Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Hydro Generator
Abstract— The inrush currents related to the connection of III. ELECTRICAL INFRASTRUCTURE
generator devices is a typical matter of concern in situation with
long distribution lines or/and under low short circuit power A. Electrical Network
values at the PCC. This situation is usual for offshore devices. The EMEC tidal test facility is fed via a spur from a 33kV
In this case, it is analyzed the magnetization current of the hydro ring. The Newbigging substation provides the 11kV
generator developed by Magallanes Renewables supposed to be
connection for EMEC and for an adjacent 800kW wind
installed at the EMEC tidal test site. For this analysis, the
turbine via a 33:11kV 4/8MVA transformer, as shown in Fig.
surrounding network and the transformer has been modelled
and simulated under different conditions (short circuit power,
1.
remanent flux…). The results show that the voltage depression The minimum and maximum short circuit powers
related to that inrush current fulfills the regulation of the local (30MVA and 46.2MVA) at the 11kV point of coupling are
regulations. given by the local distribution network operator. The 11kV
underground feeder from Newbigging to Caldale substation
Keywords—Inrush current, transformer energization, tidal has only 50 m long, so it is not considered in the study.
energy
The Eday tidal test facility consists of eight test berths in a
I. INTRODUCTION range of different tidal conditions, each with a nominal
The main objective of this paper is to analyze the inrush capacity in excess of 1MVA at a working voltage of 11kV.
current for the transformer installed in the hydro generator The authorized export capacity of the grid connection is
developed by Magallanes Renewables. This report presents 4MW.
the analysis of the impact of this current on the voltage level Finally, the three phase transformer of Magallanes Project
at the point of common coupling placed at the EMEC (“The hydro generator has three secondary windings (2.1MVA
European Marine Energy Centre”) [1] facility in the Eday 11kV/690V/690V/400V).
Island (Scotland). The results of this study will be used to
analyze the compliance of the hydro generator (“Magallanes Eday
Substation
Project”) related to the under-voltage limits according to the Subsea
33 kV
Subsea
Overhead Line
regulation stablished by the network operator. Cable to Cable to
Westray Sanday
LA
RSC
ͳǤʹ
ȋȌ
ͳ
+
ͲǤͺ
ͲǤ
E
ͲǤͶ
Fig. 3. Simplified model for the transformer inrush current
ͲǤʹ
Ͳ C. Transient Model for the Transformer
Ͳ ͲǤͷ ͳ ͳǤͷ ʹ ʹǤͷ A transient model for the transformer has been developed
ȋΨȌ in order to obtain the waveforms of electrical variables during
Fig. 2. Saturation curve (given by ABB and fitted) and asymptote the process of energization. In this case, the transformer has
been modeled using a non-linear model where saturation is
B. Simplified model for the inrush current calculation simulated introducing a current source in one of the windings.
In order to obtain a preliminary estimation of the inrush The value of this current is obtained from the magnetic flux
currents, it is used a simplified model of the transformer which which is firstly calculated from the voltage integral using the
consists in: a series circuit with a resistance that represents the linearized and simplified saturation curve. This transformer
equivalent electrical resistance of the windings and a model is available in the PSCAD program which is used to
reactance whose value is the air core reactance, as shown in simulate the transient behavior of electrical systems [5].
Fig. 3 [6]. In this model, the air core inductance simulates the
V. RESULTS
behavior of the transformer winding when the core is saturated
whose value is much lower than the unsaturated magnetizing Firstly, the transformer in connected using a zero
inductance. The transition between the saturated and impedance voltage source in order to obtain the inrush current
unsaturated state is simulated by means of a switch which is with different models, the simplified model and the transient
closed when the flux reaches the saturation value. As a model, so their results can be compared and validated in a
consequence, the analytical equation for the peak value of the certain way. Next, the simulation is performed including the
inrush current is obtained [6]: whole electrical network at EMEC with the objective of
obtaining both the inrush current and the under-voltage value
ξʹܧ provoked by that current.
ܫǡ௫ ൌ ͳ
ଶ
ඥܴ௦ ߱ ଶ ܮଶ (3) All simulations have been carried out considering the
ିோ ഏ
െ ݁ ఠ ൫ మ షഗషഇ൯ ݊݅ݏሺߠ െ ߰ሻ൨ worst connection conditions that means both, zero voltage in
one phase and the maximum residual flux at the moment of
Where: transformer energization.
• Approximated model with the parameters shown in The wave form of the inrush current for the different
Table 7. models three-phase and monophasic can be seen in Fig. 5.
windings transformer has been modeled as a DY
three-phase transformer using the HV winding
parameters (winding 1) and one of the LV winding
(690V) parameters (winding 2). The parameters for
this model can be seen in Table 8.
• Transient single-phase equivalent model modeled
using the HV winding (winding 1) and the one of the
LV winding (winding 2) parameters.
Sbase = 4 MVA ͶǤͲͲ
Fig. 6. Main parameters and scheme for the complete model ͵ǤͷͲ
Fig. 8. Peak maximum value for different values of shortcircuit power and
X/R ratio at the 11 kV level (marked values are those given by EMEC).
ͲǤͻ
ͲǤͻͷ
ͲǤͻ͵
ͲǤͻͳ ȀαʹǤʹ
ȀαͳǤͻ
ͲǤͺͻ EMEC
Datos
αͶǤʹǡȀαʹǤʹ
ͲǤͺ
α͵ͷǡȀαͳǤͻ
ͲǤͺͷ
Ͳ ʹͲ ͶͲ Ͳ ͺͲ ͳͲͲ
Fig. 7. Voltage and current during the energization of the transformer
̷ͳͳȋȌ
(Network shortcircuit power 46.2 MVA).
Fig. 9. Minimum voltage value for different values of shortcircuit power and
X/R ratio at the 11 kV level (marked values are those given by EMEC).
As the short circuit power at the point of common coupling
at 11kV is the parameter whose variation has the greatest ͳʹΨ
influence on the inrush current, several simulations have been
carried out to determine this dependence with the following ͳͲΨ ȀαʹǤʹ
Ψ
values: ȀαͳǤͻ
ͺΨ
αͶǤʹǡȀαʹǤʹ
• Maximum peak value of the inrush current in phase
α͵ͷǡȀαͳǤͻ
Ψ
(as shown in Fig. 8)
ͶΨ
• Minimum value of the RMS voltage between phases
at the point of common coupling in the EMEC ʹΨ
substation (as shown in Fig. 9)
ͲΨ
• Maximum voltage drop at the point of common Ͳ ʹͲ ͶͲ Ͳ ͺͲ ͳͲͲ
coupling in the EMEC substation (as shown in Fig.
̷ͳͳȋȌ
10). Fig. 10. Maximum voltage drop value for different values of shortcircuit
power and X/R ratio at the 11 kV level (marked values are those given by
The inrush current peak value has a maximum value from EMEC).
3.4 to 3.7 times the rated current of the transformer when the
EMEC network conditions are taken into account. C. Effect of remanent flux
Consequently, the voltage depression at the point of common In this section it is analyzed the influence of the remanent
coupling varies from 4% to 5.4% of the nominal voltage. magnetization flux supposing the worst short circuit
By analyzing the results it can be concluded that the conditions provided by the Distribution Network Operator. A
voltage depression value is higher than the 3% of the nominal shortcircuit power equal to 30.3 MVA at 11kV level has been
voltage required in the Engineering Recommendation P28 for considered for this purpose. As a result, the maximum values
transients with a maximum starting frequency of 750 seconds. for the inrush current peak and voltage depression have been
This value is below the limits for cases of infrequent starting obtained, as shown in Fig. 11 and Fig. 12.
which is rated at 6% of the nominal voltage. In order to get
starting frequency of 750 seconds. This value is below
the limits for cases of very infrequent starting which is
rated at 6% of the nominal voltage.
• To achieve voltage depressions lower than 3% a
shortcircuit power of at least 60MVA would be
necessary.
• When the remanent flux is near to zero, the voltage
depression values are lower than 3% for a shortcircuit
power equal to 30.3MVA. According to this, the use
of pre-insertion resistors of pre-magnetization would
be very useful in order to reduce inrush currents.
Fig. 11. Maximum peak current for different remanent flux values (Scc = 30 ACKNOWLEDGMENT
MVA @11kV)
The authors would like to thank the personnel of EMEC
ͺǤͲΨ for their contribution and for their accessibility to the technical
ǤͲΨ
data of the test site.
ǤͲΨ REFERENCES
Ψ
ͷǤͲΨ [1] EMEC, “The European Marine Energy Centre LTD (EMEC).”
[Online]. Available: http://www.emec.org.uk/. [Accessed: 14-Apr-2016].
ͶǤͲΨ
[2] System Utilisation Consultancy Group, “Engineering
͵ǤͲΨ Recommendation P28: Planning Limits for Voltage Fluctuations Caused by
ʹǤͲΨ Industrial, Commercial and Domestic Equipment in the United Kingdom,”
Electricity Council Engineering Management Conference. 1989.
ͳǤͲΨ
[3] M. Salimi, A. M. Gole, and R. P. Jayasinghe, “Improvement of
ͲǤͲΨ Transformer Saturation Modeling for Electromagnetic Transient Programs,”
ͲǤͲ ͲǤʹ ͲǤͶ ͲǤ ͲǤͺ in International Conference on Power Systems Transients, 2013, pp. 1–6.
ȋȌ [4] Manitoba HVDC Research Centre Inc., “Applications of
Fig. 12. Maximum voltage drop for different remanent flux values (Scc = 30 PSCAD/EMTDC.” Manitoba.
MVA @11kV) [5] Manitoba-HVDC Research Centre, “USER’S GUIDE: EMTDC
(v. 4.7).” Manitoba, pp. 1–248, 2010.
Considering the hypothesis above, in order to keep the [6] J. E. HOLCOMB, “Distribution Transformer Magnetizing Inrush
voltage depression lower than the P28 requirements, the Current,” Trans. Amer. Inst. Elect. Eng. (Power App. Syst.), vol. 80, no. 3,
pp. 697–702, 1961.
remanent flux should be nearly null when energizing the
[7] N. Chiesa and H. K. Høidalen, “Novel Approach for Reducing
transformer. Supposing this, the maximum peak value of the Transformer Inrush Currents: Laboratory Measurements, Analytical
inrush current would be 1.65 times the nominal current and Interpretation and Simulation Studies,” IEEE Trans. Power Deliv., vol. 25,
the voltage depression would remain lower than the 3%. no. 4, pp. 2609–2616, 2010.
VI. CONCLUSIONS
The aim of this paper is to analyze the under-voltage
values at the point of common coupling (11kV level of the
EMEC substation) related to the inrush current of the
transformer to be installed in the Magallanes Project hydro
generator. The main results obtained in the simulations are:
• The maximum peak value of the inrush current when
energizing the transformer and supposing the worst
conditions, i.e. a zero impedance power source, is
lower than 5 times the rated current.
• The maximum peak value of the inrush current
supposing it being installed at the EMEC facility
would be between 3.4 and 3.7 times the rated current.
• The voltage depression at the point of common
coupling would be between the 4% and the 5.4% of the
nominal voltage.
• The voltage depression value is higher than the 3% of
the nominal voltage required in the Engineering
Recommendation P28 for transients with a maximum