Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Objectives
Introduction
The transformer is a device that transfers electrical energy from one electrical circuit to
another electrical circuit through the medium of magnetic field and without the change of
frequency. The electrical circuit that receives energy from the source is called as primary
winding and the other circuit that delivers electrical energy to the load is called as Secondary
winding.
The primary and secondary windings of a transformer are coupled magnetically that is the
electrical energy input to the transformer is first converted to magnetic energy and then this
energy is again converted to electrical energy by the secondary winding to be delivered to
load.
Transformer does not have any moving parts so out of all electrical machines it has the
highest efficiency and requires least amount of maintenance. Usually the transformer steps
up the voltage output of alternator before transmission so that at high voltage transmission
the losses are less.
In electronic and control circuits. Transformers are used for impedance matching for
maximum power transfer from source to the load. Pulse Transformers find wide application
in radar, television and digital computers.
Magnetic Circuits
Maxwell’s equations for magnetic fields are
H.dl I.da
C S
B.da 0
S
To find general solution for H& B is difficult so we tend to reduce a complex three
dimensional problem to an equivalent circuit.
of material is much higher than 0 , so flux is almost entirely confined to the core.
The source of magnetic field is ampere-turn product Ni, in magnetic circuit terminology
Ni is magneto-motive force (MMF)
Flux, B.da
S
Also BC CHC
C Ni
C
AC lC
l
Ni C C
A C
F R
lc
R Reluctance of transformer core
A c
Flux in core
F=MMF
Sometimes, energy conversion device like generators or motors may have air gap
between stator & rotor, when air gap is much smaller than the dimensions of adjacent core
faces, magnetic flux will follow the path defined by air gap & core.
Bc
Ac
Bg
Ag
F Hclc Hgg
Where g is air gap length
Bc Bg l g
F lc g c
c 0 c A c 0 A g
lc g
Rc Rg
c A c 0 A g
F Rc Rg
F R tot
So, introduction of air gap increases the reluctance in the path of flux. So, to maintain same
flux machines draw more amount of magnetizing current.
Magnetic Materials
Magnetic materials are those materials which get magnetized in the presence of magnetic
field. Even Non Magnetic materials get magnetized in presence of magnetic field but they
exhibit weak magnetization.
1) Diamagnetic
2) Paramagnetic
3) Ferromagnetic
Diamagnetic materials
It is a weak form of magnetism that is non-persistent and persists only when an external
field is applied. It is induced by a change in the orbital motor of electrons due to an applied
magnetic field.
The magnitude of induced magnetic moment is extremely small and in a direction
opposite to that of applied field.
Diamagnetic materials are repelled by magnetic field
Some of the materials that exhibit diamagnetism are Cu, Au, Ge, Si, Diamond, Al2O3 ,NaCl
etc.
Paramagnetic Materials
Such materials which when placed in a magnetic field acquire a weak magnetization in the
same direction as applied field.
In some materials, permanent magnetic dipole moments of the atoms or ions are acted
upon individually, with no mutual interaction upon them, (randomly distributed), this effect is
called Paramagnetism.
The total dipole moment in this material & hence magnetization is zero, in absence of
external field.
In the presence of magnetic field, dipoles align in the direction of field.
But in absence of field due to thermal agitation dipoles are randomly oriented.
Paramagnetic materials are attracted by external field so it moves from low intensity to
high intensity of the field.
Ferromagnetic Materials
In a Transformer the primary and secondary windings are wound around the core of a
transformer. Core is a magnetic material which allows the flow of magnetic flux lines to link
both primary and secondary windings.
There are certain properties that the core material must satisfy:
1. Core should have low reluctance and high permeability to the flow of magnetic flux.
2. Core is generally made of Silicon steel
Features of Silicon Steel:
Ferrous Magnetic Material
Low reluctance and high permeability
Low hysteresis coefficient (x= 1.6)
P k B1.6 f
h n m
Laminations
The magnetic core is a stack of thin Silicon Steel laminations about 0.35mm thick for 50 Hz
Transformers. To reduce eddy current losses, laminations are electrically isolated from each
other.
The materials used for electrical isolation are:
1. China clay
2. Japan Varnish
3. Impregnated paper
4. Oxide paints
For a laminated core we define the Stacking Factor as:
Net CS Area
Stacking Factor = Iron factor = <1
Gross CS Area
Where,
Gross cross section area (Ag): Cross Sectional Area of Magnetic material and Insulation
Net cross section area (An): Cross Sectional Area of Magnetic material
Laminations must be tightly riveted because if there is a thin air gap between laminations
then it increases reluctance of magnetic path and hence increases magnetizing current for
same flux.
NI (cons tant) R
Magneto-striction
Tendency of any magnetic material due to which changes in dimensions of magnetic
materials take place whenever flux is flowing through it.
If laminations are not properly riveted then there may be vibrations due to this phenomenon
and if frequency of vibrations fails in audible range. We can hear this and it will then produce
a humming sound called as Magnetic Hum.
Core is generally made of Ferromagnetic Material like Silicon Steel but for high frequency
Transformers core is made of Ferrimagnetic materials or Ferrites because at high frequencies
eddy current losses are high and to reduce losses we need material with high resistivity
called as Ferrites.
Here the two windings are wound on opposite limbs of the core. Hence, the core is
surrounded on both sides by the winding.
The magnetic circuit of the Transformer has reluctances
connected in series as shown below:
Here the two windings are wound on same limb i.e. middle limb of the core. Hence, the
windings are surrounded on both sides by the core.
The magnetic circuit of the Transformer has reluctances connected in parallel as shown
below:
Placement of Windings
There are two types of windings generally employed for Transformers. The concentric coils
are used for core type of Transformers. Interleaved or Sandwiched windings are used for
Shell Type Transformers.
Interleaved windings are preferred to reduce magnetic leakage flux thereby increasing
coefficient of coupling between the windings. In Interleaved windings the Low Voltage
winding is usually placed near to the core and High Voltage winding outside the Low
Voltage winding. Insulation is provided between two windings and between core and
winding.
The amount of insulation required for transformer between core and winding is reduced.
It also reduces the amount of Cu required for windings
If HV winding is outer to low voltage, then HV is accessible to provide tapings for voltage
control purpose.
The directions of flux in HV and LV are of Opposing as per Lenz Law because induced emf
must oppose the cause of Induction.
If HV and LV are placed on separate limbs, then they should carry ‘I’ in same direction to
satisfy Lenz’s law
Ideal Transformer
A Practical Transformer is one which does not make the following assumptions. So, in the
next section we remove these assumptions one by one.
The current responsible for setting up the working flux in a transformer is called as
Magnetizing Current. This current is drawn by primary winding from the source and it also
exists even under no-load conditions.
iµ = Magnetizing current
iµ= Iµ sin ωt
At t
E1max N1m
E1max N1m
E1
2 2
N1m 2f
4.44N1mf
2
E1 4.44N1BmAnf
Similarly,
e2 N2 m sin t
2
So, emf induced in secondary winding also lags flux by 90
and is in phase with primary induced emf.
E2 4.44N2BmAnf
Where, E2 = RMS Value of emf induced in secondary winding
N2 = Number of Turns in Secondary Winding
Observations
E1 E2
4.44Bm Anf
N1 N2
E2 N2
K Transformation Ratio
E1 N1
Turns ratio N1 :N2 or E1 : E2
V1
To keep Bmax as constant, keep Cons tant
f
By keeping V as constant and if the frequency of operation is reduced, then the maximum
value of the flux density is increased which drives transformers into saturation magnetizing
component of current drawn by primary winding is increased sharply.
For a given KVA rating and for given maximum value of B of core, more the designed
frequency lesser is size and weight of transformers.
For a given KVA rating and for a given design frequency superior the magnetic material of
core, lesser will be size and weight of core.
Solved Examples
Problem: A magnetic circuit with a cross sectional area of 20cm2 is to be operated at 50Hz
from a 120 V (rms) supply the no of turn required to achieve the peak magnetic flux density
(B) 1.8T in the core is?
Solution: The induced emf in a transformer is given by,
E 4.44Nfm ;B 1.8 T
E
N
4.44Nfm
120
N 150
4.44 50 1.8 20 107
Transformer with Iron Losses
Iron Losses in a Transformer consist of Hysteresis Loss and Eddy Current Loss. The losses
consume active power which must be supplied by the source in terms of active component
of current which has same phase as Voltage so that reactive power for loss component is
zero.
Magnetizing component of No-Load Current is around 4-6% of Full Load Current and lags
applied voltage by 900.
Core Loss Component is 1-2% of Full Load Current and is in phase with the applied voltage.
o 70 to 75
cos 0 0.2lag
Transformer has poor No load PF because I Iw
Power consumed by a transformer at No-load is used to supply iron losses [if primary
winding resistance is considered, small amount of NL primary Cu loss also takes place].
No- load equivalent circuit of the Transformer looks like as shown below:
opposition to primary flux (in accordance to Lenz Law). This causes an addition current to
induce in Primary Winding to cancel the secondary MMF so that flux can be kept constant.
Flux on the transformer core is always equal to NL flux irrespective of load across secondary
terminals. So the Transformer can be treated as constant flux device
1 ' 2
N1I1 ' N2I2
Load component of primary MMF = Secondary MMF
N2 I1 ' E
K 2 = Transformation ratio
N1 I2 E1
I1
I1 ' KI2 ; K
I2
E1I1 ' E2I2
Due to winding resistance there is voltage drop between primary applied voltage and
induced EMF and also secondary induced EMF and Load Voltage.
Also, due to winding resistance there is power loss in both primary as well as secondary
windings called as Copper Loss as the windings are made of Copper.
Assuming R1 is the Primary Winding Resistance and R 2 is the Secondary Winding Resistance.
V1 E1 I1 R1 ; E2 V2 I2 R2
Total Cu loss = I12R1 I22 R 2
Cu loss before transfer must be equal to Cu loss after transferring resistance from one
winding to another winding that is copper loss must be unaffected by referring the entire
resistance in one winding or the other.
R 2 ' = equivalent of secondary resistance with respect to primary winding
Leakage flux is a flux which links either primary or secondary but not both. It does not
help in transferring power from primary to secondary so it’s is undesirable.
Leakage flux depends on respective load currents.
The leakage flux at primary and secondary winding are in phase with load currents.
The EMF due to magnetic leakage flux can be taken in to account by assuming additional
voltage components in the resistance voltage sources. Such that additional voltage
components is used to compensate EMF due to magnetic leakage flux.
The additional voltage components should lead the resistive load by 90 , it can be taken
into account by assuming imaginary reactance in series with primary and secondary
windings.
V1 E1 j I1 X1 To compensate Ex1
E2 V2 j I2 X2 To compensate E x2
If resistances are considered
V1 E1 I1 R1 j I1 X1
E1 I1 (R1 jX1) E1 I1Z1
E2 V2 jI2 Z 2
pu reactance drop should remain same while transferring from primary to secondary.
I2 X 2 I1X 2 '
E2 E1
X2
X2 '
k2
E1 1 I2
E2 k I1
X 2,s
X 2,p
k2
X1,s X1,p k 2
X2
Equivalent Reactance on Primary Side = X01 X1 X2 ' X1
k2
Equivalent Reactance on Secondary Side = X 02 X1 ' X 2 X1k 2 X 2
Phasor Diagram
Solved Examples
Problem: A 5KV/400V 75kVA 1 Transformer has a series reactance of 0.12pu the reactor
in ohm referred to low voltage and high voltage side are?
V 5 10
2 2
3
base,p
Solution: Zbase,p 333.33
Sbase 75 103
Z Zpu Zbase 0.12 333.33 40
V 400
2 2
base,S
Zbase,s 2.133
Sbase 75 103
Z Zpu Zbase 0.12 2.133 0.256
Problem: A Single Phase Transformer takes a no load current of 1.3A when HV side is kept
open if the iron loss component of no load current is 0.5A. Find magnetizing component of
no load current.
Solution: No-Load Current in a Transformer is given by,
I0 I2 I2w
I 1.2 A
Irated 2.174kA
V2 23000 V
I2 2.17400 kA
E2 V2 I2 Z 2 230 2.174 103 2 j6 103 234.73.10 V
E1 N1
10 E1 10E2 2347.13.10 V
E2 N2
Losses in a Transformer
Copper Loss
The losses that occur in primary and secondary windings of Transformer due to winding
resistances are called as Copper Losses.
Total copper losses = I12R1 I22R 2 = I12R01 I22 R02
Full load Cu losses = I1,FL
2
R01 I2,FL
2
R02
The losses that occur in Transformer core due to alternating flux set up by primary winding is
called as Iron Loss. It has two components:
Hysteresis loss
Eddy Current Loss
Hysteresis Loss
In the Ferromagnetic material, magnetic dipoles retain their magnetization even after the
removal of Magnetic Field. But the flux or Magnetic Field developed in Transformer core is
alternating in nature so the magnetization of dipoles reverses periodically. This requires
energy being supplied to the material resulting in Hysteresis Loss.
The Hysteresis curve for a magnetic material looks like as shown below:
The value of magnetic flux density can have two different values for same value of magnetic
field intensity depending upon whether magnetic field intensity is increasing or decreasing.
The area under hysteresis loop gives hysteresis loss per cycle.
Total hysteresis loss for frequency f = Area of hysteresis loop per cycle f
Steinmetz formula
Hysteresis Loss is given by Steinmetz formula:
Wh Bmax
x
fV
x= Steinmetz exponent
= Steinmetz constant
f= frequency of magnetic reversal
V= volume of core material
V
Case 1: = constant then Bmax = constant; then Wh f
f
V
Case 2: 1 constant Bmax constant
f
x
V1 V
Bmax Wh 1 f
f f
Wh V1xf1x
For x= 1.6
V11.6
Wh 0.6
f
By keeping applied voltage constant and by increasing frequency, Hysteresis Loss will
decrease.
The alternating flux set up in the core by Primary Winding causes emf to be induced in the
core which causes swirling currents in the core. These currents since they flow in circular
loops like eddy in sea are called as Eddy Currents. The losses due to these currents are called
as Eddy Current Losses.
Eddy current losses in Transformer core conductivity of Transformer core
Since, eddy currents induced Ie
1
Resistance of Core R ce
1
Hence, Eddy Current Loss, We I2eR ce 2 We
Silica content in Transformer core reduces conductivity of steel, hence eddy current losses
reduce. But we cannot add Silica beyond 4% else it would make the Transformer core brittle.
V
Case 1: const Bm const
f
Pe f 2
So, eddy current losses are proportional to square of frequency.
V
Case 2: const, Bm const
f
2
V
Pe f 2 V2
f
If voltage is kept constant but frequency of operation of Transformer is reduced then No
change in eddy current loss but Hysteresis Loss increases.
1. Magnetizing Current drawn by the primary winding from the source increases.
2. No-load Power Factor of transformer reduces
3. Iron loss in Transformer core increases.
These losses are dependent on load current and are like Eddy Current Losses but occur in
different parts of Transformer instead of core. The Stray Load Loss has two components:
1. Cu stray load losses
2. Iron stray load losses
Cu Stray Load Losses occur in conductors of primary and secondary windings of the
transformer and can be reduced by using Stranded Conductors instead of Solid Conductors.
Magnetic leakage flux produces some additional iron losses in Transformer which are
counted against iron stray load losses. More or less eddy current losses but due to leakage
flux, depend on load.
Since, Stray Load Losses depend on Load Current they are considered as Variable Losses.
Dielectric Losses
These loss normally takes place in insulating materials of Transformer such as inter winding
insulation and also Transformer oil. As dielectric loss is independent of load current, it is a
constant loss. It depends on impressed voltage.
These losses occur due to finite resistivity of the insulating material so it allows a leakage
current through it. Practically, 0.25% of total output can be taken as dielectric losses.
This test is conducted on LV side keeping HV side open circuited because this test is
conducted at rated voltage and more convenient to apply rated voltage at LV side
NL current is more on LV side. Hence can be accurately measured
E1 E1 V1 V1
Ro , Xo or R o , Xo
Iw I Iw I
Under the assumption that NL primary Cu loss is small and dielectric losses are neglected.
Wattmeter Reading = Iron losses
During this test, short circuit is done on LV terminals and applied voltage on other terminal is
increased until rated current flows in both windings. As this test is conducted at rated current
condition, it is convenient to conduct on HV by short circuiting LV as rated current is lesser
on HV side.
As LV winding is shorted, 8- 10 % of rated voltage is enough to produce rated short circuit
current in both windings.
Wsc =Losses in Transformer under SC condition
= Full Load Cu losses in both windings + stray load losses +small amount of iron losses
corresponding to Vsc
Usually, Short Circuit Voltage is much less than Rated Voltage so, we can neglect Iron losses
under Short Circuit Test. Also, Stray Load Losses are small so wattmeter reading under Short
Circuit Test give Full Load Copper Losses.
The equivalent circuit for the Short Circuit Test is shown below. Here we have ignored the
shunt branch as No-Load Current is 5-8% of Full Load Current
Short-Circuit Impedance:
V
Z 01 sc
Isc
Then the reactance can be calculated as:
X01 Z01
2
R01
2
R 01
o Short Circuit Power Factor, c os sc increases as Short Circuit Impedance
Z 01
decreases.
Efficiency
Efficiency if any system indicates that how much input is being converted to the output. In
case of Transformer it will indicate how much primary input is being converted to the
secondary output.
outputpower
Efficiency = 100
Inputpower
By Power conservation, Pout Pin Ploss
Therefore, we can also express efficiency as
Pout
100
Pout Ploss
Pin Ploss
100
Pin
In case of Transformer, we express the output power or Load as a percentage of Rated KVA
or Full Load.
Assuming load is ‘x’ times the full load power.
Load KVA = x KVA
rated
Assuming that the terminal voltage equals rated voltage under all conditions. Then,
Load KVA V rated I x Vrated Irated
Hence, I x Irated
Rated current is also referred to as Full Load Current. Therefore, I x IFL
Hence, copper losses are given by PCu I2R 02 xIFL R 02 x 2 IFL 2R 02 x 2 PCu FL
2
Maximum Efficiency
With any system, the desirable condition is to have minimum losses so that maximum part of
Input energy is transformed to output. Hence, we need to determine the conditions under
which efficiency is maximum.
If Power Factor of load is variable and we need to determine the power factor at which we
have maximum efficiency then
d
0
d
x(KVA)sin x KVA cos Pi x2PCuFL 0
0 and cos 1
i.e. Maximum efficiency in a transformer for fixed load is obtained for unity power factor
load.
Efficiency depends on the load connected to Transformer but Load is variable and in case
of Distribution Transformer the load varies throughout the day. Hence, efficiency definition
needs to be modified to have physical significance for variable load.
Hence, we define All Day Efficiency,
Voltage Regulation
The second performance index upon which Transformer performance is judged is called as
Voltage Regulation.
It basically defines the fluctuation in Transformer output voltage as the load connected to
Transformer is varied from No-Load conditions to Rated Value that is Full Load Condition.
The desirable condition is that fluctuation should be minimum and hence Voltage
Regulation should also be minimum and ideally it should be zero.
Under No-Load I2 0
Hence, the voltage at secondary terminals = E2
The Voltage under Full Load conditions = V2 E2 IFL Z02
E2 V2
Voltage Regulation is given by, VR 100%
V2
We are only interested in magnitude of voltage to calculate Voltage Regulation and hence
we have rotated the vector E2 to lie along the horizontal axis.
E2 AE AB BC CD DE
As an approximation neglecting DE
E2 AE AB BC CD V2 I2R02 cos I2X02 cos 90
E2 V2 I2R02 cos I2 X02 cos 90
E2 V2 I2R02 cos I2X02 sin
E2 V2 I2R02 cos I2X02 sin
Leading pf load, VR = R02 pu cos X02 pu sin 100%
Condition for Maximum Voltage Regulation
In case of lagging pf load, both terms are summed and in leading pf load both terms are
subtracted so maximum voltage regulation can be achieved for lagging pf load.
d(VR)
0
d
d
R pu cos X 02 pu sin R 02 pu sin X 02 pu cos 0
d 02
X02 pu X02
tan
R 02 pu R 02
X
Hence, load pf angle is tan1 02 lagging
R 02
Condition for Zero Voltage Regulation
In case of leading load since both terms are subtracted, it can give zero voltage regulation
but not lagging pf load.
Hence, VR R02 pu cos X02 pu sin 0
R 02 pu R 02
tan
X02 pu X02
R
Hence, load pf angle is tan1 02 leading
X02
Solved Examples
Problem: The % resistance of a 10kVA 900/200V, 3-phase transformer is 2% if the constant
losses in machine are 1% then maximum possible efficiency of the transformer will be?
Solution: % res=2%
R pu 0.02
Pcu,FL IFL
2
R
Pcu,FL pu 12 0.02 0.02pu
I
Ipu
IFL
IFL
IFL pu 1pu
IFL
S
S pu
Srated
Srated 1pu
Pi 0.01
x 0.707
PCuFL 0.02
x(KVA)cos 0.707 1 1
100% 100%
x(KVA)cos 2Pi 0.707 1 1 2 0.01
97.2%
Problem: A 1 Transformer has maximum of 90% at full load at unity power factor
calculate the at half load and unity power factor.
Solution: Maximum Efficiency is given by,
x KVA cos
x KVA cos Pi x2PCu,FL
KVA
max (i)
KVA 2Pi
Pi
Loading for Maximum Efficiency, x 0.9
PCu,FL
Pi
PCu,FL
0.81
KVA
0.9
KVA 2Pi
18Pi KVA
0.5KVA
0.5KVA Pi 0.25 PCu,FL
0.5 18Pi 0.5 18Pi
0.5 18Pi Pi 0.25 PCu,FL Pi
0.5 18Pi Pi 0.25
0.81
87.3%
0
E V I R cos 50 0.12 1
200 V 6
V 194V
Problem: A 23kVA, 50Hz, 2300/230V Transformer has primary and secondary turns of
200/20 when rated voltage is applied calculate mutual core flux neglecting winding voltage
drop at full load the leakage flux linking each winding is 1% of mutual flux calculate primary
and secondary leakage reactance and total reactance refer to each side.
Solution: 230kVA, 2300/230V
Assumption Assume no-load
Vrated 2300V
Np 200
m 0.052 Wb
At full load
l 1% of m 0.00052wb
N LI
200 0.0052 L 1.0
L 0.0104H
23 103
IFL ,P 10A
2300
XL L 2 50 0.0104
Xl 3.26
23 103
IFL,sec 100A
230
0.00052 20 L 100
L 0.000104H
Xl L 2 50 0.000104
Xl 0.03
Ratings of Transformer
The rating of any electrical machine is limited by temperature of a machine during its
operation. The temperature rise in any machine is due to losses in that machines that means
rating of any machine is indirectly determined by losses in that machine.
In case of transformers, iron loss depends on voltage rating and Cu loss depends on current
rated.
Voltage Rating
E 4.44NfBmAn
Where, A n =Normal area
Bm Cons tant to avoid saturation
Hence, E Area
S, if all Dimension become 2 times then Area become 2 times
Voltage rating is doubled.
Current Rating
Cross sec tion area of Cu
Window space factor
Window area
N1a1 N2a2
kw
A
I1 I2
a1 a2
2N1I1
kw
A
I1 A
If all dimension of Transformer become 2 times, then window area doubles and hence
current rating also doubles.
KVA Rating
A k
S VI 4.44N1fBm Ai
2N1
4.44fBmk
S
2
Ai A
So, if all the dimensions of the transformer become 2 times, both the areas would double
and KVA rating would become 4 times.
Pcore VI
So, core loss component of no-load current is,
Pcore Volume
I length
Voltage Area
I length
Magnetizing Inductance can be expressed as,
NN A
Lm 0 1 2
L
Area
Lm width
length
Xm width
Magnetizing Current is given by,
V Area
I length
Xm width
I length
Solved Examples
Problem: A 550KVA 60Hz Transformer with a 6.6KV primary winding draws a current of 5A at
no-load rated voltage and frequency. A second transformer has a core with all the dimension
2 times that of first transformer the primary winding of both transformers has same
number
of turns the second transformer is applied with 13.2kV, 60Hz at primary it will draw a no load
current of?
Solution: Initially, No-Load current is 5A. When dimension is made 2 times, the current will
be scaled by the same factor.
I'nl Inl 2
I'nl 5 2 7.07 A
Problem: When a 400Hz Transformer is operated at 50Hz what happen to KVA rating?
Solution: KVA rating f
f
KVA rating 2 2 KVA rating
f1
50
KVA rating 2 KVA rating
400
1
KVA rating 2 KVA rating
8
Solution: RL R Th
2
N
2 1 8
40
N1 80 turns
Problem: Circuit diagram shows a two winding lossless transformer with no leakage flux
excited form current source i(t) winding wave form is shown the transformer has magnetizing
400
inductance of mH .
di t
E Lm
dt
400 10
10 3 10
3
5
800
E V
Problem: If the wave form of i t 10sin 100t then the peak voltage across A and B with
switch ‘S’ closed is?
Solution: The circuit with switch S closed and the entire circuit referred to primary side is
also shown,
400
X L 100 40
I j40 10 40 j
I2 836.870 A
30 j40 30 j40
V2 I2R 24036.870 V
Problem: A 220/115V 25Hz 1 Transformer as eddy current loss of 100W which is half of
the no load loss at rated applied voltage if the Transformer is connected to 440V, 50Hz
mains then the total no load loss will be?
P
Solution: Peddy 100W 0
2
P0 200W Ph Pe
Ph 100W
V V
8.8 8.8
f f
Ph f Pe f 2
Ph2 f2 50
1
Ph1 f1 25
Ph2 200W
2
Pe2 f2
Pe1 f1
Problem: A S.C test when perform on the H.V side of 10KVA 2000/400V single phase
transformer give the following data 60V, 4A 100W. If the L.V side is delivering rated current
at 0.8pf (lag) and 400V find voltage applied to H.V side.
Solution: 60V, 4A, 100W
2000/400V
P
R 01 2 100 6.25
I 16
60
Z 01 15
4
X 01 X 01
2
R 01
2
152 6.252
X 01 13.63
2
400 13.63
R02 6.25 0.25; X02 0.54
2000 25
10 103
Irated LV 25A
400
VL 4000V
E VL IL R jX
E 413.150.970 V
E1 N1 2000
5
E2 N2 400
E1 5 413.15 2066.17 V
V.R 3.28%
In the figure shown above in first case the magnetization curve of the transformer is shown
and based on that assuming a sinusoidal flux distribution, magnetizing current has been
plotted.
From, the figure it can be observed that for establishing a sinusoidal flux in the core of the
transformer a peaky magnetizing current is required. The peak of magnetizing current aligns
with the peak of the flux. Due to non-sinusoidal nature of the magnetizing current, it consists
of harmonics in which third harmonic is most pre-dominant.
I I1 sin t I3 sin3t I5 sin5t .........
Fundamental
If we consider the effect of hysteresis then there will be some residual flux density in the
core of the transformer and due to that flux will be non-zero for zero magnetizing current.
This causes a phase shift between the flux and magnetizing current waveforms as zero of
both cannot align with each other.
The phase lead of magnetizing current with respect to flux is termed as Hysteresis Angle.
From the figure it can be observed that due to third harmonic the flux becomes flat-
topped. The flux can be expressed as,
1 sin t 3 sin3 t 3 sin5 t .............
To determine the induced emf from the flux distribution shown above,
d
e
dt
e 1 cos t 33 cos3t 55 cos5t
The waveform for emf using fundamental and
third harmonic has been shown in
adjoining figure,
Effect of Harmonics
Due to harmonics RMS value of current increases due to which copper loss also increases.
I I1 sin t I3 sin3t .............
1
Irms I12 I32 I52
2
Pcu Irms
2
R
The third harmonic behaves as zero sequence and hence causes interference with the
nearby communication lines.
When emf is peaky and flux is flat topped hysteresis loss and eddy current losses reduce
due to reduction if flux and hence core loss reduces.
Summary of Harmonics
If applied voltage is sinusoidal then flux is also sinusoidal but magnetizing current is
peaky wave due to 3rd harmonic.
For sinusoidal magnetizing current, flux is flap topped and emf is peaky wave containing a
strong 3rd harmonic.
Switching Transients are more severe when switch is closed at the instant. When applied
voltage crosses zero value, switching transients are less severe of switch ‘S’ is closed at when
the applied voltage wave crosses peak value.
Flux cannot be changed instantaneously in a Transformer. It is termed as Magnetic Inertia in
a Transformer.
If switch is closed when the applied voltage wave crossing 0 points, flux demanded by
core is m as induced emf lags the flux demanded by 900 . But no Transformer can produce
this much flux instantaneously due to magnetic inertia. In this case produced in
transformer core doesn’t trace the normal path but it traces the transient flux path and
attains twice the max value of normal flux. This effect is called doubling effect.
Double the flux produces double the emf in primary and secondary windings within a
short period of time. Hence these are called as impulse emf.
As time period is very less most of the impulse voltage about 80%, 5% end turns on both
side of Transformer windings causing a lot dielectric stress at these turns. So these turns
should be provided with some extra thickness of insulation to protect them against impulse
emf.
Double the flux demands very high current from the source due to deep saturation of
magnetic core. This high I is known as magnetic inertia current. Approximately 50 times
normal current. This current is called as Magnetic Inrush Current. It has both even and odd
harmonics present due to unsymmetrical nature. Most dominant is 2nd harmonic current.
No load current only in primary but is only 5% of full load current. Load current
transferred from one winding to another winding. So forces are balanced. But under
transients current is only concentrated on primary so forces are not balanced.
Remedy: Proper brassing of coils so avoiding dislocation of coils.
To avoid dislocation, windings should be properly brassed and should be given good
support. If the ‘S’ is closed, when the applied voltage crosses peak value, the flux demanded
by core at the instant of switching is zero only. Flux traces normal path and transients are
absent.
If some residual flux is present in core with polarity opposite to normal flux.
p 2m r
Severity of Switching Transients is increased.
If residual flux is having same polarity
p 2m r
Severity of Switching Transients is reduced.
Since, there is no closed path for flow of flux so third harmonic flux is absent. Since, third
harmonic is absent in flux and hence emf is sinusoidal.
Polarity Test
Polarity Test is usually performed to check the polarity of connections of primary and
secondary windings before putting the transformer into operation.
The set up for the polarity test is shown below,
Delta-Delta Connection
The connections of Delta-Delta Connection are shown below,
Now first we draw primary phasor such that A2 terminal must lie vertically upwards and
parallel to primary phasors secondary phasors will be drawn.
If we observe that primary phasor is drawn from A1 to A2 and parallel to that secondary
phasor is drawn from a1 to a2.
The dotted reference phasors have been drawn inside the delta in form of Star.
If we plot both the ‘A’ phases on primary and secondary on a clock it looks like as shown
below,
Here, both A and a phase are lying on top of each other and if we read
The time then it looks like as if 12’o clock is the time.
So, the name of this connection is Dd12.
The primary is always represented in upper-case letters and secondary
In lower-case letters.
Now the output at secondary terminals is taken at a1, b1 and c1. So, reference phasors will be
drawn with respect to a1, b1 and c1.
Features
In this Transformer connection if phase turns ratio is x:1 then line to line voltage ratio is
x:1.
As phase voltage = line voltage in Delta-Delta, it requires more number of turns/phase
and also more amount of insulation when compared to Star-Star Transformer of same
voltage rating.
Line Voltage
Phase Current = Phase Voltage , this Delta-Delta Connection requires
3
57.7% of cross section area of conductors when compared to Star-Star Connection of same
I
rating. In Star Connection, IL Iph . But in delta connection Iph L 0.577 IL 57.7 % of IL .
3
Since, area of cross section is proportional to Current Rating so Area of Cross Section in case
of delta connection is lesser as compared to Star Connection.
Because of above reasons this connection is not economical for HV applications but it is
economical for LV and High Current applications.
This connection is mechanically weak when compared to Star-Star for same current rating
as conductors are thinner.
Both sides of Transformers offers closed path for 3rd harmonic component current, so
shape of induced emf is always sinusoidal.
Star-Star Connection
The connections for Star-Star Connection is shown below,
First we will draw the primary phasors such that Phase A is vertically upwards and then
secondary phasors will be drawn in parallel to primary phasors.
If we draw both primary and secondary phasors on a clock, then the both ‘A’ and ‘a’ phase
overlap. Hence, there is 00 phase shift between primary and secondary voltages.
On, the clock it looks like as if 12’o clock is the time and hence this
connection can be named as Yy12.
The primary phasors will remain same and secondary phasors will be as shown in the figure
below,
If the primary and secondary phasors with terminals A2 on primary and terminal a1 on the
secondary then it can be observed that there is 1800 phase shift between primary and
secondary phasors.
If these phasors are plotted on a clock then it will be as shown below,
Then it seems like the time on the clock is 6’o clock. So, the connection
can be named as Yy6.
Hence, the Star-Star Transformer can provide the phase shifts of 00 and 1800.
Features
Line to line voltage ratio equal to phase turn ratio.
V
L p
3Vph V N
p ph p ph p
V
L s 3Vph V N
s
ph s ph s
VL Vph ,
Vph ,Y 0.577Vph ,
3 3
Vph ,Y 57.7% of Vph ,
Delta-Star Transformer
The first possible connection for Delta-Star Transformer is shown below,
The other possible connection for the delta-star transformer is shown below,
Features
Vph,S Ns
Vph,P Np
VL,S 3Vph,S N N
3 s 1.73 s
VL,P Vph,P Np Np
For the same voltage rating number of turns required are lesser as compared to other
connection.
Since primary side is Delta, it allows the flow of 3rd harmonic magnetizing current so emf
is sinusoidal and it can be used to supply both 1 and 3 load.
The phasor diagram for the above connection can be d rawn as shown below,
KVA = Vph
3 Iph 3 VphIph
3 VphIph
TUF = 100% 86.6%
2VphIph
Hence, each unit operates at 86.6% of the capacity.
KVA V
3 VphIph
0.577 or 57.7%
KVA
3 VphIph
Suppose, if both Delta-Delta Transformer and Open Delta Transformer both supply the same
load. Then,
3 VphI'ph 3VphIph
Necessary Conditions
1. Voltage ratings on name plate of Transformer must be same.
2. Phase sequence of both Transformer should be same.
3. Phase displacement angle between secondary of both Transformer must be 0. This will
eliminate circulating currents.
4. Transformers must be connected with same polarity to avoid circulating currents.
The Three Phase Transformers that can be connected in parallel should have same phase
shift.
Star-Star and Delta-Delta Transformers can be connected in parallel as they provide 00 and
1800 phase shift.
Star-Delta and Delta-Star Transformers can be connected in parallel as they provide
300 or 1500 .
V2 E2A IA Z A .......(i)
V2 E2B IB ZB ...............(ii)
The impedance drop of both Transformer are same if voltage ratios are same
ZB
IA I L
Z A ZB
ZA
IB I L
Z A ZB
KVA shared by Transformer A
* *
ZB ZB
S A VL IA VL IL
* *
SL
Z A ZB Z A ZB
Auto-Transformer
It is used for Step-up and Step-down applications and here the primary and secondary
windings are not isolated but rather some part of winding is common between the two.
The schematic arrangement of windings of an auto-transformer is shown in the figure below,
Note:
If K<0.333, this is low percentage tapping and so advantages are very less. So auto
transformer is not feasible.
In Auto Transformer power is not only transferred by induction process but also by
conduction process. Common part of winding transfers the power from Primary to secondary
by means of conduction.
1. (KVA)induction (1 k) inputKVA
2. (KVA)conduction k inputKVA
3. weight of copper Auto
= (1-k) (weight of copper)2wdg
4. % full load losses in Auto Transformer = (1-k) (% losses in 2 winding Transformer)
5. % voltage drop in Auto Transformer = (1-k) (%voltage drop in 2winding Transformer)
1
6. (KVA)AutoTransformer (KVA)2 winding
(1 k)
E1 N1 N2
E2 N2
N1 N2
E1 E2
N2
N1 N2
VAB E2 I1 r1 jx1
N2
E2 V2 I2 r2 jx 2
N N2 N1 N2
VAB 1 V2 I1 r1 jx1 I2 r2 jx2
N2 N2
N 1
N2 I1 N2I2
N1 N2
I2 I
N2 1
2
N N2 N1 N2
VAB 1 V2 I1 r1 jx1 I1 r2 jx 2
N2 N2
2
N N2
req r1 1 r2
N2
2
N N2
X eq X1 1 X 2
N2
If efficiency of two-winding Transformer is given as 98% at Full Load upf, the we need to
determine the efficiency of Auto-Transformer at Full Load upf.
20 103 1
2 wdg 0.98
20 103 1 Total losses
Total losses=408W
220 103 1
AT 99.8%
220 103 1 408
If efficiency of two-winding Transformer is given as 98% at Full Load upf, the we need to
determine the efficiency of Auto-Transformer at Full Load upf.
20 103 1
2 wdg 0.98
20 103 1 Total losses
Total losses=408W
180 103 1
AT 99.77%
180 103 1 408
Drawback
Not feasible if k<0.333
No isolation between primary and secondary, so if any fault occurs in secondary, it is
carried to primary.
Sumpner’s Test
During OC and SC test, iron and copper loss do not occur simultaneously so temperature
rise cannot be estimated so we conduct Sumpner’s test.
Heat run test: We conduct this for a certain period of time as instantaneous heat rise
cannot be obtained
Difficulty in Sumpner’s Test: Two identical 1- Transformer are needed
Primary should be connected in parallel and executed from a main source at rated voltage
and frequency (OC Test)
Secondary should be connected in series with subtractive polarity and this combination
should be supplied by auxiliary source.
Step 1: Short auxiliary supply voltage and excite the Transformer by main supply at rated
voltage and frequency
Step 2: Short windings on supply side and excite auxiliary source only (SC test)
Step 3: Conduct with both sources.
Observations
Solved Examples
Problem: A Y Transformer with connection on primary side is operating in a parallel
with a Y Transformer with Y connection primary side the ratio primary turn per phase and
secondary turn per phase of the former is x times of the latter the x is?
VLP V 1 NP
Solution: Ph,P
VLS 3VPh,S 3 NS 1
VLP' 3VPh N
3 P
V '
LS
VPh NS 2
1 NP NP
3
3 NS 1 NS 2
NP
NS 1
x 3
NP
NS 2
415
Esec 1.038 1.870 Volt
3
Eph,S 248.831.870 V
Eph,P NP 6000
24.11 24
Eph,S NS 248.83
Problem: Two 1 transformers with equal turn have impedance of 0.5 j0.3 and
0.6 j1 with respect to secondary if they operates in parallel how will they share a load of
100KW at 0.8 pf lag.
*
ZB
Solution: S A SL
Z A ZB
*
0.6 j1
S A 12536.87
1.1 1.3 j
S A 12536.87 0.1323.41
PL 100
SL 125 KVA
pf 0.8
SL 125KVA
SB SL S A
Problem: A 1 50KVA 250/500V 2-winding Transformer has an of 95% at full load U.P.F
it is reconfigured as auto transformer of rating 500V its at new rated load and U.P.F is?
500
Solution: k
750
1
Snew 50
500
1
750
Snew 150KVA
x KVA cos
100%
x KVA cos Ploss
50
.95 Ploss 2.63KW
50 Ploss
150
100%
150 2.63
98.27%