLEAN OF DEBRIS AS DIRECTED BY CONTRACTING OFFICER. ARE NOT ESTABLISHED ROADWAYS, WILL BE COVERED WITH A LAYER OF GRAVEL AS NECESSARY TO PREVENT RUTTING AND THE C-100 EXISTING CONDITIONS AND DEMOLITION PLAN

Date Appr
CONTRACTOR WASTE DUMPSTERS SHALL BE EMPTIED ON A REGULAR BASIS. TRACKING OF MUD ONTO PAVED OR ESTABLISHED ROADWAYS, SHOULD THE CONTRACTOR ELECT TO TRAVERSE THEM WITH
CONSTRUCTION EQUIPMENT OR OTHER VEHICLES; GRAVEL GRADATION WILL BE AT THE CONTRACTOR'S DISCRETION. MOW AND C-110 SITE PLAN
B. STAGING NOTES MAINTAIN GRASS LOCATED WITHIN THE BOUNDARIES OF THE CONSTRUCTION SITE FOR THE DURATION OF THE PROJECT. GRASS AND C-111 ENLARGED DETAIL
CENTERLINE SYMBOL = DETAIL MARKER
VEGETATION ALONG FENCES, BUILDINGS, UNDER TRAILERS, AND IN AREAS NOT ACCESSIBLE TO MOWERS WILL BE EDGED OR TRIMMED C-130 OVERALL GRADING DRAINAGE AND EROSION CONTROL PLAN
C.H. GUERNSEY & COMPANY

1. CONTRACTOR SHALL INSTALL AND MAINTAIN A TEMPORARY CONSTRUCTION CHAIN LINK FENCE, 6 FEET HIGH, AROUND THE LIMITS NEATLY. C-150 UTILITY PLAN SIM SIMILAR (IF APPLICABLE)
OF WORK NOT INCLUDING THE CONSTRUCTION ACCESS ROAD. COORDINATE CHAIN AND PADLOCKS ON GATES WITH 3. GRASS AND WEEDY VEGETATION WITHIN THE AREAS UTILIZED BY THE CONTRACTOR, INCLUDING WORK AREAS, ADMINISTRATIVE AREAS, KEYNOTE SYMBOL = 1
C-501 DETAILS 1 DETAIL VIEW NUMBER
GOODFELLOW FIRE DEPARTMENT. EACH GATE SHALL BE NUMBERED FOR EMERGENCY ACCESS, SHALL HAVE ENTRY/EGRESS AND STORAGE AREAS, SHALL BE KEPT MOWED TO CONTROL VEGETATIVE GROWTH. VEGETATION SHALL BE MOWED WHEN IT
5555 N. GRAND BLVD.

C-502 DETAILS A-101 SHEET ON WHICH DETAIL


SIGNAGE AND AREA LIGHTING. CONTRACTORS SHALL MAINTAIN FIRE ACCESS THROUGH EACH INDIVIDUAL CONSTRUCTION SITE AT REACHES A HEIGHT OF 6 INCHES. MOWING SHALL BE TO A HEIGHT OF 3 INCHES. MOWING SHALL BE ACCOMPLISHED WITH A ROTARY DOOR SYMBOL

Description
ALL TIMES. MOWER THAT LEAVES THE CLIPPINGS EVENLY DISTRIBUTED ON THE SOIL SURFACE. MOWING SHALL BE ACCOMPLISHED DURING C-503 DETAILS APPEARS
PERIODS AND IN SUCH MANNER THAT THE SOIL AND GRASS WILL NOT BE DAMAGED. TOWED OR SELF-PROPELLED RIDING MOWERS C-504 DETAILS 101 NUMBER
2. TRUCK WASHOUT AREA SHALL BE CONSTRUCTED, MAINTAINED AND CLEANED IN ACCORDANCE WITH TCEQ REGULATIONS. SHALL NOT BE OPERATED WITHIN 3 FEET OF TREES OR SHRUBS. AREAS ADJACENT TO TREES AND SHRUBS SHALL BE MOWED WITH 6000 - LANDSCAPE DESIGNATION
PROVIDE DETAILS AND MAINTENANCE PLAN AS PART OF THE STORMWATER POLLUTION PREVENTION PLAN. STORMWATER HAND-PROPELLED MOWERS. ELEVATION SYMBOL EXTERIOR ELEVATION MARKER
L-010 LANDSCAPE PLAN (BASE BID)
PERMITS ARE REQUIRED PRIOR TO THE START OF CONSTRUCTION. 4. EROSION CONTROL DEVICES SHALL BE USED FOR THE STAGING AREA AND ANY MATERIAL STOCK PILES WHEN NECESSARY TO CONTROL DIRECTION OF ELEVATION VIEW
L-100 LANDSCAPE – HARDSCAPE PLAN (ALT. 4) LEVEL 30 NAME DESIGNATION
EROSION AND STORM WATER RUNOFF IN ACCORDANCE WITH FEDERAL, STATE, AND LOCAL REGULATIONS.
3. ALL CONTRACTORS SHALL STOCKPILE REQUIRED MATERIALS AND EQUIPMENT WITHIN LIMITS OF RESPECTIVE PROJECT AREAS OR 5. AREAS NOT MOWED: GOVERNMENT MAY IMMEDIATELY AFTER NOTICE TO THE CONTRACTOR AND AT THE DISCRETION OF THE L-101 LANDSCAPE – HARDSCAPE DIMENSIONS (ALT. 4) 24'-0" HEIGHT DESIGNATION SIM SIMILAR (IF APPLICABLE)
STAGING AREA AS INDICATED ON THE DRAWINGS. CONTRACTING OFFICER MOW THE CONTRACTOR'S AREAS AT ANY TIME THE VEGETATION HEIGHT EXCEEDS 6 INCHES. L-102 LANDSCAPE – HARDSCAPE PLAN (NORTH MEDIANS) 1 ELEVATION VIEW NUMBER

Symbol
L-103 LANDSCAPE – HARDSCAPE PLAN (SOUTH MEDIANS)
EQUIPMENT/FURNITURE SYMBOL A101 SHEET ON WHICH ELEVATION APPEARS
4. CONTRACTOR SHALL CONNECT TO EXISTING OR NEW FIRE HYDRANTS FOR TEMPORARY CONSTRUCTION WATER. INSTALL QUICK L-104 LANDSCAPE – HARDSCAPE PLAN (TROOPWALK) (BASE BID)
DISCONNECT, BACK FLOW PREVENTER AND SHUT-OFF VALVE ON 2 1/2" HOSE CONNECTION ONLY. PRIOR TO MAKING ANY PRIVATIZED ELECTRICAL UTILITY SYSTEMS: L-110 LANDSCAPE - PLANTING PLAN (ALT. 4)
CONNECTIONS TO BASE WATER SYSTEMS, THE CONTRACTOR MUST NOTIFY AND COORDINATE WITH 17CES. A FIRE PLUG USAGE 1234 NUMBER
PERMIT IS REQUIRED AND USAGE SHALL BE METERED AT ALL TIMES. AEP TEXAS NORTH COMPANY IS THE UTILITY OWNER AND SOLE PROVIDER OF THE ELECTRICAL DISTRIBUTION UTILITY SYSTEM AT GOODFELLOW L-111 LANDSCAPE - PLANTING PLAN (MEDIANS) (ALT. 4) DESIGNATION

Appr
L-120 LANDSCAPE – DETAILS & NOTES INTERIOR ELEVATION MARKER
AIR FORCE BASE, TEXAS. GRID SYMBOL
5. ALL TEMPORARY ELECTRIC POWER FACILITIES SHALL MEET OR EXCEED NESC AND NEC REQUIREMENTS AS APPLICABLE FOR L-121 LANDSCAPE – DETAILS & NOTES 1 ELEVATION VIEW NUMBER

Date
PRIMARY AND SECONDARY FACILITIES. NEWLY PROVIDED SYSTEM INFRASTRUCTURE AND/OR MODIFICATIONS OF OR CONNECTIONS TO THE EXISTING SYSTEM INFRASTRUCTURE 7000 - STRUCTURAL
IDENTIFIED IN THE SPECIFICATIONS AND/OR DRAWINGS MUST BE COORDINATED WITH THE UTILITY OWNER PRIOR TO THE CONTRACT START DIRECTION OF VIEW FOR ELEVATION
S-001 GENERAL STRUCTURAL NOTES 0 0 LETTER/NUMBER
C. ACCESS AND VEHICLE PARKING DATE. TO CONNECT FACILITIES, THE CONSTRUCTION CONTRACTOR SHALL REQUEST THAT THE UTILITY OWNER PROVIDE THE REQUIRED DESIGNATION
S-002 GENERAL STRUCTURAL NOTES

REVISIONS
CONNECTING FACILITIES, UP TO A POINT OF DEMARCATION WHICH INCLUDES ALL TERMINATIONS AT THE TRANSFORMER. EXISTING NEW A-101 SHEET ON WHICH ELEVATION APPEARS
1. ACCESS TO THE PROJECT FOR ALL CONSTRUCTION PERSONNEL, VEHICLES AND EQUIPMENT IS ILLUSTRATED ON THE S-003 GENERAL STRUCTURAL NOTES
STAGING/LAYDOWN AND ACCESS PLAN. ACCESS ROUTES MAY BE SUBJECT TO CHANGE BASED ON OPERATIONAL ALL WORK ON THE SYSTEM OR FACILITIES EXPECTED TO CONNECT TO THE SYSTEM SHALL COMPLY WITH THE UTILITY OWNER'S SPECIFICATIONS S-010 TYPICAL DETAILS MATCHLINE SYMBOL

Description
REQUIREMENTS. POTENTIAL SCHEDULE IMPACTS SHALL BE COORDINATED WITH 17CES. AND CONSTRUCTION STANDARDS. IN NO EVENT SHALL THE CONSTRUCTION CONTRACTOR CONNECT TO, OR OTHERWISE TOUCH THE UTILITY S-011 TYPICAL DETAILS
OWNER'S INFRASTRUCTURE WITHOUT THE UTILITY OWNER'S EXPRESS WRITTEN PERMISSION. S-012 TYPICAL DETAILS 1 / A-121 LETTER/NUMBER
2. LOCATION OF ACCESS/ HAUL ROADS ARE AS INDICATED ON THE STAGING/LAYDOWN AND ACCESS PLAN. DESIGNATION OF BUILDING / WALL SECTION MARKER
S-101 COMPOSITE FOUNDATION PLAN
THE UTILITY OWNER: CONTACT VIA: 1 / A-122 FLOOR PLAN(S) DIRECTION OF SECTION VIEW
3. ALL HAUL ROADS SHALL BE MAINTAINED SUCH THAT UNOBSTRUCTED ACCESS WILL BE PROVIDED AT ALL TIMES FROM THE ROAD AEP TEXAS NORTH COMPANY S-102 COMPOSITE ROOF FRAMING PLAN
TO THE STAGING AREA AND FROM THE STAGING AREA TO THE WORK SITE AND FACILITATE GOVERNMENT ACCESS TO THE BASE AT 930 West 19th Street S-111 FOUNDATION PLAN SIM SIMILAR (IF APPLICABLE)
ALL TIMES. THE MAINTENANCE OF HAUL ROADS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AT NO ADDITIONAL COST TO San Angelo, Texas 76903 S-121 FRAMING PLAN - LOW ROOF PARTITION TYPE SYMBOL 1 SECTION VIEW NUMBER
THE GOVERNMENT. THE HAUL ROAD LOCATIONS SHALL BE AS INDICATED ON THE STAGING/LAYDOWN AND ACCESS PLAN OR BY PHONE: 325-657-2800 S-122 FRAMING PLAN - HIGH ROOF

Symbol
17CES. G012 LETTER/NUMBER A101 SHEET ON WHICH SECTION APPEARS
S-201 ELEVATIONS DESIGNATION
ARCHITECT / ENGINEER RESPONSIBILITIES:
4. CONTRACTOR SHALL COORDINATE ACTIVITIES THROUGHOUT THE PROJECT IN A MANNER THAT ALLOWS EMERGENCY ACCESS TO 1. SITE PLAN WITH ADJACENT STREETS OR LANDMARKS IDENTIFIED. S-501 FOUNDATION SECTIONS
ALL EXISTING ROADWAYS AT ALL TIMES WITHOUT DELAYS TO EMERGENCY VEHICLES RESPONSE TIME. 2. BUILDING PLAN SHEETS WITH THE FOLLOWING INFORMATION: S-502 FOUNDATION SECTIONS
ROOM NAME/NUMBER SYMBOL MILLWORK ELEVATION MARKER
A. LOCATION OF SERVICE ENTRANCE S-521 ROOF FRAMING DETAILS
5. ALL CONTRACTOR VEHICLES AND PERSONNEL MAY BE SEARCHED BY SECURITY FORCES WHEN ENTERING THE BASE AND MAY B. REQUESTED TRANSFORMER LOCATION, IF A PREFERENCE IS KNOWN. S-522 ROOF FRAMING DETAILS Room name DIRECTION OF ELEVATION VIEW
EXPERIENCE DELAYS. ALL PERSONNEL ENTERING GOODFELLOW A.F.B. MUST HAVE A VALID PHOTO ID PER BASE SECURITY C. SQUARE FOOTAGE OF BUILDING SPACE WITH THE TYPE OF LOAD TO BE SERVED. S-523 ROOF FRAMING DETAILS 101 NUMBER
REQUIREMENTS. ALL VEHICLES ENTERING THE BASE MUST HAVE CURRENT/ VALID REGISTRATION, CURRENT/ VALID INSURANCE D. ELECTRICAL PANEL SCHEDULE 1 / A-101 ELEVATION VIEW NUMBER / SHEET NUMBER
S-601 SCHEDULES 150 SF DESIGNATION
AND CURRENT/ VALID DRIVERS LICENSE FOR THE OPERATOR. ALL DRIVERS MUST COMPLY WITH ALL GOODFELLOW AFB DRIVING E. NUMBER AND SIZE OF SECONDARY CONDUCTORS TO BE TERMINATED AT THE TRANSFORMER
REQUIREMENTS (SPEED LIMITS, SEATBELTS, ETC.) F. PROPOSED LOCATION OF OTHER UTILITY ROUTES AND ENTRANCES. S-602 SCHEDULES
3. LOAD DEMAND INFORMATION FROM EXISTING SIMILAR BUILDINGS. S-603 SCHEDULES SPOT/CEILING ELEVATION SYMBOL GRAPHIC SCALE SYMBOL
6. WHEN NOT ENGAGED IN CONSTRUCTION ACTIVITIES, THE CONTRACTOR'S CONSTRUCTION EQUIPMENT AND VEHICLES SHALL BE 4. SCHEDULE OF WORK. 8000 - ARCHITECTURAL 8' 4' 0 8'

B. McCOMBS
PARKED WITHIN THE WORK AREA OR STAGING AREA. 10'-0" HEIGHT

S. SPRAGUE
A-001 ABBREVIATIONS & NOTES

J. MORGAN
S. SNYDER

Submitted by:
DESIGNATION

Reviewed by:
CONTRACTOR / BUILDER RESPONSIBILITIES:

Designed by:
A-002 ADA STANDARDS
D. COORDINATION AND COMMUNICATION DURING CONSTRUCTION 1. CONTACT NAMES AND NUMBERS UPON ARRIVAL AT THE SITE.

Drawn by:
2. LOCATION OF TRANSFORMER PAD. AD-100 DEMOLITION PLAN SCALE: 1/8" = 1'-0"
1. PRIOR TO CONSTRUCTION, THE CONTRACTOR SHALL CORDON OFF THE WORK AREAS AND STREET CROSSINGS BY USING 3. INSTALL SECONDARY CONDUITS INTO THE APPROPRIATE WELL LOCATION BEFORE PAD INSTALLATION. THIS INCLUDES ANY REQUIRED A-101 COMPOSITE FLOOR PLAN TOILET ACCESSORY SYMBOL
APPROVED BARRICADES. METERING CABLE CONDUITS. A-121 FLOOR PLAN NORTH ARROW
4. PROVIDE FINAL GRADE IN TRANSFORMER PAD AREA PRIOR TO PAD CONSTRUCTION. A-141 REFLECTED CEILING PLAN A LETTER PLAN NORTH
E. TRAFFIC CONTROL 5. INSTALLATION OF ANY REQUIRED INSTRUMENT RATED METERING EQUIPMENT. A-161 ROOF PLAN DESIGNATION
6. PROVIDE SECONDARY CABLE TERMINALS.
7. PRIMARY CONDUIT DITCH COMPACTION IF REQUIRED. A-201 EXTERIOR ELEVATIONS PLAN NORTH
1. ONLY RUBBER-TIRED VEHICLES SHALL BE ALLOWED ON EXISTING PAVEMENT THAT IS TO REMAIN.
8. ASPHALT AND/OR CONCRETE CUT AND REPAIR IF REQUIRED. A-221 INTERIOR ELEVATIONS ARROW DIRECTION
WINDOW/STOREFRONT SYMBOL
2. ANY DAMAGE TO ROADS AND PAVEMENT DUE TO CONSTRUCTION EQUIPMENT, CONSTRUCTION TRAFFIC OR CONSTRUCTION 9. LOCATION OF OTHER UTILITY LINES INSTALLED DURING THIS CONSTRUCTION. A-301 BUILDING SECTIONS TRUE NORTH

CRESSMAN DINING FACILITY EXPANSION


ARROW DIRECTION

GOODFELLOW AIR FORCE BASE, TEXAS


ACTIVITY SHALL BE REPAIRED TO THEIR ORIGINAL CONDITION BY THE CONTRACTOR AT HIS/ HER OWN EXPENSE . 10. TEMPORARY POWER POLE (SEE ATTACHED SKETCHES). LOCATION TO BE APPROVED BY AEP TEXAS. NOTE: ANY LINE EXTENSION REQUIRED A-321 EXTERIOR WALL SECTIONS A LETTER
FOR THE PURPOSE OF TEMPORARY SERVICE WILL REQUIRE A CIAC TO COVER THE COST OF INSTALLATION AND REMOVAL OF TEMPORARY A-341 PARTITION TYPES DESIGNATION
F. EQUIPMENT AND STOCKPILE HEIGHT FACILITIES AND ANY MATERIAL WHICH CANNOT BE REUSED.
A-501 PLAN DETAILS VIEW TITLE
1. STOCKPILE ALL CONSTRUCTION MATERIALS WITHIN STAGING AREA. MAXIMUM HEIGHT 15.00' WITH 5:1 SIDE SLOPES. PROVIDE AEP TEXAS RESPONSIBILITIES: A-521 VERTICAL DETAILS
EROSION CONTROL PROTECTION AROUND THE STOCKPILE LIMITS. ANY MATERIALS THAT ARE TO BE STOCKPILED FOR USE FOR 1. SIZING AND INSTALLATION OF ALL PRIMARY CONDUCTORS INCLUDING DITCH AND CONDUIT. A-601 DOOR SCHEDULE
REVISIONS SYMBOL
View Name
OTHER PROJECTS ON THE BASE SHALL BE COORDINATED WITH 17CES. ALL MATERIAL NOT REQUIRED SHALL BE HAULED OFF
GOVERNMENT PROPERTY.
2. SIZING AND INSTALLATION OF DISTRIBUTION TRANSFORMERS.
3. CONSTRUCTION OF TRANSFORMER PAD. SEE ATTACHED SKETCH
A-641
A-701
ROOM FINISH SCHEDULE
FINISH AND SPECIALTIES PLAN
1 REVISION NUMBER 1 SCALE: 1/8" = 1'-0"
4. INSTALLATION OF SECONDARY CABLE TERMINALS. AREA / ITEM(S)

17th TRAINING WING


A-731 FURNITURE AND EQUIPMENT PLAN

NATURE OF WORK:
G. EXCAVATION AND TRENCHES TO BE REVISED VIEW NUMBER
CONSTRUCTION NOTES: A-801 PERSPECTIVE VIEWS
1. OPEN TRENCHES AND EXCAVATIONS AT THE CONSTRUCTION SITE SHALL BE PROMINENTLY MARKED WITH ORANGE AND WHITE 1. THE EDGE OF THE TRANSFORMER PAD SHALL NOT BE CLOSER THAN TWO FEET FROM A WALL, OR FIVE FEET FROM A DOOR OR WINDOW, OR 9000 - FIRE ALARM
TYPE III BARRICADES AND WITH FLASHING TYPE A-LOW INTENSITY WARNING LIGHTS FROM DUSK TILL DAWN. TWENTY FEET FROM A STAIRWELL OR FIRE ESCAPE. FA-001 FIRE ALARM GENERAL NOTES
2. TRANSFORMERS SHALL NOT BE COMPLETELY ENCLOSED BY WALLS, FENCES, OR LANDSCAPING WITHOUT VENTILATION WHICH IS APPROVED FA-101 FIRE ALARM FLOOR PLAN
H. OTHER SAFETY REQUIREMENTS BY AEP TEXAS. THE ENTIRE WIDTH OF THE FRONT OF THE TRANSFORMER AND SECONDARY CABINET SHALL BE ACCESSIBLE. IF A FENCE IS 10000 - FIRE SUPPRESSION
INSTALLED, IT WILL HAVE SUFFICIENT GATES NECESSARY TO PROVIDE THIS ACCESS.
3. TRANSFORMERS WILL BE LOCATED IN THE AREAS WITH ALL WEATHER ACCESS BY SERVICE TRUCKS. IN ADDITION, THERE WILL BE NO FX-001 FIRE SUPPRESSION GENERAL NOTES
1. CONTRACTOR SHALL MAINTAIN SAFETY PRACTICES THAT CONFORM TO OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION
(OSHA) REGULATIONS. STRUCTURES CONSTRUCTED ABOVE TRANSFORMERS WHICH WOULD INHIBIT CRANE OPERATIONS. FX-101 FIRE SUPPRESSION FLOOR PLAN
4. NO OTHER UTILITY LINES WILL BE INSTALLED WITHIN TWO FEET OF THE TRANSFORMER PAD. 12000 - PLUMBING
2. CONTRACTOR SHALL MAINTAIN AT ALL TIMES ONE FIRE LANE FREE FROM OBSTRUCTION AND MAINTAIN ACCESS TO THE SITE 5. NO CUSTOMER EQUIPMENT, EXCEPT INSTRUMENT RATED METERING EQUIPMENT WHICH IS PLACED ON THE SECONDARY BUSHINGS, SHALL P-001 PLUMBING LEGEND
AND ALL SURROUNDING ROADS AND STREETS. BE ATTACHED TO AEP TEXAS TRANSFORMERS; NOR WILL THERE BE ANY HOLES DRILLED INTO THE TRANSFORMER CABINET FOR CONDUITS, P-101 UNDERFLOOR PLUMBING PLAN - AREA A
CONDUCTORS OR METERS.
P-102 UNDERFLOOR PLUMBING PLAN - AREA B
I. CONTRACTOR SAFETY PLAN SUBMITTALS 6. THE NUMBER AND SIZE OF THE SECONDARY CONDUCTORS WHICH ARE ALLOWED TO BE ATTACHED TO THE TRANSFORMER SECONDARY
BUSHINGS WILL BE CONTROLLED BY AEP TEXAS. IF THE DESIGN REQUIRES MORE OR LARGER CONDUCTORS THAN ALLOWED FOR A P-103 PLUMBING FLOOR PLAN - AREA A
1. CONTRACTOR SHALL FURNISH A CONSTRUCTION SAFETY PLAN IN ACCORDANCE WITH THE SPECIFICATIONS WITH HIS/HER PARTICULAR TRANSFORMER SIZE, AEP TEXAS WILL INSTALL A SECONDARY CABINET WITH BUS BARS (SEE ATTACHED SKETCH) ADJACENT TO P-104 PLUMBING FLOOR PLAN - AREA B
PROJECT SCHEDULE. THE SAFETY PLAN SHALL IDENTIFY THE FOLLOWING ITEMS: THE TRANSFORMER. AEP TEXAS WILL SUPPLY AND INSTALL THE SECONDARY CONDUCTORS FROM THE TRANSFORMER TO THE SECONDARY P-501 PLUMBING SCHEDULE AND DETAILS
C:\Work\R18_70374-000_A_mrjessel.rvt

A. PROPOSED ACCESS POINTS, STAGING AREA AND HAUL ROUTES. CABINET. THE POINT OF INTERCONNECTION WILL BE THE BUS BARS WITHIN THE SECONDARY CABINET. THIS CABINET WILL REQUIRE A 14000 - MECHANICAL
B. TEMPORARY MARKINGS TO BE USED, IF ANY. LARGER TRANSFORMER PAD AS SHOWN ON THE ATTACHED SKETCH.
M-001 HVAC LEGEND
C. LOCATIONS AND TYPE OF BARRICADES OR OTHER TRAFFIC CONTROL DEVICES. 7. TRANSFORMERS LARGER THAN 1000 kVA WILL REQUIRE A LARGER PAD. THIS PAD IS SHOWN ON THE SKETCH LABELED 1500 AND 2500 kVA.
8. TEMPORARY CONSTRUCTION POWER WILL BE SUPPLIED TO CUSTOMER SUPPLIED POWER POLES LOCATED WITHIN FIVE FEET OF AN M-101 HVAC FLOOR PLAN - AREA A

PROJECT TITLE
D. METHODS BY WHICH THE CONTRACTOR WILL COMMUNICATE WITH 17CES.
EXISTING PAD MOUNTED TRANSFORMER OR WITHIN FIFTY FEET OF A PRIMARY POWER POLE (SEE ATTACHED SKETCHES). M-102 HVAC FLOOR PLAN - AREA B
M-103 ROOF PLAN
M-401 ENLARGED PLANS
M-501 HVAC DETAILS
M-502 HVAC DETAILS
OCCUPANT LOAD CALCULATIONS (2015 IBC SECTION 1004) M-601 HVAC SCHEDULES

PLUMBING FIXTURE CALCULATIONS (2015 IPC; TABLE 403.1) MATERIAL SYMBOLS M-801
M-802
HVAC CONTROLS
HVAC CONTROLS
15000 - ELECTRICAL Project Number:
EARTH RIGID INSULATION MORTAR NET E-001 ELECTRICAL LEGEND AND NOTES
ES101 SITE PLAN OK70374-000
OCCUPANT LOAD AND TOILET COUNT REQUIREMENTS
DISCONTINUOUS EL101 LIGHTING PLAN
AGGREGATE FILL BLANKET INSULATION ROUGH LUMBER SHEET TITLE
SF per %OCC. %OCC. W.C. per Mens Womens Mens Womens Service EP101 POWER PLAN
Name OCC OCC. LOAD MEN WOMEN OCC. W.C. Req. W.C. Req. Lav. per OCC. Lav. Req. Lav. Req. Sink EP102 MECHANICAL POWER PLAN SHEET INDEX & CONVENTIONS
CONTINUOUS
EXISTING ASSEMBLY 15 278 0.5 0.5 75 1.85 1.85 200 0.70 0.70 CONCRETE FIRE SAFING INSULATION E-501 ELECTRICAL DETAILS
LUMBER
EXISTING BUSSINESS 100 10 0.5 0.5 25 0.20 0.20 40 0.13 0.13 E-601 ONE-LINE AND SCHEDULES
7/12/2018 12:22:16 PM

Date:
EXISTING KITCHEN 100 45 0.5 0.5 75 0.30 0.30 200 0.11 0.11 PRECAST CONCRETE INSULATED METAL PANEL WOOD GRAIN 12 JUL 2018
EXISTING MECHANICAL 500 2 0.5 0.5 100 0.01 0.01 100 0.01 0.01
EXISTING STORAGE 500 5 0.5 0.5 100 0.03 0.03 100 0.03 0.03
BRICK GROUT PLYWOOD
NEW ASSEMBLY 15 287 0.5 0.5 75 1.91 1.91 200 0.72 0.72 1
NEW BUSSINESS 100 19 0.5 0.5 25 0.38 0.38 40 0.24 0.24 SEQ. SHEET OF
NEW KITCHEN 100 2 0.5 0.5 75 0.01 0.01 200 0.01 0.01 CONCRETE MASONRY UNITS LATH & PLASTER FINISH LUMBER
NEW MECHANICAL 500 2 0.5 0.5 25 0.04 0.04 100 0.01 0.01
NEW STORAGE 500 3 0.5 0.5 75 0.02 0.02 100 0.02 0.02 CUT/ CAST STONE MARBLE/ GRANITE G-002
TOTAL REQUIRED 5 5 2 2 1
TOTAL PROVIDED 5 5 2 3 1 STEEL SPRAY FOAM INSULATION
GENERAL INFORMATION: PASSIVE FIRE SAFETY FEATURES:

PROPERTY NAME & PHYSICAL ADDRESS: CRESSMAN DINING FACILITY INTERIOR FINISH: INTERIOR WALL AND CEILING FINISHES IN EXIT ENCLOSURES, CLASS A OR B REQUIRED (NFPA 101, SECTION 7.1.4) - PROVIDED
GOODFELLOW AIR FORCE BASE, TEXAS INTERIOR WALL AND CEILING FINISHES IN GENERAL ASSEMBLY AREAS WITH MORE THAN 300 OCCUPANTS, CLASS A OR B
REQUIRED (NFPA 101, SECTION 12.3.3.3) - PROVIDED
INTERIOR WALL AND CEILING FINISHES IN GENERAL ASSEMBLY AREAS WITH LESS THAN 300 OCCUPANTS, CLASS A, B, OR C
PROJECT CONSTRUCTION PURPOSE: ADDITION TO EXISTING FACILITY PER UFC 3-600-01, SECTION 2-1.1
C.R. ENGINEERING: #F-6671 EXPIRES JUNE 30, 2019

REQUIRED (NFPA 101, SECTION 12.3.3.3) - PROVIDED


INTERIOR FLOOR FINISHES IN EXIT ENCLOSURES, EXIT ACCESS CORRIDORS, AND IN SPACES NOT SEPARATED FROM THEM BY www.poolefire.com
REASON FOR SUBMITTAL: CODE COMPLIANCE OF ADDITION TO EXISTING FACILITY WALLS, MIMIMUM OF CLASS II REQUIRED (NFPA 101, SECTION 12.3.3.5) - PROVIDED
INTERIOR FLOOR FINISHES IN ALL OTHER AREAS, NO CLASSIFICATION REQUIRED (NFPA 101, SECTION 12.3.3.5) - PROVIDED
CRITERIA USED: UNIFIED FACILITIES CRITERIA (UFC) 1-200-01: GENERAL BUILDING REQUIREMENTS, 20 JUNE 2016; CHANGE 1, 1 FEBRUARY 2018
UNIFIED FACILITIES CRITERIA (UFC) 3-600-01: FIRE PROTECTION ENGINEERING FOR FACILITIES, 8 AUGUST 2016; CHANGE 2, 25 MARCH 2018 ROOM SEPARATION: SMOKE PARTITION FOR BOILER AND FURNACE ROOMS IN ASSEMBLY OCCUPANCIES WITH AN AGGREGATE INPUT RATING THAT

Date Appr
UNIFIED FACILITIES CRITERIA (UFC) 4-010-01: DOD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS, 9 FEBRUARY 2012; CHANGE 1, OCTOBER 2013 EXCEEDS 200,000 BTU REQUIRED (NFPA 101, SECTIONS 12.3.2.1.2(1)(A)(I.) AND 8.7.1.2) - PROVIDED
OLATHE, KS 66062 913.829.8650

UNIFIED FACILITIES CRITERIA (UFC) 4-021-01: DESIGN AND O & M: MASS NOTIFICATION SYSTEMS, 9 APRIL 2008; CHANGE 1, JANUARY 2010
INTERNATIONAL BUILDING CODE (IBC), 2015 EDITION CORRIDORS: NO FIRE RESISTANCE RATING REQUIRED (NFPA 101, SECTION 12.3.6) - NONE PROVIDED
POOLE FIRE PROTECTION

NFPA 1: FIRE CODE, 2018 EDITION


19910 W. 161ST STREET

NFPA 13: STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2016 EDITION HORIZONTAL EXITS: NOT APPLICABLE

Description
NFPA 70: NATIONAL ELECTRICAL CODE, 2017 EDITION
STAIRWAYS: NOT APPLICABLE
NFPA 72: NATIONAL FIRE ALARM AND SIGNALING CODE, 2016 EDITION
NFPA 90A: STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATING SYSTEMS, 2018 EDITION
VERTICAL SHAFTS: NOT APPLICABLE
NFPA 101: LIFE SAFETY CODE, 2018 EDITION
NFPA 291: RECOMMENDED PRACTICES FOR FIRE FLOW TESTING AND MARKING OF HYDRANTS, 2016 EDITION
OPENINGS AND PENETRATIONS: THROUGH PENETRATIONS OF FIRE RESISTANCE RATED CONSTRUCTION PROTECTED BY AN APPROVED FIRE STOP SYSTEM
NFPA 780: STANDARD FOR THE INSTALLATION OF LIGHTNING PROTECTION SYSTEMS, 2017 EDITION INSTALLED AS TESTED IN ACCORDANCE WITH ASTM E 814 OR UL 1479 REQUIRED (IBC, SECTION 714.4.1.2 AND NFPA 101,

Symbol
GOODFELLOW AIR FORCE BASE DESIGN STANDARD SECTION 8.3.4.2) - PROVIDED

ELECTRICAL CLASSIFICATION: NOT REQUIRED (NFPA 70) - NOT PROVIDED


ANTICIPATED ADDITIONS: NONE

Appr
ACTIVE FIRE SAFETY FEATURES
DATE DEVELOPED: JULY 12, 2018

Date
AUTOMATIC SPRINKLER PROTECTION: REQUIRED (UFC 3-600-01, SECTION 9-7.2.1.1) - WET PIPE SPRINKLER TO BE PROVIDED IN THE ADDITION BY EXPANDING THE
DATE REVISED: NOT APPLICABLE

REVISIONS
EXISTING WET-PIPE SPRINKLER SYSTEM THAT SERVES THE EXISTING FACILITY

OWNER INFORMATION: UNITED STATES AIR FORCE SEISMIC PROTECTION FOR SPRINKLER SYSTEM: NOT REQUIRED FOR SEISMIC DESIGN CATEGORY A (ASCE 7, SECTION 11.7) - NOT PROVIDED

Description
CODE CONSULTANT INFORMATION: POOLE FIRE PROTECTION, INC. STANDPIPES: NOT REQUIRED (UFC 3-600-01, SECTION 9-10.2) - NOT PROVIDED
19910 WEST 161ST STREET
OLATHE, KS 66062 AUTOMATIC FIRE PUMPS: NOT REQUIRED (HYDRAULLIC CALCULATION) - NOT PROVIDED
913.829.8650 (TELEPHONE)

Symbol
913.829.8690 (TELEFAX) SPECIAL FIRE SUPPRESSION SYSTEM: WET-CHEMICAL FIRE EXTINGUISHING SYSTEM FOR COOKING EQUIPMENT THAT PRODUCES SMOKE OR GREASE-LADEN VAPORS
NOT REQUIRED FOR ADDITION (UFC 3-600-01, SECTION 4-15.1.1, NFPA 101, SECTIONS 9.2.3 AND 12.3.2.2, AND NFPA 96, SECTION
10.2.3) - NOT PROVIDED FOR THE ADDITION AS A KITCHEN IS NOT TO BE INCLUDED IN THE ADDITION
DESIGNER’S SEAL: SEE TITLE BLOCK

FIRE SERVICE: GOODFELLOW AIR FORCE BASE FIRE DEPARTMENT KITCHEN HOOD VENTILATION SYSTEMS: HOOD AND DUCT SYSTEMS IN ACCORDANCE WITH NFPA 96 NOT REQUIRED FOR ADDITION (UFC 3-600-01, SECTION 4-15.1.1, AND
NFPA 101, SECTIONS 9.2.3 AND 12.3.2.2) - NOT PROVIDED FOR ADDITION AS A KITCHEN IS NOT TO BE INCLUDED IN THE ADDITION

LOCAL BUILDING INSPECTOR: GOODFELLOW AIR FORCE BASE FIRE DEPARTMENT


PORTABLE FIRE EXTINGUISHERS: NOT REQUIRED (UFC 3-600-01, SECTION 9-17.1) - NOT PROVIDED PER DIRECTION FROM RFI 002

AUTHORITY HAVING JURISDICTION: 17 CES GOODFELLOW AIR FORCE BASE

B. McCOMBS
SMOKE CONTROL SYSTEM: NOT REQUIRED (UFC 3-600-01 AND NFPA 101) - NOT PROVIDED
TOM GREEN COUNTY

Submitted by:
Reviewed by:
Designed by:

Drawn by:
HVAC SYSTEM: INTERLOCKED WITH FIRE ALARM ACTIVATION FOR AIR HANDLER SHUT DOWN REQUIRED (UFC 3-600-01, SECTION 9-18.1.2.2 AND

JMW

DBN
SAB
OCCUPANCY GROUP AND TYPE: ASSEMBLY (GROUP A-2) (IBC, SECTION 303.3) NFPA 90A, SECTION 6.4.4.2) - PROVIDED
FIRE DAMPERS AND SMOKE DAMPERS INSTALLED IN ALL TRANSFER OPENINGS OF EACH FIRE BARRIER AND SMOKE PARTITION
ASSEMBLY (NFPA 101, SECTION 6.1.2.1) REQUIRED (UFC 3-600-01, SECTION 28-1.1 AND NFPA 90A, SECTION 5.3.1.2) - NOT APPLICABLE

MECHANICAL, ELECTRICAL, RESTROOM, AND CORRIDOR SPACES WILL BE CONSIDERED AS A PART OF THE PREDOMINANT OCCUPANCY FOR THE EXIT SIGNS: INTERNALLY OR EXTERNALLY ILLUMINATED EXIT SIGNS ALONG THE PATH OF EGRESS TRAVEL REQUIRED (NFPA 101, SECTIONS
BUILDING REQUIRED (NFPA 101, SECTION 3.3.22.2 ) - PROVIDED 12.2.10, 7.10.1.2, AND 7.10.5.1) - INTERNALLY ILLUMINATED LED TYPE PROVIDED IN ADDITION

CRESSMAN DINING FACILITY EXPANSION


TACTILE EXIT SIGNS AT EACH EXIT DOOR REQUIRING AN EXIT SIGN REQUIRED (NFPA 101, SECTION 7.10.1.3) - PROVIDED

GOODFELLOW AIR FORCE BASE, TEXAS


TYPE OF CONSTRUCTION: TYPE II-B (IBC, TABLE 601)
EMERGENCY LIGHTING: EMERGENCY LIGHTING IN ALL MEANS OF EGRESS REQUIRED (NFPA 101, SECTIONS 12.2.9 AND 7.9) - PROVIDED IN ADDITION
STRUCTURAL CODE REQUIREMENTS: HEIGHT LIMITATION
C:\Users\sbrinkmeyer.pcs\Documents\R18_70374-000_F_sbrinkmeyer8U4LS.rvt

BASE ALLOWABLE HEIGHT 3 STORIES, 75 FT. (IBC, TABLES 504.3 AND 504.4) FIRE ALARM REPORTING SYSTEM: REQUIRED (UFC 3-600-01, SECTION 9-18.1.2.1) - PROVIDED VIA MONACO MAAP-X PANEL THAT IS COMPATABLE WITH EXISTING
ACTUAL HEIGHT 1 STORY, 31 FT. - COMPLIANT BASE FIRE DEPARTMENT MONACO D21 SYSTEM

17th TRAINING WING


NATURE OF WORK:
AREA LIMITATION SMOKE DETECTION: FULL AREA DETECTION NOT REQUIRED (UFC 3-600-01, SECTION 9-18.5) - NOT PROVIDED

BASE ALLOWABLE AREA 38,000 SQ.FT. (IBC, SECTION 506.2) SMOKE DETECTOR ABOVE FIRE ALARM / MASS NOTIFICATION CONTROL UNIT, NOTIFICATION APPLIANCE CIRCUIT POWER
EXTENDERS, AND SUERVISING STATION TRANSMITTING EQUIPMENT REQUIRED (NFPA 72, SECTION 10.4.4) - PROVIDED
ACTUAL AREA 20,441 SQ.FT. - COMPLIANT
DUCT SMOKE DETECTION ON AIR HANDLING UNITS GREATER THAN 2,000 CFM SUPPLY AIR CAPACITY REQUIRED (NFPA 90A,
SECTION 6.4.2.1(1)) - PROVIDED
FIRE RESISTIVE REQUIREMENTS (IBC, TABLES 601 AND 602)
PRIMARY STRUCTURAL FRAME 0-HOUR - REQUIRED (IBC, TABLE 601) - PROVIDED CARBON MONOXIDE DETECTION: CARBON MONOXIDE DETECTORS IN EACH ROOM WHERE FOSSIL FUEL BURNING EQUIPMENT IS LOCATED REQUIRED (UFC 3-600-
BEARING WALLS - EXTERIOR 0-HOUR - REQUIRED (IBC, TABLE 601) - PROVIDED 01, SECTION 9-19) - PROVIDED FOR AREAS THAT HVAC EQUIPMENT USES FOSSIL FUEL EQUIPMENT IN THE ADDITION AS WELL
AS WHERE FOSSIL FUEL EQUIPMENT IS BEING USED FOR COOKING IN THE EXISTING FACILITY.
BEARING WALLS - INTERIOR 0-HOUR - REQUIRED (IBC, TABLE 601) - PROVIDED
NON BEARING WALLS - EXTERIOR 0-HOUR - REQUIRED (IBC, TABLE 602) - PROVIDED
FIRE ALARM SYSTEM: MANUALLY ACTIVATED, EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM WITH VISIBLE ALARM NOTIFICATION APPLIANCES
NON BEARING WALLS - INTERIOR 0-HOUR - REQUIRED (IBC, TABLE 601) - PROVIDED IN ALL COMMON USE AREAS, EMPLOYEE WORK AREAS, AND PUBLIC USE AREAS REQUIRED (UFC 3-600-01, SECTIONS 9-18) -
FLOOR CONSTRUCTION AND SECONDARY MEMBERS 0-HOUR - REQUIRED (IBC, TABLE 601) - PROVIDED PROVIDED
ROOF CONSTRUCTION AND SECONDARY MEMBERS 0-HOUR - REQUIRED (IBC, TABLE 601) - PROVIDED MASS NOTIFICATION SYSTEM: REQUIRED (UFC 4-010-01, SECTION 1-8) - PROVIDED IN ADDITION AS WELL AS EXISTING FACILITY AS UFC REQUIRES THAT MNS
BE PROVIDED FOR INHABITED BUILDINGS
OCCUPANCY SEPARATION: NOT REQUIRED (IBC, SECTION 508.1) - NOT PROVIDED

PROJECT TITLE
LIGHTNING PROTECTION: ANALYSIS WAS NOT PERFORMED (NFPA 780 ANALYSIS) - NOT PROVIDED

WATER SUPPLY REQUIREMENTS:

FIRE HYDRANT FLOW TEST: STATIC: 68 PSI


RESIDUAL: 63 PSI
FLOW: 1,271 GPM
LOCATION: HYDRANTS 32-7 AND 32-6
Project Number:
DATE: APRIL 10, 2018
SOURCE: POOLE FIRE PROTECTION, INC. OK70374-000
AVAILABLE: 4,311 GPM AT 20 PSI
SHEET TITLE
FIRE FLOW: 1,000 GPM AT 20 PSI REQUIRED (UFC 3-600-01, SECTION 9-2.1) - PROVIDED LIFE SAFETY CODE NARRATIVE

FIRE WATER DEMAND: 430 GPM AT 63.3 PSI REQUIRED (PRELIMINARY HYDRAULIC CALCULATIONS) - PROVIDED
7/12/2018 11:28:17 AM

Date:
12 JUL 2018

SEQ. SHEET OF

G-003
MEANS OF EGRESS:

OCCUPANT LOAD: CALCULATED OCCUPANT LOAD PER OCCUPANCY CLASSIFICATION AND USE (NFPA 101, TABLE 7.3.1.2 AND UFC 3- GUARD REQUIREMENTS: LOCATION: GUARDS PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS THAT
600-01, TABLE 10-1) EXCEED 30 IN. ABOVE THE FLOOR OR THE FINISHED GROUND LEVEL
BELOW REQUIRED (NFPA 101, SECTION 7.1.8) - NOT PROVIDED FOR
USE OCCUPANT LOAD FACTOR GROSS OR NET AREA ADDITION AS THERE IS NOT A 30 IN. ELEVATION CHANGE
C.R. ENGINEERING: #F-6671 EXPIRES JUNE 30, 2019

ASSEMBLY - LESS CONCENTRATED 15 SQ.FT. PER PERSON NET


STORAGE 500 SQ.FT. PER PERSON GROSS HEIGHT: GREATER THAN OR EQUAL TO 42 INCHES REQUIRED (NFPA 101, www.poolefire.com
KITCHEN 100 SQ.FT. PER PERSON GROSS SECTION 7.2.2.4.6.2) - PROVIDED FOR ADDITION
IT EQUIPMENT 100 SQ.FT. PER PERSON GROSS
OPENING LIMITATIONS: LESS THAN OR EQUAL TO 21 INCHES REQUIRED (NFPA 101, SECTION
MECHANICAL, ELECTRICAL AND OTHER 500 SQ.FT. PER PERSON GROSS
7.2.2.4.6.3(2)) - PROVIDED FOR ADDITION
BUILDING EQUIPMENT SPACES

Date Appr
BUSINESS 150 SQ.FT. PER PERSON GROSS
OLATHE, KS 66062 913.829.8650

DOOR REQUIREMENTS: ALL EXIT DOOR ASSEMBLIES, AND DOORS WITHIN THE EGRESS PATHS, EQUIPPED WITH APPROPRIATE HARDWARE
REQUIRED (NFPA 101, SECTIONS 7.2.1.5, 7.2.1.6, AND 7.2.1.7) - PROVIDED IN ADDITION
BUILDING OCCUPANT LOAD SERVING THE ADDITION: 306*
POOLE FIRE PROTECTION

ALL DOORS SERVING MORE THAN 50 PEOPLE OR HIGH HAZARD SPACES SWING IN THE DIRECTION OF EGRESS
19910 W. 161ST STREET

* INDICATES CAPACITY OF EGRESS COMPONENTS ASSOCIATED WITH THE ADDITION TAKES INTO CONSIDERATION TRAVEL REQUIRED (NFPA 101, SECTION 7.2.1.4.2) - PROVIDED IN ADDITION
THE ESTIMATED OCCUPANT LOAD ASSOCIATED WITH THE EXISTING FACILITY ALL DOORS IN A REQUIRED MEANS OF EGRESS SERVING 100 PEOPLE OR MORE EQUIPPED WITH PANIC

Description
HARDWARE REQUIRED (NFPA 101, SECTION 12.2.2.2.3) - PROVIDED IN ADDITION
NUMBER OF EXITS: TWO BUILDING EXITS REQUIRED (NFPA 101, SECTIONS 12.2.4.1 AND 7.4.1.2(1)) - EIGHT BUILDING EXITS PROVIDED. DELAYED EGRESS LOCKS PROHIBITED ON MAIN ENTRANCE/EXIT DOORS REQUIRED (NFPA 101, SECTION 12.2.2.2.5)
THREE NEW EXITS WILL BE ADDED TO THE FIVE EXISTING EXITS. - PROVIDED IN ADDITION

ARRANGEMENT OF EXITS: WHERE TWO EXITS OR EXIT ACCESS DOORWAYS ARE REQUIRED, EXITS OR EXIT ACCESS DOORWAYS SEPARATED MAXIMUM TRAVEL DISTANCE: ALLOWABLE TRAVEL DISTANCE
BY NOT LESS THAN ONE-THIRD THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE AREA
SERVED REQUIRED (NFPA 101, SECTION 7.5.1.3.3) - PROVIDED ASSEMBLY 250 FT. (NFPA 101, SECTION 12.2.6.2)

Symbol
MAIN ENTRANCE/EXIT SIZED TO ACCOMMODATE AT LEAST ONE-HALF OF THE CALCULATED OCCUPANT LOAD OF
THE SPACE REQUIRED (NFPA 101, SECTION 12.2.3.6.2(2)) - PROVIDED ACTUAL
ASSEMBLY SEE LIFE SAFETY PLANS

Appr
MEANS OF EGRESS SIZING: CALCULATED MEANS OF EGRESS COMPONENTS SIZING REQUIREMENTS PER COMPONENT REQUIRED (NFPA 101,
SECTION 12.2.3.8 AND TABLES 7.3.3.1 AND 7.3.4.1) - PROVIDED
COMMON PATH OF TRAVEL: ALLOWABLE COMMON PATH OF TRAVEL
COMPONENT SIZING FACTOR - LOW/ORDINARY MINIMUM SIZE

Date
ASSEMBLY GREATER THAN 50 OCCUPANTS 20 FT. (NFPA 101, SECTION 12.2.5.1.2)
HAZARD
ASSEMBLY NO MORE THAN 50 OCCUPANTS 75 FT. (NFPA 101, SECTION 12.2.5.1.2)
STAIRWAYS 0.3 INCHES PER PERSON 36 INCHES

REVISIONS
RAMPS 0.2 INCHES PER PERSON 36 INCHES
CORRIDORS (< 50 PEOPLE) 0.2 INCHES PER PERSON 36 INCHES ACTUAL

Description
CORRIDORS (≥ 50 PEOPLE) 0.2 INCHES PER PERSON 44 INCHES ASSEMBLY GREATER THAN 50 OCCUPANTS SEE LIFE SAFETY PLANS
PASSAGEWAYS 0.2 INCHES PER PERSON 36 INCHES ASSEMBLY NO MORE THAN 50 OCCUPANTS SEE LIFE SAFETY PLANS
DOORS 0.2 INCHES PER PERSON 32 INCHES
DEAD-END CORRIDORS: ALLOWABLE DEAD-END CORRIDORS
STAIRWAY DIMENSIONAL REQUIREMENTS: WIDTH: 44 INCHES REQUIRED (NFPA 101, TABLE 7.2.2.2.1.2(B)) - PROVIDED ASSEMBLY 20 FT. (NFPA 101, SECTION 12.2.5.1.3)

Symbol
HEADROOM: 80 INCHES REQUIRED (NFPA 101, TABLE 7.2.2.2.1.1(A)) - PROVIDED ACTUAL
ASSEMBLY SEE LIFE SAFETY PLANS
STAIR TREADS AND RISERS: 44 INCH MINIMUM TREAD WIDTH REQUIRED (NFPA 101, TABLE
7.2.2.2.1.2(B)) - PROVIDED
11 INCH MINIMUM TREAD DEPTH REQUIRED (NFPA 101, TABLE FIRE DEPARTMENT NEEDS:
7.2.2.2.1.1(A)) - PROVIDED
7 INCH MAXIMUM RISER HEIGHT REQUIRED (NFPA 101, TABLE PREMISES IDENTIFICATION: APPROVED ADDRESS NUMBERS PLACED IN A POSITION TO BE PLAINLY LEGIBLE AND VISIBLE FROM THE STREET OR ROAD FRONTING THE
7.2.2.2.1.1(A)) - PROVIDED PROPERTY REQUIRED (NFPA 1, SECTION 10.11.1) - PROVIDED
ADDRESS NUMBERS CONTRAST WITH THEIR BACKGROUND REQUIRED (NFPA 1, SECTION 10.11.1.2) - PROVIDED
STAIRWAY LANDINGS: LANDING DIMENSION, MEASURED IN THE DIRECTION OF TRAVEL, NOT

B. McCOMBS
ADDRESS NUMBERS SHALL BE ARABIC NUMERALS OR ALPHABET LETTERS REQUIRED (NFPA 1, SECTION 10.11.1.3) - PROVIDED
LESS THAN THE WIDTH OF THE STAIR REQUIRED (NFPA 101, SECTION

Submitted by:
Reviewed by:
Designed by:
7.2.2.3.2.3) - PROVIDED

Drawn by:
FIRE DEPARTMENT ACCESS: AT LEAST ONE MEANS OF ALL-WEATHER GROUND ACCESS NO FARTHER THAN 33 FT. FROM THE BUILDING REQUIRED (UFC 3-600-01,

JMW

DBN
SAB
SECTION 9-1.1) - PROVIDED
VERTICAL RISE: LESS THAN OR EQUAL TO 12 FT. PER LANDING REQUIRED (NFPA 101,
TABLE 7.2.2.2.1.1(A)) - PROVIDED AT LEAST ONE MEANS OF ALL-WEATHER GROUND ACCESS NO FARTHER THAN 150 FT. FROM FIRE DEPARTMENT CONNECTION REQUIRED
(UFC 3-600-01, SECTION 9-1.4) - PROVIDED
FIRE DEPARTMENT ACCESS ROADS SUCH THAT ANY PORTION OF THE FACILITY OR ANY PORTION OF AN EXTERIOR WALL OF THE FIRST STORY OF THE
HANDRAILS: ON EACH SIDE REQUIRED (NFPA 101, SECTION 7.2.2.4.1.1) - PROVIDED
BUILDING IS LOCATED NOT MORE THAN 450 FT. FROM FIRE DEPARTMENT ACCESS ROADS REQUIRED (NFPA 1, SECTION 18.2.3.2.2.1) - PROVIDED
FIRE APPARATUS ACCESS ROADS UNOBSTRUCTED WIDTH NOT LESS THAN 20 FT. AND UNOBSTRUCTED VERTICAL CLEARANCE NOT LESS
RAMP DIMENSIONAL REQUIREMENTS: WIDTH: SEE TABLE ABOVE THAN 13.5 FT. REQUIRED (NFPA 1, SECTIONS 18.2.3.4.1.1 AND 18.2.3.4.1.2) - PROVIDED

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


FORCE PROTECTION EQUIPMENT ARRANGED TO NOT REQUIRE MORE THAN ONE PERSON TO REMOVE OR OPEN REQUIRED (UFC 3-600-01,
HEADROOM: 80 INCHES REQUIRED (NFPA 101, SECTION 7.1.5) - PROVIDED SECTION 9-1.3) - PROVIDED
LOCKING DEVICES CONTROLLING VEHICLE ACCESS UNDER CONTROL OF FIRE DEPARTMENT REQUIRED (UFC 3-600-01, SECTION 9-1.3) -
PROVIDED
C:\Users\sbrinkmeyer.pcs\Documents\R18_70374-000_F_sbrinkmeyer8U4LS.rvt

REDUCTIONS IN WIDTH: RAMPS AND INTERMEDIATE LANDINGS CONTINUE WITH NO


DECREASE IN WIDTH ALONG THE DIRECTION OF EGRESS TRAVEL KEY BOX: REQUIRED (NFPA 1, SECTION 18.2.2.1) - PROVIDE PER THE DIRECTION OF GOODFELLOW AIR FORCE BASE FIRE DEPARTMENT
REQUIRED (NFPA 101, SECTION 7.2.5.4.2(7)) - PROVIDED

17th TRAINING WING


NATURE OF WORK:
FIRE HYDRANTS: FIRE HYDRANTS INSTALLED SO THAT ALL PARTS OF THE FACILITY EXTERIOR IS WITHIN 350 FEET OF A HYDRANT WITH CONSIDERATION
RAMP LANDINGS LANDINGS AT THE TOP, AT THE BOTTOM, AND AT DOOR LEAVES GIVEN TO ACCESSIBILITY AND OBSTRUCTIONS REQUIRED (UFC 3-600-01, SECTION 9-3.5.8.2) - PROVIDED
OPENING ONTO THE RAMP REQUIRED (NFPA 101, SECTION 7.2.5.4.2(1))
- PROVIDED FOR ADDITION FIRE HYDRANT SPACING SUCH THAT ALL FIRE DEPARTMENT CONNECTIONS ARE WITHIN 150 FT. OF A FIRE HYDRANT REQUIRED (UFC 3-600-
01, SECTION 9-3.5.8.4(A)) - PROVIDED
LANDINGS SLOPE NO STEEPER THAN 1 IN 48 REQUIRED (NFPA 101,
3 FT. CLEAR SPACE AROUND CIRCUMFERENCE OF FIRE HYDRANTS REQUIRED (UFC 3-600-01, SECTION 9-3.5.7(G)) - PROVIDED
SECTION 7.2.5.4.2(2)) - PROVIDED FOR ADDITION
HEIGHT TO THE CENTER OF A HOSE OUTLET GREATER THAN OR EQUAL TO 18 IN. ABOVE FINAL GRADE REQUIRED (UFC 3-600-01, SECTION
EVERY LANDING WIDTH NO LESS THAN THE WIDTH OF THE RAMP
3-7.3.2 AND NFPA 24, SECTION 7.3.3) - PROVIDED
REQUIRED (NFPA 101, SECTION 7.2.5.4.2(3)) - PROVIDED FOR
ADDITION PHYSICAL PROTECTION FOR FIRE HYDRANTS THAT ARE SUBJECT TO IMPACT BY A MOTOR VEHICLE REQUIRED (UFC 3-600-01, SECTION 9-
EVERY LANDING LESS THAN 60 IN. LONG IN THE DIRECTION OF
3.5.9) - PROVIDED
TRAVEL REQUIRED (NFPA 101, SECTION 7.2.5.4.2(4)) - PROVIDED FOR
ADDITION
WHERE THE RAMP IS NOT PART OF AN ACCESSIBLE ROUTE, RAMP
LANDING NOT TO EXCEED 48 IN. IN THE DIRECTION OF TRAVEL, FIRE SAFETY AND EVACUATION PLANS: REQUIRED (NFPA 101, SECTION 12.2.10.3) - PROVIDED
PROVIDED THAT THE RAMP HAS A STRAIGHT RUN PERMITTED (NFPA
101, SECTION 7.2.5.4.2(5)) - NOT APPLICABLE
FIRE COMMAND CENTER: NOT REQUIRED (UFC 3-600-01 AND NFPA 101) - NOT PROVIDED

HANDRAILS: HANDRAILS PROVIDED ALONG SIDES OF A RAMP RUN WITH A RISE


GREATER THAN 6 IN. REQUIRED (NFPA 101, SECTION 7.2.5.5.2) -
PROVIDED FOR ADDITION

PROJECT TITLE
EDGE PROTECTION: CURBS, WALLS, RAILINGS, OR PROJECTION SURFACES NOT LESS
THAN 4 IN. IN HEIGHT THAT PREVENT PEOPLE FROM TRAVELING OFF
THE EDGE OF THE RAMP OR LANDING REQUIRED (NFPA 101, SECTION
7.2.5.4.3) - PROVIDED FOR ADDITION

HANDRAIL REQUIREMENTS: HEIGHT: 34 INCHES TO 38 INCHES REQUIRED (NFPA 101, SECTION 7.2.2.4.5.1) -
PROVIDED FOR ADDITION
Project Number:
GRASPABILITY: OUTSIDE DIAMETER OF 1.25-2 INCHES OR PERIMETER OF 4-6.25
INCHES WITH A MAXIMUM CROSS-SECTIONAL DIMENSION OF 2.25 OK70374-000
INCHES, EDGE RADIUS GREATER THAN OR EQUAL TO 0.125 INCH, SHEET TITLE
REQUIRED (NFPA 101, SECTION 7.2.2.4.5.6) - PROVIDED FOR ADDITION
LIFE SAFETY CODE NARRATIVE
CONTINUITY: HANDRAILS CONTINUE FOR THE FULL LENGTH OF EACH FLIGHT OF
STAIRS AND AT TURNS OF NEW STAIRS, INSIDE HANDRAILS SHALL BE
7/12/2018 11:28:17 AM

Date:
CONTINUOUS BETWEEN FLIGHTS AT LANDINGS REQUIRED (NFPA 101, 12 JUL 2018
SECTION 7.2.2.4.2) - PROVIDED FOR ADDITION

CLEARANCE: HANDRAILS INSTALLED TO PROVIDE A CLEARANCE OF NOT LESS


THAN 2.25 IN. BETWEEN THE HANDRAIL AND THE WALL TO WHICH IT IS SEQ. SHEET OF
FASTENED REQUIRED (NFPA 101, SECTION 7.2.2.4.5.5) - PROVIDED
FOR ADDITION

INTERMEDIATE HANDRAILS: 20 IN. MINIMUM CLEAR WIDTH BETWEEN HANDRAILS AND


G-004
INTERMEDIATE HANDRAILS REQUIRED (NFPA 101, SECTION 7.2.2.4.1.3)
- PROVIDED FOR ADDITION
EGRESS PATH SCHEDULE OVERALL OCCUPANCY CLASSIFICATION LIFE SAFETY LEGEND
TAG ABBREVIATIONS: SYMBOL DESCRIPTION
ASSEMBLY
CPT = COMMON PATH OF TRAVEL
MTD = MAXIMUM TRAVEL DISTANCE OUT OF SCOPE OF WORK EXTERIOR EXIT
DEC = DEAD-END COORIDOR
PATH INFORMATION 0 / 0" OCCUPANTS / REQUIRED WIDTH
TOTAL 0" PROVIDED WIDTH
C.R. ENGINEERING: #F-6671 EXPIRES JUNE 30, 2019

TAG LENGTH MAX. ALLOWABLE LENGTH Space: Number Space: Name


SP SMOKE PARTITION
CPT1.1 50' - 8" 75' - 0" 118 PREPARATION ROOM www.poolefire.com
CPT1.2 33' - 5" 75' - 0" 110 STORAGE
K KEY BOX
DEC1.1 11' - 5" 20' - 0" 117 EXISTING KITCHEN
MTD1.1 118' - 5" 250' - 0" 118 PREPARATION ROOM
EGRESS PATH
MTD1.2 126' - 7" 250' - 0" 103 PRIVATE DINING

Date Appr
XX#.# EGRESS PATH TAG
OLATHE, KS 66062 913.829.8650

### OCCUPANT LOAD TAG


POOLE FIRE PROTECTION
19910 W. 161ST STREET

OCCUPANT USE FACTOR


X A ASSEMBLY (LESS CONCENTRATED) (15 FT²/PERSON)

Description
B BUSINESS (UNCONCENTRATED) (150 FT²/PERSON)
S STORAGE (500 FT²/PERSON)
M MECHANICAL/ELECTRICAL (500 FT²/PERSON)
K KITCHEN (200 FT²/PERSON)

Symbol
Appr
Date

REVISIONS
195/ 32"
68"

Description
9

VESTIBULE

Symbol
104 B
472 SF
4
K
7
MTD1.2

FAMILY

SP
SP SP SP SP SP 6
TOILET
DEC1.1

B. McCOMBS
SP
105 B
EXISTING
SP

Submitted by:
Reviewed by:
Designed by:
60 SF EXISTING
WOMEN'S

Drawn by:
MECHANICAL DINING
SP

JMW
COMM

DBN
1

SAB
SP

108 B
107 M 116 A
106 M SP
155 SF
308 SF CORRIDOR
SP

62 SF 2
1
2 115 B EXISTING
PRIVATE JAN.
SP

SP SP SP SP SP
439 SF
DINING 3 109 S
103 A OFFICE CONF. ROOM 32 SF

CRESSMAN DINING FACILITY EXPANSION


5

GOODFELLOW AIR FORCE BASE, TEXAS


424 SF 112 B 111 A 1 EXISTING
29 120 SF 114 SF KITCHEN
DINING STORAGE
1 8 117 K
102 A 110 S MTD1.1
C:\Users\sbrinkmeyer.pcs\Documents\R18_70374-000_F_sbrinkmeyer8U4LS.rvt

3605 SF 83 SF
STUDENT CPT1.2
241 EXISTING 1 4
ADMIN.
MEN'S

17th TRAINING WING


113 B

NATURE OF WORK:
R R R
R
R

114 B
379 SF
155 SF
3
2
L
L

VESTIBULE
101 B CPT1.1
472 SF 3
4

PROJECT TITLE
195/ 32"
68"

1
PREPARATION
ROOM
118 K
379 SF
2

Project Number:

A B C D E F G OK70374-000

SHEET TITLE

LIFE SAFETY FLOOR PLAN


7/12/2018 11:28:26 AM

Date:
12 JUL 2018

LIFE SAFETY FLOOR PLAN


1 3/32" = 1'-0"
PLAN NORTH
12' 6' 0 12'
SEQ. SHEET OF

SCALE: 3/32" = 1'-0" G-005


C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018 EXISTING(LEGEND FROM SURVEYOR) NEW HATCH PATTERNS LEGEND ABBREVIATIONS

FIRE HYDRANT AI AREA INLET


FIRE HYDRANT FH HEAVY DUTY CONCRETE BOC BACK OF CURB
WATER VALVE ASPHALT PAVING SIDEWALK CB CATCH BASIN
OKLAHOMA CITY, OK 73112 405.416.8100

CI CURB INLET
WATER METER FIRE DEPT. CONNECTION FDC C COMMUNICATIONS
CMH COMM. MANHOLE
_ICV C.O. CLEAN OUT
ASPHALT PAVING GRAVEL PAVING

Date Appr
POST INDICATOR VALVE CP CULVERT PIPE
GAS VALVE CU UNDERGROUND COMMUNICATIONS
C.H. GUERNSEY & COMPANY

CWS CHILLED WATER SUPPLY


STORM MANHOLE WATER VALVE CWR CHILLED WATER RETURN
HEAVY DUTY CY CUBIC YARD
SOD / GRASS
5555 N. GRAND BLVD.

SANITARY SEWER MANHOLE CONCRETE PAVING E ELECTRIC LINE


WATER METER W EMH ELECTRIC MANHOLE

Description
SEWER CLEANOUT F FIRE LINE
FDC FIRE DEPARTMENT CONNECTION
LIGHT POLE GAS VALVE FES FLARED END SECTION
CONCRETE PAVING INLAID TRUNCATED DOMES FFE FINISHED FLOOR ELEVATION
ELEC. MANHOLE
FH FIRE HYDRANT
TELE. MANHOLE GAS METER G FL FLOW LINE
FM FORCE MAIN

Symbol
TREE REINFORCED FOC FACE OF CURB
SANITARY SEWER MANHOLE S CONCRETE PAVING
RIP-RAP FO FIBER OPTIC
CONTROL POINT G GAS LINE
GR GAS REGULATOR
CLEANOUT CO GM GAS METER

Appr
REF. DETAIL NUMBER GV GAS VALVE
Wx WATER LINE
HDPE HIGH DENSITY POLYETHYLENE

Date
LIFT STATION L HH HAND HOLE
Gx Gx GAS LINE
X HW HEADWALL
DETAIL REFERENCE HWS HOT WATER SUPPLY

REVISIONS
SDx STORM SEWER
STORM SEWER MANHOLE
C-50_
HWR HOT WATER RETURN
SS x SANITARY SEWER HAG HORIZONTAL AT GRADE

Description
REF. SHEET NUMBER OF DETAIL HUG HORIZONTAL UNDERGROUND
CATCH BASIN/AREA INLET HYD HYDRANT
Ex PRIMARY UNDERGROUND ELECTRIC
JBOX JUNCTION BOX
Cx UNDERGROUND COMM. INV INVERT
CURB INLET X X I.P. IRON PIN
E-CATV UNDERGROUND TV CABLE C-50_ C-50_ IW INDUSTRIAL WASTE
IRR IRRIGATION LINE

Symbol
PIPE END SECTION REF. SECTION NUMBER LF LINEAR FEET
LP LIGHT POLE
L.S. LIFT STATION
HEADWALL X X MH MANHOLE
SECTION REFERENCES
C-50_ C-50_ M.W. MONITORING WELL
OHE OVERHEAD ELECTRIC
DIRECTION OF FLOW RCP REINFORCED CONCRETE PIPE
FLOW FLOW REF. SHEET NUMBER OF SECTION PB PULL BOX
PE POLYETHYLENE
INDUSTRIAL WASTE MANHOLE I PED PEDESTAL/RISER
P.I.V. POST INDICATOR VALVE
JOINTING LEGEND

R. FAIRSHEETS
PP POWER POLE
I

Submitted by:
INDUSTRIAL WASTE METER

Reviewed by:

GUERNSEY
Designed by:
PSI POUND PER SQUARE INCH

C. MORRIS
K. HANES
LONGITUDINAL / TRANSVERSE

Drawn by:
PVC POLYVINYL CHLORIDE PIPE
CONSTRUCTION / CONTRACTION JOINTS SD STORM DRAIN
SIGN SF SILT FENCE
EXPANSION JOINTS SF SQUARE FEET
E SS SANITARY SEWER

CRESSMAN DINING FACILITY EXPANSION


HANDICAP SYMBOLS THICKENED EDGE JOINTS TC TOP OF CURB

GOODFELLOW AIR FORCE BASE, TEXAS


DOWELED JOINTS TELE TELEPHONE LINE
TMH TELEPHONE MANHOLE
WHEELSTOP TR TELEPHONE RISER
UE UNDERGROUND ELECTRIC
REINFORCED CONCRETE VAG VERTICAL AT GRADE
BOLLARD/GUARD POST R
PANEL W WATER LINE
WMH WATER MANHOLE
WM WATER METER
FLAG POLE WV WATER VALVE

17th TRAINING WING


NATURE OF WORK:
DOMESTIC WATER LINE W
FIRE PROTECTION LINE F
NATURAL GAS LINE G
SANITARY SEWER LINE SS
FORCEMAIN FM
STORM SEWER LINE SD
ROOF DRAIN RD
INDUSTRIAL WASTE LINE INW
IRRIGATION LINE LS
UNDERGROUND ELECTRIC E
UNDERGROUND COMM. LINE CU
FENCE X X X

PROJECT TITLE
FENCELINE1
FENCELINE2
GUARDRAIL
PROPERTY LINE
LIMITS OF CONSTRUCTION
FLOW LINE
RIGHT OF WAY / EASEMENT Project Number:

BUILDING SET BACK LINE OK70374-000


RAILROAD TRACKS
SHEET TITLE
REMOVE / DEMO SILT FENCE
NOTE: ITEMS TO BE DEMOLISHED/REMOVED WILL BE BOLD AND SF CIVIL LEGEND
HATCHED: EXAMPLES BELOW CONTOUR 1200
4/24/2018 11:16:09 AM

TC (TOP OF CURB) Date:


SPOT ELEVATION G (GUTTER) 12 JUL 2018
DOMESTIC WATER LINE Wx
TREE LINE

ASPHALT PAVING SEQ. SHEET OF

C-001
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

TBM-[] @ BC

10.9'

11'
ELEV.=1868.17
OKLAHOMA CITY, OK 73112 405.416.8100

CONTROL POINT #1 DEMOLITION NOTES:


SET 1/2" IRON ROD WITH RED

x
SD
CAP MARKED "CONTROL" ALTERNATE #5: SAW CUT AND 1. ALL UNDERGROUND UTILITIES SHOWN WERE LOCATED FROM

Date Appr
CONTROL POINT #2 INFORMATION OBTAINED ON SITE, PREVIOUS SURVEY AND
NORTHING=10484192.64' REMOVE ASPHALT PAVEMENT AND
REMOVE PARKING

Gx
SET 1/2" IRON ROD WITH RED RECORDED DOCUMENTS. NO EXCAVATION WAS PERFORMED TO
C.H. GUERNSEY & COMPANY

EASTING=2273230.09' CURB AND GUTTER. SEE NOTE 13.


AND ADA STRIPING.

SD
CAP MARKED "CONTROL" DETERMINE THE SIZE OR LOCATION. NOT NECESSARILY ALL
ELEV.=1868.21'
(TYP.) NORTHING=10484187.28' UNDERGROUND UTILITIES ARE SHOWN AND THOSE SHOWN ARE IN

x
EASTING=2273516.19' APPROXIMATE LOCATION ONLY. IT SHALL BE THE RESPONSIBILITY
REMOVE LIGHT POLE
5555 N. GRAND BLVD.

ELEV.=1868.70' OF THE CONTRACTOR TO VERIFY ALL UNDERGROUND UTILITIES


17' 50.5' RE: ES101
AND THE LOCATIONS THEREOF PRIOR TO BEGINNING

Description
x

SS x Wx
CONSTRUCTION. NO RESPONSIBILITY IS HEREBY EXTENDED FOR

SD
THE LOCATION OF UNDERGROUND UTILITIES.

Gx
2. THE CONTRACTOR SHALL CONTACT UTILITY LOCATE SERVICE TO

10.9'

SD
11'
LOCATE EXISTING UTILITIES PRIOR TO WORK BEGINNING.

x
SEE NOTE 11 3. EXISTING PAVEMENT, SIDEWALK OR CURB TO BE REMOVED SHALL

Symbol
BE SAW CUT TO FULL DEPTH AND EDGES SHALL BE STRAIGHT AND
X X X X X X
Wx Wx X X X X X UNIFORM.

x
Wx

SD
Wx Wx Wx Wx Wx Wx Wx Wx
22.9' 4. CONTRACTOR SHALL VERIFY THE PROJECT BENCHMARKS AND

Appr
LIMITS OF CONSTRUCTION BEFORE CONSTRUCTION BEGINS.
X

Ex Ex Ex Ex

SS x
E-CATV
E-CATV E-CATV E-CATV Ex

SD
E-CATV Wx Wx Wx 5. CONTRACTOR SHALL VERIFY LOCATIONS OF ALL EXISTING

Date
x
REMOVE RAMP, STAIRS, Wx Wx BUILDING FINISHED FLOOR ELEVATIONS AND RELEVANT
HANDRAILS AND PORCH
Wx
STRUCTURES BEFORE CONSTRUCTION BEGINS.
Ex

REVISIONS
SS x SS x SS x SS x SS x SS x SS x SS x SS x 6. CONTRACTOR SHALL CLEAN OUT EXISTING STORM STRUCTURES
X

C
Cx

x PRIOR TO BEGINNING CONSTRUCTION.

Description
CONSTRUCTION C 7. CONTRACTOR SHALL COORDINATE ALL EXISTING UTILITIES, TO BE
x REMOVE CONCRETE EDGING. TEMPORARY REMOVED AND/OR RELOCATED, WITH CIVIL, MECHANICAL,
FENCE (TYP.) WEAPON CLEARING BARREL ADA RAMP, ELECTRICAL, AND PLUMBING PLAN DRAWINGS.

SS x
TO BE RE-LOCATED. RE: L-100 SEE NOTE 10

Wx
C
X

UNDERGROUND COMM x 8. ALL DIMENSIONS ARE TO BACK OF CURB, FACE OF BUILDING,


LINE TO BE REMOVED EXISTING CLEANOUT TO TEMPORARY
CENTER OF FENCE, CENTER OF PAINT STRIPE, AND TO CENTER OF

Symbol
BACK TO PULL BOX AND REMAIN AND BE RAISED TO ENTRANCE
Ex

C PIPE, UNLESS OTHERWISE NOTED.


RELOCATED. RE:C-150 x NEW FINISHED GRADE. RE:
P101 FOR CONTINUATION. 9. ALL DIMENSIONS ARE IN FEET UNLESS OTHERWISE NOTED.
Cx

APACHE TRAIL
X

REMOVE LIGHT EXISTING CLEANOUT


POLES. RE: KEYED 10. CONTRACTOR TO PROVIDE TEMPORARY ADA RAMP WITH
REMOVE TO REMAIN. RE: P-101 HANDRAILS. SLOPE OF RAMP IS NOT TO EXCEED 8.33%.
TREES NOTE 1/ ES101 FOR CONTINUATION.

Wx
SS x
11. CONTRACTOR IS TO PROVIDE SIGNAGE INDICATING LOCATION OF
RE: AD-100 FOR
TEMPORARY ENTRANCES.
EXISTING BUILDING
X

DEMOLITION. (TYP.)
12. IF ALTERNATE #1, FOOD PREP ADDITION, IS SELECTED, ADD

R. FAIRSHEETS
Ex

REMOVE EXISTING CLEANOUT TO CONSTRUCTION FENCE, AS SHOWN. IF NOT SELECTED, OMIT.

Submitted by:
Reviewed by:

GUERNSEY
Designed by:

C. MORRIS
K. HANES
SIDEWALK (TYP.) REMAIN AND BE RAISED TO

Drawn by:
Cx

NEW FINISHED GRADE. RE: 13. IF ALTERNATE #5, SPEED TABLE, IS SELECTED, ADD PAVEMENT
P101 FOR CONTINUATION. REMOVAL, CURB AND GUTTER DEMOLITION, AND RAMP/SIDEWALK
REMOVAL. IF NOT SELECTED, OMIT ABOVE ITEMS. GRAVEL IN
X

TEMPORARY ALTERNATE #1: RE: AD-100 CURB ISLANDS ON BUILDING SIDES IS TO BE REMOVED AND
EXISTING CLEANOUTS

W
ENTRANCE FOR EXISTING BUILDING REPLACED, PER LANDSCAPE PLANS, REGARDLESS OF SELECTION

CRESSMAN DINING FACILITY EXPANSION


x
SS x
TO REMAIN. RE: P-102

GOODFELLOW AIR FORCE BASE, TEXAS


DEMOLITION (TYP.) FOR CONTINUATION OF ALTERNATES.
TEMPORARY
ADA RAMP,
SEE NOTE 10 SURVEY PROVIDED BY:
Ex
X

REMOVE RAMP, STAIRS, SKG ENGINEERING, LLC SURVEYING, ENVIRONMENTAL, LAB/CMT


HANDRAILS AND PORCH 706 SOUTH ABE STREET
Cx

SAN ANGELO, TEXAS 76903


5' MIN. PH: 325.655.1288 FAX: 325.657.8189
REMOVE CONCRETE EDGING. CONSTRUCTION

Wx
X
WEAPON CLEARING BARREL FENCE FLOOD ZONE
X

SEE NOTE 11

17th TRAINING WING


TO BE RE-LOCATED. RE: L-100 SEE NOTE 12

NATURE OF WORK:
X X Wx Wx THIS PROPERTY LIES ENTIRELY WITHIN FLOOD ZONE(S) 'X'
ACCORDING TO FEMA MAP NUMBER 48451C0495E, JUNE 19, 2012.
X X
BASIS OF BEARING
Ex

x
SS
SAW CUT AND REMOVE
X

CURB AND GUTTER. COORDINATES SHOWN HEREIN ARE BASED ON TEXAS STATE PLANES,
Cx

(TYP.) CENTRAL ZONE, US FOOT (TX83-CF)


17' 61.5' DISTANCES SHOWN ARE SURFACE HORIZONTAL.
REMOVE

Wx
X
GRAVEL (TYP.)
X X X X X X X
X X X X X X
10.8'

11'

x
X

SS
Ex

X
SDx

SDx
Cx

REMOVE PARKING ALTERNATE #5: SAW CUT AND


STRIPING. (TYP.)

Wx
REMOVE ASPHALT PAVEMENT AND
Wx

CURB AND GUTTER. SEE NOTE 13.


CONTRACTOR

PROJECT TITLE
X

X
LAY DOWN AREA

x
SS
Ex

SDx

SDx

X
0 20 40
10.8'
Cx

Wx
11'
Wx

SDx X X X X SCALE OF FEET Project Number:


SDx
X X
SDx
SDx OK70374-000
SDx SDx
x
Wx SDx SDx SS SDx SHEET TITLE
Wx Wx Wx SDx EXISTING CONDITIONS AND
Wx SDx SDx
Ex Wx Wx Wx DEMOLITION PLAN
Ex Ex Wx Wx Wx
Ex Ex Ex Ex
4/24/2018 11:16:09 AM

Cx Cx Cx Cx Cx Ex Ex Date:
Cx Cx Cx 12 JUL 2018

SDx

Wx
x

SEQ. SHEET OF
SS

C-100
1 EXISTING CONDITIONS AND DEMOLITION PLAN
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

8'
1
OKLAHOMA CITY, OK 73112 405.416.8100

CURB AND GUTTER 19.5'


C-501
(TYP.)
SITE NOTES:

Date Appr
1. ALL DIMENSIONS ARE TO BACK OF CURB, FACE OF BUILDING,
CENTER OF FENCE, CENTER OF PAINT STRIPE, AND TO CENTER
C.H. GUERNSEY & COMPANY

OF PIPE, UNLESS OTHERWISE NOTED.


6.1' 18' 11' 4 @ 9' = 36'

27'
5' 11' 9.5'
5 2. ALL DIMENSIONS ARE IN FEET UNLESS OTHERWISE NOTED.
SCREEN WALL
5555 N. GRAND BLVD.

A-301
3. ALL RADII ARE 5 FT., UNLESS OTHERWISE NOTED.

Description
8'

18.5' (TYP.)
4. ALL PARKING STRIPING SHALL BE 4 IN. WIDE WHITE PAINTED
STRIPE.
19.5' 5. TYPICAL SIDEWALK, PROVIDE CONTROL JOINTS AT 5 FT. ON
CENTER AND EXPANSION JOINTS AT 25 FT. ON CENTER, REFER
N:10484198.72 7.4' TO DETAIL 2 C-501
/ .

8'

Symbol
E:2273157.52
R45' 6. CONCRETE SURROUNDING TROOPWALK PAVERS IS TO BE
22.6' 2.5' THICKENED TO 8 INCHES AND REINFORCED. RE: 1/L-121.

R1
0'
5'

5.8'
R2

Appr
N:10484189.20
R2 5'

49.3'
E:2273164.05

16'
ADA

Date
3 3'x3' TRANSFORMER PAD
STRIPING
N:10484167.38 C-503 2.5'
DETAIL (TYP.)

REVISIONS
E:2273141.25 12'x8' MECHANICAL PAD

N:10484161.20 3 RISERS

Description
E:2273146.34 CONCRETE
2
EQUIPMENT
C-501
PAD (TYP.)

R62

Symbol
'

CRESSMAN DINING HALL


EXPANSION
F.F.E = 1870.38
1
STAIRS AND SWITCHBACK RAMP

R. FAIRSHEETS
C-111
PLAN ENLARGED DETAIL (TYP.)

Submitted by:
Reviewed by:

GUERNSEY
Designed by:

C. MORRIS
K. HANES
Drawn by:
N:10484086.18
E:2273130.02
8'
N:10484082.68 FIBER REINFORCED
E:2273122.83 3
CONCRETE SIDEWALK

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


C-501
(TYP.)

4 RISERS ALTERNATE #1
FOOD PREP
ADDITION
TROOPWALK CONCRETE F.F.E.=1870.38
1 7'
R45 AND PAVERS (TYP.)
' L-121
SEE NOTE 6

17th TRAINING WING


NATURE OF WORK:
N:10484032.54
59.8'

E:2273126.02 R3
N:10484024.39 5'
E:2273105.80 ADA RAMP
1 5'
R3
R1 0' HANDICAP DETAIL

42.7'
0'
R1 SIGN POST
4 C-503
(TYP.) 0'

R1
C-503 R1

0'
(TYP.)

8'
17'
18.5' (TYP.)

8'
TRANSITION DOWN
TO GUTTER (TYP.)

12.6' 6.9' 12' 5 @ 9' = 45' 9.5'

4
29'

PROJECT TITLE
C-501

0 20 40

SPEED LIMIT SCALE OF FEET


5 17'
SIGN POST
C-501 8'
(TYP.)

Project Number:

OK70374-000
SHEET TITLE

SITE PLAN
4/24/2018 11:16:09 AM

Date:
12 JUL 2018

1 SITE PLAN SEQ. SHEET OF

C-110
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
OKLAHOMA CITY, OK 73112 405.416.8100

NOTES:

Date Appr
1. ALL RETAINING WALL FOOTINGS ADJACENT TO BUILDING GRADE
BEAMS SHALL BE ONE-SIDED FOOTING, AND SHALL BE
C.H. GUERNSEY & COMPANY

CONSTRUCTED ACCORDING TO DETAIL 5B ON C-504. ALL OTHER


3 2 1 RETAINING WALL FOOTINGS SHALL BE TWO-SIDED FOOTINGS,
C-504 C-504 C-504 AND SHALL BE CONSTRUCTED ACCORDING TO DETAIL 5A ON
5555 N. GRAND BLVD.

C-504.

Description
2. PROVIDE EXPANSION JOINTS BETWEEN ALL RETAINING WALLS
AND GRADE BEAMS.
CRESSMAN DINING HALL
EXPANSION

Symbol
5.7'
9.3'

Appr
Date

REVISIONS
Description
ONE-SIDED

Symbol
5B
FOOTING (TYP.)
C-504
SEE NOTE 1 AND 2.

10'
8.1'

4
BUILDING SLAB
RE: STRUCTURAL PLANS C-504

R. FAIRSHEETS

Submitted by:
Reviewed by:

GUERNSEY
Designed by:

C. MORRIS
14.7'

K. HANES
26'

Drawn by:
1
C-502 4.3'

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


TWO-SIDED
5A
FOOTING (TYP.)
C-504
SEE NOTE 1.
5.2'

17th TRAINING WING


5'

NATURE OF WORK:
4.3'

8.4' 8.4'
10.6'

1.1'

8" CURB N
(TYP.)

FOOTING OUTLINE (TYP.)

PROJECT TITLE
1.8'

HANDRAIL (TYP.)
0 2 4

SCALE OF FEET

Project Number:

OK70374-000
SHEET TITLE

ENLARGED PLAN DETAILS


4/24/2018 11:16:09 AM

Date:
12 JUL 2018

SEQ. SHEET OF

STAIRS AND SWITCHBACK


RAMP PLAN ENLARGED DETAIL C-111
1
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

TBM-[] @ BC
ELEV.=1868.17
OKLAHOMA CITY, OK 73112 405.416.8100

CONTROL POINT #1
SET 1/2" IRON ROD WITH RED UTILITY NOTES:

x
SD
CAP MARKED "CONTROL"

Date Appr
CONTROL POINT #2 1. ALL UNDERGROUND UTILITIES SHOWN WERE LOCATED FROM
NORTHING=10484192.64'

Gx
SET 1/2" IRON ROD WITH RED INFORMATION OBTAINED ON SITE, PREVIOUS SURVEY AND
EASTING=2273230.09'
C.H. GUERNSEY & COMPANY

SD
CAP MARKED "CONTROL" RECORDED DOCUMENTS. NO EXCAVATION WAS PERFORMED
ELEV.=1868.21'
NORTHING=10484187.28' TO DETERMINE THE SIZE OR LOCATION. NOT NECESSARILY ALL

x
EASTING=2273516.19' UNDERGROUND UTILITIES ARE SHOWN AND THOSE SHOWN ARE
5555 N. GRAND BLVD.

ELEV.=1868.70' IN APPROXIMATE LOCATION ONLY. IT SHALL BE THE


RESPONSIBILITY OF THE CONTRACTOR TO VERIFY ALL

Description
UNDERGROUND UTILITIES AND THE LOCATION THEREOF PRIOR

SS x Wx
SD
LP-5 TO BEGINNING CONSTRUCTION. NO RESPONSIBILITY IS HEREBY
EXTENDED FOR LOCATION OF UNDERGROUND UTILITIES.

Gx
SD
2. THE CONTRACTOR IS TO EXPOSE ALL EXISTING UTILITY

x
CONNECTIONS AND UTILITY CROSSINGS PRIOR TO THE START
OF ANY CONSTRUCTION TO VERIFY LOCATIONS OF

Symbol
CONNECTIONS. CONTRACTOR WILL NOTIFY THE OWNER AND
Wx ENGINEER OF ANY DISCREPANCIES OR CONFLICTS.
Wx

x
Wx

SD
Wx Wx Wx Wx Wx Wx Wx Wx 3. CONTRACTOR SHALL PLACE A MINIMUM REQUIRED COVER
OVER ALL PIPE DURING CONSTRUCTION TO PREVENT DAMAGE

Appr
Ex Ex Ex Ex

SS x
E-CATV E-CATV E-CATV E-CATV
Ex FROM CONSTRUCTION VEHICLES.

SD
E-CATV Wx Wx Wx
6" x 45°

Date
x
SEE NOTE 4 BEND (2) Wx Wx Wx 4. MAINTAIN MINIMUM 2 FOOT VERTICAL SEPARATION BETWEEN
EE E STORM SEWER AND SANITARY SEWER. CONTRACTOR SHALL
Ex

E
EXPOSE SANITARY SEWER LINE TO DETERMINE DEPTH AND

REVISIONS
SSC
xU SS x SS x SS x SS x 33.8' SS x SS x SS x SS x ADJUST STORM PIPE, AS NECESSARY.

6" HDPE
Cx

CU CU

Description
LP-4 5. EXPOSED TRENCHES WILL REQUIRE DE-WATERING AFTER
E E 6" x 45°

27.5'
BEND (2) STORM EVENTS.
CONNECT TO
EXISTING M.H. 6. ALL PIPE APPURTENANCES SUCH AS TEES, HORIZONTAL AND

SS x
CO

FL= 1865.76' VERTICAL BENDS WATER AND/OR ANY OTHER PRESSURIZED

Wx
PIPE SHALL HAVE THRUST BLOCKS OR MECHANICAL JOINTS.
REFRIGERANT LINES IN

Symbol
Ex

4" PVC TO CONDENSING 7. MINIMUM SLOPE OF STORM SEWER LINES IS 1%.


NEW COMM LINE ENTRY.
RE: ES101 UNIT; RE: M-101
Cx

APACHE TRAIL
SD CLEANOUT
FL= 1866.38'
LIGHT POLE POINT TABLE
CRESSMAN DINING HALL RE: P-101 FOR

Wx
SS x
EXPANSION ROOF DRAIN POINT
F.F.E = 1870.38 CONTINUATION NORTHING EASTING DESCRIPTION
NO.
LP-3
1 10483995.1 2273273.9 LP-1
Ex

R. FAIRSHEETS

Submitted by:
Reviewed by:

GUERNSEY
Designed by:

C. MORRIS
2 10484032.0 2273127.4 LP-2

K. HANES
Cx

Drawn by:
SD CLEANOUT
FL= 1866.38' 3 10484099.4 2273126.6 LP-3
4 10484156.5 2273142.8 LP-4

Wx
SS x

CRESSMAN DINING FACILITY EXPANSION


CO
5 10484214.7 2273276.5 LP-5

GOODFELLOW AIR FORCE BASE, TEXAS


23'
Ex

FOOD PREP
E

~
EXPANSION
Cx

6" x 11.25° F.F.E.=1870.38 3" PVC


6" HDP

BEND RE: P-102

Wx
E

17th TRAINING WING


NATURE OF WORK:
E E Wx Wx
49.7'

LP-2 PIPE TRENCH E


6
DETAIL
Ex

C-503

x
SS
(TYP.)
Cx

Wx
N
E

LP-1

x
SS
Ex

SDx

SDx
CONNECT TO
Cx

EXISTING M.H.

Wx
Wx

FL= 1865.21'

PROJECT TITLE
0 20 40

x
SS
Ex

SCALE OF FEET
SDx

SDx
Cx

Wx
Wx

SDx
SDx Project Number:
SDx
SDx OK70374-000
SDx SDx
x
Wx SDx SDx SS
SDx
Wx Wx Wx SDx
SHEET TITLE
Wx SDx SDx
Ex Wx Wx Wx UTILITY PLAN
Ex Ex Wx Wx Wx
Ex Ex Ex Ex Ex
4/24/2018 11:16:09 AM

Cx Cx Cx Cx Cx Cx Cx Ex Date:
Cx 12 JUL 2018

SDx
1 UTILITY PLAN

Wx
x
SS

SEQ. SHEET OF

C-150
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018 3,000 PSI CONCRETE
3 #5 @ 15" O.C.E.W. SEE SITE PLAN
4" SLOPE TOWARD GUTTER
PATCH TO MATCH EXISTING, EXPANSION JOINT FINISHED PREMOLDED
SEE NOTE 1 EXPANSION 1
AS REQUIRED GRADE 8"
FINISHED

6"
JOINT

/2 "
GRADE

4"
CURB AND

41
OKLAHOMA CITY, OK 73112 405.416.8100

6"
3"

R
GUTTER

6"
R

12"
1 FIBER REINFORCED 2"
1 4" AGGREGATE

6"

1"
CONCRETE SIDEWALK

Date Appr
6" BASE COURSE SAND CUSHION
C.H. GUERNSEY & COMPANY

COMPACTED BASE
MATERIAL 95% STD
(3) #3 CONT. LAP 18"
24" DENSITY MIN. EQUIPMENT PAD SECTION SEE SITE PLAN
5555 N. GRAND BLVD.

2 FINISHED 1" SEE NOTE 1


FINISHED
GRADE

Description
GRADE
BRUSH FINISHED CONCRETE CURB WITH 1/2"

4"
EXPANSION JOINT AT 40'-0", CONTROL JOINTS AT 8'-0"
O.C., EXPANSION JOINTS REQUIRED AT BEGINNING NOTES: CONTRACTION JOINT
AND END OF CURVES 2"
1. SECTION SHOWN SHALL BE CONSIDERED A MINIMUM REQUIREMENT. FIBER REINFORCED
CONCRETE SIDEWALK SAND CUSHION 1
CONTRACTOR SHALL VERIFY SECTION WITH EQUIPMENT 1 4"
CURB AND GUTTER 2"

Symbol
MANUFACTURER.
1 2. PAD LAYOUT SHALL BE AT LEAST 6-INCHES LARGER THAN FOOTPRINT
OF EQUIPMENT. CENTER EQUIPMENT ON PAD UNLESS FIBER REINFORCED 1
8"R
NOTE:
CONCRETE SIDEWALK DETAILS

Appr
RECOMMENDED OTHERWISE BY EQUIPMENT MANUFACTURER.
CONTRACTOR TO VERIFY CURB
PROFILE TO MATCH EXISTING. 3. REFER TO ELECTRICAL DESIGN FOR TRANSFORMER AND GENERATOR 3

Date
EQUIPMENT REQUIREMENTS.

REVISIONS
4. REFER TO MECHANICAL DESIGN FOR HVAC EQUIPMENT
REQUIREMENTS.
SIDEWALK NOTES:

Description
1. A CROSS SLOPE OF 1/4" PER FOOT SHALL BE PROVIDED (UNLESS NOTED OTHERWISE
ON THE GRADING PLAN) AND SHALL SLOPE TOWARDS THE DIRECTION OF POSITIVE
DRAINAGE IN THE AREA.
EXPANSION JOINT
2. CONCRETE WALKS SHALL BE GROOVED TRANS- VERSELY AT INTERVALS MATCHING
SIDE- WALK WIDTH (UNLESS OTHERWISE SHOWN) TO A DEPTH OF 1-INCH. WALKS

Symbol
OVER 10-FEET WIDE SHALL BE GROOVED LONGITUDINALLY TO A DEPTH OF 1-INCH.
ALL ODD-SHAPED PANELS AND ANY PANELS WHERE THE LENGTH EXCEEDS THE
WIDTH BY MORE THAN 25% SHALL BE REINFORCED WITH 6 INCH x 6 INCH – W2.9 x
W2.9 WIRE MESH. EXPANSION JOINTS SHALL BE INSTALLED AT 30 FEET MAXIMUM
SPACING.

3. 1/2" EXPANSION JOINTS SHALL BE SPACED NOT LESS THAN 30-FEET NOR MORE
THAN 50-FEET AND ON ONE SIDE WHEN WALK IS BETWEEN TWO CURBS.

4. 1/2" EXPANSION JOINTS SHALL BE INSTALLED AT INTERSECTIONS OF SIDEWALKS,


CURBS AND TO SURROUND OR TO SEPARATE ALL STRUCTURES OR FEATURES

R. FAIRSHEETS
WHICH PROJECT THROUGH OR AGAINST THE SIDEWALK SLAB (ie, FIRE HYDRANTS,

Submitted by:
Reviewed by:

GUERNSEY
Designed by:

C. MORRIS
SIGN POSTS, ETC).

K. HANES
Drawn by:
CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


POST CAP

SIGN MOUNTING
SAW CUT LINE AS SHOWN SAW CUT LINE AS SHOWN BOLTS
ON DEMOLITION PLAN ON DEMOLITION PLAN

17th TRAINING WING


NATURE OF WORK:
#5 BARS AT 18" O.C.E.W.
1' GUTTER VARIES 8' VARIES 1' GUTTER
SEE PLANS SEEPLANS
MATCH EXISTING PAVEMENT SLOPE EXISTING FLEXIBLE
EXISTING FLEXIBLE 9.5"
(SLOPE NOT TO EXCEED 2%) TYP. 6" PAVEMENT
PAVEMENT
TYP. 6
1
EXISTING SUBGRADE
EXISTING SUBGRADE C-501

3
SIGN MOUNTING
BOLTS

6' - 0"
2 12" STANDARD WEIGHT 30" x 30" W8-1 BLACK
GALV. STEEL SQUARE POST ON YELLOW W/6"
SERIES 'E' LEGEND
10
CONCRETE SPEED TABLE

1"
PROVIDE BREAK-AWAY
4 CONNECTION MPH

PROJECT TITLE
1 PORTLAND CEMENT CONCRETE
6 W8-1 SIGN DETAIL
3,000 PSI MINIMUM @ 28 DAYS

2' - 0"
CONCRETE FOOTING
1
2 6" CRUSHED LIMESTONE 2" DIAM. x 4" STEEL
PER TxDOT ITEM 247, TYPE A, GRADE 2 ROD THRU POST
Project Number:

3 6" COMPACTED SUBGRADE

3"
OK70374-000
95% COMPACTION PER A.S.T.M. D-698
SHEET TITLE
6% TO 12% LIME ADDED AT CONTRACTORS OPTION 1' - 0" DIA.
DETAILS
4/24/2018 11:16:09 AM

Date:

SPEED BUMP SIGN 12 JUL 2018

5 POST DETAIL
SEQ. SHEET OF

C-501
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
1' - 1" 3 TREADS @ 1' - 1" = 3' - 3" 1' - 1" 6.3'
OKLAHOMA CITY, OK 73112 405.416.8100

CENTER HANDRAIL ELEVATION

℄ POST
ONLY. CONTINUE AS NEEDED
FOR HANDRAILS ON EITHER

1' - 8"
SIDE OF STAIRS.

Date Appr
NOTE 1

EDGE OF STAIRS
C.H. GUERNSEY & COMPANY

3'-0"
2 3
(TYP.) 4" DIA. X 16" LONG SMOOTH
C-502 DOWEL @ 12" O.C. APPLY BOND 4" 4"
5555 N. GRAND BLVD.

BREAKER TO ONE END (TYP.)

Description
1' - 8"
7
1
2"
EXPANSION 32" DIA. WEEP HOLE
JOINT (TYP.) STRUCTURAL SLAB
AND GRADE BEAM NON-SHRINK

RISER HEIGHT = 5-5/8" (TYP.)


4" RE: STRUCTURAL GROUT
3
3 4" CHAMFER
(TYP.)

6"
C-502

4"
1"

Symbol
3"
SLOPE14" TYP.
8"

Appr
TROOPWALK TOP OF RETAINING WALL
1

2' - 0"
DETAIL

5"
L-121

Date
(TYP.)

6"
NOTE 3

REVISIONS
8"

Description
ENGINEERED FILL 2" DIA. x 6" SCH. 40
COMPACTED TO 95% 1' - 0" STEEL PIPE SLEEVE
STANDARD PROCTOR
1' - 4"

FOOTING BEYOND

Symbol
CLOSER PLATE18" x 3" x 3"
5A TACK WELD TO PIPE
2-#4 TOP AND BOTTOM C-504
W/ #3 STIRRUPS @ 18"
C/C (TYPICAL) 1' - 0"

2 HANDRAIL POST SLEEVE


1 STAIRS LONGITUDINAL SECTION

R. FAIRSHEETS

Submitted by:
Reviewed by:

GUERNSEY
Designed by:

C. MORRIS
K. HANES
Drawn by:
NOTES:

1. 112" STANDARD SCHEDULE 40 STEEL PIPE POSTS AND RAILING.


WELD AND GRIND JOINTS SMOOTH, HOT DIPPED GALVANIZED

CRESSMAN DINING FACILITY EXPANSION


AFTER FABRICATION.

GOODFELLOW AIR FORCE BASE, TEXAS


2. STAIR WIDTH (BETWEEN RETAINING WALLS)1=4".8'-4

3. ALUMINUM NON-SLIP TREAD NOSING WITH ANCHORS AND


#4 NOSING REBAR.

17th TRAINING WING


NATURE OF WORK:
℄ HANDRAIL

℄ HANDRAIL

℄ HANDRAIL

TO TOP OF HANDRAIL
2' - 8" (TYP.)

PROJECT TITLE
1 RISER BEYOND
2" EXPANSION
JOINT (TYP.)

RE:1/C-502
8' - 414" (TYP.)

VARIES
Project Number:

OK70374-000
#4 @ 12" O.C.E.W.
ENGINEERED FILL SHEET TITLE
COMPACTED TO 95% DETAILS
STANDARD PROCTOR (TYP.)
TWO-SIDED
5A
4/24/2018 11:16:09 AM

FOOTING Date:
C-504 12 JUL 2018
(TYP.)

3 STAIRS TRANSVERSE SECTION SEQ. SHEET OF

C-502
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018 6' - 0" 5' - 0"
6' - 0"
TERMINATE TERMINATE
CURB
CURB CURB

60"
6" CURB
OKLAHOMA CITY, OK 73112 405.416.8100

(TYP.)

MAX.
1:50
1:12 1:12
MAX. MAX.
CAP COVER

Date Appr
.9"Ø A
REPLACEABLE

8' - 0"
2
C.H. GUERNSEY & COMPANY

TRUNCATED

24"
C-503
DOME

2.35"
.2"
5555 N. GRAND BLVD.

24" MIN

Description
CONCRETE SIDEWALK, ANCHOR 2.35"
BACK OF REF. DETAIL #3/C-501 BOLT
CURB
PLAN VIEW
SECTION - A ENLARGED PLAN
SEE
6' - 0" 6' - 0" ENLARGED
TERMINATE 5' - 0" PLAN
TERMINATE

Symbol
CURB CURB
SIDE VIEW

LIP OF
REPLACEABLE TRUNCATED DOME INSERT

Appr
GUTTER
PLAN - ALONG SIDEWALK
2

Date
1 HANDICAP RAMP DETAIL NOTES:

REVISIONS
1. INSERTS SHALL EXTENDED FROM EDGE TO EDGE OF WALKWAY ENTERING THE CROSSWALK

Description
AT STREET LEVEL.

2. INSERTS SHALL BE ADA COMPLIANT AND CONSIST OF TRUNCATED DOMES WITH A NOMINAL
DIAMETER OF 0.9", A NOMINAL HEIGHT 0.2" AND A CENTER-TO-CENTER SPACING OF NOMINAL
2.35" AND SHALL CONTRAST VISUALLY WITH ADJOINING SURFACES, EITHER LIGHT-ON-DARK
OR DARK-ON-LIGHT.

Symbol
3. THE MATERIAL USED TO PROVIDE CONTRAST SHALL BE AN INTEGRAL PART OF THE WALKING
SURFACE. MATERIAL COLOR SHALL BE BRICK RED UNLESS INDICATED OTHERWISE.

R. FAIRSHEETS

Submitted by:
Reviewed by:

GUERNSEY
Designed by:

C. MORRIS
K. HANES
Drawn by:
4
C-503 6" 6"

112"
POST CAP
12"

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


SIGN MOUNTING 12"
BOLTS
112"

CONCRETE BACK OF CURB


GUTTER
5

17th TRAINING WING


NATURE OF WORK:
6"

C-503

45°
7' - 0"

18"
EQUAL SIGN MOUNTING
BOLTS
4" WHITE STRIPE (TYP.)
6' - 0"

2 12" STANDARD WEIGHT


GALV. STEEL SQUARE POST
1"

PROVIDE BREAK-AWAY
CONNECTION
18.5'

R7-8
3'

2' - 0"

CONCRETE FOOTING

PROJECT TITLE
1
2" DIAM. x 4" STEEL
ROD THRU POST
6"
3"

12"
1' - 0" DIA.
R7-8P
CL
ACCESSIBILITY
SYMBOL PER M.U.T.C.D.
6 PIPE TRENCH DETAIL Project Number:

VARIES
SEE PLANS
VARIES
SEE PLANS
VARIES
SEE PLANS
HANDICAP SIGN HANDICAP OK70374-000

4 POST DETAIL 5 SIGN DETAIL SHEET TITLE

DETAILS

3 ADA STRIPING DETAIL


4/24/2018 11:16:09 AM

Date:
12 JUL 2018

SEQ. SHEET OF

C-503
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018 NEW DINING 1 12" DIA. STEEL PIPE
FACILITY EXPANSION HANDRAIL (TYP.)

NEW CONVERED
ENTRY PORCH

TYP.

12" 0.C.
OKLAHOMA CITY, OK 73112 405.416.8100

TYP.
1'
HANDRAIL
2
POST SLEEVE

TYP.

VARIES
TYP.
C-502

36"
3'
(TYP.) NEW COVERED

Date Appr
36"
ENTRY PORCH
MAXIMUM DISTANCE
C.H. GUERNSEY & COMPANY

1 4'-4" 4'-4"
BETWEEN POSTS IS 4' O.C. 2" EXPANSION JOINT

VARIES
5555 N. GRAND BLVD.

Description
VARIES GRADE BEAM
FINISHED GRADE
5" (TYP.) RE: STRUCTURAL
1/2" EXPANSION
ENGINEERED FILL JOINT (TYP.)

12"
PROVIDE #3 REBAR
@ 18" O.C.E.W.

Symbol
5B STRUCTURAL
C-504 GRANULAR FILL

Appr
5' 10' 5' 5B
LANDING RAMP RUN LANDING C-504

Date
5A

REVISIONS
C-504

1 RAMP SECTION

Description
4 RAMP SECTION
MAXIMUM DISTANCE RAMP SLOPE IS NOT TO EXCEED NEW DINING
BETWEEN POSTS IS 4' O.C. 8.33%, PER ADA REQUIREMENTS; FACILITY EXPANSION
RE:C-130 FOR SPOT ELEVATIONS

Symbol
TYP.
1'

TYP.
3'
1
2" EXPANSION JOINT

R. FAIRSHEETS

Submitted by:
Reviewed by:

GUERNSEY
Designed by:

C. MORRIS
K. HANES
Drawn by:
CRESSMAN DINING FACILITY EXPANSION
8" 8"

GOODFELLOW AIR FORCE BASE, TEXAS


5A
C-504

ENGINEERED FILL
#5 REBAR @ 18" O.C.

VARIES
VARIES
5' 10'
LANDING RAMP RUN 5B TRANSVERSE TOP AND
TOP OF FOOTING IS TOP OF FOOTING IS
C-504 BOTTOM WITH STD ACI
TO BE 12" BELOW TO BE 12" BELOW
HOOK AT EACH END

17th TRAINING WING


GRADE, AT MINIMUM GRADE, AT MINIMUM

NATURE OF WORK:
2 RAMP SECTION

16"
16"
(3) #5 REBAR ALONG 24" (3) #5 REBAR ALONG 16"
TOP AND BOTTOM TOP AND BOTTOM

RAMP SLOPE IS NOT TO EXCEED NEW DINING


8.33%, PER ADA REQUIREMENTS; FACILITY EXPANSION
TWO-SIDED FOOTING ONE-SIDED FOOTING
RE:C-130 FOR SPOT ELEVATIONS A B

PROJECT TITLE
TYP.
1'

1
5A 2" EXPANSION JOINT
3
C-501 C-504
5 RETAINING WALL DETAILS
TYP.

MAXIMUM DISTANCE
3'

4" CURB BETWEEN POSTS IS 4' O.C.


(TYP.)
TOP OF
SIDEWALK

Project Number:

OK70374-000
SHEET TITLE

SWITCHBACK RAMP DETAILS

5B
4/24/2018 11:16:09 AM

6' Date:
14.7' 5' C-504 12 JUL 2018
RAMP RUN LANDING

3 RAMP SECTION SEQ. SHEET OF

C-504
ABBREVIATIONS DESIGN CRITERIA GENERAL
1. GOVERNING BUILDING CODES B. SHOP DRAWINGS MUST BE CHECKED AND STAMPED BY THE CONTRACTOR PRIOR TO SUBMISSION. THE
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018 SYMBOL                                                                                                                                                   I                                                                                                                                                                    
A. IBC 2015 INTERNATIONAL BUILDING CODE CONTRACTOR’S STAMP OF APPROVAL WILL CONSTITUTE CERTIFICATION THAT HE HAS VERIFIED ALL FIELD
# NUMBER I.E. IN OTHER WORDS
B. ASCE 7-10 MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES MEASUREMENTS, CONSTRUCTION CRITERIA, MATERIALS AND SIMILAR DATA AND HAS CHECKED EACH DRAWING FOR
( )" INCH OR INCHES IBC INTERNATIONAL BUILDING CODE
C. UFC 1-200-01 GENERAL BUILDING REQUIREMENTS COMPLETENESS, COORDINATION, AND COMPLIANCE WITH THE CONTRACT DOCUMENTS.
( )' FOOT OR FEET ID INSIDE DIAMETER
D. UFC 3-301-01 STRUCTURAL LOAD DATA SHOP DRAWINGS SHALL BE ORIGINAL DRAWINGS, PREPARED BY CONTRACTOR, SUBCONTRACTOR, SUPPLIER OR
( )˚ DEGREE IN INCH(ES)
E. UFC 3-310-04 SEISMIC DESIGN FOR BUILDINGS DISTRIBUTOR. REPRODUCTION OF STRUCTURAL CONSTRUCTION DOCUMENTS AS ERECTION PLANS OR DETAILS WILL
= EQUAL INCL INCLUDE(D)(ING), INCLUSIVE
C( ) CHANNEL INFO INFORMATION
F. UFC 4-010-01 DOD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS NOT BE PERMITTED AND WILL BE REJECTED WITHOUT REVIEW.
FOUNDATION
CL CENTERLINE INT INTERIOR
2. WIND DESIGN CRITERIA C. CHANGES TO SHOP DRAWINGS THAT ARE RE-SUBMITTED MUST BE CLOUDED OR SOMEHOW INDICATE THAT A CHANGE c. EARTH FORMING: GRADE BEAMS ARE DETAILED IN THE DRAWINGS AS BEING EARTH-FORMED.
OKLAHOMA CITY, OK 73112 405.416.8100

HSS( ) HOLLOW STRUCTURAL SECTION ISO JT ISOLATION JOINT


A. ULTIMATE WIND SPEED (Vult) 115 MPH HAS BEEN MADE TO PREVIOUSLY ISSUED AND REVIEWED DRAWING.
K( ) OPEN WEB STEEL JOIST
B. NOMINAL DESIGN WIND SPEED (Vasd) 89 MPH 4. STRUCTURAL SLAB CONSTRUCTION:
L( ) ANGLE J                                                                                                                                                                    

Date Appr
C. EXPOSURE CATEGORY C D. THE CONTRACTOR IS TO PROVIDE THE ENGINEER WITH WRITTEN NOTICE OF DEVIATIONS OF ANY TYPE FROM THE
LL( ) DOUBLE ANGLE JB JOIST BEARING
D. INTERNAL PRESSURE COEFFICIENT +/- 0.18 REQUIREMENTS OF THE CONSTRUCTION DOCUMENTS. THE NOTICE MUST BE RECEIVED PRIOR TO SHOP DRAWING A. SLAB THICKNESS AND REINFORCING: STRUCTURAL SLABS SHALL BE OF THICKNESS AND REINFORCED AS
MC( ) MISCELLANEOUS CHANNEL JST JOIST
SUBMITTAL. THE CONTRACTOR REMAINS LIABLE FOR ANY DEVIATION UNLESS REVIEWED BY THE ENGINEER AND INDICATED ON DRAWINGS. REINFORCING BARS SHALL BE PLACED AS INDICATED IN THE CONCRETE COVER SCHEDULE
S( ) AMERICAN STANDARD SHAPE JT JOINT
C.H. GUERNSEY & COMPANY

3. SEISMIC DESIGN CATEGORY ACKNOWLEDGED IN WRITING, PRIOR TO THE RECEIPT OF THE SHOP DRAWINGS. USING CHAIRS OR SLAB BOLSTERS COMPLYING WITH CRSI'S "MANUAL OF STANDARD PRACTICE".
W( ) WIDE FLANGE
A. RISK CATEGORY II
WT( ) STRUCTURAL TEE K                                                                                                                                                                   
B. SEISMIC IMPORTANCE FACTOR (le) 1.0 14. THE GENERAL CONTRACTOR SHALL REPORT PROGRESS OF WORK TO ENGINEER OF RECORD. B. CONSTRUCTION MONITORING: CONSTRUCTION ACTIVITY MAY CAUSE DAMAGE AND DETERIORATION TO THE
K KIP(S)
C. SITE CLASS D
5555 N. GRAND BLVD.

A                                                                                                                                                                    KB KNEE BRACE PREPARED SUBGRADE. A FIELD REPRESENTATIVE OF THE GEOTECHNICAL ENGINEER SHALL OBSERVE THE FINAL
D. SEISMIC DESIGN CATEGORY A 15. THE CONTRACT DOCUMENTS SHALL TAKE PRECEDENCE OVER SHOP DRAWINGS UNLESS SPECIFICALLY NOTED

Description
A/E ARCHITECT/ENGINEER KCF KIPS PER CUBIC FOOT SUBGRADE PRIOR TO PLACEMENT OF THE SLAB-ON-GRADE, PERFORM FURTHER TESTING AS NECESSARY, AND
E. SHORT PERIOD SPECTRAL ACCELERATION (Ss) 0.06 OTHERWISE. DETERMINE IF ANY REMEDIAL MEASURES ARE NECESSARY PRIOR TO SLAB PLACEMENT.
AB ANCHOR BOLT KLF KIPS PER LINEAR FOOT
F. ONE SECOND SPECTRAL ACCELERATION (S1) 0.03
ABV ABOVE KSF KIPS PER SQUARE FOOT
G. SHORT PERIOD RESPONSE ACCELERATION (Sds) 0.064 16. INSPECTION, TESTING, CONSTRUCTION, WORKMANSHIP AND MATERIALS SHALL CONFORM TO THE REQUIREMENTS OF THE C. VAPOR RETARDER: A VAPOR RETARDER SHALL BE PLACED IMMEDIATELY BELOW THE CONCRETE SLAB. VAPOR
ACI AMERICAN CONCRETE INSTITUTE KSI KIPS PER SQUARE INCH
H. ONE SECOND RESPONSE ACCELERATION (Sd1) 0.048 GOVERNING BUILDING CODES AND REFERENCED STANDARDS. ASTM, ASCE, IBC, UFC AND OTHER STANDARDS SHALL BE RETARDER SHALL BE SEALED TO PREVIOUSLY PLACED CONCRETE AS RECOMMEND BY VAPOR RETARDER
ADDL ADDITIONAL
I. ANALYSIS METHOD ASCE 7-10 CHAPTER 11, SECTION 11.7 PER THE EDITIONS INDICATED IN THE IBC, OR AS AMENDED TO LATEST DATE IF NOT SO INDICATED. MANUFACTURER. BEFORE PLACING CONCRETE, PATCH AND SEAL ANY RIPS, TEARS, OR HOLES IN VAPOR RETARDER
AFF ABOVE FINISH FLOOR L                                                                                                                                                                   
AHU AIR HANDLING UNIT L LENGTH INCURRED DURING CONSTRUCTION.
4. DEAD LOADS 17. COORDINATE ANY CONSTRUCTION SITUATION NOT COVERED BY THESE PLANS, GENERAL NOTES, OR SPECIFICATIONS
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION LB POUND
A. ROOF WITH THE ENGINEER OF RECORD. D. VOID FORMS: VOID FORMS SHALL BE CONSTRUCTED OF BIODEGRADABLE PAPER SURFACE, TREATED FOR MOISTURE

Symbol
ALT ALTERNATE LG LONG
a. HIPPED ROOF 23 PSF RESISTANCE, AND STRUCTURALLY SUFFICIENT TO SUPPORT WEIGHT OF PLASTIC CONCRETE AND OTHER SUPER
APPROX APPROXIMATE LL LIVE LOAD
b. FLAT ROOF 25 PSF 18. NON-BEARING INTERIOR WALLS SHALL BE ADEQUATELY BRACED TO THE STRUCTURE ABOVE WITH ALLOWANCE FOR IMPOSED LOADS.
ARCH ARCHITECT OR ARCHITECTURAL(S) LLH LONG LEG HORIZONTAL
B. MINIMUM (FOR UPLIFT) 6 PSF DEFLECTION OF THE STRUCTURE ABOVE AND/OR BELOW.
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS LLO LONG LEG OUTSTANDING
AT/FP ANTI-TERRORISM/FORCE PROTECTION LLV LONG LEG VERTICAL E. CURING OF SLAB: CONCRETE SLABS SHALL BE CURED BY METHOD COMPATIBLE WITH SPECIFIED FLOOR FINISH.
5. LIVE LOADS 19. OBSERVATION VISITS TO THE SITE BY REPRESENTATIVES OF THE ENGINEER OF RECORD SHALL NOT BE CONSTRUED AS

Appr
LONG LONGITUDINAL WHERE ACCEPTABLE USE A LIQUID MEMBRANE-CURING COMPOUND AT THE MANUFACTURER'S RECOMMEND
A. ROOF 20 PSF (NON-REDUCIBLE) INSPECTION OR APPROVAL OF CONSTRUCTION. COVERAGE. STRUCTURAL SLABS SHALL BE WATER CURED FOR A MINIMUM OF 7 DAYS OF PONDING, SPRAYING,
B                                                                                                                                                                    LP LOW POINT
B. DINING 100 PSF SPRINKLING OR BY USE OF SATURATED COVERINGS.
B/ BOTTOM OF ℓd DEVELOPMENT LENGTH

Date
C. OFFICE 50 PSF
BF BOTH FACES
D. PARITIONS 15 PSF (APPLIED IN OFFICES ONLY) F. ISOLATION JOINTS: PROVIDE SLAB ISOLATION AROUND COLUMNS PENETRATING THE SLAB-ON-GRADE. PROVIDE 30#
BLDG BUILDING M                                                                                                                                                                  
E. VESTIBULE/CORRIDOR 100 PSF
FOUNDATION

REVISIONS
BLK BLOCK MATL MATERIAL FELT AROUND PERIMETER OF ISOLATION JOINTS. REFER TO TYPICAL DETAILS FOR ADDITIONAL INFORMATION.
F. MECHANICAL/ELECTRICAL/STORAGE 125 PSF
BM BEAM MAX MAXIMUM
BOT BOTTOM MECH MECHANICAL(S) 1. GEOTECHNICAL REPORT: A SUBSURFACE ENGINEERING SERVICES REPORT FOR THE CRESSMAN DINING FACILITY EXPANSION, G. SLAB CONSTRUCTION JOINTS: PLACE SLAB CONSTRUCTION JOINT AT ONE-THIRD OF SLAB SPAN AND PARALLEL TO
6. SNOW LOADS SLAB SPAN AS REQUIRED FOR MEANS AND METHODS OF CONSTRUCTION. CONFORM TO ACI REQUIREMENTS. SUBMIT

Description
BP BASE PLATE OR BEARING PLATE MEP MECHANICAL, ELECTRICAL, AND PLUMBING GOODFELLOW AIR FORCE BASE, TEXAS, WAS PERFORMED BY SKG ENGINEERING, LLC IN THEIR GEOTECHNICAL REPORT
A. GROUND SNOW LOAD (Pg) 5 PSF CONSTRUCTION JOINT PLAN TO EOR FOR REVIEW PRIOR TO PLACING CONCRETE.
BRG BEARING MFR MANUFACTURER PREPARED FOR THIS PROJECT DATED APRIL 23, 2018, FILE NUMBER 18-E-0427.
B. FLAT ROOF SNOW LOAD (Pf) 3.5 PSF
BS BOTH SIDES MID MIDDLE
C. SLOPED ROOF SNOW LOAD (Ps) 3.5 PSF H. SEE ARCHITECTURAL AND/OR CIVIL FOR EXTERIOR SLABS-ON-GRADE, TYPICAL UNLESS NOTED OTHERWISE.
BT BENT MIN MINIMUM 2. SITE SUB-GRADE PREPARATION:
D. SNOW IMPORTANCE FACTOR (Is) 1.0
BTR BETTER MISC MISCELLANEOUS
E. SNOW EXPOSURE FACTOR (Ce) 1.0 5. MISCELLANEOUS:
BTWN BETWEEN A. STRIPPING: SITE PREPARATION FOR THE BUILDING PAD SHALL INCLUDE REMOVING ANY SOFT OR UNSUITABLE
F. SNOW THERMAL FACTOR (Ct) 1.0
N                                                                                                                                                                    MATERIALS ENCOUNTERED DURING CONSTRUCTION. VEGETATION ROOTS, PAVEMENT, UTILITIES GRAVEL, FOOTINGS,
G. ADDITIONAL SNOW DRIFT AS PER APPLICABLE BUILDING CODE(S). A. GROUNDWATER CONDITIONS: GROUNDWATER WAS NOT ENCOUNTERED IN THE BORINGS AT THE TIME OF DRILLING.
C                                                                                                                                                                    N NORTH SLABS, AND ANY TOPSOIL WILL REQUIRE REMOVAL DURING INITIAL SITE STRIPPING. REMOVAL DEPTHS SHALL BE
NOT TO EXCEED THE DESIGN LIVE LOADS OR CONSTRUCTION LOADS.

Symbol
C-C CENTER TO CENTER NF NEAR FACE DETERMINED BY A GEOTECHNICAL ENGINEER OR THEIR REPRESENTATIVE. HOWEVER, IT IS POSSIBLE THAT TRANSIENT OVER-SATURATED GROUND CONDITIONS COULD DEVELOP AT SHALLOWER
CF CUBIC FOOT OR CUBIC FEET NIC NOT IN CONTRACT DEPTHS AT A LATER TIME DUE TO PERIODS OF HEAVY PRECIPITATION, LANDSCAPE WATERING, LEAKING WATER LINES,
7. FOUNDATION DESIGN CRITERIA OR OTHER UNFORSEEN CAUSES. THE CONTRACTOR SHALL DETERMINE THE ACTUAL GROUNDWATER LEVELS AT TIME
CFS COLD FORMED STEEL NO NUMBER B. PROOF-ROLLING: AFTER MAKING ANY REQUIRED CUTS, THE BUILDING PAD SHALL BE PROOF-ROLLED (UNDER
A. ALLOWABLE SKIN FRICTION FOR DRILLED PIERS 0.350 KSF (10 FEET AND BELOW) OF CONSTRUCTION. IF GROUNDWATER ISSUES ARE ENCOUNTERED DURING CONSTRUCTION, THE GEOTECHNICAL
CHAM CHAMFER NS NEAR SIDE OBSERVATION OF A GEOTECHNICAL ENGINEER OR THEIR REPRESENTATIVE) WITH A TWENTY-FIVE (25) TON LOADED,
B. ALLOWABLE END BEARING PRESSURE FOR DRILLED PIERS 12.2 KSF ENGINEER SHALL BE CONTACTED.
CIP CAST IN PLATE NTS NOT TO SCALE TANDEM AXLE DUMP TRUCK TO LOCATE ANY SOFT OVERLAPPING PASSES IN MUTUALLY PERPENDICULAR DIRECTIONS.
C. SOIL DENSITY (ASSUMED) 120 PCF
CJ CONTROL JOINT/CONSTRUCTION JOINT SOILS IN AREAS WHERE RUTTING (DEFLECTION GREATER THAN 1 INCH) OR PUMPING OCCURS DURING PROOF-ROLLING
D. MINIMUM GRADE BEAM DEPTH BELOW FINISHED GRADE 30 INCHES B. DRAINAGE CONSIDERATIONS: DUE TO ADVERSE EFFECT ON STRUCTURES, WATER SHALL NOT BE ALLOWED TO
CLR CLEAR O                                                                                                                                                                    SHALL BE OVER EXCAVATED, MOISTURE CONDITIONED AND REPLACED WITH PROPERLY COMPACTED LOW VOLUME
CMU CONCRETE MASONRY UNIT OC ON CENTER CHANGE SOILS. COLLECT IN THE FOUNDATION EXCAVATION OR ON PREPARED SUBGRADE OF THE CONSTRUCTION AREA EITHER
8. AT/FP DESIGN CRITERIA DURING OR AFTER CONSTRUCTION. UNDERCUT OR EXCAVATED AREAS SHALL BE SLOPED TOWARD ONE CORNER TO
COL COLUMN OD OUTSIDE DIAMETER
A. MINIMUM STANDOFF DISTANCE 13 FT FACILITATE REMOVAL OF ANY COLLECTED RAINWATER, OR POSITIVE RUNOFF SHALL BE PROVIDED. THE CONTRACTOR
COMP COMPOSITE OH OVERHEAD C. SCARIFICATION: AFTER STRIPPING, EXCAVATING AND PROOF-ROLLING, THE EXPOSED SOILS SHALL BE SCARIFIED TO A
B. CONVENTIONAL CONSTRUCTION STANDOFF DISTANCE 82 FT SHALL EXERCISE CARE IN CREATING DRAINAGE PATHS FOR WATER DURING THE CONSTRUCTION PHASE OF THE
CONC CONCRETE OHNG OVERHANG DEPTH OF 6 INCHES AND THEN ADJUSTED TO WITHIN 2% POINTS OF ITS OPTIMUM VALUE PRIOR TO BEING COMPACTED TO
C. STANDOFF DISTANCE TO CONTROLLED PERIMETER GREATER THAN 200 FT PROJECT. TO REDUCE INFILTRATION OF SURFACE WATER AROUND THE PERIMETER OF THE BUILDING AND BENEATH
CONN CONNECTION OPNG OPENING AT LEAST 95 PERCENT OF ITS MAXIMUM DRY DENSITY AS DETERMINED BY THE STANDARD PROCTOR TEST METHOD (ASTM
D. ACTUAL STANDOFF DISTANCES RE: C-110 THE FLOOR SLABS, POSITIVE DRAINAGE SHALL BE PROVIDED DURING ALL PHASES OF CONSTRUCTION.
CONST CONSTRUCTION OPP (HAND) OPPOSITE HAND D698).

B. McCOMBS
M.MAURICIO

M.MAURICIO
E. BUILDING CLASSIFICATION PRIMARY GATHERING

W. McCANN
CONT CONTINUOUS

Submitted by:
Reviewed by:
Designed by:
F. APPLICABLE LEVEL OF PROTECTION LOW C. EXCAVATION AND TEMPORARY SLOPES: THE CONTRACTOR, DESIGNATED AS "RESPONSIBLE PERSON" IN OSHA
COORD COORDINATE P                                                                                                                                                                    D. ACCEPTABLE FILL: THE IN-SITU SOILS ARE NOT SUITABLE FOR USE AS STRUCTURAL FILL. STRUCTURAL FILL MATERIALS

Drawn by:
G. APPLICABLE EXPLOSIVE WEIGHT II CONSTRUCTION STANDARDS FOR EXCAVATIONS, 29 CFR PART 1926, IS SOLELY RESPONSIBLE FOR PLANNING AND
CRSI CONCRETE REINFORCING STEEL INSTITUTE PC PIER CAP SHALL BE FREE OF ORGANIC OR OTHER DELETERIOUS MATTER AND BE A LOW VOLUME CHANGE SOIL OF COHESIVE
H. EXTERIOR WALL CONSTRUCTION NON-LOADBEARING METAL STUDS WITH BRICK IMPLEMENTING ALL SAFETY PROCEDURES. ALL EXCAVATION HEIGHT, SLOPE, AND DEPTH MUST ADHERE TO ALL
PCF POUNDS PER CUBIC FOOT MATERIALS HAVING A LIQUID LIMIT OF LESS THAN 40 AND A PLASTICITY INDEX BETWEEN 6 AND 14 WITH GRADATION AS
VENEER SPECIFICATIONS OUTLINED IN LOCAL, STATE, AND FEDERAL SAFETY REGULATIONS. GUERNSEY DOES NOT ASSUME
D                                                                                                                                                                    PCI POUNDS PER CUBIC INCH SPECIFIED IN THE GEOTECHNICAL REPORT. BASE CONSISTING OF TxDOT TYPE A, GRADE 2 LIMESTONE IS AN ACCEPTABLE
I. LOCATION PARKING AND ROADWAYS WITHIN A CONTROLLED ANY RESPONSIBILITY FOR CONSTRUCTION SITE SAFETY OR ANY PARTY'S, INCLUDING THE CONTRACTOR'S,
d DISTANCE PEN PENETRATION ENGINEERED FILL. BLENDED MATERIALS UTILIZED FOR ENGINEERED FILL WILL HAVE TO MEET GEOTECHNICAL
PERIMETER COMPLIANCE WITH THE APPLICABLE LOCAL, STATE, AND FEDERAL SAFETY REGULATIONS OR ANY OTHER APPLICABLE
DB DECK BEARING PL PLATE SPECIFICATIONS AND APPROVAL.
db BAR DIAMETER PLF POUNDS PER LINEAR FOOT REGULATIONS.
DBE
DBL
DECK BEARING ELEVATION
DOUBLE
PROJ
PSF
PROJECTION
POUNDS PER SQUARE FOOT
GENERAL E. FILL PLACEMENT: AFTER IN-SITU SOIL PREPARATION AND INSPECTION IS COMPLETE, FILL PLACEMENT MAY BEGIN. THE
ZONE OF FILL COMPACTED TO MEET THESE CRITERIA SHALL EXTEND BEYOND THE BUILDING FOOTPRINT AT LEAST 1 FOOT D. TRENCH BACKFILL: ALL REQUIRED TRENCH BACKFILL SHALL BE MECHANICALLY COMPACTED IN LAYERS TO AT
DEV DEVELOP PSI POUNDS PER SQUARE INCH 1. THE CONSTRUCTION DOCUMENTS CONSIST OF THE DRAWINGS, PROJECT SPECIFICATIONS, ADDENDA ISSUED PRIOR TO LATERALLY FOR EACH FOOT OF FILL REQUIRED TO DEVELOP DESIGN GRADE, BUT UNDER NO CIRCUMSTANCE SHALL IT BE LEAST 95 PERCENT OF THE STANDARD PROCTOR MAXIMUM DRY DENSITY AS DETERMINED BY ASTM D698. SOME

CRESSMAN DINING FACILITY EXPANSION


DIA DIAMETER PVMT PAVEMENT EXECUTION OF THE CONTRACT, OTHER DOCUMENTS LISTED IN THE AGREEMENT AND MODIFICATIONS ISSUED VIA LESS THAN 5 FEET. THE FILL SHALL BE PLACED IN MAXIMUM LOOSE LIFTS OF 8 INCHES, ADJUSTED TO 1% POINT BELOW TO SETTLEMENT OF THE BACKFILL MAY BE EXPECTED AND ANY UTILITIES WITHIN THE TRENCHES SHALL BE CONSTRUCTED

GOODFELLOW AIR FORCE BASE, TEXAS


DIAG DIAGONAL SUPPLEMENT INSTRUCTION. 2% POINTS ABOVE OF ITS OPTIMUM MOISTURE CONTENT AND COMPACTED TO 95 PERCENT STANDARD DENSITY PER ASTM TO ALLOW THESE DIFFERENTIAL MOVEMENTS.
DIM DIMENSION Q                                                                                                                                                                    D698.
DL DEAD LOAD QTY QUANTITY 2. THE CONSTRUCTION DOCUMENTS ARE COMPLIMENTARY, AND WHAT IS REQUIRED BY ONE SHALL BE AS BINDING AS IF E. CONSTRUCTION MONITORING: A GEOTECHNICAL ENGINEER SHALL BE RETAINED TO PROVIDE OBSERVATIONS
DN DOWN REQUIRED BY ALL. IF CONFLICTING REQUIREMENTS ARE FOUND BETWEEN THE DRAWINGS, SPECIFICATIONS AND/OR THESE F. DEPTH OF FILL: THE FLOOR SLAB SHALL BE CONSTRUCTED ON A MINIMUM DEPTH OF 1'-0" OF MOISTURE CONDITIONED AND TESTING OF SOILS EXPOSED DURING PROJECT CONSTRUCTION IN ORDER TO VERIFY THAT SOIL CONDITIONS ARE
DT DOUBLE TEE R                                                                                                                                                                    GENERAL STRUCTURAL NOTES, THE MORE STRINGENT PROVISION SHALL CONTROL UNLESS DIRECTED OTHERWISE IN LOW-PLASTICITY STRUCTURAL FILL. AS ANTICIPATED. CONSTRUCTION ACTIVITIES PERTAINING TO EARTHWORK, FOUNDATIONS, AND OTHER RELATED
DTL DETAIL RAD RADIUS OR RADII WRITING BY THE STRUCTURAL ENGINEER. ACTIVITIES SHALL ALSO BE OBSERVED BY THE GEOTECHNICAL ENGINEER'S REPRESENTATIVES AS OUTLINED ABOVE.
DWG(S) DRAWING(S) RE: REFER TO G. FILL PLACEMENT TESTING: EACH LIFT OF COMPACTED FILL SHALL BE TESTED BY A GEOTECHNICAL ENGINEER PRIOR TO
DWL DOWEL REF REFERENCE 3. THE STRUCTURAL GENERAL NOTES SUPPLEMENT THE PROJECT SPECIFICATIONS. REFER TO THE PROJECT SPECIFICATIONS PLACEMENT OF SUBSEQUENT LIFTS. FIELD DENSITY TESTS SHALL BE TAKEN AT A MINIMUM OF ONE PER EVERY 2000

17th TRAINING WING


REINF REINFORCEMENT/REINFORCING SQUARE FEET, BUT AT LEAST THREE SETS OF DENSITY TESTS SHALL BE TAKEN FOR EACH LIFT.

NATURE OF WORK:
FOR ADDITIONAL REQUIREMENTS.
E                                                                                                                                                                    REQD REQUIRED
(E) EXISTING REV REVISION OR REVISE 4. METHODS, PROCEDURES AND SEQUENCES OF CONSTRUCTION ARE THE RESPONSIBILITY OF THE CONTRACTOR. THE H. SITE DRAINAGE: THE CONTRACTOR SHALL PROVIDE POSITIVE DRAINAGE AWAY FROM THE AREAS OF EXCAVATION
EA EACH ROT ROTATE CONTRACTOR IS RESPONSIBLE FOR IDENTIFYING AND IMPLEMENTING THE NECESSARY PRECAUTIONS TO MAINTAIN AND DURING CONSTRUCTION TO PREVENT PONDING UNDER FUTURE FLOOR SLABS AND FOOTINGS. THE CONTRACTOR SHALL
EF EACH FACE RTU ROOF TOP UNIT ENSURE THE INTEGRITY OF THE STRUCTURE AT ALL STAGES OF CONSTRUCTION. PROVIDE POSITIVE CUTOFF IN UTILITY TRENCHES AS REQUIRED PREVENTING WATER MIGRATION INTO THE AREAS OF
EL ELEVATION EXCAVATION AND FUTURE FLOOR SLABS AND FOOTINGS.
ELEC ELECTRICAL S                                                                                                                                                                    5. TEMPORARY BRACING, SHEETING, SHORING, ETC, REQUIRED TO ENSURE THE STRUCTURAL INTEGRITY/STABILITY OF
EMBED EMBEDMENT SC SLIP CRITICAL EXISTING BUILDINGS, SIDEWALKS, UTILITIES, ETC, DURING CONSTRUCTION IS THE RESPONSIBILITY OF THE CONTRACTOR AND I. MAINTENANCE OF SOIL MOISTURE: SOIL MOISTURE SHALL BE MAINTAINED UP UNTIL CONCRETE PLACEMENT TO PREVENT
ENGR ENGINEER SCHED SCHEDULE SHALL BE DESIGNED BY A REGISTERED PROFESSIONAL ENGINEER EMPLOYED BY THE CONTRACTOR. SHRINKAGE AND SUBSEQUENT POST-CONSTRUCTION SWELL OF SUBGRADE SOILS.
EOR ENGINEER OF RECORD SDI STEEL DECK INSTITUTE
EOS EDGE OF SLAB SECT SECTION 6. IMPLEMENTATION OF JOB SITE SAFETY IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR. 3. BUILDING FOUNDATIONS
EQ EQUAL SHT SHEET
EQUIP EQUIPMENT SIM SIMILAR 7. SLEEVES OR BLOCK-OUTS REQUIRED FOR PASSAGE OF DUCTWORK, PIPING, DRAINS, CONDUIT, ETC, IN ADDITION TO A. DRILLED PIERS:
EST ESTIMATE(D) SJ SLAB CONTROL JOINT ANCHORS AND HANGERS REQUIRED FOR EQUIPMENT AND PIPING AND UNDER-SLAB UTILITIES ARE NOT SPECIFICALLY, NOR
ETC ET CETERA SL SLOPE(D) OR SLOPING GENERALLY, INDICATED ON THE STRUCTURAL DRAWINGS. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING SUCH a. PIER DESIGN PARAMETERS: DRILLED PIERS HAVE BEEN DESIGNED FOR A MAXIMUM ALLOWABLE END BEARING
EW EACH WAY SLO SHORT LEG OUTSTANDING REQUIREMENTS PRIOR TO FABRICATION OR ERECTION OF THE STRUCTURE. PENETRATIONS OF STRUCTURAL MEMBERS ARE PRESSURE PER THE DESIGN CRITERIA AT A MINIMUM PENETRATION INTO BEARING STRATUM OF TWO FEET OR ONE (1)
C:\Work\R18_70374-000_S_mmauricio.rvt

EXC EXCAVATE OR EXCAVATION SLV SLEEVE SUBJECT TO APPROVAL BY THE ENGINEER. PIER DIAMETER, WHICH EVER IS DEEPER. MAXIMUM ALLOWABLE SKIN FRICTION CAPACITY IS PER THE DESIGN CRITERIA
EXIST EXISTING SOG SLAB-ON-GRADE FOR THE PART OF THE PIER THAT PENETRATES THE CLAYEY SAND. ALLOWABLE SKIN FRICTION WAS NOT USED.
EXP EXPANSION SP SPACE(S) 8. DIMENSIONS AND INSTALLATION DETAILS OF PURCHASED EQUIPMENT MUST BE VERIFIED AND COORDINATED WITH THE DESIGN UPLIFT FORCES ARE RESISTED BY AN ALLOWANCE FOR PIER WEIGHT AND THE DEAD LOAD OF THE STRUCTURE.
EXT EXTERIOR SPEC SPECIFICATIONS SUPPORTING STRUCTURE. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING SUCH REQUIREMENTS FROM
STD STANDARD SUBCONTRACTORS AND EQUIPMENT SUPPLIERS ALONG WITH COORDINATING THE LOCATIONS AND DETAILS FOR THESE b. PIER DIMENSIONS: DRILLED SHAFT DIAMETERS SHALL BE A MINIMUM OF 24 INCHES, WITH AN ASPECT RATIO

PROJECT TITLE
F                                                                                                                                                                   STIFF STIFFENER ITEMS PRIOR TO FABRICATION OR ERECTION OF THE SUPPORTING STRUCTURE. ADDITIONAL FRAMING MAY BE REQUIRED (LENGTH/DIAMETER) OF THREE OR MORE, AND SPACED NO CLOSER THAN THREE PIER DIAMETERS CENTER-TO-CENTER.
FD FLOOR DRAIN STL STEEL FOR THE PROPER SUPPORT OF SUCH UNITS AND/OR EQUIPMENT. LATERAL SUPPORT FOR THE EQUIPMENT SHALL BE
FDN FOUNDATION STRUCT STRUCTURAL PROVIDED BY THE EQUIPMENT INSTALLER. ANY CONFLICTS BETWEEN THESE ITEMS AND THE BUILDING STRUCTURE IS TO BE c. IMPROVEMENT OF BEARING CONDITIONS: SOFT OR LOOSE SOIL ZONES ENCOUNTERED AT THE BEARING LEVEL
FF FAR FACE SUB SUBSTITUTE BROUGHT TO THE ATTENTION OF THE ENGINEER FOR RESOLUTION. SHALL BE REMOVED FROM THE FOUNDAITON EXCAVATIONS. THE PIER FOUNDATION SHALL BE EXCAVATED AND
FIN FINISHED CLEANED AS QUICKLY AS POSSIBLE TO REDUCE THE POTENTIAL FOR WETTING/DRYING OF THE SUBSURFACE SOIL. IF
FL FLOOR T                                                                                                                                                                    9. THE STRUCTURAL DRAWINGS GOVERN THE WORK FOR STRUCTURAL FEATURES, UNLESS OTHERWISE NOTED. DIMENSIONS EXPOSED SOILS BECOME SIGNIFICANTLY WET OR DRY, THE SOILS SHALL BE REMOVED AND THE PIER ENLARGED UNTIL
FS FAR SIDE T THICKNESS SHOWN ON PLANS AND DETAILS ARE TO GOVERN THE STRUCTURAL WORK. THE CONTRACTOR IS TO REFER TO THE MORE UNIFORM MOISTURE CONDITIONS ARE ACHIEVED (AS DIRECTED BY GEOTECHNICAL ENGINEERING
FT FOOT OR FEET T&B TOP AND BOTTOM ARCHITECTURAL DRAWINGS FOR DIMENSIONS AND DETAILS NOT PROVIDED. DIMENSIONAL CONFLICTS IN THE DOCUMENTS REPRESENTATIVE).
FTG FOOTING T&S TEMPERATURE AND SHRINKAGE SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER.
FULL PEN FULL PENETRATION WELD T/ TOP OF d. TEMPORARY CASING: TEMPORARY CASING MAY BE REQUIRED AS DETERMINED BY THE GEOTECHNICAL ENGINEER
Fy STEEL YIELD STRENGTH THD THREAD(ED) 10. WORK NOT INDICATED ON A PART OF THE DRAWINGS, BUT REASONABLY IMPLIED TO BE SIMILAR TO THAT SHOWN AT AT TIME OF EXCAVATION TO SEAL OUT GROUNDWATER OR SLOUGHING SOILS. CASING SHALL EXTEND FROM TOP OF Project Number:
THK THICKNESS CORRESPONDING LOCATIONS, IS TO BE REPEATED. PIER ELEVATION, AND SEAL INTO TOP OF BEARING STRATUM ELEVATION.
G                                                                                                                                                                   THRU THROUGH OK70374-000
GA GAGE OR GAUGE TMS THE MASONRY SOCIETY 11. EXISTING BUILDING INFORMATION SHOWN IS BASED UPON EXISTING BUILDING DOCUMENTS AND/OR FROM FIELD e. PLACEMENT: CONCRETE FOR PIERS SHALL BE CAST AS SOON AS PRACTICAL AFTER DRILLING. NO PIER HOLE SHALL
GALV GALVANIZED TRANS TRANSVERSE OBSERVATION. THE INFORMATION CONTAINED HEREIN MAY REQUIRE ADJUSTMENTS AND/OR MODIFICATIONS TO CONFORM BE LEFT OPEN OVERNIGHT. SUFFICIENT CONCRETE HEAD SHALL BE MAINTAINED INSIDE THE SHAFT TO OFFSET SHEET TITLE
GB GRADE BEAM TYP TYPICAL TO EXISTING CONDITIONS. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING BUILDING INFORMATION SHOWN HYDROSTATIC HEAD OUTSIDE THE SHAFT AND TO PREVENT THE INTRUSION OF SOIL AND GROUNDWATER INTO THE
GC GENERAL CONTRACTOR (DIMENSIONS, ELEVATIONS, ETC) AND NOTIFY THE ENGINEER OF ANY DISCREPANCIES PRIOR TO FABRICATION OF ANY PIER CONCRETE. CONCRETE SHALL HAVE A PLACEMENT SLUMP OF SIX (6) INCHES. GENERAL STRUCTURAL NOTES
GR GRADE U                                                                                                                                                                    STRUCTURAL COMPONENT.
GSN GENERAL STRUCTURAL NOTES UNO UNLESS NOTED OTHERWISE B. GRADE BEAMS:
7/12/2018 12:02:58 PM

12. DETAILS DESIGNATED AS “TYPICAL DETAILS,” APPLY GENERALLY TO THE DRAWINGS IN AREAS WHERE CONDITIONS ARE Date:
H                                                                                                                                                                   V                                                                                                                                                                    SIMILAR TO THOSE DESCRIBED IN THE DETAILS. a. CONSTRUCTION: GRADE BEAMS SHALL BE STRUCTURALLY CONNECTED TO THE TOP OF THE PIERS. GRADE BEAMS 12 JUL 2018
Hef EFFECTIVE EMBEDMENT VERT VERTICAL SHALL EXTEND AT LEAST TWO AND ONE HALF (2.5) FEET BELOW THE FINAL EXTERIOR ADJACENT GRADE. A MINIMUM
HORIZ HORIZONTAL VIF VERIFY IN FIELD 13. SHOP DRAWINGS: VOID SPACE OF SIX (6) INCHES BENEATH THE GRADE BEAMS SHALL BE MAINTAINED USING VOID FORMS. EXCAVATIONS
HP HIGH POINT FOR GRADE BEAMS SHALL BE FREE OF LOOSE MATERIAL.
HSA HEADED STUD ANCHOR W                                                                                                                                                                   A. SHOP DRAWINGS FOR ALL MATERIALS ARE TO BE SUBMITTED TO THE ENGINEER FOR REVIEW PRIOR TO THE START OF SEQ. SHEET OF
HT HEIGHT W WIDTH FABRICATION OR COMMENCEMENT OF WORK PER THE PROJECT SPECIFICATIONS. b. VOID FORMS: VOID FORMS SHALL BE CONSTRUCTED OF BIODEGRADABLE PAPER SURFACE, TREATED FOR MOISTURE
W/ WITH RESISTANCE, AND STRUCTURALLY SUFFICIENT TO SUPPORT WEIGHT OF PLASTIC CONCRETE AND OTHER SUPER
W/O WITHOUT IMPOSED LOADS.
WF
WL
WIDE FLANGE
WIND LOAD S-001
WP WORKING POINT
WT WEIGHT
REINFORCED CONCRETE REINFORCING STEEL - CONCRETE STRUCTURAL STEEL
1. REINFORCED CONCRETE WORK IS TO BE IN ACCORDANCE WITH THE AMERICAN CONCRETE INSTITUTE (ACI) EDITIONS OF: 1. REINFORCING STEEL SHALL BE DEFORMED BARS AND SHALL CONFORM TO ASTM A615 GRADE 60, WITH A DESIGN YIELD D. BOLT SHALL BE BEARING TYPE CONNECTIONS UNLESS NOTED OTHERWISE.
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
STRENGTH OF 60,000 PSI, EXCEPT AS NOTED BELOW.
A. ACI 301 (LATEST EDITION), "SPECIFICATIONS FOR STRUCTURAL CONCRETE". E. BOLTED CONNECTIONS SHALL HAVE WASHERS AND SHALL BE TIGHTENED TO SNUG TIGHT CONDITION.
A. DOWELS TO BE BENT IN THE FIELD DURING CONSTRUCTION SHALL BE ASTM A706 GRADE 60, "LOW-ALLOY STEEL".
B. ACI 318 (2014), "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE", EXCEPT AS MODIFIED BY THE IBC. F. ENLARGING OF HOLES SHALL BE ACCOMPLISHED BY MEANS OF REAMING. DO NOT USE A TORCH ON ANY BOLT HOLES.
B. REINFORCING TO BE WELDED SHALL BE ASTM A706 GRADE 60, "LOW-ALLOY STEEL".
C. ACI 347 (LATEST EDITION), "GUIDE TO FORMWORK FOR CONCRETE". 12. WELDED CONNECTIONS:
2. MECHANICAL SPLICE COUPLERS SHALL BE CAPABLE OF DEVELOPING 125% OF THE SPECIFIED STRENGTH OF THE BAR.
2. MIXING, TRANSPORTING, PLACING AND TESTING OF CONCRETE IS TO BE DONE IN ACCORDANCE WITH ACI 301. A. WELDING AND GAS CUTTING SHALL BE DONE PER AWS. OPEN WEB STEEL JOISTS
OKLAHOMA CITY, OK 73112 405.416.8100

3. REINFORCING STEEL SHALL BE FREE OF LOOSE FLAKY RUST, SCALE, GREASE, OIL, DIRT, AND OTHER MATERIALS WHICH MIGHT
3. PRIOR TO CONCRETE PLACEMENT, THE CONTRACTOR MUST SUBMIT CONCRETE MIX DESIGNS FOR EACH TYPE OF CONCRETE AFFECT OR IMPAIR BOND. B. WELDING TO BE IN ACCORDANCE WITH THE AMERICAN WELDING SOCIETY (AWS) "STRUCTURAL WELDING CODE-ANSI/AWS 10. THE STEEL JOIST/GIRDER MANUFACTURER SHALL BE RESPONSIBLE FOR THE DESIGN AND FABRICATION OF ALL STEEL JOISTS

Date Appr
TO BE USED, PREPARED IN ACCORDANCE WITH THE SPECIFICATIONS TO THE ENGINEER FOR REVIEW. D1.1/D1.1M" (LATEST EDITION). USE E70XX ELECTRODES UNLESS OTHERWISE INDICATED ON THE DRAWINGS. AND THEIR ASSOCIATED HARDWARE.
4. BENDS SHALL BE MADE COLD. DO NOT USE HEAT. BENDS SHALL BE DONE IN THE FABRICATOR'S SHOP UNLESS SPECIFICALLY
4. CAST-IN-PLACE CONCRETE SHALL HAVE A MINIMUM 28 DAY COMPRESSIVE STRENGTH (f'c) AS INDICATED ON THE CONCRETE NOTED FOR THE FIELD. DO NOT UN-BEND OR RE-BEND A PREVIOUSLY BENT BAR. C. WELDERS SHALL BE CURRENTLY CERTIFIED ACCORDING TO AWS WITHIN THE LAST 12 MONTHS. ALL WELDING A. ALL STEEL JOISTS AND SHALL BE DESIGNED AND STAMPED BY A PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF
C.H. GUERNSEY & COMPANY

MATERIALS SCHEDULE ON DRAWING S-002. PROCEDURES SHALL BE PRE-QUALIFIED. WELDERS SHALL FOLLOW WELDING PROCEDURES. WHICH THE PROJECT IS CONSTRUCTED AND BEARING THE SEAL OF THE PROFESSIONAL ENGINEER. DESIGN
5. NO REINFORCING SHALL BE WELDED UNLESS SPECIFICALLY NOTED AS SUCH. USE E90XX ELECTRODES AND ASTM A706 CALCULATIONS AND SHOP DRAWINGS BEARING THE ENGINEER’S STAMP SHALL BE SUBMITTED TO THE ENGINEER OF
5. THE SLUMP AT POINT OF PLACEMENT IS NOT TO EXCEED 4”+/-1” AND THE WATER/CEMENT RATIO IS NOT TO EXCEED 0.45. IF REINFORCING. COMPLY WITH AWS D1.4 REQUIREMENTS. D. WELDS SHALL HAVE THE SLAG REMOVED. RECORD FOR REVIEW.
5555 N. GRAND BLVD.

ADDITIONAL SLUMP (UP TO 8”) IS DESIRED FOR PUMPING, A SUPER-PLASTICIZER ADMIXTURE MAY BE ADDED.
6. CODES AND STANDARDS: E. FULL PENETRATION WELDS, SHOP OR FIELD, SHALL HAVE BACKER BARS REMOVED, BE BACK GOUGED, AND WELDED PER

Description
B. JOISTS SHALL BE DESIGNED TO SAFELY SUPPORT ALL LOADS TO WHICH THEY ARE SUBJECTED, INCLUDING THE LOADS
6. CONCRETE EXPOSED TO WEATHER AND FREEZE/THAW SHALL HAVE AN AIR CONTENT FROM 5% TO 7% IN ACCORDANCE WITH AWS TO HAVE FULL PENETRATION WELD. INDICATED IN THE DESIGN CRITERIA SECTION OF THESE GENERAL NOTES, OTHER LOADS SHOWN OR INDICATED ON THE
ACI RECOMMENDATIONS. AIR ENTRAINING ADMIXTURE SHALL CONFORM TO ASTM C260. A. CONCRETE REINFORCING STEEL INSTITUTE (CRSI) "MANUAL OF STANDARD PRACTICE". DRAWINGS, AND ANY ADDITIONAL LOADS FROM MECHANICAL OR OTHER EQUIPMENT OR ELEMENTS. THEY SHALL ALSO
13. POST INSTALLED ANCHORS HAVE BEEN DESIGNED WITH HILTI ANCHORS (NOTED BELOW) AS THE BASIS OF DESIGN. PROVIDE BE DESIGNED IN ACCORDANCE WITH SNOW DRIFT REQUIREMENTS OF THE IBC AND ASCE 7, FOR UNBALANCED LOADS,
7. CONCRETE TO BE NORMAL WEIGHT CONCRETE (150 PCF) WITH CEMENT CONFORMING TO ASTM C150 TYPE I, II, OR I/II. B. AMERICAN CONCRETE INSTITUTE, ACI 315 (OR SP-66) "DETAILS AND DETAILING OF CONCRETE REINFORCEMENT". ANY APPROPRIATE ANCHOR WITH SIZE AND FINISH AS NOTED AND EQUIVALENT SHEAR AND TENSION CAPACITIES AFTER LOWER ROOFS, OVERHANGS, VALLEYS, RIDGES, GABLES, ETC. REFERENCE MECHANICAL AND/OR OTHER DRAWINGS FOR
MODIFICATION DUE TO EMBEDMENT, SPACING AND EDGE DISTANCES. OTHER AVAILABLE MANUFACTURERS INCLUDE SIMPSON, LOCATIONS AND WEIGHTS OF EQUIPMENT OR ELEMENTS TO BE SUPPORTED. COORDINATE AS REQUIRED.
8. CONTINUOUS REINFORCING BARS TO BE TURNED AND LAPPED AT CORNERS AND INTERSECTIONS OF WALLS AND FOOTINGS. 7. REINFORCING SHALL BE DETAILED, FABRICATED, BOLSTERED, AND SUPPORTED PER ACI 315. ITW RED HEAD AND POWERS FASTENERS. INSTALL ANCHORS PER THE MANUFACTURER’S INSTRUCTIONS/RECOMMENDATIONS.
HOOKED BARS TO HAVE STANDARD ACI HOOKS UNLESS NOTED OTHERWISE. C. IN ADDITION, JOISTS SHALL BE DESIGNED TO SUPPORT THE UPLIFT LOADS INDICATED IN THE C&C DIAGRAM AND
8. SPLICES IN CONTINUOUS REINFORCING IN CONCRETE SHALL BE PER THE CONCRETE REINFORCING LAP SPLICE SCHEDULE. A. EXPANSION ANCHORS: KWIK BOLT TZ EXPANSION ANCHOR SCHEDULE. FOR NET UPLIFT, USE 8 PSF FOR DEAD LOAD.

Symbol
9. CONCRETE SHALL BE PROPERLY VIBRATED DURING PLACEMENT.
A. SPLICES SHALL BE MADE IN AREAS OF COMPRESSION AND/OR AT POINTS OF MINIMUM STRESS, TYPICAL UNLESS NOTED B. ADHESIVE ANCHORS: HIT-HY 200 D. LIVE LOAD DEFLECTIONS SHALL BE LIMITED TO L/240 FOR ROOF JOISTS.
10. PRIOR TO PLACING CONCRETE, CHECK WITH ALL TRADES TO INSURE SLEEVES, INSERTS, MECHANICAL OPENINGS, CONDUITS, OTHERWISE. TENSION SPLICES SHALL BE USED IN CONCRETE; USE CLASS B SPLICE UNLESS NOTED OTHERWISE. SPLICES
PIPES, RECESSES. DEPRESSIONS, CURBS AND OTHER EMBEDDED ITEMS TO BE PROVIDED AS SHOWN ON THE ARCHITECTURAL, IN TOP BARS IN SUSPENDED CONCRETE SLABS AND BEAMS SHALL BE MADE AT MID SPAN. SPLICES IN BOTTOM BARS IN C. SCREEN TUBE ANCHORS: HIT-HY 70 11. PROVIDE ADEQUATE BEARING LENGTH AT ALL SUPPORTS. EXTEND BEARING TO AT LEAST 1 INCH PAST CENTERLINE OF

Appr
MECHANICAL AND ELECTRICAL DRAWINGS AND AS REQUIRED BY EQUIPMENT MANUFACTURERS ARE INSTALLED, SUSPENDED CONCRETE SLABS AND BEAMS SHALL BE MADE AT SUPPORTS. STEEL BEAM SUPPORTS WHERE EVER POSSIBLE.
COORDINATED, AND PROVIDED FOR. D. SCREW ANCHORS: KWIK HUS-EZ SCREW ANCHOR
9. REINFORCING STEEL IN CONCRETE SHALL HAVE COVER PER THE CONCRETE COVER SCHEDULE. 12. NO LOADS SHALL BE APPLIED TO THE JOISTS UNTIL BRIDGING HAS BEEN COMPLETELY INSTALLED AND THE JOIST ENDS HAVE

Date
A. ANCHOR RODS AND DOWELS SHALL BE PLACED PRIOR TO CASTING CONCRETE. 14. SUBSTITUTION OF EXPANSION ANCHORS FOR EMBEDDED ANCHORS SHOWN ON THE DRAWINGS WILL NOT BE PERMITTED. BEEN SECURED TO THEIR SUPPORTS.
10. REINFORCING STEEL IN CONCRETE SHALL BE SECURELY ANCHORED AND TIED IN PLACE PRIOR TO PLACING CONCRETE. IF
11. ALL CONTACT SURFACES, NEW OR EXISTING, AT CONSTRUCTION JOINTS SHALL BE INTENTIONALLY ROUGHENED TO 1/4" REQUIRED, ADDITIONAL BARS, STIRRUPS, OR CHAIRS SHALL BE PROVIDED BY THE CONTRACTOR TO FURNISH SUPPORT FOR 15. PAINT AND PROTECTION:

REVISIONS
13. DO NOT CUT, DRILL, MODIFY, OR OMIT ANY PART OF ANY JOIST WITHOUT PRIOR WRITTEN CONSENT AND DIRECTION FROM
AMPLITUDE PRIOR TO CASTING ADJACENT POUR. ALL BARS WHERE NECESSARY DURING CONSTRUCTION. THE MANUFACTURER.
A. STRUCTURAL STEEL, UNLESS INDICATED OTHERWISE, TO BE SHOP CLEANED PER SSPC SP3 AND PAINTED ONE SHOP COAT
12. OPENINGS IN FLOORS AND/OR WALLS SHALL HAVE ADDITIONAL REINFORCING AROUND ALL SIDES AS SHOWN IN TYPICAL OF FABRICATOR’S STANDARD RUST INHIBITING PRIMER. TOUCH UP AFTER ERECTION.

Description
14. DO NOT WELD THE BOTTOM CHORD OF THE JOISTS TO THE STABILIZER PLATES.
DETAILS.

13. NO PENETRATION SHALL BE ALLOWED THROUGH ANY CONCRETE BEAM, PIER CAP, OR PIER WITHOUT THE ENGINEER'S PRIOR
STRUCTURAL STEEL B. DO NOT PAINT STEEL WHERE ENCASED WITH CONCRETE, OR AT FIELD WELD AREAS.

WRITTEN APPROVAL. PENETRATIONS SHALL BE RE-ROUTED AS REQUIRED AT THESE LOCATIONS. 1. STRUCTURAL STEEL WORK IS TO BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH: C. DO NOT PAINT STRUCTURAL STEEL TO BE FIREPROOFED. SHOP CLEAN PER SSPC SP3. METAL DECK
14. LEVELING GROUT TO BE NON-SHRINK, FACTORY PREMIXED GROUT IN ACCORDANCE WITH ASTM C1107, HAVING A MINIMUM A. THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) "SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS" D. EXPOSED STRUCTURAL STEEL TO RECEIVE PAINTED FINISH TO BE SHOP CLEANED AND PRIME PAINTED PER THE 1. METAL DECK MUST BE DESIGNED AND DETAILED IN ACCORDANCE WITH THE STEEL DECK INSTITUTE (SDI) "DESIGN MANUAL
COMPRESSIVE STRENGTH OF NOT LESS THAN 5000 PSI. (FOURTEENTH EDITION) SPECIFICATIONS. REFERENCE ARCHITECTURE FOR FINISH PAINT SYSTEMS. FOR COMPOSITE DECKS, FORM DECKS AND ROOF DECKS" (LATEST EDITION).

Symbol
15. ANCHOR RODS TO BE ASTM F1554 Fy=36 KSI MINIMUM, UNLESS NOTED OTHERWISE. ANCHOR ROD EMBEDMENT SHALL BE AS B. THE “CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES”. E. EXPOSED STRUCTURAL STEEL FOR SCREEN WALLS, EQUIPMENT PLATFORMS, LOOSE ANGLE LINTELS ETC, TO BE HOT 2. STEEL DECK SHALL BE SIZE AND GAUGE AS SPECIFIED ON PLANS.
INDICATED ON THESE STRUCTURAL DRAWINGS. DIPPED GALVANIZED PER ASTM A123.
C. RCSC "SPECIFICATION FOR STRUCTURAL JOINTS USING HIGH STRENGTH BOLTS". 3. ROOF DECK TO BE FASTENED TO THE SUPPORTING STEEL PER PLAN AND DETAILS. ANY SPLIT OR PARTIAL PANELS TO BE
A. ALL BOLT HOLES TO BE FILLED WITH EPOXY SHALL BE WIRE BRUSHED AND CLEANED WITH COMPRESSED AIR PER F. GALVANIZED FASTENERS AND ACCESSORIES TO BE HOT DIPPED GALVANIZED PER ASTM A153/A153M. FASTENED TO THE SUPPORTING STRUCTURE IN EVERY VALLEY REGARDLESS OF ADJACENT FASTENER PATTERNS.
MANUFACTURER’S RECOMMENDATIONS. 2. STRUCTURAL STEEL, UNLESS NOTED OTHERWISE, TO BE NEW STEEL CONFORMING TO THE REQUIREMENTS OF ASTM A 6/A 6M
AND AS INDICATED ON THE STEEL MATERIAL SCHEDULE ON DRAWING S-002. G. REPAIR DAMAGE TO GALVANIZED COATINGS USING ASTM A780 ZINC RICH PAINT. 4. DECK UNITS TO BE A MINIMUM OF THREE (3) SPANS CONTINUOUS WITH LAPS PLACED OVER SUPPORTS.
16. SUSPENDED FLOOR SLABS:
3. PRIOR TO FABRICATION, THE STEEL FABRICATOR IS TO SUBMIT TO THE ENGINEER FOR REVIEW THE FOLLOWING: H. PROVIDE MINIMUM 3” CONCRETE COVER FOR ALL STEEL BELOW GRADE. 5. STEEL DECK AND ACCESSORIES SHALL BE MANUFACTURED FROM COLD ROLLED STEEL CONFORMING TO ASTM A653,
A. CONSTRUCTION JOINTS IN SUSPENDED SLABS AND/OR BEAMS SHALL OCCUR AT THIRD POINTS OF SLAB SPAN. (GALVANIZED G-60), AND SHALL CONFORM TO THE STEEL DECK INSTITUTE (SDI) AND AISC STANDARDS.
COORDINATE PLACEMENT WITH THE ENGINEER. A. SHOP DRAWINGS SHOWING ERECTION PLANS, PIECE DRAWINGS, AND CONNECTION DETAILS. 16. DEFORMED BAR ANCHORS SHALL CONFORM TO THE MANUFACTURER'S SPECIFICATIONS.
6. WELDING SHALL BE DONE WITH E60XX OR E70XX ELECTRODES.
4. THE STRUCTURAL STEEL FABRICATOR, AND/OR GENERAL CONTRACTOR, MUST VERIFY ALL EXISTING DIMENSIONS AND 17. CONSTRUCTION:

B. McCOMBS
CONCRETE MATERIALS SCHEDULE

M.MAURICIO

M.MAURICIO
CONDITIONS AT THE SITE. ALL DISCREPANCIES FOUND ARE TO BE REPORTED TO THE ENGINEER PRIOR TO PREPARATION OF

W. McCANN
7. END LAPS SHALL OVERLAP AT LEAST 2" AND SHALL OCCUR OVER A SINGLE MEMBER STEEL SUPPORT.

Submitted by:
Reviewed by:
Designed by:
SHOP DRAWINGS. SHOP DRAWINGS ARE TO INCLUDE ALL FIELD MEASUREMENTS AND CONDITIONS. A. FABRICATION SHALL BE DONE IN AN APPROVED FABRICATOR'S SHOP.

Drawn by:
MAX 8. DO NOT STRETCH DECK PERPENDICULAR TO FLUTES.
MIN f'c 28 DAYS WATER/CEMENT 5. STRUCTURAL STEEL FABRICATOR IS TO PROVIDE FOR VERTICAL AND HORIZONTAL FIELD ADJUSTMENT OF ALL SUPPORT B. USE HIGH STRENGTH (5000 PSI MINIMUM AT 28 DAY), NON-SHRINK, FACTORY PRE-MIXED GROUT IN ACCORDANCE WITH
STRUCTURAL ELEMENT (PSI) RATIO AGGREGATE AIR CONTENT REMARKS ASSEMBLIES. ASTM C1107 BENEATH ALL STEEL BASE PLATES AND BEARING PLATES. MIX GROUT WITH SAND OR PEA GRAVEL AS 9. DO NOT BEND OR MAR DECK.
PIERS 3500 0.45 #57 5-7% RECOMMENDED BY THE MANUFACTURER. PLACE GROUT AS SOON AS STEEL MEMBER HAS BEEN PROPERLY POSITIONED
6. CUTS, HOLES, COPING, ETC REQUIRED FOR OTHER TRADES MUST BE SHOWN ON THE SHOP DRAWINGS AND MADE IN THE AND ALIGNED. 10. STORE DECKING OFF THE GROUND WITH ONE END ELEVATED. COVER DECK WITH WATERPROOF MATERIAL AND VENTILATE
GRADE BEAMS & PIER 4000 0.45 #57 EXT 5-7%
SHOP. CUTS OR BURNING OF HOLES IN THE FIELD WILL NOT BE PERMITTED. TO AVOID CONDENSATION.
CAPS INT 2%
INTERIOR SLABS 4000 0.45 #57 2% 7. STEEL BEAMS ARE TO BE EQUALLY SPACED IN BAYS UNLESS OTHERWISE NOTED.
EXTERIOR SLABS 4000 0.45 #57 5-7%
8. FABRICATE AND INSTALL BEAMS WITH NATURAL CAMBER UP UNLESS CAMBER IS NOTED ON THE DRAWINGS. STEEL MATERIALS SCHEDULE

CRESSMAN DINING FACILITY EXPANSION


COLD FORMED STEEL FRAMING

GOODFELLOW AIR FORCE BASE, TEXAS


STANDARD CONCRETE HOOK SCHEDULE 9. PROVIDE CAMBER IN BEAMS WHERE INDICATED ON THE DRAWINGS. CAMBER INDICATED ON PLANS AFTER BEAM SIZE AS: C=##.
STRUCTURAL ELEMENT
WIDE FLANGE BEAMS & COLUMNS (UNO)
Fy YIELD STRENGTH (KSI)
50
REMARKS
ASTM A992 1. STRUCTURAL MEMBERS MUST BE DESIGNED IN ACCORDANCE WITH THE AMERICAN IRON AND STEEL INSTITUTE (AISI) S100
HOOK EXTENSION

STANDARD HOOKS IN 10. ALL STRUCTURAL STEEL FRAMES ARE TO BE SECURELY BRACED UNTIL ALL ROOF DECKS HAVE BEEN INSTALLED AND BECOME ROUND TUBE STEEL 46 ASTM A500 GRADE C "NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS" (LATEST EDITION).
PER ACI 318

TENSION PER ACI 318 CAPABLE OF STABILIZING THE FRAMES. CONNECTIONS, PLATES, & ALL OTHERS 36 ASTM A36
ANCHOR RODS 36 UNO F1554 UNO 2. STRUCTURAL MEMBERS TO BE FORMED FROM CORROSION RESISTANT STEEL CONFORMING TO ASTM A1003 WITH MINIMUM
HOOK DEVELOPMENT LENGTH 11. BOLTED CONNECTIONS: YIELD STRESS (Fy) AS REQUIRED BY STRUCTURAL PERFORMANCE. ALL COLD FORMED METAL COMPONENTS TO HAVE A
ℓdh (INCHES) LIGHT GAGE METAL STUDS 50 ASTM A1003
MINIMUM GALVANIZING RATING OF G-60.

17th TRAINING WING


A. STEEL-TO-STEEL BOLTED CONNECTIONS: 3/4" DIAMETER ASTM A325 UNO WITH MATCHING WASHERS AND HEAVY HEX NUTS.

NATURE OF WORK:
BAR SIZE f'c=3000 PSI f'c=4000 PSI 3. INTERIOR STUD WALLS SHALL BE DESIGNED FOR A MINIMUM OUT OF PLANE UNIFORM LIVE LOAD PRESSURE OF 5 PSF
USE TENSION CONTROL BOLT ASSEMBLIES CONFORMING TO ASTM F1852 AT CONTRACTOR'S OPTION. NUTS AND WASHERS
HOOK DEVELOPMENT SHALL CONFORM TO ASTM A563 AND ASTM F436 RESPECTIVELY. UNLESS NOTED OTHERWISE, WITH A MAXIMUM DEFLECTION OF L/240.
#3 9 8
NOTES: LENGTH, ℓdh
B. ALL OTHER BOLTED CONNECTIONS SHALL BE MADE WITH BOLTS AND NUTS CONFORMING TO ASTM A307 UNLESS NOTED
OPEN WEB STEEL JOISTS 4. MAXIMUM STUD SPACING TO BE 16" ON CENTER WITH DOUBLED STUDS (MINIMUM) AT EACH SIDE OF OPENINGS.
#4 11 10 1. CONCRETE IS NORMAL WEIGHT CONCRETE FOR
OTHERWISE. 1. DESIGN, FABRICATION AND ERECTION OF OPEN WEB STEEL JOISTS MUST CONFORM TO THE STEEL JOIST INSTITUTE (SJI)
LIGHTWEIGHT CONC MULTIPLY VALUES BY 1.33.
"STANDARD SPECIFICATIONS LOAD TABLES AND WEIGHT TABLES FOR STEEL JOISTS AND JOIST GIRDERS"(LATEST EDITION). 5. FRAMING COMPONENTS ARE TO BE CUT SQUARELY FOR ATTACHMENT TO PERPENDICULAR MEMBERS OR AS REQUIRED
#5 14 12 2. BAR YIELD STRENGTH, Fy = 60 KSI.
C. STANDARD SPACING SHALL BE 3" OC AND STANDARD EDGE DISTANCE SHALL BE 1 1/2" TYPICAL, UNLESS NOTED FOR AN ANGULAR FIT AGAINST ABUTTING MEMBERS.
3. SIDE COVER REQUIREMENTS OF ACI 318 ARE
#6 17 15 OTHERWISE. 2. THE JOIST MANUFACTURER IS TO PROVIDE ALL ANCHORS AND FASTENERS REQUIRED FOR INSTALLATION OF JOISTS, BRIDGING
ASSUMED TO NOT BE MET.
AND BOTTOM CHORD EXTENSIONS. 6. FIELD CUTTING OF STUDS MUST BE DONE BY SAWING OR SHEARING, TORCH CUTTING OF COLD FORMED MEMBERS IS
4. TIE OR STIRRUP REQUIREMENTS OF ACI 318 ARE
#7 20 17 UNACCEPTABLE.
ASSUMED TO NOT BE MET.
5. REDUCTION FOR EXCESS REINFORCEMENT IS NOT 3. PROVIDE BRIDGING AND ANCHORAGE IN ACCORDANCE WITH SJI REQUIREMENTS. WHERE ERECTION BRIDGING IS REQUIRED,
#8 22 19 TAKEN. CONCRETE REINFORCING LAP SPLICE SCHEDULE (IN) HAVE IN PLACE A ROW OF BOLTED BRIDGING BEFORE RELEASING HOIST LINES. BRIDGING IN LAST BAY SHALL BE ATTACHED TO
A STRUCTURAL WALL OR STEEL BEAM.
7. INSTALLATION OF ALL COLD FORMED FRAMING SHALL BE BY AN EXPERIENCED INSTALLER APPROVED BY THE
MANUFACTURER. INSTALLATION SHALL BE AS RECOMMENDED BY THE MANUFACTURER.
6. HOOK DEVELOPMENT LENGTH IS VALID FOR 180°
#9 25 22 HOOKS ALSO. f' c= 3000 PSI f' c= 4000 PSI f'c= 5000 PSI f'c= 6000 PSI
4. NO LOADS MAY BE APPLIED TO THE JOISTS UNTIL BRIDGING HAS BEEN COMPLETELY INSTALLED AND THE JOIST ENDS HAVE 8. ALL LATERAL BRACING SHALL CONFORM TO SECTION D3 OF AISI S100 SPECIFICATIONS.
BAR SIZE
C:\Work\R18_70374-000_S_mmauricio.rvt

TOP OTHER TOP OTHER TOP OTHER TOP OTHER BEEN SECURED TO THEIR SUPPORTS.
BARS BARS BARS BARS BARS BARS BARS BARS 9. FASTENING OF COMPONENTS IS TO BE WITH SELF-DRILLING SCREWS OR WELDING. WELDING OF STUDS MUST COMPLY WITH
CONCRETE COVER SCHEDULE #3 28 22 24 19 22 17 20 15 5. STEEL JOISTS ARE TO BE EQUALLY SPACED IN BAYS UNO. DO NOT EXCEED JOIST SPACING INDICATED ON THE DRAWINGS. AWS D1.1/D1.1M AND AWS D1.3/D1.3M. 16 GAGE OR HEAVIER MATERIAL IS REQUIRED FOR WELDING. ALL WELDS TO BE
TOUCHED-UP WITH ZINC-RICH PAINT. SCREWS AND WELDS TO BE OF SUFFICIENT SIZE TO ENSURE THE STRENGTH OF THE
#4 37 29 32 25 29 22 26 20 CONNECTION. WIRE TYING OF COMPONENTS IS NOT PERMITTED.
6. STEEL JOIST MANUFACTURER IS TO PROVIDE ADDITIONAL BOTTOM CHORD BRIDGING AS REQUIRED FOR UPLIFT LOADS.

PROJECT TITLE
MINIMUM CONCRETE COVER PROTECTION FOR REINFORCEMENT BARS SHALL BE AS FOLLOWS: (RE: ACI 318 #5 47 36 40 31 36 28 33 25
LATEST EDITION FOR CONDITIONS NOT NOTED). DIMENSIONS FOR BAR PLACEMENT GIVEN IN SECTIONS AND #6 56 43 48 37 43 33 40 31 7. HANGERS SUPPORTING MECHANICAL, ELECTRICAL OR OTHER EQUIPMENT ARE TO BE PLACED AT JOIST PANEL POINTS 10. COLD FORMED STEEL FRAMING MEMBERS ARE TO BE SECURELY ATTACHED TO THE STRUCTURE WHERE INDICATED ON THE
DETAILS SHALL SUPERSEDE MINIMUM COVER REQUIREMENTS GIVEN HERE. (WELDING NOT PERMITTED) AND APPLIED LOADS ARE TO BE COORDINATED WITH STEEL JOIST MANUFACTURER. DO NOT DRAWINGS, OR APPROVED SHOP DRAWINGS. FASTENERS TO BE COMPATIBLE TO THE STRUCTURAL MEMBERS.
#7 81 63 70 54 63 49 58 44
#8 93 72 80 62 72 55 66 51 SUSPEND ANY EQUIPMENT FROM BRIDGING OR METAL DECK.
FOOTINGS (EARTH FORMED) 3 INCHES 11. PROVIDE VERTICAL SLIDE TRACKS, OR SLIDE CLIPS, WHERE INDICATED ON THE DRAWINGS OR OTHERWISE REQUIRED TO
#9 105 81 91 70 81 63 74 57 ALLOW FOR VERTICAL STRUCTURAL MOVEMENTS. MAXIMUM EXPECTED STRUCTURE LIVE LOAD DEFLECTION IS L/240 AT
8. STEEL JOIST MANUFACTURER TO VERIFY SIZE, LOCATION AND WEIGHT OF ALL SUPPORTED MECHANICAL UNITS AND
#10 118 91 102 79 91 70 83 64 ASSOCIATED OPENINGS PRIOR TO FABRICATION. ROOFS.
SLAB ON GRADE:
#11 131 101 113 87 101 78 93 71
BOTTOM 3 INCHES 12. REFERENCE ARCHITECTURAL DRAWINGS FOR ADDITIONAL INFORMATION, INCLUDING SHEATHING TYPE, FINISHES,
SIDES (EARTH FORMED) 3 INCHES NOTES: OPENINGS, LOCATIONS, ETC.
SIDES (BOARD FORMED): 1. TABULATED VALUES ARE BASED ON A MINIMUM YIELD STRENGTH OF 60,000 PSI. LENGTHS ARE IN INCHES. Project Number:
#5 BAR & SMALLER 1 1/2 INCHES 2. TENSION DEVELOPMENT LENGTHS AND TENSION LAP SPLICE LENGTHS ARE CALCULATED PER ACI 318.
3. TABULATED VALUES FOR BEAMS OR COLUMNS ARE BASED ON TRANSVERSE REINFORCEMENT AND CONCRETE COVER MEETING OK70374-000
#6 THROUGH #11 BAR 2 INCHES
MINIMUM CODE REQUIREMENTS.
4. LAP SPLICE LENGTHS (MINIMUM OF 12 INCHES) ARE MULTIPLES OF TENSION DEVELOPMENT LENGTHS; CLASS B = 1.3 ℓd. WHEN SHEET TITLE
SLAB ON GRADE (NO EXPOSURE TO WEATHER) FROM TOP 1 1/2 INCHES DETERMINING THE LAP SPLICE LENGTH, ℓd IS CALCULATED WITHOUT THE 12-INCH MINIMUM OF ACI.
SLAB ON GRADE (EXPOSURE TO WEATHER) FROM TOP 1 1/2 INCHES 5. ACI 318 DOES NOT ALLOW TENSION LAP SPLICES OF #14 OR #18 BARS. THE TABULATED VALUES FOR THOSE BAR SIZES ARE THE GENERAL STRUCTURAL NOTES
TENSION DEVELOPMENT LENGTHS.
6. TOP BARS ARE HORIZONTAL BARS WITH MORE THAN 12 INCHES OF CONCRETE CAST BELOW THE BARS.
RETAINING WALLS (NO SURFACES SHALL BE EARTH FORMED) EARTH SIDE AND FRONT
7/12/2018 12:02:58 PM

7. FOR EPOXY-COATED BARS, IF THE C-C SPACING IS AT LEAST 7.0 db AND THE CONCRETE COVER IS AT LEAST 3.0 db, THEN CASE 1 Date:
SIDE (EXPOSED TO WEATHER):
LENGTHS MAY BE MULTIPLIED BY 0.918 (FOR TOP BARS) OR 0.8 (FOR OTHER BARS). 12 JUL 2018
#5 BAR & SMALLER 1 1/2 INCHES 8. FOR GRADE 75 (MINIMUM YIELD STRENGTH OF 75,000 PSI) REINFORCING BARS, LENGTHS MUST BE MULTIPLIED BY 1.25.
#6 THROUGH #11 BAR 2 INCHES 9. FOR LIGHTWEIGHT AGGREGATE CONCRETE, MULTIPLY THE TABULATED VALUES BY 1.33.
10. TABULATED VALUES ARE BASED ON CLASS B LAP SPLICES AND CASE 1 PER ACI 318.
WALLS & SLABS 3/4 INCHES 11. CASE 1, WHICH DEPENDS ON THE TYPE OF STRUCTURAL MEMBER, CONCRETE COVER, AND CENTER-TO-CENTER SPACING OF
SEQ. SHEET OF
THE BARS, IS DEFINED AS:
CONCRETE BEAMS 1 1/2 INCHES BEAMS, COLUMNS CONCRETE COVER AT LEAST 1.0 db AND C-C SPACING AT LEAST 2.0 db

PROVIDE STANDARD BAR CHAIRS AND SPACERS AS REQUIRED TO MAINTAIN CONCRETE PROTECTION
ALL OTHERS CONCRETE COVER AT LEAST 1.0 db AND C-C SPACING AT LEAST 3.0 db
S-002
SPECIFIED
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
X2
AA BB CC DD EE FF GG HH JJ A
OKLAHOMA CITY, OK 73112 405.416.8100

Date Appr
7.9
8
C.H. GUERNSEY & COMPANY

7.8
5555 N. GRAND BLVD.

Description
7

Symbol
6

Appr
Date
5.6

REVISIONS
"a P
"
TY

Description
"a"
TYP

Symbol
4
3.8

3.4

B. McCOMBS
M.MAURICIO

M.MAURICIO

W. McCANN

Submitted by:
Reviewed by:
Designed by:
3

Drawn by:
TYP
"a"

2.2
TYP

CRESSMAN DINING FACILITY EXPANSION


2
"a"

GOODFELLOW AIR FORCE BASE, TEXAS


2.1
"a" 1
TYP "a"
TYP

TYP
"a"

17th TRAINING WING


NATURE OF WORK:
X1
B C D E F G
"a"
TYP
DESIGN UPLIFT WIND PRESSURES FOR DESIGN WIND PRESSURES FOR
ROOF COMPONENTS (PSF) WALL COMPONENTS (PSF)
ROOF COMPONENT TRIBUTARY AREA (FT²) WALL COMPONENT TRIBUTARY AREA (FT²) ALT #1
ZONE ZONE
θ≤7° 10 50 100+ θ≤7° 10 100 500+
1 -31 -29 -28 4 +28 -30 +24 -26 +21 -23

2 -51 -39 -33 5 +28 -37 +24 -29 +21 -23


C:\Work\R18_70374-000_S_mmauricio.rvt

3 -77 -46 -33 PARAPET - - - - - -


ROOF COMPONENT TRIBUTARY AREA (FT²) WALL COMPONENT TRIBUTARY AREA (FT²)
ZONE ZONE
10 50 100+ 7°<θ≤27° 10 100 500+
7°<θ≤27°

PROJECT TITLE
1 -28 -26 -25 4 +31 -33 +26 -29 +23 -25
2 -49 -40 -36 5 +31 -41 +26 -32 +23 -25

3 -49 -40 -36 1. LOADS SHOWN ARE ULTIMATE (LRFD) WIND


PRESSURES
OHNG -57 -57 -57 2. (+) AND (-) INDICATE PRESSURES ACTING
TOWARDS AND AWAY FROM THE BUILDING
1. LOADS SHOWN ARE ULTIMATE (LRFD) WIND UPLIFT SURFACES RESPECTIVELY.
PRESSURES. 3. LINEAR INTERPOLATION BETWEEN TRIBUTARY
2. (-) SIGN INDICATES PRESSURE ACTING AWAY FROM AREAS SHOWN IS PERMITTED. Project Number:
SURFACE. 4. BUILDING ZONES ARE DEFINED IN ASCE 7-10
3. WIND LOADS & BUILDING ZONES WERE DETERMINED WITH a = 8'-0".
OK70374-000
USING ASCE 7-10.
4. BUILDING ZONES ARE DEFINED IN ASCE 7-10 WITH a=8'-0". SHEET TITLE

GENERAL STRUCTURAL NOTES


7/12/2018 12:02:58 PM

C&C WIND PRESSURE SCHEDULES AND DIAGRAMS Date:

1 NOT TO SCALE
12 JUL 2018

PLAN NORTH SEQ. SHEET OF

S-003
KEY PLAN
ℓd ℓd
CLASS "B" LAP SPLICE
CONSTRUCTION JOINT
MIDDLE THIRD MIDDLE THIRD
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019 LOCATED AT THIRD SPAN
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
SCRATCH FINISH #4 @ 12" OC
FULL LAP STOP REINFORCEMENT W/ EPOXY EACH WAY

ℓd

ℓd
SPLICE 2'' EACH SIDE OF JOINT BONDING

D/3
2" KEY
ADHESIVE
SEE CONCRETE REINF LAP SEE NOTES
SPLICE SCHEDULE FOR ℓd #4 @ 24" OC, TYP

D= DEPTH
OKLAHOMA CITY, OK 73112 405.416.8100

4"
D/3
T/FLOOR

Date Appr
RE: PLAN

CHAIRS PER SPECIFICATIONS


6" VOID FORMS
C.H. GUERNSEY & COMPANY

VAPOR RETARDER BONDED

D/3
TO UNDERSIDE OF SLAB
COMPACTED SUBGRADE NOTES:

ℓd

ℓd
5555 N. GRAND BLVD.

1. SIZE OF EQUIPMENT BASE TO SUIT EQUIPMENT 12"

Description
MIN BEYOND EDGE OF EQUIPMENT.
2. PROVIDE ANCHOR BOLTS AS REQUIRED BY
BOTTOM REINF UNINTERRUPTED ADD 1-#6 x 5'-0" FOR EQUIPMENT MANUFACTURER.
ℓd ℓd
(SPLICE BARS OVER PIER) EA 6" OF BEAM WIDTH @ 3. FINISH T/EQUIPMENT BASE TO DRAIN.
MID-DEPTH.
INTERSECTION CORNER
TYPICAL SLAB-ON-GRADE TYPICAL INTERIOR

Symbol
CONSTRUCTION JOINT DETAIL TYPICAL GRADE BEAM CONSTRUCTION JOINT TYPICAL CORNER BAR DETAIL EQUIPMENT PAD
1 NOT TO SCALE 2 SCALE: NONE 3 NOT TO SCALE 4 NOT TO SCALE

Appr
Date
WALLS, PIERS AND/OR COLUMNS WHICH
WALLS, PIERS AND/OR COLUMNS PENETRATE THE FLOOR SLAB 1'-0" MIN

REVISIONS
WHICH PENETRATE THE FLOOR SLAB.
2-#4 x 4'-0 EA SIDE STEM WALL
COL
CJ LONG TYP STEM WALL
ISOLATION JOINT

Description
(FULL DEPTH BOND
TOP 1/3 OF SLAB (TYP) BREAKER) GRADE

EXT WALL
1 CONSTRUCTION BEAM GRADE BEAM
1 JOINT STEEL COLUMN
COL & BASE PLATE

Symbol
INDEPENDENT
TY 0"
2'-

ISOLATION JOINT
P

CONC POUR
INDEPENDENT
(1) #4 x IN TOP 1/3 CONCRETE POUR
STEEL COL
OF SLAB, EA SIDE, TYP CONSTRUCTION BASE PLATE PROVIDE PIPE SLEEVE W/ DIA

2"
TY "
JOINT

CL
2
4" P
2" LARGER THAN PIPE DIA

P
TY

R
TY 0"
2'-

PLUMBING/UTILITY LINE
P

AT OPENINGS AT CORNER FILL PIPE TRENCH W/ CONC TO BOTTOM OF GB


USING LEAN MIX CONC - 2000 PSI
EXTERIOR COLUMN INTERIOR COLUMN

B. McCOMBS
M.MAURICIO

M.MAURICIO

W. McCANN
TYPICAL RE-ENTRANT CORNER REINFORCING TYPICAL ISOLATION JOINT DETAIL UTILITY PIPE UNDER GRADE BEAM

Submitted by:
Reviewed by:
Designed by:
5 6 7

Drawn by:
NOT TO SCALE NOT TO SCALE NOT TO SCALE

2 ADDL SETS OF STIRRUPS (2) #5 x 6'-0" LG ADDL


EA SIDE OF SLEEVE BARS T&B
STIRRUPS SLEEVE AT ALL PIPE

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


RE: SCHEDULE PENETRATIONS
(RE: MECH DWGS)

6" MIN.

6" MIN
WIDTH "W"
PIPE SLEEVE
8" DIA MAX

17th TRAINING WING


NATURE OF WORK:
6" MIN
LOCATE SLEEVE WITHIN

6" MIN
MIDDLE 3RD OF BM SPAN
TOP & BOT BARS
GRADE BEAM
RE: SCHEDULE
PLAN VIEW RE: PLAN & SCHEDULE
LOCATE SLEEVE WITHIN

MIDDLE 3RD OF BM SPAN


VERTICAL PIPE PENETRATION
UTILITY PIPE THROUGH GRADE BEAM THROUGH GRADE BEAM
C:\Work\R18_70374-000_S_mmauricio.rvt

8 NOT TO SCALE 9 NOT TO SCALE

PROJECT TITLE
Project Number:

OK70374-000

SHEET TITLE

TYPICAL DETAILS
7/12/2018 12:02:59 PM

Date:
12 JUL 2018

SEQ. SHEET OF

S-010
TYP
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019 3/16
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
BEAM/ BEAM/
JOIST JOIST
TYP SEAT TO T/FL
ATTACHMENT @ ENDS AND SUPPORTS SIDELAP FASTENERS 3/16
ZONE 1 ZONE 2 & 3 ZONE 1 ZONE 2 & 3
INTERMEDIATE L5X3
SUPPORT OPTION 1 5/8" DIA PUDDLE WELDS 5/8" DIA PUDDLE WELDS (2) #10 TEK SCREWS (3) #10 TEK SCREWS
36/4 PATTERN 36/7 PATTERN PER SPAN PER SPAN
OKLAHOMA CITY, OK 73112 405.416.8100

PENETRATION REINFORCEMENT
SIDELAP FASTENERS OPTION 2 HILTI X-HSN 24 HILTI X-HSN 24 (3) #10 TEK SCREWS (3) #10 TEK SCREWS TYP

Date Appr
36/4 PATTERN 36/7 PATTERN PER SPAN PER SPAN MAX WIDTH OF MAX WEBS REINFORCEMENT 3/16
PENETRATION REMOVED NEEDED 4
S-011

L4X4

L4X4
ENDS & SUPPORTS 6" 2 NONE
C.H. GUERNSEY & COMPANY

ATTACHMENT PLATE
WIDTH OF PENETRATION 8" 3 0.045" PLATE L6X4X5/16X0'-6" LG (TYP)
5555 N. GRAND BLVD.

< 12" >3 0.057" PLATE


END SUPPORT

Description
L5X3
NOTES:
NOTE:
NOTE:
1. IT IS THE CONTRACTOR'S CHOICE AS TO WHICH OPTION TO USE.
2. WHEN ARC SPOT WELDS (PUDDLE WELDS) ARE USED, CONTRACTOR IS TO TAKE EXTRA CARE NOT TO PROVIDE BURN THROUGH HOLES IN NUMBER OF WEBS 1. FOR OPENINGS ≥ 12"
PLATES SHOULD EXTEND PAST THE OPENING 12"
THE DECK. REFER TO SPECIFICATIONS FOR SPECIAL INSPECTION REQUIREMENTS. REMOVED 2. CONTRACTOR SHALL COORDINATE SIZE AND LOCATION OF
MINIMUM ON EACH SIDE
3. ZONES INDICATE WIND ZONES AS DEPICTED IN "ROOF C&C WIND PRESSURE PLAN" ON SHEET S-003 OPENINGS WITH THE MECHANICAL EQUIPMENT PURCHASED.

Symbol
ROOF DECK ATTACHMENT DETAIL ROOF DECK PENETRATION FRAMING AT ROOF OPENING
1 NOT TO SCALE 2 NOT TO SCALE 3 NOT TO SCALE

Appr
Date
CONCENTRATED LOAD 500 LB
GREATER THAN OR
MAX, TYP TOP OR BOTTOM
EQUAL TO 6"
CHORD. A MAXIMUM OF 1000 LB

REVISIONS
TYP LOAD TO BE APPLIED TO JOIST
3/16
COORDINATE OPENING PARTIAL PEN,

Description
SIZE & LOCATION W/ MECH X BOTH LEGS TYP DECK LOAD
TYP EQUIP PURCHASED ANGLE
3/16
SEE NOTE 6
5"

Symbol
JOIST OR BEAM
RE: PLAN (4) PLACES EA
TYP (2) 1 3/4" X 3/8" X 10"
3/16 PLATE 5/16 4 TIE PLATES, ONE EA
L5X3X5/16" (LLV) L4X4X5/16" RE: NOTE 4 L6X4X5/16" (LLV) X 6" LG LEG
RE: NOTE 4 (OMIT WHERE X < 6")
(2)L'S 2 1/2"X2 1/2"X1/4" TYP NOTE:
LOAD
NOTES: WELD TO TOP & BOTTOM CHORD @
PANEL POINT, WHEN LOAD OCCURS 6" THIS DETAIL APPLIES WHEN SUPPORT
1. PROVIDE FRAME AT OPENING WHERE ANY DIMENSION EXCEEDS 1'-0". OR MORE FROM PANEL JOINT AT A PANEL POINT IS IMPOSSIBLE.
2. WHEN JOIST SPACING EXCEEDS 5'-0". VERIFY ALL ANGLE SIZES W/ ENGINEER. THE ALLOWABLE CONCENTRATED

B. McCOMBS
TYP

M.MAURICIO

M.MAURICIO

W. McCANN
3. COORDINATE OPENING DIMENSIONS, LOCATIONS AND CURB CONSTRUCTION W/ ARCH & MECH DWGS. LOAD MAY VARY PER JOIST

Submitted by:
Reviewed by:
3/16

Designed by:
4. PROVIDE L6X4X3/8 (LLV) UNDER MECH UNIT CURBS NOT SUPPORTED BY ROOF STRUCTURE. GREATER THAN OR MANUFACTURER. CONTACT THE

Drawn by:
5. RE: TYPICAL JOIST REINFORCING DETAIL FOR ADDITIONAL INFORMATION. EQUAL TO 6" JOIST MANUFACTURER TO REVIEW
6. PROVIDE 1-1/2" - 20 GA REINF CHANNELS AT SIDE OF DECK FLUTES WHICH DO NOT ALIGN W/ ANGLE CONCENTRATED LOADS NOT APPLIED
TYPICAL ROOF DECK AT A PANEL POINT.

FRAMING AT ROOF OPENING (CONTINUED) EDGE ANGLE SPLICE JOIST BRACING DETAIL
4 NOT TO SCALE 5 NOT TO SCALE 6 NOT TO SCALE

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


17th TRAINING WING
NATURE OF WORK:
C:\Work\R18_70374-000_S_mmauricio.rvt

PROJECT TITLE
Project Number:

OK70374-000

SHEET TITLE

TYPICAL DETAILS
7/12/2018 12:02:59 PM

Date:
12 JUL 2018

SEQ. SHEET OF

S-011
(2) #10 SCREWS AT
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018 A TYP EACH STUD, TYP
OKLAHOMA CITY, OK 73112 405.416.8100

CFS HEADER SCHEDULE

Date Appr
ROOF BEAM
OPENING WIDTH HEADER
C.H. GUERNSEY & COMPANY

HEADER, RE: (2) - 800S200-54


SCHEDULE UP TO 9'-4" AND
5555 N. GRAND BLVD.

(2) - 800T150-54

Description
C
WINDOW NOTES:
1. 'L' IS THE CLEAR OPENING WIDTH
TYPICAL JAMB SHALL BE (2) #10 SCREWS AT 18" OC
(2) 800S200-54 (50 KSI) TRACK TO JAMB STUD

54 MIL PIECE OF TRACK. ATTACH TO HEADER W/ (3) SIMPSON


STRONG-TIE SELF-DRILLING SCREWS XQ1016 @ EA FLANGE

Symbol
#10 SCREWS AT
18" OC JACK
STUD TO TRACK ATTACH TRACK TO JAMB W/ (6) SIMPSON
TYP T&B TRACK TO
DOOR STRONG-TIE SELF-DRILLING SCREWS XQ1S1016
BE 800T150-54 (50 KSI)

Appr
54 MIL FULL
HEIGHT TRACK PERIMETER BEAM, RE: FRAMING PLAN

Date
1 1/2"
L8x6x7/16xCONT TYP (LLV) PERIMETER BEAM, RE: FRAMING PLAN

REVISIONS
L2”X2”X54 MIL X 1/2”
BRIDGING AT 4'-0" (2) #10 SCREWS
SHORTER THAN STUD
OC MAX, RE: 5/S-012 AT EACH STUD TYP 800T125-54
DEPTH W/ (4) #10-16 EA CFS STUD, RE: 1/S-012

Description
LEG. ANGLE MAY BE SIMPSON STRONG-TIE MSCB45.5 SIMPSON STRONG-TIE MSCB45.5 BYPASS
BOX WINDOW SILL OMMITTED WHEN BYPASS FRAMING SIDE-CLIP W/ (3) # FRAMING SIDE-CLIP W/ (3) #14 SHLDR SCREWS
FOR L≤4'-0" (1) 800T150-54 OPENING WIDTH ≤ 4’-0” BOX HEADER PER
14 SHLDR SCREWS TO STUD AND (4) TO STUD AND (4) SELF-DRILLING SCREWS
FOR L>4'-0" (1) 800S200-54 SCHEDULE
AND (1) 800T150-54 DETAIL A SELF-DRILLING SCREWS XQ1S1214 XQ1S1214 TO ANGLE, TYP EACH SIDE OF JAMB
NOTE: ALTERNATE FRAMING TO ANGLE, TYP AT EA STUD
CONFIGURATIONS ARE FULL HEIGHT TRACK JAMB STUDS, RE: 1/S-012
ACCEPTABLE AND SHALL TYPICAL WALL STUD SHALL BE
BE SENT TO EOR FOR 800S162-54 (50 KSI) @ 16” OC

Symbol
APPROVAL
TYP EXT WALL STUD JAMB STUD

JAMB STUDS
DETAIL B DETAIL C

TYPICAL COLD FORMED STEEL WALL FRAMING TYPICAL CFS STUD AT ROOF
1 2

B. McCOMBS
M.MAURICIO

M.MAURICIO
NOT TO SCALE

W. McCANN
SCALE: 3/4" = 1'-0"

Submitted by:
Reviewed by:
Designed by:

Drawn by:
SLAB EDGE
2 1/4"

CRESSMAN DINING FACILITY EXPANSION


CFS JAMB STUDS

GOODFELLOW AIR FORCE BASE, TEXAS


CLIP ANGLE W/ SCREWS
4 1/2"

EACH LEG AS REQUIRED

TOP VIEW
OPTION 2

17th TRAINING WING


TYPICAL STUD

NATURE OF WORK:
SIMPSON STRONG-TIE RCA
SCREWS TO 1 1/2"X1 1/2"X16 GA,
RIGID CONNECTOR ANGLE W/ (8)
EACH BLOCK AS CLIP ANGLE FASTENED
#10 SCREWS TO STUD AT EACH
REQUIRED W/ (4) #10-16 SCREWS.
PERIMETER STUD RUNNER TRACK
ANGLE LENGTH SHALL
(6) 0.157” DIA X-U PAF W/ 1 NOT BE LESS THAN
1/2" EMBED INTO CONCRETE STUD DEPTH MINUS 1/2"
CONT STRAP BOTH SIDES
@ EA PERIMETER STUD (1)#10-16 SCREW AS REQUIRED
@ EACH FLANGE
RUNNER TRACK
SIMPSON STRONG-TIE RCA
(1) #10-16 SCREW CONC SLAB RIGID CONNECTOR ANGLE W/ (8)
@ EACH FLANGE SCREW(S) @ EA 1 1/2"X16 GA
#10 SCREWS TO STUD AT EACH
INTERSECTION BOTH SIDES AS U-CHANNEL
JAMB STUD (2 TOTAL PER JAMB)
REQUIRED BRIDGING SPACING
AS REQUIRED
C:\Work\R18_70374-000_S_mmauricio.rvt

(6) 0.157” DIA X-U PAF W/ 1 1/2"


EMBED INTO CONCRETE @ SOLID BLOCKING AS
EA RCA RIGID CONNECTOR REQUIRED, FIT BETWEEN
FIRST & LAST 2 BAYS. REPEAT TYPICAL STUD
OPTION 1 IN 2 BAYS EVERY 8' OC.

PROJECT TITLE
JAMB ATTACHMENT FOR 54 MIL JAMB STUDS

TYPICAL TRACK ATTACHMENT TRACK ATTACHMENT AT JAMB TYPICAL COLD FORMED STEEL BRIDGING DETAIL
3 NOT TO SCALE 4 NOT TO SCALE 5 NOT TO SCALE

Project Number:

OK70374-000

SHEET TITLE

TYPICAL DETAILS
7/12/2018 12:02:59 PM

Date:
12 JUL 2018

SEQ. SHEET OF

S-012
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
OKLAHOMA CITY, OK 73112 405.416.8100

AA BB CC DD EE FF GG HH JJ A B C D E F G

Date Appr
C.H. GUERNSEY & COMPANY
5555 N. GRAND BLVD.

104'-6"

Description
7'-10" 6'-1" 14'-8" 20'-7" 7'-3" 11'-7" 11'-6" 3'-6" 19'-11"
68'-10" 1'-7" 35'-8"
15'-0"
X2
2" BUILDING EXPANSION

Symbol
JOINT ALONG THIS LINE,
RE: PLAN AND KEYNOTES

Appr
9

Date
2'-1"

45°
7.9

REVISIONS
8

Description
7.8

10'-10"
10'-5"
7'-11"

12'-11"

14'-7"

CL OF
COLS

5"
7
11'-8"

Symbol
7'-3 1/2"
7'-10"

1
1'-2"

21'-4"

21'-4"

6
14'-6"

1 1/2"
4'-2"
7'-11"

7'-11"

5.6
12'-8 1/2"
14'-1"

14'-1"

B. McCOMBS
7'-10" 8'-7 1/2" 5'-2 1/2" 7'-4" 10'-4" 10'-8" 6'-10" 11'-1" 9'-4" 6'-3 3/8"

M.MAURICIO

M.MAURICIO

W. McCANN

Submitted by:
Reviewed by:
Designed by:
5'-1 1/2"

Drawn by:
85'-6"

22'-0"

22'-0"

5
7'-7 1/2"

(E) FOUNDATON TYP


14'-1"

14'-1"

10'-2 1/2"

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


3.8
7'-11"

7'-11"

1 1/2"
4'-2"
21'-5"

21'-5"

3.4
7'-3 1/2"
1'-2"

7'-10"

(E) FLOOR FRAMING, TYP.

17th TRAINING WING


1 7'-5" 6'-0" 6'-8"

NATURE OF WORK:
NOT ALL SHOWN.
11'-8"

3
5"

7'-6 1/2"

CL OF
COLS
12'-11"
7'-11"

10'-4"

10'-9"

2.2
8'-1 1/2"

2.1 45°
2'-1"

3'-6"

5'-6"
1'-7"
6'-1" 4'-4" 3'-0" 7'-4" 10'-4" 11'-4" 6'-2" 2'-7" 9'-5" 15'-0" 1
C:\Work\R18_70374-000_S_mmauricio.rvt

13'-1"
1'-2" 1'-2"

11'-6"

9'-10"

7'-10"

PROJECT TITLE
11'-2" 5'-2" 5'-2" 11'-2"
15'-6" 15'-6"
31'-0" 43'-1"
X1 TO OUTSIDE FACE OF EXISTING BRICK, VIF AND COORD W/ ARCH

Project Number:
ALT #1
# KEY NOTES OK70374-000
COMPOSITE FOUNDATION PLAN
1 SCALE: 3/32" = 1'-0"
1. BUILDING EXPANSION JOINT PER THE FOLLOWING:
A. NOMINAL DIMENSION: 2"
B. MINIMUM DIMENSION: 1"
SHEET TITLE

COMPOSITE FOUNDATION PLAN


C. MAXIMUM DIMENSION: 3"
7/12/2018 12:02:59 PM

Date:
12 JUL 2018
LEGEND
SLAB STEP RE: FOUNDATION PLAN AND DETAILS
SEQ. SHEET OF

PLAN NORTH
12' 6' 0 12'
S-101
KEY PLAN SCALE: 3/32" = 1'-0"
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

AA BB CC DD EE FF GG HH JJ A B C D E F G
OKLAHOMA CITY, OK 73112 405.416.8100

Date Appr
84'-7"
7'-10" 6'-1" 14'-8" 20'-7" 7'-3" 11'-7" 11'-6" 3'-6"
C.H. GUERNSEY & COMPANY

60'-2" 1'-7" 1'-7" 15'-0"


1'-4" 3'-0" 4'-8" 4'-8" 4'-8" 4'-8" 4'-8" 4'-8" 4'-8" 3'-0" 4'-3" 3'-0" 2'-0" 5'-0" 4'-7" 4'-7" 4'-7" 4'-7"
5555 N. GRAND BLVD.

1'-4" 7" 8"

Description
X2

Symbol
9
45°

10"

Appr
7.9 8
2'-1"

4:12

4'-6"
E
RI

Date
DG
DG
3'-6"
8"

RI
E
7.8

15'-0"
4'-5"
4:12 4:12
12'-11"

REVISIONS
4'-10"

E
RI

DG

4:12

4'-5"
DG

RI

Description
4'-4"

RI
E

DG

DG
RI

E
7

3'-8"

10"
4:12
4'-7"
7'-10"

EY

4'-0"
LL
VA
4'-7"

6 4:12 4:12

4'-9"

Symbol
7'-11"

ROOF HATCH,
RIDGE

4'-10" 5'-0" 5'-0" 5'-0"


6'-2"

RE: ARCH

4'-9"
4'-7"
4'-9"

E
DG
5.6
RI

4'-9"
RI
4:12
VA
DG

4'-7"
LL
E
14'-1"

EY
4'-10"

1/4:12
4:12

RI

4'-9"
4'-3"

DG
E
4'-10"

SEE NOTE 10

4:12 4:12 4:12 RIDGE

4'-9"
4'-9"

B. McCOMBS
M.MAURICIO

M.MAURICIO

W. McCANN
89'-8"

Submitted by:
Reviewed by:
4'-7"

Designed by:
1/4:12
4'-9"

Drawn by:
4'-3"
4:12

E
DG

RIDGE
14'-1"

E
4'-7"

RI
DG

EY

4'-7"
RI

4'-9"
LL
VA

4
4:12

RI
4'-7"

3.8
DG
4'-7"

4'-9"
RIDGE
6'-2"
7'-11"

4:12 4:12
4'-9"

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


3.4
4'-7"

4'-9"
VA
7'-10"

LL
EY
4:12
4'-7"

3'-8"

3
4'-4"

RI
E

4:12
DG

DG

17th TRAINING WING


E
RI

DG
RI

NATURE OF WORK:
DG
E

RI
12'-11"

E
4'-10"

4:12 4:12

RIDGE
2.2
3'-6"
8"

4:12
E

RI

4:12 4:12
2'-1"

DG

2
DG

2.1
RI

7"
45°

7"
1

4'-7"

1'-0"
7"

4:12

12'-5"
E

RI

11'-5"
DG

DG
RI

E
4'-7"
1'-8"
C:\Work\R18_70374-000_S_mmauricio.rvt

3'-5"
X1

FACE OF EXISTING
FROM OUTSIDE
2'-0" 4'-6" 4'-7" 4'-4" 4'-4" 4'-7" 4'-6" 2'-0"

BRICK, VIF

PROJECT TITLE
12'-0" 3'-5" 3'-5" 12'-0"
15'-5" 15'-5"
3'-5" 30'-10" 43'-9"
COMPOSITE ROOF FRAMING PLAN NOTES TYP FROM OUTSIDE FACE OF EXISTING BRICK, VIF
COMPOSITE ROOF FRAMING PLAN ALT #1
1 SCALE: 3/32" = 1'-0"
1.
2.
RE: DRAWINGS S-001 THROUGH S-003 FOR GENERAL NOTES, DESIGN CRITERIA, AND ABBREVATIONS.
COORDINATE DIMENSIONS, ELEVATIONS, SECTIONS, AND DETAILS WITH ARCHITECTURAL DWGS.
3. JOISTS, JOIST SUBSTITUTES, AND BEAMS SHALL BE SPACED AT 5'-0" OC MAX.
4. JOIST SEATS SHALL BE 6" DEEP TYPICAL. Project Number:
5. RE: DRAWING S-201 AND S-202 FOR FRAME ELEVATIONS.
6. RE: FOUNDATION PLAN FOR COLUMN SIZES. OK70374-000
7. REFER TO TYPICAL ROOF OPENING DETAIL ON 3/S-011 & 4/S-011 FOR ROOF OPENING FRAMING. COORDINATE
SIZE, LOCATION, AND QUANTITY OF OPENINGS WITH MEP DRAWINGS AND MECHANICAL CONTRACTOR. SHEET TITLE
8. RE: DRAWING S-603 FOR CONNECTION SCHEDULE.
9. RE: DRAWINGS S-011 THROUGH S-012 FOR TYPICAL FRAMING DETAILS. COMPOSITE ROOF FRAMING PLAN
10. ADJACENT JOISTS SHALL BE OFFSET 6" TYPICAL FOR JOIST SEAT ATTACHMENT TO SUPPORTING STRUCTURE.
7/12/2018 12:03:00 PM

Date:
12 JUL 2018

SEQ. SHEET OF
PLAN NORTH
12' 6' 0 12'
S-102
KEY PLAN SCALE: 3/32" = 1'-0"
AA BB CC DD EE FF GG HH JJ A B C
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
103'-11" 1'-0"
7'-10" 6'-1" 14'-8" 20'-7" 7'-3" 11'-7" 1'-7" 11'-6" 3'-6" X1
7'-10" 41'-4" 6" 19'-11" 15'-0" 19'-4"
X2
OKLAHOMA CITY, OK 73112 405.416.8100

Date Appr
6 9

3 53

3 53
C.H. GUERNSEY & COMPANY

BP 14X

BP 14X
7.9 S-501 DP2.0

W
PC7

HS
8

1 57

1 57
BP 16X
S5
7

BP 16X
BP 00
X0

W
5555 N. GRAND BLVD.

GB5

8
.5
S-502 DP2.0 GB5
4"

Description
PC7
7.8 DP2.0 DP2.0
PC1 DP2.0 DP2.0 DP2.0
PC8 PC2

GB5

GB5
7'-11"

GB5
W

GB1

GB3

GB2

GB3

15'-0"
BP 57
16

GB6
2
X

DP2.0 DP2.0 6
9 S-502

0
5 FOUNDATION PLAN NOTES

.50
DP2.5 DP2.5 S-502

HS

3 53
7

Symbol
4 X0
DP2.0

BP 14X
S-502

S5
BP SS5

BP 00
PC8

X0

W
S-501

4
GB5

.5
1 TYP GB5 GB4 DP2.0 1. RE: DRAWINGS S-001 THROUGH S-003 FOR GENERAL NOTES, DESIGN CRITERIA,
7 AND ABBREVATIONS.

2'-0" MIN
GB5

0
TYP
2. COORDINATE DIMENSIONS, WALL OPENINGS, ELEVATIONS, SECTIONS, AND DETAILS
28'-8"
11'-8"

.50
2 57
DP2.5 DP2.0 DP2.0

GB1
BP 16X

4 X0

Appr
PC5 PC3 WITH ARCHITECTURAL DWGS.

GB2
DP2.5

BP SS5
W

GB1

H GB1

0
3. TOP OF SLAB ELEVATION = 1870.38 FT TO MATCH EXISTING, RE: C-110. THIS IS THE

.50

GB1

GB1

GB1
H

HS

4 X0
DP2.0 DATUM ELEVATION = 0'-0". ALL ELEVATIONS ARE REFERENCED FROM THIS

S5

BP SS5
2'-0" MIN

Date
BP 00
X0
PC8 ELEVATION.

4
.5
10 GB1
1'-2"

4. TOP OF CONCRETE PIER CAP ELEVATIONS = -0'-8" (TYP UNO).


6 S-501 5. TOP OF CONCRETE PIER ELEVATIONS = -3'-2" (TYP UNO).

REVISIONS
GB1

GB2

GB2

GB2
DP3.5

6 65
DP2.5 6. TOP OF CONCRETE GRADE BEAM ELEVATIONS VARY. RE: PLAN AND DETAILS.

BP 18X
PC6

HS
FD (E) FDN,

S5
7. STRUCTURAL SLAB: 6" CONCRETE SLAB REINFORCED WITH #4 AT 8" OC EACH WAY,
9'-1"

DP2.5

BP 00
X0
2'-0" MIN

TYP UNO
1 57

CENTERED IN SLAB TYP. PLACE SLAB OVER 15 MIL VAPOR RETARDER AND 6"
1 57

.5
4

Description
BP 16X

PC9 FD
BP 16X

1 TYP CARTON VOID FORMS. VAPOR RETARDER SHALL BOND TO SLAB AND MEET
W

DP2.0

GB1

GB1
GB5 ADHESION TESTS PER SPECS.
PC2
5.6 8. PROVIDE SLAB ISOLATION JOINT AT ALL COLUMNS. RE: 6/S-010.
DP2.0 DP2.0 DP2.5 FD 9. PROVIDE ADDITIONAL SLAB REINFORCEMENT AT ALL RE-ENTRANT CORNERS. RE:
PC9 DP2.5 5/S-010.
5 8 12 10. COORDINATE LOCATIONS AND EXTENTS OF ALL DEPRESSED SLAB AREAS WITH
S-501

0
S-501 DP2.5 S-501 THE ARCHITECTURAL DWGS. RE: 8/S-010.

.50

0
DP2.5

.50
GB1

GB3

4 X0

4 X0
11. RE: DRAWING S-010 FOR TYPICAL FOUNDATION AND SLAB DETAILS.

Symbol
BP SS5
GB1

GB1

GB2
14'-1"

BP SS5
12. RE: DRAWING S-601 AND S-602 FOR FOUNDATION SCHEDULES.

H
DP2.5

H
HS
0
86'-2"

.50

GB1
S5

11
KEY NOTES
4 X0

HS
BP 00
X0

S-201 5 #
BP SS5
GB4

S5
.5
4

DP3.0 S-501 (E) COL,

BP 00
X0
GB2

GB2
H

.5
4
PC9 TYP UNO 1. PROVIDE TYPICAL ISOLATION JOINT PER DETAIL 6/S-010 AT EACH
5

GB1

GB1
DP2.0 COLUMN TYPICAL. ALSO PROVIDE ADDITIONAL REINFORCING AS
4 DP2.0 DP2.5 SHOWN ON PLAN FOR UNSUPPORTED SLAB. ADDITIONAL REINFORCING
PC10 DP3.0

W
S-501 SHALL BE (2) #4 BARS EACH SIDE OF SLAB OPENING TYPICAL. NOT

0
BP 65

.50
18

0
PC6

.50
6
X
GB2
SHOWN AT ALL LOCATIONS FOR CLARITY.

4 X0
0"

4 X0
BP SS5

BP SS5
GB1

GB1

TYP

H
DP2.5

GB1

H
14'-1"

B. McCOMBS
UNO 13

M.MAURICIO

M.MAURICIO

W. McCANN
LEGEND

Submitted by:
Reviewed by:
Designed by:
S-501

GB3
GB1

Drawn by:
HS
1 57

GBx CONTINUOUS GRADE BEAM, RE: PLAN AND SCHEDULE


BP 16X

S5
4

BP 00
X0
DP2.0
GB2
W

4
.5
PC9 DP2.5 DP2.5 DP2.5 PCx PIER CAP, RE: PLAN AND SCHEDULE
DP2.5 1
57'-6"

3.8 DPx DRILLED PIER, RE: PLAN AND SCHEDULE

6 65
S-502
BP 18X

GB1
GB1
DP2.0 GB5 DP2.0 W BPx COLUMN BASE PLATE, RE: PLAN AND SCHEDULE
PC2 2 W#x# WIDE FLANGE COLUMN, RE: PLAN AND SCHEDULE
W

0
BP 57

.50
16

DP3.5
1
X

4 X0
DP2.5 S-502 HSS#x# HSS ROUND COLUMN, RE: PLAN AND SCHEDULE
2 57

PC6

BP SS5
BP 16X
9'-1"

PC9

GB2

H
GB1
W

DP2.5 SLAB STEP, RE: FOUNDATION DETAILS

CRESSMAN DINING FACILITY EXPANSION


9

GOODFELLOW AIR FORCE BASE, TEXAS


3.4
S-501
GB1

GB2

GB2

GB2

GB1 1 SIM FD APPROXIMATE LOCATION OF FLOOR DRAIN.


COORDINATE W/ MEP DRAWINGS.

HS

HS
0

S-502
.50

DP2.0

GB1

GB1

GB1
S5

S5
HS

GB1
BP 00

BP 00
4 X0

X0

X0
HS
S5

PC8

GB1
BP SS5

.5
4

.5
4
BP 00
X0

S5

S-501 DP2.5
4

BP 00
.5

X0
H
11'-8"

4
.5

GB4
3
GB5

2 57

DP2.5 GB5 DP2.0 DP2.0 GB5

17th TRAINING WING


BP 16X

NATURE OF WORK:
PC5
W

PC3
BP 53
W

14

3
X

DP2.5 DP2.5
DP2.0 4 D
GB6

PC8 DP2.0 GB5 DP2.0


GB1

GB3

GB2

GB3

S-502
15'-0"
7'-11"

1 57

1 57
.50

BP 16X

BP 16X

GB5
GB5
8 X0

3
BP SS5

DP2.0 DP2.0 (2) #4 EA SIDE OF


H

PC1 DP2.0 PC8 DP2.0 S-502 UNSUPPORTED SLAB TYP


2'-0"
TYP

2.2 DP2.0 AT VESTIBULE COLUMNS


4"

GB5 PC2 GB5


DP2.0
2
3 53

PC7 DP2.0
BP 14X
W
BP 53

PC7
14

2.1
W
3
X

1 2 8 DP2.0 DP2.0
1
C:\Work\R18_70374-000_S_mmauricio.rvt

S-501 S-501 PC4 PC4

HS
S-502

HS
DP2.0 DP2.0

S5
S5

BP 00
X0
BP 00
X0
GB6

7
.5
GB6
7
.5
S-201 2
7'-10" 20'-9" 20'-7" 20'-5" 15'-0"

GB4

GB4
1

HS

PROJECT TITLE
8'-0" 4" 61'-9" 15'-0" 19'-4"

S5
S-501

BP 00
DP2.0

X0
.5
7
X1 104'-5" PC8
DP2.0
PC1 GB6 DP2.0

HS
HS
X2 PC1

S5
S5

BP .500
BP 00

X0
X0

10
1 11 12

.5
9
AA BB CC DD EE FF GG HH JJ S-502 S-502
S-201
Project Number:

OK70374-000

FOUNDATION PLAN ALT #1 FOUNDATION PLAN SHEET TITLE


1 SCALE: 1/8" = 1'-0" 2 SCALE: 1/8" = 1'-0" FOUNDATION PLAN
7/12/2018 12:03:01 PM

Date:
12 JUL 2018

PLAN NORTH SEQ. SHEET OF

8' 4' 0 8'

SCALE: 1/8" = 1'-0"


S-111
KEY PLAN
4 5
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
S-121
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
T/ STL EL =
METAL DECK, RE: LOW ROOF 12'-10 3/4" CONN, RE: SCHED ON SHT
FRAMING PLAN NOTES S-603 TYP
GG HH JJ A
SLOPE SLOPE

T/ STL EL
OKLAHOMA CITY, OK 73112 405.416.8100

8 VARIES
S-121

Date Appr
HSS10X6X1/4 EAVE
7.9

2'-1"
112'-0"
C.H. GUERNSEY & COMPANY

CONN, RE: S-603 TYP

HSS10X6X1/4
WF BMS, RE: LOW ROOF
7.8
5555 N. GRAND BLVD.

HSS COL, RE: FOUNDATION FRAMING PLAN TYP


3

Description
HSS10X6X1/4
HSS6X6X3/16 7 PLAN TYP
15'-0"
12'-11" S-121
S-121
5
S-121
BEAM SPLICE AT LOW ROOF
7
W10X22
2 SCALE: 1" = 1'-0"

Symbol
GG HH JJ
W10X15 1/4 2@12

7'-8 1/2"
W10X15

W10X15
7'-10"

W10X15

Appr
7"
6 5 9"x6"x1/4"xCONT (E) BUILDING
BENT PL (LLH) GRID
7

Date
CANTILEVERED BM,
7'-11"

4 W10X15 L4x4x1/4 FOR ATTACHMENT


RE: FRAMING PLAN OF CFS STUDS

W10X15

REVISIONS
S-121 L6x6x3/8xCONT L3x3x1/4xCONT
TOP OF STEEL
5.6 114'-3" 1/4 2@12
W10X15

17'-0"

Description
11"x6"x1/4"xCONT 1/4 2@12
1/4 2@12 BENT PL (LLH)
W10X15

TYP
2 STAGGERED 1/4 2@12 SLOPE

3 1/4"
1/4 2@12
W10X15 S-121

1 1/2"
TYP
14'-1"

EAVE
112'-0"
W8 BEAMS AT 5'-0" OC MAX

BRG EL @ LOW ROOF

Symbol
W10X15
5'-1 1/2"
VARIES
1 1/2"
TYP
59'-8"

L4X4X1/4 FOR ATTACHMENT


5 EQ EQ
8"x6"x3/8" PL W/
OF CFS STUDS
W10X15 (2) 3/4" DIA A325 FRAMING, RE: LOW ROOF
BOLTS TO EA BM FRAMING PLAN, TYP
7'-7 1/2"

RE: ARCH 10"

W10X15 FRAMING, RE: FRAMING PLAN TYP


14'-1"

BEAM SPLICE SECTION THRU LOW ROOF SECTION AT ENTRY TOWER


OPP
HAND
2
3 SCALE: 1 1/2" = 1'-0" 4 SCALE: 1" = 1'-0" 5 SCALE: 1" = 1'-0"

B. McCOMBS
W10X15

Submitted by:
Reviewed by:
S-121

Designed by:
Designer

Checker
3.8

Drawn by:
Author
W10X15

W10X15

14'-6"

W10X15
GRID
7'-11"

GRID GRID
A WF COL, RE:
FOUNDATION PLAN
7'-2" BM
W10X15 SPLIT-FACE
3.4
VENEER, RE: ARCH HSS BM, RE: LOW ROOF
CFS STUDS, RE: ARCH
W10X15

W10X15

FRAMING PLAN TYP


7'-8 1/2"

EAVE EAVE 6"x6"x3/8" SHEAR TAB EA


7'-10"

CRESSMAN DINING FACILITY EXPANSION


L3x3x1/4x0'-4" CLIP ANGLE

GOODFELLOW AIR FORCE BASE, TEXAS


W10X15 112'-0" 112'-0" SIDE OF HSS BM, TYP UNO
EACH SIDE OF HSS BM
4"

6"

6"
9

10"
HSS BM, RE: FRAMING PLAN T/ STL EL
3 1/4
S-121 W10X22 PL TO COL 111'-6"
1/4
5
HSS10X6X1/4

S-121 3/16 2@12


12'-11"

HSS10X6X1/4

17th TRAINING WING


7

NATURE OF WORK:
15'-0"

HSS6X6X3/16 PL TO BM
RE: 6/S-S121 FOR
S-121 L6x6x1/2xCONT SHELF ANGLE INFO NOT NOTED 3 SIDES TYP 3/16
BM, RE: LOW ROOF
FRAMING PLAN, TYP 1/2"
STAGGER 3 SIDES, TYP
2.2 WELDS 3/16 2@12 CURTAINWALL, RE: ARCH 3/16
2'-1"

HSS10X6X1/4
2.1 ENTRY FRAMING SECTION ENTRY FRAMING SECTION ENTRY FRAMING SECTION
6
S-121
6 SCALE: 1" = 1'-0" 7 SCALE: 1" = 1'-0" 8 SCALE: 1" = 1'-0"
C:\Work\R18_70374-000_S_mmauricio.rvt

LOW ROOF FRAMING PLAN HH


1 SCALE: 1/8" = 1'-0" SPLIT-FACE CMU, RE: ARCH

PROJECT TITLE
L6x6x1/2xCONT SHELF ANGLE,
COPE VERT LEG AT COL &
WELD HORIZ LEG TO 1/2" PL
EAVE
1/4 112'-0"
ANGLE LEG

6"
TO 1/2" PL 1/4

ROOF FRAMING PLAN NOTES

8"
WF COL
1. RE: DRAWINGS S-001 THROUGH S-003 FOR GENERAL NOTES, DESIGN CRITERIA, AND ABBREVATIONS.
Project Number:
2. COORDINATE DIMENSIONS, WALL OPENINGS, ELEVATIONS, SECTIONS, AND DETAILS WITH
ARCHITECTURAL DWGS.
# KEY NOTES
3. ROOF STEEL SLOPES. JOIST BEARING/TOP OF STEEL ELEVATION AROUND THE PERIMETER = +14'-3" OK70374-000
1. HSS5x0.500 POST
FROM THE DATUM ELEVATION UNLESS NOTED OTHERWISE. (+/- X'-X") DENOTES STEEL ELEVATION 2. HSS5x0.500 POST CONNECTED TO TOP OF EXISTING WF COLUMN, RE: 10/S-521
WF COL, RE: FDN PLAN SHEET TITLE
VARIATIONS FROM THE SLOPING STEEL PLANE. 3. PROVIDE JOIST EXTENDED ENDS THIS END ONLY FOR SUPPORT OF ROOF DECK
4. RE: DRAWING S-102 FOR JOIST SPACING TYPICAL. 1/2" PL TO FRAMING PLAN - LOW ROOF
5. ROOF DECK: 1 1/2" - 20 GAGE, TYPE B, GALVANIZED METAL DECK. DECK ATTACHMENT PER 1/S-011. FLANGE TYP
6. ALL CONTINUOUS DECK ANGLES TO BE FULL DEVELOPMENT BUTT WELDED AT SPLICES, SEE DETAIL 1/4
7/12/2018 12:03:01 PM

5/S-011. Date:
7. RE: DRAWING S-201 AND S-202 FOR FRAME ELEVATIONS. LEGEND 1/2" PL BTWN COL
FLANGES
12 JUL 2018
8. RE: FOUNDATION PLAN FOR COLUMN SIZES.
9. REFER TO TYPICAL ROOF OPENING DETAIL ON 3/S-011 & 4/S-011 FOR ROOF OPENING FRAMING. FULLY RESTRAINED MOMENT CONNECTION
COORDINATE SIZE, LOCATION, AND QUANTITY OF OPENINGS WITH MEP DRAWINGS AND MECHANICAL
CONTRACTOR. SPAN DIRECTION
10. RE: DRAWING S-603 FOR CONNECTION SCHEDULE. CMU SUPPORT AT COLUMN SEQ. SHEET OF
11. RE: DRAWINGS S-011 THROUGH S-012 FOR TYPICAL FRAMING DETAILS.
12. LOCATIONS AND WEIGHTS OF THE EQUIPMENT SHOWN ON THE PLAN HAVE BEEN ASSUMED FOR 9 SCALE: 1" = 1'-0"
PLAN NORTH
8' 4' 0 8' 1' 0' 1' 2'
BIDDING PURPOSES ONLY. CONTRACTOR TO COORDINATE FINAL UNIT LOCATIONS AND WEIGHTS (AND
ADDITIONAL UNITS) AND SUBMIT TO CONTRACTING OFFICER FOR REVIEW PRIOR TO PROCEEDING WITH
ANY FABRICATION.
S-121
KEY PLAN SCALE: 1/8" = 1'-0" SCALE: 1" = 1'-0"
AA BB CC DD EE FF GG HH JJ A B C
X2
3'-7" 4'-5" 3'-5" 41'-4" 3'-7" 15'-3" 7" 1'-0" 15'-0"
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

TYP
3
S-522
5 ROT TYP
S-521 3 1
OKLAHOMA CITY, OK 73112 405.416.8100

S-521 S-521 9

Date Appr
C6X8.2

C6X8.2

C6X8.2
C6X8.2
W12X35
8

2.5K3

2.5K3
C.H. GUERNSEY & COMPANY

7.9
3'-5"

W10X22 (LO)
W14X30 W16X67 C6X8.2 W C6X8.2
8X
10 10
8X
2.5K3 2.5K3 W

2.5K3

2.5K3
5555 N. GRAND BLVD.

7.8 4 C6X8.2 C6X8.2

Description
W14X30
S-522 1
ROOF FRAMING PLAN NOTES

W12X35

W12X35
2.5K3

2.5K3
10K1SP

12K1SP

12K1SP

10K1SP

15'-0"
2.5K3 2.5K3

W14X30
W10X22 (LO)
1. RE: DRAWINGS S-001 THROUGH S-003 FOR GENERAL NOTES, DESIGN CRITERIA, AND ABBREVATIONS.

W10X22 (LO)
2.5K3 2.5K3 C6X8.2 C6X8.2 2. COORDINATE DIMENSIONS, WALL OPENINGS, ELEVATIONS, SECTIONS, AND DETAILS WITH

10

W
ARCHITECTURAL DWGS.

8X
8X
8
W

10
W
X3
3. ROOF STEEL SLOPES. JOIST BEARING/TOP OF STEEL ELEVATION AROUND THE PERIMETER = +14'-3"

14
TYP

14
C6X8.2 C6X8.2

X3
FROM THE DATUM ELEVATION UNLESS NOTED OTHERWISE. (+/- X'-X") DENOTES STEEL ELEVATION

W
8
10K1SP 10K1SP W14X30
7 3

Symbol
VARIATIONS FROM THE SLOPING STEEL PLANE.

C6X8.2

C6X8.2

C6X8.2

C6X8.2
W12X35

2.5K3
S-521 4. RE: DRAWING S-102 FOR JOIST SPACING TYPICAL.
W16X67 2 5. ROOF DECK: 1 1/2" - 20 GAGE, TYPE B, GALVANIZED METAL DECK. DECK ATTACHMENT PER 1/S-011.

10K1SP
6. ALL CONTINUOUS DECK ANGLES TO BE FULL DEVELOPMENT BUTT WELDED AT SPLICES, SEE DETAIL

W12X14
12K1SP 10K1SP 5 SIM

W12X14
10K1SP
5/S-011.

8
X3
S-521 ROT

Appr
7. RE: DRAWING S-201 AND S-202 FOR FRAME ELEVATIONS.

14
6

W
8
8. RE: FOUNDATION PLAN FOR COLUMN SIZES.

X3
6

14
S-522 9. REFER TO TYPICAL ROOF OPENING DETAIL ON 3/S-011 & 4/S-011 FOR ROOF OPENING FRAMING.

12K1SP
16K2SP 10K1SP

Date
W
COORDINATE SIZE, LOCATION, AND QUANTITY OF OPENINGS WITH MEP DRAWINGS AND MECHANICAL
2.5K3
W14X30

4 CONTRACTOR.
10K1SP

REVISIONS
S-521 10. RE: DRAWING S-603 FOR CONNECTION SCHEDULE.
16K2SP

12K1SP
2.5K3 2.5K3 11. RE: DRAWINGS S-011 THROUGH S-012 FOR TYPICAL FRAMING DETAILS.
12. LOCATIONS AND WEIGHTS OF THE EQUIPMENT SHOWN ON THE PLAN HAVE BEEN ASSUMED FOR

Description
BIDDING PURPOSES ONLY. CONTRACTOR TO COORDINATE FINAL UNIT LOCATIONS AND WEIGHTS (AND
W16X67 10K1SP

W12X14
ADDITIONAL UNITS) AND SUBMIT TO CONTRACTING OFFICER FOR REVIEW PRIOR TO PROCEEDING WITH

(E) W18X35
5.6 12K1SP 2.5K3 2.5K3 ANY FABRICATION.

W16X67
2.5K3

12K1SP
W

10K1SP
W

14

8
12

X3
10K1SP
X3
W14X30

10K1SP
X1

14
8

TYP 10K1SP
4

W
W
12
KEY NOTES
X1
10K1SP TYP #

4
3 1

Symbol
3 EXISTING BUILDING
S-521 10K1SP 12K1SP 4 1. HSS5x0.500 POST
1 1 S-121

W12X14
10K1SP 2. HSS5x0.500 POST CONNECTED TO TOP OF EXISTING WF COLUMN, RE: 10/S-521
10K1SP W16X89 (LO) 1 3. PROVIDE JOIST EXTENDED ENDS THIS END ONLY FOR SUPPORT OF ROOF DECK
5 W12X14 W12X14 (HI) S-522
85'-6"

W12X14 10K1SP
W18X35

12K1SP
10K1SP
LEGEND
4
X1

10K1SP 3
12
W

10K1SP
W14X30

10K1SP FULLY RESTRAINED MOMENT CONNECTION


4
X1

10K1SP
W18X55
12

W16X67
W
W

(E) W18X35
8

SPAN DIRECTION
14
X3

X3
10K1SP
14

2.5K3

B. McCOMBS
8
W

12K1SP

10K1SP

M.MAURICIO

M.MAURICIO
4

W. McCANN
2.5K3

Submitted by:
Reviewed by:
Designed by:
3.8 12K1SP

W12X14
2.5K3

Drawn by:
W16X67
12K1SP

2 10K1SP
S-521 16K2SP 2.5K3
W14X30

12K1SP

2.5K3
2.5K3 TYP
W

10K1SP
14

10K1SP
X3

16K2SP 3 7
8

3.4 S-522

W12X14
S-522
W12X14

W
10K1SP

14
10K1SP

CRESSMAN DINING FACILITY EXPANSION


X3

GOODFELLOW AIR FORCE BASE, TEXAS


37'-11"
10K1SP

8
12K1SP
W16X67

TYP
2.5K3

C6X8.2
C6X8.2

C6X8.2
C6X8.2
2
10K1SP
3 W12X35
3 S-521 10K1SP W14X30 3

W10X22 (L0)
C6X8.2 C6X8.2
8

W
X3

10
14

8X
14

8X
X3

2.5K3 COLD-FORMED STEEL


W

10
2.5K3

W
8

OVERBUILD ON EXISTING ROOF


W14X30

C6X8.2 C6X8.2

17th TRAINING WING


5 SIM (EXISTING STANDING SEAM

NATURE OF WORK:
6
2.5K3

2.5K3

6
12K1SP
10K1SP

10K1SP
12K1SP

W12X35

W12X35
W10X22 (L0) 1 S-521 ROT ROOF TO BE REMOVED THIS
2.5K3 S-521 S-522 2 AREA DURING DEMOLITION)
W14X30

2.5K3
2.5K3 S-523

18'-10"
2.5K3

2.5K3

W10X22 (L0)
2.2 2.5K3 C6X8.2 C6X8.2

W
10

8X
8X

10
W

W14X30 W16X67 C6X8.2 C6X8.2


3'-5"

2.1 1 1
W12X35 1
C6X8.2

C6X8.2

C6X8.2

C6X8.2
W16X40 (LO)
2
2.5K3 2.5K3 S-523
5 10K1SP 10K1SP
1 10 1
S-521

W
X2
S-521 S-521

12
12

X2
W
4

W12X22
W12X22
C:\Work\R18_70374-000_S_mmauricio.rvt

2 2 S-201

10K1SP

10K1SP

10K1SP
S-522 1 LOW ROOF S-201
S-121 FRAMING PLAN

W12X22

PROJECT TITLE
W12X22

X1
1
5
S-521 D 1 5 E
S-521 ROT
S-201 S-521

HIGH ROOF FRAMING PLAN ALT #1 Project Number:


1 SCALE: 1/8" = 1'-0" OK70374-000
ROOF FRAMING PLAN
2 SCALE: 1/8" = 1'-0"
SHEET TITLE

FRAMING PLAN - HIGH ROOF


7/12/2018 12:03:02 PM

Date:
12 JUL 2018

SEQ. SHEET OF

PLAN NORTH
8' 4' 0 8'
S-122
KEY PLAN SCALE: 1/8" = 1'-0"
2 1 METAL DECK, RE: PLAN NOTES
D METAL DECK, RE: PLAN NOTES 3/16" CONT BENT PL BTWN
COL COL
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018 COL EA JST @ PERIMETER COL
3/16" CONT BENT PL BTWN
EA JST @ PERIMETER TOP OF STEEL
114'-3"
WP
TOP OF STEEL TOP OF STEEL
114'-3" 114'-3"
BM BM
WF BM, RE: FRAMING PLAN WF BM, RE: FRAMING PLAN
OKLAHOMA CITY, OK 73112 405.416.8100

2"
RE: S-603 FOR CONN TYP
WP

Date Appr
3/8" STIFFENER TYP WP
1/4
EAVE EAVE 1" M
112'-0" 112'-0" TYP IN 1/4
C.H. GUERNSEY & COMPANY

RE: S-603 FOR


CONN TYP 1/2" GUSSET PL TYP
3
5555 N. GRAND BLVD.

3 S-201

Description
S-201
1/4 4" MIN
TYP
1/4 4" MIN
EQ EQ

Symbol
HSS COL, RE: FDN PLAN

HSS COL, RE: FDN PLAN

X1/4

L4X
BRACED FRAME AT ROOF

4X1
L4X

L4X4
3

HSS COL, RE: FDN PLAN

HSS COL, RE: FDN PLAN


/4

/4
4X1
4X1

SCALE: 1" = 1'-0"

/4
L4X

Appr
Date

REVISIONS
1/4 4" MIN

Description
1" M 1/4 4" MIN
T IN
2" YP

4 OPP 4 4 SIM 4 1/2" GUSSET PL


S-201 HAND S-201 S-201
SIM OPP S-201
HAND 1/4
WP

Symbol
1/4
WP WP
FINISH FLR
WP WP 100'-0"
FINISH FLR FINISH FLR
100'-0" 100'-0"

B. McCOMBS
M.MAURICIO

M.MAURICIO

W. McCANN

Submitted by:
Reviewed by:
B PL & ANCHORS,

Designed by:
RE: PLAN & SCHED

Drawn by:
FDN TYPE VARIES AT SIM CONDITION

15'-5"
11'-5"

E-W BRACED FRAME N-S BRACED FRAME BRACED FRAME AT FLOOR

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


1 SCALE: 1/2" = 1'-0" 2 SCALE: 1/2" = 1'-0" 4 SCALE: 1" = 1'-0"

5.6 5 3.8

17th TRAINING WING


NATURE OF WORK:
3/8" CAP PL, EXTEND TO METAL ROOF DECK, RE: HIGH ROOF FRAMING PLAN NOTES ROOF FRAMING, RE: HIGH ROOF FRAMING PLAN, TYP
CATCH DECK RUNNING
PERPENDICULAR TYP

T/ STL EL
118'-1"
@ MOMENT
FRAME BEAMS
C:\Work\R18_70374-000_S_mmauricio.rvt

CONNECTION, RE: SCHED ON SHT S-603 TYP WF MOMENT FRAME BEAM, RE: T/ STL EL
HIGH ROOF FRAMING PLAN TYP
115'-10"

WF MOMENT FRAME COL, RE: FOUNDATION PLAN TYP

PROJECT TITLE
WF BM, RE: HIGH ROOF FRAMING PLAN

Project Number:
STRUCT SLAB, RE: FOUNDATION PLAN ANCHOR RODS & BASE PLATES, RE: FOUNDATION PLAN,
DETAILS, AND SCHED ON SHT S-603 TYP OK70374-000

FINISH FLR SHEET TITLE


100'-0" ELEVATIONS
7/12/2018 12:03:02 PM

Date:
FOUNDATION, RE: FOUNDATION PLAN & SCHED TYP 12 JUL 2018

17'-10" 17'-10"
SEQ. SHEET OF

INTERIOR MOMENT FRAME ALONG GRID FF


5 SCALE: 1/2" = 1'-0" S-201
GRID
GRID BB AA
11"
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
FOR INFORMATION NOT
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
11" 11"
7" NOTED, RE: 1/S-501 1'-1"
7" FOR INFORMATION NOT
800S162-54 AT 16" OC WITH 7" NOTED, RE: 1/S-501 7" FOR INFORMATION NOT
TRACK OF SAME GAGE, TYP COL, RE: PLAN NOTED, RE: 1/S-501
COL, RE: PLAN
BRICK VENEER, 2'-0"x2'-0" #4 DOWEL AT 18" OC TYP BP & ANCHORS, RE: PLAN & SCHED
RE: ARCH BP & ANCHORS, RE: PLAN & SCHED COL, RE: PLAN
STRUCTURAL SLAB, RE: BP & ANCHORS, RE: PLAN & SCHED
BRICK LEDGE, TYP 2" HIGH STRENGTH NON-SHRINK GROUT TYP 2" HIGH SRENGTH NON-SHRINK GROUT TYP
PLAN AND PLAN NOTES
OKLAHOMA CITY, OK 73112 405.416.8100

#4 CONT, TYP 1/2" ISOLATION JT, RE: 6/S-010 1/2" ISOLATION JT, RE: 6/S-010
1/2" ISOLATION JT, RE: 6/S-010

Date Appr
#4x2'-0" DOWEL SLAB, RE: FDN PLAN NOTES SLAB, RE: FDN PLAN NOTES
AT 18" OC, TYP SLAB, RE: FDN PLAN NOTES
FINISH FLR FINISH FLR FINISH FLR FINISH FLR

VARIES 2"

VARIES 2"
C.H. GUERNSEY & COMPANY

100'-0" 100'-0" FINISHED GRADE, 100'-0" FINISHED GRADE,


100'-0"

6"

6"

6"

6"
RE: CIVIL RE: CIVIL

2"

2"

2"

2"
SLOPE SLOPE SLOPE
5555 N. GRAND BLVD.

Description
VAPOR RETARDER, TYP
FINISHED GRADE, 6" VOID FORMS, TYP FINISHED GRADE,

2'-6"

2'-6"

2'-6"
RE: CIVIL

D
RE: CIVIL
COMPACTED PIER CAP, RE: PIER CAP, RE:
SUBGRADE, TYP PLAN & SCHED PERIMETER GB PERIMETER GB
PLAN & SCHED
PIER CAP, RE: BEYOND, EXTEND BEYOND, EXTEND

Symbol
PERIMETER GRADE BEAM, PLAN & SCHED HORIZ REINF HORIZ REINF
RE: PLAN AND SCHEDULE DRILLED PIER, RE: THRU PC TYP DRILLED PIER, RE:
PLAN & SCHED THRU PC TYP
PLAN & SCHED
DRILLED PIER, RE:
PLAN & SCHED GB, RE: PLAN. EXTEND FULLY
6" VOID FORM TYP

Appr
BENEATH GRADE BEAMS DEV HORIZ REINF INTO PC W/
CORNER BARS PER 3/S-010
W RETAINER BOARD TYP

Date
PERIMETER GB BEYOND, EXTEND
HORIZ REINF THRU PC TYP

REVISIONS
Description
TYP EXT GRADE BEAM SECTION AT PERIMETER WF COL SECTION AT PERIMETER WF COL SECTION AT PERIMETER HSS COL
1 SCALE: 3/4" = 1'-0" 2 SCALE: 3/4" = 1'-0" 3 SCALE: 3/4" = 1'-0" 4 SCALE: 3/4" = 1'-0"

AA DD
GRID

Symbol
7" 6"
1" 7" 4" GRID

COL, RE: PLAN 800S162-54 AT 16" OC WITH


TRACK OF SAME GAGE, TYP
ANCHORS & BP, RE: PLAN & SCHED STRUCTURAL SLAB, RE: PLAN & NOTES 1/2" ISOLATION JT, TYP
2'-0"x2'-0" #4 DOWEL AT 18" OC TYP STRUCTURAL SLAB, RE: PLAN & NOTES
1/2" ISOLATION JT, RE: 6/S-010 STRUCTURAL SLAB, RE: PLAN & NOTES
STRUCTURAL SLAB, RE:

EQ TYP
PLAN AND PLAN NOTES

B. McCOMBS
FINISH FLR FINISH FLR FINISH FLR FINISH FLR FINISH FLR

M.MAURICIO

M.MAURICIO

W. McCANN

Submitted by:
Reviewed by:
100'-0" 100'-0" 100'-0" 100'-0" 100'-0"

Designed by:

Drawn by:
8"
2'-6"

PIER CAP, RE: PLAN & SCHED


6" VOID FORM TYP

CRESSMAN DINING FACILITY EXPANSION


GB, RE: PLAN & SCHED.

GOODFELLOW AIR FORCE BASE, TEXAS


PIER CAP, RE: PROVIDE CORNER BARS GB, RE: PLAN & SCHED
PLAN & SCHED GB, RE: PLAN & SCHED GB BEYOND, EXTEND
PER 3/S-010 TYP. HORIZ REINF THROUGH
6" VOID FORM TYP PIER CAP TYP

PERIMETER GB PIER, RE: PLAN & SCHED


DRILLED PIER, RE: BEYOND, EXTEND PROVIDE (4) DOWELS
PLAN & SCHED. HORIZ REINF MATCHING SIZE OF VERT

17th TRAINING WING


PROVIDE DOWELS REINF INTO GB ABOVE

NATURE OF WORK:
THRU PC TYP PIER, RE: PLAN & SCHED
MATCHING SIZE AND EXTEND VERT REINF INTO
NUMBER OF VERT PIER CAP ABOVE TYP
REINF INTO GB ABOVE

SECTION AT MOMENT FRAME GRADE BEAM INTERSECTION TYP INTERIOR GRADE BEAM TYPICAL INTERIOR PIER SECTION AT INTERIOR COLUMN
5 SCALE: 3/4" = 1'-0" 6 SCALE: 3/4" = 1'-0" 7 SCALE: 3/4" = 1'-0" 8 SCALE: 3/4" = 1'-0" 9 SCALE: 3/4" = 1'-0"

FF
GRID GG HH
JJ A
1'-7"
COL & GB FILL (E) BRICK LEDGE W/
NON-SHRINK GROUT FLUSH
C:\Work\R18_70374-000_S_mmauricio.rvt

(E) CMU INFILL TO REMAIN


WITH FINISHED FLOOR, TYP
HSS COL, RE: FDN PLAN COL, RE: PLAN
3/4" DIA x 16" LONG SMOOTH
Ld 1/2" ISO JT BTWN
STRUCTURAL BASE PL & ANCHORS, RE: PLAN TYP BASE PL & ANCHORS, RE: PLAN & SCHED DOWEL @ 12" OC. APPLY BOND
PER SCHEDULE NEW AND (E) TYP
SLAB TYP, RE: BREAKER TO ONE END, TYP

PROJECT TITLE
1 1/8" TYP

1/2" ISO JT TYP


@ TILE

PLAN & NOTES 1/2" ISO JT TYP (E) SLAB

FINISH FLR FINISH FLR FINISH FLR FINISH FLR


100'-0" 100'-0" 100'-0" 100'-0"
8"
6"

PROVIDE CORNER
BARS PER 3/S-010 TYP.
Project Number:
(E) FDN
OK70374-000
2'-6"

GB, EXTEND HORIZ


SHEET TITLE
REINF INTO
INTERSECTING GB GB, RE: PLAN & SCHED FOUNDATION SECTIONS
W/ STD ACI HOOKS
TYP
6" VOID FORM TYP
7/12/2018 12:03:03 PM

BENEATH SLAB AND GB Date:


12 JUL 2018
GB, RE: PLAN & SCHED
PROVIDE CORNER
GB BEYOND, EXTEND
BARS PER 3/S-010 TYP. 2' 1' 0 2'
HORIZ REINF THRU SEQ. SHEET OF
INTERSECTING GB TYP

SCALE: 3/4" = 1'-0"

S-501
SLAB RECESS AT TILE COLUMN TO GRADE BEAM COLUMN TO GRADE BEAM SECTION AT EXISTING
10 SCALE: 3/4" = 1'-0" 11 SCALE: 3/4" = 1'-0" 12 SCALE: 3/4" = 1'-0" 13 SCALE: 3/4" = 1'-0"
A 3.4
GRID GRID
3
GRID
3 A
1/2" ISO JT TYP 1" HH GG
3/4" DIA x 16" LONG SMOOTH 7" 800S162-54 AT 16" OC WITH
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018 1" CURTAINWALL, RE: ARCH 6" 8"
DOWEL @ 12" OC. APPLY BOND (E) CMU INFILL TO REMAIN 800S162-54 AT 16" OC TRACK OF SAME GAGE, TYP
7"
BREAKER TO ONE END, TYP WITH TRACK OF 2'-0"x2'-0" #4 DOWEL AT 2'-0"x2'-0" #4 DOWEL
1'-2" 5"
FILL (E) BRICK LEDGE W/ SAME GAGE, TYP 18" OC TYP AT 18" OC TYP
2'-0"x2'-0" #4 DOWEL AT 18" OC TYP NON-SHRINK GROUT, TYP RECESSED SLAB
FINISH, RE: ARCH SLAB RECESS AT TILE, STRUCT SLAB, RE:
AT TILE TYP,
TYP. COORD W/ ARCH

VARIES
SLAB, RE: PLAN TYP (E) FLOOR SLAB COORD W/ ARCH PLAN & NOTES

1 1/8"

1 1/8"
ELEV VARIES AT SIM
FINISH FLR FINISH FLR FINISH FLR FINISH FLR FINISH FLR
OKLAHOMA CITY, OK 73112 405.416.8100

2"
100'-0" 100'-0" 100'-0" 100'-0" 100'-0"

Date Appr
8"

8"
6"
C.H. GUERNSEY & COMPANY

RE: PLAN & SCHED TYP


CONT GB W/ BRICK

RE: PLAN & SCHED

3'-0 7/8"
LEDGE, RE: PLAN & SCHED
5555 N. GRAND BLVD.

Description
D

D
FOR INFO NOT
NOTED, RE: 1/S-501 GB, RE: PLAN & SCHED

6" VOID FORM BENEATH


6" VOID FORMS SLAB & GB TYP
BENEATH SLAB &
GB TYP GB, RE: PLAN & SCHED

Symbol
(E) FDN

W
W

Appr
SECTION AT EXISTING SLAB AT TILE ENTRY SECTION AT RAMP EXTERIOR WALL AT RAMP SECTION AT ENTRY

Date
1 SCALE: 3/4" = 1'-0"
2 SCALE: 3/4" = 1'-0" 3 SCALE: 3/4" = 1'-0" 4 SCALE: 3/4" = 1'-0" 5 SCALE: 3/4" = 1'-0"

REVISIONS
Description
7
GRID

8" 2'-0"x2'-0" #4 DOWEL AT GRID GRID


3
18" OC TYP A
RECESSED SLAB AT

Symbol
TILE, TYP. COORD SPLIT-FACE CMU, RE: ARCH
1/2" ISO JT
W/ ARCH FINISH, RE: ARCH 8'-1 1/2" 8'-2 1/2" RECESSED SLAB
3/4" DIA x 16" LONG SMOOTH AT TILE, COORD
DOWEL AT 12" OC. APPLY BOND W/ ARCH
-1 1/2"

VARIES
(E) SLAB BREAKER TO ONE END, TYP NEW SLAB,

1/4"
STAIR STOOP, RE: CIVIL SLOPE NEW EXT RAMP
RE: PLAN TYP
10 WALL, RE: CIVIL
FINISH FLR FINISH FLR FINISH FLR

6"
100'-0" 100'-0" 100'-0" S-502

1 1/8"
RE-ENTRANT

8"

6"
2"

CORNER REINF
TYP, RE: 5/S-010
CONT GB W/ BRICK

B. McCOMBS
M.MAURICIO

M.MAURICIO
LEDGE, RE: PLAN &

W. McCANN

Submitted by:
Reviewed by:
Designed by:
SCHED

1"

Drawn by:
7
GRID

2'-6"
GB, RE: PLAN
& SCHED TYP
6" VOID FORMS TYP
VAPOR
RETARDER (E) COL
COMPACTED
(E) FDN SUBGRADE COMPACTED GB BELOW, (E) PIER CAP
SUBGRADE TYP. RE: PLAN

CRESSMAN DINING FACILITY EXPANSION


PIER, RE: PLAN & & SCHED

GOODFELLOW AIR FORCE BASE, TEXAS


SCHED. EXTEND (E) PIER
PIER, RE: PLAN & SCHED. DOWELS MATCHING
EXTEND VERT REINF INTO VERT REINF SIZE &
PIER CAP ABOVE NUMBER INTO GB
ABOVE TYP

SECTION AT EXISTING SECTION AT EXTERIOR COLUMN SECTION AT ENTRY PLAN AT EXIST COL

17th TRAINING WING


6 7 8 9

NATURE OF WORK:
SCALE: 3/4" = 1'-0" SCALE: 3/4" = 1'-0" SCALE: 3/4" = 1'-0" SCALE: 3/4" = 1'-0"

FILL (E) BRICK LEDGE W/ 1 2


COL, RE: PLAN
1 HIGH STRENGTH NON- 2
GRID
7 COL SHRINK GROUT TYP
7" 12'-8 1/2"
(E) COL & GROUT FILL 7" 4" BASE PL & ANCHORS,
RE: PLAN & SCHED 1/2" ISO JT, TYP 800S162-54 AT 16" OC FILL (E) BRICK LEDGE W/ HIGH
ANCHOR BOLTS FLUSH WITH FIN (E) CMU INFILL TO REMAIN
WITH TRACK OF STRENGTH NON-SHRINK GROUT TYP
FLR AS REQUIRED 1/2" ISO JT 3/4" DIA x 16" LONG (E) SLAB SAME GAGE, TYP
C:\Work\R18_70374-000_S_mmauricio.rvt

SMOOTH DOWEL @ 12" OC. 1/2" ISO JT, TYP (E) CMU INFILL TO REMAIN
1/2" EXP JT TYP
1 1/8" TYP

STRUCT SLAB, FINISH, RE: ARCH


@ TILE

APPLY BOND BREAKER TO (E) FLOOR FRAMING 3/4" DIA x 16" LONG SMOOTH (E) SLAB
RE: PLAN & ONE END, TYP DOWEL @ 12" OC. APPLY BOND
NOTES (E) FLOOR FRAMING
BREAKER TO ONE END, TYP
FINISH FLR FINISH FLR FINISH FLR

PROJECT TITLE
2"

2"
100'-0" 100'-0" 100'-0"
TYP
8"

(E) FDN

(E) FDN
Project Number:

3/4" DIA x 16" LONG 6" VOID FORMS PC, RE: SCHED NOT AT SIM
NOT AT SIM CONDITION OK70374-000
SMOOTH DOWEL @ TYP CONDITION
PROVIDE CORNER SHEET TITLE
12" OC, 2 EA SIDE OF VAPOR
DRILLED PIER, BARS PER 3/S-010 TYP. FOUNDATION SECTIONS
(E) PIER CAP MIN. RETARDER TYP RE: SCHED
APPLY BOND
(E) PIER CAP NOT AT SIM
7/12/2018 12:03:04 PM

BREAKER TO ONE CONDITION Date:


GB, RE: PLAN & 1/2"
END, TYP. (E) PIER
12 JUL 2018
SCHED
PIER, RE: PLAN & SCHED
2' 1' 0 2'
SEQ. SHEET OF

EXISTING COLUMN SECTION AT PREP AREA SECTION AT PREP AREA


10 SCALE: 3/4" = 1'-0"
11 SCALE: 3/4" = 1'-0" 12 SCALE: 3/4" = 1'-0"
SCALE: 3/4" = 1'-0"

S-502
ROOFING, RE: ARCH GRID
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018 6"
1/4" BENT PL BTWN JOISTS
AA METAL ROOF DECK, RE: PLAN GRID

REQD
6" TYP
@ PERIMETER, TYP 1/8 6"
TYP 1/4" CONT BENT PL
METAL ROOF DECK, EXTEND END OF 1/4"

REQD
RE: PLAN BENT PL FOR DECK BTWN JST @
PERIMETER, TYP METAL ROOF
SUPPORT WHERE REQD

SEAT, TYP
6"x6"x1/4" CONT BENT PL DECK, RE: PLAN

6" JST
AROUND PERIMETER, TYP DD
OKLAHOMA CITY, OK 73112 405.416.8100

UNO

Date Appr
TOP OF STEEL TOP OF STEEL TOP OF STEEL
114'-3" 114'-3" 114'-3"

6" JST SEAT


1" MIN
C.H. GUERNSEY & COMPANY

TYP OPEN WEB STEEL JOIST

TYP
1" MIN
RE: ROOF FRAMING PLAN
TYP
5555 N. GRAND BLVD.

TYP JST CONN GRID


6

Description
TYPE 'R' TOP CHORD JOIST SUBSTITUTE WITH
EXTENSION, TYP 1/8
EXTENDED END, TYP SHEAR TAB CONN TYP,
3/16 2 @ 12 RE: S-603
STAGGER, TYP L2x2x1/4 BOTTOM FLANGE BRACE TYP
1/4 WF BM, RE: ROOF
3/16 2 @ 12 TO EA JOIST. ATTACH TO JST FOR INFO NOT FRAMING PLAN, TYP HSS COL, RE:
PANEL PT TYP NOTED, RE: 1/S-521 FRAMING PLAN GRID
WF BEAM, RE: ROOF FRAMING PLAN
8

Symbol
CONN, RE: S-603 TYP EAVE EAVE EAVE FRAMING, RE:
112'-0" 112'-0" 112'-0" S-521 FRAMING PLAN TYP
L8x6x7/16xCONT (LLV) TYP FOR WALL
1/4 2@12 STUD ATTACHMENT, RE: 2/S-012
STAGGER
WELDS WF BM, RE: FRAMING PLAN TYP
1/4 2@12 CFS STUD, RE: 1/S-012

Appr
WF COL, RE: FDN PLAN TYP
3'-5" 3'-7" 3'-5"

Date

REVISIONS
TYPICAL DETAIL AT EAVE SECTION AT MOMENT FRAME FRAMING SECTION PLAN AT HIP APEX
1 SCALE: 1" = 1'-0" 2 SCALE: 1" = 1'-0" 3 SCALE: 1" = 1'-0" 4 SCALE: 1" = 1'-0"

Description
DD

JST SUB (CHANNEL AT SIM


GRID GRID GRID CONT LT GA BENT PL @ RIDGE TYP

Symbol
CONDITION), RE: PLAN
1/8 3" MIN

6" JST SEAT


3/8"x9"xCONT BRG PL

TYP
SIM
JST SUB W/
HIP BEAM, RE: PLAN
9 SEAT AS REQD
S-521
PERIMETER BM, 2'-0"x8"x1/4" BRG PL
RE: PLAN IN
1'-0" M T/ STL EL
(2) 1/4"xREQD CONT PL W/ RIDGE BENT PL TYP
SHEAR TAB CONN (VALLEY BENT PL AT SIM CONDITION) 121'-2 1/4"
TYP, RE: S-603
GRID

B. McCOMBS
M.MAURICIO

M.MAURICIO
GRID
3

W. McCANN

Submitted by:
Reviewed by:
Designed by:

Drawn by:
2'-0"x8"x1/4" BRG PL TOP OF STEEL
PERIMETER BM, RE:
114'-3"
PLAN

1/4 2@12
STAGGERED
1/4 2@12
SHEAR TAB CONN, RE: S-603
L3x3x1/4x1'-0" EA SIDE OF

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


HSS COL
GRID BEAM, RE: FRAMING PLAN
RIDGE SECTION
TYP
1/4 COL, RE: FDN PLAN
8 SCALE: 1" = 1'-0"
(2) 3"xREQD BENT PL, BACK-TO-BACK (LLV), FOR
FOR INFO NOT
DECK SUPPORT EAVE
NOTED, RE: 5/S-521
JST SUB (CHANNEL AT SIM
112'-0"
CONDITION), RE: PLAN RE: ARCH FOR SOFFIT FRAMING TYP

17th TRAINING WING


NATURE OF WORK:
METAL DECK, RE: FRAMING PLAN (2) 1/4"xREQD CONT PL W/
RIDGE BENT PL, RE: 9/S-521
7 PERIMETER DECK ANGLE TYP (LINES DASHED FOR CLARITY)
S-521 7
SIM S-521 JST SUB W/ BRG SEATS AS
PLAN AT HIP PLAN AT TYPICAL VALLEY SECTION AT HIP REQD, RE: FRAMING PLAN
5 SCALE: 1" = 1'-0" 6 SCALE: 1" = 1'-0" 7 SCALE: 1" = 1'-0"

2'-0"x8"x1/4" BRG PL TOP OF STEEL


114'-3"
C:\Work\R18_70374-000_S_mmauricio.rvt

1/4
WF BM, COPE FLANGES AS REQD EA FLANGE
GRID HIP BM, RE: FRAMING PLAN 1/4
CONT LT GA RIDGE PL CONT LT GA VALLEY PL BENT PL 1/4"x6"x6"xCONT
BY DECK MFR TYP BY DECK MFR TYP AT VALLEY TYP 10A BEAM/COLUMN GRID
11 GRID S-521 CONNECTIONS 1/2" FLANGE PL, RE: 10/S-521 1/4
BRG PL TO

PROJECT TITLE
BENT PL 1/4"x6"x6"xCONT 1/4 1@6 S-521 BM/COL
1/4" BRG PL TO MOMENT FRAME COL W/ 1/4
AT HIP/RIDGE TYP ANGLES

1 1 YP
1/4 1@6 3/8" CAP PL, RE: FDN PLAN

/2"
T
5"
WF BM, RE: ROOF HIP SECTION AT

1 1/2"
TYP
JST SUB FRAMING PLAN TYP
1/4 1@6
1/4" BRG PL TO FRAMING MOMENT FRAME
TOP OF STEEL
1/4 1@6 ANGLES ABOVE
JST SUB FRAMING
ABOVE, RE: ROOF
FRAMING PLAN TYP
11 SCALE: 1" = 1'-0"
114'-3"
VARIES

Project Number:
1'-6"x1'-0"x1/2" PL
GRID GRID
TYP TYP OK70374-000
3/16 2@12 3/16 2@12 1/4
L3x3x1/4 SLOPED, L3x3x1/4 SLOPED, PL TO COL SHEET TITLE
EA SIDE OF COL EA SIDE OF COL 1/4
SHEAR PL CONN PER ROOF FRAMING DETAILS
WF COL, RE: FDN PLAN SCHED TYP EXCEPT
HSS COL, RE: FDN PLAN HSS COL, RE: FDN PLAN AS NOTED, RE: S-603
1/4" PL ABOVE FOR SUPPORT
7/12/2018 12:03:05 PM

Date:
OF DECK SUPPORT ANGLES 12 JUL 2018
MOMENT FRAME BM BENT PL FOR DECK SUPPORT
10A CONNECTION
7
SIM CONDITION @ VALLEY 1' 0' 1' 2'
S-521 SEQ. SHEET OF

SCALE: 1" = 1'-0"

HIP/RIDGE SECTION HIP PLAN AT MOMENT FRAME S-521


9 SCALE: 1" = 1'-0" 10 SCALE: 1" = 1'-0"
1/4 POST POST GRID
5
TYP
1/4 FRAMING, RE: FRAMING
PLAN TYP CONT LT GA RIDGE
2" PLATE BY DECK MFR
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
METAL DECK BENT PL 1/4"x6"x6"XCONT
AT RIDGE TYP

1"
ROOF
124'-0"
OKLAHOMA CITY, OK 73112 405.416.8100

T/ STL EL =

Date Appr
118'-10 1/2"
C.H. GUERNSEY & COMPANY

PL 1/4"xREQDxCONT
AT RIDGE TYP
1/4 2@12
BM, RE: FRAMING PLAN
5555 N. GRAND BLVD.

Description
1
2'-0"x8"x1/2" BRG PL SHEAR TAB CONN, RE:
S-522
S-603 TYP

TYP DECK SUPPORT AT RIDGE


2

Symbol
METAL DECK, RE: FRAMING PLAN HSS POST, RE: FRAMING
CC PLAN
2 SCALE: 1" = 1'-0"
FRAMING, RE: FRAMING PLAN TYP POST
S-522
18'-10 1/2"
1/4" BENT PL AT RIDGE TYP

Appr
Date
GRID
3

REVISIONS
CHANNEL, RE: FRAMING PLAN. COPE
BOTTOM END AND EXTEND TO EDGE OF

Description
ROOF, TYP. ATTACH TO BEAM EA END WITH
L3x3x1/4x0'-6" W/ (2) 3/4" DIA A325 BOLTS, TYP

METAL ROOF DECK, RE: PLAN

6"x6"x1/4" CONT BENT PL


AROUND PERIMETER, TYP

Symbol
1/4 T/ STL EL
TYP 120'-6"
1/4 1'-0
"
TYP

TYP
1/4 COPED 1/4
POST CHANNEL

B. McCOMBS
T/ STL WF BEAM, RE:

Submitted by:
Reviewed by:
Designed by:
Designer
FRAMING PLAN

Checker
115'-10"

Drawn by:
Author
L3x3x1/4 ALONG

MIN
3"
L2x2x1/4 EXTENSION COPED CHANNEL
ALONG COPED END
OF CHANNEL

TYP
1/4
1/4 1@12 CONN TO
3'-4" STAGGER WELDS BM BEYOND
TOP OF STEEL 1/4 1@12

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


114'-3"

TYPE 6 CONN,
RE: S-603
3/8" STIFFENER EA SIDE OF BM TYP
TOWER ROOF FRAMING COPED CHANNEL
3 SCALE: 1" = 1'-0" 3A SCALE: 3" = 1'-0"

17th TRAINING WING


NATURE OF WORK:
2'-1 1/2" 5'-10 1/2" 15'-6" 1'-2"
3

UPPER RIDGE SECTION NEW HSS5.000x0.500 POST W/


1 SCALE: 1" = 1'-0"
LT GA RODGE PLATE BY DECK MFR 8"x8"x1/2" BASE PL ATTACHED
TO (E) COL BELOW
PROVIDE 1/4" PLATE AT APEX FOR 3
DECK SUPPORT AND ATTACHMENT
1/4
1'-0" 5"
6" T/ (E) STL EL
VIF
1/4
5 ROOF
124'-0" TOP OF STEEL
S-522
C:\Work\R18_70374-000_S_mmauricio.rvt

1/4
114'-3"
METAL DECK, RE: FRAMING
PLAN NOTES
(E) COL TO CAP PL

PROJECT TITLE
1/4
TOP OF STEEL
114'-3"
(E) WF BM (E) WF COL

HSS POST ROOF BEAMS, RE:


HIGH ROOF
6"x6"x1/4"xCONT BENT PL
FRAMING PLAN TYP 9 FOR DECK ATTACHMENT
HSS POST, RE: S-121
FRAMING PLAN 1/4
WF BM, RE: FRAMING PLAN 3/8" BENT CAP PL
EXIST COLUMN MODIFICATION Project Number:

7"x6"x1/2" PL
CONN, RE: S-603 HSS COL, RE: FDN PLAN (2) 3"xREQD BENT PL, BACK-TO-
7 SCALE: 1" = 1'-0" OK70374-000
CONN PER SCHED ON BACK (LLV), FOR DECK SUPPORT SHEET TITLE
SHT S-603 TYP 3/16
SUPPORT BEAMS EAVE ROOF FRAMING DETAILS
BELOW TYP, RE: T/ STL EL 112'-0"
HIGH ROOF 120'-5"
7/12/2018 12:03:06 PM

FRAMING PLAN Date:


12 JUL 2018

SEQ. SHEET OF
SUPPORT BEAMS, RE:
FRAMING PLAN TYP

TOWER APEX CONNECTION TOWER ROOF SUPPORT ROOF/TOWER INTERSECTION S-522


4 SCALE: 1" = 1'-0" 5 SCALE: 1" = 1'-0" 6 SCALE: 1" = 1'-0"
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

RE: 2/S-523 FOR PLAN VIEW OF


JOIST BEARING CONDITION
OKLAHOMA CITY, OK 73112 405.416.8100

Date Appr
C.H. GUERNSEY & COMPANY
5555 N. GRAND BLVD.

EXTEND AND COPE

Description
ENDS OF CANTILEVERED
BEAMS, RE: 2/S-523. NOT
GRAPHICALLY SHOWN
STEEL JOIST, RE:
ROOF FRAMING PLAN

CANTILEVERED BEAM TYP, CONN, RE: S-603 TYP


RE: ROOF FRAMING PLAN
1'-0"x8"x1/4" BRG PL FOR

Symbol
JST ATTACHMENT

Appr
TYP @ JST SEAT
1/8 3" MIN TYP @ EA BM
3/16 4" MIN

Date
HSS POST TYP, RE: ROOF FRAMING PLAN
TYP
1/4

REVISIONS
WF SUPPORT BM, RE: ROOF FRAMING PLAN
CANTILEVERED WF BM TYP,
TOP OF STEEL RE: ROOF FRAMING PLAN

Description
114'-3"

2
STEEL JST, RE: ROOF FRAMING PLAN

Symbol
ROOF FRAMING AT PREP AREA JOIST BEARING AT CANTILEVERED BEAMS
1 SCALE: 1" = 1'-0" 2 SCALE: 1" = 1'-0"

B. McCOMBS
Submitted by:
Reviewed by:
Designed by:
Designer

Checker
Drawn by:
Author
CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


17th TRAINING WING
NATURE OF WORK:
C:\Work\R18_70374-000_S_mmauricio.rvt

PROJECT TITLE
Project Number:

OK70374-000

SHEET TITLE

ROOF FRAMING DETAILS


7/12/2018 12:03:06 PM

Date:
12 JUL 2018

1' 0' 1' 2'


SEQ. SHEET OF

SCALE: 1" = 1'-0"

S-523
DRILLED PIER SCHEDULE PIER CAP SCHEDULE
VERT BOT BARS TOP BARS
MARK Dp (IN) VERT REINF TIES MINIMUM EMBEDMENT NOTES MARK TYPE A B TIES REINF LAYOUT REMARKS
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018 REINF LW TR LW TR
DP2.0 24 (6) #6 #4 @ 12" OC 2'-0" -
PC1 1 2'-0" 2'-0" #3 @ 10" OC (12) #5 - - - - -
DP2.5 30 (9) #6 #4 @ 12" OC 2'-0" -
PC2 4 2'-8" 2'-0" #3 @ 10" OC (14) #5 - - - - -
DP3.0 36 (12) #6 #4 @ 12" OC 2'-0" -
PC3 5 3'-9" 2'-0" #3 @ 10" OC (18) #5 - - - - -
DP3.5 42 (16) #6 #4 @ 12" OC 2'-0" -
OKLAHOMA CITY, OK 73112 405.416.8100

NOTES: PC4 6 2'-0" 4'-6" - - (3) #5 #3 TIES (3) #5 #3 TIES - #3 TIES SPACED AT 10" OC

Date Appr
1. RE: PLANS FOR PIER MARK. DOWELS TO EXTEND INTO
2. SEE SPECIFICATIONS FOR CONSTRUCTION TOLERANCES. GRADE BEAM OR PIER CAP. DOWEL
TO MATCH NUMBER AND SIZE OF PC5 3 2'-2" 2'-2" #3 @ 10" OC (12) #5 - - - - -
3. BEARING SURFACE SHALL BE LEVEL AND FREE OF LOOSE MATERIAL.
VERTICAL PIER REINF, SEE NOTE 4.
C.H. GUERNSEY & COMPANY

4. EXTEND STRAIGHT DOWELS TO WITHIN 3" OF TOP OF GRADE BEAM/PIER

ld
CAP. DOWELS THAT CANNOT MEET THE DEVELOPMENT LENGTH
NOTED IN THE LAP SPLICE SCHEDULE SHALL HAVE ACI STD HOOKED PC6 3 4'-0" 4'-0" #3 @ 10" OC (28) #6 - - - - -
ENDS. T/DP
5555 N. GRAND BLVD.

5. PIER VERT REINFORCING SHALL EXTEND DOWN A MIN OF 30' FROM TOP

Description
OF PIER, UNLESS PIER LENGTH IS SHORTER THAN THAT LENGTH DUE RE: PLAN PC7 7 2'-8" 2'-8" #3 @ 10" OC (18) #5 - - - - -

5" TYP
TO REQUIRED BEARING DEPTH, IN WHICH CASE THE PIER SHALL BE
REINFORCED FULL DEPTH. REINFORCING IS NOT REQ'D BEYOND THE
30' DEPTH FROM TOP OF PIER. PC8 2 2'-0" 2'-0" #3 @ 10" OC (12) #5 - - - - -

ld
6. ALL PIERS SHALL BEAR INTO THE "CLAYEY SAND" LAYER FOUND
APPROXIMATELY 20 FEET BELOW EXISTING GRADE. MINIMUM
EMBEDMENT INTO "CLAYEY SAND" LAYER IS AS NOTED IN SCHEDULE.
PLACE (3) TIES PC9 3 4'-0" 4'-0" #3 @ 10" OC (28) #6 - - - - -

Symbol
IN TOP 5" OF PIER

PC10 8 2'-0" 2'-0" #3 @ 10" OC (12) #5 - - - - -


3" CLR
TYP

Appr
3" CLR VERT REINF
NOTES:
TYP 48 BAR DIA. LAP 1. LW = LENGTHWISE, TR = TRANSVERSE

Date
2. WHERE PIER IS INTEGRAL WITH A GRADE BEAM(S), RUN HORIZONTAL GRADE BEAM REINFORCING CONTINOUS THROUGH PIER.
TEMP CASING 3. DEPTH OF PIER CAP SHALL BE THE DIFFERENCE BETWEEN THE T/ PC ELEVATION AND T/ PIER ELEVATION.
IF REQ'D

REVISIONS
4. PROVIDE 3 SETS OF TIES IN TOP 5" OF PIERS, TYP.
5. CHAMFER EXPOSED EXTERIOR CORNERS, TYP.
6. MAINTAIN 2 INCH CONCRETE CLEAR COVER ON ALL SIDES OF PIER CAPS.

Description
GRID
CIRCULAR TIES
CIRCULAR TIES
GRID GRID
A
GRID
EQ EQ

Symbol
A A A
GB BELOW, TYP
EQ EQ (LOCATION VARIES)
GB BELOW, TYP GB BELOW EXT WALL, TYP
PLAN GB BELOW, TYP DP BELOW DP BELOW
TOP OF "CLAYEY SAND" DP BELOW (LOCATION VERIES)
LAYER

EQ

B
B
5
GRID GRID

B
GRID

B
GRID

11"
EQ
11"

11"

B. McCOMBS
M.MAURICIO

M.MAURICIO

W. McCANN

Submitted by:
Reviewed by:
Designed by:
5" 8"

Drawn by:
EMBEDMENT

DP BELOW
PER SCHED

11" EXT WALL COLUMN TYPE VARIES


END BEARING IN EXT WALL, TYP
APPROVED
"CLAYEY SAND"
LAYER

PIER CAP TYPE 1 PIER CAP TYPE 2 PIER CAP TYPE 3 PIER CAP TYPE 4
1 NOT TO SCALE 2 NOT TO SCALE 3 NOT TO SCALE 4 NOT TO SCALE

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


12" MAX
3" MIN

DIAMETER
ELEVATION
Dp

GRID GRID A
GRID AA

17th TRAINING WING


11"

NATURE OF WORK:
A
A A
1'-2" 1'-7"
1'-2" 1'-1"

1'-0"
GB BELOW
(E) BLDG
GB BELOW, TYP EXT WALL
DP BELOW

2'-0"

EQ

EQ
B

B
3
GRID 1 GRID 5
1'-1"

8"

B
PIER

EQ
EQ
1'-0"
C:\Work\R18_70374-000_S_mmauricio.rvt

EXT WALL DP BELOW DP BELOW


GB BELOW DP BELOW
DP & PC TYP EXT WALL GB BELOW
GB BELOW

PROJECT TITLE
PIER CAP TYPE 5 PIER CAP TYPE 6 PIER CAP TYPE 7 PIER CAP TYPE 8
5 NOT TO SCALE 6 NOT TO SCALE 7 NOT TO SCALE 8 NOT TO SCALE

Project Number:

OK70374-000

SHEET TITLE

SCHEDULES
7/12/2018 12:03:06 PM

Date:
12 JUL 2018

SEQ. SHEET OF

S-601
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019 CL SUPPORT CL SUPPORT
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
CANTILEVER SPAN LC SPAN L1 SPAN L2
END SPAN INTERIOR SPAN

'E1' BARS #5 STIRRUP SUPPORT 'T1' BARS


BARS AS REQUIRED STIRRUPS "T" OR "E" BARS
EXTEND 'E' BARS INTO L1/4 LARGER OF L1/3 LARGER OF L1/3 (OUTER LAYER)
CANTILEVER AND L2/3 AND L2/3
OKLAHOMA CITY, OK 73112 405.416.8100

STD ACI
HOOK

Date Appr
1'-0"
DEPTH "D"

DEPTH "D"
SPLICE TYP
#4 @12" O.C. FOR
C.H. GUERNSEY & COMPANY

BEAMS THAT EXCEED


36" IN DEPTH
5555 N. GRAND BLVD.

2" CLR.

Description
"B" BARS

CLR
(OUTER

CLR

3"
3"
PROVIDE STIRRUPS SAME LAYER)
'B2' BARS 6" 'B1' BARS SHALL BE CONTINUOUS OR
AS IN BACKSPAN
3" S TYP TENSION B LAP SPLICED AT SUPPORT WIDTH "W"
EXTEND 'B' BARS INTO CANTILEVER TYP 'B1' BARS
TYP
'B1' BARS TO TERMINATE STIRRUPS
WITH STD HOOK
GRADE BEAM SCHEDULE

Symbol
PIER
'S1' 'S2' 'S1' RE: PLAN & SCHED
DOWELS W/ STD HOOK AT TOP WIDTH "W" DEPTH "D" END BARS TOP BARS BOT BARS STIRRUPS
INSTALL FULLY DEVELOPED INTO PIER L1/3 L1/3 L1/3 MARK TYPE REMARKS
(IN) (IN) E1 E2 T1 T2 B1 B2 SIZE S1 (IN) S2 (IN) TYPE
GB1 1 16 30 (2) #6 (2) #6 (3) #5 #3 13 18

Appr
TYPE 1: NON-PERIMETER BEAM GB2 1 16 30 (3) #7 (3) #7 (3) #7 #3 13 18
GB3 1 16 30 (3) #7 (3) #7 (3) #5 #3 13 18

Date
GB4 1 16 30 (2) #6 (2) #6 (2) #5 #3 13 18

REVISIONS
CL SUPPORT CL SUPPORT GB5 2 12 30 (2) #5 (2) #5 (2) #5 #3 13 18
GB6 2 12 30 (2) #6 (2) #6 (2) #6 #3 13 18
CANTILEVER SPAN LC SPAN L1 SPAN L2

Description
END SPAN INTERIOR SPAN NOTES:
'T1' BARS TO BE CONTINUOUS OR
CLASS B TENSION SPLICE AT MIDSPAN 'T1' BARS 1. PLACE 'T' BARS AT INTERIOR SUPPORTS OF GRADE BEAM. PLACE 'E' BARS @ END SUPPORT OF END SPAN, OR BOTH ENDS OF
SINGLE SPAN GRADE BEAMS.
'E2' BARS 'E1' BARS 'T2' BARS 2. SPLICE BOTTOM REINF AT SUPPORT AND TOP REINF AT MIDSPAN AS SHOWN.
STIRRUPS, ALTERNATE 135 AND 90 3. WHERE TWO LAYERS OF REINFORCING ARE INDICATED, PROVIDE A CLEAR DISTANCE EQUAL TO THE BAR DIAMETER BETWEEN
1/2 L1 1/2 L1 1/2 L2 LAYERS, HOWEVER CLEAR DISTANCE SHALL NOT BE LESS THAN 1".
EXTEND 'E' BARS DEG HOOKS
4. ALL GRADE BEAMS SHALL BE PLACED ON 6" VOID FORMS W/ RETAINER BOARDS ON BOTH SIDES.
INTO CANTILEVER L1/4 LARGER OF L1/3 LARGER OF L1/3 "T" OR "E" BARS 5. DRILLED PIER REINF NOT SHOWN FOR CLARITY. RE SCHEDULE ON S-601.

Symbol
AND L2/3 AND L2/3
STD ACI
HOOK

CLR
1 1/2" CLR.

1"
DEPTH "D"

DEPTH "D"
#4 @12" O.C. FOR
BEAMS THAT EXCEED
36" IN DEPTH

1"
2" CLR.

B. McCOMBS
M.MAURICIO

M.MAURICIO
"B" BARS

W. McCANN

Submitted by:
Reviewed by:
Designed by:
CLR
CLR

3"
3"
'B2' BARS

Drawn by:
PROVIDE STIRRUPS 6" 'B1' BARS SHALL BE CONTINUOUS OR
SAME AS IN BACKSPAN 3" S 'B1' BARS TYP TENSION B LAP SPLICED AT SUPPORT WIDTH "W"
EXTEND 'B' BARS INTO TYP TYP STIRRUPS
CANTILEVER PIER, RE: PLAN & SCHED
'B1' BARS TO TERMINATE 'S1' 'S2' 'S1'
WITH STD HOOK Ln/3 Ln/3 Ln/3
DOWELS Ln

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


TYPE 2: PERIMETER BEAM

CONCRETE BEAM SCHEDULE


1 SCALE: 3/4" = 1'-0"

17th TRAINING WING


NATURE OF WORK:
C:\Work\R18_70374-000_S_mmauricio.rvt

PROJECT TITLE
Project Number:

OK70374-000

SHEET TITLE

SCHEDULES
7/12/2018 12:03:06 PM

Date:
12 JUL 2018

SEQ. SHEET OF

S-602
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
TYPICAL SIMPLE STEEL CONNECTION SCHEDULE STEEL COLUMN BASE PLATE SCHEDULE
N (# ROWS WEB ANCHOR
BEAM SIZE TYPE 1, 2 CONNECTOR TYPE 3 CONNECTOR TYPE 4, 5 CONNECTOR OF BOLTS) BOLT TYPE WELD SIZE STIFFENER BASE PLATE DIMENSIONS RODS
W8 L4X4X7/16 SLO LL4X4X7/16 SLO SHEAR PLATE 3/8" 2 3/4" DIA A325 1/4" 3/8" MARK COLUMN SIZE TYPE T a b c d DIA Hef REMARKS
W10 L4X3 1/2X5/16 SLO LL4X3 1/2X5/16 SLO SHEAR PLATE 3/8" 2 3/4" DIA A325 1/4" 3/8" BP1 W16x57 2 3/4" 8" 1'-6" 5 1/2" 1 1/2" 7/8" 12"
W12, W14 L4X3 1/2X5/16 SLO LL4X3 1/2X5/16 SLO SHEAR PLATE 3/8" 3 3/4" DIA A325 1/4" 3/8" BP2 W16x57 2 3/4" 8" 1'-6" 5 1/2" 1 1/2" 3/4" 9"
W16, W18 L4X3 1/2X5/16 SLO LL4X3 1/2X5/16 SLO SHEAR PLATE 3/8" 4 3/4" DIA A325 1/4" 3/8" BP3 W14x53 2 3/4" 9" 1'-3" 4" 2" 3/4" 9"
BP4 HSS5x0.500 1 3/4" 9" 9" - - 3/4" 9"
OKLAHOMA CITY, OK 73112 405.416.8100

NOTES:
1. SEE FRAMING PLANS FOR BEAM AND/OR POST SIZES AND FOUNDATION PLAN FOR COLUMNS SIZES. BP5 HSS5x0.500 1 3/4" 9" 9" - - 3/4" 9"
BP6 W18x65 2 3/4" 8" 1'-7" 6" 1 1/2" 3/4" 9"

Date Appr
2. ALL BOLTS SHALL BE HEAVY HEX BOLTS AND SHALL ONLY BE TIGHTENED TO THE SNUG TIGHT UNO.
3. DECK AND JOIST NOT SHOWN. BP7 HSS5x0.500 3 3/4" 9" 1'-0" 4" 3" 3/4" 9"
4. BEAM MAY OCCUR HIGHER FOR DECK BEARING, COORD W/ PLAN. BP8 HSS5x0.500 4 3/4" 9 1/2" 9 1/2" 4" 4" 3/4" 9"
5. FOR SHEAR TABS WELDED TO HSS COLUMNS W/ 3/16" WALLS, USE 5/16" SHEAR PLATES.
C.H. GUERNSEY & COMPANY

BP9 HSS5x0.500 5 3/4" 11 1/2" 11 1/2" 4" 4" 3/4" 9"


6. SHEAR PLATE CAN BE PROVIDED W/ HORIZONTAL SHORT SLOTTED HOLES AT CONTRACTOR'S OPTION, UNO.
7. CONNECTOR TYPE 6 IS AS NOTED IN DETAIL BELOW. BP10 HSS5x0.500 6 3/4" 9 1/2" 11 1/2" 4" 4" 3/4" 9"
NOTES:
5555 N. GRAND BLVD.

1. ALL BASE PLATES SHALL BE A36 STEEL, TYP, UNO.

Description
1/2" 2. ALL BASE PLATES SHALL BEAR ON 2" THICK 5000 PSI NON-SHRINK GROUT AND SHALL HAVE LEVELING NUTS, TYP, UNO.
SEE NOTE 4 1/2"
3. ALL BASE PLATES SHALL BE WELDED TO THE COLUMN WITH A 1/4" FILLET WELD ALL AROUND, TYP, UNO.
4. ALL ANCHOR RODS SHALL BE DIAMETER NOTED IN SCHEDULE, ASTM F1554 GR 36. THEY SHALL BE HEADED ANCHOR RODS
COL WEB STEEL COL OR SHALL HAVE A HEAVY HEX NUT AT THE BASE, TYP, UNO. ALL ANCHOR RODS SHALL HAVE HARDENED WASHERS AND
TYP

NUTS, WITH FULL HEIGHT OF EXTENSIONS THREADED. WASHERS SHALL CONFORM TO AISC STEEL CONSTRUCTION MANUAL
3"

TABLE 14-2.
5. ALL ANCHOR RODS SHALL BE SET IN PLACE WITH A TEMPLATE. THEY SHALL BE PLACED PLUMB AND AT THE CORRECT DEPTH

TYP
3"
TYP
3"
AND EXTENSION.

Symbol
6. ALL ANCHOR ROD HOLES IN BASE PLATES SHALL BE OVERSIZED PER AISC. COL
7. SEE THE STRUCTURAL GENERAL NOTES FOR ADDITIONAL INFORMATION.
8. FOR BASE PLATES ON BRACE FRAME COLUMNS, NO GROUT PAD SHALL BE USED. EQ EQ
SINGLE ANGLE PER
SCHED, TYP (NOTE 2).

Appr
SINGLE ANGLE PER DOUBLE ANGLES
1/2"
SCHED, TYP (NOTE PER SCHED, TYP
2" 2). (NOTE 2).

Date
TYP
1 1/2" 1/4
TYP
BEAM TO COLUMN BEAM TO COLUMN TYP 1/4

REVISIONS
EQ
BEAM TO GIRDER WEAK AXIS STRONG AXIS COL

b
EQ
1 2 3

Description
ANCHOR
ROD TYP

TYP
ANCHOR

c
COL COL COL

b
1 1/2"
2" ROD TYP

TYP
1 1/2" M
TYP TYP
3/8" WEB STIFFENER BOTH STEEL COL
1/2"
SIDES OF BEAM WEB
d

Symbol
1 1/2"
TYP

TYP
STEEL COL 1/4
STEEL BEAM a a

TYP
WF COL

3"
RE: PLAN BASE PLATE DETAIL BASE PLATE DETAIL
SHEAR TAB AND 1 2
TYP
3"

BOLTS PER SCHED

INSIDE FACE OF BRICK LEDGE


1 1/2"
TYP

WF BEAM, RE: PLAN


2" CAP PL 11"x3/4"xREQD 1/4 INSIDE FACE OF BRICK LEDGE

B. McCOMBS
COL

M.MAURICIO

M.MAURICIO
W/ (4) 3/4" DIA A325 1 1/2"

W. McCANN

Submitted by:
COL

Reviewed by:
Designed by:
SEE TYP M BOLTS 1/4 1/4

Drawn by:
SCHED 1 1/2"
STEEL POST TYP
ANCHOR c
ROD TYP

BEAM TO HSS COLUMN MOMENT CONNECTION HSS POST UP TO CANTILEVERED BEAM


4 5 6

1 1/2"
TYP
COL
TYP

b
1/4 COL

CRESSMAN DINING FACILITY EXPANSION


c

GOODFELLOW AIR FORCE BASE, TEXAS


d
1 1/2"
c TYP
1/4
d
a
a

BASE PLATE DETAIL BASE PLATE DETAIL

17th TRAINING WING


NATURE OF WORK:
3 4
INSIDE FACE OF BRICK LEDGE INSIDE FACE OF BRICK LEDGE

COL COL
1 1/2" c c 1 1/2"

1/4 0 1/4
TYP
1/4 0 1/4

b
C:\Work\R18_70374-000_S_mmauricio.rvt

COL COL

c
d

d
TYP TYP
1/4 1/4
d d

1 1/2"

1 1/2"

PROJECT TITLE
a a
AISC TABLE 14-2 MAXIMUM SIZES FOR ANCHOR-ROD
MISCELLANEOUS LOOSE LINTEL SCHEDULE FOR HOLES AND WASHER REQUIREMENTS

NON-LOAD BEARING MASONRY VENEERS ANCHOR BASE PLATE DETAIL BASE PLATE DETAIL
ROD MAX. HOLE MIN. MIN. 5 6
VENEER THK DIAMETER, DIAMETER, WASHER WASHER
4" VENEER 6" VENEER 8" VENEER 10" VENEER 12" VENEER in. in. SIZE, in. THICKNESS
MO SIZE
3/4 1 5/16 2 1/4 NUT & LEVELING
UP TO 4'-0 L4x3 1/2 x 5/16 WT4x10.5 LL4x4x5/16 L5x3 1/2x5/16 + L4x3 1/2x5/16 -
7/8 1 9/16 2 1/2 5/16 NUT TO MATCH Project Number:
4'-0 TO 6'-0 L5x3 1/2 x 5/16 WT7x11 LL5x5x5/16 L5x5x5/16 + L4x4x5/16 - 1 1 13/16 3 3/8 BOLTS
1 1/4 2 1/16 3 1/2 NON-SHRINK OK70374-000

T
6'-0 TO 8'-0 L6x3 1/2 x 5/16 LL6x6x5/16 L5x5x5/16 + L6x4x5/16 - 1 1/2 2 5/16 3 1/2 1/2 GROUT UNO
SHEET TITLE
8'-0 TO 12'-0 L6 x 6x 1/2 1 3/4 2 3/4 4 5/8
2 3 1/4 5 3/4 T/CONCRETE SCHEDULES
12'-0 TO 16'-0 L8 x 6 x 5/8 2 1/2 3 3/4 5 1/2 7/8

4 1/2" PROJ
TYP
2"
7/12/2018 12:03:07 PM

TYP
Hef
NOTES: Date:
1. RE: ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS FOR OPENING SIZE AND LOCATION. NOTES: 12 JUL 2018
2. CONNECT 2 ANGLES TO ALL 2 AND 3 ANGLE LINTELS BACK TO BACK AT 24" OC MAX. 1. WHEN BASE PLATES ARE LESS THAN 1 1/4" THICK,
3. ALL ANGLES LONG LEG VERTICAL, UNO. PUNCHING OF HOLES MAY BE AN ECONOMICAL
4. BEARING END OF STEEL LINTEL AT CONTROL JOINT SHALL BE WRAPPED WITH BUILDING PAPER. OPTION. IN THIS CASE, 3/4" ANCHOR RODS AND 1 HEAVY HEX NUT
5. PROVIDE MINIMUM 6" BEARING ON BRICK OR SOLID CONCRETE BLOCK. 1/16" DIAMETER PUNCHED HOLES MAY BE USED
WITH ASTM F844 (USS STANDARD) WASHERS IN SEQ. SHEET OF
6. PROVIDE MINIMUM 8" X WALL THICKNESS X 8" HIGH GROUTED CMU OR BRICK BEARING PAD UNDER ALL LINTELS, UNO.
GROUT JAMBS OF MASONRY OPENINGS 6'-0" AND LARGER FULL HEIGHT FOR 8" MINIMUM WIDTH. PLACE OF FABRICATED PLATE WASHERS. 1/4" MIN EXTENSION
7. CONNECT LINTEL TO COLUMN IF MASONRY OPENING IS ADJACENT TO COLUMN AND LINTEL HAS LESS THAN 8" BELOW NUT.
BEARING ON CMU BEYOND COLUMN FLANGES.
8. ANGLES IN EXTERIOR WALLS ARE TO BE GALVANIZED.
ANCHOR ROD DAMAGE THREADS
AFTER NUT IS
S-603
INSTALLED.
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019

ABBREVIATIONS GENERAL ARCHITECTURAL NOTES


C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

A FURR FURRED, FURRING PSI POUNDS PER SQ IN 1. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER IMMEDIATELY OF DISCREPANCIES IN THE DRAWINGS BETWEEN
@ AT FWC FABRIC WALL COVERING PT PAINT THE DRAWINGS AND THE SPECIFICATIONS, AND/OR BETWEEN THE CONSTRUCTION DOCUMENTS AND ACTUAL JOB CONDITIONS
WHICH AFFECT THE EXECUTION OF THE WORK AS INDICATED.
A/C AIR CONDITIONING PTD PAINTED
2. CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF ALL CONSTRUCTION WORK PERFORMED BY
AB ANCHOR BOLT G PTDD PAPER TOWEL DISPENSER / DISPOSAL
OKLAHOMA CITY, OK 73112 405.416.8100

SUBCONTRACTORS UNLESS NOTED OR INDICATED OTHERWISE.


ABI ADDITIVE BID ITEM GA GAUGE PTN PARTITION 3. CONTRACTOR SHALL LOCATE AND LAYOUT WALLS AND PARTITIONS AS THEY RELATE TO THE STRUCTURE AND OTHER BUILDING

Date Appr
ACT ACOUSTICAL CEILING TILE GALV GALVANIZED PVC POLYVINYL CHLORIDE ELEMENTS AS SHOWN IN THE CONSTRUCTION DOCUMENTS. CONFLICTS OR AREAS OF INTERPRETATION SHALL BE RESOLVED BY
ADJ ADJACENT, ADJUSTABLE GB GRAB BAR THE CONTRACTING OFFICER.
GL GLASS, GLAZING Q 4. THE CONTRACTOR SHALL PROVIDE CONCEALED FIRE-TREATED WOOD BLOCKING WHERE REQUIRED IN METAL STUD PARTITIONS
AFF ABOVE FINISH FLOOR
FOR THE PROPER ANCHORAGE OF WALL ATTACHED ITEMS SUCH AS GRAB BARS, TOILET ACCESSORIES, TACKBOARDS,
C.H. GUERNSEY & COMPANY

AFL ATHLETIC FLOORING GRT GROUT QT QUARRY TILE


MARKERBOARDS, SHELF BRACKETS AND SHELVING, MILLWORK, AND ALL OTHER WALL ATTACHED MATERIALS UNLESS NOTED OR
AGGR AGGREGATE GT GLASS TILE QZ QUARTZ MATERIAL OTHERWISE INDICATED.
ALT ALTERNATE GWB GYPSUM WALLBOARD 5. THE CONTRACTOR SHALL MAKE ALL EXTERIOR WALL/ROOF OR WALL/WALL TRANSITIONS WATERTIGHT AND AIRTIGHT WITH
5555 N. GRAND BLVD.

GYP GYPSUM R SEALANT, FLASHING, EXPANDABLE FOAM, AIR INFILTRATION BARRIER, ETC. TO MAINTAIN REQUIRED INSULATION VALUES AND

Description
ALUM, AL ALUMINUM
RA RETURN AIR MECHANICAL SYSTEM PERFORMANCE IN THE FACILITY UNLESS NOTED OR INDICATED OTHERWISE. NO GAPS, OPENINGS, OR
AP ACRYLIC PANEL PENETRATIONS IN THE EXTERIOR WALL OR ROOF ASSEMBLIES SHALL BE LEFT EXPOSED TO THE ELEMENTS.
H RAF RAISED ACCESS FLOORING
APPROX APPROXIMATE 6. CONTRACTOR SHALL VERIFY AND COORDINATE ALL DIMENSIONS DURING THE CONSTRUCTION LAYOUT OF THE WORK. THE
HB HOSE BIB RB RUBBER BASE FOLLOWING GUIDANCE APPLIES TO DIMENSIONS USED ON THE ARCHITECTURAL DRAWINGS:
APVD APPROVED
HC HANDICAPPED RD ROAD, ROOF DRAIN
ARCH ARCHITECT, ARCHITECTURAL A. THE CONTRACTOR SHALL USE DIMENSIONS INDICATED ON THE DRAWINGS.
HC HOLLOW CORE RECT RECTANGULAR B. THE CONTRACTOR SHALL NOT SCALE FROM THE DRAWINGS.
ATFP ANTI-TERRORISM FORCE PROTECTION
HDW HARDWARE REF, RE REFER, REFERENCE C. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER OF DISCREPANCIES IN DIMENSIONS SHOWN ON THE
ATTEN ATTENUATOR, ATTENUATION
HDWD HARDWOOD REINF REINFORCE, REINFORCED DRAWINGS IMMEDIATELY.

Symbol
AWP ACOUSTIC WALL PANEL
HM HOLLOW METAL REP REPRESENTATIVE D. ALL PLAN DIMENSIONS ARE TO THE STRUCTURAL GRID LINES OR TO THE CENTERLINE OF COLUMNS AND BEAMS, TO
THE CENTER OF METAL STUD WALLS, OR TO THE NOMINAL FACE OF MASONRY UNITS UNLESS NOTED OR INDICATED
B HMB HORIZONTAL METAL BLINDS REQD REQUIRED
OTHERWISE.
BB BASE BID HORIZ HORIZONTAL RFG ROOFING E. ALL PLAN DIMENSIONS ON EXTERIOR WALL ASSEMBLIES ARE FROM THE ACTUAL OUTSIDE FACE OF WALL TO THE

Appr
BD BOARD HPL HIGH PRESURE LAMINATE RFL RUBBER FLOORING ACTUAL INSIDE FACE OF METAL STUD UNLESS NOTED OR INDICATED OTHERWISE.
BITUM BITUMINOUS HT HEIGHT RH ROBE HOOK F. ALL MASONRY OPENING DIMENSIONS ARE INDICATED AS NOMINAL DIMENSIONS WHICH INCLUDE AN ALLOWANCE FOR
HTR HEATER RM ROOM + OR - 3/8" MORTAR JOINT UNLESS NOTED OR INDICATED OTHERWISE.

Date
BLDG BUILDING
BLKG BLOCKING HVAC HEATING, VENTILATING, AND RND ROUND
AIR CONDITIONING RS ROLLER SHADES
BM BEAM, BENCH MARK

REVISIONS
BOT, BTM BOTTOM RST RUBBER STAIR TREADS
I
BRG BEARING
ID INSIDE DIAMETER

Description
S
BRK BRICK
IN INCH S SIGNAGE
BSMT BASEMENT
INSUL INSULATION SB SPLASH BLOCK
INT INTERIOR SC SEALED CONCRETE
C
C TO C CENTER TO CENTER SCHED SCHEDULE
J
CAB CABINET SCN STAINED CONCRETE
JST JOIST
CBB CEMENTITIOUS BACKER BOARD SD SOAP DISPENSER

Symbol
JT JOINT
CC CONTRACTOR CONNECT SECT SECTION
CF CONTRACTOR FURNISHED SEQ SEQUENCE
L
CFMF COLD-FORMED METAL FRAMING SHT SHEET
LAM LAMINATE
CG CORNER GUARD SIM SIMILAR
LAV LAVATORY
CI CONTRACTOR INSTALLED SJ STUCCO JOINT, SAWN JOINT
LB POUND
CJ CONSTRUCTION CONTROL JOINT SMC SUSPENDED METAL CEILING
LBL LABEL
CL CENTER LINE SND SANITARY NAPKIN DISPENSER
LF LINEAL FEET
CLG CEILING SPECS CONTRACT SPECIFICATIONS
LN LINOLEUM
CLR CLEAR SQ SQUARE
LVR LOUVER
CMU CONCRETE MASONRY UNIT SS STAINLESS STEEL
LVT LUXURY VINYL TILE

B. McCOMBS
S. SPRAGUE
SSM SOLID SURFACE MATERIAL

J. MORGAN
S. SNYDER
CO CLEANOUT

Submitted by:
LWT LIGHTWEIGHT

Reviewed by:
Designed by:
COL COLUMN ST STAIN

Drawn by:
CONC CONCRETE M STD STANDARD
CONT CONTINUOUS MACH MACHINE STL STEEL
CPT CARPET MAINT MAINTENANCE STN NATURAL STONE
CR CONTRACTOR ROUGH-IN MATL MATERIAL STOR STORAGE
CT CERAMIC TILE MAX MAXIMUM STRUCT STRUCTURAL
MB MARKER BOARD SUSP SUSPENDED
D MBR MEMBER SWC SUSPENDED WOOD CEILING
DB DOUBLE

CRESSMAN DINING FACILITY EXPANSION


MC MEDICINE CABINET

GOODFELLOW AIR FORCE BASE, TEXAS


DEMO DEMOLITION, DEMOLISH T
MECH MECHANICAL
DF DRINKING FOUNTAIN T TREAD
MEZZ MEZZANINE
DIA DIAMETER TC TOWEL DISPENSER
MFR MANUFACTURE, MANUFACTURER
DIAG DIAGONAL TFMR TRANSFORMER
MH MANHOLE
DIM DIMENSION THK THICK
MIN MINIMUM
DN, DWN DOWN THRU THROUGH
MISC MISCELLANEOUS
DP DAMPPROOFING TOC TOP OF CONCRETE
MK MARK

17th TRAINING WING


NATURE OF WORK:
DR DOOR TOM TOP OF MASONRY
ML METAL LOCKER
DS DOWNSPOUT TOS TOP OF STEEL
MLDG MOLDING
DTL DETAIL TOW TOP OF WALL
MO MASONRY OPENING
DWG DRAWING TP TOILET PARTITION
MSNRY MASONRY
DWP DECORATIVE WALL PANEL TS FLOORING TRANSITION
MSP METAL SPLASH PAN
DWR DRAWER TT TILE TRIM
MT METAL THRESHOLD
TTD TOILET TISSUE DISPENSER
MTD MOUNTED
E TYP TYPICAL
MTL METAL
C:\Work\Projects\R18_70374-000_A_SSnyderOKC.rvt

EA EACH TZ TERRAZZO
MVBL MOVABLE
EF EXHAUST FAN
MWP MEMBRANE WEATHERPROOFING
EIFS EXTERIOR INSULATION & FINISH SYSTEM U
ELEC ELECTRICAL UGND UNDERGROUND
N
ELEV ELEVATION UL UNDERWRITERS LABORATORIES
NIC NOT IN CONTRACT
EPC EPOXY COATING UNO UNLESS NOTED OTHERWISE
NO NUMBER
EQ EQUAL UR URINAL
NOM NOMINAL
EQPT EQUIPMENT NPRN NEOPRENE
V
ES EMERGENCY SHOWER NTS NOT TO SCALE

PROJECT TITLE
VB VINYL BASE, VAPOR BARRIER
EW EYE WASH
VCT VINYL COMPOSITION TILE
EWC ELECTRIC WATER COOLER O
VERT VERTICAL
EXIST EXISTING OA OVERALL, OUTSIDE AIR
VF VINYL FLOORING
EXP EXPANSION, EXPOSED OC ON CENTER
VP VENT PIPE
EXP JT, EJ EXPANSION JOINT OD OUTSIDE DIAMETER
VTR VENT THROUGH ROOF
EXT EXTERIOR OPNG OPENING
VWC VINYL WALL COVERING
OPP OPPOSITE
F OVHD OVERHEAD
W
FD FLOOR DRAIN OZ OUNCE
W/ WITH (COMB. FORM) Project Number:
FDN FOUNDATION
W/O WITHOUT
FE FIRE EXTINGUISHER P OK70374-000
WB WOOD BASE
FEC FIRE EXTINGUISHER CABINET PART PARTIAL
WC WATER CLOSET SHEET TITLE
FF FINISH FLOOR PEMB PRE-ENGINEERED METAL BUILDING
WD WIDTH, WINDOW DIMENSION, WOOD
FH FIRE HYDRANT PL PLATE, PLASTIC ABBREVIATIONS & NOTES
WDW WINDOW
FHC FIRE HOSE CABINET PLAS PLASTIC
WF WOOD FLOORING
FHS FIRE HOSE STATION PLBG PLUMBING
7/12/2018 11:28:03 AM

WH WATER HEATER Date:


FIN FINISHED PLYWD PLYWOOD
WM WALK-OFF MAT 12 JUL 2018
FLR FLOOR PNL PANEL, PANELBOARD
WP WATERPROOF
FPRF FIREPROOF PREFAB PREFABRICATED
WR WASTE RECEPTACLE
FRP FIBER-REINFORCED PLASTIC PREFIN PREFINISHED
WS WEATHERSTRIPPING
FT FOOT, FEET PRJ PROJECTION SEQ. SHEET OF
WT WINDOW TILE
FTG FOOTING PROP PROPERTY

A-001
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
OKLAHOMA CITY, OK 73112 405.416.8100

ACCESSIBILITY NOTES

Date Appr
1. FLOOR SURFACE OPENINGS SHALL BE A SIZE THAT
DOES NOT PERMIT THE PASSAGE OF A 1/2 INCH
C.H. GUERNSEY & COMPANY

DIAMETER SPHERE. ELONGATED OPENINGS SHALL BE


PLACED SO THAT THE LONG DIMENSION IS
PERPENDICULAR TO THE DOMINANT DIRECTION OF
5555 N. GRAND BLVD.

TRAVEL.

Description
2. WALKS AND SIDEWALKS SHALL HAVE A CONTINUOUS
COMMON SURFACE NOT INTERRUPTED BY STEPS OR
BY ABRUPT CHANGES IN LEVEL EXCEEDING 1/2 INCH
AND SHALL BE A MINIMUM OF 48 INCHES IN WIDTH.
60" MIN 3. CHANGES IN LEVEL OF 1/4 INCH MAXIMUM IN HEIGHT
4" MAX SHALL BE PERMITTED VERTICALLY. CHANGES IN LEVEL
15" MIN 42" MIN GREATER THAN 1/4 INCH IN HEIGHT AND NOT MORE
THAN 1/2 INCH MAXIMUM SHALL BE BEVELED WITH A
SLOPE NOT STEEPER THAN 1:2. CHANGES IN LEVEL

Symbol
GREATER THAN 1/2 INCH IN HEIGHT SHALL BE RAMPED
WITH A RUNNING SLOPE NOT TO EXCEED 1:12.

59" MIN
4. SURFACES WITH A SLOPE OF LESS THAN 6 PERCENT

48" MIN
GRADIENT SHALL BE AT LEAST AS SLIP-RESISTANT AS
ø 5'-0"

Appr
THAT DESCRIBED AS A MEDIUM-SALTED FINISH.

80" MIN
SURFACES WITH A SLOPE OF 6 PERCENT OR GREATER
SHALL ALSO BE SLIP-RESISTANT.

48" MAX

46" MAX

Date
5. HANDLES, PULLS, LATCHES, LOCKS, AND OTHER

34" MAX
27" MIN
OPERABLE PARTS ON ACCESSIBLE DOORS SHALL

15" MAX
HAVE A SHAPE THAT IS EASY TO GRASP WITH ONE

REVISIONS
HAND AND DOES NOT REQUIRE TIGHT GRASPING,
PINCHING, OR TWISTING OF THE WRIST TO OPERATE.
10" - 24" OPERABLE DOOR PARTS SHALL BE 34 INCHES MINIMUM

Description
30" X 48" CLEAR FLOOR SPACE
BEYOND AREA OF DOOR SWING AND 48 INCHES MAXIMUM ABOVE FINISHED FLOOR.
6. DOOR HARDWARE SHALL BE OPERABLE FROM THE
PROTRUDING OBJECTS UNOBSTRUCTED FORWARD REACH UNOBSTRUCTED HIGH-SIDE REACH INSIDE WITHOUT THE USE OF A KEY, SPECIAL
WHEELCHAIR ACCESSIBLE RESTROOM ELEVATION ELEVATION ELEVATION KNOWLEDGE, OR EFFORT.
PLAN 7. THRESHOLDS AT DOORWAYS SHALL BE 1/2 INCH
MAXIMUM IN HEIGHT. RAISED THRESHOLDS AND
CHANGES IN LEVEL AT DOORWAYS SHALL COMPLY
WITH THE REQUIREMENTS FOR CURB RAMPS.

Symbol
8. SURFACE CROSS SLOPES SHALL NOT EXCEED 1/4 INCH
PER FOOT.
9. THE TOP OF ACCESSIBLE WATER CLOSET SEATS
SHALL BE WITHIN 17 TO 19 INCHES ABOVE FINISHED
FLOOR. FLUSH VALVES SHALL BE MOUNTED ON THE
WIDE SIDE OF TOILET AREA AND WITHIN 40 INCHES OF
THE FLOOR. THE FORCE REQUIRED TO ACTIVATE THE
CONTROLS SHALL NOT EXCEED 5 POUNDS.
10. HOT WATER AND DRAIN PIPES UNDER ACCESSIBLE

40" MAX ABOVE LAV/COUNTER TO REFLECTIVE SURFACE


LAVATORIES AND SINKS SHALL BE INSULATED OR
FLOOR-MOUNTED
48" MIN

OTHERWISE CONFIGURED TO PROTECT AGAINST


(IF APPLICABLE) CONTACT. NO SHARP OR ABRASIVE SURFACES OR

4'-10"

B. McCOMBS
12" MIN*

S. SPRAGUE
60" MIN

EDGES ARE PERMITTED.

J. MORGAN
3'-6"

S. SNYDER
35" MAX WITHOUT LAV/COUNTER

Submitted by:
Reviewed by:
Designed by:
11. FAUCET CONTROLS SHALL BE OPERABLE WITH ONE

Drawn by:
HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
18" MIN PINCHING, OR TWISTING OF THE WRIST. THE FORCE
REQUIRED TO ACTIVATE THE CONTROLS SHALL NOT

4'-0' MAX
EXCEED 5 POUNDS. LEVERS ARE ACCEPTABLE.

2'-0"

1'-5" MAX
17"-19"

1'-6"
(a) FRONT APPROACH, PULL SIDE (b) FRONT APPROACH, PUSH SIDE
1'-2"

1'-0"
*IF BOTH CLOSER AND LATCH ARE PROVIDED
F.F.

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


WALL-MOUNTED WALL-MOUNTED WALL-MOUNTED WALL-MOUNTED PARTITION AT PARTITION AT RECESSED-MOUNTED MIRROR
WATER CLOSET WATER CLOSET URINAL URINAL TOILET URINAL PAPER TOWEL DISPENSER (ACCESSIBLE)
60" MIN

54" MIN

(STANDARD) (ACCESSIBLE) (STANDARD) (ACCESSIBLE) OR HAND DRYER


(STANDARD/ACCESSIBLE)
36" MIN 42' MIN
39"-41"

17th TRAINING WING


NATURE OF WORK:
1'-6" MIN.
3'-0" MIN.
(c) HINGE APPROACH, PULL SIDE (d) HINGE APPROACH, PULL 2'-0" MIN 1'-0"
SIDE
54" MIN MIN.
12" MIN* DISPENSER
OUTLET

WALL

WALL
1'-0"
MAX 3'-6" MIN.

48" MAX

TO OPERABLE PART
18" MIN.
42" MIN**

48" MIN*

48" MAX
24" MIN
C:\Work\Projects\R18_70374-000_A_SSnyderOKC.rvt

39"-41"
16"-18"

TO TABLE

33"-36"

33"-36"
42" MAX

48" MAX
22" MIN 24" MIN

28"-34"
48" MAX
48" MAX

40" MIN
18" MIN

2'-6"

18" MIN.

18" MIN.

17"-19"
F.F.
DISPENSER
RECESSED/PARTITION RECESSED/PARTITION SANITARY NAPKIN SEAT COVER FOLDING SHELF BABY CHANGING OUTLET INSTALLATION INSTALLATION
(e) HINGE APPROACH, PUSH SIDE (f) LATCH APPROACH, PUSH SIDE MOUNTED TOILET MOUNTED SANITARY DISPENSER DISPENSER (ACCESSIBLE) STATION (ACCESSIBLE) (ACCESSIBLE)

PROJECT TITLE
*IF BOTH CLOSER AND LATCH ARE PROVIDED *54" MINIMUM IF CLOSER PROVIDED TISSUE DISPENSER NAPKIN DISPOSAL (ACCESSIBLE) (ACCESSIBLE) (ACCESSIBLE)
**48" MINIMUM IF BOTH CLOSER AND LATCH PROVIDED (ACCESSIBLE) (STANDARD/
ACCESSIBLE)

FIRE
EXTINGUISHER

6"
24" MIN
48" MIN*

F
I
R
E
E
X
4'-0" TOP OF LEVER
T
I
Project Number:
38" MIN. TO 43" MAX.

N
5'-0"

ACCESSIBLE

G
U
I NOTE: ALL MOUNTING DIMENSIONS

4'-0" MAX
48" MAX

S
STANDING

H
ARE TO BE FROM A FINISHED SURFACE.
44" MAX

E
OK70374-000
ACCESSIBLE

R
36" MAX

SHEET TITLE
(g) LATCH APPROACH, PULL SIDE
*54" MINIMUM IF CLOSER IS PROVIDED ADA STANDARDS
7/12/2018 11:28:04 AM

F.F. Date:
12 JUL 2018
DRINKING FOUNTAIN
SOAP DISPENSER COAT AND ROBE HOOKS FIRE EXTINGUISHER BRACKET FIRE EXTINGUISHER CABINET
(ACCESSIBLE) (FEB) (FEC)
SEQ. SHEET OF
2' 1' 0 2' 4' 2' 0 4'
CLEARANCE AT MANUAL SWINGING DOORS TOILET ACCESSORIES TYPICAL MOUNTING HEIGHTS
SCALE: 1/4" = 1'-0" SCALE: 1/2" = 1'-0" SCALE: 1/2" = 1'-0" SCALE: 1/4" = 1'-0" A-002
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

A B C D E F G
OKLAHOMA CITY, OK 73112 405.416.8100

Date Appr
KEY NOTES
C.H. GUERNSEY & COMPANY

13

1 WITHIN THIS HATCHED AREA REMOVE ALL FINISHES


5555 N. GRAND BLVD.

INCLUDING BUT NOT LIMITED TO FLOORING, CEILINGS, WALL


9 9

Description
BASE, AND WALL TILE. REMOVE WALL GYPSUM BOARD. WALL
STUDS TO REMAIN. REMOVE ALL LIGHT FIXTURES AND AIR
TERMINALS. HVAC DUCTWORK SHALL REMAIN.
8 8
2 REMOVE ALL ITEMS BACK TO THE EXTERIOR SHEATHING
INCLUDING BUT NOT LIMITED TO BRICK VENEER, INSULATION
CAVITY BOARD, BRICK TIES, EXCESS CAVITY MOTOR, AND
ELECTRICAL ITEMS.

Symbol
3 REMOVE ENTIRE WALL FULL HEIGHT.
4
4 REMOVE STAIRS, RAILINGS, RAMPS, AND EXTERIOR
CONCRETE. REFER DRAWING C-100 FOR ADDITIONAL SITE

Appr
DEMOLITION.
8
5 PROTECT EXISTING GLASS BLOCK WALL DURING

Date
CONSTRUCTION.
7 7

REVISIONS
6 EXISTING TILE AND MUD BED SHALL BE REMOVED. EXISTING
9 SLAB IS 1 1/8" RECESSED BELOW FINISH FLOOR. PREP FLOOR
2
2 AS REQUIRED FOR NEW TILE FINISH.

Description
3 7 REMOVE ROOF AS REQUIRED FOR NEW ROOF OVERBUILD.
6 6 HANG DUSTPROOF BARRIER BELOW EXISTING CEILING OVER
FOOD PREPARATION AREAS.

8 REMOVE MASONRY VENEER. STEEL COLUMN TO REMAIN.

11 9 REMOVE SOFFIT, LIGHTS, ETC. IN COVERED AREA WHICH

Symbol
WILL BE FUTURE INTERIOR OF THE NEW ADDITION.
5
10 REMOVE ROOF FASCIA AND SOFFIT FOR NEW ADDITION.

11 INSTALL TEMPORARY DUSTPROOF BARRIER.

12 12 INSTALL TEMPORARY DUSTPROOF BARRIER WHEN


DEMOLITION WORK OR NEW FINISH INSTALLATION IS BEING
DONE FOR CORRIDOR 115.

10 2 13 PROVIDE TEMPORARY 2'-0" H X 4'-0" L EXTERIOR SIGN


1
STATING "TEMPORARY ENTRANCE".
6

B. McCOMBS
5 5

S. SPRAGUE

J. MORGAN
14 PROVIDE TEMPORARY ADA-COMPLIANT RAMP AND

Submitted by:
Reviewed by:
Designed by:
CORRIDOR

J. LOPEZ
HANDRAILS COMPLYING WITH CURRENT TEXAS

Drawn by:
115 ACCESSIBILITY STANDARDS.

GENERAL NOTES
5
4 4 1. EXISTING BUILDING WILL REMAIN OCCUPIED DURING
CONSTRUCTION. ALL UTILITIES, FIRE ALARM, AND FIRE
SUPPRESSION SYSTEM MUST REMAIN OPERATIONAL

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


DURING CONSTRUCTION. ANY TEMPORARY UTILITY SHUT
11 OFF MUST BE DONE AFTER HOURS AND SCHEDULED
WITH THE BASE.
2. MAINTAIN ACCESS TO RESTROOMS. ALL DEMOLITION OR
NEW FINISH MATERIAL INSTALLATION IN CORRIDOR 115
SHALL OCCUR AFTER HOURS. IF ACCESS CANNOT BE
MAINTAINED TO THE RESTROOMS THEN THE
3 CONTRACTOR SHALL PROVIDE FIVE EXTERIOR
PORTABLE RESTROOMS WITH HANDWASHING

17th TRAINING WING


NATURE OF WORK:
2 CAPABILITY.
2
9

3 3
8
7
C:\Work\Projects\R18_70374-000_A_SSnyderOKC.rvt

4 11

3'-0" 4'-4" 4'-0"

3
2 2

PROJECT TITLE
1 1
ALT #1 10
2
32'-8" 42'-9"
13

14

A B C D E F G
Project Number:

OK70374-000

SHEET TITLE

DEMOLITION PLAN
7/12/2018 11:29:28 AM

Date:

DEMOLITION PLAN 12 JUL 2018

1 SCALE: 1/8" = 1'-0"


PLAN NORTH SEQ. SHEET OF
8' 4' 0 8'

SCALE: 1/8" = 1'-0" AD-100


C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

NEW EQUIPMENT ALIGN WALL EXISTING


AA BB CC DD EE FF GH HH JJ A B SCREEN WALL 5 FACES C EQUIPMENT D E F G
A-301 ENCLOSURE
OKLAHOMA CITY, OK 73112 405.416.8100

Date Appr
C.H. GUERNSEY & COMPANY

5
A-301

16'-0"
4
5555 N. GRAND BLVD.

Description
A-201

CU-1
RE: M-101
22'-8" 7'-2"

Symbol
9 9

Appr
7.9

Date
7.8

REVISIONS
VESTIBULE
104

Description
7

6
FAMILY TOILET

Symbol
5.6 105
MECHANICAL
107
1 COMM 1
106
A-301 EXISTING WOMEN'S A-301
108

EXISTING DINING EXISTING KITCHEN


EXISTING JAN. 116 117
5 109 5

B. McCOMBS
PRIVATE DINING DINING OFFICE CONF. ROOM STORAGE

S. SPRAGUE

J. MORGAN

Submitted by:
CORRIDOR

Reviewed by:
103 102 112 110
EXISTING

Designed by:
111

J.LOPEZ
115

Drawn by:
18 SEATS

EXISTING MEN'S
NO ARCHITECTURE
114 WORK IN THIS AREA
STUDENT ADMIN. 4
113
3.8

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


A-201
3.4

3
VESTIBULE

17th TRAINING WING


NATURE OF WORK:
101
2
2.2 A-301

2.1
2
C:\Work\Projects\R18_70374-000_A_SSnyderOKC.rvt

1
PREPARATION ROOM
1
118

ALT #1
AA BB CC DD EE FF GH HH JJ

PROJECT TITLE
2
A-301

Project Number:

COMPOSITE FLOOR PLAN


1 SCALE: 3/32" = 1'-0"
OK70374-000

SHEET TITLE

COMPOSITE FLOOR PLAN


7/12/2018 11:47:05 AM

Date:
12 JUL 2018

EXPANSION EXISTING PLAN NORTH


SEQ. SHEET OF
12' 6' 0 12'

SCALE: 3/32" = 1'-0" A-101


KEY PLAN
3 GENERAL NOTES:
4 A-301
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
AA BB CC DD EE FF GH HH JJ A B 1. ALL MASONRY DIMENSIONS ARE SHOWN AS NOMINAL DIMENSIONS. CONTRACTOR SHALL
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
A-201 COORDINATE ACTUAL BUILDING LAYOUT WITH NOMINAL DIMENSIONS AND REFERENCED
DETAILS.
105'-0" 2. REFER 1/P-501 FOR NEW TOILET ROOM FLOOR DRAINS.
3. REFER SHEET A-341 FOR PARTITION TYPES AND GENERAL NOTES.
4. REFER TO SHEET A-341 FOR ADDITIONAL CONTROL JOINTS (CJ) NOT SHOWN ON FLOOR PLAN.
8'-0" 8'-0" 9'-4" 8'-8" 9'-4" 8'-0" 3'-0" 2'-8" 2'-0" 2'-8" 2'-0" 2'-8" 23'-8" 2'-8" 2'-0" 2'-8" 2'-0" 2'-8" 3'-0"
5. WALL CONTROL JOINTS (CJ) TO MATCH WALL FIRE RATING.
7'-10" 6'-1" 14'-8" 20'-7" 7'-3" 11'-7" 1'-7" 11'-6" 3'-6" 20'-4" 6. ALL EXISTING WALLS IN CORRIDOR 115 SHALL HAVE NEW 5/8" GYPSUM BOARD INSTALLED ON
OKLAHOMA CITY, OK 73112 405.416.8100

CORRIDOR SIDE OF WALL.


7. REFER TO DRAWING SHEET A-301 FOR ADDITIONAL EXTERIOR BUILDING WORK TO THE

Date Appr
EXISTING MASONRY VENEER.
8. INTERIOR DIMENSIONS ARE TO CENTERLINE OF STUD.

PLAN NOTES
C.H. GUERNSEY & COMPANY

Sim
9 9
4

4'-0"
A-501 1 NEW 5/8" GYPSUM BOARD ON EXISTING METAL STUDS
5555 N. GRAND BLVD.

8 8

Description
A A

3'-9"
2 CONTINUOUS EXPOSED AND PAINTED 1/2" FIRE TREATED PLYWOOD FROM 12" AFF UP TO 9'-0" AFF

7.9 Sim 1'-2" 7.9 3 ROOF ACCESS LADDER


3
C EDGE OF EXISTING FLOOR SLAB

10'-0"
7.8 A-501 7.8 4
5

12'-11"
A-501 6 104A 5 PROVIDE IN-WALL TV MOUNTING BRACKET: CHIEF MANUFACTURING MODEL PNRIWUB 22" MOUNT WITH

Symbol
Sim 2 PAC501B IN-WALL BOX, USING PACHFK1 HEADER AND FOOTER AND PAC138 PADLOCK
2 D 7
1 D A-501
A-501 A-501
A-501 B B B B B B 6 PROVIDE CONCEALED, FIRE-TREATED WOOD BLOCKING (PLYWOOD PANELS) AT LOCATIONS OF OWNER-PROVIDED
MONITORS IN DINING 104. COORDINATE WITH OWNER EXACT LOCATIONS AND INSTALL WITH BOTTOM OF TV AT 6'-8"

Appr
7 7 AFF. IF STUD DOES NOT FALL AT CENTER OF MOUNTING LOCATION, BLOCK 5 BAYS AS REQUIRED TO PROVIDE A
9'-4"

A A-221 MINIMUM BACKING WIDTH OF 32" ON EACH SIDE OF THE CENTER OF MOUNTING LOCATION. OVERALL HEIGHT OF
VESTIBULE Sim PLYWOOD PANELS IS TO BE 24" AND IS TO BE CENTERED ON MOUNTING LOCATION. BLOCKING IS TO SUPPORT 150 LBS.

Date
S062
7'-10"

2 104B 104 5 9
A-121 5 PREFINISHED

REVISIONS
S021 S067 PANELS A-501

6
S068
105 107 6 TOILET ACCESSORIES SCHEDULE
4

Description
9'-4"

Sim MARK ACCESSORY CFCI GFCI COMMENTS


FAMILY TOILET 3
7'-11"

13
105 1 A 18" VERTICAL GRAB BAR YES
S068 A-501 MECHANICAL
5.6 2'-1 3/4" 6 5.6 B 36" GRAB BAR YES
S067 107
C 42" GRAB BAR YES
2'-8"

S067
D TOILET TISSUE DISPENSER YES

14" MIN.

S062
1 103 2 S067 1
106 E FEMININE HYGIENE DISPOSAL YES

Symbol
COMM F SEAT COVER DISPENSER YES

8'-6"
A-301 EXISTING WOMEN'S A-301
106 108 G SOAP DISPENSER YES
9'-4"

115
14'-1"

8'-7" 19'-5" S067 H 36" X 48" MIRROR YES


A 10 CORRIDOR J BABY CHANGING STATION YES
A-501 E 6'-0" 115
6 A-221 1 Sim K PAPER TOWEL DISPENSER YES
PRIVATE DINING 1'-5" S067 12 S067 SN5

6'-2"
S067
103 EXISTING JAN.
A-501
87'-4"

109
6'-0"

5 OFFICE CONF. ROOM STORAGE


3 A-731 5
FF 3 A-221
S067
1'-5"

112 111 110

6'-0"

B. McCOMBS
6'-0"

E E

S. SPRAGUE

J. MORGAN
11'-2"

Submitted by:
2

Reviewed by:
Designed by:
DINING S067

J. LOPEZ
7"
1

Drawn by:
2 102 6
9'-4"

A 112 111 110


11 EXISTING MEN'S

2'-4"
A-201 105
A-501 S067 114
5 10'-7" 10'-0" 7'-5" J
4 4
2'-11"

12

6'-0"
S067 E
2'-8"

A-501 F
3.8 STUDENT ADMIN. 3.8 FAMILY TOILET
C FLOOR DRAIN
S068 8 A 105
113 RE: P-101

6'-0 1/2" +/-


7'-11"

11 A-501 D

CRESSMAN DINING FACILITY EXPANSION


4 E G

GOODFELLOW AIR FORCE BASE, TEXAS


S068
9'-4"

S021 A-601 H
S067 B K
1
3.4 3.4
113 5.6
6 9
2
7'-10"

2 13 PREFINISHED 1'-5 1/2" 4'-9 3/4" 1'-6"


1 101B 5
S062 A-501 PANELS A-501
A-501 A-501 74
A-501
9'-4"

17th TRAINING WING


A
ENLARGED PLAN - FAMILY TOILET

NATURE OF WORK:
3 3
B B B A-221 B B B
7
Sim 2 SCALE: 1/4" = 1'-0"
VESTIBULE D
D A-501
101
12'-11"

2
4 5 101A 6 D
A-301
10'-0"

A-501 6 2.2 A-501 FLOOR DRAIN


A-501 C RE: P-101
3
C:\Work\Projects\R18_70374-000_A_SSnyderOKC.rvt

A-501 2.1
2.2 2
11"

A A
2 2
1
Sim
4 PREPARATION ROOM

12'-5"
1 1

13'-4"
118 1
A-501
A-201

PROJECT TITLE
8'-0" 8'-0" 9'-4" 8'-8" 9'-4" 8'-0" 3'-0" 2'-8" 2'-0" 2'-8" 2'-0" 2'-8" 8'-10" 6'-0" 5'-0" 3'-10 1/4" 2'-8" 2'-0" 2'-8" 2'-0" 2'-8" 2'-11 3/4"

11"
1'-1" 7'-10" 6'-1" 14'-8" 20'-7" 7'-3" 11'-7" 1'-7" 11'-6" 3'-6" 20'-4" 4'-1" 26'-9"
105'-0" 11" 32'-8" 11"

AA BB CC DD EE FF GH HH JJ A B
3 FLOOR PLAN AREA-B (ALT #1) Project Number:

A-301 3 SCALE: 1/8" = 1'-0" OK70374-000

SHEET TITLE

FLOOR PLAN AREA-A FLOOR PLAN

1 SCALE: 1/8" = 1'-0"


7/12/2018 11:28:10 AM

Date:
12 JUL 2018

EXPANSION EXISTING
PLAN NORTH SEQ. SHEET OF
8' 4' 0 8'

SCALE: 1/8" = 1'-0" A-121


KEY PLAN
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

AA BB CC DD EE FF GH HH JJ A B
3
A-301
OKLAHOMA CITY, OK 73112 405.416.8100

Date Appr
8
B
7.9
C.H. GUERNSEY & COMPANY

7.9 ACOUSTICAL CEILING TILE

7.8 6" UNFACED BATT


EXISTING CEILING
5555 N. GRAND BLVD.

MECH. AIR CURTAIN INSULATION


7.8

Description
6" METAL STUDS

10'-8" 10'-0"
EXISTING SOFFIT 5/8" GYPSUM BOARD
VESTIBULE
104
6
9'-10" 9'-0"

Symbol
A-301 7

2"
12'-2" 9'-10" 2 1/2" METAL
10'-0" STUDS

Appr
CEILING DETAIL
6 3

Date
9'-0" SCALE: 3/4" = 1'-0"
ACOUSTICAL CEILING TILE

REVISIONS
14'-0" FAMILY TOILET
EXHAUST FAN 105 ACCESS MECHANICAL 6" UNFACED BATT
PANEL 14'-0" INSULATION
107

Description
5.6 5.6 6" METAL STUDS
COMM
106 CORRIDOR 2
9'-0" 5/8" GYPSUM
115 3
BOARD
EXISTING WOMEN'S A-141
8'-10" 6" METAL STUDS
5/8" GYPSUM BOARD

Symbol
12'-2"
PRIVATE DINING 9'-0" 9'-0" 9'-0" ACOUSTICAL CEILING TILE
103 DINING EXISTING JAN. EQ EQ
102 10'-0" 10'-0"
5 5 4'-0"

2"
5 OFFICE CONF. ROOM STORAGE
112 111 110
10'-0" A-141
ACOUSTICAL
CEILING TILE

EXISTING MEN'S LIGHT 10'-0"

B. McCOMBS
S. SPRAGUE

J. MORGAN

Submitted by:
Reviewed by:
Designed by:
4

J. LOPEZ
Drawn by:
STUDENT ADMIN.
3.8 113 3.8
12'-2" 9'-0"
CEILING DETAIL CEILING DETAIL
4 SCALE: 3/4" = 1'-0" 5 SCALE: 3/4" = 1'-0"

3.4 3.4
9'-10"

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


10'-0"

3
SIM VESTIBULE
5 101

17th TRAINING WING


A-141

NATURE OF WORK:
10'-8" EXISTING SOFFIT

MECH. AIR CURTAIN D


2 4
2.2 2.2 A-301 A-141

2.1 2.1
C:\Work\Projects\R18_70374-000_A_SSnyderOKC.rvt

2
2 PREPARATION ROOM
118
1 1
10'-0"
MODIFY EXISTING MODIFY EXISTING
SOFFIT SOFFIT

3
A-301

PROJECT TITLE
AA BB CC DD EE FF GH HH JJ A B

FIRST FLOOR - REFLECTED CEILING PLAN AREA-A


1 SCALE: 1/8" = 1'-0"
2
A-301

Project Number:

LEGEND: FIRST FLOOR - REFLECTED CEILING PLAN AREA-B (ALT #1) OK70374-000
2 SCALE: 1/8" = 1'-0" SHEET TITLE

REFLECTED CEILING PLAN


ACOUSTICAL CEILING TILE
SUPPLY DIFFUSER
7/12/2018 11:28:14 AM

Date:
PREFINISHED METAL SOFFIT PANELS RETURN GRILL 12 JUL 2018

2' x 2' CEILING MOUNTED FIXTURE


EXPANSION EXISTING
GYPSUM BOARD CEILING
PLAN NORTH SEQ. SHEET OF
1' x 4' STRIP FIXTURE 8' 4' 0 8'

DOWNLIGHT ACT CEILING EXPANSION JOINT


REFER DETAIL 6/A341 SCALE: 1/8" = 1'-0"
A-141
KEY PLAN 2' 1' 0 2'

SCALE: 3/4" = 1'-0"


STANDING SEAM
ROOF HATCH
METAL ROOF LEGEND: GENERAL NOTES:
BUTYL TAPE FLUE, RE: 1. REFER TO MECHANICAL (SHEET M-103) FOR EXACT LOCATIONS OF ROOF PENETRATIONS AND SIZES.
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
MECHANICAL EXISTING STANDING SEAM ROOF 2. PROVIDE ICE & WATER SHIELD FLASHING 3'-0" BACK FROM EAVES AND RAKES. PROVIDE FLEXIBLE
CONT. PRESERVATIVE-TREATED ICE & WATER SHIELD 3'-0" EACH DIRECTION FROM CENTER LINE OF VALLEYS AND EXPANSION JOINTS.
4"x4" WOOD CANT STRIP-SAWN 3. THE WARRANTY ON THE EXISTING STANDING SEAM METAL ROOF IS IN FORCE. ALL MODIFICATIONS
INTO HALF TO EXISTING ROOF SHALL NOT VOID THE EXISTING ROOF WARRANTY.
STANDING SEAM METAL ROOF

ROOF MEMBRANE
TPO ROOFING MEMBRANE WITH
OKLAHOMA CITY, OK 73112 405.416.8100

1/2" COVER BOARD SLOPED STRUCTURE 1/4" PER FOOT

Date Appr
(2) LAYERS OF 2.5" RIGID
INSULATION BOARD
RD ROOF DRAIN PLAN NOTES
C.H. GUERNSEY & COMPANY

ORD OVERFLOW ROOF DRAIN 1 GUTTERING ON FOUR SIDES OF ENTRANCE ELEMENT.


METAL ROOF DECKING DOWNSPOUTS WILL BE ON BACKSIDE ONLY DRAINING
DS DOWNSPOUT - PROVIDE SPLASH ONTO THE TPO ROOF AREA.
DRAW BAND
5555 N. GRAND BLVD.

PANS ON SACRIFICE PADS @ EA


4"x4" ROOF GUTTER.

Description
DOWNSPOUT.
2

PREFINISHED SHEET
METAL FLASHING
MATCHING ROOF COLOR

ROOF HATCH DETAIL ROOF DETAIL

Symbol
2 SCALE: 1 1/2" = 1'-0" 3 SCALE: 3/4" = 1'-0"
4

Appr
A-201

Date
AA BB CC DD EE FF GH HH JJ A B C D E F G

REVISIONS
3
A-301

Description
1
9 9

8
7.9

RI

E
DG
DG

Symbol
RI
E
7.8
1
1

RI
RI

DG
DG

DG
DG

RI
RI

E
E

A-301 7
RD
EY

ORD
LL

DS
VA

DS 1
6

B. McCOMBS
S. SPRAGUE

J. MORGAN
MECH.

Submitted by:
Reviewed by:
Designed by:

J. LOPEZ
VENT
ROOF HATCH

Drawn by:
5.6
E
DG

RE: 2/A-161
RIDGE

RI

1/4" / 12"
CU-2
RE: M-103 HVAC FRESH AIR
1 INTAKE HOOD
VA
RI

LL

A-301
DG

EY
E

DS
DS
RI

6
DG

CRESSMAN DINING FACILITY EXPANSION


E

GOODFELLOW AIR FORCE BASE, TEXAS


RIDGE RIDGE A-521
5 5
E

2
DG
RI

2
DS DS
A-201
EY
E
DG

LL

4
RI

17th TRAINING WING


VA

NATURE OF WORK:
RI
DG
RIDGE

3.8
E

1/4" / 12"

HVAC RELIEF AIR


EXHAUST HOOD 1
A-201
3.4 1
DS DS
VA

ORD
LL
EY
C:\Work\Projects\R18_70374-000_A_SSnyderOKC.rvt

RD
3 3
RI
E

RI

E
DG

DG
DG

DG
RI

RI
E

RIDGE
1
1
2.2
RI
E
DG

DG
RI

2.1

PROJECT TITLE
2

1 1
1

RI
DG

DG
RI

E
3
A-301
Project Number:

3 OK70374-000
AA BB CC DD EE FF GH HH JJ
A-201 ALT #1
SHEET TITLE
A B C D E F ROOF PLAN
7/12/2018 11:28:16 AM

2 Date:
12 JUL 2018
A-301

COMPOSITE ROOF PLAN EXPANSION EXISTING PLAN NORTH


1 SCALE: 3/32" = 1'-0" 16' 8' 0 16'
SEQ. SHEET OF

SCALE: 1/16" = 1'-0" A-161


KEY PLAN
GENERAL NOTES:
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

1. ALL MECHANICAL EQUIPMENT, LOUVERS, ETC. LOCATED IN MASONRY WALLS, METAL


WALL PANELS, OR ON ROOF SHALL BE PAINTED TO MATCH ADJACENT COLOR.
OKLAHOMA CITY, OK 73112 405.416.8100

1 1

Date Appr
1 2 2.1 2.2 3 3.4 3.8 4 5 A-301 5.6 6 7 8 9 9 8 7.9 7.8 7 6 5.6 A-301 5 4 3.8 3.4 3 2.2 2.1 2 1
C.H. GUERNSEY & COMPANY
5555 N. GRAND BLVD.

STANDING SEAM METAL ALT #1 TOP OF ROOF

Description
25'-6" LIGHT STANDING SEAM METAL
ROOFING & FASCIA ROOFING & FASCIA
TOP OF ROOF
6 STANDING SEAM METAL 6
20'-7" ROOFING & FASCIA
A-301 A-301
TOP OF STEEL TOP OF STEEL
114'-3" 114'-3"

Symbol
SPLIT-FACE CMU VENEER
BRICK VENEER BRICK VENEER
BRICK VENEER SPLIT-FACE CMU VENEER A A A A
SPLIT-FACE CMU VENEER

Appr
FINISH FLOOR FINISH FLOOR

Date
100'-0" 100'-0"

REVISIONS
REMOVE EXISTING CONTINUOUS BRICK SOLDIER COURSE ALUMINUM STOREFRONT
AND REPLACE WITH NEW CONTINUOUS SPLIT-FACE CMU VENEER (ALT #2)
EAST ELEVATION WEST ELEVATION

Description
1 SCALE: 3/32" = 1'-0" 2 SCALE: 3/32" = 1'-0"

Symbol
2
A-301
AA BB CC DD EE FF GH HH JJ A C D E F G

STANDING SEAM METAL


ROOFING & FASCIA
TOP OF ROOF LIGHT SURFACE MOUNTED
EXISTING STANDING
25'-3" ALUMINUM CHANNEL
SEAM METAL
LETTER SIGNAGE
STANDING SEAM METAL ROOFING & FASCIA

B. McCOMBS
S. SPRAGUE
ROOFING & FASCIA

J. MORGAN

Submitted by:
Reviewed by:
Designed by:

J. LOPEZ
Drawn by:
ALT #2
TOP OF STEEL
114'-3"

BRICK VENEER C
A A B B B B B B
SPLIT-FACE CMU VENEER

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


FINISH FLOOR
100'-0"

101A
ALUMINUM STOREFRONT SPLIT-FACE CMU VENEER EXISTING REMOVE EXISTING CONTINUOUS BRICK SOLDIER COURSE BRICK VENEER REMOVE EXISTING CONTINUOUS BRICK SOLDIER COURSE
BRICK AND REPLACE WITH NEW CONTINUOUS SPLIT-FACE CMU VENEER (ALT #2) AND REPLACE WITH NEW CONTINUOUS SPLIT-FACE CMU VENEER (ALT #2)
SPLIT-FACE CMU VENEER
SOUTH ELEVATION
3 SCALE: 3/32" = 1'-0"

17th TRAINING WING


NATURE OF WORK:
2
A-301
G F E D C B A JJ HH GH FF EE DD CC BB AA
C:\Work\Projects\R18_70374-000_A_SSnyderOKC.rvt

EXISTING STANDING
SEAM METAL SURFACE MOUNTED TOP OF ROOF
ROOFING & FASCIA ALUMINUM CHANNEL 25'-3"
LETTER SIGNAGE

STANDING SEAM METAL


ROOFING & FASCIA

PROJECT TITLE
LIGHT
TOP OF STEEL
114'-3"

CMU ACCENT COURSE


B B B B B B A A
BRICK VENEER

FINISH FLOOR
100'-0" Project Number:

SPLIT-FACE CMU VENEER ALUMINUM STOREFRONT OK70374-000


EXISTING REMOVE EXISTING CONTINUOUS BRICK EXISTING SCREEN WALL NEW SCREEN WALL
BRICK SOLDIER COURSE HIDDEN FOR HIDDEN FOR SHEET TITLE
NORTH ELEVATION AND REPLACE WITH NEW CONTINUOUS SPLIT- CLARIFICATION OF CLARIFICATION OF

4 SCALE: 3/32" = 1'-0"


FACE CMU VENEER (ALT #2) BUILDING ELEVATION BUILDING ELEVATION EXTERIOR ELEVATIONS
7/12/2018 11:28:27 AM

Date:
12 JUL 2018

SEQ. SHEET OF
12' 6' 0 12'

SCALE: 3/32" = 1'-0" A-201


C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

PT1
PT1
NON-RECESSED NON-RECESSED
TV TV
TV NIC TV NIC
OKLAHOMA CITY, OK 73112 405.416.8100

ART NIC
WALL TILE LEGEND

Date Appr
TS3 TS3 TS3 TS3 TS3
CT1, CT2, CT3

4"
C.H. GUERNSEY & COMPANY

7'-2"
CT4, CT5, CT9

4'-6"

4'-0"
3'-4"
5555 N. GRAND BLVD.

2'-10"

Description
SSM1 HPL1
30" W x 20" H x 4.5" D RECESSED
3'-0" 3'-0" 2'-11 3/4" BOX WITH IN-WALL SWING ARM
EXPANSION JOINT PREFINISHED INTERIOR
PANEL SYSTEM

Symbol
INTERIOR ELEVATION - DINING ROOM
1

1'-0" 6" 1'-0" 1'-0" 6" 1'-0" 1'-0" 1'-0" 6" 1'-0" 1'-0" 6"
SCALE: 1/4" = 1'-0"

2'-4"

Appr
RECESSED

1'-8"
2'-8"

Date
TV
TV NIC

10'-0"
CT1 CT1

REVISIONS
2'-6"

2'-6"

Description
H
K
G B C E C J

2'-2"
B
A
RECEPTACLE
F A
WRAP SINK E
F
PIPING FOR ADA TS2 D TS2 1'-0" 6'-0"
TS2 MB1 COORDINATE SIZE OF TV WITH TS2
COMPLIANCE

Symbol
DIMENSIONS OF CENTER PANEL

INTERIOR ELEVATION - FAMILY TOILET INTERIOR ELEVATION - FAMILY TOILET INTERIOR ELEVATION - VESTIBULE 101
2 SCALE: 1/4" = 1'-0" 3 SCALE: 1/4" = 1'-0" 4 SCALE: 1/4" = 1'-0"

B. McCOMBS
CT2

Submitted by:
6"

Reviewed by:
CT5

Designed by:
Designer
CT9

Checker
CT2 CT2

Drawn by:
Author
1'-0"
CT4 CT2 CT9
CT5

1'-0"
CT2 CT4 CT1 CT1
30" W x 20" H x 4.5" D RECESSED BOX PREFINISHED INTERIOR
WITH IN-WALL SWING ARM PANEL SYSTEM

6"
EXPANSION JOINT CT5
CT1 CT1

1'-0"

CRESSMAN DINING FACILITY EXPANSION


CT3

GOODFELLOW AIR FORCE BASE, TEXAS


CT2
2'-4"

CT5
CT4

1'-0"
CT2 CT9 CT4 CT3
RECESSED CT5
1'-8"
2'-8"

TV
TV NIC CT2

1'-0"
CT1 CT1 CT4
10'-0"

2'-6"

17th TRAINING WING


6"
2'-6"

CT5

NATURE OF WORK:
CT5
CT4 CT2

1'-0"
CT2 CT4 CT2
CT5
2'-2"

CT5

1'-0"
CT1 CT3 CT2
4"

CT2 CT1
TS2 MB1 COORDINATE SIZE OF TV WITH TS2 TS2 TS2

6"
CT5
DIMENSIONS OF CENTER PANEL CT4
C:\Work\Projects\R18_70374-000_A_SSnyderOKC.rvt

1'-0"
CT4 CT2 CT4 CT2
CT5

INTERIOR ELEVATION - VESTIBULE 104 INTERIOR ELEVATION - WALL TILE PATTERN TYP.
5 SCALE: 1/4" = 1'-0" 7 SCALE: 1/2" = 1'-0"

PROJECT TITLE
PT1 PT1 ON PT1 PT1 ON
COLUMN COLUMN
Project Number:

OK70374-000

OPEN BEYOND OPEN BEYOND SHEET TITLE

TS3 TS3 TS3 TS3 TS3 TS3 TS3 INTERIOR ELEVATIONS


7/12/2018 11:28:29 AM

Date:
12 JUL 2018
4'-0"

SEQ. SHEET OF
TS1 TS1 4' 2' 0 4'
INTERIOR ELEVATION - DINING ROOM
6 SCALE: 1/4" = 1'-0" SCALE: 1/4" = 1'-0" A-221
AA BB CC DD EE FF GH HH JJ A B 1 2
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
3
A-301
LOW SLOPE
STANDING SEAM ROOFING MEMBRANE
METAL ROOF

STANDING SEAM
5 6 METAL ROOF
OKLAHOMA CITY, OK 73112 405.416.8100

A-521 A-521

Date Appr
TOP OF STEEL 3 TOP OF STEEL TOP OF STEEL
C.H. GUERNSEY & COMPANY

114'-3" 114'-3" 114'-3"


A-141
5555 N. GRAND BLVD.

Description
A-321 1
A-321

FINISH FLOOR FINISH FLOOR FINISH FLOOR


100'-0" 100'-0" 100'-0"

Symbol
GRADE

Appr
Date
BUILDING SECTION BUILDING SECTION (ALT #1)
1 2 SCALE: 1/8" = 1'-0"

REVISIONS
SCALE: 1/8" = 1'-0"

Description
A-301 OPP

7.9 7 6 5.6 5 4 3.8 3.4 3 3 2.1 OPP


3 A-321
4
4 A-321
A-301
A-301

Symbol
METAL ROOF DECK SLOPE (EACH SIDE)

8 7.9
#4 @ 16" O.C. VERT BRICK ROWLOCK
TOP OF STEEL TOP OF STEEL
114'-3" 114'-3"
STANDING SEAM 3'-8"
METAL ROOFING 4 3/4"
3 5/8" 3 5/8"
GROUT CAVITY FULL
7 OPP (2500 PSI CONCRETE)

B. McCOMBS
S. SPRAGUE
11

J. MORGAN
A-521

Submitted by:
Reviewed by:
Designed by:

J. LOPEZ
EXTERIOR INTERIOR

6'-0"
A-521

Drawn by:
FACE BRICK
1/2" EXTERIOR #4 @ 16" O.C. HORIZ.
FINISH FLOOR FINISH FLOOR
GRADE PLYWOOD
100'-0" 100'-0"
DOWELS TO MATCH
VERT. REINF.
1
GRADE LINE
A-301 (4) #4 AS SHOWN

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


CONCRETE SPREAD
BUILDING SECTION

1'-4"
FOOTING (2500 PSI) GRAVEL LINE
3 SCALE: 1/8" = 1'-0"
STEEL BEAM 1'-3" 1'-3"
#5 TRANSVERSE @12"
O.C., PROVIDE STD AC1

1'-0"
HOOK EACH END

GH HH 6" COLD-FORMED METAL (3) #5 LONG

17th TRAINING WING


NATURE OF WORK:
PRE-FINISHED SHEET METAL COUNTER FRAMING @ 16" O.C. MAX
3'-6"
FLASHING REGLET
PRE-FINISHED SHEET METAL EXPANSION
JOINT COVER. SIZE TO ALLOW MOVEMENT SPLIT-FACE CMU VENEER
SCREEN WALL SECTION

4'-0"
SET IN SEALANT
"Z" CLOSURE SET IN SEALANT
STANDING SEAM METAL ROOF
WEATHER BARRIER 5 SCALE: 1/2" = 1'-0"
6" COLD-FORMED METAL FRAMING MASONRY TIE
ICE & WATER SHIELD, TYP.
C:\Work\Projects\R18_70374-000_A_SSnyderOKC.rvt

@ 16" O.C. MAX


1/2" EXTERIOR GRADE PLYWOOD 1/2" GLASS-MAT GYPSUM WALL MOISTURE BARRIER ON
SHEATHING 1/2" GYPSUM SHEATHING
BENT STEEL PLATE
(2) LAYERS OF RIGID INSULATION BOARD SPLIT-FACE CONCRETE FACE TOP OF STEEL
METAL ROOF DECKING BRICK 114'-3"
TOP OF STEEL TOP OF STEEL
114'-3" 114'-3"
6" COLD-FORMED METAL
CAVITY DRAINAGE MAT FRAMING @ 16" O.C. MAX

PROJECT TITLE
STEEL BEAM
6" COLD-FORMED METAL FRAMING @
16" O.C. MAX
STEEL BEAM
PREFINISHED METAL SOFFIT ON 1/2 THRU-WALL FLASHING
PLYWOOD ON 7/8" FURRING CHANNELS @ SET IN SEALANT
24" O.C. PREFINISHED METAL SOFFIT OVER
GRID SUSPENSION SYSTEM
"Z" CLOSURE SET IN SEALANT
PRE-FINISHED SHEET METAL EXPANSION Project Number:
JOINT COVER. SIZE TO ALLOW MOVEMENT GWB OVER GRID SUSPENSION OK70374-000
SYSTEM
WEEPS W/ INSECT MESH @ 32" O.C.
STEEL PLATE SHEET TITLE
8
BUILDING SECTIONS
A-521
VERTICAL DETAIL WALL SECTION
6 4
7/12/2018 11:28:33 AM

SCALE: 1 1/2" = 1'-0" SCALE: 3/4" = 1'-0" Date:


12 JUL 2018

SEQ. SHEET OF
2' 1' 0 2' 8' 4' 0 8'

SCALE: 3/4" = 1'-0" SCALE: 1/8" = 1'-0" A-301


C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
7

METAL ROOF DECK

3'-3 3/4" STANDING SEAM


METAL ROOFING
OKLAHOMA CITY, OK 73112 405.416.8100

Date Appr
12" 11
A-521
6"
C.H. GUERNSEY & COMPANY
5555 N. GRAND BLVD.

Description
1/2" EXTERIOR
GRADE PLYWOOD

Symbol
AA DOWNSPOUT BEYOND

Appr
STANDING SEAM STANDING SEAM 6" COLD-FORMED METAL
METAL ROOFING METAL ROOFING FRAMING @ 16" O.C. MAX

Date
FOAM SEAL FOAM SEAL 1 1/2" METAL WALL PANEL
1/2" EXTERIOR 1/2" EXTERIOR 4 1/4"

REVISIONS
4'-0"
GRADE PLYWOOD GRADE PLYWOOD MOISTURE BARRIER ON
1/2" PLYWOOD
2 LAYERS OF 2.5" RIGID 2 LAYERS OF 2.5" RIGID
INSULATION BOARD 1 INSULATION BOARD

Description
24"x24" WEATHER TIGHT
1 METAL ROOF DECK A-521 METAL ROOF DECK ACCESS PANEL
A-521
12" 12" SPLASH PAN
4" 4" 4 TAPPER INSULATION
TOP OF STEEL TOP OF STEEL A-521 TOP OF STEEL

Symbol
114'-3" 114'-3" 114'-3"
2 LAYERS OF 2.5" RIGID
INSULATION BOARD

METAL ROOF DECK


2'-3"

2'-3"
STEEL BEAM

B. McCOMBS
S. SPRAGUE
6" NON-STRUCTURAL

J. MORGAN

Submitted by:
Reviewed by:
Designed by:

J. LOPEZ
2 FRAMING @ 16" O.C MAX.

Drawn by:
A-521 5/8" GYPSUM BOARD

2'-8"
2'-6" 2'-6"

6"
3/4" 3/4"
CMU VENEER
ACCENT COURSE

2"
ACOUSTIC PANEL CEILING -

CRESSMAN DINING FACILITY EXPANSION


8"

8"

8"
ACOUSTIC PANEL ACOUSTIC PANEL

GOODFELLOW AIR FORCE BASE, TEXAS


RE: ROOM FINISH SCHEDULE
CEILING CEILING
MTL STUD BOX HEADER
CMU VENEER
ACCENT COURSE 1/2" GYPSUM BOARD OVER
GRID SUSPENSION SYSTEM
5/8" GYPSUM BOARD 9
A-521 DOOR BEYOND

17th TRAINING WING


NATURE OF WORK:
R-19 BATT INSULATION

14'-3"
8" COLD-FORMED METAL
+/- 12'-0" (MATCH EXISTING)

+/- 12'-0" (MATCH EXISTING)

FRAMING @ 16" O.C. MAX

5'-7 1/4"
MOISTURE BARRIER ON
1/2" GYPSUM SHEATHING

1" XPS INSULATION BOARD


C:\Work\Projects\R18_70374-000_A_SSnyderOKC.rvt

+/- 9'-1 1/4" (MATCH EXISTING)

BRICK VENEER
9'-9 1/4"
9'-1 1/4"

10
A-521

PROJECT TITLE
MOISTURE BARRIER ON 5/8" GYPSUM BOARD
ADJUSTABLE MASONRY- 1/2" GYPSUM SHEATHING
VENEER ANCHORS @ 16" O.C.
R-19 BATT INSULATION
1" XPS INSULATION BOARD

BRICK VENEER
3'-6"

ADJUSTABLE MASONRY- CAST-IN-PLACE CONCRETE


3
VENEER ANCHORS @ 16" O.C. FLOOR SLAB
A-521 Project Number:

VAPOR RETARDER OK70374-000


8" COLD-FORMED METAL SHEET TITLE
FRAMING @ 16" O.C. MAX
FINISH FLOOR FINISH FLOOR FINISH FLOOR EXTERIOR WALL SECTIONS
2"

2"

100'-0" 100'-0" 100'-0"


EXPOSED CONCRETE EXPOSED CONCRETE
7/12/2018 11:28:36 AM

FOUNDATION FOUNDATION Date:


12 JUL 2018
GRADE GRADE

SEQ. SHEET OF
2' 1' 0 2'

WALL SECTION WALL SECTION 3


WALL SECTION A-321
1 SCALE: 3/4" = 1'-0" 2 SCALE: 3/4" = 1'-0"
A-521 3 SCALE: 3/4" = 1'-0" SCALE: 3/4" = 1'-0"
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
STRUCTURE STRUCTURE STRUCTURE STRUCTURE
GENERAL NOTES:
SLIP TRACK SLIP TRACK SLIP TRACK SLIP TRACK 1. REFER TO FLOOR PLANS FOR
LOCATIONS OF PARTITION TYPES.

2. "LINE OF STRUCTURE" INDICATED AT HEAD CONDITIONS FOR EACH


OKLAHOMA CITY, OK 73112 405.416.8100

PARTITION TYPE IS DIAGRAMMATIC ONLY AND DOES NOT INDICATE


EXACT CONSTRUCTION CONDITIONS.

Date Appr
3. TERMINATE FIRE RESISTANCE RATED PARTITIONS AT STRUCTURAL
MEMBER WITH A RATING GREATER THAN OR EQUAL TO THE PARTITION.
C.H. GUERNSEY & COMPANY

REFER CEILING PLAN REFER CEILING PLAN REFER CEILING PLAN REFER CEILING PLAN 4. INSTALL BRACING AND FIRE RETARDANT TREATED WOOD BLOCKING
FOR CASEWORK, EQUIPMENT, ETC. AT PARTITIONS AS REQUIRED.
FINISHED CEILING- FINISHED CEILING- FINISHED CEILING- FINISHED CEILING-
5555 N. GRAND BLVD.

REFER SCHEDULE REFER SCHEDULE REFER SCHEDULE REFER SCHEDULE 5. ALL INTERIOR PARTITION STUDS SHALL BE 33 MIL. MINIMUM, L/240, 16" O.C.

Description
6. THE MATERIALS AND DETAILS SHOWN ARE FOR TYPICAL INSTALLATIONS WHERE
3 1/2" UNFACED BATT 6" UNFACED BATT 6" UNFACED BATT THE STUD MANUFACTURER'S RECOMMENDATIONS OR LOCAL ORDINANCES ARE
INSULATION TO DECK INSULATION TO DECK INSULATION TO DECK MORE RESTRICTIVE, THEY SHALL APPLY.

7. PARTITIONS SHALL BE CONTINUOUS OVER DOORS SAME AS ADJACENT WALLS


3 5/8" NON-STRUCTURAL METAL 2 1/2" NON-STRUCTURAL METAL 6" NON-STRUCTURAL METAL 8" NON-STRUCTURAL METAL (UNLESS NOTED OTHERWISE) WHERE DRYWALL CONTINUES ABOVE CEILING LEVEL
FRAMING AT 16" O.C. FRAMING AT 16" O.C. FRAMING AT 16" O.C. FRAMING AT 16" O.C. AND ABOVE THE CEILING LEVEL UP TO THE STRUCTURE ABOVE.

Symbol
8. ALL PENETRATIONS IN DRYWALL CONSTRUCTION ABOVE FINISHED CEILING AND AS
5/8" GYPSUM BOARD 5/8" GYPSUM BOARD 5/8" GYPSUM BOARD 5/8" GYPSUM BOARD NOTED ELSEWHERE SHALL BE EFFECTIVELY SEALED TO ACHIEVE STATED STC RATING
AND FIRE STOP CAULKED AT FIRE RATED PARTITIONS.

Appr
9. ALL MECHANICAL CHASES AND OTHER NOTED CHASES ARE TO EXTEND UP TO THE
UNDERSIDE OF THE DECK STRUCTURE ABOVE. ALL PLUMBING CHASES UNLESS

Date
OTHERWISE NOTED SHALL EXTEND ABOVE THE HIGHEST ADJOINING CEILING AND
BASE - REFER SCHEDULE BASE - REFER SCHEDULE BASE - REFER SCHEDULE BASE - REFER SCHEDULE BE BRACED TO STRUCTURE.

REVISIONS
METAL STUD RUNNER-ANCHOR METAL STUD RUNNER-ANCHOR METAL STUD RUNNER-ANCHOR METAL STUD RUNNER-ANCHOR 10. ACOUSTICAL NOTES:
TO STRUCTURE TO STRUCTURE TO STRUCTURE TO STRUCTURE
FINISHED FLOORING - FINISHED FLOORING - FINISHED FLOORING - FINISHED FLOORING - A. PARTITION TO BE INSTALLED WITH SOUND ATTENUATION BLANKETS (SAB) - EXTEND

Description
REFER SCHEDULE REFER SCHEDULE REFER SCHEDULE REFER SCHEDULE S.A.B. FOR FULL-HEIGHT OF PARTITION.
ACOUSTICAL SEALANT EACH SIDE ACOUSTICAL SEALANT EACH SIDE ACOUSTICAL SEALANT EACH SIDE ACOUSTICAL SEALANT EACH SIDE

FIN. FLOOR FIN. FLOOR FIN. FLOOR FIN. FLOOR

Symbol
S021 NON-RATED 3 5/8" NON STRUCTURAL METAL S062 NON-RATED 2 1/2" NON STRUCTURAL METAL S067 NON-RATED 6" NON STRUCTURAL METAL S068 NON-RATED 8" NON STRUCTURAL METAL
FRAMING AND GYPSUM BOARD ONE SIDE FRAMING AND GYPSUM BOARD ONE SIDE FRAMING AND GYPSUM BOARD EACH SIDE FRAMING AND GYPSUM BOARD EACH SIDE

PARTITION S021 PARTITION S062 PARTITION S067 PARTITION S068


1 SCALE: 1/2" = 1'-0" 2 SCALE: 1/2" = 1'-0" 3 SCALE: 1/2" = 1'-0" 4 SCALE: 1/2" = 1'-0"

B. McCOMBS
S. SPRAGUE

J. MORGAN

Submitted by:
Reviewed by:
Designed by:

J. LOPEZ
Drawn by:
CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


DETAIL 5 NOT USED

17th TRAINING WING


NATURE OF WORK:
ACOUSTICAL TILE CEILING SYSTEM -
REFER REFLECTED CEILING PLAN
C:\Work\Projects\R18_70374-000_A_SSnyderOKC.rvt

2"

LINE OF FURR
METAL EXPANSION JOINT COVER
DOWN WHERE
IT OCCURS

EXPANSION JOINT - CEILING AT ACT


6

PROJECT TITLE
SCALE: 3" = 1'-0"

LINE OF STRUCTURE LINE OF STRUCTURE

CJ CJ
CJ CJ LINE OF CEILING
LINE OF CEILING Project Number:
CJ CJ
CJ CJ 1'-8" 3'-4" OK70374-000

AT SHEET TITLE
AT NON- FIRE-RATED
PARTITION TYPES
FIRE-RATED
4'-6"
7/12/2018 11:28:37 AM

Date:
12 JUL 2018
7'-2"

6"
2'-8"

SEQ. SHEET OF
F.F. ELEV.
F.F. ELEV. 6" 3" 0 6" 2' 1' 0 2' 4' 2' 0 4'

TYPICAL CONTROL JOINT ELEVATION SCALE: 3" = 1'-0" SCALE: 1/2" = 1'-0" SCALE: 1/4" = 1'-0" A-341
7 SCALE: 1/4" = 1'-0"
GH HH AA
GH HH
1'-1"
EE 9 1/2" 11" 2 1/2" METAL
R-19 BATT INSULATION
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
CONCRETE WALL AND RAILING BELOW STUDS @ 16" O.C.
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
ELASTOMERIC SEAL
5/8" BACKER BOARD WALL JOINT COVER
5 1/4" 8 1/2" ADJUSTABLE MASONRY-
VENEER ANCHORS @ 16" O.C. MOISTURE BARRIER ON
8" COLD-FORMED METAL
2 1/2" METAL STUDS 1/4" TILE 1/2" GYPSUM SHEATHING
FRAMING @ 16" O.C. MAX MOISTURE BARRIER ON
@ 16" O.C. 1/2" GYPSUM SHEATHING
5/8" GYPSUM BOARD 1" XPS INSULATION

3 1/4"
6" METAL STUDS
BOARD
3 1/2" UNFACED BATT
OKLAHOMA CITY, OK 73112 405.416.8100

EXTERIOR ELASTOMERIC

1'-0"
INSULATION
SEAL WALL JOINT COVER
10 1/4"

Date Appr
3 5/8" METAL STUDS

7"
@ 16" O.C. 5/8" GYPSUM BOARD
C.H. GUERNSEY & COMPANY

3
3

4 1/2"

1'-4"
3 1/2"

BRICK VENEER
5555 N. GRAND BLVD.

R-19 BATT INSULATION 5/8" GYPSUM BOARD

8"

Description
R-19 BATT INSULATION MOISTURE BARRIER ON
ADJUSTABLE MASONRY-
1/2" GYPSUM SHEATHING
VENEER ANCHORS @ 16" O.C.

2'-7 5/8"
1/4"
2"
MOISTURE BARRIER ON 1" XPS INSULATION 2.1
1/2" GYPSUM SHEATHING
BRICK VENEER
BOARD 2" 8" COLD-FORMED METAL
PLAN DETAIL
FRAMING @ 16" O.C. MAX
10

WINDOW DIM.
WOOD BLOCKING

REFER ELEV.
BRICK VENEER SCALE: 1 1/2" = 1'-0"
8" COLD-FORMED METAL 1" XPS INSULATION

Symbol
FRAMING @ 16" O.C. MAX BOARD
AA

1'-3 3/4"
ADJUSTABLE MASONRY-VENEER
ANCHORS @ 16" O.C.

Appr
MOISTURE BARRIER ON
EXTERIOR EXPANSION JOINT 1/2" GYPSUM SHEATHING
3 1/4" 2" 1'-1" PREFORMED FOAM JOINT SEAL

Date
1" XPS INSULATION

PLAN DETAIL PLAN DETAIL BOARD


R-19 BATT INSULATION

REVISIONS
1 SCALE: 1 1/2" = 1'-0"
2 SCALE: 1 1/2" = 1'-0"
STEEL COLUMN
SPLIT-FACE CMU VENEER

Description
1'-1 7/8" 1'-5 3/4" ADJUSTABLE MASONRY- 5/8" GYPSUM BOARD
VENEER ANCHORS @ 16" O.C.
2'-7 5/8"

2 3/4"
3.8
BB

Symbol
PLAN DETAIL

1'-0 1/4"
11" 4" 8" 3 SCALE: 1 1/2" = 1'-0"
8" COLD-FORMED METAL
FRAMING @ 16" O.C. MAX
5/8" BACKER BOARD
3 5/8" METAL STUDS
@ 16" O.C. BRICK VENEER
1/4" TILE
CC
1" XPS INSULATION 1/4" TILE 5/8" BACKER BOARD 2" WINDOW DIM.
BOARD 1/4" REFER ELEV. EXISTING BUILDING
8"

R-19 BATT INSULATION


PLAN DETAIL
11

B. McCOMBS
S. SPRAGUE
2 SCALE: 1 1/2" = 1'-0"

J. MORGAN

Submitted by:
Reviewed by:
Designed by:
8" COLD-FORMED METAL

J. LOPEZ
Drawn by:
HOSE BIB FRAMING @ 16" O.C. MAX

4"
2.2 2.2 GH HH
5/8" GYPSUM BOARD

R-19 BATT INSULATION 5/8" BACKER BOARD 2"


1'-3"

6" UNFACED BATT INSULATION


R-19 BATT INSULATION

11"
1" XPS INSULATION
BRICK VENEER BOARD

6"

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


MOISTURE BARRIER ON
8" COLD-FORMED METAL 1/2" GYPSUM SHEATHING BRICK VENEER 1/4" TILE 6" METAL STUDS

3/4"
FRAMING @ 16" O.C. MAX @ 16" O.C.
ADJUSTABLE MASONRY- 8" COLD-FORMED METAL
ADJUSTABLE MASONRY- VENEER ANCHORS @ 16" O.C. FRAMING @ 16" O.C. MAX
VENEER ANCHORS @ 16" O.C. ELASTOMERIC SEAL WALL JOINT
MOISTURE BARRIER ON 1" XPS INSULATION COVER
BRICK VENEER
1/2" GYPSUM SHEATHING BOARD
MOISTURE BARRIER ON

17th TRAINING WING


NATURE OF WORK:
1/2" GYPSUM SHEATHING
PLAN DETAIL PLAN DETAIL PLAN DETAIL PLAN DETAIL
4 SCALE: 1 1/2" = 1'-0" 5 SCALE: 1 1/2" = 1'-0" 6 SCALE: 1 1/2" = 1'-0"
12 SCALE: 1 1/2" = 1'-0"
ELASTOMERIC SEAL
EXISTING WALL WITH WALL JOINT COVER
NEW 5/8" GYPSUM GH HH
BOARD 2"
5/8" GYPSUM BOARD
C:\Work\Projects\R18_70374-000_A_SSnyderOKC.rvt

6" UNFACED BATT INSULATION

EXISTING BUILDING B 3.4


BRICK VENEER NEW 6" METAL
STUDS @ 16" O.C.
A 6" METAL STUDS
1" XPS INSULATION
5/8" GYPSUM BOARD @ 16" O.C.
BOARD
5/8" BACKER BOARD

PROJECT TITLE
MOISTURE BARRIER ON
1/4 " TILE ON J-TRIM
1/2" GYPSUM SHEATHING
6" UNFACED BATT INSULATION THINSET MORTAR
METAL EXPANSION JOINT COVER

8" COLD-FORMED METAL 2 1/2" METAL STUDS @ 16" O.C.


PLAN DETAIL
FRAMING @ 16" O.C. MAX
13
8"

6" METAL STUDS @ 16" O.C. SCALE: 1 1/2" = 1'-0"


5/8" GYPSUM BOARD

7 6" UNFACED BATT INSULATION EXISTING WALL


R-19 BATT INSULATION 4 1/2"
Project Number:
5/8" GYPSUM BOARD
7"

6" METAL STUDS


OK70374-000

SHEET TITLE
ALUMINUM STORE FRONT
3.4 PLAN DETAILS
JOINT SEALANT &
BACKING AT CONTROL
JOINTS
7/12/2018 11:28:41 AM

6" METAL STUDS @ 16" O.C. Date:


3.4

4 1/2"
12 JUL 2018
EXISTING BUILDING
5/8" BACKER BOARD

1/4" TILE
SEQ. SHEET OF
EXISTING WALL WITH 1' 6" 0 1'
NEW 5/8" GYPSUM
BOARD
PLAN DETAIL PLAN DETAIL PLAN DETAIL PLAN DETAIL SCALE: 1 1/2" = 1'-0" A-501
7 SCALE: 1 1/2" = 1'-0" 8 SCALE: 1 1/2" = 1'-0" 9 SCALE: 1 1/2" = 1'-0" 14 SCALE: 1 1/2" = 1'-0"
STANDING SEAM 7
MOISTURE BARRIER ON MOISTURE BARRIER
METAL ROOF 1/2" GYPSUM SHEATHING 4"
BRICK VENEER PRE-FINISHED METAL
ICE & WATER 7/8" FURRING CHANNELS @
1" INSULATION BOARD DOWNSPOUT
SHIELD, TYP. 24" O.C. ADJUSTABLE MASONRY-
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
VENEER ANCHORS @ 16" O.C. 1/2" PLYWOOD METAL WALL PANEL
6" COLD-FORMED METAL 5/8" GYPSUM BOARD
FRAMING @ 16" O.C. MAX PRE-FINISHED SHEET METAL
TOP OF STEEL
MORTAR NETTING COUNTER FLASHING W/
114'-3" R-19 BATT INSULATION RECEIVER HEAD
THRU-WALL FLASHING 6" COLD-FORMED
2 LAYERS OF RIGID 6" UNFACED BATT INSULATION
METAL FRAMING @ 16"
INSULATION BOARD 8" COLD-FORMED METAL

FLASHING HT
CAVITY DRAINAGE MAT O.C. MAX
FRAMING @ 16" O.C. MAX
OKLAHOMA CITY, OK 73112 405.416.8100

8" MIN.
5/8" GYPSUM BOARD
BENT STEEL PLATE
R-38 BLOWN CELLULOSE

Date Appr
FINISH FLOOR INSULATION
PREFINISHED METAL SOFFIT ON MOISTURE BARRIER ON 100'-0"
METAL ROOF DECK

2"
1/2" PLYWOOD 1/2" GYPSUM SHEATHING
C.H. GUERNSEY & COMPANY

WEEPS W/ INSECT SPLASH PAN BEYOND


1/2" EXTERIOR 1" INSULATION BOARD
GRADE PLYWOOD MESH @ 24" O.C. ROOF MEMBRANE
BRICK VENEER 8" COLD-FORMED METAL
TAPPERED ROOF INSULATION
5555 N. GRAND BLVD.

FRAMING @ 16" O.C. MAX


EXPOSED CONCRETE

Description
1 1/2" PREFINISHED METAL WALL PANEL ADJUSTABLE MASONRY- 1/2" GYPSUM BOARD COVER BOARD
ON 1/2 PLYWOOD ON 7/8" FURRING R-19 BATT INSULATION FOUNDATION
VENEER ANCHORS @ 16" O.C.
CHANNELS @ 24" O.C. ON 6" COLD- BACKER ROD & SEALANT (2) LAYERS OF RIGID INSULATION
FORMED METAL FRAMING BOARD

CLOSURE TRIM STEEL BEAM METAL ROOF DECKING

VERTICAL DETAIL VERTICAL DETAIL VERTICAL DETAIL

Symbol
PREFINISHED METAL SOFFIT ON 1/2 PLYWOOD
ON 7/8" FURRING CHANNELS @ 24" O.C. ON 6"
2 SCALE: 1 1/2" = 1'-0" 3 SCALE: 1 1/2" = 1'-0" 4 SCALE: 1 1/2" = 1'-0"
COLD-FORMED METAL FRAMING

Appr
VERTICAL DETAIL
1

Date
SCALE: 1 1/2" = 1'-0"

REVISIONS
TOP OF STEEL

Description
GH HH JJ A 114'-3"
ICE & WATER SHIELD,
TYP. R-38 BLOWN CELLULOSE
STANDING SEAM METAL ROOF
1" MI INSULATION
N. TY EXISTING METAL ROOF DECKING
P.
(2) LAYERS OF RIGID 1/2" EXTERIOR GRADE PLYWOOD
INSULATION BOARD 6" COLD-FORMED
PRE-FINISHED METAL GUTTER STRAP METAL FRAMING @ 16"

Symbol
METAL ROOF DECKING O.C. MAX
PRE-FINISHED METAL GUTTER

METAL WALL PANEL 1/2" GLASS-MAT GYPSUM


WALL SHEATHING
STEEL JOIST PRE-FINISHED SHEET METAL COUNTER EXISTING STEEL JOIST
FLASHING W/ RECEIVER HEAD
MOISTURE BARRIER
BENT STEEL PLATE MEMBRANE SHEET CLOSURE EXISTING STANDING SEAM EXISTING STEEL BEAM
SECURED & ADHERED TO WALL METAL ROOF
SUSPENSION WIRE
TOP OF STEEL PRE-FINISHED SHEET METAL PRE-FINISHED METAL TOP OF STEEL
114'-3" EXPANSION JOINT COVER. SIZE TO GUTTER STRAP 114'-3"

B. McCOMBS
S. SPRAGUE
ALLOW MOVEMENT

J. MORGAN

Submitted by:
STEEL BEAM

Reviewed by:
Designed by:
1/2" GYPSUM BOARD

J. LOPEZ
PRE-FINISHED SHEET METAL T-TYPE

Drawn by:
CONTINUOUS CLEAT PRE-FINISHED METAL
FLASHING HT.

GUTTER MOISTURE BARRIER


8" MIN.

ROOF MEMBRANE FLASHING


ROOF MEMBRANE FLASHING 1/2" GLASS-MAT GYPSUM RECESSED AIR CURTAIN
ROOF MEMBRANE WALL SHEATHING
ROOF MEMBRANE
COVER BOARD
2'-0"

STEEL ANGLE STEEL BEAM

FLEXIBLE LINER W/ COMPRESSIBLE COVER BOARD EXISTING METAL PREFINISHED METAL SOFFIT OVER
COLUMN BEYOND INSULATION

CRESSMAN DINING FACILITY EXPANSION


FRAMING GRID SUSPENSION SYSTEM

GOODFELLOW AIR FORCE BASE, TEXAS


3 5/8" COLD-FORMED (2) LAYERS OF RIGID INSULATION (2) LAYERS OF RIGID INSULATION
METAL FRAMING @ 16" BOARD BOARD
O.C. MAX
METAL ROOF DECKING METAL ROOF DECKING
BENT STEEL PLATE STEEL ANGLE
ALUMINUM STOREFRONT
STEEL BEAM STEEL BEAM R-13 BATT INSULATION 4 1/2"

17th TRAINING WING


MOISTURE BARRIER

NATURE OF WORK:
1/2" GYPSUM BOARD OVER GRID
WOOD NAILER ATTACHED TO ROOF SUSPENSION SYSTEM
R-13 BATT INSULATION DECKING. OVERALL THICKNESS TO
MATCH INSULATION
ALUMINUM STOREFRONT

VERTICAL DETAIL VERTICAL DETAIL VERTICAL DETAIL


5 SCALE: 1 1/2" = 1'-0" 6 SCALE: 1 1/2" = 1'-0" 7 SCALE: 1 1/2" = 1'-0"
C:\Work\Projects\R18_70374-000_A_SSnyderOKC.rvt

AA AA

MOISTURE BARRIER ON 6"


7.9 1/2" GYPSUM SHEATHING R-19 BATT INSULATION

PROJECT TITLE
1/2" GLASS-MAT GYPSUM WALL BRICK VENEER
10" SHEATHING 5/8" GYPSUM BOARD THRU-WALL FLASHING GLAZING
1" INSULATION BOARD METAL ROOF DECKING
VERTICAL DETAIL
WINDOW DIM.
REFER ELEV.

ADJUSTABLE MASONRY
VENEER ANCHORS
6" COLD-FORMED METAL FRAMING
ADJUSTABLE MASONRY-
VENEER ANCHORS @ 16" O.C. ALUMINUM FRAME
ICE & WATER SHIELD, TYP. 12 SCALE: 1 1/2" = 1'-0"
@ 16" O.C. MAX STANDING SEAM METAL ROOF
WEATHER BARRIER CAVITY DRAINAGE MAT
RE: REFLECTED BACK ROD AND
THRU-WALL FLASHING CEILING PLAN SEALANT EACH SIDE 1/2" EXTERIOR GRADE PLYWOOD
STEEL BEAM
2"

SPLIT-FACE CMU VENEER 8" COLD-FORMED METAL


SPLIT-FACE CONCRETE FACE
FRAMING @ 16" O.C. MAX PRE-FINISHED METAL GUTTER STRAP Project Number:
BRICK
PRE-FINISHED METAL GUTTER OK70374-000
STUD BOX HEADER (TYP.)
STUD BOX SILL (TYP.)
CAVITY DRAINAGE MAT BACK ROD AND SPLIT-FACE SHEET TITLE
PREFINISHED METAL SOFFIT OVER SEALANT EACH SIDE CMU VENEER
WEEPS W/ INSECT METAL WALL PANEL VERTICAL DETAILS
GRID SUSPENSION SYSTEM
2"

MESH @ 32" O.C. ALUMINUM FRAME 1" INSULATION BOARD 5/8" GYPSUM BOARD 1/2" EXTERIOR GRADE PLYWOOD
WINDOW DIM.
REFER ELEV.
7/12/2018 11:28:45 AM

THRU-WALL FLASHING WEEPS W/ INSECT GLAZING BRICK VENEER R-19 BATT INSULATION 6" COLD-FORMED METAL FRAMING @ 16" Date:
BACKER ROD & SEALANT MESH @ 24" O.C. O.C. MAX 12 JUL 2018
STEEL ANGLE MOISTURE BARRIER ON 8" COLD-FORMED METAL
STEEL LINTEL 1/2" GYPSUM SHEATHING FRAMING @ 16" O.C. MAX

6" ADJUSTABLE MASONRY- SEQ. SHEET OF


VENEER ANCHORS @ 16" O.C.
1' 6" 0 1'

VERTICAL DETAIL VERTICAL DETAIL VERTICAL DETAIL VERTICAL DETAIL SCALE: 1 1/2" = 1'-0" A-521
8 SCALE: 1 1/2" = 1'-0" 9 SCALE: 1 1/2" = 1'-0" 10 SCALE: 1 1/2" = 1'-0" 11 SCALE: 1 1/2" = 1'-0"
SOUND ATTENUATION BLANKETS-
REFER PARTITION TYPES

C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019


C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
DOOR SCHEDULE 5/8" GYP. BD. TYPE 'X' EACH
DOOR FRAME DETAILS SIDE ON METAL STUDS
AT 16" O.C.
PANEL SIZE WIDTH
MARK PANEL 1 WIDTH PANEL 2 WIDTH HEIGHT MATERIAL TYPE HEAD JAMB MATERIAL TYPE HEAD JAMB SILL FIRE RATING HW SET COMMENTS
101A 3'-0" 3'-0" 7'-0" ALUMINUM ALD1 2" 2" ALUMINUM ALF1 5/A-601 6/A-601 7/A-601 0 1 DOOR AND DOOR GLAZING SHALL MEET AT/FP REQUIREMENTS
101B 3'-0" 3'-0" 7'-0" ALUMINUM ALD1 2" 2" ALUMINUM ALF1 8/A-601 9/A-601 N/A 0 2 STUD BOX HEADER (TYP.)

1/4"
103 3'-0" 7'-0" WOOD WDD1 2" 2" HOLLOW METAL HMF1 2/A-601 3/A-601 N/A 0 7
104A 3'-0" 3'-0" 7'-0" ALUMINUM ALD1 2" 2" ALUMINUM ALF1 5/A-601 6/A-601 7/A-601 0 1 DOOR AND DOOR GLAZING SHALL MEET AT/FP REQUIREMENTS
OKLAHOMA CITY, OK 73112 405.416.8100

104B 3'-0" 3'-0" 7'-0" ALUMINUM ALD1 2" 2" ALUMINUM ALF1 8/A-601 9/A-601 N/A 0 2

Date Appr
2"
105 3'-0" 7'-0" WOOD WDD1 2" 2" HOLLOW METAL HMF1 2/A-601 3/A-601 N/A 0 8
106 3'-0" 7'-0" WOOD WDD1 2" 2" HOLLOW METAL HMF1 2/A-601 3/A-601 N/A 0 6 SEALANT EACH SIDE
107 3'-0" 3'-0" 7'-0" WOOD WDD1 2" 2" HOLLOW METAL HMF1 2/A-601 3/A-601 N/A 0 11
C.H. GUERNSEY & COMPANY

110 3'-0" 7'-0" WOOD WDD1 2" 2" HOLLOW METAL HMF1 2/A-601 3/A-601 N/A 0 9 ALUMINUM DOOR
111 3'-0" 7'-0" WOOD WDD1 2" 2" HOLLOW METAL HMF1 2/A-601 3/A-601 N/A 0 10 FRAME

REFER DOOR
112 3'-0" 7'-0" WOOD WDD1 2" 2" HOLLOW METAL HMF1 2/A-601 3/A-601 N/A 0 5

5"
SCHEDULE
5555 N. GRAND BLVD.

113 3'-0" 7'-0" ALUMINUM ALD1 2" 2" ALUMINUM ALF2 2/A-601 3/A-601 N/A 0 4 DOOR AS SCHEDULED

Description
115 3'-0" 3'-0" 7'-0" ALUMINUM ALD1 2" 2" ALUMINUM ALF1 8/A-601 9/A-601 N/A 0 2
FRAME BEYOND

LINE OF WALL BEYOND

GLAZING TYPES

Symbol
RE: DOOR SCHEDULE RE: DOOR SCHEDULE RE: DOOR SCHEDULE MARK COMMENTS
DOOR HEAD
RE: DOOR SCHEDULE RE: DOOR SCHEDULE
2" 2" 2" 2" 2" 2" 1'-10" 2" G1 1/4" CLEAR TEMPERED GLASS
8 SCALE: 3" = 1'-0"

2"
G2 1" INSULATED, LOW-E, LAMINATED, TEMPERED, TINTED TO MATCH EXISTING

2"

2"
GLASS. ALL NEW EXTERIOR GLAZING SHALL MEET ATFP REQUIREMENTS

Appr
5"

SOUND ATTENUATION BLANKETS-


5" 2"
REFER PARTITION TYPES
1/4" NOTE: DETAIL 10
RE: DOOR SCHEDULE

RE: DOOR SCHEDULE

RE: DOOR SCHEDULE


RE: DOOR SCHEDULE

RE: DOOR SCHEDULE

Date
5" 5" G1 NOT USED

REVISIONS
G1 AT INTERIOR
G2 AT EXTERIOR

Description
G1
DOOR AS SCHEDULED FF
10"

ALUMINUM DOOR
TYPE WDD1 TYPE ALD1 TYPE ALF2 FRAME
TYPE HMF1 TYPE ALF1
WOOD ALUMINUM HM FRAME ALUMINUM FRAME ALUMINUM FRAME CONT. SEALANT EACH SIDE
(HEAVY)
PROVIDE DOUBLE STUDS

Symbol
FRAME TYPES @ JAMBS EXTEND TO 5/8" GYP. BD. TYPE 'X' EACH
DOOR TYPES SIDE ON METAL STUDS
STRUCTURE ABOVE -
AT 16" O.C.

WINDOW DIM.
FASTEN STUDS TOGETHER

REFER ELEV.
DOOR AND FRAME TYPES 1'-9" 2'-7" 2'-11"
16'-0"
2'-11" 2'-7" 1'-9" 2'-2"
7'-6"
2'-2" 2'-3" DOOR JAMB
SCALE: 1/4" = 1'-0" 9'-4" 2'-8" 5" 2" 2" 2" 2" 2" 5" 5" 2" 2" 2"
9 SCALE: 3" = 1'-0"
2'-11" 2'-10" 2'-11" 2'-4" 7

2"
7
2" 2" 2" 2" 2" 2" 6'-0"
A-521 A-521

1/4"
9 1'-9" 1'-10" 1'-9" 8" METAL STUDS
9

B. McCOMBS
2"
2"

S. SPRAGUE
2" 2" 2" 2"

J. MORGAN

Submitted by:
Reviewed by:
A-521

Designed by:
A-521

J. LOPEZ
Drawn by:
11 6" UNFACED BATT
2"
2"

3'-4"

3'-4"
G2 G2 G2 G2 G2 G2 G2 G2 G2 INSULATION
A-601
5

2"
2"

2"
A-501 5 5/8" GYPSUM BOARD
4'-0"

G2 G2 G2 14
5'-7"

5'-7"
5'-3"

G1 A-501 A-501 14 2 11
10'-8"

10'-8"

3'-10"
3'-6"
3'-11"

3'-11"
5 A-501 G1 G1 G1 A-601
2"

G2 G2 G2 G2 A-501 G2 G2 G2
A-601
1'-1"

CRESSMAN DINING FACILITY EXPANSION


G2 G2 G2
2"

2"
2"

GOODFELLOW AIR FORCE BASE, TEXAS


2"

2"
6
10 10 11 WINDOW JAMB/SILL
3'-4"

3'-4"

3'-4"
A-601
11
2'-9"

2'-9"
G2 G2 G2 G2 G2 G2 G2
A-521 A-521 A-601 SCALE: 1 1/2" = 1'-0"
2"

2"
FINISH FLOOR FINISH FLOOR FINISH FLOOR FINISH FLOOR FINISH FLOOR
100'-0" 100'-0" 100'-0" 100'-0" 100'-0"

17th TRAINING WING


TYPE A TYPE B 12 TYPE C TYPE D TYPE E

NATURE OF WORK:
12
ALUMINUM FRAME STOREFRONT ALUMINUM FRAME STOREFRONT ALUMINUM FRAME STOREFRONT ALUMINUM FRAME STOREFRONT ALUMINUM FRAME STOREFRONT
A-521 A-521

WINDOW ELEVATIONS ADJACENT WALL WHERE


SCALE: 1/4" = 1'-0" SHOWN ON PLAN

PROVIDE DOUBLE STUDS


C:\Work\Projects\R18_70374-000_A_SSnyderOKC.rvt

SOUND ATTENUATION BLANKETS- @ JAMBS EXTEND TO GLAZING RE:


REFER PARTITION TYPES 4 1/2"
STRUCTURE ABOVE - ELEVATIONS
FASTEN STUDS TOGETHER
5/8" GYP. BD. TYPE 'X' EACH
SIDE ON METAL STUDS GLAZED ALUMINUM
AT 16" O.C. REFER DOOR 2" 4" GLAZING RE: STORE FRONT
SCHEDULE ELEVATIONS

10"
STUD BOX HEADER (TYP.) GLAZED ALUMINUM
GLAZED ALUMINUM DOOR DOOR RE: SCHEDULE
RE: SCHEDULE
5 3/4" @ 3 5/8" MTL. STUDS
10 1/4" @ 8" MTL. STUDS
8 1/4" @ 6" MTL. STUDS

SEALANT EACH SIDE GLAZED ALUMINUM NEW ALUMINUM RAMP TYPE

PROJECT TITLE
STORE FRONT THRESHOLD SET IN MASTIC

4 1/2"
2"

1/4"
2"

STRUCTURAL SLAB
HOLLOW METAL DOOR
FRAME
REFER DOOR
SCHEDULE

DOOR STOP
DOOR AS SCHEDULED 2" 5"

1/4"
5/8" GYP. BD.
5"

NOTE: DETAIL 4
SCHEDULE

EA. SIDE ON MTL.


RE: DOOR

JAMB ANCHORS NOT USED


STUDS @ 16" O.C.
Project Number:
HOLLOW METAL GLAZED ALUMINUM DOOR
FRAMES SEALANT EA. SIDE RE: SCHEDULE
5 3/4" @ 3 5/8" MTL. STUDS OK70374-000

8 1/4" @ 6" MTL. STUDS SHEET TITLE

10 1/4" @ 8" MTL. STUDS DOOR SCHEDULE


7/12/2018 11:28:48 AM

Date:

DOOR HEAD DOOR JAMB DOOR HEAD DOOR JAMB DOOR SILL 12 JUL 2018

2 SCALE: 3" = 1'-0" 3 SCALE: 3" = 1'-0" 5 SCALE: 3" = 1'-0" 6 SCALE: 3" = 1'-0" 7 SCALE: 3" = 1'-0"
SEQ. SHEET OF
6" 3" 0 6" 4' 2' 0 4'

SCALE: 3" = 1'-0" SCALE: 1/4" = 1'-0" A-601


ROOM FINISH SCHEDULE
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
ROOM NUMBER ROOM NAME FLOOR FIELD BASE NORTH WALL FINISH SOUTH WALL FINISH EAST WALL FINISH WEST WALL FINISH WALL ACCENTS CEILING FIELD CEILING ACCENTS REMARKS
101 VESTIBULE CPT3 RB1/TS2 CT1/CT2/CT3/CT4/CT6 EXISTING/PT1 EXISTING/PT1 EXISTING/PT1 - ACT1 PT2 -
102 DINING LVT1/CPT1 RB1 CT1/CT2/CT3/CT4/CT5/PT1 CT1/CT2/CT3/CT4/CT5/PT1 CT1/CT2/CT3/CT4/CT5/PT1 CT1/CT2/CT3/CT4/CT5/PT1 - ACT1 ACT2 CERAMIC TILE (CT) WAINSCOT IS ALT #3. BASE BID SHALL BE PAINTED GYPSUM BOARD WITH A CHAIR RAIL (CR) MOUNTED AT 32" AFF TO BOTTOM OF CR.
103 PRIVATE DINING CPT2 RB1 PT1/CR PT1/CR PT1/CR PT1/CR - ACT1 -
104 VESTIBULE CPT3 RB1 CT1/CT2/CT3/CT4/CT/PT1 CT1/CT2/CT3/CT4/CT5/PT1 CT1/CT2/CT3/CT4/CT5/PT1 CT1/CT2/CT3/CT4/CT5/PT1 - ACT1 PT2
105 FAMILY TOILET CT7 TS2 CT1 CT1 CT1 CT1 - PT2 -
OKLAHOMA CITY, OK 73112 405.416.8100

106 COMM SC1 RB1 PT1 PT1 PT1 PT1 - OPEN TO STRUCTURE - GENERAL NOTES:

Date Appr
107 MECHANICAL SC1 RB1 PT1 PT1 PT1 PT1 - OPEN TO STRUCTURE
108 EXISTING WOMEN'S EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING 1. REFER SHEET A-141 REFLECTED CEILING PLANS FOR CEILING HEIGHTS AND
109 EXISTING JAN. EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING MATERIAL LOCATIONS.
C.H. GUERNSEY & COMPANY

110 STORAGE CPT2 RB1 PT1 PT1 PT1 PT1 - ACT1 - - 2. INTERIOR HOLLOW METAL DOOR FRAMES TO BE PAINTED PT2 UNLESS NOTED
111 CONF. ROOM CPT2 RB1 PT1 PT1 PT1 PT1 - ACT1 - OTHERWISE.
3. LVT1 TO BE INSTALLED IN BRICK PATTERN.
112 OFFICE CPT2 RB1 PT1 PT1 PT1 PT1 - ACT1 -
4. REFER SHEET A-701 FOR LOCATION OF SIGNS.
5555 N. GRAND BLVD.

113 STUDENT ADMIN. CPT2 RB1 PT1 PT1 PT1 PT1 - ACT1 5. REFER SHEET A-701 FOR LOCATION OF FLOOR TRANSITIONS.

Description
114 EXISTING MEN'S EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING 6. VERIFY WITH OWNER ALL SIGNAGE TEXT PRIOR TO MANUFACTURING SIGNS.
115 CORRIDOR CT8 TS2/RB1 CT1/CT2/CT3/CT4/CT5/PT1 CT1/CT2/CT3/CT4/CT5/PT1 CT1/CT2/CT3/CT4/CT5/PT1 CT1/CT2/CT3/CT4/CT5/PT1 - ACT1 7. INSTALL SIGNS SN2 AND SN5 BACK-TO-BACK ON GLASS.
116 EXISTING DINING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING
117 EXISTING KITCHEN EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING
118 PREPARATION ROOM EF1 CT7 CT6 CT6 CT6 CT6 - ACT3 - ALT #1. BASE BID, NO WORK.

Symbol
Appr
INTERIOR MATERIALS SCHEDULE

Date
CODE PRODUCT SPECIFICATION MANUFACTURER STYLE COLOR SIZE NOTES CONTACT

REVISIONS
TS5 TRANSITION 09 65 13 JOHNSONITE RESILIENT T-MOLDING CE-XXX-A PEPPERCORN 1 1/16" WIDE
1. CEILING
ACT1 ACOUSTICAL CEILING TILE 09 51 13 ARMSTRONG CIRRUS #577, FIRE RESISTIVE, BEVELED TEGULAR EDGE WITH SUPRAFINE 9/16" SUSPENSION SYSTEM WH WHITE 24" X 24" X 3/4"

Description
ACT2 WOOD GRID CEILING 09 54 26 ARMSTRONG WOODWORKS OPEN CELL VECTOR LINEAR PANELS #6624 WITH WOOD PERIMETER TRIM NATURAL VARIATIONS LINEAR WALNUT 24" X 24" X 2 1/4" DINING ROOM
ACT3 ACOUSTICAL CEILING TILE 09 51 13 ARMSTRONG KITCHEN ZONE #673, SQUARE LAY-IN 15/16" SUSPENSION SYSTEM WHITE
PT1 PAINT 09 91 23 BENJAMIN MOORE INTERIOR ACRYLIC PAINT: REGAL INTERIOR PAINT - SEMIGLOSS OC-25 CLOUD COVER - GENERAL CEILING PAINT
2. WALL
CR CHAIR RAIL 10 26 00 CS ACROVYN WOOD CRASH RAIL 451 WALNUT 5 1/2" HGH INSTALL AT 32" AFF TO BOTTOM OF CHAIR RAIL ALONG PERIMETER OF PRIVATE
DINING ROOM
CT1 WALL TILE 09 30 13 CROSSVILLE STUDIOS IMOLA COLORBODY PORCELAIN TILE; UPDATE WHITE 12"X24"

Symbol
CT2 WALL TILE 09 30 13 CROSSVILLE STUDIOS IMOLA COLORBODY PORCELAIN TILE; UPDATE WHITE 12"X12"
CT3 WALL TILE 09 30 13 CROSSVILLE STUDIOS IMOLA COLORBODY PORCELAIN TILE; UPDATE WHITE 2"X2" MOSAIC
CT4 WALL TILE 09 30 13 CROSSVILLE BUENOS AIRES MOOD, POLISHED POLO, POLISHED 12"X24"
CT5 WALL TILE 09 30 13 CROSSVILLE BUENOS AIRES MOOD, POLISHED POLO, POLISHED 6"X36"
CT6 WALL TILE 09 30 13 DAL TILE SEMIGLOSS WALL TILE K101 WHITE 6" X 6" TO MATCH EXISTING KITCHEN WALL TILE, FULL HEIGHT.
CT9 WALL TILE 03 30 00 CROSSVILLE BUENOS AIRES MOOD, UNPOLISHED POLO, UNPOLISHED 12"X12"
GRT1 GROUT 09 30 13 CUSTOM BUILDING PRODUCTS FUSION PRO SINGLE COMPONENT TILE GROUT #386 OYSTER GRAY - FOR USE WITH WALL TILE
GRT3 GROUT 09 30 13 CUSTOM BUILDING PRODUCTS FUSION PRO SINGLE COMPONENT TILE GROUT #381 BRIGHT WHITE - FOR USE WITH PREP AREA SEMIGLOSS WALL TILE AND WALL BASE
HPL2 METAL LAMINATE 09 77 00 CHEMETAL INTERIOR METAL LAMINATE #614 BEOWULF AR FOR USE WITH FRY REGLET PREFINISHED INTERIOR PANEL SYSTEM, REFER
4/A-221

B. McCOMBS
PT1 PAINT 09 91 23 BENJAMIN MOORE INTERIOR ACRYLIC PAINT; REGAL INTERIOR PAINT -SEMI-GLOSS OC-25 CLOUD COVER - GENERAL FIELD PAINT

Submitted by:
Reviewed by:
Designed by:
PT2 PAINT 09 91 23 SHERWIN WILLIAMS DTM ACRYLIC COATING, PRO INDUSTRAIL DTM ACRYLIC - SEMI-GLOSS SW7505 MANOR HOUSE - HM DOOR FRAMES

Designer

Checker
Drawn by:
Author
S1 SIGNAGE 101423.16 INPRO CORP. ROOM IDENTIFICATION SIGNAGE TBD AS INDICATED REFER SHEET A-701.
TS3 TRANSITION EDGE 09 30 13 SCHLUTER QUADEC TSOB BRONZE (TRENDLINE) - FOR TOP CAP AT TILE WAINSCOT AND OUTSIDE CORNERS
PROTECTION
3. BASE
CT7 CERAMIC WALL BASE 09 30 13 AMERICAN OLEAN SANITARY COVE BASE S-3419T 0090 WHITE 6" X 6" PREP AREA WALL BASE
MB1 METAL WALL BASE 09 77 00 FRY REGLET FLAT STOCK ALUMINUM ANODIZED ALUMINUM TO MATCH REVEALS IN PREFINISHED PANEL SYSTEM 4" HIGH FEATURE WALLS: PREFINISHED INTERIOR PANEL SYSTEM REFER 4/A-221 AND
5/A-221.
RB1 RUBBER BASE 09 65 13 JOHNSONITE RESILIENT WALL BASE; 4" HIGH STRAIGHT TOE PEPPERCORN 4" HIGH

CRESSMAN DINING FACILITY EXPANSION


TS1 TRANSITION COVE 09 30 13 SCHLUTER DILEX AHK COVE SHAPED PROFILE TSOB BRONZE (TRENDLINE) - FOR TRANSITION AT WALL, WALL TILE TO RESILIENT

GOODFELLOW AIR FORCE BASE, TEXAS


TS2 TRANSITION COVE 09 30 13 SCHLUTER DILEX AHKA COVE SHAPED PROFILE TSOB BRONZE (TRENDLINE) - FOR TRANSITION AT WALL, WALL TILE TO FLOOR TILE
4. FLOOR
CPT1 CARPET TILE 09 68 13 J&J INVISION KINETEX, TIMBER WITH PREFIX ADHESIVE 1926 BUCKTHORN 12"X48"
CPT2 CARPET TILE 09 68 13 J&J INVISION CRAFTWORK MODULAR 2205 QUILTER 24"X24"
CPT3 CARPET TILE 09 68 13 J&J INVISION INCOGNITO WALK-OFF MODULAR 1843 WIRETAP 24" X 24" APPROX.
CT8 FLOOR TILE 09 30 13 CROSSVILLE PORCELAIN STONE TILE; SPEAK EASY AV281 SIDECAR 8" X 36"
EF1 EPOXY QUARTZ FLOOR 09 67 20 EVERLAST EPOXY SYSTEMS INC. EVERLAST FLOOR NORTHWOOD AR COLOR TO MATCH EXISTING FLOORING IN KITCHEN

17th TRAINING WING


NATURE OF WORK:
SYSTEM
GRT2 GROUT 09 30 13 CUSTOM BUILDING PRODUCTS GROUT, REFER SPECIFICATION 093000 #540 TRUFFLE FOR USE WITH FLOOR TILE
LVT1 LUXURY VINYL TILE 09 65 19 MOHAWK ENHANCED RESILIENT TILE; MOLVENO RIGID CORE ERT CARAIBE 8" X 60" PLANKS
SC1 CONCRETE SEALER 03 30 00 TBD SEALED CONCRETE CLEAR
TS4 TRANSITION 09 30 13 SCHLUTER RENO-TK REDUCER ATK125ABGB BRUSHED ANTIQUE BRONZE ANODIZED 1/2" TRANSITION FROM CERAMIC TILE TO LVT OR CARPET
5. MILLWORK
HPL1 HIGH PRESSURE 06 41 16 WILSONART HIGH PRESSURE LAMINATE, AEON SCRATCH RESISTANCE, HD LAMINATE, ALIGNED TEXTURE MORRIS OAK 17005K-57 - MILLWORK CABINETS AND DOORS
LAMINATE
C:\Work\Projects\R18_70374-000_A_SSnyderOKC.rvt

SSM1 SOLID SURFACE 12 36 61.16 WILSONART SOLID SURFACE KIMBERLITE 9215CE -


6. WINDOWS
RS1 WINDOW ROLLER SHADES 12 24 13 HUNTER DOUGLAS CONTRACT DUAL ROLLER WINDOW SHADES, MANUAL BLACKOUT FABRIC: SHEERWEAVE 7000, 0% OPENNESS, WHITE / PRIMARY AS REQUIRED ALL WINDOWS
FABRIC: GREENSCREEN SPECTRA, 10% OPENNESS, CREAM
7. DOORS
WD WOOD DOORS 08 14 16 TBD DOOR WOOD STAIN TO MATCH APPROVED HIGH PRESSURE LAMINATE ON CABINETS MATCH APPROVED HIGH PRESSURE LAMINATE ON CABINETS -

10"

PROJECT TITLE
8" 6" 6" 8"
SIGNAGE SCHEDULE
RAISED TACTILE RAISED TACTILE RAISED TACTILE
PICTOGRAMS DOOR NUMBER SIGN TYPE SIGN TEXT
ROOM NUMBER ROOM NUMBER HOURS OF
#### #### 101A SN2 EXIT

2"
OPERATION 101A SN5 EXIT
GRADE 2 BRAILLE GRADE 2 BRAILLE
MILITARY
EXIT
RAISED TACTILE 104A SN2 EXIT
8"

OFFICE
1 1/2"

MONDAY X-X
TEXT
6"

6"

6"

6"
104A SN5 EXIT
TEXT WINDOW
RAISED TACTILE
TEXT
TRAINING TUESDAY
WEDNESDAY
X-X
X-X 105 SN1 FAMILY TOILET
RAISED TACTILE
LETTERING GRADE 2 BRAILLE
INSERT OCCUPANT LEADERS
THURSDAY
FRIDAY
X-X
X-X 112 SN3 COORDINATE WITH OWNER
Project Number:

FAMILY RESTROOM
3/4"

OCCUPANT'S TITLE SATURDAY X-X


113 SN4 MILITARY TRAINING LEADERS OK70374-000
GRADE 2 BRAILLE SUNDAY X-X

GRADE 2 BRAILLE SHEET TITLE

ROOM FINISH SCHEDULE

FAMILY RESTROOM PICTOGRAM (SN1) EXIT (SN2) EMPLOYEE IDENTIFICATION (SN3) ROOM IDENTIFICATION (SN4) HOURS OF OPERATION (SN5)
7/12/2018 11:28:49 AM

Date:
12 JUL 2018

SIGNAGE PICTOGRAMS
1 SCALE: 3" = 1'-0" SEQ. SHEET OF
6" 3" 0 6"

SCALE: 3" = 1'-0" A-641


3
A-301
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

AA BB CC DD EE FF GH HH JJ A B
OKLAHOMA CITY, OK 73112 405.416.8100

GENERAL NOTES:

Date Appr
1. INSTALL FLOORING MATERIAL UNDER APPLIANCES AND KNEESPACE AREAS
UNLESS NOTED OTHERWISE.
C.H. GUERNSEY & COMPANY

9 9 2. REFER TO 1/A-641 FOR SIGNAGE DETAILS.


5555 N. GRAND BLVD.

7.9 8

Description
7.8 7.9
SN5 FLOOR FINISH LEGEND:
7.8
104A CPT-1

Symbol
SN2
VESTIBULE CPT-2
104
TS4
CPT-3

Appr
7

Date
CT-1
ALIGN FLOORING WITH TS4
COLUMN AND WALL SN1 PLANK DIRECTION
6'-0"

REVISIONS
LVT-1
105 6

Description
SC-1
FAMILY TOILET
105
EXISTING
MECHANICAL

PLANK DIRECTION
5.6 107 5.6

Symbol
COMM
106 EXISTING WOMEN'S
108

PATTERN DIRECTION EXISTING JAN.


109
5 PRIVATE DINING DINING OFFICE CONF. ROOM STORAGE
5
103 102 112 111 110 CORRIDOR
115

B. McCOMBS
S. SPRAGUE

J. MORGAN
S. SNYDER

Submitted by:
Reviewed by:
Designed by:

Drawn by:
6'-6" 112
TYP EXISTING MEN'S 4
SN3
114

STUDENT ADMIN.
3.8 ALIGN FLOORING 3.8
113
WITH WALL
EPOXY FLOORING TO MATCH
EXISTING KITCHEN FLOOR

CRESSMAN DINING FACILITY EXPANSION


TS4

GOODFELLOW AIR FORCE BASE, TEXAS


3.4 113 3.4
TS4
ALIGN FLOORING WITH SN4 PLANK DIRECTION
COLUMN AND WALL TS4

17th TRAINING WING


NATURE OF WORK:
3
VESTIBULE
101 PREPARATION ROOM
118
SN2

101A
2.2
2.2
C:\Work\Projects\R18_70374-000_A_SSnyderOKC.rvt

SN5
2.1 FLOOR FINISH LEGEND
2.1
2
EF1

1 1
EXIST

PROJECT TITLE
FINISH PLAN AREA-B (ALT #1)
2 SCALE: 1/8" = 1'-0"

AA BB CC DD EE FF GH HH 3
JJ Project Number:
A-301
OK70374-000

SHEET TITLE

FINISH AND SPECIALTIES PLAN

FINISH PLAN AREA-A


1
7/12/2018 11:28:51 AM

Date:
SCALE: 1/8" = 1'-0" 12 JUL 2018

EXPANSION EXISTING
PLAN NORTH SEQ. SHEET OF
8' 4' 0 8'

SCALE: 1/8" = 1'-0" A-701


KEY PLAN
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

GENERAL NOTES:
OKLAHOMA CITY, OK 73112 405.416.8100

Date Appr
1. FURNITURE, FIXTURES AND EQUIPMENT ARE SHOWN FOR COORDINATION
PURPOSES ONLY.
2. FURNITURE & A/V ARE NOT PART OF THE CONSTRUCTION CONTRACT.
C.H. GUERNSEY & COMPANY

3. FOOD SERVICE EQUIPMENT SHALL BE PROCURED AND INSTALLED BY THE


GENERAL CONTRACTOR.
4. A SCHEDULE FOR AUDIO-VISUAL EQUIPMENT IS AVAILABLE ON SHEET
AV101.
5555 N. GRAND BLVD.

5. PROVIDE CONCEALED, FIRE-TREATED WOOD BLOCKING (PLYWOOD

Description
ART4 C4 C4 C4 C4 C4 C4
PANELS) AT LOCATIONS OF OWNER-PROVIDED MONITORS IN DINING 104.
T2 T2 T2 TV - IN AV BID. COORDINATE WITH OWNER EXACT LOCATIONS AND INSTALL WITH
C4 C4 C4 C4 C4 C4 BOTTOM OF TV AT 6'-8" AFF. IF STUD DOES NOT FALL AT CENTER OF
C5 C5 C5 MOUNTING LOCATION, BLOCK 5 BAYS AS REQUIRED TO PROVIDE A
C4 C4 C4 C4 C4 C4
MINIMUM BACKING WIDTH OF 32" ON EACH SIDE OF THE CENTER OF
T3 T2 T2 T2 MOUNTING LOCATION. OVERALL HEIGHT OF PLYWOOD PANELS IS TO BE
C4 C4 C4 C4 C4 C4 24" AND IS TO BE CENTERED ON MOUNTING LOCATION. BLOCKING IS TO
VESTIBULE
C5 C5 C5 SUPPORT 150 LBS.
104

Symbol
C4 C4 C4 C4 C4 C4 6. ALL OTHER TVS SHALL BE MOUNTED WITH PRE-MANUFACTURED IN-WALL
T2 T2 T2 HEADER, FOOTER AND WALL BOX PROVIDED BY OWNER.
C4 C4 C4 C4 C4 C4
TV - IN AV BID.
REFER 7/A-221 FOR TV

Appr
C5 C5 C5
MOUNTING HEIGHT TYP.
T3
FURNITURE SCHEDULE

Date
C5 C5 C5 C4 C4 C4 C4 C4 C4
T2 T2 FAMILY TOILET MARK DESCRIPTION COMMENTS CFCI OFOI
T2

REVISIONS
105 Teem
C4 C4 C4 C4 C4 C4 SN6 ART1 40" FRAMED ART INSTALL 57" AFF TO CENTERLINE YES
MECHANICAL ART2 40" FRAMED ART INSTALL 57" AFF TO CENTERLINE YES

Description
TV - IN AV BID
SN7
107 ART3 40" FRAMED ART INSTALL 57" AFF TO CENTERLINE YES
C4 C4 C4 C4 C4 C4 C4 C4 ART4 40" FRAMED ART INSTALL 57" AFF TO CENTERLINE YES
MB1 T2 T2 T2 T2 SN7 BB1 TACK BOARD PRIVATE OFFICE YES
COMM
C3 C4 C4 C4 C4 C4 C4 C4 C4 EXISTING WOMEN'S SN6 C1 TASK/CONFERENCE CHAIR YES
106
108 C2 GUEST CHAIR YES
C3 C3 C3 TASK/CONFERENCE CHAIR YES

Symbol
C4 C4 C4 C4 C4 C4 C4 C4 C4 METAL DINING CHAIR YES
C3 C3 S1 EXISTING DINING EXISTING KITCHEN
PRIVATE DINING T2 T2 T2 T2 TB1 C5 METAL DINING CHAIR YES
3 A-731 116 117
C3 103 C3 ART2 C3 C3 EXISTING JAN. D1 PRIVATE OFFICE SUITE YES
C4 C4 C4 C4 C4 C4 C4 C4 OFFICE
109 D2 OPEN OFFICE WORKSTATION YES
DINING C1 112
C3 T1 C3 STORAGE CORRIDOR FS FOOD SERVICE EQUIPMENT CONTRACTOR TO PROVIDE FOOD YES
102 D1 C3 C3
110 115 SERVICE EQUIPMENT
C3 C3 C4 C4 C4 C4 C4 C4 C4 C4 EXISTING FLAT MB1 MARKER BOARD PRIVATE DINING YES
ART1
T2 T2 T2 T2 SCREEN TO BE S1 LATERAL FILE 3 DRAWER, 30" WIDE YES
C3 C3 C2 RELOCATED S2 AV CABINET COORDINATE INSTALLATION OF AV YES
C4 C4 C4 C4 C4 C4 C4 C4
EXISTING MEN'S RACK WITH AV INTEGRATOR
C3 C3 SN6 10"H X 36"W ACRYLIC SIGN WITH APPLIED ACRYLIC SIGNS FOR BIOGRAPHIES
CONF. ROOM S1 114

B. McCOMBS
BB1 SN6

S. SPRAGUE
TV - IN AV S2 LETTERS MOUNTED WITH STANDOFFS PURCHASED AS PART OF ART

J. MORGAN
S. SNYDER
C3 111

Submitted by:
Reviewed by:
C4 C4 C4 C4 C4 C4 C4 C4

Designed by:
BID COPIER NIC BUDGET
T2 T2 T2 T2 SN7

Drawn by:
SN7 8-1/2" X 11" CHANGABLE GRAPHIC INSERT WITH SIGNS FOR BIOGRAPHIES YES
C2 C2 C2 ALUMINUM FRAME SIGN PURCHASED AS PART OF ART
C4 C4 C4 C4 C4 C4 C4 C4 R R R

R
R

R
STUDENT ADMIN. BUDGET
113 SN6 T1 CONFERENCE TABLE, BOAT SHAPE, 192" X 55" YES
C1
T2 DINING TABLE 30" X 60" YES
C4 C4 C4 C4 C4 C4 C1 C1
T2 T2 T2 D2 D2 SN7 T3 DINING TABLE 30" X 96" YES
D2
C5 C5 C5 TB1 TACK BOARD PRIVATE OFFICE YES

L
L
L

C4 C4 C4 C4 C4 C4
T3

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


TV - IN AV BID
C5 C5 C5 TV - IN AV BID.
VESTIBULE REFER 7/A-221 FOR TV
101 MOUNTING HEIGHT TYP.
C4 C4 C4 C4 C4 C4
T2 T2 T2
C5 C5 C5 C4 C4 C4 C4 C4 C4
NOTE: KITCHEN EQUIPMENT IS CONTRACTOR
T3

17th TRAINING WING


C4 C4 C4 C4 C4 C4 FURNISHED, CONTRACTOR INSTALLED.

NATURE OF WORK:
T2 T2 T2
C5 C5 C5 C4 C4 C4 C4 C4 C4
ART3 C4 C4 C4 C4 C4 C4
T2 T2 T2 CART CART CART

CART
C4 C4 C4 C4 C4 C4 TV - IN AV BID.
(5) x A556BC

PREP TABLE
PREPARATION ROOM
(1) x FSS-366 118
C:\Work\Projects\R18_70374-000_A_SSnyderOKC.rvt

(1) x FSS-3612 (1) x RRI332LUT-FHS

PREP TABLE
CART REFRIGERATOR

(1) x WS-15-144 SHELF

FURNITURE PLAN AREA-A EQUIPMENT PLAN AREA-B (ALT #1)

PROJECT TITLE
1 SCALE: 1/8" = 1'-0" 2 SCALE: 1/8" = 1'-0"

Project Number:
4'-2" 3'-0" 4'-1 1/4" 3'-0" 4'-2 1/8" 4'-2" 3'-0" 4'-1 1/4" 3'-0" 4'-2"
OK70374-000
SN6 SN6 SN6 SN6
SHEET TITLE
1'-8"

SN7 SN7 SN7 SN7 FURNITURE AND EQUIPMENT PLAN


1'-4"
7/12/2018 11:28:55 AM

Date:
12 JUL 2018
3'-8"

EXPANSION EXISTING PLAN NORTH


SEQ. SHEET OF
8' 4' 0 8'

INTERIOR ELEVATION - CORRIDOR 115 SCALE: 1/8" = 1'-0" A-731


3 SCALE: 1/4" = 1'-0" KEY PLAN
C.H. GUERNSEY & COMPANY
7/12/2018 11:29:26 AM C:\Work\Projects\R18_70374-000_A_SSnyderOKC.rvt 5555 N. GRAND BLVD.
OKLAHOMA CITY, OK 73112 405.416.8100
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

2
1

SCALE:
SCALE:

SOUTH ISOMETRIC
NORTH ENTRANCE PERSPECTIVE

ALT #1

PROJECT TITLE Designed by:


SEQ.

S. SPRAGUE
Date:

NATURE OF WORK: Drawn by:


CRESSMAN DINING FACILITY EXPANSION S. SNYDER
SHEET TITLE
Project Number:

SHEET

17th TRAINING WING Reviewed by:


12 JUL 2018
OK70374-000

J. MORGAN
A-801

GOODFELLOW AIR FORCE BASE, TEXAS


PERSPECTIVE VIEWS

Symbol Description Date Appr


Submitted by:
OF

B. McCOMBS REVISIONS Symbol Description Date Appr


C.R. ENGINEERING: #F-6671 EXPIRES JUNE 30, 2019

A
S www.poolefire.com

FIRE ALARM LEGEND GENERAL FIRE ALARM NOTES


GENERAL

Date Appr
SYMBOL DESCRIPTION 1. THE CONTRACTOR SHALL CAREFULLY REVIEW ALL APPLICABLE DESIGN CRITERIA, THESE DRAWINGS,
s AOM s AIM AIM AIM F AND THE PROJECT SPECIFICATIONS FOR IMPORTANT QUALIFICATION, DEFINITION, SUBMITTAL, PRODUCT,
OLATHE, KS 66062 913.829.8650

FAA CO
AREA WIDE MASS NOTIFICATION FMCP FIRE ALARM/MASS NOTIFICATION CONTROL PANEL (MONACO MAAP-X PANEL) INSTALLATION, AND TESTING REQUIREMENTS.
MESSAGES ARE SENT FROM LOC RTS VS WF FES 2. ALL SUBMITTALS, INSTALLATION, AND TESTING SHALL BE COMPLETED IN A NEAT, WORKMAN-LIKE
POOLE FIRE PROTECTION

THE BASE COMMAND POST MANNER.


THROUGH THE ATI SYSTEM ATI TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR
19910 W. 161ST STREET

SEE FIRE ALARM 3. PRODUCT, DESIGN, INSTALLATION, AND TESTING ALTERNATE APPROACHES AND/OR SUBSTITUTIONS WILL
GENERAL NOTE 5 BE CONSIDERED BY THE ENGINEER IF THE CONTRACTOR PROVIDES WRITTEN, WELL-DOCUMENTED,
FMCP ACOUSTIC TECHNOLOGY, INC. PANEL USED TO COMMUNICATE WITH THE BASE ENGINEERING-BASED SUBSTANTIATION FOR PROPOSED ALTERNATIVE.

Description
ATI
AREA WIDE MASS NOTIFICATION SYSTEM 4. FINAL MASS NOTIFICATION SYSTEM PRE-RECORDED MESSAGES TO BE PROGRAMMED PER THE
TO DEDICATED 120V AC CIRCUIT TO BE COMPLIANT WITH DIRECTION OF THE GOODFELLOW AIR FORCE BASE FIRE DEPARTMENT. SEE UFC 4-021-01 APPENDIX B
TVSS FAA FIRE ALARM ANNUNCIATOR FOR SAMPLE PRE-RECORDED MESSAGES.
BREAKER, MARKED RED, MONACO D21 RADIO FIRE
LABELED, AND SECURED FROM ALARM MONITORING BASE 5. NEW FIRE ALARM/MASS NOTIFICATION SYSTEM SHALL INCORPORATE MONITORING OF EXISTING GAS AND
UNAUTHORIZED ACCESS STATION LOC LOCAL OPERATING CONSOLE ELECTRIC UTILITY SHUT-OFF VALVES. NEW SYSTEM SHALL MAINTAIN IDENTICAL FUNCTIONS AS EXISTING
SYSTEM AS IT PERTAINS TO SHUNT TRIP BREAKERS OF THE ELECTRICAL SYSTEM UNDER THE KITCHEN
HOODS, AS WELL AS GAS SHUT-OFF UPON ACTIVATION OF THE EXISTING AUTOMATIC WET-CHEMICAL
FES EXISTING WET CHEMICAL FIRE EXTINGUISHING SYSTEM FIRE EXTINGUISHING SYSTEM.

Symbol
APPLICABLE CODES AND STANDARDS
FA RISER DIAGRAM F FIRE ALARM PULL STATION
1. UFC 3-600-01 FIRE PROTECTION ENGINEERING FOR FACILITIES (8 AUGUST 2016; CHANGE 2, 25 MARCH 2018)
1 N.T.S. ADDRESSABLE INPUT MODULE
2. UFC 4-021-01 DESIGN AND O&M: MASS NOTIFICATION SYSTEMS (9 APRIL 2008 WITH CHANGE 1, JANUARY
2010)

Appr
AIM
3. INTERNATIONAL BUILDING CODE (2015)
4. NFPA 70 NATIONAL ELECTRIC CODE (2017)
AOM ADDRESSABLE OUTPUT MODULE

Date
5. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE (2016)

WF AUDIBILITY DESIGN
EXISTING WATERFLOW SWITCH

REVISIONS
1. BECAUSE OF UNPREDICTABLE BACKGROUND NOISES AND PROJECT CONDITIONS, THE AUDIBILITY DESIGN
OUTPUTS GOALS SHALL BE CONFIRMED BY MEASUREMENT WITH CALIBRATED TEST EQUIPMENT. IF RESULTS INDICATE
VS EXISTING VALVE SUPERVISORY SWITCH THAT ADDITIONAL NOTIFICATION APPLIANCES, THE CONTRACTOR SHALL ADD THEM AT NO ADDITIONAL COST.

Description
2. THE EXPECTED AMBIENT SOUND PRESSURE LEVELS ARE AS FOLLOWS:
3. OFFICES, RESTROOMS, CIRCULATION AREAS: 55 dBA
RTS REMOTE TEST SWITCH
4. PLACES OF ASSEMBLY: 55 dBA
5. MECHANICAL EQUIPMENT AREAS: 85 dBA
6. THE DESIGN GOAL IS FOR THE ALERT TONE PRECEDING THE VOICE MESSAGE TO REACH THE FOLLOWING
SMOKE DETECTOR - DUCT TYPE SOUND PRESSURE LEVELS (PUBLIC MODE):
s 7. OFFICES, RESTROOMS, CIRCULATION AREAS: 70 dBA
8. LOCKER ROOMS: 70 dBA

Symbol
s SMOKE DETECTOR - SPOT TYPE 9. MECHANICAL EQUIPMENT AREAS: 100 dBA
10. SPEAKERS MAY BE FIELD-LOCATED WITHIN 6 FT OF THE LOCATION INDICATED ON THE APPROVED DESIGN
WITHOUT CONSULTING THE ENGINEER.
GAS DETECTOR - CARBON MONOXIDE
11. THE ALERT SIGNAL PORTION OF THE VOICE ALARM MESSAGE FOR CARBON MONOXIDE MUST BE A 520 Hz

ACTIVATE TEMPORAL 4 (T-4) ALERT TONE AND UNIQUE CARBON MONOXIDE MESSAGE
CO

ACTIVATE TEMPORAL 3 (T-3) ALERT TONE AND UNIQUE FIRE EVACUATION MESSAGE
TEMPORAL 4 (T-4) SIGNAL. THE ALERT SIGNAL MUST REPEAT TWICE BEFORE THE VOICE ANNOUNCEMENT.
COMBINATION SPEAKER AND FIRE ALARM STROBE WITH CLEAR LENS MARKED "FIRE"
INTELLIGIBILITY DESIGN
1. BECAUSE OF UNPREDICTABLE BACKGROUND NOISES AND PROJECT CONDITIONS, THE INTELLIGIBILITY

ACTUATE AMBER MASS NOTIFICATION VISIBLE NOTIFICATION APPLIANCES


A
FIRE ALARM STROBE WITH AMBER LENS MARKED "ALERT" DESIGN GOALS SHALL BE CONFIRMED BY MEASUREMENT WITH CALIBRATED TEST EQUIPMENT. IF
RESULTS INDICATE THAT ADDITIONAL NOTIFICATION APPLIANCES, THE CONTRACTOR SHALL ADD THEM

TRANSMIT UNIQUE SUPERVISORY SIGNAL TO SUPERVISING STATION


FIRE ALARM STROBE WITH CLEAR LENS MARKED "FIRE" AT NO ADDITIONAL COST.

ACTUATE CLEAR FIRE ALARM VISIBLE NOTIFICATION APPLIANCES

ACTUATE ALL SPEAKER CIRCUITS FOR MANUAL ANNOUNCEMENT


2. SPEAKERS ARE LOCATED AND TAPPED TO ACHIEVE THE FOLLOWING INTELLIGIBILITY GOALS

DE-ACTIVATE MASS NOTIFICATION SIGNAL AFTER 10 MINUTES


3. 0.8 CIS THROUGHOUT THE BUILDING UNLESS NOTED OTHERWISE.

B. McCOMBS
DE-ACTIVATE FIRE ALARM EVACUATION MESSAGE IF ACTIVE
SPEAKER 4. FOR CARBON MONOXIDE ALARM/NOTIFICATION, A SIMPLE MESSAGE SHALL BE PROVIDED AS FOLLOWS:

Submitted by:
Reviewed by:
DEACTIVATE SPEAKERS WITHIN 15 FEET OF MICROPHONE
S

Designed by:
(TEMPORAL 4 ALERT TONE)...(TEMPORAL 4 ALERT TONE)..."ATTENTION...ATTENTION...CARBON MONOXIDE

Drawn by:
ACTUATE COMMON SUPERVISORY SIGNAL INDICATOR

HAS BEEN DETECTED IN THE BUILDING. PLEASE LEAVE THE BUILDING BY THE NEAREST EXIT."

JMW

DBN
SAB
SYMBOL MODIFIERS

TRANSMIT CONTACT ID TO SUPERVISING STATION


(TEMPORAL 4 ALERT TONE).
ACTUATE COMMON TROUBLE SIGNAL INDICATOR

C CEILING MOUNTED 5. AREAS OF THE BUILDING WHERE OCCUPANTS ARE NOT EXPECTED TO BE NORMALLY PRESENT ARE
ACTUATE COMMON ALARM SIGNAL INDICATOR

SHUT DOWN ASSOCIATED AIR HANDLING UNIT


ACTUATE ANTIRERRORISM THREAT MESSAGE
PERMITTED TO HAVE A CIS SCORE OF LESS THAN THE MINIMUM REQUIRED VALUE IF PERSONNEL CAN

ACTUATE HAZARDOUS MATERIAL MESSAGE


ncd CANDELA RATING DETERMINE THAT A VOICE SIGNAL IS BEING BROADCAST AND THEY MUST NOT WALK MORE THAN 50
ACTUATE AUDIBLE SUPERVISORY SIGNAL

ACTUATE NATURAL DISASTER MESSAGE


nW WATT TAP

ACTUATE SEVERE WEATHER MESSAGE


FEET TO A LOCATION WITH AT LEAST WITH THE MINIMUM REQUIRED CIS VALUE WITHIN IN THE SAME
ACTUATE AUDIBLE TROUBLE SIGNAL

AREA PER UFC 4-021-01, SECTION 5-7.1.2. THIS IS REPRESENTED AS KEYNOTE 2 ON DRAWINGS.

DISPLAY/PRINT CHANGE OF STATUS


WP WEATHER PROOF

ACTUATE SYSTEM TEST MESSAGE


ACTUATE AUDIBLE ALARM SIGNAL

VISUAL NOTIFICATION DESIGN

ACTUATE ALL CLEAR MESSAGE

CRESSMAN DINING FACILITY EXPANSION


1. CLEAR STROBES MARKED "FIRE" SHALL BE PROVIDED WHERE INDICATED ON THE APPROVED DESIGN

GOODFELLOW AIR FORCE BASE, TEXAS


DRAWINGS FOR FIRE ALARM SYSTEM VISUAL NOTIFICATION.
2. AMBER STROBES MARKED "ALERT" SHALL BE PROVIDED WHERE INDICATED ON THE APPROVED
DESIGN FOR FIRE ALARM SYSTEMS VISUAL NOTIFICATION.
3. STROBES MAY BE FIELD-LOCATED WITHIN 3 FT OF THE LOCATION INDICATED ON THE APPROVED
DESIGN WITHOUT CONSULTING THE ENGINEER. CONSULT WITH ENGINEER PRIOR TO RELOCATING
C:\Users\sbrinkmeyer.pcs\Documents\R18_70374-000_F_sbrinkmeyer8U4LS.rvt

STROBES MORE THAN 3 FT.


INITIATING DEVICES

17th TRAINING WING


1. INITIATING DEVICES MAY BE FIELD-LOCATED WITHIN 3 FT OF THE LOCATION INDICATED ON THE

NATURE OF WORK:
APPROVED DESIGN WITHOUT CONSULTING THE ENGINEER. CONSULT WITH ENGINEER PRIOR
INPUTS A B C D E F G H I J K L M N O P Q R S T U V W X TO RELOCATING INITIATING DEVICES MORE THAN 3 FT.
2. IF DUCT SMOKE DETECTORS IS PROVIDED IN AN INACCESSIBLE LOCATION, PROVIDE A REMOTE
1 MANUAL PULL STATION X X X X X X 1
TEST SWITCH IN ACCORDANCE WITH NFPA 72 SECTION 23.8.5.4.6.4. DUCT DETECTORS SHALL
2 SMOKE DETECTOR - SPOT TYPE X X X X X X 2 EITHER BE RESETTABLE FROM THE PROTECTED PREMISES FIRE ALARM SYSTEM, OR A LISTED
3 WATERFLOW SWITCH (NOTIFICATION APPLIANCES NON-SILENCABLE WHILE IN ALARM) X X X X X X 3 SUPERVISORY INDICATOR WITH INTEGRAL RESET SWITCH SHALL BE PROVIDED.
4 VALVE SUPERVISORY (NOTIFICATION APPLIANCES NON-SILENCABLE WHILE IN ALARM) X X X X 4 CIRCUITS AND CONDUIT
5 SMOKE DETECTOR - DUCT TYPE X X X X X 5 1. ALL CIRCUITS SHALL BE PROVIDED IN CONDUIT IN ACCORDANCE WITH NFPA 70 AND THE CONDUIT
LISTING.
6 CARBON MONOXIDE DETECTOR X X X X X X 6 2. NEW SIGNALING LINE CIRCUITS SHALL BE ARRANGED SO THAT A SINGLE FAULT DOES NOT CAUSE THE
7 KITCHEN HOOD FIRE EXTINGUISHING SYSTEM ALARM X X X X X X 7 LOSS OF ADDRESSABLE DEVICES ON MORE THAN ONE FLOOR.
8 AC POWER FAILURE X X X X 8 INSTALLATION
9 LOW BATTERY X X X X 9 1. ALL EQUIPMENT SHALL BE INSTALLED TIGHT TO THE BUILDING STRUCTURE AND SHALL BE INSTALLED
PARALLEL OR PERPENDICULAR TO THE BUILDING STRUCTURE UNLESS NOTED OTHERWISE.
10 ANY OPEN CIRCUIT X X X X 10 2. THE CONTRACTOR SHALL NOT APPRECIABLY DEVIATE FROM THE APPROVED DESIGN WITHOUT
11 ANY GROUND FAULT X X X X 11 WRITTEN APPROVAL FROM THE ENGINEER.
12 ANY NOTIFICATION APPLIANCE CIRCUIT SHORT X X X X 12 TESTING
13 ANY OTHER TROUBLES X X X X 13 1. UNLESS SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR SHALL PERFORM ALL ACCEPTANCE

PROJECT TITLE
TESTING IN ACCORDANCE WITH THE APPLICABLE DESIGN CRITERIA AND THE EQUIPMENT
14 MASS NOTIFICATION SIGNAL INITIATED WHILE SYSTEM CONTAINS ACTIVE FIRE ALARM X X X X X X X 14 MANUFACTURER'S INSTRUCTIONS.
15 MICROPHONE KEYED-ALL CALL X X X 15 2. UNLESS SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR SHALL PERFORM TESTING AND PROVIDE
DOCUMENTATION PRIOR TO REQUESTING ENGINEER'S PRESENCE TO WITNESS TESTING.
16 MNS PRE-RECORDED MESSAGE ACTIVATED - FIRE X X 16
17 MNS PRE-RECORDED MESSAGE ACTIVATED - SEVERE WEATHER X X 17
18 MNS PRE-RECORDED MESSAGE ACTIVATED - ANTITERRORISM THREAT X X 18
19 MNS PRE-RECORDED MESSAGE ACTIVATED - NATURAL DISASTER X X 19
20 MNS PRE-RECORDED MESSAGE ACTIVATED - HAZARDOUS MATERIAL X X 20
Project Number:
21 MNS PRE-RECORDED MESSAGE ACTIVATED - GAS ALARM X X 21
22 MNS PRE-RECORDED MESSAGE ACTIVATED - SYSTEM TEST X X 22 OK70374-000
23 MNS PRE-RECORDED MESSAGE ACTIVATED - ALL CLEAR X 23
SHEET TITLE
24 MESSAGE FROM WIDE AREA CENTRAL CONTROL UNIT X X 24
FIRE ALARM GENERAL NOTES
A B C D E F G H I J K L M N O P Q R S T U V W X
NOTE: THIS MATRIX IS ONLY INTENDED TO SHOW THE MAJOR SYSTEM FUNCTIONS, SYSTEM SHALL ALSO PERFORM
7/12/2018 11:52:04 AM

INPUTS/OUTPUTS REQUIRED BY NFPA 72 AND THE PRODUCTS' LISTING. Date:


12 JUL 2018
X PERFORM OPERATION/REPORT DEVICE STATUS

SEQ. SHEET OF

FIRE ALARM INPUT/OUTPUT MATRIX


2 N.T.S.
FA001
SHEET KEYNOTES
1 FIRE ALARM APPLIANCES IN COOLERS AND FREEZERS SHALL BE SURFACE MOUNTED IN SURFACE MOUNTED
CONDUIT. APPLIANCES SHALL BE WEATHERPROOF. POINT OF PENETRATION FOR CONDUIT INTO
COOLER/FREEZER SHALL BE PACKED WITH INSULATION AND SEALED AS DIRECTED BY THE MANUFACTURER OR
VENDOR. THE INSIDE OF THE CONDUIT SHALL BE SEALED WITHIN 6 INCHES OF THE POINT OF PENETRATION.
INTERNAL CONDUIT SEAL SHALL BE INSTALLED ON THE WARM SIDE OF THE COOLER/FREEZER ENCLOSURE.
CLOSE COORDINATION WITH THE KITCHEN EQUIPMENT CONTRACTOR IS REQUIRED.
C.R. ENGINEERING: #F-6671 EXPIRES JUNE 30, 2019

2 AREAS OF THE BUILDING WHERE OCCUPANTS ARE NOT EXPECTED TO BE NORMALLY PRESENT ARE PERMITTED
TO HAVE A CIS SCORE OF LESS THAN THE MINIMUM REQUIRED VALUE IF PERSONNEL CAN DETERMINE THAT A
VOICE SIGNAL IS BEING BROADCAST AND THEY MUST NOT WALK MORE THAN 50 FEET TO A LOCATION WITH AT www.poolefire.com
LEAST WITH THE MINIMUM REQUIRED CIS VALUE WITHIN IN THE SAME AREA PER UFC 4-021-01, SECTION 5-7.1.2.

Date Appr
OLATHE, KS 66062 913.829.8650
POOLE FIRE PROTECTION
19910 W. 161ST STREET

Description
Symbol
Appr
Date

REVISIONS
Description
9

8
WOMEN

RTS
A 0.5W VS
110cd 75cd 15cd 30cd VS
s

0.25W
A 0.5W
0.25W A WF
MECH.
AHU-1

Symbol
ROOM

0.5W
110cd 75cd

15cd 30cd

75cd 30cd
30cd 75cd
A

A
2

110cd 75cd
SNACK LINE A 0.25W MECH.

A
VESTIBULE 30cd 15cd ROOM

0.25W

0.25W
A

F
104 7

15cd 30cd
MEN 2

0.25W
15cd30cd
0.25W A CO

30cd 15cd
15cd 30cd

0.25W
A

0.25W
EXISTING

S
1W A OFFICE JAN. DRY STORAGE

B. McCOMBS
A
WOMEN'S

0.25W

Submitted by:
2

30cd
15cd 30cd

Reviewed by:
0.5W 0.25W

Designed by:
0.25W
0.5W

0.25W
108

Drawn by:
S S
FAMILY S MECHANICAL

JMW

DBN
SAB
TOILET LOC F

30cd 15cd
107
A A
0.5W
s EXISTING EXISTING CORRIDOR
FMCP

105 CO

75cd
ATI

75cd 30cd 2 30cd 15cd


DINING KITCHEN FES

A
A

0.25W
COMM 2
116 117

0.5W
106
RECEIVING

FES
0.5W
30cd 15cd

110cd 75cd
CO
OFFICE CONF. ROOM FES
CO
OFFICE
STORAGE

CRESSMAN DINING FACILITY EXPANSION


112 111 5

15cd 30cd
2

GOODFELLOW AIR FORCE BASE, TEXAS


2

A
PRIVATE

A
A
110
DINING

F
15cd 30cd
DINING 0.25W 0.25W
PRODUC
2
0.5W

102 A
0.25W

103 TION 2
S CORRIDOR CAN

0.5W
C:\Users\sbrinkmeyer.pcs\Documents\R18_70374-000_F_sbrinkmeyer8U4LS.rvt

110cd 75cd

MAIN LINE WASH


30cd 15cd

115 75cd 110cd


0.5W

STUDENT 0.5W 4
A
ADMIN.
A

DRY A

17th TRAINING WING


DAIRY

NATURE OF WORK:
113
EXISTING CO
STORAGE 110cd 75cd
REF.
30cd 75cd A 0.5W
0.5W MEN'S
110cd 75cd 1 2
0.25W

A
114
30cd 15cd

CO
A 110cd 75cd THAW REF.
0.5W

75cd 30cd 0.5W PREPAR A


A
A

0.25W 1 2
110cd 75cd
75cd 110cd

ATION 30cd 15cd 3


F
A

LOC VESTIBULE

30cd 75cd
A

0.5W
FAA

A
101
WARE WASH FREEZER
0.5W

UTENSIL

S
WASH 1 2

0.25W
15cd 30cd VEGGIE 15cd 30cd
1 2 1 2
0.25W A PREP 0.5W A

F
2

PROJECT TITLE
A 0.5W
(ALT#1) 110cd 75cd 1
PREPARATION
ROOM
118

Project Number:

A B C D E F G OK70374-000

SHEET TITLE

FIRE ALARM FLOOR PLAN


7/12/2018 11:52:05 AM

Date:
12 JUL 2018

FIRE ALARM FLOOR PLAN


1 3/32" = 1'-0"
PLAN NORTH
12' 6' 0 12'
SEQ. SHEET OF

SCALE: 3/32" = 1'-0" FA101


C.R. ENGINEERING: #F-6671 EXPIRES JUNE 30, 2019

www.poolefire.com

Date Appr
FIRE SUPPRESSION NOTES
OLATHE, KS 66062 913.829.8650

1. THE DESIGN AND INSTALLATION OF THE FIRE SUPPRESSION SYSTEM MUST BE IN


ACCORDANCE WITH UFC 3-600-01 (8 AUGUST 2016; CHANGE 2, 25 MARCH 2018),
EXISTING POTTER SIGNAL VSR-F FLOW SWITCH
POOLE FIRE PROTECTION

NFPA 13 (2016 EDITION), NFPA 24 (2016 EDITION), AND THE DESIGN SPECIFICATIONS.
2. ALL HANGERS MUST BE PROVIDED AND INSTALLED IN ACCORDANCE WITH NFPA 13.
19910 W. 161ST STREET

EXISTING 4" CENTRAL SWING CHECK VALVE 3. THE INSPECTOR'S TEST VALVES MUST BE LOCATED NO MORE THAN 7 FEET AFF.
4. WHERE PIPES PASS THROUGH FIRE RESISTANCE RATED CONSTRUCTION, THE

Description
SEE NOTE #19 PENETRATION MUST BE PROTECTED WITH A LISTED OR APPROVED FIRESTOPPING
ASSEMBLY.
EXISTING 4" CENTRAL MODEL "G" ALARM VALVE WITH TRIM 5. ALL VALVES (DRAINS, INSPECTOR'S TEST, CONTROL) MUST BE IDENTIFIED AS

12' - 9"
REQUIRED BY NFPA 13.

11' - 10"
6. PIPING MUST BE ARRANGED FOR FLUSHING IN ACCORDANCE WITH NFPA 13.
READILY REMOVABLE FITTINGS MUST BE PROVIDED AT THE END OF ALL CROSS
MAINS.
EXISTING 4" ELL OUT TO FIRE DEPARTMENT CONNECTION 7. ALL PENDENT SPRINKLERS MUST BE INSTALLED IN THE CENTER OF THE CEILING

Symbol
TILES.
8. DRAINS MUST BE LOCATED TO PROVIDE DRAINAGE IN ACCORDANCE WITH NFPA 13.
EXISTING AMES 2000SS BACKFLOW WITH TAMPER SWITCHES
ALL DRAINS AND TEST CONNECTIONS MUST DISCHARGE TO THE EXTERIOR OF THE
BUILDING ON TO A SPLASH BLOCK OR PAVEMENT, AND SHALL NOT DISCHARGE
EXISTING 2" MAIN DRAIN TO OUTSIDE ACROSS ANY MEANS OF EGRESS.

Appr
9. ALL SPRINKLER SYSTEM ALARM INITIATING DEVICES MUST BE CONNECTED TO THE
FIRE ALARM SYSTEM.

Date
10. ALL NORMALLY OPEN VALVES MUST BE ELECTRICALLY SUPERVISED (i.e. TAMPER
SWITCH) AND ALL NORMALLY CLOSED VALVES MUST BE SUPERVISED BY SECURING
SEE NOTE #20 THEM WITH A LOCK AND CHAIN OR SEALED.

REVISIONS
11. DRAWINGS ARE DIAGRAMMATIC, INTENDED TO CONVEY THE SCOPE OF WORK AND
EXISTING 6" DUCTILE IRON FLANGED SPIGOT GENERAL ARRANGEMENTS OF THE SYSTEM. COORDINATE THE SYSTEM LAYOUT
WITH ALL OTHER DISCIPLINES. EXISTING SYSTEM IS UNDERSTOOD TO HAVE MET

Description
CODE REQUIREMENTS WHEN INSTALLED. AS SUCH, EXISTING SYSTEM WAS NOT
EVALUATED FOR COMPLIANCE WITH CURRENT CODE AS IT IS NOT TO BE MODIFIED.
12. PROVIDE CLEARANCE AROUND ALL PIPING EXTENDING THROUGH WALLS AND
FLOORS IN ACCORDANCE WITH NFPA 13, SECTION 9.3.4. EXISTING RISER DOES NOT
MEET CLEARANCE REQUIREMENTS OF CURRENT NFPA 13.
13. PROVIDE AIR VENTING IN ACCORDANCE WITH NFPA 13, SECTION 7.1.5.
14. THIS BUILDING WILL HAVE A WET PIPE AUTOMATIC SPRINKLER SYSTEM WHICH WILL
REQUIRE ALL AREAS OF THE BUILDING TO BE MAINTAINED ABOVE 40 DEGREES F.

Symbol
15. PROVIDE OVERSIZED ESCUTCHEONS FOR HARD PIPED DROPS IN DROP CEILINGS.
16. PROVIDE SPRINKLER PROTECTION WITHIN ALL COMBUSTIBLE CONCEALED SPACES.
17. THE SEISMIC DESIGN CATEGORY FOR THE FACILITY IS A. SEISMIC BRACING WILL
EXISTING SPRINKLER RISER SECTION NOT BE REQUIRED IN ACCORDANCE WITH ASCE 7, SECTION 11.7 AND NFPA 13.
1 1/4" = 1'-0"
18. THE EXISTING WET PIPE SPRINKLER SYSTEM IS TO BE MAINTAINED IN SERVICE
THROUGHOUT CONSTRUCTION. CLOSELY COORDINATE CONSTRUCTION ACTIVITIES
WITH OTHER TRADES AND THE BASE REPRESENTATIVE.
19. CURRENT WET PIPE SYSTEM RISER DOES NOT HAVE A FORWARD FLOW TEST
CONNECTION PROVIDED. THE REQUIREMENT TO PROVIDE A FORWARD FLOW TEST
CONNECTION COMES FROM NFPA 13, SECTION 8.17.4.5.1. CONTRACTOR TO MODIFY
EXISTING SYSTEM TO CREATE CODE COMPLIANCE.
20. CURRENT WET PIPE SPRINKLE SYSTEM IS NOT PROVIDED WITH ADEQUATE

B. McCOMBS
CLEARANCE REQUIREMENTS OF NFPA 13, SECTION 9.3.4. CONTRACTOR TO MODIFY

Submitted by:
Reviewed by:
Designed by:
EXISTING SYSTEM TO CREATE CODE COMPLIANCE.

Drawn by:
21. PERFORM SYSTEM TESTING IN ACCORDANCE WITH NFPA 25 AND NFPA 13 TO

DBN
DRF

DRF
ENSURE EXISTING SYSTEM FUNCTIONS PROPERLY PRIOR TO
ALTERATION/MODIFICATION OF THE EXISTING SYSTEM.

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


C:\Users\sbrinkmeyer.pcs\Documents\R18_70374-000_F_sbrinkmeyer8U4LS.rvt

17th TRAINING WING


NATURE OF WORK:
PROJECT TITLE
Project Number:

OK70374-000

SHEET TITLE

FIRE SUPPRESSION GENERAL


NOTES
7/12/2018 11:52:05 AM

Date:
12 JUL 2018

SEQ. SHEET OF

FX001
HAZARD CLASSIFICATION SCHEDULE HAZARD CLASSIFICATION LEGEND
LIGHT HAZARD
ROOM
(0.10 GPM/FT² OVER 1,500 FT² WITH 250 GPM EXTERIOR HOSE DEMAND)
NUMBER ROOM NAME HAZARD CLASSIFICATION
ORDINARY HAZARD
101 VESTIBULE LIGHT HAZARD (0.20 GPM/FT² OVER 2,500 FT² WITH 250 GPM EXTERIOR HOSE DEMAND)
102 DINING LIGHT HAZARD
OUT OF SCOPE
103 PRIVATE DINING LIGHT HAZARD
104 VESTIBULE LIGHT HAZARD
C.R. ENGINEERING: #F-6671 EXPIRES JUNE 30, 2019

105 FAMILY TOILET LIGHT HAZARD


106 COMM ORDINARY HAZARD www.poolefire.com
107 MECHANICAL ORDINARY HAZARD
108 EXISTING WOMEN'S OUT OF SCOPE
109 EXISTING JAN. OUT OF SCOPE
110 STORAGE ORDINARY HAZARD

Date Appr
111 CONF. ROOM LIGHT HAZARD
OLATHE, KS 66062 913.829.8650

112 OFFICE LIGHT HAZARD


113 STUDENT ADMIN. LIGHT HAZARD
POOLE FIRE PROTECTION

114 EXISTING MEN'S OUT OF SCOPE


19910 W. 161ST STREET

115 CORRIDOR LIGHT HAZARD


116 EXISTING DINING OUT OF SCOPE

Description
117 EXISTING KITCHEN OUT OF SCOPE
118 PREPARATION ROOM LIGHT HAZARD

Symbol
Appr
Date
EXISTING 4" MAIN LINE THAT

REVISIONS
SPRINKLER CONTRACTOR WILL NEED
TO TIE INTO WHEN INSTALLING THE
EXISTING FIRE DEPARTMENT CONNECTON
SUPRESSION FOR THE ADDITION.

Description
EXISTING FIRE SUPPRESSION SYSTEM RISER
9

8
1
____________________________________________________

FX001

Symbol
7
VESTIBULE
104

FAMILY 6
TOILET EXISTING

B. McCOMBS
EXISTING 4" MAIN LINE THAT SPRINKLER
WOMEN'S

Submitted by:
105

Reviewed by:
Designed by:
CONTRACTOR WILL NEED TO TIE INTO WHEN

Drawn by:
MECHANICAL 108 INSTALLING THE SUPRESSION FOR THE ADDITION.

DBN
DRF

DRF
107
COMM
106
DINING CORRIDOR
102
PRIVATE EXISTING 115
DINING CONF. ROOM JAN.

CRESSMAN DINING FACILITY EXPANSION


111 5

GOODFELLOW AIR FORCE BASE, TEXAS


103 OFFICE STORAGE
109
EXISTING EXISTING
112
110 DINING KITCHEN
116
117
C:\Users\sbrinkmeyer.pcs\Documents\R18_70374-000_F_sbrinkmeyer8U4LS.rvt

EXISTING SPRINKLER CONTRACTOR TO TIE INTO EXISTING 4"


STUDENT MEN'S 4
MAIN LINE OR EXISTING 2 1/2" CROSS MAIN WHEN

17th TRAINING WING


ADMIN. 114 INSTALLING THE SUPRESSION SYSTEM FOR THE

NATURE OF WORK:
R R R
R
R

ADDITION. PRELIMINARY CALCULATIONS FOR


113 ALT#1:
TYING INTO EXISTING 2 1/2" CROSS MAIN,
EXISTING 4" MAIN LINE THAT
LOCATED ABOVE EXISTING RESTROOMS, SHOW A
SPRINKLER CONTRACTOR WILL NEED
SAFETY FACTOR OF 29 PSI. MODIFICATION OF
TO TIE INTO WHEN INSTALLING THE
EXISTING SPRINKLER SYSTEM TO BE DONE AT
L
L

SUPRESSION FOR THE ADDITION.


CONTRACTORS DISCRETION.
VESTIBULE
101
3

PROJECT TITLE
(ALT#1) 1
PREPARATION
ROOM
118

Project Number:

A B C D E F G OK70374-000

SHEET TITLE

FIRE SUPPRESSION FLOOR PLAN


7/12/2018 11:52:11 AM

Date:
12 JUL 2018

FIRE SUPPRESSION FLOOR PLAN


1 3/32" = 1'-0"
PLAN NORTH
12' 6' 0 12'
SEQ. SHEET OF

SCALE: 3/32" = 1'-0" FX101


C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
PLUMBING ABBREVIATIONS PLUMBING SYMBOLS GENERAL NOTES

SS SANITARY SEWER SHUT OFF VALVE IN DROP


1. THE PLUMBING INSTALLATION SHALL COMPLY WITH CURRENT LOCAL PLUMBING CODES.
ABV ABOVE NIC NOT IN CONTRACT
2. PIPE ROUTING SHOWN IS SCHEMATIC AND IS NOT INTENDED TO INDICATE EXACT
AC ABOVE CEILING NPW NON-POTABLE WATER A AIR OUTLET ROUTING. CONTRACTOR SHALL PROVIDE ANY ADDITIONAL OFFSETS AND FITTINGS
OKLAHOMA CITY, OK 73112 405.416.8100

RD ROOF DRAIN
ACC ACCESS REQUIRED FOR PROPER INSTALLATION AND TO MAINTAIN CLEARANCES. COORDINATE
AFF ABOVE FINISHED FLOOR OC ON CENTER WITH OTHER DISCIPLINES TO AVOID WHEN ROUTING PIPING.

Date Appr
C COLD WATER OUTLET
AHU AIR HANDLING UNIT OD OVERFLOW DRAIN OD OVERFLOW DRAIN 3. PROVIDE ALL FITTINGS AND OFFSETS REQUIRED TO MAKE CONNECTION TO SITE
OR ON ROOF UTILITIES.
BFF BELOW FINISHED FLOOR OS&Y OUTSIDE, SCREW AND YOKE G GAS OUTLET 4. CONCEAL PIPING ABOVE CEILING AND WITHIN WALLS OR CHASES, EXCEPT IN
C.H. GUERNSEY & COMPANY

BLW BELOW
PLUMBING VENT MECHANICAL SPACES OR WHEN OTHERWISE NOTED.
BV BALL VALVE PD PRESSURE DROP H 5. PROVIDE ACCESS PANELS FOR ALL VALVES CONCEALED IN WALLS OR ABOVE
HOT WATER OUTLET
NON-ACCESSIBLE CEILINGS.
5555 N. GRAND BLVD.

BWV BACK WATER VALVE PRES PRESSURE COLD WATER


6. SLEEVE AND/OR FIRESTOP ALL PENETRATIONS THROUGH RATED WALLS, CEILINGS, AND

Description
PRV PRESSURE RELIEF VALVE O OXYGEN OUTLET FLOORS WITH UL LISTED ASSEMBLIES. FIRESTOP ASSEMBLIES SHALL BE EQUAL TO OR
CD CONDENSATE DRAIN PSI POUNDS PER SQUARE INCH DOMESTIC HOT WATER SUPPLY EXCEED THE RATING OF THE WALL, CEILING OR FLOOR. SEE ARCHITECTURAL DRAWINGS
CI CAST IRON RD ROOF DRAIN FOR FINAL FINISHES. ALL FIRESTOP MATERIAL TO BE PROVIDED BY A SINGLE
V VACUUM INLET
CLG CEILING RPBP REDUCED PRESSURE BACKFLOW PREVENTER MANUFACTURER.
DOMESTIC HOT WATER RETURN
CO CLEAN OUT RPM REVOLUTIONS PER MINUTE 7. SEE ARCHITECTURAL DRAWINGS FOR FIXTURE LOCATIONS AND MOUNTING HEIGHTS.
COND CONDENSATE B BREATHING AIR OUTLET 8. PROVIDE TRAP PROTECTION FOR ALL FLOOR DRAINS.
120 DOMESTIC 120 H.W. SUPPLY 9. PROVIDE AN AIR GAP, WHEN REQUIRED BY CODE, SERVING INDIVIDUAL FIXTURES,
CV CHECK VALVE SD SHOWER DRAIN

Symbol
SF SUPPLY FAN ECCENTRIC REDUCER, WATER DEVICES, APPLIANCES AND APPARATUS.
DCW DOMESTIC COLD WATER SH SHOWER 120 DOMESTIC 120 H.W. RETURN 10. ALL EXPOSED PIPE AND FITTINGS IN FINISHED AREAS SHALL BE CHROME PLATED, UNLESS
OTHERWISE NOTED.
DFU DRAINAGE FIXTURE UNITS SK SINK CONCENTRIC REDUCER 11. MOUNT HOSE BIBBS 18" ABOVE FINISHED FLOOR, UNLESS OTHERWISE NOTED.
DHW DOMESTIC HOT WATER SO SHUT OFF 140 DOMESTIC 140 H.W. SUPPLY

Appr
12. MOUNT WALL HYDRANTS 18" ABOVE GRADE, UNLESS OTHERWISE NOTED. COORDINATE
DHWR DOMESTIC HOT WATER RETURN SS SANITARY SEWER
DIRECTION OF FLOW WITH ARCHITECTURAL DRAWINGS.
DN DOWN TMV THERMOSTATIC MIXING VALVE 140 13. PROVIDE CLEANOUTS IN ACCORDANCE WITH THE PLUMBING CODE. INSTALL CLEANOUT

Date
DOMESTIC 140 H.W. RETURN
DS DOWN SPOUT TYP TYPICAL WITH COVER FLUSH TO FINISHED SURFACE.
SLOPE DOWN
G 14. COORDINATE EXACT FLOOR DRAIN LOCATIONS WITH ARCHITECTURAL DRAWINGS.

REVISIONS
ECC ECCENTRIC UF UNDERFLOOR GAS
INSTALL FLOOR DRAINS WITH GRATE FLUSH WITH FINISHED FLOOR.
ELEC ELECTRIC UG UNDER GROUND 15. COORDINATE PIPING WITH ELECTRICAL EQUIPMENT (PANELS , TRANFORMERS, ETC)
ERD EMERGENCY ROOF DRAIN UH UNIT HEATER A COMPRESSED AIR PRESSURE REDUCING VALVE PRIOR TO ANY INSTALLATION. DO NOT ROUTE ANY PIPING OVER ANY ELECTRICAL PANELS

Description
EWC ELECTRIC WATER COOLER UR URINAL UNDER ANY CIRCUMSTANCES. ANY PIPING ROUTED OVER PANELS SHALL BE RE-ROUTED
EXIST EXISTING AT NO ADDITIONAL COST.
CD CONDENSATE DRAIN LINE ANCHOR
EXT EXTERNAL W WASTE 16. ALL WALL MOUNTED LAVATORIES SHALL BE ATTACHED TO A FLOOR MOUNTED CARRIER.
WC WATER CLOSET 17. CONTRACTOR SHALL INSULATE ALL DOMESTIC WATER PIPING. INSULATION SHALL
GW GREASE WASTE EXPANSION JOINT COMPLY WITH THE SPECIFICATIONS.
FCU FAN COIL UNIT WCO WALL CLEANOUT
18. INSTALL SHOCK ARRESTORS PER PDI WH-201.
FD FLOOR DRAIN WHA WATER HAMMER ARRESTOR
ACID 19. INSTALL ALL CONDENSATE DRAIN PIPING WITH INSULATION PER SPECIFICATIONS.

Symbol
FL FLOW LINE WM WATER METER ACID WASTE PIPE GUIDE
20. INSULATE ALL HORIZONTAL FLOOR DRAIN PIPING FOR FLOOR DRAINS RECEIVING
FLR FLOOR YH YARD HYDRANT CONDENSATE ABOVE GRADE WITH INSULATION PER SPECIFICATIONS.
FR FROM NPW NON-POTABLE WATER (GREY WATER) CONNECT TO EXISTING 21. ANY DEVIATIONS IN ELECTRICAL REQUIREMENTS FROM THE BASIS OF DESIGN FOR
FS FLOOR SINK PLUMBING EQUIPMENT SHALL BE THE RESPONSIBILITY OF THE PLUMBING CONTRACTOR
FT FEET TO ENSURE COORDINATION WITH THE ELECTRICAL CONTRACTOR FOR PROPER WIRE
F FIRE WATER
M WATER METER SIZE, CONDUITS, DISCONNECTS, FUSES, STARTERS, VFD'S, ETC. AT NO ADDITIONAL COST.
G GAS 22. PROVIDE CONCRETE HOUSEKEEPING PADS UNDER ALL FLOOR MOUNTED EQUIPMENT.
GC GENERAL CONTRACTOR CHECK VALVE REFER TO SPECIFICATIONS FOR DETAILED REQUIREMENTS.
GPF GALLONS PER FLUSH GAS PRESSURE REGULATOR 23. THESE CONTRACT DOCUMENTS HAVE BEEN SUBMITTED FOR CONTRACTOR
DEVELOPMENT OF THE CONSTRUCTION WORK PLAN. COORDINATION BETWEEN THE
GPH GALLONS PER HOUR PLUG COCK
CONTRACTOR AND SUBCONTRACTORS IS THE RESPONSIBILITY OF THE CONTRACTOR.
GPM GALLONS PER MINUTE

B. McCOMBS
CHANGES TO THESE DRAWINGS AS A RESULT OF THE CONSTRUCTION COORDINATION

M. WILSON

Submitted by:
GW GREASE WASTE

Reviewed by:
AND THE DEVELOPMENT OF THE CONSTRUCTION WORK PLAN ARE THE RESPONSIBILITY

R. PRADO
Designed by:
BUTTERFLY VALVE FLOOR SINK

Checker
OF THE CONTRACTOR.

Drawn by:
HB HOSE BIBB 24. THESE CONTRACT DOCUMENTS DETAIL THE CONCEPT OF THE WORK. COORDINATION OF
BALL VALVE CONCEPTUALLY EQUAL BUT NOMINALLY DIFFERENT SYSTEMS OR PRODUCTS SELECTED
HP HORSEPOWER
FLOOR DRAIN BY CONTRACTOR ARE THE RESPONSIBILITY OF THE CONTRACTOR.
IN INCHES BALANCING VALVE 25. MOUNT ALL EQUIPMENT ACCORDING TO REQUIREMENTS OF UFC 4-010-1.

P-TRAP
LAV LAVATORY STRAINER

CRESSMAN DINING FACILITY EXPANSION


MAX MAXIMUM

GOODFELLOW AIR FORCE BASE, TEXAS


UNION
MIN MINIMUM
MSB MOP SERVICE BASIN
GAS COCK
MTD MOUNTED

17th TRAINING WING


NATURE OF WORK:
C:\Work\R18_70374-000_M_rprado.rvt

PROJECT TITLE
Project Number:

OK70374-000

SHEET TITLE

PLUMBING LEGEND

Date:
7/12/2018 8:24:29 AM

12 JUL 2018

SEQ. SHEET OF

P-001
C
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
OKLAHOMA CITY, OK 73112 405.416.8100

Date Appr
AA BB CC DD EE FF GG HH JJ A B
C.H. GUERNSEY & COMPANY
5555 N. GRAND BLVD.

Description
9

Symbol
RELOCATE CLEANOUT AND EXTEND
7.9 PIPING UP TO GRADE.

Appr
3" RD AT 48" INVERT B.F.F. REFER TO CIVIL FOR CONTINUATION.
7.8

Date
SLEEVE THRU FOOTING DOUBLE CO

REVISIONS
REFER TO STRUCTURAL
FOR DETAIL

Description
7

3" W. DN. & 3"


1-1/2" V UP RD

Symbol
2" W. FR.
ABV. 3" FD
3" ERD FR. ABV.
2" FD

5.6 REMOVE EXISTING


2" FD
4" WCO 4" CO AND CAP PIPE

4" W. DN & 2" V UP

2" W. DN & SS SS
4"

B. McCOMBS
1-1/2" V UP 4" WCO EXISTING 4" SANITARY SEWER LINE

M. WILSON

Submitted by:
Reviewed by:
R. PRADO
Designed by:

Checker
Drawn by:
2" W DN. &
1-1/2" V UP
5
SLEEVE PIPE THRU FOOTING. REFER
STRUCTURAL FOR DETAIL (TYP)

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


4

3.8

17th TRAINING WING


NATURE OF WORK:
3" RD FR. ABV.

3.4
SLEEVE THRU FOOTING. REFER
TO STRUCTURE FOR DETAIL
RD
3"

DOUBLE CO
2.2
C:\Work\R18_70374-000_M_rprado.rvt

2.1 RELOCATE CLEANOUT AND EXTEND

PROJECT TITLE
PIPING UP TO GRADE.
3" RD AT 48" INVERT B.F.F. REFER TO CIVIL FOR CONTINUATION.
2

Project Number:

UNDERFLOOR PLUMBING PLAN - AREA A


1 SCALE: 1/8" = 1'-0"
OK70374-000

SHEET TITLE

PLAN NORTH UNDERFLOOR PLUMBING PLAN -


A B AREA A

Date:
7/12/2018 8:24:29 AM

12 JUL 2018

KEY PLAN SEQ. SHEET OF

8' 4' 0 8'

P-101
SCALE: 1/8" = 1'-0"
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
C
OKLAHOMA CITY, OK 73112 405.416.8100

Date Appr
C.H. GUERNSEY & COMPANY
5555 N. GRAND BLVD.

Description
E F G
D

Symbol
9

Appr
Date

REVISIONS
Description
7

Symbol
6

B. McCOMBS
M. WILSON

Submitted by:
Reviewed by:
R. PRADO
Designed by:

Checker
Drawn by:
5

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


ALT#1: FOOD PREP ADDITION

17th TRAINING WING


NATURE OF WORK:
EXIST. 3" GREASE WASTE
EXIST. 4" GREASE WASTE

EXIST. 2" SS LINE

EXIST. 4" SS LINE

EXIST. 2" DHW


EXIST. 1" DCW
C:\Work\R18_70374-000_M_rprado.rvt

PROJECT TITLE
1/2" DOMESTIC COLD/HOT WATER UP TO
LAV ABV. ROUTE PIPING IN CRAWL SPACE.
2

SS
1 2" W. FR LAV. ABV.
3"
3" CO Project Number:
EXTEND PIPING UP TO EXIST. EXTERIOR CO AT 24" INVERT B.F.F.
GRADE AND REPLACE OK70374-000
EXISTING CO.
SHEET TITLE

PLAN NORTH UNDERFLOOR PLUMBING PLAN -


A B AREA B

Date:
7/12/2018 8:24:31 AM

12 JUL 2018

UNDERFLOOR PLUMBING PLAN - AREA B KEY PLAN


1 SCALE: 1/8" = 1'-0"
SEQ. SHEET OF

8' 4' 0 8'

P-102
SCALE: 1/8" = 1'-0"
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019 C
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
OKLAHOMA CITY, OK 73112 405.416.8100

Date Appr
AA BB CC DD EE FF GG HH JJ A B
C.H. GUERNSEY & COMPANY
5555 N. GRAND BLVD.

Description
9

Symbol
8

7.9

Appr
FREEZELESS WH-1

Date
7.8
VESTIBULE

REVISIONS
104 REPLACE CO
3/4"
DOWNSPOUT

Description
NOZZLE
CO
7 RD FR. ABV.
3"
OD

RD
3" OD FR. ABV. 3"

Symbol
6
1-1/4"
FAMILY TOILET
EXISTING WOMEN'S
105 MECHANICAL
3/4" 108
107
5.6 EXISTING DCW, DHW, AND DHWR

PRIVATE DINING
103 COMM
106 G

B. McCOMBS
DINING 2"

M. WILSON

Submitted by:
Reviewed by:
R. PRADO
Designed by:
102

Checker
Drawn by:
EXISTING
3/4" DCW DN. FOR FUTURE BEVERAGE STATION TMV CORRIDOR
1
5 115
P-501 EXISTING JAN.
CONF. ROOM STORAGE
110 109
111
OFFICE
112

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


4 STUDENT ADMIN. EXISTING MEN'S
113 114

3.8

17th TRAINING WING


NATURE OF WORK:
RD. DN.
3.4
3/4" CO
3" OD FR. ABV. RD
EXISTING DINING
OD
3" 116
3"
3 RD FR. ABV.

CO
DOWNSPOUT NOZZLE
VESTIBULE
REPLACE CO
101
C:\Work\R18_70374-000_M_rprado.rvt

2.2
FREEZELESS WH-1

PROJECT TITLE
2.1

Project Number:

OK70374-000

SHEET TITLE

PLUMBING FLOOR PLAN - AREA A PLAN NORTH PLUMBING FLOOR PLAN - AREA A
1 SCALE: 1/8" = 1'-0"
A B

Date:
7/12/2018 8:24:32 AM

12 JUL 2018

KEY PLAN SEQ. SHEET OF

8' 4' 0 8'

P-103
SCALE: 1/8" = 1'-0"
C.H. GUERNSEY & COMPANY
7/12/2018 8:24:32 AM C:\Work\R18_70374-000_M_rprado.rvt 5555 N. GRAND BLVD.
OKLAHOMA CITY, OK 73112 405.416.8100
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

1
2
3
4
5
6
7
8
9

1
C

SCALE: 1/8" = 1'-0"


G
2"

EXIST. 2" VENT PIPING


D

PLUMBING FLOOR PLAN - AREA B


G

1-1/2"
EXIST. 3"

TO AVOID FOOTING
2" W DN. OFFSET PIPE

FLUSH CO WITH FLR.


G

P-2
117

118
EXIST. 3"

EXISTING KITCHEN

PREPARATION ROOM
G

2" W DN. & 1-1/2" V UP


E

ALT#1: FOOD PREP ADDITION

G
EXIST. 3"
EXIST. 4"
EXISTING GAS METER
F
G

PLAN NORTH

8'
A

4'
0

SCALE: 1/8" = 1'-0"


KEY PLAN
B

8'

PROJECT TITLE Designed by:


SEQ.

M. WILSON
Date:

NATURE OF WORK: Drawn by:


CRESSMAN DINING FACILITY EXPANSION R. PRADO
SHEET TITLE
Project Number:

SHEET

17th TRAINING WING Reviewed by:


12 JUL 2018
OK70374-000

Checker
P-104

GOODFELLOW AIR FORCE BASE, TEXAS


Symbol Description Date Appr
Submitted by:
PLUMBING FLOOR PLAN - AREA B

OF

B. McCOMBS REVISIONS Symbol Description Date Appr


C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
A
HH JJ SYSTEMS MATERIALS SCHEDULE - PLUMBING
INSULATION
FD-B SYSTEM MATERIAL THICKNESS TYPE JACKET
2" G DN. TO B-1 DOMESTIC CW TYPE "L" HARD COPPER REFER SPECS FIBERGLASS VAPOR BARRIER
DOMESTIC HW/HWR TYPE "L" HARD COPPER REFER SPECS FIBERGLASS VAPOR BARRIER
1-1/2" V UP 3/4" DCW DN. TO HOSE BIBB LOCATE
OKLAHOMA CITY, OK 73112 405.416.8100

SHUT-OFF VALVE IN CORRIDOR SANITARY WASTE - BELOW GRADE SCHEDULE 40 PVC -- -- --


SANITARY VENT SWCI HUBLESS -- -- --

Date Appr
6 SANITARY WASTE SWCI HUBLESS -- -- --
G
3" RD DN. ROOF DRAIN SWCI HUBLESS 1" FIBERGLASS VAPOR BARRIER
1-1/4"
3" 3" VTR CONDENSATE DRAIN, INSIDE BUILDING TYPE "M" COPPER 1/2" FLEX. UNICELLULAR --
C.H. GUERNSEY & COMPANY

FAMILY TOILET NATURAL GAS SCHEDULE 40 BLACK STEEL -- -- --


WHA-A W/ ACC. PANEL
105
RPBP
5555 N. GRAND BLVD.

Description
3/4" MAKE-UP WATER MECHANICAL 2"
P-1
P-2 107
WCO
FD-A
2"
WATER HAMMER ARRESTOR SCHEDULE FLOOR DRAIN SCHEDULE
MARK FIXTURE UNIT CAPACITY PIPE SIZE MARK DESCRIPTION

G
5.6 WHA-A 1 - 11 3/4" FD-A 5" ROUND, NICKEL BRONZE
FD-B
EWH-1 WHA-B 12 - 32 1" FD-B 5" ROUND, NICKEL BRONZE WITH RIM

Symbol
2" WHA-C 33 - 60 1"
4" W. DN. & 2" V UP 1-1/2" V UP 2" W. DN. & 1-1/2" V UP WHA-D 61 - 113 1"

COMM

Appr
106

PLUMBING FIXTURE SCHEDULE

Date
BASIS OF DESIGN
WCO
MARK DESCRIPTION CW HW WASTE VENT FIXTURE BOD VALVE BOD REMARK

REVISIONS
P-1 FLOOR MOUNTED WATER CLOSET 1-1/4" - 4" 2" KOHLER HIGHLINE K-4405 SLOAN ROYAL 111-1.28
P-2 WALL-HUNG LAVATORY 1/2" 1/2" 2" 1-1/2" AMERICAN STANDARD DECLYN KOHLER CORALAIS K-15182-F

Description
1-1/2" V UP 1-1/2" V FR. BLW. OFFSET
PIPE TO AVOID FOOTING

ELECTRIC WATER HEATER SCHEDULE


ENLARGED PLUMBING PLAN
1 SCALE: 1/4" = 1'-0" MARK DESCRIPTION GPM RECOVERY @ 57°F RISE W CW
CONNECTION SIZE
HW VOLT/PHASE BASIS OF DESIGN REMARKS

Symbol
EWH-1 POINT OF USE ELECTRIC TANKLESS WATER HEATER 0.5 4160 1/2" 1/2" 208/1 CHRONOMITE SR-20L

OPEN
COUNTERSUNK CLEANOUT FLOOR
SCREW COVER 2"
OPTIONAL FUNNEL TYPICAL PIPE

B. McCOMBS
THROUGH

M. WILSON

Submitted by:
Reviewed by:
R. PRADO
Designed by:

C. NICEK
ROOF DRAIN
SECURE TO

Drawn by:
STRAINER COVER WITH EPDM PAN SEE SPECIFICATION
FLOOR REMOVABLE PIPE PORTAL RUBBER CAP FOR DRAIN PIPING
STRAINER ASSEMBLY. REFER 1"
SPECIFICATIONS STAINLESS CLEANOUT
CAULKING
STEEL PIPE PLUG
FERRULE
STRAP
ADJUSTABLE ROOF VARIES; PROVIDE
ROOF 1"
HOUSING CURB BY EXTENSION AIR GAP FITTING
GC 2"
PIECE AS

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


REQUIRED

COLLAR
CONCRETE
FLOOR
PLUGGED TEES
TO SANITARY

TYPICAL PIPE PENETRATION

17th TRAINING WING


NATURE OF WORK:
FLOOR DRAIN DETAIL THROUGH ROOF FLOOR CLEANOUT DETAIL TYPICAL CONDENSATE DRAIN TRAP
2 NOT TO SCALE 3 NOT TO SCALE 4 NOT TO SCALE 5 NOT TO SCALE

6" TYP CONCRETE


COVER COLLAR
1"
PAVEMENT GRADE
C:\Work\R18_70374-000_M_rprado.rvt

#3 BARS ALL

PROJECT TITLE
AROUND WITH 6"
EXPANSION OVERLAP
CLEANOUT PLUG
JOINT WITH
JOINT SEAL
CLEANOUT BOX SHORT LENGTH OF CAST IRON PIPE GRAVEL FLASHING RING OUTSIDE WALL
FURNISHED WITH CLEANOUT BOX
& GRAVEL STOP
ROOFING FELT BEARING PLATE OUTSIDE WALL INSIDE WALL
PIPE RISER
CONCRETE ENCASEMENT
4" MINIMUM COVER Project Number:
BRONZE DOWNSPOUT
OK70374-000
NOZZLE.
SHEET TITLE

STEEL DECK INSULATION PLUMBING SCHEDULE AND DETAILS


STANDARD ROOF DRAIN
FLOW PLAN NORTH
DECK CLAMP
INSULATION Date:
7/12/2018 8:24:34 AM

CEILING 12 JUL 2018

SEWER LINE
DOUBLE CLEANOUT WYE
SEQ. SHEET OF

TYPICAL TWO-WAY DOUBLE CLEANOUT TYPICAL ROOF DRAIN DETAIL ROOF DRAIN TERMINATION DETAIL 4' 2' 0 4'

6 NOT TO SCALE 7 NOT TO SCALE 8 NOT TO SCALE


SCALE: 1/4" = 1'-0"
P-501
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019

ABBREVIATIONS SYMBOLS GENERAL NOTES


C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

P
HPS STEAM, HIGH PRESSURE
A NO NORMALLY OPEN 3-WAY VALVE (PNEUMATIC)
1. THE MECHANICAL INSTALLATION SHALL COMPLY WITH THE CURRENT LOCAL MECHANICAL CODE.
AC ABOVE CEILING NIC NOT IN CONTRACT
MPS STEAM, MEDIUM PRESSURE 2. CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH MANUFACTURER'S CERTIFIED DRAWINGS.
ABV ABOVE O M TRANSITIONS TO ALL EQUIPMENT SHALL BE VERIFIED AND PROVIDED FOR EQUIPMENT FURNISHED.
OKLAHOMA CITY, OK 73112 405.416.8100

AFF ABOVE FINISHED FLOOR OC ON CENTER


3-WAY VALVE (ELECTRIC) 3. DIMENSIONS SHALL BE VERIFIED AND COORDINATED PRIOR TO PROCUREMENT OR FABRICATION.
ACC ACCESS OR ON ROOF LPS STEAM, LOW PRESSURE

Date Appr
COORDINATE THE WORK WITH OTHER TRADES INVOLVED. FIELD MODIFICATIONS SUCH AS OFFSETS IN
ACU AIR CONDITIONING UNIT OSD OPEN SIGHT DRAIN PIPING OR DUCTWORK NEEDED DUE TO OBSTRUCTIONS OR INTERFERENCES SHALL BE PROVIDED AT NO
AHU AIR HANDLING UNIT OV OUTLET VELOCITY HPC CONDENSATE RETURN HIGH PRESSURE ADDITIONAL COST.
ASME RELIEF VALVE
C.H. GUERNSEY & COMPANY

AV AIR VENT OA OUTSIDE AIR 4. SEE SPECIFICATIONS FOR DUCT PRESSURE CLASS.
B OS&Y OUTSIDE, SCREW & YOKE 5. PROVIDE AIR TURNING VANES IN ALL 90 DEGREE RECTANGULAR DUCT ELBOWS.
MPC CONDENSATE RETURN MEDIUM PRESSURE GATE VALVE
BDD BACKDRAFT DAMPER P 6. COORDINATE DIFFUSER, GRILLE AND REGISTER LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING
5555 N. GRAND BLVD.

BV BALL VALVE PSI POUNDS PER SQUARE INCH PLANS, EQUIPMENT, FURNITURE AND DOOR SWINGS.

Description
BFF BELOW FINISHED FLOOR PRESS PRESSURE LPC CONDENSATE RETURN LOW PRESSURE GATE VALVE W/OUTSIDE SCREW & YOKE 7. DUCT CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE SMACNA HVAC DUCT
BTU BRITISH THERMAL UNIT PD PRESSURE DROP CONSTRUCTION STANDARD.
C R HWS HEATING HOT WATER SUPPLY 8. LOCATE THERMOSTATS, TEMPERATURE SENSORS, HUMIDISTATS, CO2 SENSORS AND HUMIDITY SENSORS
CHECK VALVE AT 48" ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. COORDINATE LOCATIONS WITH OTHER
CLG CEILING REC RECOVERY EQUIPMENT, FURNITURE, DOOR SWINGS AND LIGHT SWITCHES.
CV CHECK VALVE REG REGISTER HWR HEATING HOT WATER RETURN BUTTERFLY VALVE 9. ALL DUCT SIZES ARE SHOWN ARE INSIDE CLEAR DIMENSIONS.
CHWP CHILLED WATER PUMP RH RELATIVE HUMIDITY
10. DAMPERS AND INTERIOR OF DUCT VISIBLE THOUGH AIR DEVICES SHALL BE PAINTED FLAT BLACK.
CWR CHILLED WATER RETURN RA RETURN AIR

Symbol
BOILER FEED WATER GLOBE VALVE 11. PROVIDE TRAPPED CONDENSATE DRAINS WITH APPROPRIATE DEPTH FOR ALL COOLING COILS.
CWS CHILLED WATER SUPPLY RAG RETURN AIR GRILLE
12. ACCESS PANELS IN DUCT WORK AND CEILINGS SHALL BE PROVIDED WHERE REQUIRED FOR OPERATION,
CRAC COMPUTER ROOM AIR CONDITIONER RAO RETURN AIR OPENING BALANCING, OR MAINTENANCE OF ALL MECHANICAL EQUIPMENT.
CONC CONCENTRIC RAR RETURN AIR REGISTER + BOILER BLOW OFF BALL VALVE 13. ALL DUCTWORK AND PIPING IS SHOWN SCHEMATICALLY. PROVIDE ALL TRANSITIONS, TURNING VANES,
COND CONDENSATE RPM REVOLUTIONS PER MINUTE ELBOWS, FITTINGS, ETC. TO ALLOW SMOOTH FLOWS. ALL DUCT SPLITS SHALL TRANSITION TO FULL SIZE OF

Appr
CD CONDENSATE DRAIN RTU ROOF TOP UNIT RS REFRIGERANT SUCTION LINE BALANCING VALVE THE SUM OF BOTH BRANCHES, UPSTREAM OF SPLIT.
CWP CONDENSER WATER PUMP S 14. PROVIDE CONCRETE HOUSEKEEPING PADS UNDER ALL FLOOR MOUNTED EQUIPMENT. REFER TO

Date
CR CONDENSER WATER RETURN SO SHUT OFF SPECIFICATIONS FOR DETAILED REQUIREMENTS.
RL REFRIGERANT LIQUID LINE STRAINER
CS CONDENSER WATER SUPPLY SDPR SMOKE DAMPER 15. VERIFY FINISHES WITH ARCHITECT PRIOR TO PURCHASING GRILLES, REGISTERS, DIFFUSERS, LOUVERS
AND OTHER AIR DISTRIBUTION DEVICES.

REVISIONS
CU CONDENSING UNIT SF SQUARE FEET
RH REFRIGERANT HOT GAS LINE UNION 16. PROVIDE DUCT FLEX CONNECTIONS ON ALL DUCTWORK CONNECTING TO EACH FAN, AIR HANDLING UNIT,
CF CUBIC FEET SS STAINLESS STEEL
AND FAN COIL UNIT.
CFH CUBIC FEET PER HOUR ST STATIC PRESSURE

Description
CWS 17. PROVIDE TRANSITIONS AT DIFFUSER NECKS AS REQUIRED TO MATCH SIZES OF FLEX DUCTS TO BE
CFM CUBIC FEET PER MINUTE STM STEAM CHILLED WATER SUPPLY
CONNECTED.
T NIGHT SETBACK THERMOSTAT
D SA SUPPLY AIR 18. SLEEVE AND/OR FIRESTOP ALL PENETRATIONS THROUGH RATED WALLS, CEILINGS, AND FLOORS WITH UL
N
DPR DAMPER SAG SUPPLY AIR GRILLE CWR CHILLED WATER RETURN LISTED ASSEMBLIES. FIRESTOP ASSEMBLIES SHALL BE EQUAL TO OR EXCEED THE RATING OF THE WALL,
DR DEW POINT SAR SUPPLY AIR REGISTER T THERMOSTAT CEILING OR FLOOR. SEE ARCHITECTURAL DRAWINGS FOR FINAL FINISHES. ALL FIRESTOP MATERIAL TO BE
DIFF DIFFUSER SF SUPPLY FAN PROVIDED BY A SINGLE MANUFACTURER.
CS CONDENSER WATER SUPPLY
DN DOWN T T TEMPERATURE SENSOR 19. INTERRUPTIONS TO EXISTING SERVICES SHALL BE SCHEDULED FOR TIMES OTHER THAN NORMAL
OPERATING HOURS. SUCH INTERRUPTIONS TO SERVICES SHALL NOT BE MADE WITHOUT THE PRIOR

Symbol
DT DRAW THROUGH TD TEMPERATURE DIFFERENCE S
CR CONDENSER WATER RETURN WRITTEN CONSENT OF THE OWNER'S REPRESENTATIVE AND PROPER COORDINATION WITH OTHER
DB DRY BULB THERM THERMOMETER H
T TRADES. PRE-WORK SHALL BE PERFORMED TO MAKE THE SHUTDOWN PERIOD AS BRIEF AS POSSIBLE.
HUMIDISTAT
E TG TRANSFER GRILLE
20. MAINTAIN A MINIMUM CLEARANCE OF 6" BETWEEN DUCTWORK, PIPING, EQUIPMENT, ETC. AND ALL FIRE
ECC ECCENTRIC TYP TYPICAL CD CONDENSATE DRAIN LINE RATED AND FIRE/SMOKE RATED ASSEMBLIES TO ALLOW FOR INSPECTION OF ASSEMBLY.
H
T HUMIDITY SENSOR
ELEC ELECTRIC UV ULTRA VOILET 21. WATER PRESSURE DROPS THROUGH COIL CONTROL VALVES SHALL NOT EXCEED 12 FEET OF WATER.
S
EAT ENTERING AIR TEMPERATURE UF UNDER FLOOR 22. SLEEVE AND SEAL ALL PIPING PENETRATIONS THROUGH BUILDING PARTITIONS AND MAINTAIN STC
EWT ENTERING WATER TEMPERATURE UG UNDERGROUND P PRESSURE SENSOR RATINGS. SEE ARCHITECTURAL DRAWINGS FOR PARTITION RATINGS.
ES EQUAL SPLIT UH UNIT HEATER 23. ANY DEVIATIONS IN ELECTRICAL REQUIREMENTS FROM THE BASIS OF DESIGN FOR MECHANICAL
EXH EXHAUST UNO UNLESS NOTED OTHERWISE S EMERGENCY SHUTDOWN SWITCH EQUIPMENT SHALL BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO ENSURE
EF EXHAUST FAN V COORDINATION WITH THE ELECTRICAL CONTRACTOR FOR PROPER WIRE SIZE, CONDUITS, DISCONNECTS,
FUSES, STARTERS, VFD'S, ETC. AT NO ADDITIONAL COST.

B. McCOMBS
EAG EXHAUST GRILLE VAC VACUUM
AIR DEVICE B C 24. PROVIDE AUTOMATIC AIR VENTS WITH ISOLATION VALVES IN ALL FINISHED AREAS AT ALL HIGH POINTS IN

M. WILSON
CO2 SENSOR

Submitted by:
Reviewed by:
R. PRADO
EXIST EXISTING VAV VARIABLE AIR VOLUME

Designed by:
DESIGNATION HYDRONIC PIPING SYSTEMS.

Checker
Drawn by:
EXT EXTERNAL VFD VARIABLE FREQUENCY DRIVE 230 CFM
25. PROVIDE UP-STREAM AND DOWN-STREAM TEST PLUGS FOR ALL COILS, BOILERS, CHILLERS, AND PUMPS.
F VEL VELOCITY
ECCENTRIC REDUCER, WATER 26. THESE CONTRACT DOCUMENTS HAVE BEEN SUBMITTED FOR CONTRACTOR DEVELOPMENT OF THE
FCU FAN COIL VF VENTILATION FAN CONSTRUCTION WORK PLAN. COORDINATION BETWEEN THE CONTRACTOR AND SUBCONTRACTORS IS THE
FT FEET W RESPONSIBILITY OF THE CONTRACTOR. CHANGES TO THESE DRAWINGS AS A RESULT OF THE
FPM FEET PER MINUTE WG WATER GAUGE CONCENTRIC REDUCER CONSTRUCTION COORDINATION AND THE DEVELOPMENT OF THE CONSTRUCTION WORK PLAN ARE THE
FDPR FIRE DAMPER W WATTS RESPONSIBILITY OF THE CONTRACTOR.
F/SDPR FIRE/SMOKE DAMPER WB WET BULB 27. THESE CONTRACT DOCUMENTS DETAIL THE CONCEPT OF THE WORK. COORDINATION OF CONCEPTUALLY
D DIRECTION OF FLOW
F&T FLOAT & THERMOSTATIC EQUAL BUT NOMINALLY DIFFERENT SYSTEMS OR PRODUCTS SELECTED BY CONTRACTOR ARE THE
RESPONSIBILITY OF THE CONTRACTOR.

CRESSMAN DINING FACILITY EXPANSION


FTR FLUE THRU ROOF DROP IN DUCTWORK

GOODFELLOW AIR FORCE BASE, TEXAS


SLOPE DOWN 28. MOUNT ALL EQUIPMENT ACCORDING TO REQUIREMENTS OF UFC 4-010-1.
FR FROM
G R
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE RISE IN DUCTWORK PRESSURE REDUCING VALVE
G GAS
GC GENERAL CONTRACTOR ANCHOR

17th TRAINING WING


GR GRILLE

NATURE OF WORK:
MANUAL BALANCING DAMPER IN DUCT
H EXPANSION JOINT
HVU HEATING AND VENTILATING UNIT
HHWP HEATING HOT WATER PUMP
PIPE GUIDE
HWR HEATING HOT WATER RETURN
AIR FLOW MEASUREMENT STATION
HWS HEATING HOT WATER SUPPLY
HP HORSEPOWER CONNECT TO EXISTING
P
I
IN INCHES
K STATIC PRESSURE SENSOR
KW KILOWATTS PRESSURE GAUGE
L
LAT LEAVING AIR TEMPERATUE
LWT LEAVING WATER TEMPERATURE
FIRE DAMPER
LD LINEAR DIFFUSER THERMOMETER
C:\Work\R18_70374-000_M_rprado.rvt

M
MBH 1000 BTU PER HOUR STEAM TRAP
MAU MAKE-UP AIR UNIT

PROJECT TITLE
MBD MANUAL BALANCING DAMPER FIRE/SMOKE DAMPER
MAX MAXIMUM
MC MECHANICAL CONTRACTOR THERMOMETER WELL
MIN MINIMUM
MTZ MOTORIZED
MTD MOUNTED
N
ND NECK DIAMETER
NC NORMALLY CLOSED Project Number:

OK70374-000

SHEET TITLE

HVAC LEGEND

Date:
7/11/2018 7:30:40 PM

12 JUL 2018

SEQ. SHEET OF

M-001
C
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

CU-1
OKLAHOMA CITY, OK 73112 405.416.8100

A B

Date Appr
AA BB CC DD EE FF GG HH JJ
C.H. GUERNSEY & COMPANY

RS
RH
RL
5555 N. GRAND BLVD.

Description
UNDERGORUND 4" PVC FOR REF. PIPING. COORDINATE
WITH ELECTRICAL LINES AND ROOF DRAIN PIPING

RL
RH
RS
8

Symbol
7.9

Appr
7.8

RS

Date
AC-1

RH
D D D

REVISIONS
485 490 490 VESTIBULE

RL
104

Description
7 14x14 D G
6"ø DUCT UP THRU ROOF D
415 RA 415
G G D
RS B
RA RA 415 RH 215
C VAV-6 RL
D T
C 1-1/4" 255 1-1/2"
6 485 255 HWR
20x14
HWS

Symbol
HWR
CORRIDOR
3/4" VAV-2 T
EF-1 EXISTING WOMEN'S 115
C
VAV-3 14x12 12ø 108
T MECHANICAL
5.6 VAV-3
10x12 107
DINING VAV-2 COMM
102 106
T 18"x18" RAO 42x22 24x12
D 1-1/4" 1
465 C
HWS

C C DU-1 FLEX DUCT M-401


2

36x22

B. McCOMBS
255 16ø 255
M-401

M. WILSON

Submitted by:
Reviewed by:
R. PRADO
Designed by:
CONF. ROOM

Checker
30x26

Drawn by:
111 EXISTING JAN. EXISTING DINING
G 3/4" G A 109 116
5 A
12x14 RA RA 6x6 RAO
100 130
G STORAGE
1" 12ø
RA VAV-1 OFFICE F F 110
112 RA RA

D C C 16ø EXISTING MEN'S


465 255 260 8ø VAV-4 10x10 114

CRESSMAN DINING FACILITY EXPANSION


HWR

GOODFELLOW AIR FORCE BASE, TEXAS


22x18

PRIVATE DINING RAO F


4
HWS

VAV-8 30"x30" UP THRU RA


103 10x12 14x12 12ø
VAV-7 32x28 ROOF TO H-2 22"x20" RAO
A STUDENT ADMIN. A
VAV-7 T 3/4" 110 110
3.8 3/4" HWS
3/4" 113
HWR
16x14
20x14

14ø 10x14

17th TRAINING WING


NATURE OF WORK:
C
D C C VAV-5 VAV-4 T C
3.4 VAV-8 T
495 G 260 G 255 VAV-5 T
RA RA B
D D D 215
415 415 415
G
S
14x14 RA
3
AT/FP SHUTDOWN VESTIBULE
WITH LOCKABLE 101
D D D
495 500 500 ENCLOSURE
AC-2

2.2
C:\Work\R18_70374-000_M_rprado.rvt

2.1

PROJECT TITLE
2

Project Number:

HVAC FLOOR PLAN - AREA A OK70374-000

1 SCALE: 1/8" = 1'-0" SHEET TITLE

PLAN NORTH HVAC FLOOR PLAN - AREA A


A B

Date:
7/11/2018 7:30:45 PM

12 JUL 2018

KEY PLAN SEQ. SHEET OF

8' 4' 0 8'

M-101
SCALE: 1/8" = 1'-0"
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
OKLAHOMA CITY, OK 73112 405.416.8100

Date Appr
C.H. GUERNSEY & COMPANY
5555 N. GRAND BLVD.

Description
E F G
D

EXISTING DDC CONTROL CABINET.


CONNECT NEW AT/FP SHUTDOWN SWITCH TO HERE.
ALL NEW AND EXISTING AHUS, HVUS, MAUS, ETC.
9

Symbol
SHALL SHUTOFF UPON ACTIVATION OF SWITCH.

Appr
Date

REVISIONS
Description
7

Symbol
6

B. McCOMBS
M. WILSON

Submitted by:
Reviewed by:
R. PRADO
Designed by:

Checker
Drawn by:
ALT#1: FOOD PREP ADDITION

EXISTING DUCTWORK

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


EXIST.
EXISTING KITCHEN EXIST. 550
117 550

36x24

17th TRAINING WING


NATURE OF WORK:
EXIST. EXIST. EXIST.
550 550 550
12x16
EXIST.
24x16 550
28x16 28x24
RE-BALANCE EXISTING DIFFUSER
TO SPECIFIED CFM (TYP.)

EXIST. EXIST.
650 650
C:\Work\R18_70374-000_M_rprado.rvt

14ø

EXIST.
550

PROJECT TITLE
2
PREPARATION ROOM
1 118 E
700 Project Number:

OK70374-000

SHEET TITLE

PLAN NORTH HVAC FLOOR PLAN - AREA B


A B

Date:
7/11/2018 7:30:47 PM

12 JUL 2018

HVAC FLOOR PLAN - AREA B KEY PLAN


1 SCALE: 1/8" = 1'-0" SEQ. SHEET OF

8' 4' 0 8'

M-102
SCALE: 1/8" = 1'-0"
C.H. GUERNSEY & COMPANY
7/11/2018 7:30:49 PM C:\Work\R18_70374-000_M_rprado.rvt 5555 N. GRAND BLVD.
OKLAHOMA CITY, OK 73112 405.416.8100
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

1
2
3
4
5
6
7
8
9

2.1
2.2
3.4
3.8
5.6
7.8
7.9

1
AA
BB

SCALE: 1/8" = 1'-0"


CC
DD

MECHANICAL ROOF PLAN - AREA A


EE
FF

ROOF CAP

BOILER COAXIAL FLUE/VENT


GG
HH

CU-2

3" VTR

H-2
3" RD
3" OD

H-1

3" OD

3" RD
JJ
A
B
C

PLAN NORTH

8'
A

4'
0

SCALE: 1/8" = 1'-0"


KEY PLAN
B

8'

PROJECT TITLE Designed by:


SEQ.

M. WILSON
Date:

NATURE OF WORK: Drawn by:


CRESSMAN DINING FACILITY EXPANSION R. PRADO
SHEET TITLE
Project Number:

SHEET

17th TRAINING WING Reviewed by:


12 JUL 2018
ROOF PLAN
OK70374-000

Checker
M-103

GOODFELLOW AIR FORCE BASE, TEXAS


Symbol Description Date Appr
Submitted by:
OF

B. McCOMBS REVISIONS Symbol Description Date Appr


C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

HH JJ A
OKLAHOMA CITY, OK 73112 405.416.8100

6" COAXIAL VENT/FLUE UP THRU ROOF

Date Appr
HWP-1
6
C.H. GUERNSEY & COMPANY

B-1 16x14 10x14


LOW-LOSS HEADER
5555 N. GRAND BLVD.

HWR

Description
16x14
AIR SEPERATOR

HWS MECHANICAL

RH
RL
RS
107 DDC CONTROLS
ET-1 VAV-6
5.6

Symbol
HWP-2 1-1/2"
22"x20" OA DN. FR. H-1
14ø

2"

Appr
42x22 5.6 6

Date
24x12

REVISIONS
18x20
30x26
FLEX DUCT AHU-1
2

Description
M-401

3
M-401 COAXIAL FLUE

Symbol
HWS
HVAC ENLARGED PLAN - MECHANICAL ROOM
1 SCALE: 1/4" = 1'-0"

G
AIR
2" HWP-2 SEPERATOR
B-1
RPBP

HWR

B. McCOMBS
HWS

M. WILSON

Submitted by:
Reviewed by:
R. PRADO
Designed by:
ET-1

Checker
Drawn by:
HWP-1
HWR

CD
HWR
EWH-1

LOW-FLOW HEADER FD-B

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


CONDENSING BOILER DETAIL
3 SCALE: 1/4" = 1'-0"

17th TRAINING WING


NATURE OF WORK:
3
M-401
VAV-3 OA INTAKE AIR HOOD
VAV-2 H-1
EBTRON FLOW MEASURING
12x10 12x14 22x42 STATION

SUPPLY AIR
PLENUM
C C
12x24
255 255 22x42

20x22
C:\Work\R18_70374-000_M_rprado.rvt

34x56
18"x28" RA
DU-1

PROJECT TITLE
20x26
FLEX DUCT
30x26
FAN
DINING COMM
RETURN AIR PLENUM
102 106
AHU-1
44x32
MECHANICAL
Project Number:
107
FINISHED FLOOR MIXING BOX OK70374-000

SHEET TITLE

HEATING COIL ENLARGED PLANS


CONCRETE PAD
DX COIL
REHEAT
ENLARGED HVAC PLAN - AHU SECTION Date:
7/11/2018 7:30:52 PM

12 JUL 2018
2 SCALE: 1/4" = 1'-0"

SEQ. SHEET OF

4' 2' 0 4'


M-401
SCALE: 1/4" = 1'-0"
1-1/8" 1-1/8"

1-1/2 "
1" R
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019

3-1/4 "
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

2-1/4 " 2-1/4 "


45° 2" R
30° MAX.
2-1/4 " R 45°
60.00° R.A. DUCT
OKLAHOMA CITY, OK 73112 405.416.8100

PLAN OR SIDE VIEW SMALL SINGLE VANE ELBOW USE FOR


AIR FLOW ELBOWS UP TO 31" IN WIDTH AND/OR DEPTH

Date Appr
30° MAX. 22.5° MAX. INLET 4-1/2 " R
FLANG
C.H. GUERNSEY & COMPANY

E WIDTH(W)
AIR FLOW AIR FLOW 45° 45°

MIN 6"
5555 N. GRAND BLVD.

DEPTH(D)

Description
30° MAX. 22.5° MAX.
NOTE: TYPICAL FOR ALL RETURN AIR
INLETS NOT EQUIPPED WITH
RETURN AIR GRILLES OR REGISTERS
PLAN OR SIDE VIEW PLAN OR SIDE VIEW FRONT VIEW SIDE VIEW
LARGE DOUBLE VANE ELBOW USE FOR
ELBOWS 32" OR WIDER AND ANY DEPTH TYPICAL ELBOW

TYPICAL DUCT TRANSITIONS TYPICAL RETURN AIR INLET NOTES:

Symbol
1 NOT TO SCALE 2 NOT TO SCALE 1. ALL SQUARE OR RECTANGULAR ELBOWS SHALL HAVE ONE OF THE TWO TYPES OF TURNIG VANES SHOWN ABOVE.
2. VANES SHALL BE CONSTRUCTED, SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.
3. ALL SQUARE AND RECTANGULAR ELBOWS SHOWN ON PLANS FOR SUPPLY DUCT MAY BE MADE WITH RADIUSED

Appr
ELBOWS PROVIDED SPACE PERMITS RADIUS INSTALLATION AND/OR THERE ARE NO OUTLETS OR TAKE-OFFS
WITHIN 5 DIAMETERS ON THE DOWNSTREAM SIDE OF THE ELBOW.
4. FOR VELOCITES OVER 1500 FPM, WELD EVERY 6TH VANE TO RUNNER.
STRAP HANGERS

Date
(TABLE 1)
TABLE 1 STRAP HANGERS (PAIR) SPACED
SQUARE OR RECTANGULAR ELBOWS

REVISIONS
W 1/2W
HANGER
W + D MAX.
72"
10' - 0" MAX.
1" X 18 GA.
8' - 0" MAX.
1" X 20 GA.
5' - 0" MAX.
1" X 22 GA. 60" MAX 3 NOT TO SCALE 1/3W

Description
LOAD
RATED BAND OF SAME 96" 1" X 16 GA. 1" X 18 GA. 1" X 20 GA. 1/6W
FASTENERS SIZE AS HANGER
120" 1-1/2" X 16 GA. 1" X 16 GA. 1" X 18 GA. 12" OC VANE R
STRAP

D
MAX.
SECURE WIRE 36" DIA. MAX. 168" 1-1/2" X 16 GA. 1-1/2" X 16 GA. 1" X 16 GA. SPACING MAIN SUPPLY DUCT R SHALL EQUAL TO
10" DIA. MAX. W OR GREATER THAN
192" - 1-1/2" X 16 GA. 1" X 16 GA.
3" 45.00° 1/6 W
193" SPECIAL ANALYSIS REQUIRED 1" MINIMUM

Symbol
PROVIDE
HANGER RODS
VOLUME DAMPER SHORT RADIUS ELBOW WITH TWO VANES
1/4 W - 4" MIN
(TABLE 2)
BRANCH DUCT
L
LOAD
HANGER RODS, 6" MAX
RATED W
WIRES OR HANGER RODS 2/3W
FASTENERS
STRAPS (TABLE 2)
L PLAN VIEW 1/3W
6" MAX
REFER NOTE 2 BRANCH DUCT TAKE-OFF
R
VANE
SEE PLANS

B. McCOMBS
M. WILSON
FOR

Submitted by:
Reviewed by:
R. PRADO
Designed by:
DIMENSIONS W

Checker
Drawn by:
ALTERNATE.
NUTS VERIFY UPPER
24" DIA. MAX. BAND OVER 36" DIA.
TRAPEZE LOAD
CAPACITY SHORT RADIUS ELBOW WITH ONE VANE
ANGLE (TABLE 3) MAIN SUPPLY
MINIMUM HANGER SIZES FOR ROUND DUCT ANGLE (TABLE 3)
NUTS
DUCT
MAX. ROD VOLUME
DIA. WIRE DIAMETER STRAP
SPACING DIA. TURNING VANES DAMPER
10" DN 12' (1) 12 GA. 1/4" 1"x22 GA.
TABLE 2 ALLOWABLE HANGER LOAD, MAX. TABLE 3 TRAPEZE ANGLE LOAD, MAX. SQUARE ELBOW SHOWN, W

CRESSMAN DINING FACILITY EXPANSION


11-18" 12' (2)12 GA. OR (1)8 GA. 1/4" 1"x22 GA. SUPPLY

GOODFELLOW AIR FORCE BASE, TEXAS


PROVIDE RADIUSED WHEN
STRAPS LBS. RODS LBS. L 2" X 2" X 1/4" 2 1/2" X 2 1/2" X 1/4" BRANCH
19-24" 12' (2) 10 GA. 1/4" 1"x22 GA. SHOWN ON PLANS
12' (2) 8 GA. 3/8" 1"x20 GA. 2 - 1" X 22 GA. 520 2 - 1/4" DIA. 540 36" 1200 LBS 1940 LBS R
25-36" PLAN VIEW
37-50" 12' --- (2)3/8" (2)1"x20 GA. 2 - 1" X 20 GA. 640 2 - 3/8" DIA. 1360 48" 1160 LBS 1900 LBS AIR SPLIT TYPE DUCT TAKE-OFF
51-60" 12' --- (2)3/8" (2)1"x18 GA. 2 - 1" X 18 GA. 840 2 - 1/2" DIA. 2500 60" 1060 LBS 1800 LBS

61-84" 12' --- (2)3/8" (2)1"x16 GA. 2 - 1" X 16 GA. 1400 2 - 5/8" DIA. 4000 72" 900 LBS 1640 LBS
2 - 3/4" DIA. 6000 84" 660 LBS 1400 LBS TYPICAL SUPPLY DUCT TAKEOFFS STANDARD RADIUS ELBOW

17th TRAINING WING


6

NATURE OF WORK:
NOTES: 96" 320 LBS 1060 LBS NOT TO SCALE NOTES:
1. STRAPS ARE GALVANIZED STEEL; RODS ARE UNCOATED OR GALVANIZED NOTES:
STEEL; WIRE IS BLACK ANNEALED, BRIGHT BASIC OR GALVANIZED STEEL; 1. THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND
ALL ARE ALTERNATIVES. 1. TABULATED DATA FROM SMACNA ALLOWS FOR DUCT 2. ALL STANDARD RADIUS ELBOWS SHOWN ON PLANS MAY BE MADE SHORT
2. TABULATED DATA FROM 1995 SMACNA STANDARDS ALLOWS FOR DUCT REINFORCING AND INSULATION, BUT NO EXTERNAL LOAD. RADIUS ELBOES. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES WHICH
REINFORCING AND INSULATION, BUT NO EXTERNAL LOAD. 2. PROVIDE HIGH DENSITY INSERT AT TRAPEZE FOR INSULATED SHALL BE CONSTRUCTED, SUPPORTED AND FASTENED AS RECOMMENDED
3. HANGERS MUST NOT DEFORM DUCT SHAPE. DUCTS. BY SMACNA

ROUND DUCT HANGARS RECTANGULAR DUCT HANGARS RADIUS ELBOWS


4 NOT TO SCALE 5 NOT TO SCALE 7 NOT TO SCALE
C:\Work\R18_70374-000_M_rprado.rvt

INSULATED SUPPLY

PROJECT TITLE
WIRE FROM STRUCTURE
DUCT EXTEND SOUND BOOT 12" PAST THE LINE
PRE- 1-1/2" WIDE STRAP SUSPEND FROM OF SIGHT. BOOT WIDTH TO BE SAME AS
INSULATED STRUCTURE USINF 1-1/2" DEVICE. SEE BOOT SCHEDULE FOR
FLEXIBLE DUCT METAL STRAPS HEIGHT
DISCHARG
SHEET METAL ELBOW PROVIDE FIRE DAMPERS SUPPORT FROM
E PLENUM
W/ EXTERNAL 1" LONG SHEET AT PENETRATION OF ALL STRUCTURE INDEPENDENT
INSULATION METAL SCREW (TYP) RATED WALLS. SEE 12" OF CEILING
PLANS
R/A BOOT SCHEDULE
DEVICE SIZE BOOT HEIGHT Project Number:
VOLUME
CONICAL SPIN-IN VAV TERMINAL R/A

HEIGHT
DAMPE 24"x8" 6"
FITTING WITH VOLUME OK70374-000
R
DAMPER 24"x12" 10"
1.5 X FLEXIBLE DUCT INLET DUCT SHEET TITLE
DIAMETER 24"x16" 12"
NO MORE THAN 18" WHERE PRATICAL TO HVAC DETAILS
24"x24" 14"
T
SHEET METAL DUCT
ALLOW ACCESS FOR SERVICING THRU
SIGH LINE WITH 1/2" DUCTLINER
CEILING CEILING O F
E 6" MIN.
LIN Date:
7/11/2018 7:30:53 PM

T-BAR CEILING
12 JUL 2018
SAME SIZE AS R/A DEVICE.
NOTES:
1. USE THE SUPPORT METHOD PRESCRIBED FOR RECTANGULAR DUCT IN
NOTES: SPECIFICATIONS
SUPPLY DIFFUSER 1. SEAL ALL CONNECTIONS WITH SEALANT 2. DO NOR OBSTRUCT THE ACCESS PANELS WITH SUPPORT STRAPS. CEILING RETURN AIR

R/A
DEVICE IN CEILING SEQ. SHEET OF
2. MAXIMUM RUN-OUT LENGTH OF FLEXIBLE DUCT IS 5'-0" 3. TYPICAL FOR FAN POWERED AND NON-FAN POWERED UNITS.

DIFFUSER INSTALLATION VAV TERMINAL MOUNTING DETAIL TYPICAL R.A. SOUND BOOT DETAIL M-501
8 NOT TO SCALE 9 NOT TO SCALE 10 NOT TO SCALE
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

CALIBRATED BALANCING VALVE

RETURN
OKLAHOMA CITY, OK 73112 405.416.8100

VALVE, (TYPICAL)

Date Appr
3-WAY CONTROL VALVE
C.H. GUERNSEY & COMPANY

UNION, (TYPICAL)
MANUAL AIR VENT
TEST PLUG, (TYPICAL)
REDUCER, TYPICAL
5555 N. GRAND BLVD.

SUPPLY
UNION

Description
PRESSURE GAUGE
TEST PLUG
VIBRATION ISOLATOR, TYP.
HEATING
HOT MODULATING CONTROL VALVE REF: NOTE
STRAINER W/HOSE END DRAIN VALVE FLOW CONTROL VALVE UNION, TYP. P
WATER
1/4" BALL

Symbol
COIL COIL BALL VALVE
VALVE, TYP.
COPPER PIPE

THERMOMETER ISOLATING UNION

Appr
(TYPICAL)

UNION

Date
1/2" UNLESS
P&T PLUG
TEST PLUG OTHERWISE SHOWN
ISOLATION
IN-LINE PUMP

REVISIONS
VALVE, TYP
STRAINER
DRAIN VALVE W/HOSE CONNECTION CHECK VALVE
BALL VALVE STEEL PIPE (WHEN USED)

Description
Y-STRAINER W/
COPPER PIPE CALIBRATED BALANCING VALVE BLOW-OFF VALVE &
W/FLOW MEASUREMENT PORTS HOSE CONNECTION
ISOLATING UNION
NOTE:
NOTE:
PROVIDE 2-WAY OR 3-WAY CONTROL VALVES AS INDICATED HANGER SUPPORTS 2 SIDES
OFFSET PIPING FOR COIL REMOVAL. DO NOT ON THE CONTROL DRAWINGS. PROVIDE UNIONS ON COIL SIDE
BLOCK ACCESS DOORS. OF S.O. VALVES IF ALL SWEAT CONNECTIONS ARE USED. REDUCER, TYP. (IF REQ'D)

Symbol
PIPING AT AHU HEATING COILS H.H.WW. PIPING AT VAV UNIT IN-LINE PUMP PIPING DETAIL
1 NOT TO SCALE 2 NOT TO SCALE 3 NOT TO SCALE

B. McCOMBS
M. WILSON

Submitted by:
Reviewed by:
R. PRADO
Designed by:

Checker
Drawn by:
SLOPE SUCTION LINE IN THE
DIRECTION OF FLOW

LR
A/C COOLING COIL

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


EXPANSION VALVE REFRIGERANT PIPING SHALL BE SIZED IN
ACCORDANCE WITH MANUFACTURERS
RECOMMENDATIONS

PRESSURE GAGE WITH NEEDLE DIAPHRAGM EXPANSION TANK


VALVE. (TYP.) SUSPENDED FROM STRUCTURE PER.
WALL
FILTER-DRIER MANUFACTURER'S INSTRUCTIONS.
EXPANSION LIFTING

17th TRAINING WING


NATURE OF WORK:
VALVE BULB LUG
RPBP COMPLETE WITH SHUT-OFF TANK CHARGING VALVE
SIGHT GLASS VALVES, UNIONS, AND DRAIN.

AUTO AIR
DRAIN PAN 1" QUICK FILL LINE
P VENT P
CONDENSING UNIT ON
CONCRETE PAD 1"
CONDENSATE LINE TANK DRAIN
TO FLOOR DRAIN

1" CW SUPPLY INSULATING UNION


SEAL WATER-TIGHT AIR SEPARATOR
PRESSURE REGULATING VALVE
GRADE SET AT 12 PSI THERMOMETER
MAKE CONN.
FROM SYSTEM FROM SIDE OF
C:\Work\R18_70374-000_M_rprado.rvt

FLOOR PIPE TO PUMP SUCTION SIDE


DRAIN W/H.B.
OF SYSTEM
UNION OR FLANGE 1"

PROJECT TITLE
SHUT OFF VALVE

INSULATING UNION AS
SEAL WATER TIGHT REQUIRED BETWEEN DIS-
SIMILAR METALS.

Project Number:

OK70374-000
LIQUID & SUCTION LINES UNDER GRADE SHALL BE
INCASED IN SCH. 40 PVC PIPE - REFRIGERANT LINES IN SHEET TITLE
PVC PIPE SHALL BE SOFT COPPER DRAIN W/H.B.
HVAC DETAILS

REFRIGERANT PIPING DIAGRAM DIAPHRAGM EXPANSION TANK, AIR SEPARATION AND WATER MAKEUP SYSTEM Date:
7/11/2018 7:30:54 PM

4 NOT TO SCALE 5 NOT TO SCALE


12 JUL 2018

SEQ. SHEET OF

M-502
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

AIR DISTRIBUTION DEVICE SCHEDULE SYSTEMS MATERIAL SCHEDULE - HVAC


BASIS OF DESIGN NECK SIZE RANGE (MIN/MAX) MAX A.P.D. INSULATION
MARK SYSTEM TYPE (MFR & MODEL NO.) DESCRIPTION (IN) AIRFLOW (CFM) THROW (FT.) NC (IN. WC) NOTES SYSTEM MATERIAL THICKNESS TYPE JACKET
OKLAHOMA CITY, OK 73112 405.416.8100

A SUPPLY TITUS OMNI 24"x24" SQUARE PLAQUE DIFFUSER 6 90/140 4/9 <21 0.08 REFRIGERANT RS/RL TYPE "ACR" COPPER 1/2" FLEX. UNICELLULAR --
B SUPPLY TITUS OMNI 24" x24" SQUARE PLAQUE DIFFUSER 8 170 6/12 <21 0.08

Date Appr
C SUPPLY TITUS OMNI 24"x24" SQUARE PLAQUE DIFFUSER 10 325/410 8/14 <21 0.08 L.P. S/A DUCTWORK G.I.S.M. 1" -- --
D SUPPLY TITUS OMNI 24"x24" SQUARE PLAQUE DIFFUSER 12 325/510 12/16 <21 0.08 L.P. S/A RUNOUTS G.I.S.M. 1" -- --
C.H. GUERNSEY & COMPANY

E SUPPLY TITUS OMNI 24" x24" SQUARE PLAQUE DIFFUSER 14 428/748 13/19 <21 0.08 L.P. S/A FLEX DUCT 1" INSULATED FLEX -- -- --
F RETURN TITUS 355RL 24"x12" RETURN GRILLE - 0/830 - <21 0.05 WITH SOUND BOOT, REFER PLANS FOR TYPE L.P. R/A DUCTWORK G.I.S.M. 1" -- --
G RETURN TITUS 355RL 24"x24" RETURN GRILLE - 0/1800 - <21 0.05 WITH SOUND BOOT, REFER PLANS FOR TYPE L.P. EXHAUST DUCTWORK G.I.S.M. -- -- --
5555 N. GRAND BLVD.

Description
VAV UNIT SCHEDULE
HEATING DATA
MARK DESCRIPTION CFM MIN CFM TERMINAL INLET MAX SP DOWNSTREAM SP MBH HEATING CFM GPM @ 140°F MAX WTR PD BASIS OF DESIGN
VAV-1 PRESSURE INDEPENDENT 930 465 1.0 0.3 30.1 465 2.2 5 TITUS DESV

Symbol
VAV-2 PRESSURE INDEPENDENT 1020 545 1.0 0.3 14.7 545 1.3 5 TITUS DESV
VAV-3 PRESSURE INDEPENDENT 1950 975 1.0 0.3 56.5 975 4.2 5 TITUS DESV
VAV-4 PRESSURE INDEPENDENT 450 225 1.0 0.3 6.2 225 0.7 5 TITUS DESV
VAV-5 PRESSURE INDEPENDENT 1460 730 1.0 0.3 47.1 730 3.6 5 TITUS DESV

Appr
VAV-6 PRESSURE INDEPENDENT 1460 730 1.0 0.3 47.1 730 3.6 5 TITUS DESV
VAV-7 PRESSURE INDEPENDENT 1990 995 1.0 0.3 56.9 995 4.2 5 TITUS DESV

Date
VAV-8 PRESSURE INDEPENDENT 1030 545 1.0 0.3 14.7 545 1.3 5 TITUS DESV
1. MAX TERMINAL STATIC PRESSURE IS THE MAXIMUM ALLOWABLE STATIC PRESSURE LOSS IN INCHES OF WATER THRU THE VAV TERMINAL, INCLUDING THE HEATING COIL AT MAX CFM SHOWN.

REVISIONS
2. PROVIDE 1, 2, 3, OR 4 ROW COIL AS NECESSARY TO ACHIEVE THE HEATING CAPACITY AT THE CONDITIONS SHOWN.
3. PROVIDE ALL UNITS W/ 1" LINER.

Description
4. ENSURE UNITS HAVE MINIMUM 10-BIT A/D CONVERTER & FLOW SENSOR W/ A MIN. VELOCITY PRESSURE SIGNAL OF 0.004 IN. W.G. TO MEASURE LOW MINIMUM AIRFLOWS.

AIR HANDLING UNIT SCHEDULE1


ELECTRICAL SUPPLY FANWALL DATA DX COOLING COIL PREHEATING HOT WATER COIL HOT GAS REHEAT COIL FILTER DATA
MARK DESCRIPTION VOLTS/PHASE FLA # FANS TOTAL CFM O.A. CFM E.S.P. (IN. WG.) T.S.P. (IN. WG.) RPM H.P. EACH FAN B.H.P. EACH FAN TOTAL MBH SENSIBLE MBH EAT DB (°F) EAT WB (°F) LAT DB (°F) LAT WB (°F) OA DB/WB (°F) HEATING CFM CAPACITY (MBH) EAT/LAT DB (°F) GPM EWT/LWT (°F) MAX. WTR. P.D. FT. CAPACITY (MBH) LAT DB/WB (°F) EFF/MERV BASIS OF DESIGN

Symbol
AHU-1 AIR HANDLING UNIT 203/3 37 2 9,500 2,710 2.0 3.21 2750 8 3.98 276.6 235.9 85.4 65.0 53.1 51.3 100/70 9,500 83.8 38.1/55.0 5.6 140/110 10 158 70/58.37 8 AAON V3-ER
1. E.S.P. DOES NOT INCLUDE ALLOWANCE FOR FILTERS.

COOLING ONLY DUCTLESS MINI-SPLIT SCHEDULE CONDENSING UNIT SCHEDULE


FAN DATA COOLING DATA AIRFLOW RATE ELECTRICAL DATA
MARK - INDOOR MARK - ENT. AIR W.B. MARK DESCRIPTION (CFM) VOLT/PHASE MCA (A) MOCP (A) BASIS OF DESIGN
UNIT OUTDOOR UNIT DESCRIPTION MOUNTING TOTAL CFM FAN SPEED FAN WATTS TOTAL BTU/H ENT. AIR D.B. DEG F DEG F AMBIENT DEG F MINIMUM SEER BASIS OF DESIGN CU-1 AIR-COOLED CONDESNING UNIT 9,500 208/3 134 150 AAON CFA
DU-1 CU-2 DUCTLESS MINI-SPLIT WALL 425 HIGH 30 12,000 80 67 105 15.2 MITSUBISHI PKA-A12HA6 CU-2 CONDENSING UNIT 1,200 208/1 13 15 MITSUBISHI PUY

B. McCOMBS
1. PROVIDE ACU'S W/ ACCESSORY WIND BAFFLE FOR LOW AMBIENT OPERATION DOWN TO 0° F.

M. WILSON

Submitted by:
Reviewed by:
R. PRADO
Designed by:
2. PROVIDE R410a REFRIGERANT.

Checker
Drawn by:
3 DC INVERTER DRIVEN COMPRESSOR.
4 PROVIDE EACH ACU W/ CONDENSATE PUMP.

DIAPHRAGM EXPANSION TANK SCHEDULE


SIZE
MARK DESCRIPTION DIA. LENGTH CHARGE PSI FULL CAP. GALLONS ACCEPTANCE VOLUME (GAL) BASIS OF DESIGN REMARKS

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


ET-1 PRE-CHARGED DIAPHRAGM EXPANSION TANK 8" 12-5/8" 12 2.0 0.6 B&G HFT

EXHAUST FAN SCHEDULE


AIRFLOW E.S.P. (IN. VOLTAGE
MARK BASIS OF DESIGN (MFR & MODEL NO.) DESCRIPTION (CFM) WC) W FAN SPEED (RPM) (V/ø/HZ) NOTES
EF-1 COOK GEMINI CEILING EXHAUST FAN 70 0.20 58 900 115/1/60

17th TRAINING WING


NATURE OF WORK:
HOOD SCHEDULE
AIRFLOW E.S.P. (IN.
MARK BASIS OF DESIGN (MFR & MODEL NO.) DESCRIPTION (CFM) WC) SIZE (IN.) NOTES
H-1 GREENHECK GRSI-30 INTAKE AIR HOOD 2,710 0.05 30 PROVIDE WITH MOTORIZED DAMPER
H-2 GREENHECK GRSI-30 RELIEF AIR HOOD 2,710 0.05 30 PROVIDE WITH MOTORIZED DAMPER

PUMP SCHEDULE
MARK DESCRIPTION GPM HEAD FT. WTR. POWER RPM BASIS OF DESIGN REMARKS
C:\Work\R18_70374-000_M_rprado.rvt

HWP-1 HEATING HOT WATER PRIMARY PUMP 22 15 625 W 1800 GRUNDFOS UPS 32-160 COORDINATE WITH BOILER PRESSURE DROP
HWP-2 HEATING HOT WATER SECONDARY PUMP 27 40 1.5 HP 1800 B&G E-90

PROJECT TITLE
HHW BOILER SCHEDULE
Mark DESCRIPTION INPUT MBH OUTPUT MBH OPERATING PRESSURE LEAVING TEMP. DEG. F BASIS OF DESIGN REMARKS
B-1 WALL MOUNTED CONDENSING BOILER 352 333 30 140 VIESSMANN VITODENS 200-W GENERAL NOTES:
1. FURNISH APPROPRIATE MOTOR STARTER FOR ALL MOTORS.
2. FOR ALL MOTORS - MOTOR BRAKE HORSEPOWER SHALL NOT EXCEED 85% 0F NORMAL NAMEPLATE HORSEPOWER (WITHOUT
CONSIDERATION OF THE SERVICE FACTOR). Project Number:
AIR CURTAIN SCHEDULE 3. FAN RPM AT DESIGN CONDITIONS SHALL NOT EXCEED 85% OF MANUFACTURER'S MAXIMUM FOR THE CLASS OF CONSTRUCTION.
OK70374-000
MARK DESCRIPTION CFM NOZZLE WIDTH (IN) HP MAX. VELOCITY AT NOZZLE (FPM) VOLT/PHASE BASIS OF DESIGN REMARKS 4. PUMP IMPELLER DIAMETER SHALL NOT EXCEED 10/11THS OF THE MAXIMUM IMPELLER DIAMETER.
AC-1 AMBIENT AIR CURTAIN 3,014 72 2 @ 1/2 5444 208/1 BERNER ARD12 5. EQUIPMENT CAPACITIES SHALL BE BASED ON AN ELEVATION OF 1900 ABOVE SEA LEVEL. SHEET TITLE
AC-2 AMBIENT AIR CURTAIN 3,014 72 2 @ 1/2 5444 208/1 BERNER ARD12 HVAC SCHEDULES

Date:
7/11/2018 7:30:56 PM

12 JUL 2018

SEQ. SHEET OF

M-601
AO - Relief Air Damper

AI - Return Air Humidity

AI - Return Air Temp


C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

M H T

RELIEF AIR RA
OKLAHOMA CITY, OK 73112 405.416.8100

Date Appr
C.H. GUERNSEY & COMPANY
5555 N. GRAND BLVD.

Description
AO - Mixed Air Dampers
M N.O.

BI - Freezestat AI - Supply Air Temp

AI - Prefilter Differential Pressure BI - Supply Air Smoke Detector

Symbol
AI - Mixed Air Temp BI - High Static Shutdown AO - Zone Damper

AI - Airflow AI - Discharge Air Temp


H L H L

Appr
M T T T
HW SF M
H T
OA SA BI - Zone Override

Date
HW
L SA DA
M AI - Zone Temp
N.C. T
Locate ¾ distance

REVISIONS
AI - Outside Airflow BI - Supply Fan Status down longest duct
CT
AI - Supply Air Static Pressure AI - Zone Setpoint Adjust

Description
VFD
AO - Reheating Valve
M
BO - Supply Fan Start/Stop
AI - Zone CO2
C
AO - Supply Fan VFD Speed

BI - Supply Fan VFD Fault

Symbol
HWS HWR
AO - Preheating Valve
M DX MHGR

BO - Cooling Modulating BO - Modulating Hot-Gas Reheat

HWR
HWS

B. McCOMBS
AHU-1 CONTROLS VAV CONTROLS

M. WILSON

Submitted by:
Reviewed by:
R. PRADO
Designed by:
1 2

Checker
Drawn by:
NOT TO SCALE NOT TO SCALE

Variable Air Volume - AHU

Run Conditions - Scheduled: Minimum Outside Air Ventilation - Carbon Dioxide (CO2) Control: Variable Air Volume - Terminal Unit
The unit shall run based upon an operator adjustable schedule. When in the occupied mode, the controller shall monitor zone CO2 concentrations served by this air handling unit and outside airflow from AFMS. The
controller shall take the highest zone CO2 concentration and modulate the outside air dampers open on rising CO2 concentrations, overriding normal Run Conditions - Scheduled:
Emergency Shutdown: damper operation to maintain a CO2 setpoint of 750 ppm (adj.). The unit shall run according to a user definable time schedule in the following modes:
The unit shall shut down and generate an alarm upon receiving an emergency shutdown signal either internally or from AT/FP shutdown button. • Occupied Mode: The unit shall maintain

CRESSMAN DINING FACILITY EXPANSION


Alarms shall be provided as follows:

GOODFELLOW AIR FORCE BASE, TEXAS


• A 75°F (adj.) cooling setpoint
Freeze Protection: • High Zone Carbon Dioxide Concentration: If the highest zone CO2 concentration is greater than 1000 ppm (adj.). • A 70°F (adj.) heating setpoint.
The unit shall shut down and generate an alarm upon receiving a freezestat status.
Dehumidification: • Unoccupied Mode (night setback): The unit shall maintain
High Static Shutdown: The controller shall measure the return air humidity and override the cooling sequence using modulating hot gas reheat to maintain return air humidity at • A 85°F (adj.) cooling setpoint.
The unit shall shut down and generate an alarm upon receiving an high static shutdown signal. or below 55% rh (adj.). Dehumidification shall be enabled whenever the supply fan status is on. • A 55°F (adj.) heating setpoint.

Supply Air Smoke Detection: Prefilter Differential Pressure Monitor: Alarms shall be provided as follows:
The controller shall monitor the differential pressure across the prefilter. • High Zone Temp: If the zone temperature is greater than the cooling setpoint by a user definable amount (adj.).

17th TRAINING WING


The unit shall shut down and generate an alarm upon receiving a supply air smoke detector status.

NATURE OF WORK:
• Low Zone Temp: If the zone temperature is less than the heating setpoint by a user definable amount (adj.).
Supply Fan: Alarms shall be provided as follows:
The supply fan shall run anytime the unit is commanded to run, unless shutdown on safeties. To prevent short cycling, the supply fan shall have a user definable • Prefilter Change Required: Prefilter differential pressure exceeds a user definable limit (adj.). Zone Setpoint Adjust:
(adj.) minimum runtime. The occupant shall be able to adjust the zone temperature heating and cooling setpoints at the zone sensor.
Mixed Air Temperature:
Alarms shall be provided as follows: The controller shall monitor the mixed air temperature and use as required for economizer control (if present) or preheating control (if present). Zone Optimal Start:
• Supply Fan Failure: Commanded on, but the status is off. The unit shall use an optimal start algorithm for morning start-up. This algorithm shall minimize the unoccupied warm-up or cool-down period while still achieving
• Supply Fan in Hand: Commanded off, but the status is on. Alarms shall be provided as follows: comfort conditions by the start of scheduled occupied period.
• Supply Fan Runtime Exceeded: Status runtime exceeds a user definable limit (adj.). • High Mixed Air Temp: If the mixed air temperature is greater than 90°F (adj.).
• Low Mixed Air Temp: If the mixed air temperature is less than 45°F (adj.). Zone Unoccupied Override:
Supply Air Duct Static Pressure Control: A timed local override control shall allow an occupant to override the schedule and place the unit into an occupied mode for an adjustable period of time. At the
The controller shall measure duct static pressure and shall modulate the supply fan VFD speed to maintain a duct static pressure setpoint of 1.5in H2O (adj.). Return Air Humidity: expiration of this time, control of the unit shall automatically return to the schedule.
The supply fan VFD speed shall not drop below 20% (adj.). The controller shall monitor the return air humidity and use as required for economizer control (if present) or humidity control (if present).
Dual Maximum Variable Volume Terminal Unit - Flow Control:
Alarms shall be provided as follows: Alarms shall be provided as follows: The terminal unit direct digital controller shall modulate the primary air damper, reheat valve to maintain the room temperature at the heating or cooling setpoint.
• High Supply Air Static Pressure: If the supply air static pressure is 25% (adj.) greater than setpoint. • High Return Air Humidity: If the return air humidity is greater than 70% (adj.). As the room temperature rises above the cooling setpoint the primary air damper will modulate open until the box maximum cfm setpoint is reached or the cooling
• Low Supply Air Static Pressure: If the supply air static pressure is 25% (adj.) less than setpoint. • Low Return Air Humidity: If the return air humidity is less than 35% (adj.). space temperature setpoint is satisfied. As the room temperature falls below the cooling setpoint the primary air damper will modulate closed to its minimum cfm
C:\Work\R18_70374-000_M_rprado.rvt

• Supply Fan VFD Fault. setpoint.


Return Air Temperature:
Preheating Coil Valve: The controller shall monitor the return air temperature and use as required for setpoint control or economizer control (if present). When the room temperature is in the deadband between the heating and cooling setpoints, the primary air damper shall modulate, as necessary, to maintain the
minimum cfm setpoint.

PROJECT TITLE
The controller shall measure the mixed air temperature and modulate the preheating coil valve to maintain its setpoint 5°F (adj.) less than the supply air
temperature setpoint. Alarms shall be provided as follows: When the room temperature falls below the heating setpoint the controller will maintain the space temperature as follows:
• High Return Air Temp: If the return air temperature is greater than 90°F (adj.).
The preheating shall be enabled whenever: • Low Return Air Temp: If the return air temperature is less than 45°F (adj.). • 0 – 50% Heating Demand: The controller shall reset the discharge air setpoint from 55 deg F to the maximum supply air temperature setpoint (95 deg F,
• Outside air temperature is less than 60°F (adj.). adj) and will modulate the HHW valve to maintain the discharge air temperature at setpoint.
• AND the economizer (if present) is disabled. Supply Air Temperature: • 50 – 100% Heating Demand: The controller shall reset the air flow cfm setpoint from the minimum air flow setpoint to the maximum heating air flow
• AND the supply fan status is on. The controller shall monitor the supply air temperature. setpoint (50% of cooling maximum, adj). The controller will continue to maintain the discharge air at setpoint.

The preheating coil valve shall open for freeze protection whenever: Alarms shall be provided as follows: Note: All HHW valves shall be analog modulating valves (4-20ma or 2-10vac), 3-pt floating are not acceptable
• Mixed air temperature drops from 40°F to 35°F (adj.). • High Supply Air Temp: If the supply air temperature is greater than 120°F (adj.).
• OR the freezestat (if present) is on. • Low Supply Air Temp: If the supply air temperature is less than 45°F (adj.). Discharge Air Temperature:
The controller shall monitor the discharge air temperature. Project Number:
Supply Air Temperature Setpoint - Fixed:
The controller shall monitor the supply air temperature and shall maintain fixed supply air temperature setpoints as follows: Alarms shall be provided as follows: OK70374-000
• Cooling: The setpoint shall be 55°F (adj.). • High Discharge Air Temp: If the discharge air temperature is greater than 120°F (adj.).
• Low Discharge Air Temp: If the discharge air temperature is less than 40°F (adj.). SHEET TITLE
• Heating: The setpoint shall be 95°F (adj.) whenever the return air temperature drops below 68°F (adj.).
HVAC CONTROLS
Cooling Stage:
The controller shall measure the supply air temperature and stage the cooling to maintain its cooling setpoint. To prevent short cycling, the stage shall have a
user definable (adj.) minimum runtime. Date:
7/11/2018 7:30:57 PM

12 JUL 2018
The cooling shall be enabled whenever:
• Outside air temperature is greater than 60°F (adj.).
• AND the economizer (if present) is disabled or fully open.
• AND the supply fan status is on.
• AND the heating (if present) is not active. SEQ. SHEET OF

Alarms shall be provided as follows:


• High Supply Air Temp: If the supply air temperature is 5°F (adj.) greater than setpoint.
M-801
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

BO - Hot Water Pump 1 Start/Stop


OKLAHOMA CITY, OK 73112 405.416.8100

Date Appr
Starter
C.H. GUERNSEY & COMPANY

CT
BI - Hot Water Pump 1 Status
AI - Primary Hot Water Supply Temp
5555 N. GRAND BLVD.

Description
T
SUN SHIELD
P1 HWS

AI - Outside Air Temp


T
M AI - Outside Air Humidity

BI - Circulation Pump Status

Symbol
CT
Boiler

BO - Circulation Pump Start/Stop


Starter
BO - Boiler Enable

Appr
BI - Boiler Status

BI - Boiler Alarm Status

Date
BI - Low Water Level

REVISIONS
Description
HWR
T
AI - Primary Hot Water Return Temp

Symbol
BOILER CONTROLS
1 NOT TO SCALE

Single Boiler System Heating Water Secondary Pump:


The circulation pump shall run anytime the boiler is called to run and shall have a user definable (adj.) delay on stop.
Boiler System - Run Conditions:
The boiler system shall be enabled to run whenever outside air temperature is less than 65°F (adj.). Alarms shall be provided as follows:
• Circulation Pump Failure: Commanded on, but the status is off.

B. McCOMBS
To prevent short cycling, the boiler system shall run for and be off for minimum adjustable times (both user definable), unless shutdown on • Circulation Pump Running in Hand: Commanded off, but the status is on.

M. WILSON
safeties or outside air conditions. • Circulation Pump Runtime Exceeded: Status runtime exceeds a user definable limit.

Submitted by:
Reviewed by:
R. PRADO
Designed by:

Checker
Drawn by:
The boiler shall run subject to its own internal safeties and controls. Boiler Enable:
The boiler shall be enabled when the boiler system is commanded on. The boiler shall be enabled after pump status is
The boiler system shall also run for freeze protection whenever outside air temperature is less than 38°F (adj.) proven on and shall run subject to its own internal safeties and controls.

Boiler Safeties: Alarms shall be provided as follows:


The following safeties shall be monitored: • Boiler Failure: Commanded on, but the status is off.
• Boiler alarm. • Boiler Running in Hand: Commanded off, but the status is on.
• Low Water Level. • Boiler Runtime Exceeded: Status runtime exceeds a user definable limit.

CRESSMAN DINING FACILITY EXPANSION


Alarms shall be provided as follows: Hot Water Supply Temperature Setpoint Reset:

GOODFELLOW AIR FORCE BASE, TEXAS


• Boiler alarm. The hot water supply temperature setpoint shall reset based on outside air temperature.
• Low Water Level alarm.
As outside air temperature rises from 0°F (adj.) to 70°F (adj.) the hot water supply temperature setpoint shall reset
Heating Water Primary Pump: downwards by subtracting from 0°F (adj.) up to 20°F (adj.) from the current boiler setpoint.
The hot water pump shall run anytime the boiler is called to run and shall have a user definable delay (adj.) on stop.
Primary Hot Water Temperature Monitoring:
Alarms shall be provided as follows: The following temperatures shall be monitored:
• Primary hot water supply.

17th TRAINING WING


NATURE OF WORK:
• Hot Water Pump Failure: Commanded on, but the status is off. • Primary hot water return.
• Hot Water Pump Running in Hand: Commanded off, but the status is on.
• Hot Water Pump Runtime Exceeded: Status runtime exceeds a user definable limit. Alarms shall be provided as follows:
• High Primary Hot Water Supply Temp: If greater than 200°F (adj.).
• Low Primary Hot Water Supply Temp: If less than 100°F (adj.).

GENERAL CONTROLS NOTES:


C:\Work\R18_70374-000_M_rprado.rvt

1. CONTROLS SYSTEM TO BE AN EXTENSION OF THE EXISTING BUILDING CONTROLS.


2. BASIS OF DESIGN IS AUTOMATD LOGIC. CONTACT JOHN SAULT AT 254-842-7675.

PROJECT TITLE
Project Number:

OK70374-000

SHEET TITLE

HVAC CONTROLS

Date:
7/11/2018 7:30:57 PM

12 JUL 2018

SEQ. SHEET OF

M-802
PLAN LEGEND NOTES
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
LEGEND NOTES

J JUNCTION BOX, WALL MOUNTED INDICATES NEW OVERHEAD POLE


DATA OUTLET, RECESSED, MOUNTED 18"AFF, UON, "X" INDICATES INDICATES EXISTING OVERHEAD POLE
J JUNCTION BOX, CEILING MOUNTED (X) NUMBER OF OUTLETS. A BLANK IN "X" LOCATION INDICATES 2 PORT
PB-X 1. BRANCH CIRCUIT NUMBERS MAY BE SHOWN NEXT TO SYMBOLS IN MULTIWIRE CIRCUITS.
PULL BOX , NEW, "X" INDICATES PULL BOX NUMBER 2. SYMBOL ORIENTATION DOES NOT IMPLY DEVICE OR EQUIPMENT ORIENTATION UNLESS NOTED AS SUCH. SEE REFLECTED
OKLAHOMA CITY, OK 73112 405.416.8100

TELEPHONE TERMINAL BOARD (4' x 8' x 3/4", UON) CEILING PLANS FOR LIGHT FIXTURE POSITIONS AND ORIENTATIONS.
J JUNCTION BOX, FLOOR MOUNTED PB-X 3. SYMBOL SIZE DOES NOT IMPLY EQUIPMENT SIZE, UON
PULL BOX , EXISTING, "X" INDICATES PULL BOX NUMBER

Date Appr
DATA OUTLET, INSTALLED IN FLOOR, "X" INDICATES 4. LOWER CASE LETTER IN POSITION "X" INDICATES FIXTURES CONTROLLED BY SAME LETTERED SWITCH.
(X)
PUSH BUTTON NUMBER OF OUTLETS MH-X
MANHOLE , NEW, "X" INDICATES PULL BOX NUMBER
C.H. GUERNSEY & COMPANY

SWITCH, SAFETY, 30A , NON-FUSED, NEMA 3R (EXTERIOR) / NEMA 1 (INTERIOR), UON. ANTENNA
MH-X
MANHOLE , EXISTING, "X" INDICATES PULL BOX NUMBER GENERAL NOTES (APPLICABLE TO ALL SHEETS)
MOTOR STARTER OR LIGHTING CONTACTOR, SURFACE MOUNTED SP SPEAKER, CEILING MOUNTED
5555 N. GRAND BLVD.

HH-X
HAND HOLE , NEW, "X" INDICATES PULL BOX NUMBER

Description
SP SPEAKER, WALL MOUNTED 1. ALL WORK SHALL BE COORDINATED WITH THE OTHER TRADES BEFORE INSTALLATION. MATERIALS INSTALLED IN AN
HH-X ARBITRARY MANNER OR CREATES AN UNFAIR CONDITION OR HARDSHIP FOR ANOTHER TRADE WILL NOT BE ACCEPTED.
HAND HOLE , EXISTING, "X" INDICATES PULL BOX NUMBER CONTRACTOR SHALL VERIFY PHYSICAL CHARACTERISTICS, VOLTAGE, LOAD, AND WIRING REQUIREMENTS FOR ALL
M OVERHEAD DOOR MOTOR AND CONTROLS
CR CARD READER EQUIPMENT PRIOR TO ROUGH-IN.
CONDUIT, CONCRETE ENCASED (DUCT) SYSTEM; QUANTITY OF CIRCLES 2. ALL MATERIALS PROVIDED FOR CONSTRUCTION SHALL BE UL LISTED AND NEW, UNLESS OTHERWISE NOTED (UON).
MS MOTION SENSOR IN SYMBOL DENOTES QUANTITY AND ARRANGEMENT OF CONDUIT; 3. ALL WORK PERFORMED SHALL BE BY A LICENSED ELECTRICIAN.
DARKENED CIRCLE INDICATES CONDUIT WITH CONDUCTORS 4. ALL PENETRATIONS THROUGH WALL, FLOOR, OR CEILING ASSEMBLIES SHALL BE SEALED WITH SEALANT APPROVED FOR
PANELBOARD, SURFACE MOUNTED WITH COPPER BUS THE APPLICATION FOR WHICH IT IS BEING USED. FIRE STOP SHALL BE PROVIDED AT ALL LOCATIONS WHERE ELECTRICAL

Symbol
RX REQUEST TO EXIT EQUIPMENT OR SYSTEMS PENETRATE FIRE RATED WALLS. SEE ARCHITECTURAL PLANS FOR RATED WALL LOCATIONS.
PANELBOARD, RECESSED WITH COPPER BUS 5. EQUIPMENT INTERRUPTING CAPACITIES SPECIFIED IN THE CONTRACT DOCUMENTS ARE BASED UPON EQUIPMENT
CONDUIT AND WIRING RUN, UNDERGROUND; QUANTITY AND SIZE AS NOTED CHARACTERISTICS AND IMPEDANCES. THE CONTRACTOR SHALL INCREASE THE INTERRUPTING CAPACITIES OF ALL ITEMS
GROUND ROD LOCATION 2'-3"
CONDUIT STUB OFF BELOW GROUND, CAPPED, UON ON THE LOAD SIDE OF THE DEVIANT EQUIPMENT IN DIRECT PROPORTION TO THE CHANGED CHARACTERISTICS.
INTERRUPTING CAPACITIES SHALL NOT BE REDUCED TO VALUES LESS THAN THOSE REQUIRED BY THE CONTRACT

Appr
LIGHTNING PROTECTION SYSTEM AIR TERMINAL POLE MOUNTED SITE LIGHT FIXTURE DOCUMENTS.
M MOTOR CONNECTION
6. CONTROL WIRING FOR MECHANICAL EQUIPMENT IS NOT SHOWN ON THESE SHEETS (RE: MECHANICAL).

Date
GROUND BAR WITH PHENOLIC STAND-OFFS; SIZE AS SPECIFIED NEW RISER (PRIMARY OR SECONDARY) 7. RISER AND ONE-LINE DIAGRAMS ARE MEANT TO SHOW ONLY ELECTRICAL RELATIONSHIPS, AND THEREFORE MAY NOT
POWER WIRING AND CONDUIT RUN, LONG HASH MARK INDICATES INCLUDE ALL REQUIRED EQUIPMENT, DEVICES, AND ACCESSORIES.
X QUANTITY OF PHASE CONDUCTORS AND SWITCH LEG CONDUCTORS. 8. ALL CONDUCTOR SIZES ARE BASED ON THE USE OF COPPER CONDUCTORS, UNLESS OTHERWISE NOTED.

REVISIONS
SHORT HASH MARKS INDICATE NUMBER OF NEUTRAL CONDUCTORS. POWER TRANSFORMER, RATINGS ARE SHOWN IN TRANSFORMER SCHEDULE EXISTING RISER (PRIMARY OR SECONDARY) 9. ALL BUSES SHALL BE COPPER, UNLESS OTHERWISE NOTED.
ALL CIRCUITS SHALL HAVE EQUIPMENT GROUND CONDUCTOR. NO 10. CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING AND AVOIDING ALL EXISTING OR NEW UNDERGROUND UTILITIES,
HASH MARKS INDICATE TWO CONDUCTORS PLUS GROUND. CONDUCTOR EVEN IF NOT SHOWN, AT NO ADDITIONAL COST TO THE OWNER. COORDINATE UTILITY "SPOTTING" WITH CONTRACT OFFICER.
GROUNDING CONNECTION; WHEN USED WITH TRANSFORMER WINDING OHE ELECTRICAL OVERHEAD

Description
SIZES GREATER THAN No. 12 AWG ARE NOTED AT POSITION "X" 11. NOT ALL SYMBOLS AND ABBREVIATIONS SHOWN ARE USED ON THIS PROJECT.
SYMBOL IT INDICATES A NEUTRAL GROUNDING CONNECTION
(ON SECONDARY SIDE ONLY) 12. CONTRACTOR TO INSTALL PULL WIRE IN EMPTY RACEWAY AND INNER-DUCTS. USE #14 ZINC-COATED STEEL OR
TRANSFORMER, DRY-TYPE, DESIGNATOR SHOWN IN POSITION "X" UE UNDERGROUND ELECTRICAL MONOFILAMENT PLASTIC LINE WITH NO LESS THAN 200LBS TENSILE STRENGTH. LEAVE AT LEAST 24-INCHES OF SLACK AT
T"X"
INDICATES EQUIPMENT IDENTIFIER THE END OF PULL WIRE AND PROVIDE IDENTIFICATION FOR THE LOCATION OF OTHER END.
DELTA WINDING CONNECTION UC UNDERGROUND COMMUNICATIONS 13. MULTIPLE LIGHTING SWITCHES INDICATED IN A ROOM WITH FLUORESCENT FIXTURES INDICATES MULTIPLE LEVEL
CIRCUIT HOMERUN TO PANEL OR CABINET NOTED; W=PANEL NAME; SWITCHING. FIXTURES SHALL HAVE TWO BALLAST FOR INNER AND OUTER LAMP SWITCHING, UNLESS OTHERWISE NOTED.
W-X,Y,Z X,Y,Z,=CIRCUIT NUMBERS; SYMBOL CAN BE USED WITH LONE CONDUCTOR CONNECTION 14. MULTIPLE LIGHTING SWITCHES INDICATED IN A ROOM WITH LED FIXTURES INDICATES MULTIPLE LEVEL SWITCHING. UNLESS
CONDUIT OR WIRING SYMBOLS OTHERWISE NOTED.
ABBREVIATIONS

Symbol
15. IF DIMMER SWITCHES ARE INDICATED IN THE ROOM WITH FLUORESCENT FIXTURES, THE FLUORESCENT FIXTURES SHALL
RECEPTACLE, DUPLEX, NEMA 5-20R, 18" AFF, UON CIRCUIT BREAKER, MOLDED CASE, TRIP CURRENT [A] AND QUANTITY HAVE DIMMING BALLAST.
OF POLES [P] SHOWN NEXT TO THE SYMBOL 16. IF DIMMER SWITCHES ARE INDICATED IN THE ROOM WITH LED FIXTURES, THE LED FIXTURES SHALL HAVE DIMMING DRIVERS.
ABV. DESCRIPTION ABV. DESCRIPTION
RECEPTACLE, DUPLEX, NEMA 5-20R, 18" AFF, UON. "S" INDICATES THE RECEPTACLE 17. ALL EXISTING ELECTRICAL ITEMS SHALL REMAIN AND BE MAINTAINED IN SERVICE, UNLESS OTHERWISE NOTED.
(S) IS SWITCHED BY THE OCCUPANCY SENSOR IN THE ROOM. 18. VERIFY THAT THE WIRING BEING REMOVED SERVES ONLY THE ITEM SHOWN TO BE REMOVED ON THESE DRAWINGS.
SWITCH, DISCONNECT, NON-FUSED, LOAD BREAK; CONTINUOUS A AMPERES OR TRIP AMPERES KWH KILOWATT HOURS
PROVIDE ALL MATERIALS AND LABOR REQUIRED TO RESTORE CONTINUITY TO CIRCUITS DISRUPTED BY DEMOLITION.
RECEPTACLE, DUPLEX, NEMA 5-20R, 18" AFF, UON. "TR" INDICATES THE CURRENT RATING [A] AND QUANTITY OF POLES [P] SHOWN NEXT 19. REMOVE EXISTING CEILING TILE AS REQUIRED FOR INSTALLATION OF ELECTRICAL WORK. REINSTALL TILES AS WORK IS
(TR) RECEPTACLE IS TAMPER RESISTANT. TO SYMBOL AC ABOVE COUNTER MH MANHOLE
COMPLETED. NOTIFY OWNER OF ANY BROKEN OR DAMAGED CEILING TILE BEFORE PERFORMING WORK. ALL DAMAGED AND
AFF ABOVE FINISHED FLOOR NEC NATIONAL ELECTRIC CODE BROKEN CEILING TILES CAUSED BY CONTRACTOR'S PERSONNEL SHALL BE REPLACED AT NOT ADDITIONAL COST TO OWNER.
RECEPTACLE, GFCI, NEMA 5-20R, 18" AFF, UON 20. REMOVE ALL EXISTING UNUSED WIRING, CONDUIT, BOXES, DEVICES, ETC. UNCOVERED DURING DEMOLITION.
SWITCH, DISCONNECT, FUSED, LOAD BREAK; FUSE AMPERE RATING [A] AFG ABOVE FINISHED GRADE NEMA NATIONAL ELECTRICAL
RECEPTACLE, QUADRUPLEX, NEMA 5-20R, 18" AFF, UON AND FUSE TYPE SHOWN NEXT TO SYMBOL MANUFACTURERS ASSOCIATION

B. McCOMBS
AIC SYMMETRICAL AMPS

Z. KORENAK
S. HUDSON

S. HUDSON
N NEUTRAL

Submitted by:
INTERRUPTING CAPACITY

Reviewed by:
Designed by:
RECEPTACLE, DUPLEX, MOUNTED IN FLOOR
FUSE, AMPERE RATING [A] AND FUSE TYPE SHOWN NEXT TO SYMBOL

Drawn by:
AV AUDIBLE AND VISUAL NIC NOT IN THIS CONTRACT
RECEPTACLE, QUADRUPLEX, MOUNTED IN FLOOR
INTEGRAL PHOTOELECTRIC CELL AND RELAY (PHOTOCONTROL)
C CONDUIT OH OVERHEAD
RECEPTACLE, DUPLEX, MOUNTED IN CEILING
WH WATT-HOUR METER CKT CIRCUIT PH PHASE
RECEPTACLE, QUADRUPLEX, MOUNTED IN CEILING
FEEDER NUMBER; SEE FEEDER SCHEDULE CP COMPUTER PNL PANELBOARD
X
RECEPTACLE , SINGLE SPECIAL PURPOSE, MOUNTED 48" AFF, UON EMERGENCY MONITORING PVC POLYVINYL
NUMBER IN POSITION "X" INDICATES TYPE (SEE SCHEDULE) EMCS

CRESSMAN DINING FACILITY EXPANSION


X AND CONTROL SYSTEM CHLORIDE

GOODFELLOW AIR FORCE BASE, TEXAS


VSD VARIABLE SPEED DRIVE RURAL ELECTRIFICATION
EMT ELECTRICAL METALIC TUBING REA
RECEPTACLE , RECESSED, FLOOR MOUNTED QUADRUPLEX OUTLET, ADMINISTRATION
NEMA 5-20R, AND VOICE/DATA OUTLET EQUIPMENT ENCLOSURE
EP EXPLOSION PROOF REQ'D REQUIRED
PP SWITCHED POWER PACK ABOVE CEILING, UON MOTORIZED GENERATOR EWC ELECTRIC WATER COOLER RM ROOM

F FIXED TEMPERATURE SPARE SPARE BREAKER OR DEVICE

17th TRAINING WING


S WALL MOUNTED SWITCH ATS AUTOMATIC TRANSFER SWITCH

NATURE OF WORK:
FACP FIRE ALARM CONTROL PANEL SPECS CONTRACT SPECIFICATIONS
SM SWITCH, MOTOR RATED, WITH THERMAL OVERLOADS POTENTIAL TRANSFORMER, PRIMARY TO SECONDARY RATIO SHOWN
EX EXISTING SWBD SWITCHBOARD
NEXT TO SYMBOL
SD DIMMER SWITCH FT FEET TB TELEPHONE BACKBOARD
SOS CURRENT TRANSFORMER, TURNS RATIO SHOWN NEXT TO SYMBOL
OCCUPANCY SENSOR, WALL MOUNTED GFI GROUND FAULT INTERRUPTER UL UNDERWRITERS LABORATORIES

SEPARABLE CONNECTOR OR CONNECTION FOR DRAWOUT ASSEMBLIES GND GROUND UON UNLESS OTHERWISE NOTED
OS OCCUPANCY SENSOR, CEILING MOUNTED
RECESSED SPLIT BOX MOUNTED 72" AFF, UON, WITH 1.25" RACEWAY STUBOUT FOR CATV GRC GALVANIZED RIGID STEEL CONDUIT V VOLTS
TV TO ACCESSIBLE CEILING SPACE. BOX SHALL INCLUDE POWER (SIMPLEX 5-20R), COAX CABLE MOTOR THERMAL OVERLOAD PROTECTOR
WITH F CONNECTOR, DATA, VGA, AND HDMI. ROUTE BACK TO MAIN SERVER ROOM. HPS HIGH PRESSURE SODIUM VA VOLTS-AMPERES

ROUND, RECESSED, SURFACE, OR PENDANT LIGHT FIXTURE H HD HEAVY DUTY W WATTS


O SWITCH, SELECTOR, HAND-OFF AUTOMATIC
A
C:\Work\R18_70374-000_E_shudson.rvt

2'X4' LIGHTING FIXTURE K KEYED WP WEATHERPROOF


CONTACTOR OR RELAY COIL, LETTER(S) INSIDE OF SYMBOL MATCH
C CONTACTS CONTROLLED KV KILOVOLTS USED WITH A NUMERAL, WHICH
+
1'X4' LIGHTING FIXTURE INDICATES HEIGHT OF ITEM IN INCHES
AFF LEVEL

PROJECT TITLE
KVA KILOVOLT AMPERES
RELAY OR CONTACTOR CONTACTS
1/C SINGLE CONDUCTOR CABLE
LIGHTING FIXTURE WITH EMERGENCY LIGHTING CAPABILITY KVAR KILOVOLT AMPS REACTIVE
3/C THREE CONDUCTOR CABLE
1 KEYED NOTE, NUMBER IN POSITION "1" INDICATES NOTE NUMBER
EXIT SIGN, LIGHTED, WALL MOUNTED; FACES ARE SOLID
CHEVRON'S INDICATED EGRESS PATH

XXX ROOM NUMBER IDENTIFIER; ROOM NUMBER SHOWN IN POSITION "X"


EXIT SIGN, LIGHTED, CEILING MOUNTED; FACES ARE SOLID
CHEVRON'S INDICATED EGRESS PATH

EMERGENCY LIGHTING UNIT DETAIL, SECTION, PLAN, OR VIEW REFERENCE SYMBOL; IN POSITION Project Number:
X "X" IS THE DETAIL IDENTIFIER NUMBER
OK70374-000
PC PHOTO-CONTROLLER, INTEGRAL PHOTOELECTRIC CELL AND RELAY
SHEET TITLE
X ENLARGED PLAN REFERENCE; IN POSITION "X" IS THE PLAN IDENTIFIER
NUMBER; IN POSITION "Y" IS THE SHEET NUMBER WHERE THE PLAN IS ELECTRICAL LEGEND AND NOTES
Y REFERENCED
7/12/2018 11:22:04 AM

Date:
12 JUL 2018

SEQ. SHEET OF

E-001
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
OKLAHOMA CITY, OK 73112 405.416.8100

Date Appr
C.H. GUERNSEY & COMPANY
5555 N. GRAND BLVD.

GENERAL NOTES:

Description
1 1. TWO EXISTING LIGHT POLES IN NEW BUILDING FOOT PRINT. REFER TO CIVIL SHEET C-100 FOR
LOCATION. DEMOLISH COMPLETELY BACK TO SOURCE. RETURN MATERIALS TO GOVERNMENT.
#10
X KEYED NOTES:
P1 -11
1. FOR EXISTING LIGHT POLE. DEMOLISH COMPLETELY BACK TO SOURCE. RETURN MATERIALS TO

Symbol
GOVERNMENT. NEW POLE WILL BE IN SAME LOCATION.
2. INCLUDE IN ALT #4.

Appr
NEW 4" PVC CONDUIT (1) 2 1/2"
T

Date
FOR NEW 12 STRAND CONDUIT FOR
SINGLE MODE FIBER LINE MECHANICAL
T EQUIPMENT
REFER TO CIVIL SHEET

REVISIONS
C-100 TO CONFIRM
UC
LOCATION.
(1) 2" CONDUIT AND (1) 4"

Description
UC
2 CONDUIT FOR 480V TO
#10 TRANSFORMER AND
UC
P1 -9 BACK TO 208V PANEL

UC
PB
PB
PB PB
EXISTING
UNDERGROUND

Symbol
COMM TO BE
#10
DEMOLISHED BACK
TO PULL BOX. STUB UP 4" PVC
CONDUIT FOR
FIBER LINE.

B. McCOMBS
Z. KORENAK
S. HUDSON

S. HUDSON

Submitted by:
Reviewed by:
Designed by:

Drawn by:
(1) 3/4" CONDUIT

PB

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


17th TRAINING WING
NATURE OF WORK:
2
PARTIAL CIRCUIT
#10 P1 -10

PARTIAL CIRCUIT
P1 -10
#10
C:\Work\R18_70374-000_E_shudson.rvt

PROJECT TITLE
SITE PLAN
1 1" = 20'-0"
Project Number:

OK70374-000

SHEET TITLE

SITE PLAN
7/12/2018 11:22:10 AM

Date:
12 JUL 2018

PLAN NORTH
40' 20' 0 40' SEQ. SHEET OF

SCALE: 1" = 20'


ES101
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018
OKLAHOMA CITY, OK 73112 405.416.8100

AA BB CC DD EE FF GGHH JJ X1

Date Appr
C.H. GUERNSEY & COMPANY
5555 N. GRAND BLVD.

Description
9
EE

BB BB
7.9 8
#10 #10
AA

7.8

Symbol
D D D
E E E
AA
AA VESTIBULE

Appr
104 LIGHTING FIXTURE SCHEDULE
A A A A #10 P3 -1 EXISTING SOFFIT
Type Mark Manufacturer Model Lamp Mounting

Date
E
A A A LITHONIA EPANL-22-34L-40K-PS1055CP (E10WCP) FMC BRKT LED RECESSED
AA LITHONIA DSXW1 LED-10C-530-40K-T2M-MVOLT-(ELCW) LED WALL @ 10' TO BOTTOM OF FIXTURE

REVISIONS
7 B LITHONIA Z1LD-L48-SMR-5000LM-FST-MVOLT-40K-80CRI-(E10WLCP) LED SURFACE
S BB U.S. ARCHITECTUAL LIGHTING LAS5562/16LED-FF-NW-RAL-9005-T-277V LED WALL @ 8' TO BOTTOM OF FIXTURE
A A A A

Description
D LITHONIA LDN6-40/-15-L06-AR-LD-MVOLT-EL-WL LED RECESSED
P1 -6 OS E USAI LIGHTING LNRP3-9014-M2-10-10-G2-10-40KS-277V-DIML2 LED SUSPENDED AT 7' TO BOTTOM OF FIXTURE
A A A A
EE MODA MGE-HO-S1-S-DC-4-TBD-40 LED SOFIT
S3S3S3 LP LITHONIA DSX2 LED-P4-40K-T5W-MVOLT-RPA-DDBXD-DLL127F 1.5 JU- LED RSA-30'-6G-PT-DDBXD POLE
6 E
OS
S
S P1 OS X LITHONIA EDG-1-R-(EL) LED WALL
#10 FAMILY TOILET
A A A A A 105 B B CORRIDOR
P2 115

Symbol
A ACCESS P3
PANEL
EXISTING WOMEN'S
5.6 108 A
COMM
B B
106
MECHANICAL
SD

A A A A
107

S
A B
P1 -2 P1 -7
A

DINING

S
A
A 102 A A A

B. McCOMBS
Z. KORENAK
S. HUDSON

S. HUDSON

Submitted by:
P1 -4

Reviewed by:
A EXISTING JAN.

Designed by:
5 AA A A
A OS STORAGE 109 A

Drawn by:
A OFFICE
CONF. ROOM 110 OS
112
PRIVATE DINING 111
103
A A A A A A A
SOS SD S A
2 P1 -8
A
A
1

CRESSMAN DINING FACILITY EXPANSION


A A A A A A A

GOODFELLOW AIR FORCE BASE, TEXAS


A A A A EXISTING MEN'S PREPARATION ROOM
3.8 STUDENT ADMIN.
114 118
OS 113 OS OS
A
A A A A
OS
A A A
3.4 A A A A 3 3 3 S

17th TRAINING WING


SSS

NATURE OF WORK:
E

OS A
A A A
#10 VESTIBULE S
3 A A A A
101

E A A EXISTING SOFFIT LIGHTING PLAN - ALT #1


A A A A AA 2 1/8" = 1'-0"
AA

E E E
2.2 D D D
C:\Work\R18_70374-000_E_shudson.rvt

#10 AA
#10
2.1 2
BB BB

PROJECT TITLE
EE 1

Project Number:
A B X2
LIGHTING PLAN - AREA A OK70374-000
1 1/8" = 1'-0"
A B
SHEET TITLE

LIGHTING PLAN
GENERAL NOTES:
7/12/2018 11:22:06 AM

1. DASHED LINES INDICATE SWITCHING. Date:

KEY PLAN 12 JUL 2018

PLAN NORTH
SEQ. SHEET OF
8' 4' 0 8'

SCALE: 1/8" = 1'-0"


EL101
AA BB CC DD EE FF GG HH JJ

C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019


C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

X1
OKLAHOMA CITY, OK 73112 405.416.8100

P3 -26

Date Appr
C.H. GUERNSEY & COMPANY
5555 N. GRAND BLVD.

Description
9

7.9 24"
WP 8
P2 -3 P2 -20

7.8

Symbol
Appr
TV
24"

Date
P2 -38 WP
VESTIBULE
1

REVISIONS
104
7 OS P3 -16
P3 -2
2

Description
P2 -40
AC AC AC
P2 -7

TV
1
P2 -33 P2 -13
6 PREPARATION ROOM
P2 -16 OS P1 AC 118
1 379 SF

TV
P2 -12 P2 P2 -17 P2 -31
P2 -15 P3 -14

Symbol
P3 AC AC AC
PARTIAL CIRCUIT 4 CORRIDOR
P2 -14 3
5.6 EP101 MECHANICAL J EXISTING WOMEN'S 115
108 439 SF
107

COMM
P2 -28 106 EXISTING WOMEN'S
108
P3 -18 P2 -19
PRIVATE DINING EXISTING DINING
103 TV EXISTING JAN. 116
AC P2 -2
109

B. McCOMBS
2 36"

Z. KORENAK
OS
POWER PLAN - ALT #1

S. HUDSON

S. HUDSON

Submitted by:
Reviewed by:
P2 -30

Designed by:
5 OS 1
2

Drawn by:
J
P3 -13 OFFICE STORAGE 1/8" = 1'-0"
CONF. ROOM
DINING 112 110
111
102 P3 -15

EXISTING MEN'S
P2 -18 36" P3 -17 114
P3 -11 FF
4 X1

CRESSMAN DINING FACILITY EXPANSION


STUDENT ADMIN.

GOODFELLOW AIR FORCE BASE, TEXAS


TV J 113 EXISTING MEN'S
3.8 114
PARTIAL CIRCUIT
P2 -6 P2 -14
P2 -35 P2 -29
1 3 P2 -23
TV

4 3
OS
J J
3.4

17th TRAINING WING


J

NATURE OF WORK:
24" TV
WP
P3 -12 P2 -10
P2 -9 P3 -10
P2 -42
FAA J VESTIBULE
3 OS 1
101
P2 -5 24" P3 -7
P3 -9
WP
TV

J
P2 -21

AV CABINET COMM SECURED CABINET


CNTRACTOR CONTRACTOR PROVIDED
C:\Work\R18_70374-000_E_shudson.rvt

2.2
PROVIDED
24"
WP
2.1 P2 -1 2

PROJECT TITLE
ENLARGED PLAN - COMM ROOM
1 3 1/4" = 1'-0"

Project Number:

OK70374-000
A B
SHEET TITLE
A B POWER PLAN
X2
7/12/2018 11:22:07 AM

POWER/COMM PLAN - AREA A KEY PLAN


Date:
12 JUL 2018
1 1/8" = 1'-0"
PLAN NORTH
X KEYED NOTES: SEQ. SHEET OF
8' 4' 0 8' 4' 2' 0 4'
1. 100% OF RECEPTACLES IN THIS ROOM TO BE SWITCHED BY OCCUPANCY SENSORS.
2.
3.
4.
ALL RECEPTACLES EXCEPT FOR AV CABINET TO BE SWITCHED BY OCCUPANCY SENSOR.
PROVIDE JUNCTION BOX COMM TP PASS THROUGH TO FURNITURE.
COORDINATE JUNCTION BOX WITH DDC CONTROLS. REFER TO MECHANICAL SHEET M-401 DETAIL 1.
SCALE: 1/8" = 1'-0" SCALE: 1/4" = 1'-0"
EP101
AA BB CC DD EE FF GG HH JJ

C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019


C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

T1
OKLAHOMA CITY, OK 73112 405.416.8100

X1

Date Appr
CU-1
C.H. GUERNSEY & COMPANY

P3 -4,6,8
5555 N. GRAND BLVD.

Description
9

7.9 8

Symbol
7.8

Appr
Date
AC-1
P2 -8

REVISIONS
Description
7
LOCATED ON ROOF
P2 -22,24
P2 -27
1 CU-2

MS
HWP-1
6

Symbol
B-1 2 P1
P2 -26
P2 -25
P2 -4 P2
P3 -20,22,24

SM
EF-1 P3
VAV-6
J
5.6 J J VAV-2
EWH-1 HWP-2 P3 -3,5 AHU-1
VAV-3 J
P2 -32,34,36
#10
DU-1

B. McCOMBS
Z. KORENAK
S. HUDSON

S. HUDSON

Submitted by:
Reviewed by:
Designed by:

Drawn by:
POWERED FROM CU-2
5
J

VAV-1

CRESSMAN DINING FACILITY EXPANSION

GOODFELLOW AIR FORCE BASE, TEXAS


J
VAV-4 4
J
3.8 VAV-7 J
VAV-8
VAV-5

17th TRAINING WING


NATURE OF WORK:
J
3.4

3
P2 -11

AC-2
C:\Work\R18_70374-000_E_shudson.rvt

2.2

PROJECT TITLE
2.1 2

Project Number:
A B X2
OK70374-000
A B
SHEET TITLE

MECHANICAL POWER PLAN - FIRST FLOOR MECHANICAL POWER PLAN


1 1/8" = 1'-0"
MECHANICAL POWER SCHEDULE

Type Electrical Data Wire Size Conduit Size Disconnect Size Panel Circuit Number Notes
7/12/2018 11:22:08 AM

Date:
X AC-1 120 V/1-2520 VA #10, #10G 3/4" 30 A P2 8
KEYED NOTES:
AC-2 120 V/1-2520 VA #10, #10G 3/4" 30 A P2 11 KEY PLAN 12 JUL 2018

1. SWITCH SHALL BE LOCATED WITHIN SIGHT OF CU-2. AHU-1 208 V/3-13329 VA #8, #8G 3/4" 60 A P2 32,34,36
2. COORDINATE RECEPTACLE TO BE ADJACENT OF BOILER CU-1 208 V/3-43231 VA #1/0, #6G 1 1/2" 200 A P3 4,6,8 PLAN NORTH
B-1. REFER TO DETAIL 1 OF MECHANICAL SHEET M-401 CU-2 208 V/2-245 VA #10, #10G 3/4" P2 22,24 SEQ. SHEET OF
EF-1 120 V/1-600 VA #10, #10G 3/4" P2 25 8' 4' 0 8'
HWP-1 120 V/1-1392 VA #12, #12G 3/4" 30 A P2 27
HWP-2 208 V/3-5944 VA #12, #12G 3/4" 30 A P3 20,22,24 SCALE: 1/8" = 1'-0"
EP102
C.A. ARCHITECTURE: #BR258 EXPIRES FEBRUARY 28, 2019
C.A. ENGINEERING: #F-2268 EXPIRES DECEMBER 31, 2018

90 DEGREE TURN WITH


JUNCTION BUSHING
OKLAHOMA CITY, OK 73112 405.416.8100

BOX ABOVE CEILING

Date Appr
FIXTURE WHIP TO
STRUCTURE BE MAXIMUM 6'-O"
CEILING 12"
C.H. GUERNSEY & COMPANY

INSTALL WITH ALL BOXES 6" BELOW LIGHT FIXTURE


BRACKET AS TOP OF MONITOR (SEE 4"
5555 N. GRAND BLVD.

SHOWN BELOW PLANS FOR HEIGHT)

Description
EMT

POWER, DATA, & EMT EMT


BLANK FOR AV OR SECURE TO PLYWOOD
1/4"
AV STYLE BOX SEE DEVICES NOTED USING LAG BOLTS (TYP)
PLANS FOR DETAILS

Symbol
WITH "AC" ON
PLANS
4"

MONITOR REDUCE IF NECESSARY TO


AVOID MIRRORS, BULLETIN