Date of Water Tightness Test Wtaer Level Water Allowable Test
No Structure Element started End Top Bottom height Range Result 1 Thickend sludge sump 21-Dec-2019 28-Dec-2019 14.50 10.05 4.45 8.9 2 Clear Water Reserviour Outer Chamber 15-Feb-2019 22-Feb-2019 11.39 8.19 3.20 6.4 3 Thickener B Thckener -B 21-Feb-2019 28-Feb-2019 15 10.33 4.67 9.34 3.0 4 Rapid Sand Filter Tank G 23-Mar-2019 30-Mar-2019 15.07 11.51 3.56 7.12 5 Rapid Sand Filter Tank E 26-Mar-2019 2-Apr-2019 15.07 11.51 3.56 7.12 6 Rapid Sand Filter Tank A 25-Apr-2019 2-May-2019 15.07 11.51 3.56 7.12 2.0 7 Rapid Sand Filter Tank H 26-Apr-2019 3-May-2019 15.07 11.51 3.56 7.12 2.0 8 Rapid Sand Filter Tank C 1-May-2019 8-May-2019 15.07 11.51 3.56 7.12 2.0 9 Pulsatube Clarifier Tank A 1-May-2019 8-May-2019 15.86 10.78 5.08 10.0 6.0 10 Chlorine Contact Tank Tank A 2-May-2019 11-May-2019 12.320 7.825 4.495 8.99 -3.0 11 Chemical Building Lime Preperation Tank A 24-May-2019 1-Jun-2019 12.00 8.55 3.45 6.9 -4.0 12 Chemical Building Alum Dosing Tank A 24-May-2019 31-May-2019 12.34 8.55 3.79 7.58 -4.0 13 Chemical Building Alum Preperation Tank A 27-May-2019 3-Jun-2019 12.58 8.55 4.03 8.06 -1.0 14 Pulsatube Sludge Sump Pulsatube Sludge Sump 24-May-2019 1-Jun-2019 8.80 4.90 3.90 7.8 4.0 15 Clear Water Reserviour Tank A 0.00 16 Chlorine Contact Tank Tank B 12.320 7.825 4.495 8.99 17 Chemical Building Lime Preperation Tank B 12.00 8.55 3.45 6.9 18 Chemical Building Alum Dosing Tank B 12.34 8.55 3.79 7.58 19 Chemical Building Alum Preperation Tank B 12.58 8.55 4.03 8.06 20 21 Volume of Rectification Submitted Remarks Water (m3) of Defects DTF 350 1279 237.3 1628 420 1670 500 1818 500 1819 500 1919 500 1919 500 1928 2000 1927 2000 2002 94 84 33 102