Sei sulla pagina 1di 2

-48V / 35A API-6035

Features:
Wide input voltage range
Active power factor correction
High power factor and efficiency
N + 1 Redundancy
Zero Current Switching (ZCS) technology
Adjustable DC output
Floating and equalizing charging mode
Hot swappable
Current sharing of up to 60 units
Remote monitoring and control via RS485
Comprehensive fault protection and detection
schemes
OVP, OCL, and OTP
Low audio noise
Protections: Regulated fan speed
Auto recovery
Input Transient Voltage Protection:
MOV is installed to protect AC voltage
transient and spike.
Connector Pin Assignment:
AC Mains Low:
Rectifiers automatically shut down when input Pin house on rectifier Pin Function
AMP 211149-1
voltage falls below 90Vac and auto recovery 1 Output 0Vdc
when mains have recovered. 2 Output 0Vdc
AC Mains High: 
3 Output 0Vdc
Rectifiers automatically shut down when input 
+

 4 Output -48Vdc



voltage exceeds 300Vac and automatically turn




5 Output -48Vdc

'

on when mains have recovered. 


6 Output -48Vcd


Over Current Limit (OCL):



7 Output 0Vdc





8 Output -48Vdc
! '

Output current adjustable from 7A to 38.5A, LED 

illuminates when current limit exceeds the 9 RS485 TXD-


preset value. 10 RS485 RXD-
11 RS485 RXD+
Over Temperature Protection (OTP):
Rectifiers become inhibited when internal 12
      
RS485 TXD+
temperature exceeds 90 5 safety limit and 13
       -48V Battery
will automatically turn back on when internal       !14 Share Bus
temperature falls below 70 5 . ""# $# "    %

(   )  '(*
15 & & '& 
EMI Frame Ground (FG)
16 -48VS
Over Voltage Protection (OVP):      '+

Rectifiers will instantly shut down when output 17


""# $# "   ! % +&  % 
RTN2
voltage exceeds 60Vdc 0.5Vdc
(   )  (* % '(*
18 Chassis Frame Ground (FG)
19
Low Voltage Alarm: 20 ALM
If output voltage is lower than 48Vdc, LED will
21 AC OK
illuminate.
22 ALM / AC OK COM
High Voltage Alarm: 23
If output voltage is higher than 58Vdc, LED will 24 AC in Live
illuminate. 25 AC in Neutral

i. All illustrations are for reference only and specifications subject to change without notice.

7 ii. The rated current of MCBs and fuses is changeable.


API-6035, -48V / 35A

Rectifiers
Specifications:
AC Input DC Output
Nominal Voltage 220Vac Voltage -54Vdc (Nominal)
Operating Voltage 154 ~ 286Vac FL/EQ 40 ~ 60Vdc (adjustable)
Frequency Range 45 ~ 65 Hz Rated Current 35A
Current 10A @220Vac; 54Vdc; full load Power (max.) 2,100W
16A @154Vac; 60Vdc; full load Soft Start >3 second
Efficiency 89% (typical) @220Vac; 54Vdc Voltage Regulation
Power Factor >0.98 @220Vac; 54Vdc; full load Line effect 0.1%
EMI EN55022 Class B Load effect 0.5%
Current Limit 7.0 ~ 38.5A (adjustable)
Environmental
Overload Capability 110% (38.5A)
Temperature
Current Share 1%
Operating -5 ~ 45
Wide Band Noise
Storage -40 ~ 80
(10K~100MHz) 5mV
Humidity 10% to 90% (non-condensing)
Narrow Band Noise
Altitude < 3000 meter
(3.4K~150KHz) 5mV
Cooling Internal fan with thermal control
(150K~200KHz) 3mV
MTBF > 300,000 hours
(200K~500KHz) 2mV
Safety (500K~30MHz) 1mV
UL, cUL Psophomatrics < 2mV
CE Audible Noise < 45dBA (1 meter)
Hi-pot:
Mechanical
I/P to O/P 1500Vac for 1 min.
Weight 7.0Kg
I/P to FG 1500Vac for 1 min.
Dimension Refer to outline drawing
O/P to FG 500Vac for 1 min.
(Leakage current<30mA) Communication
Earth Continuity Interface RS485
Safety earth to FG 25A for 1 min.
(earth resistance < 0.1 Ohm)

Outline Drawing:
390.6
380.8
176.8 353.6 129.6
O.K.

F/W : API-6035
DC OUTPUT : 40-60 VDC 35A
AC INPUT : 200-240V ~ ,50/60Hz ,15A
SERIAL NO. : XXXXXXXX
DATE : BYYWW
API-6035

WARNING LABEL
S TAT U S D I S P L AY

DC OUTPUT

141.6 49.6 138.6


REV : X.XX
O
I

REV : X
API-6035 Rectifier

AC INPUT

44.3
O
I

147.4

160.0

Unit: mm
Scale: 1:5

e-mail: headquarter@acbel.com
Released: 11-20-'02
8