Sei sulla pagina 1di 3

CLIENT XXX

ADDRESS XXXXXXXXXXXX
XXXXXXXXXXXX
XXXXXXXXXX-600000
PROJECT TITLE 600 VA SOLAR SYSTEM DESIGN
REVISION REV P1
DATE 03.06.2013
PREPARED BY
CHECKED BY
APPROVED BY

ELECTRICAL LOAD LIST-HOME APPLIANCES

DAY NIGHT TOTAL PEAK


WATT'S/ APPROXIMATE
S.No ITEM DESCRIPTION IMAGE QUALITY TIME(Average TIME(Average CALCULATED DEMAND PER
HOUR UNIT'S/MONTH
Hours/day) Hours/day) LOAD (Watt's / DAY) WATTS

1 WATER FILTER 0 20 0.25 0 0 0 0

2 MICROWAVE OVAN 0 1200 0.4 0 0 0 0


HOME APPLIANCES

3 FRIDGE(165 LTRS) 0 300 6 6 0 0 0

4 DISH WASHER 0 750 0.25 0.25 0 0 0

5 WASHING MACHINE 0 1400 1 0 0 0 0

6 VACCUM CLEANER 0 1200 1 0 0 0 0

7 STANDFAN 0 80 0 4 0 0 0

8 CEILING FAN 2 75 5 0 750 150 22.5

9 HAIR DRYER 0 2000 0 0 0 0 0

10 MIXER 0 750 0.15 0 0 0 0

11 GRINDER 0 400 0.45 0 0 0 0

12 WATER HEATER 0 2000 0.3 0 0 0 0


GENERAL HOUSE HOLD

AIR CONDITIONER-1.5
13 TON WINDOW 0 2650 2 0 0 0 0

AIR CONDITIONER-1.0
14 TON SPLIT 0 1200 3 0 0 0 0

WATER PUMP/SUMP
14 PUMP(1HP) 0 740 0.2 0 0 0 0

WATER PUMP/SUMP
14 PUMP(1/2 HP) 0 373 0.3 0 0 0 0

15 TELEVISION-CRT 0 125 0 4 0 0 0

16 TELEVISION-LCD 0 180 3 2 0 0 0

17 TELEVISION-LED 0 100 3 2 0 0 0

18 DVD PLAYER 0 18 3 2 0 0 0

19 SETUP BOX 0 200 3 2 0 0 0


ENTERTAINMENT

20 5.1 SOUND SYSTEM 0 18 3 2 0 0 0

21 COMPUTER 0 200 3 2 0 0 0

22 LAPTOP 0 100 3 2 0 0 0

23 BULB 0 60 0.4 5 0 0 0

24 CFL LAMP1 0 11 0 5 0 0 0

24 CFL LAMP2 0 15 0 5 0 0 0

24 CFL LAMP3 0 23 0 5 0 0 0

24 CFL LAMP4 0 32 0 5 0 0 0
LIGHTING
25 TUBE LIGHT 2 40 5 0 400 80 12
LIGHTING

26 MOSQUITO REPELLER 0 9 0 8 0 0 0

27 BATTERY CHARGER 0 7 2 2 0 0 0

TOTAL CALCULATED LOAD 1150 Watt's/day

PEAK LOAD 230 Watt's

APPROXIMATE UNIT'S/MONTH 35

STEP-1 / SELECTION OF INVERTOR

CAPACITY OF THE INVERTER IN Watt's (Divide the power factor value as 0.8 if peak load in watt's) 345.00

CAPACITY OF THE INVERTER IN VA (Divide the power factor value as 0.8 if peak load in watt's) 431.25 600VA

POWER SUPPLY -SINGLE PHASE OR 3 PHASE SINGLE PHASE

STEP-2 / SELECTION OF BATTERY

INPUT'S FOR SIZING THE BATTERY

BATTERY VOLTAGE (12/24/48/96) 12 VOLTS

BATTERY DISCHARGE RATE IS CONSIDERED AS 70% 0.7

INVERTOR EFFICIENCY 0.9

BATTERY CAPACITY 152 AH

THE SELECTED BATTERY BANK CAPACITY 150 AH

NO OF BATTERY WILL BE USED AS 75 2.03 2.00 No's

NO OF BATTERY WILL BE USED AS 100 1.52 2.00 No's

NO OF BATTERY WILL BE USED AS 150 SELECTED 1.01 1.00 No's

NO OF BATTERY WILL BE USED AS 200 0.76 1.00 No's

STEP-3 / SELECTION OF PANEL

PEAK DEMAND 230 Watt's

INVERTER EFFICIENCY 0.7

BATTERY DISCHARGE RATE IS CONSIDERED AS 70% 0.7

TOTAL CALCULATED LOAD FOR PANEL 469 WATT'S

REQUIRED PANEL CAPACITY IN WATT'S 500 WATT'S

NO OF PANEL CONSIDERED IF 200WATT'S CACPCITY 2.50 3.00 No's

NO OF PANEL CONSIDERED IF 250WATT'S CACPCITY 2.00 2.00 No's

NO OF PANEL CONSIDERED IF 300WATT'S CACPCITY 1.67 2.00 No's

STEP-3 / SELECTION OF PANEL WITH VENDOR SPECIFICATION

MAKE OF PANEL TATA ENGINEERING

SELECTED CAPACITY OF PANEL 250.00 WATT'S

POWER OUTPUT P max 255.00 W

VOLTAGE AT Pmax,Vmpp (V) 26.90 V

OPEN CIRCUIT VOLTAGE Voc (V) 32.80 V

SHORT-CIRCUIT CURRENT Isc (A) 8.95 A

CALCULATING THE FILL FACTOR 0.87 A