FDAS Cause and Effect Matrix

One Roxas Triangle

Input Output
Item Initiating Device Location Fire Alarm Control Panel Field Devices

- Alarm LED "On".


- FACP buzzer will sound.
1 Smoke/Heat Detectors All Floors (Residential Units) - Buzzer in the unit will activate
- FACP shall display the Classification, Location, Date,
Time and Address number of the Smoke/Heat Detectors.

- Strobe Horn/Bell will activate. (2 floors above, floor on alarm, 1


- Alarm LED "On".
floor below)
All Floors (Common areas and Residential Units - FACP buzzer will sound. - Emergency Voice Alarm will activate.
2 Smoke/Heat Detectors
Elevator Lobby)
- FACP shall display the Classification, Location, Date,
- Pressurization Fan and Elevator Homing will activate.
Time and Address number of the Smoke/Heat Detectors.

- Strobe Horn/Bell will activate. (2 floors above, floor on alarm, 1


- Alarm LED "On".
floor below)
All Floors (Common areas and Residential Units - FACP buzzer will sound. - Emergency Voice Alarm will activate.
3 Manual Push Station
Elevator Lobby)
- FACP shall display the Classification, Location, Date,
- Pressurization Fan and Elevator Homing will activate.
Time and Address number of the Smoke/Heat Detectors.

- Supervisory LED "On".

Waterflow Switch and - FACP buzzer will sound.


4 All Floors Monitoring Only
Supervisory Switch Interfacing - FACP shall display the Classification, Location, Date,
Time and Address number of the Waterflow Switch and
Supervisory Switch Interfacing.
- Strobe Horn/Bell will activate on all floors.
- Trouble "On".
- Emergency Voice Alarm will activate.

5 Drill Button (General Alarm) FACP - Pressurization Fan and Elevator Homing will activate.

- FACP buzzer will sound. - Elevator Homing will activate