Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Bus Bars
Project – P1
Chapter ( 3 ) Bus Bars design
Contentes.
1. Design Considerations
A. Introduction
B. Types of Busbar
C. Transposition of conductors
E. Tubular bars
F. Concentric conductors
Project – P1
Chapter ( 3 ) Bus Bars design
D. Fault duration
1.Design Considerations
A. Introduction
B. Types of Busbar
A. Introduction
The word busbar, derived from the Latin word omnibus ('for all'), gives the
idea of a universal system of conveyance. In the electrical sense, the term bus
is used to describe a junction of circuits, usually in the form of a small number
of inputs and many outputs. 'Busbar' describes the form the bus system usually
takes, a bar or bars of conducting material.
In any electrical circuit some electrical energy is lost as heat which, if not kept
within safe limits, may impair the performance of the system. This energy
loss, which also represents a financial loss over a period of time, is
Project – P1
Chapter ( 3 ) Bus Bars design
proportional to the effective resistance of the conductor and the square of the
current flowing through it. A low resistance therefore means a low loss; a
factor of increasing importance as the magnitude of the current increases.
The capacities of modern-day electrical plant and machinery are such that the
power handled by their control systems gives rise to very large forces.
Busbars, like all the other equipment in the system, have to be able to
withstand these forces without damage. It is essential that the materials used
in their construction should have the best possible mechanical properties and
are designed to operate within the temperature limits laid down in BS 159, BS
EN 60439-1:1994, or other national or international standards.
e) Ease of fabrication
B. Types of Busbar
Busbars can be sub-divided into the following categories, with individual
busbar systems in many cases being constructed from several different types:
c) Totally enclosed but having the construction as those for (a) and (b)
Project – P1
Chapter ( 3 ) Bus Bars design
d) Air insulated where each phase is fully isolated from its adjacent phase(s)
by an earthed enclosure. These are usually called 'Isolated Phase Busbars'.
e) Force-cooled busbar systems constructed as (a) to (d) but using air, water,
etc. as the cooling medium under forced conditions (fan, pump, etc.).
f) Gas insulated busbars. These are usually constructed as type (e) but use a
gas other than air such as SF6, (sulphur hexafluoride).
6 Kelvin's Law Not applied. Other forms Applies. Also other forms
Project – P1
Chapter ( 3 ) Bus Bars design
15 Copper shape Usually rectangular. Tubular used for high current force-
cooled. Usually large cross section rectangular. Tubular used for some low
current high voltage applications and high current force-cooled.
Project – P1
Chapter ( 3 ) Bus Bars design
At the present time the only two commercially available materials suitable for
conductor purposes are copper and aluminum. The table below gives a
comparison of some of their properties. It can be seen that for conductivity
and strength, high conductivity copper is superior to aluminum. The only
disadvantage of copper is its density; for a given current and temperature rise,
an aluminum conductor would be lighter, even though its cross-section would
be larger. In enclosed systems however, space considerations are of greater
importance than weight. Even in open-air systems the weight of the busbars,
which are supported at intervals, is not necessarily the decisive factor.
Project – P1
Chapter ( 3 ) Bus Bars design
1 2 3 4 1 2 3 4
Project – P1
Chapter ( 3 ) Bus Bars design
120 ×10 1200 E−Cu F 30 2110 3280 4270 5130 1740 2860 3740 4500
160× 10 1600 E−Cu F 30 2700 4130 5360 6320 2220 3590 4680 5530
200 ×10 2000 E−Cu F 30 3290 4970 6430 7490 2690 4310 5610 6540
A. Skin Effect
The apparent resistance of a conductor is always higher for a.c. than for d.c.
The alternating magnetic flux created by an alternating current interacts with
the conductor, generating a back e.m.f. which tends to reduce the current in
the conductor. The centre portions of the conductor are affected by the
The ratio of the apparent d.c. and a.c. resistances is known as the skin effect
ratio:
Project – P1
Chapter ( 3 ) Bus Bars design
The magnitude and importance of the effect increases with the frequency, and
the size, shape and thickness of conductor, but is independent of the
magnitude of the current flowing.
It should be noted that as the conductor temperature increases the skin effect
decreases giving rise to a lower than expected a.c. resistance at elevated
temperatures. This effect is more marked for a copper conductor than an
aluminium conductor of equal cross-sectional area because of its lower
resistivity. The difference is particularly noticeable in large busbar sections.
Copper rods
The skin effect ratio of solid copper rods can be calculated from the formulae
derived by Maxwell, Rayleigh and others (Bulletin of the Bureau of
Standards, 1912):
d = diameter of rod, mm
f = frequency, Hz
ρ = resistivity, ρ cm
Project – P1
Chapter ( 3 ) Bus Bars design
Copper tubes
Skin effect in tubular copper conductors is a function of the thickness of the
wall of the tube and the ratio of that thickness to the tube diameter, and for a
given cross sectional area it can be reduced by increasing the tube diameter
and reducing the wall thickness.
Figure 5, Figure 6, and Figure 7, which have been drawn from formulae
derived by Dwight (1922) and Arnold (1936), can be used to find the value of
skin effect for various conductor sections. In the case of tubes (Figure 5), it
can be seen that to obtain low skin effect ratio values it is desirable to ensure,
where possible, low values of t/d and (f/r). For a given cross-sectional area
the skin effect ratio for a thin copper tube is appreciably lower than that for
any other form of conductor. Copper tubes, therefore, have a maximum
efficiency as conductors of alternating currents, particularly those of high
magnitude or high frequency.
The effect of wall thickness on skin effect for a 100 mm diameter tube
carrying a 50Hz alternating current is clearly shown in Figure 5.
Project – P1
Chapter ( 3 ) Bus Bars design
Project – P1
Chapter ( 3 ) Bus Bars design
Project – P1
Chapter ( 3 ) Bus Bars design
current conductor. Figure 7 can be used to find the skin effect value for flat
bars.
Project – P1
Chapter ( 3 ) Bus Bars design
Project – P1
Chapter ( 3 ) Bus Bars design
C. Transposition of conductors
F. Tubular bars
G. Concentric conductors
The efficiency of all types of heavy current busbars depends upon careful
design, the most important factors being:
d) Low skin effect and proximity effect for a.c. busbar systems.
Project – P1
Chapter ( 3 ) Bus Bars design
It is not possible to give any generally applicable factors for calculating the
d.c. rating of laminated bars, since this depends upon the size and proportions
of the laminations and on their arrangement. A guide to the expected relative
ratings are given in Table 8 below for a 50 Hz system. The ratings for single
bars can be estimated using the methods given in Section 3 and Section 4.
Project – P1
Chapter ( 3 ) Bus Bars design
For all normal light and medium current purposes an arrangement such as that
in Figure 9a is entirely satisfactory, but for a.c. currents in excess of 3000 A
where large numbers of laminations would be required it is necessary to
rearrange the laminations to give better utilisation of the copper bars.
This curve shows that due to skin effect there is a considerable variation in the
current carried by each lamination, the outer laminations carrying
approximately four times the current in those at the centre. The two centre
laminations together carry only about one-tenth of the total current.
Project – P1
Chapter ( 3 ) Bus Bars design
The currents in the different laminations may also vary appreciably in phase,
with the result that their numerical sum may be greater than their vectorial
sum, which is equal to the line current. These circulating currents give rise to
additional losses and lower efficiency of the system. It should also be noted
that the curve is non-symmetrical due to the proximity effect of an adjacent
phase.
B. Inter-leaving of conductors
Where long low-voltage a.c. bars are carrying heavy currents, particularly at a
low power factor, inductive volt drop may become a serious problem with
laminated bars arranged as in Figure 9a. The voltage drop for any given size
of conductor is proportional to the current and the length of the bars, and
increases as the separation between conductors of different phases increases.
In the case of laminated bars the inductive volt drop can be reduced by
splitting up the bars into an equivalent number of smaller circuits in parallel,
with the conductors of different phases interleaved as shown in Figure 9b.
This reduces the average spacing between conductors of different phases and
so reduces the inductive volt drop.
C. Transposition of conductors
The unbalanced current distribution in a laminated bar carrying a.c. current
due to skin and proximity effects may be counteracted by transposing
laminations or groups of laminations at intervals. Tappings and other
connections make transposition difficult, but it can be worthwhile where long
sections of bars are free from tappings. The arrangement is as shown in Figure
9e.
With flat copper bars the nearest approach to a unity skin effect ratio is
achieved using a hollow square formation as shown in Figure 9c, though the
current arrangement is still not as good as in a tubular conductor. The heat
Project – P1
Chapter ( 3 ) Bus Bars design
dissipation is also not as good as the same number of bars arranged side by
side as in Figure 9b, due to the horizontally mounted bars at the top and
bottom.
F. Tubular bars
A tubular copper conductor is the most efficient possible as regards skin
effect, as the maximum amount of material is located at a uniform distance
from the magnetic centre of the conductor. The skin effect reduces as the
diameter increases for a constant wall thickness, with values close to unity
possible when the ratio of outside diameter to wall thickness exceeds about
20.
The natural cooling is not as good as that for a laminated copper bar system of
the same cross-sectional area, but when the proximity effects are taken into
account the one-piece tube ensures that the whole tube attains an even
temperature - a condition rarely obtained with laminated bar systems.
A tubular bar also occupies less space than the more usual copper laminated
bar and has a further advantage that its strength and rigidity are greater and
uniform in all deflection planes. These advantages are, however, somewhat
reduced by the difficulty of making joints and connections which are more
difficult than those for laminated bars. These problems have now been
reduced by the introduction of copper welding and exothermic copper forming
methods. Copper tubes are particularly suitable for high current applications,
such as arc furnaces, where forced liquid cooling can be used to great
advantage. The tube can also be used in isolated phase busbar systems due to
the ease with which it can be supported by insulators.
Project – P1
Chapter ( 3 ) Bus Bars design
G.Concentric conductors
This arrangement is not widely used due to difficulties of support but has the
advantage of the optimum combination of low reactance and eddy current
losses and is well suited to furnace and weld set applications. It should be
noted that the isolated phase busbar systems are of this type with the current in
the external enclosure being almost equal to that in the conductor when the
continuously bonded three-phase enclosure system is used.
These are easily supported and give great rigidity and strength while the
making of joints and connections presents no serious difficulty.
The permissible alternating current density in free air for a given temperature
rise is usually greater in the case of two angle-shaped conductors (diagram
(a)) than in any other arrangement of conductor material.
For low voltage heavy current single-phase bars with narrow phase centres,
single copper channels with the webs of the 'go' and 'return' conductors
towards one another give an efficient arrangement. The channel sizes can be
chosen to reduce the skin and proximity effects to a minimum, give maximum
dissipation of heat and have considerable mechanical strength and rigidity.
Where high voltage busbars are concerned the phase spacing has to be much
larger to give adequate electrical clearances between adjacent phases with best
arrangement being with the channel webs furthest apart. For high-capacity
generators which are connected to transformers and allied equipment by
Project – P1
Chapter ( 3 ) Bus Bars design
Project – P1
Chapter ( 3 ) Bus Bars design
mechanical protection and some cooling air flow with the least reduction in
current rating.
The reduction in rating for a given temperature rise will vary considerably
with the type and size of bar and enclosure. The greatest decrease in current
rating occurs with bars which depend mainly on free air circulation and less
on uniform current distribution such as the modified hollow square
arrangement (Figure 9d). In these cases the rating may be reduced to between
60 and 65% when the conductors are enclosed in non-magnetic metal
enclosures. In the case of tubular conductors or those of closely grouped flat
laminations, which are normally not so well cooled by air circulation, the
ratings may be reduced to about 75% of free air ratings for normal
temperature rises.
All parts such as conductor and switch fittings, enclosures and interphase
barriers may be subject to appreciable temperature rise due to circulating and
eddy current losses when close to the heavy current bars and connections.
These losses can be reduced to a minimum by making these parts from high
conductivity non-magnetic material such as copper or copper alloy.
Project – P1
Chapter ( 3 ) Bus Bars design
The ratings of enclosed bars are nearly always much lower than the free air
ratings. The temperature rise is dependent on the rate at which heat is
conducted through the insulating media and dissipated from the outside casing
by radiation and convection. There is nearly always a closer phase spacing
between conductors giving high proximity effects and higher heat losses in the
magnetic outer casings and so giving rise to higher temperature rises.
Proximity effect is often more important for insulated bars than those in air.
Laminated bars have fewer advantages when immersed in oil or compound
and circular copper conductors either solid or hollow though are often
preferred particularly for high-voltage gear and high current generators,
transformers, etc., where more effective cooling such as water cooling can be
Project – P1
Chapter ( 3 ) Bus Bars design
These busbars are used normally for operating voltages of between 11 kV and
36 kV though equipment using much lower voltages and higher voltages are
increasingly changing to this system. Examples of such equipment are exciter
connections, switchgear interconnections, generator to transformer
connections, high voltage switchgear using SF6 (sulphur hexafluoride) gas
insulation (this gas having an insulation level many times better than air). The
current flowing in the conductor ranges from as little as 1000 A to in excess of
40 kA. To obtain the higher currents forced cooling is used, the most
commonly used cooling media being air and water though other cooling gases
or liquids can be used. The use of these cooling systems usually creates much
Project – P1
Chapter ( 3 ) Bus Bars design
increased heat losses and so their use must be justified by benefits in other
areas, e.g., reduced civil costs, reduced physical size where space is at a
premium or reduction in size to enable normal manufacturing methods be
used both for the basic busbar material and also the complete busbar system.
Another factor which influences the method chosen for forced cooling is the
naturally cooled rating of the busbar system and also its ability to sustain
overload conditions. The busbars are usually manufactured in single-phase
units of transportable length and consist of a central conductor usually tubular
of round, square or channel cross-section, supported by porcelain or epoxy
resin insulators. The insulators are located by the external metallic sheath
through which they are normally removed for servicing.
Project – P1
Chapter ( 3 ) Bus Bars design
From table above select one conductor per phase (bare, rectangular)
Where:-
V = Rms voltage to neutral in KV
M= sursace factor = 0.96
δ = air density factor = (3.9 * Pair)/(273+θair) , For Pair = 76 cm Hg
, θair = 45 º C ,
δ = 0.95
r = 1.25 (w/2) = 1.25 * (w/2) = 1.25 (100/2) = 62.5 mm
V= (.38/√2) KV
S= 63 mm
Project – P1
Chapter ( 3 ) Bus Bars design
║ Zfault ║= 0.0887 pu
MVAs.c = 1 / ║ Zfault ║= 11.3
Is.c = 11.3/(0.38*√3) = 17.14 KAmp.
D. Fault duration:
Where:
o Θi = initial conductor (B.B) temp. before fault
o Θf = final B.B temp. after fault.
o a = area in inch2
o t= duration of fault in sec.
o Iscpeak = peak short ciruit current = 2*√2 * Isc = 48.48 KA
o Θi = 55ºC ( allowing 15ºC temp. rise at normal condition)
o Θf= 85ºC (allowing 45ºC temp. rise during s.c)
o a=1.513 in2
t= 2 sec
Project – P1