Sei sulla pagina 1di 5

TCS-200

Software and Tools

Programming and Control


Software for the
TSA-200 / TSA-200X

Technical Manual

TELEFIRE FIRE & GAS DETECTORS LTD


PO Box 7036
Petach Tikva 49250
Israel
Tel: 972 3 921 1955 TCS-
TCS-200En
200En100
En100.pdf
100.pdf
Fax: 972 3 921 1816
eMail: marketing@telefire.co.il Revision 1.00
Web: www.telefire.co.il June 2011
Prerequisites
TCS-200 version 1.0.2

Note
i The terms “Trouble” as used in NFPA 72 guideline and UL standards and
“Fault” as used in EN 54 standards are used interchangeably throughout this
manual.

Note
i Do not install, operate, and maintain this product before fully reading this
manual.

© 2011 Telefire Fire & Gas Detectors Ltd.


TCS-200
© 2011 Telefire Fire & Gas Detectors Ltd Revision 1.00 June 2011

1 Introduction
The TCS-200 is PC-based software that allows the configuration of TSA-200 /
TSA-200X features that are not configurable from the control panel's keyboard.
Note
i It is only possible to change the operator and programmer's passwords on a
TSA-200.

2 Compatibility
2.1 Control Panels
The TCS-200 is compatible with the TSA-200 and TSA-200X control panels.

2.2 Pre-Requisites
The TCS-200 requires windows XP and above, and a GSRS-232 Adapter.

3 Installation
Run the setupTCS200-v1.0.2.0.exe file and follow the on-screen instructions.

4 Running the TCS-200 Software


Connect the GSRS-232 to the TSA-200 / TSA-200X (see Figure 1) and to your PC's
RS-232 port. Use a USB to RS-232 adapter if necessary. The control panel may display
a ground-fault error when a PC is connected to it. This will not interfere with the
software or its configuration.
The current parameters are read from the control panel and are displayed on the
TCS-200.

Figure 1 Connecting the GSRS-232


Double-click on the TCS-200 icon to run the software.

– Page 1 of 3 –
TCS-200
© 2011 Telefire Fire & Gas Detectors Ltd Revision 1.00 June 2011

Figure 2 Log In Screen


Enter the user name (Telefire) and the password (9241) to get to the program's main
screen (see Figure 3).

Figure 3 TCS-200 Screen

4.1 Version
This field shows the software version of the control panel.

– Page 2 of 3 –
TCS-200
© 2011 Telefire Fire & Gas Detectors Ltd Revision 1.00 June 2011

4.2 Operator password


This field allows you to change the operator's password (required to gain level 2 Access
as per EN 54-2).
The factory default value is 1111.
Enter four digits. Valid numbers are 1 – 6.

4.3 Programmer password


This field allows you to change the programmer's password (required to gain level 3
Access as per EN 54-2).
The factory default value is 2222.
Enter four digits. Valid numbers are 1 – 6.

4.4 Delay before release


This field allows you to change the delay before extinguishant release. The default
value is 30 seconds, and can be set from 5 to 50 seconds in 5 second steps.
Note
i This field only sets the delay before extinguishing release. It does not
change whether extinguishing release will be delayed or not. You will need to
manually set the TSA-200X to delayed extinguishing via the front panel and
keyboard.

4.5 Extinguishing pulse duration


This field allows you to change the extinguishant release pulse duration. The default
value is 20 seconds, and can be set from 5 to 495 seconds in 5 second steps.

4.6 Telecom type


This field sets whether the activation condition for output 2 (Out 2 on the main board) is
alarm or extinguishant release.

4.7 Manual exting delay


This field allows changing the delay for the Manual Release Input (In 4). The default
delay is no delay (immediate activation). You can set the delay to 30 seconds by setting
this field to Yes.

4.8 Download
Press the Download button to save the changed settings to the control panel.

– Page 3 of 3 –