Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2 Issued: December 2012
Revision: D
A number of protection functions are available for • Single breaker (double or single bus)
flexibility in use for different station types and arrangement (A30)
busbar arrangements. The auto-reclose for • Double breaker arrangement (B30)
single-, two-, and/or three-phase reclose includes • 1 ½ breaker arrangement for a complete
priority circuits for multi-breaker arrangements. It diameter (C30)
co-operates with the synchrocheck function with
high-speed or delayed reclosing. Several breaker Optional functions are not configured but a
failure functions are available to provide a breaker maximum configuration with all optional functions
failure function independent from the protection is available as template in the graphical
IEDs, also for a complete one- and a half breaker configuration tool.Interface to analog and binary
diameter. IO:s are configurable from the setting tool without
need of configuration changes. Analog and
High set instantaneous phase and earth control circuits have been pre-defined. Other
overcurrent, 4 step directional or non-directional signals need to be applied as required for each
delayed phase and earth overcurrent, thermal application. The main differences between the
overload and two step under- and overvoltage packages above are the interlocking modules and
functions are examples of the available functions the number of apparatuses to control.
allowing user to fulfill any application requirement.
ABB 3
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
2. Available functions
REC670 (C30)
REC670 (B30)
REC670 (A30)
Differential protection
4 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
REC670 (C30)
REC670 (B30)
REC670 (A30)
Current protection
OC4PTOC 51_67 Four step phase overcurrent protection 1-C31 1-C32 1-C33
EF4PTOC 51N_67 Four step residual overcurrent protection 1-C31 1-C32 1-C33
N
NS4PTOC 46I2 Four step directional negative phase sequence 1-C31 1-C32 1-C33
overcurrent protection
SDEPSDE 67N Sensitive directional residual overcurrent and 1-C16 1-C16 1-C16
power protection
LPPTR 26 Thermal overload protection, one time constant 1-C31 1-C32 1-C33
TRPTTR 49 Thermal overload protection, two time constant 1-C31 1-C32 1-C33
Voltage protection
ROV2PTOV 59N Two step residual overvoltage protection 2-D02 2-D02 2-D02
Frequency protection
Multipurpose protection
ABB 5
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
REC670 (C30)
REC670 (B30)
REC670 (A30)
Control
TR1ATCC 90 Automatic voltage control for tap changer, single 1-H11 1-H11 2-H16
control
TR8ATCC 90 Automatic voltage control for tap changer, parallel 1-H15 1-H15 2-H18
control
6 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
REC670 (C30)
REC670 (B30)
REC670 (A30)
Logic
Monitoring
CVMMXN Measurements 6 6 6
ABB 7
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Designed to communicate
REC670 (C30)
REC670 (B30)
REC670 (A30)
Station communication
Scheme communication
ZCRWPSCH 85 Current reversal and weak-end infeed logic for 1-K01 1-K01 1-K01
distance protection
ECRWPSCH 85 Current reversal and weak-end infeed logic for 1-C31 1-C32 1-C33
residual overcurrent protection
8 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
ABB 9
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
available to allow application for two three-phase EF4PTOC can be set directional or non-
zones busbar protection. directional independently for each of the steps.
Instantaneous phase overcurrent protection Second harmonic blocking can be set individually
PHPIOC for each step.
The instantaneous three phase overcurrent
function has a low transient overreach and short EF4PTOC can be used as main protection for
tripping time to allow use as a high set short- phase-to-earth faults.
circuit protection function.
EF4PTOC can also be used to provide a system
Four step phase overcurrent protection OC4PTOC back-up for example, in the case of the primary
The four step phase overcurrent protection protection being out of service due to
function OC4PTOC has an inverse or definite time communication or voltage transformer circuit
delay independent for step 1 and 4 separately. failure.
Step 2 and 3 are always definite time delayed.
Directional operation can be combined together
All IEC and ANSI inverse time characteristics are with corresponding communication logic in
available together with an optional user defined permissive or blocking teleprotection scheme.
time characteristic. Current reversal and weak-end infeed functionality
are available as well.
The directional function is voltage polarized with
memory. The function can be set to be directional EF4PTOC can be configured to measure the
or non-directional independently for each of the residual current from the three-phase current
steps. inputs or the current from a separate current input.
A 2nd harmonic blocking can be set individually Four step negative sequence overcurrent
for each step. protection NS4PTOC
Four step negative sequence overcurrent
Instantaneous residual overcurrent protection protection (NS4PTOC) has an inverse or definite
EFPIOC time delay independent for each step separately.
The Instantaneous residual overcurrent protection
EFPIOC has a low transient overreach and short All IEC and ANSI time delayed characteristics are
tripping times to allow the use for instantaneous available together with an optional user defined
earth-fault protection, with the reach limited to characteristic.
less than the typical eighty percent of the line at
minimum source impedance. EFPIOC can be The directional function is voltage polarized or
configured to measure the residual current from dual polarized.
the three-phase current inputs or the current from
NS4PTOC can be set directional or non-
a separate current input. EFPIOC can be blocked
directional independently for each of the steps.
by activating the input BLOCK.
NS4PTOC can be used as main protection for
Four step residual overcurrent protection, zero
unsymmetrical fault; phase-phase short circuits,
sequence and negative sequence direction
phase-phase-earth short circuits and single phase
EF4PTOC
earth faults.
The four step residual overcurrent protection
EF4PTOC has an inverse or definite time delay NS4PTOC can also be used to provide a system
independent for each step separately. back-up for example, in the case of the primary
protection being out of service due to
All IEC and ANSI time-delayed characteristics are
communication or voltage transformer circuit
available together with an optional user defined
failure.
characteristic.
10 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Directional operation can be combined together temperature will degrade the quality of the
with corresponding communication logic in transformer/generator insulation.
permissive or blocking teleprotection scheme.
The same logic as for directional zero sequence The thermal overload protection estimates the
current can be used. Current reversal and weak- internal heat content of the transformer/generator
end infeed functionality are available. (temperature) continuously. This estimation is
made by using a thermal model of the transformer/
Sensitive directional residual overcurrent and generator with two time constants, which is
power protection SDEPSDE based on current measurement.
In isolated networks or in networks with high
impedance earthing, the earth fault current is Two warning levels are available. This enables
significantly smaller than the short circuit currents. actions in the power system to be done before
In addition to this, the magnitude of the fault dangerous temperatures are reached. If the
current is almost independent on the fault location temperature continues to increase to the trip
in the network. The protection can be selected to value, the protection initiates a trip of the
use either the residual current or residual power protected transformer/generator.
component 3U0·3I0·cos j, for operating quantity
Breaker failure protection CCRBRF
with maintained short circuit capacity. There is
Breaker failure protection (CCRBRF) ensures fast
also available one nondirectional 3I0 step and one
back-up tripping of surrounding breakers in case
3U0 overvoltage tripping step.
the own breaker fails to open. CCRBRF can be
No specific sensitive current input is current based, contact based, or an adaptive
needed.SDEPSDE can be set as low 0.25% of combination of these two conditions.
IBase.
Current check with extremely short reset time is
Thermal overload protection, one time constant used as check criterion to achieve high security
LPTTR against unnecessary operation.
The increasing utilizing of the power system
Contact check criteria can be used where the
closer to the thermal limits has generated a need
fault current through the breaker is small.
of a thermal overload protection also for power
lines. CCRBRF can be single- or three-phase initiated
to allow use with single phase tripping
A thermal overload will often not be detected by
applications. For the three-phase version of
other protection functions and the introduction of
CCRBRF the current criteria can be set to operate
the thermal overload protection can allow the
only if two out of four for example, two phases or
protected circuit to operate closer to the thermal
one phase plus the residual current start. This
limits.
gives a higher security to the back-up trip
The three-phase current measuring protection command.
has an I 2t characteristic with settable time
CCRBRF function can be programmed to give a
constant and a thermal memory..
single- or three-phase re-trip of the own breaker
to avoid unnecessary tripping of surrounding
An alarm level gives early warning to allow
breakers at an incorrect initiation due to mistakes
operators to take action well before the line is
during testing.
tripped.
Pole discordance protection CCRPLD
Thermal overload protection, two time constant
TRPTTR An open phase can cause negative and zero
sequence currents which cause thermal stress on
If a power transformer or generator reaches very
rotating machines and can cause unwanted
high temperatures the equipment might be
operation of zero sequence or negative sequence
damaged. The insulation within the transformer/
current functions.
generator will have forced ageing. As a
consequence of this the risk of internal phase-to-
Normally the own breaker is tripped to correct
phase or phase-to-earth faults will increase. High
such a situation. If the situation persists the
ABB 11
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
surrounding breakers should be tripped to clear Two step overvoltage protection (OV2PTOV)
the unsymmetrical load situation. function can be used to detect open line ends,
normally then combined with a directional reactive
The Polediscordance protection function CCRPLD over-power function to supervise the system
operates based on information from auxiliary voltage. When triggered, the function will cause
contacts of the circuit breaker for the three an alarm, switch in reactors, or switch out
phases with additional criteria from unsymmetrical capacitor banks.
phase currents when required.
OV2PTOV has two voltage steps, each of them
Directional over/underpower protection with inverse or definite time delayed.
GOPPDOP/GUPPDUP
The directional over-/under-power protection OV2PTOV has an extremely high reset ratio to
GOPPDOP/GUPPDUP can be used wherever a allow settings close to system service voltage.
high/low active, reactive or apparent power
protection or alarming is required. The functions Two step residual overvoltage protection
can alternatively be used to check the direction of ROV2PTOV
active or reactive power flow in the power system. Residual voltages may occur in the power system
There are a number of applications where such during earth faults.
functionality is needed. Some of them are:
Two step residual overvoltage protection
• detection of reversed active power flow ROV2PTOV function calculates the residual
• detection of high reactive power flow voltage from the three-phase voltage input
transformers or measures it from a single voltage
Each function has two steps with definite time input transformer fed from an open delta or
delay. Reset times for both steps can be set as neutral point voltage transformer.
well.
ROV2PTOV has two voltage steps, each with
Broken conductor check BRCPTOC inverse or definite time delay.
The main purpose of the function Broken
conductor check (BRCPTOC) is the detection of Reset delay ensures operation for intermittent
broken conductors on protected power lines and earth faults.
cables (series faults). Detection can be used to
Voltage differential protection VDCPTOV
give alarm only or trip the line breaker.
A voltage differential monitoring function is
available. It compares the voltages from two three
5. Voltage protection phase sets of voltage transformers and has one
sensitive alarm step and one trip step.
Two step undervoltage protection UV2PTUV
Undervoltages can occur in the power system Loss of voltage check LOVPTUV
during faults or abnormal conditions. Two step Loss of voltage check (LOVPTUV) is suitable for
undervoltage protection (UV2PTUV) function can use in networks with an automatic system
be used to open circuit breakers to prepare for restoration function. LOVPTUV issues a three-
system restoration at power outages or as long- pole trip command to the circuit breaker, if all
time delayed back-up to primary protection. three phase voltages fall below the set value for a
time longer than the set time and the circuit
UV2PTUV has two voltage steps, each with breaker remains closed.
inverse or definite time delay.
12 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
ABB 13
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
order to avoid unwanted operations that are in synchronism, or with at least one side dead
otherwise might occur. to ensure that closing can be done safely.
The fuse failure supervision function basically has SESRSYN function includes a built-in voltage
three different algorithms, negative sequence and selection scheme for double bus and 1½ breaker
zero sequence based algorithms and an or ring busbar arrangements.
additional delta voltage and delta current
algorithm. Manual closing as well as automatic reclosing can
be checked by the function and can have different
The negative sequence detection algorithm is settings.
recommended for IEDs used in isolated or high-
impedance earthed networks. It is based on the For systems which are running asynchronous a
negative-sequence measuring quantities, a high synchronizing function is provided. The main
value of voltage 3U 2 without the presence of the purpose of the synchronizing function is to
provide controlled closing of circuit breakers
negative-sequence current 3I 2 .
when two asynchronous systems are going to be
The zero sequence detection algorithm is connected. It is used for slip frequencies that are
recommended for IEDs used in directly or low larger than those for synchrocheck and lower
impedance earthed networks. It is based on the than a set maximum level for the synchronizing
zero sequence measuring quantities, a high value function.
of voltage 3U 0 without the presence of the
Autorecloser SMBRREC
residual current 3I 0.
The autorecloser SMBRREC function provides
high-speed and/or delayed auto-reclosing for
For better adaptation to system requirements, an
single or multi-breaker applications.
operation mode setting has been introduced
which makes it possible to select the operating Up to five three-phase reclosing attempts can be
conditions for negative sequence and zero included by parameter setting. The first attempt
sequence based function. The selection of can be single-, two and/or three phase for single
different operation modes makes it possible to phase or multi-phase faults respectively.
choose different interaction possibilities between
the negative sequence and zero sequence based Multiple autoreclosing functions are provided for
algorithm. multi-breaker arrangements. A priority circuit
allows one circuit breaker to close first and the
A criterion based on delta current and delta second will only close if the fault proved to be
voltage measurements can be added to the fuse transient.
failure supervision function in order to detect a
three phase fuse failure, which in practice is more Each autoreclosing function can be configured to
associated with voltage transformer switching co-operate with a synchrocheck function.
during station operations.
Apparatus control APC
The apparatus control functions are used for
9. Control control and supervision of circuit breakers,
disconnectors and earthing switches within a bay.
Synchrocheck, energizing check, and
Permission to operate is given after evaluation of
synchronizing SESRSYN
conditions from other functions such as
The Synchronizing function allows closing of
interlocking, synchrocheck, operator place
asynchronous networks at the correct moment
selection and external or internal blockings.
including the breaker closing time, which
improves the network stability. Apparatus control features:
• Select-Execute principle to give high reliability
Synchrocheck, energizing check, and
• Selection function to prevent simultaneous
synchronizing (SESRSYN) function checks that
operation
the voltages on both sides of the circuit breaker
• Selection and supervision of operator place
• Command supervision
14 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
ABB 15
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
16 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
protection can be supported with a logic that overcome these conditions, weak-end infeed
uses communication channels. (WEI) echo logic is used.
ABB 17
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
• SRMEMORY function block is a flip-flop that frequency, temperature and DC battery voltage as
can set or reset an output from two inputs low current values, usually in the range 4-20 mA
respectively. Each block has two outputs where or 0-20 mA.
one is inverted. The memory setting controls if
the block's output should reset or return to the Alarm limits can be set and used as triggers, e.g.
state it was, after a power interruption. Set to generate trip or alarm signals.
input has priority.
The function requires that the IED is equipped
• RSMEMORY function block is a flip-flop that with the mA input module.
can reset or set an output from two inputs
Event counter CNTGGIO
respectively. Each block has two outputs where
Event counter (CNTGGIO) has six counters which
one is inverted. The memory setting controls if
are used for storing the number of times each
the block's output should reset or return to the
counter input has been activated.
state it was, after a power interruption. RESET
input has priority. Disturbance report DRPRDRE
Complete and reliable information about
Extension logic package disturbances in the primary and/or in the
The logic extension block package includes secondary system together with continuous event-
additional trip matrix logic and configurable logic logging is accomplished by the disturbance report
blocks. functionality.
18 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
ABB 19
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
to the Event function (EVENT). The event function The compensation includes setting of the remote
block is used for LON and SPA communication. and local sources and calculation of the
distribution of fault currents from each side. This
Analog and double indication values are also distribution of fault current, together with
transferred through EVENT function. recorded load (pre-fault) currents, is used to
exactly calculate the fault position. The fault can
IEC61850 generic communication I/O function
be recalculated with new source data at the
SPGGIO
actual fault to further increase the accuracy.
IEC61850 generic communication I/O functions
(SPGGIO) is used to send one single logical signal Especially on heavily loaded long lines (where the
to other systems or equipment in the substation. fault locator is most important) where the source
voltage angles can be up to 35-40 degrees apart
IEC61850 generic communication I/O functions
the accuracy can be still maintained with the
MVGGIO
advanced compensation included in fault locator.
IEC61850 generic communication I/O functions
(MVGGIO) function is used to send the
instantaneous value of an analog signal to other 13. Metering
systems or equipment in the substation. It can
also be used inside the same IED, to attach a Pulse counter logic PCGGIO
RANGE aspect to an analog value and to permit Pulse counter (PCGGIO) function counts
measurement supervision on that value. externally generated binary pulses, for instance
pulses coming from an external energy meter, for
Measured value expander block RANGE_XP calculation of energy consumption values. The
The current and voltage measurements functions pulses are captured by the binary input module
(CVMMXN, CMMXU, VMMXU and VNMMXU), and then read by the function. A scaled service
current and voltage sequence measurement value is available over the station bus. The special
functions (CMSQI and VMSQI) and IEC 61850 Binary input module with enhanced pulse
generic communication I/O functions (MVGGIO) counting capabilities must be ordered to achieve
are provided with measurement supervision this functionality.
functionality. All measured values can be
supervised with four settable limits: low-low limit, Function for energy calculation and demand
low limit, high limit and high-high limit. The handling ETPMMTR
measure value expander block (RANGE_XP) has Outputs from the Measurements (CVMMXN)
been introduced to enable translating the integer function can be used to calculate energy
output signal from the measuring functions to 5 consumption. Active as well as reactive values are
binary signals: below low-low limit, below low calculated in import and export direction. Values
limit, normal, above high-high limit or above high can be read or generated as pulses. Maximum
limit. The output signals can be used as demand power values are also calculated by the
conditions in the configurable logic or for alarming function.
purpose.
14. Basic IED functions
Fault locator LMBRFLO
The accurate fault locator is an essential Time synchronization
component to minimize the outages after a The time synchronization source selector is used
persistent fault and/or to pin-point a weak spot to select a common source of absolute time for
on the line. the IED when it is a part of a protection system.
This makes it possible to compare event and
The fault locator is an impedance measuring
disturbance data between all IEDs in a station
function giving the distance to the fault in percent,
automation system.
km or miles. The main advantage is the high
accuracy achieved by compensating for load
current and for the mutual zero-sequence effect
on double circuit lines.
20 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
ABB 21
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
22 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Binary input/output module IOM module has one RS485 communication port. The
The binary input/output module is used when only RS485 is a balanced serial communication that
a few input and output channels are needed. The can be used either in 2-wire or 4-wire
ten standard output channels are used for trip connections. A 2-wire connection uses the same
output or any signaling purpose. The two high signal for RX and TX and is a multidrop
speed signal output channels are used for communication with no dedicated Master or
applications where short operating time is slave. This variant requires however a control of
essential. Eight optically isolated binary inputs the output. The 4-wire connection has separated
cater for required binary input information. signals for RX and TX multidrop communication
with a dedicated Master and the rest are slaves.
mA input module MIM No special control signal is needed in this case.
The milli-ampere input module is used to interface
transducer signals in the –20 to +20 mA range GPS time synchronization module GTM
from for example OLTC position, temperature or This module includes a GPS receiver used for
pressure transducers. The module has six time synchronization. The GPS has one SMA
independent, galvanically separated channels. contact for connection to an antenna. It also
includes an optical PPS ST-connector output.
Optical ethernet module OEM
The optical fast-ethernet module is used to IRIG-B Time synchronizing module
connect an IED to the communication buses (like The IRIG-B time synchronizing module is used for
the station bus) that use the IEC 61850-8-1 accurate time synchronizing of the IED from a
protocol (port A, B). The module has one or two station clock.
optical ports with ST connectors.
Transformer input module TRM
Serial and LON communication module SLM, The transformer input module is used to
supports SPA/IEC 60870-5-103, LON and DNP 3.0 galvanically separate and transform the secondary
The serial and LON communication module (SLM) currents and voltages generated by the
is used for SPA, IEC 60870-5-103, DNP3 and measuring transformers. The module has twelve
LON communication. The module has two optical inputs in different combinations of currents and
communication ports for plastic/plastic, plastic/ voltage inputs.
glass or glass/glass. One port is used for serial
communication (SPA, IEC 60870-5-103 and Alternative connectors of Ring lug or
DNP3 port or dedicated IEC 60870-5-103 port Compression type can be ordered.
depending on ordered SLM module) and one port
High impedance resistor unit
is dedicated for LON communication.
The high impedance resistor unit, with resistors
Line data communication module LDCM for pick-up value setting and a voltage dependent
Each module has one optical port, one for each resistor, is available in a single phase unit and a
remote end to which the IED communicates. three phase unit. Both are mounted on a 1/1 19
inch apparatus plate with compression type
Alternative cards for Medium range (1310 nm terminals.
single mode) and Short range (850 nm multi
mode) are available. Layout and dimensions
Dimensions
Galvanic RS485 serial communication module
The Galvanic RS485 communication module
(RS485) is used for DNP3.0 communication. The
ABB 23
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
B C
D
xx05000003.vsd
IEC05000003 V1 EN
xx05000004.vsd
IEC05000004 V1 EN
Case size A B C D E F
(mm)
24 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
ABB 25
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
1MRK002801-AC-2-670-1.2-PG V1 EN
26 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
1MRK002801-AC-3-670-1.2-PG V1 EN
ABB 27
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
1MRK002801-AC-4-670-1.2-PG V1 EN
1MRK002801-AC-5-670-1.2-PG V1 EN
28 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
1MRK002801-AC-6-670-1.2-PG V1 EN
ABB 29
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
1MRK002801-AC-10-670-1.2-PG V1 EN
12I, 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A
12I, 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A
9I+3U, 1A 1A 1A 1A 1A 1A 1A 1A 1A 110-220V 110-220V 110-220V
1A
9I+3U, 5A 5A 5A 5A 5A 5A 5A 5A 5A 110-220V 110-220V 110-220V
5A
5I, 1A 1A 1A 1A 1A 1A 5A 5A 5A 5A 110-220V 110-220V 110-220V
+4I, 5A
+3U
7I+5U, 1A 1A 1A 1A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V
1A
7I+5U, 5A 5A 5A 5A 5A 5A 5A 110-220V 110-220V 110-220V 110-220V 110-220V
5A
6I, 5A 5A 5A 5A 5A 5A 5A 1A 110-220V 110-220V 110-220V 110-220V 110-220V
+1I, 1A
+5U
3I, 5A 5A 5A 5A 1A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V
+4I, 1A
+5U
3IM, 1A 1AM 1AM 1AM 1A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V
+4IP, *) *) *)
1A+5U
3IM, 5A 5AM 5AM 5AM 5A 5A 5A 5A 110-220V 110-220V 110-220V 110-220V 110-220V
+4IP, *) *) *)
5A+5U
6I+6U, 1A 1A 1A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V 110-220V
1A
6I+6U, 5A 5A 5A 5A 5A 5A 110-220V 110-220V 110-220V 110-220V 110-220V 110-220V
5A
30 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Note that internal polarity can be adjusted by setting of analog input CT neutral direction and/or on SMAI pre-
processing function blocks.
1MRK002801-AC-15-670-1.2-PG V1 EN
1MRK002801-AC-11-670-1.2-PG V1 EN
ABB 31
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
1MRK002801-AC-8-670-1.2-PG V1 EN
1MRK002801-AC-7-670-1.2-PG V1 EN
32 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
1MRK002801-AC-12-670-1.2-PG V1 EN
Figure 9. Binary output module (BOM). Output contacts named XA corresponds to rear position X31, X41, and
so on, and output contacts named XB to rear position X32, X42, and so on.
1MRK002801-AC-13-670-1.2-PG V1 EN
ABB 33
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
1MRK002801-AC-14-670-1.2-PG V1 EN
Figure 11. Binary in/out module (IOM). Input contacts named XA corresponds to rear position X31, X41, and so
on, and output contacts named XB to rear position X32, X42, and so on.
34 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
General
Definitions
Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment
Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions,
the equipment meets the specified requirements
Operative range The range of values of a given energizing quantity for which the equipment, under specified
conditions, is able to perform its intended functions according to the specified requirements
Table 6. TRM - Energizing quantities, rated values and limits for protection transformer modules
Current Ir = 1 or 5 A (0.2-40) × Ir
Frequency fr = 50/60 Hz ± 5%
ABB 35
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Table 7. TRM - Energizing quantities, rated values and limits for measuring transformer modules
Frequency fr = 50/60 Hz ± 5%
Power consumption -
each mA-board £2W
each mA input £ 0.1 W
Number of channels 1 or 2
36 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Auxiliary DC voltage
Binary inputs 16 -
Power consumption
24/30 V max. 0.05 W/input -
48/60 V max. 0.1 W/input
110/125 V max. 0.2 W/input
220/250 V max. 0.4 W/input
Table 12. BIM - Binary input module with enhanced pulse counting capabilities
Binary inputs 16 -
Power consumption
24/30 V max. 0.05 W/input -
48/60 V max. 0.1 W/input
110/125 V max. 0.2 W/input
220/250 V max. 0.4 W/input
ABB 37
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Binary inputs 8 -
Power consumption -
24/30 V max. 0.05 W/input
48/60 V max. 0.1 W/input
110/125 V max. 0.2 W/input
220/250 V max. 0.4 W/input
Table 14. IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and signal relays Fast signal relays (parallel
reed relay)
Binary outputs 10 2
0.2 s
1.0 s 30 A 0.4 A
10 A 0.4 A
Breaking capacity for AC, cos φ > 0.4 250 V/8.0 A 250 V/8.0 A
38 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Table 15. IOM with MOV - contact data (reference standard: IEC 60255-23)
Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay)
ABB 39
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Table 16. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs
Number of outputs 6 6
Test voltage across open contact, 1 min No galvanic separation No galvanic separation
Continuous 5A 5A
220V / 0.2A
250V / 0.15A
Table 17. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs
Number of outputs 6
Continuous 8A
1.0s 10A
0.2s 30A
1.0s 10A
110V / 0.4A
125V / 0,35A
220V / 0,2A
250V / 0.15A
40 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Table 18. BOM - Binary output module contact data (reference standard: IEC 61810-2)
Binary outputs 24
Influencing factors
90-250 V DC ± 20%
Interruption interval
0–50 ms
No restart
ABB 41
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Harmonic frequency dependence (20% 2nd, 3rd and 5th harmonic of fr ± 1.0%
content)
Harmonic frequency dependence for high 2nd, 3rd and 5th harmonic of fr ±5.0%
impedance differential protection (10%
content)
100 kHz slow damped oscillatory wave 2.5 kV IEC 61000-4-18, Class III
immunity test
Ring wave immunity test, 100 kHz 2-4 kV IEC 61000-4-12, Class IV
Conducted common mode immunity test 15 Hz-150 kHz IEC 61000-4-16, Class IV
Power frequency magnetic field test 1000 A/m, 3 s IEC 61000-4-8, Class V
100 A/m, cont.
Damped oscillatory magnetic field test 100 A/m IEC 61000-4-10, Class V
1.4-2.7 GHz
42 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Damp heat test, steady state Test Ca for 4 days at +40 °C and humidity 93% IEC 60068-2-78
Damp heat test, cyclic Test Db for 6 cycles at +25 to +55 °C and IEC 60068-2-30
humidity 93 to 95% (1 cycle = 24 hours)
Test According to
Immunity EN 50263
Emissivity EN 50263
ABB 43
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Differential protection
44 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Current protection
Inverse characteristics, see 19 curve types See table 98, table 99 and table
table 98, table 99 and table 100 100
ABB 45
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Inverse characteristics, see table 18 curve types See table 98, table 99 and table
98, table 99 and table 100 100
46 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Inverse characteristics, see table 18 curve types See table 98, table 99 and table
98, table 99 and table 100 100
Minimum operate current for step (1.00 - 10000.00)% of IBase ± 1.0% of Ir at I < Ir
1-4 ± 1.0% of I at I > Ir
ABB 47
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Table 33. Sensitive directional residual overcurrent and power protection SDEPSDE
At low setting:
(0.25-1.00)% of Ir: ±0.05% of Ir
(1.00-5.00)% of Ir: ±0.1% of Ir
At low setting:
(0.25-1.00)% of Ir: ±0.05% of Ir
(1.00-5.00)% of Ir: ±0.1% of Ir
Inverse characteristics, see 19 curve types See table 98, table 99 and table 100
table 98, table 99 and table
100
48 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Table 33. Sensitive directional residual overcurrent and power protection SDEPSDE, continued
Function Range or value Accuracy
Operate time: Time constant t = (0–1000) minutes IEC 60255-8, ±5% + 200 ms
æ I 2 - I p2 ö
t = t × ln ç 2 ÷
ç I - Ib 2 ÷
è ø
EQUATION1356 V1 EN (Equation 1)
Operate time: Ip = load current before overload IEC 60255–8, ±5% + 200 ms
occurs
æ I 2 - I p2 ö Time constant τ = (1–500)
t = t × ln ç 2 ÷ minutes
ç I - Ib 2 ÷
è ø
EQUATION1356 V1 EN (Equation 2)
I = Imeasured
Alarm level 1 and 2 (50–99)% of heat content trip ± 2.0% of heat content trip
value
Reset level temperature (10–95)% of heat content trip ± 2.0% of heat content trip
ABB 49
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
50 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
ABB 51
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Voltage protection
52 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
ABB 53
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Frequency protection
Operate time, start function 100 ms typically at fset -0.5 Hz to fset +0.5 Hz -
54 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Multipurpose protection
See table 98 and table 99 Parameter ranges for customer defined See table 98 and table 99
characteristic no 17:
k: 0.05 - 999.00
A: 0.0000 - 999.0000
B: 0.0000 - 99.0000
C: 0.0000 - 1.0000
P: 0.0001 - 10.0000
PR: 0.005 - 3.000
TR: 0.005 - 600.000
CR: 0.1 - 10.0
Start overvoltage, step 1 and 2 (2.0 - 200.0)% of UBase ± 0.5% of Ur for U<Ur
± 0.5% of U for U>Ur
Start undervoltage, step 1 and 2 (2.0 - 150.0)% of UBase ± 0.5% of Ur for U<Ur
± 0.5% of U for U>Ur
ABB 55
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
High and low voltage limit, voltage (1.0 - 200.0)% of UBase ± 1.0% of Ur for U<Ur
dependent operation ± 1.0% of U for U>Ur
Overcurrent:
Undercurrent:
Overvoltage:
Undervoltage:
56 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
ABB 57
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Control
Voltage high limit for synchronizing and (50.0-120.0)% of UBaseBus and ± 0.5% of Ur at U ≤ Ur
synchrocheck UBaseLIne ± 0.5% of U at U >Ur
Phase angle difference limit between bus and (5.0-90.0) degrees ± 2.0 degrees
line for synchrocheck
Voltage difference limit between bus and line (0.02-0.5) p.u ± 0.5% of Ur
for synchronizing and synchrocheck
Voltage high limit for energizing check (50.0-120.0)% of UBaseBus and ± 0.5% of Ur at U ≤ Ur
UBaseLIne ± 0.5% of U at U >Ur
Voltage low limit for energizing check (10.0-80.0)% of UBaseBus and ± 0.5% of Ur
UBaseLine
58 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
shot 2 - t2 (0.00-6000.00) s
shot 3 - t3
shot 4 - t4
shot 5 - t5
Wait time after close command before proceeding to next shot (0.000-60.000) s
ABB 59
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
60 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Table 54. Voltage control TR1ATCC, TR8ATCC, TCMYLTC and TLCYLTC, continued
Function Range or value Accuracy
ABB 61
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Scheme communication
Table 55. Scheme communication logic for distance or overcurrent protection ZCPSCH
Table 56. Current reversal and weak-end infeed logic for distance protection ZCRWPSCH
Table 57. Scheme communication logic for residual overcurrent protection ECPSCH
62 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Table 58. Current reversal and weak-end infeed logic for residual overcurrent protection ECRWPSCH
ABB 63
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Logic
LogicAND 60 60 160 - -
LogicOR 60 60 160 - -
LogicXOR 10 10 20 - -
LogicInverter 30 30 80 - -
LogicSRMemory 10 10 20 - -
LogicRSMemory 10 10 20 - -
LogicGate 10 10 20 - -
Boolean 16 to Integer 4 4 8 - -
Boolean 16 to integer 4 4 8 - -
with Logic Node
Integer to Boolean 16 4 4 8 - -
Integer to Boolean 16 4 4 8 - -
with Logic Node
64 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
LogicAND 40 40 100 - -
LogicXOR - - 49 - -
LogicSRMemory - - 110 - -
SLGGIO 10 10 54 - -
VSGGIO 10 10 10 - -
LogicOR 40 40 100 - -
LogicGate - - 49 - -
LogicTimerSet - - 49 - -
LogicLoopDelay - - 49 - -
ABB 65
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Monitoring
66 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
ABB 67
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Maximum number of events in the Event list 1000, first in - first out -
Maximum total recording time (3.4 s recording time 340 seconds (100 recordings) at -
and maximum number of channels, typical value) 50 Hz, 280 seconds (80
recordings) at 60 Hz
Function Value
Resolution 1 ms
68 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Function Value
Function Value
Resolution 1 ms
Function Value
Function Value
Maximum total recording time (3.4 s recording time and maximum number 340 seconds (100 recordings) at 50 Hz
of channels, typical value) 280 seconds (80 recordings) at 60 Hz
ABB 69
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Metering
Energy metering kWh Export/Import, kvarh Export/ Input from MMXU. No extra error at steady load
Import
70 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Station communication
Function Value
Protocol DNP3.0
Function Value
Protocol LON
Function Value
Protocol SPA
Function Value
ABB 71
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Table 86. IEC 62439-3 Edition 1 and Edition 2 parallel redundancy protocol
Function Value
72 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Remote communication
Type of LDCM Short range (SR) Medium range (MR) Long range (LR)
Transmission rate / Data rate 2 Mb/s / 64 kbit/s 2 Mb/s / 64 kbit/s 2 Mb/s / 64 kbit/s
Clock source Internal or derived Internal or derived Internal or derived from received
from received from received signal signal
signal
ABB 73
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Hardware
IED
Table 89. Water and dust protection level according to IEC 60529
Connection system
Terminal blocks suitable for ring lug terminals 250 V AC, 20 A 4 mm2 (AWG12)
Terminal blocks suitable for ring lug terminals 300 V AC 3 mm2 (AWG14)
74 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Data Value
Function Value
Time tagging error with synchronization once/min (minute pulse synchronization), ± 1.0 ms typically
events and sampled measurement values
Time tagging error with SNTP synchronization, sampled measurement values ± 1.0 ms typically
Function Value
Accuracy +/-2μs
ABB 75
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Electrical connector:
Amplitude modulated
– low level 1-3 Vpp
– high level 3 x low level, max 9 Vpp
Accuracy +/-10μs for IRIG-B 00x and +/-100μs for IRIG-B 12x
Optical connector:
76 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Inverse characteristic
æ A ö
t = ç P + B÷ × k
ç ( I - 1) ÷
è ø
EQUATION1249-SMALL V1 EN
Reset characteristic:
tr
t = ×k
(I 2
)
-1
EQUATION1250-SMALL V1 EN
I = Imeasured/Iset
ABB 77
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
æ A ö
t = ç P ÷×k
ç ( I - 1) ÷
è ø
EQUATION1251-SMALL V1 EN
I = Imeasured/Iset
Time delay to reset, IEC inverse time (0.000-60.000) s ± 0.5% of set time ± 10 ms
TR
t = ×k
(I PR
- CR )
EQUATION1253-SMALL V1 EN
I = Imeasured/Iset
78 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
I = Imeasured/Iset
æ I ö
t = 5.8 - ç 1.35 × In ÷
è k ø
EQUATION1138-SMALL V1 EN
I = Imeasured/Iset
k
t =
æU -U >ö
ç ÷
è U > ø
EQUATION1436-SMALL V1 EN
U> = Uset
U = Umeasured
k × 480
t =
2.0
æ 32 × U - U > - 0.5 ö
ç ÷ - 0.035
è U > ø
EQUATION1437-SMALL V1 EN
k × 480
t =
3.0
æ 32 × U - U > - 0.5 ö
ç ÷ - 0.035
è U > ø
EQUATION1438-SMALL V1 EN
ABB 79
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
k
t =
æ U < -U
ö
ç ÷
è U< ø
EQUATION1431-SMALL V1 EN
U< = Uset
U = UVmeasured
k × 480
t = + 0.055
2.0
æ 32 × U < -U - 0.5 ö
ç ÷
è U < ø
EQUATION1432-SMALL V1 EN
U< = Uset
U = Umeasured
U< = Uset
U = Umeasured
80 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
U> = Uset
U = Umeasured
ABB 81
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
21. Ordering
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management.
Please refer to the available functions table for included application functions.
PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.
To obtain the complete ordering code, please combine code from the tables, as given in the example below.
Example code: REC670*1.2-A30-A02C16D02E01F01H04K01M01-B1X0-DC-KA-B-A6X0-ABFLURST-ABF-AD. Using the code of
each position #1-12 specified as REC670*1-2 2-3 3 3 3 3 3 3 3 3-4-5-6-7 7-8-9 9 9-10 10 10 10 10 10 10 10 10 10 10 10 10 10-11 11
11 11 11 11-12 12
# 1 - 2 - 3 - 4 - 5 6 - 7 - 8 - 9 -
REC670* - - - - - - - -
10 - 11 - 12
. -
Position
SOFTWARE #1 Notes and Rules
Version number
Version no 1.2
Selection for position #1.
82 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
ABB 83
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Mounting details with IP40 of protection from the front #6 Notes and Rules
No mounting kit included X
19" rack mounting kit for 1/2 x 19" case of 2xRHGS6 or RHGS12 A
19" rack mounting kit for 3/4 x 19" case or 3xRGHS6 B
19" rack mounting kit for 1/1 x 19" case C
Wall mounting kit D Note: Wall mounting not
recommended with
communication modules with
fibre connection (SLM, OEM,
LDCM)
Flush mounting kit E
Flush mounting kit + IP54 mounting seal F
Selection for position #6.
Connection type for Power supply, Input/output and Communication modules #7 Notes and Rules
Compression terminals K
Auxiliary power supply
24-60 VDC A
90-250 VDC B
Selection for position #7.
84 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
ABB 85
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
X41
X51
X61
X71
X81
X91
X101
X111
X121
X131
X141
X151
X161
8 in 3/4 rack with 1 TRM, 5 in 3/4
rack with 2 TRM, 14 in 1/1 rack
with 1 TRM and 11 in 1/1 rack
with 2 TRM
1/2 Case with 1 TRM █ █ █
3/4 Case with 1 TRM █ █ █ █ █ █ █ █
3/4 Case with 2 TRM █ █ █ █ █
1/1 Case with 1 TRM █ █ █ █ █ █ █ █ █ █ █ █ █ █
1/1 Case with 2 TRM █ █ █ █ █ █ █ █ █ █ █
No board in slot X X X X X X X X X X X X
Binary output module 24 output A A A A A A A A A A A A A Note: Maximum 4 (BOM+SOM
relays (BOM) +MIM) boards.
BIM 16 inputs, RL24-30 VDC, B B B B B B B B B B B B B
30 mA
BIM 16 inputs, RL48-60 VDC, C C C C C C C C C C C C C
30 mA
BIM 16 inputs, RL110-125 D D D D D D D D D D F F F
VDC, 30 mA
BIM 16 inputs, RL220-250 E E E E E E E E E E E E E
VDC, 30 mA
BIM 16 inputs, RL24-30 VDC, B B B B B B B B B B B B B
50 mA 1 1 1 1 1 1 1 1 1 1 1 1 1
BIM 16 inputs, RL48-60 VDC, C C C C C C C C C C C C C
50 mA 1 1 1 1 1 1 1 1 1 1 1 1 1
BIM 16 inputs, RL110-125 D D D D D D D D D D D D D
VDC, 50 mA 1 1 1 1 1 1 1 1 1 1 1 1 1
BIM 16 inputs, RL220-250 E E E E E E E E E E E E E
VDC, 50 mA 1 1 1 1 1 1 1 1 1 1 1 1 1
BIMp 16 inputs, RL24-30 VDC F F F F F F F F F F F F
for pulse counting
BIMp 16 inputs, RL48-60 VDC G G G G G G G G G G G G
for pulse counting
BIMp 16 inputs, RL110-125 H H H H H H H H H H H H
VDC for pulse counting
BIMp 16 inputs, RL220-250 K K K K K K K K K K K K
VDC for pulse counting
IOM 8 inputs, 10+2 output, L L L L L L L L L L L L
RL24-30 VDC
IOM 8 inputs, 10+2 output, M M M M M M M M M M M M
RL48-60 VDC
IOM 8 inputs, 10+2 output, N N N N N N N N N N N N
RL110-125 VDC
IOM 8 inputs, 10+2 output, P P P P P P P P P P P P
RL220-250 VDC
IOM 8 inputs, 10+2 output, L L L L L L L L L L L L
RL24-30 VDC, 50 mA 1 1 1 1 1 1 1 1 1 1 1 1
IOM 8 inputs, 10+2 output, M M M M M M M M M M M M
RL48-60 VDC, 50 mA 1 1 1 1 1 1 1 1 1 1 1 1
IOM 8 inputs, 10+2 output, N N N N N N N N N N N N
RL110-125 VDC, 50 mA 1 1 1 1 1 1 1 1 1 1 1 1
IOM 8 inputs, 10+2 output, P P P P P P P P P P P P
RL220-250 VDC, 50 mA 1 1 1 1 1 1 1 1 1 1 1 1
IOM with MOV 8 inputs, 10-2 U U U U U U U U U U U U
output, 24-30 VDC
86 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Remote end communication, DNP serial comm. #11 Notes and Rules
and time synchronization modules
Slot position (rear view)
X312
X313
X302
X303
X322
X323
Available slots in 1/2 case with 1 TRM █ █ █ █ Note: Max 1 LDCM in 1/2 case
Available slots in 3/4 & 1/1 case with 1 TRM █ █ █ █ Note: Max 2 LDCM in 3/4 and 1/1
case
Available slots in 3/4 & 1/1 case with 2 TRM slots █ █ █ █ █ █
No remote communication board included X X X X X X
Optical short range LDCM A A A A A A Note: Max 2 LDCM (same or
different type) can be selected
Optical medium range, LDCM 1310 nm B B B B B B
GPS Time Module, GTM S S S S
IRIG-B Time synchronization module, with PPS F
Galvanic RS485 communication module G G G G G G
Selection for position #11.
Serial communication unit for station communication #12 Notes and Rules
Slot position (rear view)
X301
X311
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management. Be aware that certain functions
can only be ordered in combination with other functions and that some functions require specific hardware selections.
Please refer to the available functions table for included application functions.
ABB 87
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Accessories
GPS antenna and mounting details
External interface converter from C37.94 to G703 Quantity: 1 2 1MRK 002 245-AA
External interface converter from C37.94 to G703.E1 Quantity: 1 2 1MRK 002 245-BA
Due to the high flexibility of our product and the The normally open "In test mode" contact 29-30
wide variety of applications possible the test on the RTXP test switches should be connected
switches needs to be selected for each specific to the input of the test function block to allow
application. activation of functions individually during testing.
Select your suitable test switch base on the Test switches type RTXP 24 is ordered
available contacts arrangements shown in the separately. Please refer to Section "Related
reference documentation. documents" for reference to corresponding
documents.
However our proposals for suitable variants are;
RHGS 6 Case or RHGS 12 Case with mounted
Single breaker/Single or Three Phase trip with RTXP 24 and the on/off switch for dc-supply are
internal neutral on current circuits (ordering ordered separately. Please refer to Section
number RK926 315-AK). "Related documents" for reference to
corresponding documents.
Single breaker/Single or Three Phase trip with
external neutral on current circuits (ordering
number RK926 315-AC).
88 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Protection cover
Protective cover for rear side of RHGS6, 6U, 1/4 x 19” Quantity: 1MRK 002 420-AE
Protective cover for rear side of terminal, 6U, 1/2 x 19” Quantity: 1MRK 002 420-AC
Protective cover for rear side of terminal, 6U, 3/4 x 19” Quantity: 1MRK 002 420-AB
Protective cover for rear side of terminal, 6U, 1/1 x 19” Quantity: 1MRK 002 420-AA
High impedance resistor unit 3-ph with resistor and voltage Quantity: RK795101-MB
dependent resistor for 20-100V operating voltage
High impedance resistor unit 1-ph with resistor and voltage 1 2 3
dependent resistor for 100-400V operating voltage Quantity: RK795101-CB
High impedance resistor unit 3-ph with resistor and voltage Quantity: RK795101-DC
dependent resistor for 100-400V operating voltage
Combiflex
Key switch for lock-out of settings via LCD-HMI Quantity: 1MRK 000 611-A
Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used.
Front connection cable between LCD-HMI and PC Quantity: 1MRK 001 665-CA
Manuals
Note: One (1) IED Connect CD containing user documentation (Operator’s manual, Technical reference
manual, Installation and commissioning manual, Application manual and Getting started guide),
Connectivity packages and LED label template is always included for each IED.
ABB 89
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2
Rule: Specify additional quantity of IED Connect CD requested. Quantity: 1MRK 002 290-AB
User documentation
Rule: Specify the number of printed manuals requested
Operator’s manual IEC Quantity: 1MRK 511 228-UEN
Reference information
For our reference and statistics we would be pleased to be provided with the following application data:
90 ABB
Bay control REC670 1MRK 511 232-BEN D
Pre-configured
Product version: 1.2