HOUSE PROJECT
1.1.1 Each Main LT Panel with Capacitor - as specified 1 425,000 18,000 443,000 443,000
and shown on the drawings complete
as per drawing L261 - E - 502
2.1.1 Each Power Distribution Board for GYM area 1 11,500 1,400 12,900 12,900
Incomer
I) 1# 63A TPN ELMCB(30 mA)
Outgoing :
i) 8 x 3 = 16/20A SP MCB
Outgoing :
iii) 6 x 3# 10A SP MCB
2.1.3 Each 63 A TPN MCB WITH Enclouser 6 4,300 500 4,800 28,800
2.1.4 Each 40 A TPN MCB WITH Enclouser 3 4800 500 5,300 15,900
3 CABLING
4 Cable Termination
5.1 Supply & ITC of Conduit wiring for lights, fans, socket outlets
consisting of:
f) NOTE:-
5.1.1 Pt. Primary Points (From DB):- 10 1100 220 1,320 13,200
The final subcircuit wiring commencing from the distribution
board feeder to the first light point (With 2R X 2.5Sq.mm and
1R X 1.5Sq.mm and 25mm FR PVC conduits).
5.1.2 Pt. Secondary Points (From DB):- 25 760 115 875 21,875
1-way secondary light point from above primary point,
subsequent points controlled by same DB feeder switch (With
2R X 1.5Sq.mm and 1R X 1.5Sq.mm and 20mm FR PVC
conduits).
5.1.3 Pt. Primary Points (From Switch Box):- 30 1120 220 1,340 40,200
The final subcircuit wiring commencing from the distribution
board feeder to the first light point (With 2R X 2.5Sq.mm and
1R X 1.5Sq.mm and 20/25mm FR PVC rigid conduits) and
from there to the light point complete with switch drop (With
2R X 1.5Sq.mm and 1R X 1.5Sq.mm and 20mm FR PVC
conduits).
5.1.4 Pt. Secondary Points (From Switch Box):- 31 760 115 875 27,125
1-way secondary light point from above primary point,
subsequent points controlled by same switch (With 2R X
1.5Sq.mm and 1R X 1.5Sq.mm and 20/25mm FR PVC
conduits).
5.1.6 Pt. Exhaust fan point with 5A socket near fan controlled by 6A
4
SP switch 1.5 sq mm 1450 260 1,710 6,840
located on lighting switch board(With 2Rx1.5Sq.mm and
20mm conduits)
5.1.7 Pt. 20A Socket with 20A SP neon indicator Switch for AC spilt
8
unit IDU 3050 330 3,380 27,040
(with 2Rx4Sq.mm+1Rx1.5Sq.mm and 25mm conduit)
5.1.9 Pt. 16A Power Plug Point 16 1500 260 1,760 28,160
(2Rx2.5Sq.mm+1Rx1.5Sq.mm and 20mm conduit)
7 LIGHT FIXTURES
b) Earthing of fittings
7.1.1 Each 1 x 28w Fluroscent light fitting similar 10 2,580 80 2,660 26,600
to WIPRO make WIF 21128 APF or
equivalent (Surface mounted / suspended)
7.1.2 Each 1 x 18w Recess mounted CFL down 45 1,500 80 1,580 71,100
lighter similar to WIPRO make
WCP 32118SGW
7.1.3 Each 2 x 18w Recess mounted CFL down 20 1,700 100 1,800 36,000
lighter similar to WIPRO make
WCP 32218SGW
7.1.4 Each 1 x 18w wall mounted light similar to 4 2,580 80 2,660 10,640
8 EARTHING
a) Fixing accessories.
b) Corrosion protection of
buried conductors with
bituminous coating and
covered with PVC tapes.
8.2.2 m 25 x 4 mm Cu R.O
8.2.3 m 25 x 3 mm Cu R.O
8.2.4 m 20 x 6 mm Cu R.O
9.1.2 Each Supply and installation of First aid 4 1,050 175 1,225 4,900
box & framed first aid chart in
LT panel room
9.1.3 Each Supply and instalaltion of shock 4 875 175 1,050 4,200
treatment chart in LT room
9.1.4 Each Supply & Installation of 440V 10 520 135 655 6,550
Danger boards