Sei sulla pagina 1di 7

Air Circuit Breaker

The type of circuit breaker, which operates in air (where air-blast as an arc quenching medium) at
atmospheric pressure, is known to be an Air Circuit Breaker. Air circuit breaker has completely replaced
by oil circuit breaker. In different countries, still it is a preferable choice to use an Air circuit breaker up to
15KV because, there is no chance of oil fire like in oil circuit breaker.

Construction of Air-Circuit Breaker


The following fig shows the main and external parts of an ACB. (ABB EMax Low Voltage, Current
Limiting Air Circuit Breaker and Selective (Non-Current Limiting) Air Circuit Breaker).
1. OFF button (O)
2. ON button (I)
3. Main contact position indicator
4. Energy storage mechanism status indicator
5. Reset Button
6. LED Indicators
7. Controller
8. “Connection”, “Test” and “isolated” position stopper (the three-position latching/locking
mechanism)
9. User-supplied padlock
10. Connection “,” Test “and” separation “of the position indication
11. Connection (CE) Separation, (CD) Test (CT) Position indication contacts
12. Rated Name Plate
13. Digital Displays
14. Mechanical energy storage handle
15. Shake (IN/OUT)
16. Rocker repository
17. Fault trip reset button

(ABB EMax Low Voltage Current Limiting Air Circuit Breaker and Selective (Non-Current Limiting) Air
Circuit Breaker)
1 Sheet Steel Supporting Structure
2 Current Transformer for Protection Trip Unit
3 Pole Group insulating box
4 Horizontal rare terminals
5 5a. Plates for fixed main contacts
6 5b. Plates for fixed arcing Contacts
7 6a. Plates for Main moving contacts
8 6b. Plates for Moving Arcing contacts
9 Arcing Chamber
10 Terminal box for fixed version – Sliding Contacts for withdrawable version
11 Protection Trip Unit
12 Circuit breaker Closing and Opening Control
13 Closing Springs

Principle of Operation of Air Circuit Breaker


The working principle of Air Circuit breaker is rather different from other types of circuit breaker. The
main aim of circuit breaker is to prevent reestablishment of arcing after current zero where the contact
gap will withstand the system recovery voltage. It does it same work, but in a different manner. During
interruption of arc, it creates an arc voltage instead of supply voltage. Arc voltage is defined as the
minimum voltage required for maintaining arc .The circuit breaker increases the voltage in three different
ways :

 Arc voltage can be increased by cooling arc plasma. As soon as the temperature of arc plasma
motion of particle in arc plasma is reduced, more voltage gradient will be required to maintain the
arc.
 By splitting the arc into a number of series will increases the arc voltage.
 Arc voltage can be increased by lengthening the arc path. As soon length of arc path is increased
the resistance path will increase more arc voltage is applied across the arc path hence arc voltage
is increased.

It is operated within voltage level up to 1 KV. It contains two pairs of contact. The main pair carries the
current and the contact made of copper. An additional pair of contact is made of carbon. When the breaker
is opened, the main contact opens first. During opening of the main contact, the arc contact remains in
touch with each other. The arcing gets initiated when arc contacts are separated. The circuit breaker is
obsolete for medium voltage.
Types of Air Circuit Breaker
There are four types of ACBs used in the control and protection to maintain and stable operation of
switch gears and indoor medium voltage.

 Plain Break Type Air Break Circuit Breaker or Cross-Blast Air Circuit Breaker
 Magnetic Blowout Type Air Break Circuit Breaker
 Air Chute Air Break Circuit Breaker
 Air Blast Circuit Breaker

Plain air circuit breaker or Cross-Blast Air Circuit Breaker :

The circuit breaker is fitted with a chamber surrounding the contact. The chamber is known as “arc
chute”. The arc is made to drive in it. The arc chute will help in achieving cooling. Arc chute is made
from some refractory material. The inner walls of arc chute are shaped in such a way that arc is not only
forced into close proximity, but will drive into the serpentine channel projected on arc chute wall.

The arc chute is divided into a number of small compartments by using metallic separation plates.
Metallic separation plates are arc splitters and each of small compartments behave as a mini arc chute.
Initial arc will split into a series of arcs this will make all arc voltages higher than system voltage. They
are preferable choice in low voltage application.
Air Chute Air Break Circuit Breaker

In air chute air circuit breaker, there are two types of contacts namely “main contact” and “auxiliary or
arcing contacts”. The main contacts are made of copper and the silver plates having low resistance and
conducts the current in closed position. Auxiliary or arcing contacts are made of copper alloy as they are
heat resistance and used to prevent from damaging the main contacts due to arcing and can be easily
replaced when needed in case of wear and tear. During the circuit breaker operation, the arcing or
auxiliary contacts are closed before and open after the main contacts of the circuit breaker.

Magnetic Blowout Type Air Break Circuit Breaker

Magnetic blowout air circuit breakers provide magnetic control over the arc moment to make arc
extinction within the devices. The arc extinction is controlled using magnetic field provided by the current
in blowout coils connected in series with the circuit being interrupted. These coils are known as “blow out
the coil”. Magnetic field does not control and extinguish the arc made in the breaker, but it moves the arc
into chutes where the arc is lengthened, cooled and extinguished accordingly. These kind of circuit
breakers are used up to 11kV.

Air Blast Circuit Breaker:

This type of circuit breaker is used for system voltage of 245 KV, 420 KV and even more.
Air blast circuit breaker has further divided into three categories:

 Axial blast breaker


 Axial blast with sliding moving contact.

Axial blast breaker

The moving contact is in contact. There is a nozzle orifice in fixed contact at normal closed condition of
breaker. When a fault occur high pressure is introduced into the chamber. High-pressure air will flow
through nozzle orifice voltage is sufficient to sustain.
Axial blast with sliding moving
contact
The moving contact is fitted over a piston
supported by a spring. The blast transfers arc to
arcing electrode.

Advantages of Air-Blast Circuit Beaker


 Air blast circuit breaker is a suitable option to use where frequent operation is required because of
lesser arc energy
 The risk of fire is eliminated in the operation of Air blast circuit breaker.
 Air blast circuit breaker is small in size, because of the growth of dielectric strength is so rapid
(which final contact gap needed for arc extinction is very small).
 Speed of circuit breaker is much higher during operation of the air blast.
 Arc quenching is much faster
 The duration of the arc is same for all values of current.
 Stability of operation can be maintained and depends on speed operation of circuit breakers.
 It requires less maintenance.

Disadvantages of Air-Blast Circuit Breaker

 The air supplier plant requires additional maintenance.


 It contains high capacity air compressor.
 There is a chance of air pressure leakage from the air pipes junction.
 There is chance of a high rate rise of re-striking voltage and current chopping.
 The air has relatively lower arc extinguishing properties.
Application and Uses of Air Circuit Breaker

 It is used for protection of plants


 It is used for common protection of electrical machines
 It used for protection of transformers, capacitors and generators.
 Air circuit breaker is also used in Electricity sharing system and NGD about 15kV
 Also used in Low as well as High voltage and Currents applications .

https://www.electricaltechnology.org/2014/11/air-circuit-breaker-operation-types-uses.html

Potrebbero piacerti anche