Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Considerations
Part 3 of 3 © 2015 Electric Power Research Institute, Inc. All rights reserved.
Outline – Microgrid Design and Analysis Tutorial
Part II
Time Topics
14:30-15:00 Design analysis
• Needs and Key Interconnection Issues (Arindam Maitra)
15:30-17:30
Design analysis (cont.)
• Methods and Tools
• Case Studies
#1: Renewable Rich Microgrids - Protection Case Studies
(Mohamed El Khatib)
#2: Rural radial
#3: Secondary n/w
17:00-17:30 Q&A
17:30 Adjourn
2
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Microgrids
Regulatory Issues
Value of Resiliency
System Design
Challenges
Engineering Studies
Costs
3
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Integrating Customer DER with Utility Assets
Micro Grid
Controller SCADA/DMS/
/ DERMS* Enterprise
Integrate
Energy Storage*
d Grid
Isolating Device*
Distribution
Transformer
*New assets
4
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Microgrid Types
Commercial/Industrial Microgrids: Built with the goal of reducing demand and costs
during normal operation, although the operation of critical functions during outages is
also important, especially for data centers.
University Campus Microgrids: Meet the high reliability needs for research labs,
campus housing, large heating and cooling demands at large cost reduction
opportunities, and lower emission targets. Most campuses already have DG resources,
with microgrid technology linking them together. They are usually large and may be
involved with selling excess power to the grid. Some of these facilities typically serve
as emergency shelters for surrounding communities during extreme events
6
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Microgrid Configurations Depending on Location and Purpose
7
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Micro-grid: Operating as an “Island” Isolated from the
Bulk Supply
Circuit Breaker Isolating Device
– when open the system
operates as micro-grid
“Islanded” Facility
Utility
Source Trip
Signal
Islanding Control
(opens/closes breaker as needed to
facilitate independent operation –
must provide synchronization)
Electrical Island
DG
DG Able to Carry Load on
Island and Provide Proper
Voltage and Frequency
8
© 2015 Electric Power Research Institute, Inc. All rights reserved.
“Islanding” for Reliability Enhancement
Building
Load
13.2 kV Feeder
Building
Load
Utility Substation
Building
Load
Utility System
Interface Breaker
D D Building Building
G G Load Load
Thermal Energy
Storage
Storage Heat
Distribution
10
© 2015 Electric Power Research Institute, Inc. All rights reserved.
A Single Building
Multiple Sources, Storage, and Heat Recovery
Charge/Discharge
Regulator
Building
Heat
Energy 200 kW Recovery Thermal
Storage Fuel Cell Loads
11
© 2015 Electric Power Research Institute, Inc. All rights reserved.
A Campus Microgrid System
Source: Johan Driesen and Farid Katiraei, “Design for Distributed Energy Resources,” IEEE Power & Energy Magazine,
May/June 2008
13
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Microgrid Design Elements
• Are the fault contributions from • Are DERs able to regulate the voltage and
DERs sufficient to allow frequency within the island?
satisfactory operation of • Any issues with parallel grid operation?
protection systems? • How is re-synchronization checked
• Are existing protection schemes against criteria such as out-of-phase, large
adequate? change in voltage?
Microgrids
Performance Criteria
• Electrical & Thermal Needs
• Generation Assets
• Critical Load Needs
• Power Distribution Equip.
16
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Variable Distributed Energy Assets within Microgrid
Source: PNNL
17
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Key Considerations in Design for Energy Storage
• Response time
– For seamless transition, response
time must be very fast
– This is more than just battery
response time – communications
latency and control functions also
play a role
18
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Isochronous / Droop Modes of Operation
Isochronous - Isochronous control
mode means that the frequency (and
voltage) of the electricity generated is
held constant, and there is zero
generator droop.
Droop Control Mode - strategy
commonly applied to generators for
frequency control (and occasionally
voltage control) to allow parallel
generator operation (e.g. load sharing).
For grid-tied microgrids – all the DG
and storage resources operate in
droop mode and the utility is the
isochronous generator reference.
For off-grid microgrids – one
generating unit is designated to run in
isochronous mode and all other follow
in droop mode. Larger units and
higher inertia prime movers are
normally the reference machine. PV
inverters are nearly always operating in
droop mode. Battery inverters may
operate either way when generating.
19
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Controller Integration
20
Source: EPRI DOE SHINES Project © 2015 Electric Power Research Institute, Inc. All rights reserved.
Microgrid Technical Challenges : Protection
24% 14%
22
© 2015 Electric Power Research Institute, Inc. All rights reserved.
PQ Enhancements Possible
23
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Low Voltage Ride-Through
No low voltage ride-through requirements in the current IEEE
Std1547-2003 version (or the amendments)
A full revision of the 1547 is under way – inclusion of ride-through
requirements is considered
The CA Rule 21 ride-through requirements will likely inform the IEEE
Std 1547 ride-through requirements
25
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Micro-Grid Switching - MV vs LV
From Utility
From Utility
Typical Main Switch 12 kV
Typical Main Switch 12 kV
MV-CB
MV-CB
Point Of
Control
12 kV JC
Jn. Box 12 kV
Service 12 kV/
Service 12 kV/ Xfmr 208V
Xfmr 208V
LV-CB LV-CB
Point Of
Control
Building Building Building
Load Load PV
26
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Micro-Grid Switching at MV Level
From Utility Approach:
Typical Main Switch 12 kV Circuit breakers are available only at 12kV main
ring. No 12kV circuit breakers downstream.
MV-CB
Each circuit breaker controls a group of
Point Of transformers/buildings.
Control
Control is at the group level. No individual
Jn. Box 12 kV control at building level
Consequences:
Switching OFF a transformer on 12kV side
disconnects both building loads and connected
PV. This results in loss of generation (PV on non
critical buildings) when resources are needed
Service 12 kV/ during islanded operation.
Xfmr 208V
This design necessitates permanently assigning
buildings as critical and non-critical. It is not
possible to reassign them later.
Building 12KV switching could cause high transformer
Load
inrush currents during black start. Mitigating
equipment may be required if storage inverters
are not able to handle this high inrush current.
27
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Micro-Grid Switching at LV
From Utility
Approach:
Typical Main Switch 12 kV Control is shifted to the Low Voltage side.
MV-CB
Transformers are connected to buildings through
Low Voltage distribution boards.
This creates the ability to separately control loads
JC and generation within the buildings.
12 kV
Consequences:
No loss of generation (PV on non critical
buildings) when loads are disconnected during
islanded operation.
Service 12 kV/
Xfmr 208V Ability to reassign buildings as critical / non-
critical as and when needed.
LV-CB LV-CB
As loads are disconnected from the LV side it is
Point Of
Control possible to reestablish the MV ring through soft
Building Building start with all transformers connected. This could
Load PV
reduce inrush current significantly.
28
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Transformer inrush current and its impact
30
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Transformer Core Saturation Characteristics: I-V
31
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Transformer Energizing: Full-Voltage Energizing
With a Typical Saturation Curve
Transformer is unloaded energized at bus full voltage. Short-
circuit strength is x
1.5 MVA, 12.47 kV/480V, 5.07%
Short-circuit capacity at 12.47 kV bus = 300 MVA
(for now - Ygnd Ygnd)
Short-circuit capacity at 12.47 kV bus = 30 MVA
Rated transformer
4.6x
current = 70 Arms = 98 Apk
3.5x
32
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Transformer Energizing: Full-Voltage Energizing
With a Very Flat Saturation Curve
Transformer is unloaded energized at bus full voltage.
1.5 MVA, 12.47 kV/480V, 5.07% (for now - Ygnd Ygnd)
Ratedcapacity
Short-circuit transformer current
at 12.47 kV bus = 300 MVA= 70 Short-circuit
Arms =capacity98 Apk
at 12.47 kV bus = 30 MVA
20x
9x
33
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Design Analysis Load Analysis
unacceptable
voltage
overvoltage
Load and PV
Design Analysis
Impedance Approach
Location √
no impact • Steady State load flow Relay
desensitization
• System Dynamic
Current
unserved energy
• Harmonics
Energy
case by case
Energy exceeding
normal
look needed
• Flicker
Time
Location X
• Controls
Potential risk
• Operation seq. Impedance
34
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Microgrid Design Analysis
Commissioning
Data Collection Modeling Impact Studies
& Operation
35
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Key interests
Load flow
Protection analysis
Dynamic studies
• Events (loss of large load, load step & fault clearing capabilities)
• Fault Ride Through capabilities of various inverter-based DERs
36
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Detailed Design Analysis – Tools
Source: LBNL Paper LBNL-6708E
A variety of MC capabilities
requires a variety of models to
understand
• Performance
• Grid interaction
• System Protection Scheme
Impact
OpenDSS/Grid Lab D/DEW
PSCAD/EMTP-RV/MATLAB DesignBase
DIGSILENT
All
PSS/SINCAL
CYMDIST
Need to apply a consistent modeling
SynerGEE
framework
Allow existing models to feed new analysis Transient Dynamic
Time-Series
Analysis/Slow
Time-Series
Analysis/SS Steady State
Dynamics Steps
37
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Available Tools
Software Tool Affiliated Org. Tool Type
CYMDIST CYME International T&D Inc. Planning and simulation of distribution networks,
including load flow, short-circuit, and network
optimization analysis.
DER-CAM Lawrence Berkeley National Techno-economic tool for microgrid design and
Laboratory (LBNL) operation.
DesignBase Power Analytics Broad platform for electrical system design, simulation,
and optimization.
EMTP-RV POWERSYS Solutions Power system transients simulation, load flow,
harmonics.
EUROSTAG Tractebel Engineering GDF Power system dynamics simulation; full range of
Suez transient, mid- and long-term stability; steady-state
load flow computation.
GridLAB-D Pacific Northwest National Distribution system simulation and analysis.
Laboratory (PNNL)
HOMER Homer Energy LLC, National Techno-economic tool for microgrid design and
Renewable Energy operation.
Laboratory (NREL)
OpenDSS Electric Power Research Distribution system simulation and analysis.
Institute (EPRI)
PowerFactory DIgSILENT GmbH Power system analysis tool for load flow and
harmonics in transmission, distribution, and industrial
networks.
PSCAD Manitoba HVDC Research Power system transient simulation, load flow
Center simulation.
PSS/E Siemens Power Technologies Load flow, dynamic analysis, and harmonic analysis of
International (Siemens PTI) utility and industrial networks.
38
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Simulation Tools - Comparison
Study Power
Power Flow, Short Relay Arc Harmonic Transient Dynamic Quasi Steady-
Flow,
unbalanced Circuit Coordination Flash Analysis Analysis Analysis State Analysis
Tool balanced
EMTP-RV,
Simulink,
PSCAD
Aspen, Cape
DesignBase,
PowerFactory
PSLF, PSS/E
OpenDSS
GridLAB-D
Best choice
Cannot be done
39
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Case # 1:Protection Case Studies
(Mohamed El Khatib)
40
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Case # 2: Rural Radial Community
(Arindam Maitra)
41
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Case Study: Two Remote Rural Communities
3.25MW of Load
6.5MW of DG
42
© 2015 Electric Power Research Institute, Inc. All rights reserved.
One-line diagram of the 34.5-kV
R55 R173
Existing 34.5 KV Existing
Recloser Recloser 34.5 KV
Sync DG:
0.416 MW
43
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Case Study: Reliability Assessments In Rural Areas of
New York
Fault Exposure Scenario #1
Proposed
1 MWHR Energy
Storage Wind plant : 6.6 MW
~ 2 hours
Fault Exposure Scenario #2
Proposed
Existing 34.5 KV Proposed Existing
34.5 KV Reclosure
Reclosure Reclosure Reclosure
44
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Design Study
45
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Case Study: Focus Areas
− A high-level protection system design (relay types, communication needs, etc.) that
are needed to accommodate normal and microgrid operation
− Emphasis was on 34.5 kV line and underlying 4.8 kV system as well to evaluate the
possible local microgrid effects at the 4.8 kV side.
46
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Possible Microgrid Configurations
47
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Technical Limitations with Current Protection
Fault Condition # 1:
– Grid Connected Mode: Fault Exposure Scenario #1
Proposed
Sync DG:
Microgrid 1
0.416 MW
1 3
1
Wind Farm
R173 (Form 6)
New relay
3 - set of 3 wye-gnd
2.5MVA
connected VTs
34.5kV:4.8kV
X 1 – single VT
Wethersfield
storage R199 (new)
1
battery 1
500kVA 3
Beckwith M-3410A Y
Boxler Farm storage
battery 2
50
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Permanent fault occurs here
Orangeville Tap
X Wind Farm
R55 R122 R173
X
Wethersfield
R199
500kVA
open
closed
Y
in reclosing
cycle Boxler Farm
Scenario - permanent fault between R55 and R12
51
© 2015 Electric Power Research Institute, Inc. All rights reserved.
• X and Y opened by 34.5kV voltage protection before first reclose of R55
• R55 in reclosing cycle
Orangeville Tap
X Wind Farm
R55 R122 R173
X
Wethersfield
R199
500kVA
open
closed
Y
in reclosing Boxler Farm
cycle Scenario - permanent fault between R55 and R12
52
© 2015 Electric Power Research Institute, Inc. All rights reserved.
• R55 locks out
Orangeville Tap
X Wind Farm
R55 R122 R173
X
Wethersfield
R199
500kVA
open
closed
Y
in reclosing Boxler Farm
cycle Scenario - permanent fault between R55 and R12
53
© 2015 Electric Power Research Institute, Inc. All rights reserved.
• R122, R173, and R199 open
Orangeville Tap
X Wind Farm
R55 R122 R173
X
Wethersfield
R199
500kVA
open
closed
Y
in reclosing Boxler Farm
cycle Scenario - permanent fault between R55 and R12
54
© 2015 Electric Power Research Institute, Inc. All rights reserved.
• Both battery systems come back online and close X & Y
Orangeville Tap
X Wind Farm
R55 R122 R173
X
Wethersfield
R199
500kVA
open
closed
Y
in reclosing Boxler Farm
cycle Scenario - permanent fault between R55 and R12
55
© 2015 Electric Power Research Institute, Inc. All rights reserved.
• R199 will close using hot bus – dead line
Orangeville Tap
X Wind Farm
R55 R122 R173
X
Wethersfield
R199
500kVA
open
closed
Y
in reclosing Boxler Farm
cycle Scenario - permanent fault between R55 and R12
56
© 2015 Electric Power Research Institute, Inc. All rights reserved.
• R173 will close using sync-check
• Complete island established
Orangeville Tap
X Wind Farm
R55 R122 R173
X
Wethersfield
R199
500kVA
open
closed
Y
in reclosing Boxler Farm
cycle Scenario - permanent fault between R55 and R12
57
© 2015 Electric Power Research Institute, Inc. All rights reserved.
• Fault is removed and R55 manually closed
Orangeville Tap
X
Wethersfield
R199
500kVA
open
closed
Y
in reclosing Boxler Farm
cycle Scenario - permanent fault between R55 and R1
58
© 2015 Electric Power Research Institute, Inc. All rights reserved.
• R122 closes sync-check
• System normal
Orangeville Tap
X
Wethersfield
R199
500kVA
open
closed
Y
in reclosing Boxler Farm
cycle Scenario - permanent fault between R55 and R12
59
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Recommendations - Protections
• Low voltage current based protection (e.g. 4.8kV feeders) will have to be
evaluated based on energy storage devices capability to source fault current
or alternative protection should be investigated – not addressed in this section
• Setting and reclosing setting changes needed on R55 and R173 as well as the
additional protection & control described in this section for microgrid operation
60
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Proposed Protection, Monitoring, & Control
Modifications
WNY Wind
Corp. 6.6 MW
0.1 mi
J192
Attica Prison
Wethersfield STA. 23
Thevenin equivalent 34.5 kV
source for Orangeville STA. 19
R199
Attica substation 4.8 kV
Orangeville 4.8-kV
PQ48V Wethersfield STA. 23
circuit and load
4.0 mi 4.8 kV
PQ48B
Boxler Farm Wethersfield 4.8-kV
480V, 416 kW Boxler DG circuit and load
4.8 kV
61
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Proposed System Level Modifications – Energy Storage
System
Proposed
Existing 34.5 KV Proposed Existing
34.5 KV recloser
recloser recloser recloser
Proposed
1 MWHR Energy
Storage Wind plant : 6.6 MW
Sync DG:
Microgrid OW –
0.416 MW Orangeville & Wethersfield
WNY Wind
Corp. 6.6 MW
Cooper Form
SEL PG10 Type 6
Attica Attica Prison Orangeville STA. 19
STA. 12 STA. 34.5 kV
R55 R122 R173
34.5 kV 1.12 mi 6.3 mi 0.2 mi 6.1 mi Vestas TAP
34.5 kV
0.1 mi
J192
Attica Prison
Wethersfield STA. 23
Thevenin equivalent 34.5 kV
source for Orangeville STA. 19
R199
Attica substation 4.8 kV
Orangeville 4.8-kV
PQ48V Wethersfield STA. 23
circuit and load
4.8 kV
4.0 mi
PQ48B
Boxler Farm Wethersfield 4.8-kV
480V, 416 kW circuit and load
Number of Monitor Samples/cycle Voltage level Actual Fault Circuit Data useful for
events location model fault location
63
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Line Exposed to Faults in Grid Connected Mode
Scenario G1: Multiple single line-to-ground faults applied in Line Section 1, between reclosers R55 and R122
Scenario G2: Multiple single line-to-ground faults applied in Line Section 2, between reclosers R173 and R199
Scenario G3: Multiple line-to-line faults applied in Line Section 3, between PQ48V and PQ48B
WNY Wind
Corp. 6.6 MW
0.1 mi
J192
Attica Prison
Wethersfield STA. 23
Thevenin equivalent 34.5 kV
source for Orangeville STA. 19
R199
Attica substation 4.8 kV
Orangeville 4.8-kV
PQ48V Wethersfield STA. 23
circuit and load
4.8 kV
Section 3
Line
4.0 mi
PQ48B
Boxler Farm Wethersfield 4.8-kV
480V, 416 kW Boxler DG circuit and load
4.8 kV
64
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Line Exposed to Faults in Microgrid Operation
Scenario OW1: Multiple line-to-line faults applied in Line Section 2, between reclosers R173 and R199 (in
Microgrid OW operation)
Scenario OW2: Multiple line-to-line faults applied in Line Section 3, between PQ48V and PQ48B (in Microgrid
OW operation)
Scenario O1: Multiple line-to-line faults applied in Line Section 3, between PQ48V and PQ48B (in Microgrid O
operation)
Orangeville STA. 19
34.5 kV
R122 R173
0.2 mi 6.1 mi Vestas TAP
Line Section 2 34.5 kV Orangeville STA. 19
0.1 mi 4.8 kV
J192
Orangeville 4.8-kV
Line Section 3
Wethersfield STA. 23 circuit and load PQ48V
Orangeville STA. 19 34.5 kV Orangeville
4.0 mi
4.8 kV Energy Storage
R199
Orangeville 4.8-kV
Wethersfield STA. 23
Line Section 3
Energy Storage
PQ48B
Boxler Farm
PQ48B 480V, 416 kW Boxler DG
Boxler Farm Wethersfield 4.8-kV 4.8 kV
480V, 416 kW Boxler DG circuit and load Wethersfield
4.8 kV Energy Storage
WNY Wind
Corp. 6.6 MW
0.1 mi
J192
Attica Prison
Wethersfield STA. 23
Thevenin equivalent 34.5 kV
source for Orangeville STA. 19
R199
Attica substation 4.8 kV
Orangeville 4.8-kV
PQ48V Wethersfield STA. 23
circuit and load
Line Section 3
4.8 kV
4.0 mi
PQ48B
Boxler Farm Wethersfield 4.8-kV
480V, 416 kW circuit and load
Line Section 2 One-ended methods (R173) Simple reactance, Takagi, Novosel et al.
67
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Case Study #3: Secondary Network
Models developed in
OpenDSS, EMTP-RV, &
Power Factory
68
© 2015 Electric Power Research Institute, Inc. All rights reserved.
One Line Diagram
69
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Scenarios
(44X_10384)
(44X_M1048)
(44X_M1049) (44X_10385)
10384
M1048
3. Large-scale Central CHP unit (large M1047
(44X_M1047)
Inverter
Inverter
synchronous machine) + small
scale PV + Large-scale central VS4007
(44X_VS4007)
VS3998
(44X_VS3998)
0.15 MVA 0.15 MVA
storage
Inverter
Inverter
303 Vernon Ave 303 Vernon Ave
(5766.44X_BC3998) (5916.44X_BC3998)
5. 100% Large CHP unit (large kVA = 140.5 kVA = 310.728
synchronous machine)
6. 100% Large CHP unit (large
synchronous machine behind an
inverter)
70
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Assumptions
71
© 2015 Electric Power Research Institute, Inc. All rights reserved.
General philosophy used
Determine the required level of selectivity for different fault scenarios. Generally, this
can be determined by considering the impact to the customers for different grid faults.
Group parallel cables connecting common LV nodes together into single ’branches’
Split the Microgrid into separate regions/zones which with appropriate protection
grading will achieve the desired selectivity.
Ensure LV grid relays protecting branches directly connected to customers trip first to
remove the fault from the remaining healthy grid as quickly as possible
Ensure some time delay between tripping of customer branches and any
interconnector circuits connecting together main LV nodes
Ensure customer relays trip last to ensure healthy generation remains in service post
fault
72
© 2015 Electric Power Research Institute, Inc. All rights reserved.
High selectivity protection zones
73
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Grid Connected Mode – Summer Peak Steady
State Branch Currents and Bus Voltages
From Current Loading
Line ID To Bus
Bus (A) (%)
sec_6643_1 143 17%
sec_6643_2 143 17%
10385 M1047
sec_6644_1 159 20%
sec_6644_2 159 20% Phase A Phase B Phase C
Bus ID
sec_6645_1 129 16% (pu) (pu) (pu)
sec_6645_2 129 16% M1048 0.98 0.98 0.98
sec_6646_1 M1047 M1048 115 14% 10384 0.96 0.96 0.96
sec_6646_2 115 14% 10385 0.97 0.97 0.97
sec_6646_3 115 14% BC3998 0.99 0.99 0.99
sec_6649_1 213 25% M1049 0.96 0.96 0.96
sec_6649_2 M1048 10384 213 25% M1047 0.97 0.97 0.97
sec_6650_1 239 29% VS8360 0.98 0.98 0.98
sec_6651_1 M1049 10384 0 0% VS4007 0.99 0.99 0.99
sec_6751_1 249 29% VS3998 0.99 0.99 0.99
sec_6751_2 BC399 249 29%
M1048
sec_6751_3 8 249 29%
sec_6751_4 249 29%
sec_6754_1 244 29%
sec_6754_2 244 29%
VS8360 M1048
sec_6754_3 244 29%
74
sec_6754_4 244
© 2015 Electric Power29%
Research Institute, Inc. All rights reserved. 74
Summer Peak Steady State and Fault Induced Bus Voltages –
Grid Connected & Islanded
Summer Load Fault @ 10384 Fault @ BC3998 Fault @ M1048
Bus ID Phase Phase Phase Phase Phase Phase Phase Phase Phase Phase Phas Phas
A B C A B C A B C A eB eC
M1048 0.98 0.98 0.98 0.69 0.69 0.69 0.37 0.37 0.37 0.00 0.00 0.00
10384 0.98 0.98 0.98 0.00 0.00 0.00 0.66 0.66 0.66 0.47 0.47 0.47
In grid connected
10385 0.99 0.99 0.99 0.79 0.79 0.79 0.59 0.59 0.59 0.35 0.35 0.35
mode the0.98
BC3998 bus 0.98 0.98 0.79 0.79 0.79 0.00 0.00 0.00 0.32 0.32 0.32
M1047 0.99
voltages of un- 0.99 0.99 0.74 0.74 0.74 0.48 0.48 0.48 0.17 0.17 0.17
VS8360 0.99 0.99 0.99 0.73 0.73 0.73 0.46 0.46 0.46 0.14 0.14 0.14
faulted
VS4007
buses
0.99
are
0.99 0.99 0.86 0.86 0.86 0.33 0.33 0.33 0.55 0.55 0.55
non-zero
VS3998 0.99 0.99 0.99 0.80 0.80 0.80 0.04 0.04 0.04 0.35 0.35 0.35
Summer Fault @
Line ID From Bus To Bus Fault @ 10384 Fault @ M1048
Load BC3998
sec_6643_1 78% -75% -87% -92%
sec_6643_2
When islanded 78% -75% -87% -92%
10385 M1047
sec_6644_1 78% -75% -87% -92%
fault currents
sec_6644_2 78% -75% -87% -92%
decrease
sec_6645_1
for all 78% -75% -87% -92%
3-phase faults
sec_6645_2 78% -75% -87% -92%
When islanded
sec_6646_1 M1047 M1048 78% -75% -87% -92%
sec_6646_2
line loading 78% -75% -87% -92%
sec_6646_3 78% -75% -87% -92%
increases for
sec_6649_1 -31% -82% -85% -90%
most
sec_6649_2
line
M1048 10384 -31% -82% -85% -90%
sections
sec_6650_1 -31% -82% -85% -90%
sec_6751_1 279% -86% -88% -95%
sec_6751_2 279% -86% -88% -95%
M1048 BC3998
sec_6751_3 279% -86% -88% -95%
sec_6751_4 279% -86% -88% -95%
Total Fault Current at the Fault Location (%) -89% -93% -93%
76
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Modeling Existing Protection
77
© 2015 Electric Power Research Institute, Inc. All rights reserved.
Findings and recommendations: Current-Limiting Protection
Normally the Current limiter (CL) fuse will “melt” when the
current in the fuse element exceeds the current specified by
the fuse’s melt characteristic.
Circuit breakers
Directional-
Overcurrent
79
© 2015 Electric Power Research Institute, Inc. All rights reserved. 79
3 Phase Fault @ 10384
80
© 2015 Electric Power Research Institute, Inc. All rights reserved. 80
3 Phase Fault @ 10384
1
1. D/O module between 10384 and
M1048 trips on overcurrent
2. Circuit breaker at 10384 PCC trips
on overcurrent
81
© 2015 Electric Power Research Institute, Inc. All rights reserved. 81
3 Phase Fault @ 10384
Isolated
82
© 2015 Electric Power Research Institute, Inc. All rights reserved. 82
3 Phase Fault @ 10384
83
© 2015 Electric Power Research Institute, Inc. All rights reserved. 83
1 Phase Fault @ 10384
84
© 2015 Electric Power Research Institute, Inc. All rights reserved. 84
1 Phase Fault @ 10384
1
1. D/O module between 10384 and
M1048 trips on overcurrent
2. Circuit breaker at 10384 PCC trips
on overcurrent
85
© 2015 Electric Power Research Institute, Inc. All rights reserved. 85
1 Phase Fault @ 10384
Isolated
86
© 2015 Electric Power Research Institute, Inc. All rights reserved. 86
1 Phase Fault @ 10384
87
© 2015 Electric Power Research Institute, Inc. All rights reserved. 87
1 Phase Fault (46.6 mΩ) @ 10384
88
© 2015 Electric Power Research Institute, Inc. All rights reserved. 88
1 Phase Fault (46.6 mΩ) @ 10384
1
1. D/O module between 10384 and
M1048 trips on overcurrent
2. Circuit breaker at 10384 PCC trips
on overcurrent
89
© 2015 Electric Power Research Institute, Inc. All rights reserved. 89
1 Phase Fault (46.6 mΩ) @ 10384
Isolated
90
© 2015 Electric Power Research Institute, Inc. All rights reserved. 90
1 Phase Fault (46.6 mΩ) @ 10384
91
© 2015 Electric Power Research Institute, Inc. All rights reserved. 91
Phase-Phase Fault @ 10384
92
© 2015 Electric Power Research Institute, Inc. All rights reserved. 92
Phase-Phase Fault @ 10384
1
1. D/O module between 10384 and
M1048 trips on overcurrent
2. Circuit breaker at 10384 PCC trips
on overcurrent
93
© 2015 Electric Power Research Institute, Inc. All rights reserved. 93
Phase-Phase Fault @ 10384
Isolated
94
© 2015 Electric Power Research Institute, Inc. All rights reserved. 94
Phase-Phase Fault @ 10384
95
© 2015 Electric Power Research Institute, Inc. All rights reserved. 95
Phase-Phase-Ground Fault @ 10384
96
© 2015 Electric Power Research Institute, Inc. All rights reserved. 96
Phase-Phase-Ground Fault @ 10384
1
1. D/O module between 10384 and
M1048 trips on overcurrent
2. Circuit breaker at 10384 PCC trips
on overcurrent
97
© 2015 Electric Power Research Institute, Inc. All rights reserved. 97
Phase-Phase-Ground Fault @ 10384
Isolated
98
© 2015 Electric Power Research Institute, Inc. All rights reserved. 98
Phase-Phase-Ground Fault @ 10384
99
© 2015 Electric Power Research Institute, Inc. All rights reserved. 99
3 Phase Fault @ M1048
100
© 2015 Electric Power Research Institute, Inc. All rights reserved. 100
3 Phase Fault @ M1048
1 3
Isolated
102
© 2015 Electric Power Research Institute, Inc. All rights reserved. 102
3 Phase Fault @ M1048
103
© 2015 Electric Power Research Institute, Inc. All rights reserved. 103
3 Phase Fault @ BC3998
104
© 2015 Electric Power Research Institute, Inc. All rights reserved. 104
3 Phase Fault @ BC3998
105
© 2015 Electric Power Research Institute, Inc. All rights reserved. 105
3 Phase Fault @ BC3998
Isolated
106
© 2015 Electric Power Research Institute, Inc. All rights reserved. 106
3 Phase Fault @ BC3998
107
© 2015 Electric Power Research Institute, Inc. All rights reserved. 107
3 Phase Fault @ 10385
108
© 2015 Electric Power Research Institute, Inc. All rights reserved. 108
3 Phase Fault @ 10385
109
© 2015 Electric Power Research Institute, Inc. All rights reserved. 109
3 Phase Fault @ 10385
Isolated
110
© 2015 Electric Power Research Institute, Inc. All rights reserved. 110
3 Phase Fault @ 10385
111
© 2015 Electric Power Research Institute, Inc. All rights reserved. 111
Summary
“Microgrids” brings many technical needs: Good PSA tools available
• Objective Controllability
• Scenarios Monitoring
• Modeling Reliability
113
© 2015 Electric Power Research Institute, Inc. All rights reserved.