REZAYAT LABORATORIES FOR INDUSTRIAL SERVICES W.L.

L
Sample No: 22204
Report Date: 2019-05-07
ANALYSIS REPORT
CLIENT ADDRESS
Company Name : PGP Contracting E-mail :pgp@turk.bh
Contact Person : Mr. Ali Sowaid Address :Kingdom of Bahrain
Mobile :+973 39001940 Tel./Fax :+973 17700165

EQUIPMENT DATA SAMPLING DATA


Serial No : 20180734TID004-001 Load: Sample Man Name : None (PGP)
ID No. : GTA-7 Operating Period : Sampling Date/Time : 2019-05-05
Equipment Type : Transformer Phase No.: 3 Arrival Date : 2019-05-05
Manufacture Name : Hyundai Tension,HV/LV: 220 kV Sampling From : Bottom
Manufacture Country : Korea Oil Type : Oil Temp : 34°C
Manufacture Year : 2018 Oil Weight: Winding Temp :
Station Name : Riffa Power Station Cooling Type : Ambient Temp :
Location : Riffa Sealing System : Ambient Humidity :
Operated Rate Power: 100 MVA TC Type : Reason for Sampling :
Owner: TC Chamber : Unit Status : New prior energizing
NEW OIL PRIOR ENERGIZATION (>170 KV)

Test Name Value Unit Method Normal Caution DL Date

Colour L 0.5 ASTM Color ASTM D1500 <2.0 - 2019-05-07

Water Content @ RT 3.2 ppm IEC 60814 <10 -

Acidity / TAN / Neutralization Value <0.01 mg KOH/g IEC 62021-1 <0.03 -

Interfacial Surface Tension (IST) 43 mN/meter ASTM D971 >35 - 2019-05-07

Total Furanic Compounds ppm IEC 61198 0.03

Oil Quality Index (OQIN) 4300 - Calculated >300 <160

Room Test Temperature (RT) 18.6 °C - 2019-05-07

Room Test Humidity (RH) 47 % - 2019-05-07

Indirect DP-value - Stebbin Method >800 <150

Lifetime Remaining % Calculated - -

Note 1: Value limit is used in accordance with standard IEC 60422 (2013) for new oil after filling in new electrical equipment (HV>170 kV) prior to energization and also

accordance to ASTM D3487 (2016) and IEC 60296 (2012) related to some tests for new oil. Note 2: Cell type used for DF test ASTM D924 method is IEC 60247 Fig.3 (73.0pF).

Average Voltage gradient (Electrical stress) = 1000 VAC/mm. Test Frequency = 60 Hz for D924 and 55 Hz for IEC60247. Resistivity is calculated at 250V/mm; 60s short-circuit;

90C. Note 3: DL=Detection limit along with calibration of our instruments according to ISO 17025 requirement.

EVALUATION
The result of the performed oil analysis meets the requirement of new oil prior to energizing according to
standard IEC 60422. Values of interfacial surface tension (IST) shows no oxidation products in th eoil.
Quality index value and physical parameters indicate good oil quality.

RECOMMENDATION

New sample is recommended after two days of energizing or as per the client maintenance plan.

This analysis result relates only to the specified product tested. Some values inside the brackets indicate for subcontracted parameters with other accredited lab.