The fault level calculations shall be done at 11KV end and separately at 415V end. The
system fault level at 11KV side has been assumed at 350 MVA.
By considering 350 MVA, The further calculations for 11KV end are as follows:
Voltage X 1.732
= 350
11X1.732
= 18.37 KA
GRID supply is available and Two Transformers of 2250 KVA are operating
independently as envisaged.
% Impedance of Transformer
at 2250 KVA base = 6.25%
36
Fault level KA = = 48 KA
0.433 x 1.732
Total no of DG Set Proposed are Two Nos. 1000 KVA, One No. 750 KVA and One
No. 380 KVA.
Xd’ - Sub Transient Reactance = 0.17 Per Unit (As Per Stamford)
= 2086 / 0.17
=12.27 KA
= 1043 / 0.14
= 7.45 KA
= 528 / 0.14
= 3.77 KA
Fault Level of 2 No 1000 KVA 1 No. 750 KVA and 1 No. 380 KVA = 12.27 +
12.27+7.45+3.77=35.76KA
Hence fault level of 50 KA shall be considered for main L.T. / DG Panel design.