TRAINING
FORMULAS
&
CALCULATIONS
Chilled water tons
Discharge Temperature
– Condenser Saturation Temperature
DSH =
D.S.H.
To Find Suction Superheat
p
Suction Temperature
– Evaporator Saturation Temperature
S.S.H. =
To Find The Condenser Approach
1
1. CHILLED WATER FT OF HEAD ON THE YORK CHILLER IS 27FT.
27FT WHAT IS THE DESIGN CONVERTED
TO PSID?
3. CAN ACTUAL CONDENSER WATER FLOW BE CALCULATED WITH OUT HAVING A FLOW METER
INSTALLED? CALCULATE THE ACTUAL CONDENSER GPM’s IF THE
ACTUAL PRESSURE DROP ACROSS THE CONDENSER IS 9 PSID? WHY
MIGHT THIS FORMULA BE HELPFUL?
4. IF THE ACTUAL CHILLED WATER FLOW IS 6000 GPM’s, AND THE TEMPERATURE D.T. IS 22F, WHAT
IS THE ACTUAL CHILLED WATER TONNAGE? IS THIS DESIGN
TONNAGE? CAN THE SAME DESIGN TONNAGE BE ACHIVED IF THE GPM’s ARE
HIGHER THAN DESIGN?
5. IF THE ACTUAL CONDENSER WATER P.D. IS HIGHER THAN DESIGN, BY 10 PSID WHAT IS THE
ACTUAL WATER DROP IN PSID? SHOULD THE ACTUAL CONDENSER WATER
FLOW (GPM’s) BE HIGHER THAN THE DESIGN THROUGH THE CONDENSER AND CORESSPOND TO
THE ACTUAL
C P.D. ? WHAT COULD
CO BE WRONG
O G IF THE FLOW
O DOES
O S NOTO
CORRESPOND AND IS LESS?
6. IF THE CONDENSOR SYSTEM ACTUAL DISCHARGE PRESSURE CONVERTED TO TEMPERATURE IS 101F,
AND THE ACTUAL DISCHARGE TEMPERATURE IS 120F, WHAT IS THE DISCHARGE SUPERHEAT?
7. IF THE EVAPORATOR SYSTEM ACTUAL SUCTION PRESSURE CONVERTED TO TEMPERATURE IS 34F, AND
THE ACTUAL SUCTION TEMPERATURE IS 33F, WHAT IS THE SUCTION SUPERHEAT?
8
8. THE CHILLER IS OPERATING AT AN ACTUAL CONDENSER PRESSURE OF 151PSIA,
151PSIA IS THIS ABOVE
DESIGN? IF THE WATER PRESSURE DROP ACROSS THE CONDENSER IS AT
DESIGN AND THE GPM’s IS AT DESIGN, WHAT COULD BE WRONG?
9
9. IN QUESTION 8 ABOVE IF THE APPROACH ON THE CONDENSER IS 6F AND THE DIFFERENCE BETWEEN
CONDENSER SATURATION TEMPERATURE AND CONDENSER PRESSURE CONVERTED TO
TEMPERATURE IS LESS THAN 2F, WHAT COULD BE WRONG?
10. IN QUESTION 8 ABOVE IF THE DIFFERENCE BETWEEN CONDENSER SATURATION TEMPERATURE AND
CONDENSER PRESSURE CONVERTED TO TEMPERATURE IS 5F, AND THE CONDENSER APPROACH IS .7F,
WHAT COULD BE WRONG?
11. WHEN SHOULD THE ACTUAL REFRIGERANT CHARGE FOR THE YORK CHILLERS BE CHECKED?
12. TO TROUBLE SHOOT MOST CONDITIONS AT WHAT PARAMETERS SHOULD THE CHILLER BE OPERATING?