Sei sulla pagina 1di 19

Air Mixing Handbook

How to Identify and Eliminate Air Stratification Problems


with Properly Designed HVAC Mixing Systems

Published by Blender Products, Inc.


Table of Contents
Section Page Section Page
1. Introduction ..............................................................2 6. Indoor Air Quality (IAQ) Concerns.......................11
The Company ............................................................2 Outside Air Dampers Blocked Shut to Eliminate
Why this Manual Was Written...................................2 Stratification Problems ........................................11
Dilution of Fresh Ventilation Air Into the
2. Glossary of Basic Terminology ................................3
Supply-Air Stream...............................................11
3. Discussion of Stratification and Mixing..................4 Maintaining Minimum Ventilation Air Under
How Stratification Develops .....................................4 VAV Conditions...................................................11
How to Define Mixing Effectiveness ........................4
7. Application Guidelines for Static Mixing
4. Thermal-Stratification Problems and Solutions .....5 Devices ....................................................................12
Nuisance Freeze-Stat Trips........................................5 How Much Mixing is Enough? ...............................12
Poor Mixed-Air Control ............................................5 VAV Concerns .........................................................12
Wasted Energy Due to Sensor Error..........................5 Proper Placement of Mixers in HVAC Systems.....12
Averaging-Bulb Inaccuracy.......................................5 Effect of a Combination Filter/Mixing Box on
Poor Economizer Control ..........................................7 Mixing Performance............................................14
Excessive Reheat Coil Use........................................7
8. Velocity-Stratification Problems.............................15
Stratification Downstream of Face-and-Bypass
Coil Condensate Carryover .....................................15
Sections .................................................................7
Coil Inefficiency ......................................................15
Ineffective Refrigeration-Coil Control ......................8
Filter Loading, Damage, and Particle Bypass .........15
Stratified Steam-Coil Discharge................................8
Uneven Heating with Direct-Fired Burners ..............8 9. Application Guidelines for Velocity-Equalizing
Uneven Moisture Absorption Across Humidifiers ....8 Diffusers..................................................................16
Improper Filter Loading ............................................8 Distance Requirements............................................16
System-Effect Considerations .................................16
5. Water-Coil Freeze-Up Problems and Solutions ......9
Glycol Solutions ........................................................9 Bibliography.................................................................17
Unit Heaters in Mixed-Air Plenum ...........................9
Heat Recovery ...........................................................9
Draining Water Coils ...............................................10
Pumping Fluid at Subfreezing Outside
Air Temperatures.................................................10
Static Mixing Devices .............................................10

1
1 Introduction
The Company Why This Manual Was Written
Since 1962, Blender Products, Inc. (formerly known During its history, Blender Products has published a
as RM Products) has pioneered stratification great deal of material dealing with stratification and
abatement developments in air-handler mixing mixing in HVAC systems. This material has appeared
plenums and has been an innovator in the design of primarily in technical bulletins, catalogs and articles.
static mixers. To date, very little about stratification in the HVAC
environment has appeared in textbooks or journals.
Over the years, the applications personnel at Blender
Now, due to increased interest in adding ventilation
Products have developed mixing systems for
air to combat IAQ problems, there is an increasing
thousands of applications in HVAC systems and
need to solve the associated stratification problems.
industrial process systems. As a result, they have
accumulated a large storehouse of knowledge and To help meet this demand, Blender Products has
valuable expertise in the disciplines of stratification compiled a significant body of technical information
and static mixing. and outside source articles into a single manual. This
manual will prove to be an invaluable resource in the
design and troubleshooting of stratification systems.
Although this reference is a relatively complete text
in itself, a comprehensive study of stratification
would, of necessity, include an investigation of the
references listed in the bibliography.

2
2 Glossary of Basic Terminology
Average Temperature (tavg): The average of the Mixing Section: A factory-made enclosure, which
downstream temperatures. It is found using the includes one or more static air mixers, that is designed
following equation: to be mounted between sections of an air handling unit
n Where: and is supplied separately from the mixing box.
tavg = 1n • ∑ ti n = number of temperature readings
ti = Individual temperature readings Mixing System: The entire mixing system consisting
i=1 of the mixing/control dampers and any other mixing
Blow Through System: Usually refers to a system devices such as air mixers.
where the filter or coil is installed downstream of the Modified Range Mixing Effectiveness (ERdT): The
supply fan. Therefore the fan is “blowing” through absolute amount, expressed as a percentage, that a
the coil or filter. mixing box or static air mixer reduces the temperature
Combination Mixing/Filter Box: A factory-made spread entering the mixing device. It is typically used
section that includes filters within the mixing box. in determining the freeze protection afforded by a
mixing system. See Section 3, page 4.
Economizer System: An air-side economizer system
uses the outside air for “free” cooling during times Range: The maximum temperature less the minimum
when the outside air conditions permit. temperature for a set of readings.
Range = (Tmax – Tmin)
Freeze Stat: A low-limit thermostat used to protect
hydronic coils from freezing by activating freeze Standard Deviation: A statistical calculation applied
protection sequences, such as air-handler shut down, to a set of data. In essence it is an average variation
in the air-handler control system. from the average data point. For thermal mixing
analysis the expression is as follows:
Inlet Temperature Difference (dT): The difference
n

[ ]
.5 Where:
∑(
in the temperatures between the two incoming air 1
streams. It is found using the following equation: SD =
n–1
Ti - Tm ) 2
n = Number of samples
Tm = Average temperature
i=1
Ti = Temperature measurement
dT = tHot – tCold Where: SD = Standard deviation
tHot = Temperature of hot air
tCold = Temperature of cold air Static mixing device: A mixing device fixed in
position generally consisting of baffles and blades
Mass Flow Rate (m): The mass flow rate of an air
arranged to induce mixing to a flow of water or air.
stream. It is found using the following equation:
m = ρ•A•v Where: Temperature Averaging Bulb: A control sensor
ρ = Air density (lbs/ft3) designed to read the average temperature across a
A = Area of duct (ft2) plenum by using a capillary tube or a special
v = Velocity of air stream (ft/min)
averaging wire approximately 15 to 25 feet long.
Mixing Box: A factory-made section that includes Theoretical Mixed Air Temperature: The mixed air
control dampers and may include one or more static temperature based on a calculation of the combined
air mixers. mass flow of two air streams. The theoretical mixed
Mixing Effectiveness: A means of quantifying air temperature is found using the following equation:
mixing in terms of “Range” or “Standard Deviation” mhot • Thot + mcold • Tcold
reduction across a static mixing device or other Tmix =
mhot + mcold
mixing system (see section 3).
Where:
mhot = Hot air mass flow (lbs/min)
mcold = Cold air mass flow
Thot = Hot air temperature (degrees F)
Tcold = Cold air temperature

3
3 Discussion Of Stratification And Mixing
How Stratification Develops actual, or theoretical, mixed-air temperature in the
mixed-air plenum. The latter is important to the proper
Stratification is normally thought of in terms of functioning of mixed-air thermostats and controls.
vertical temperature gradients. However, stratification
within an air handler is different. Momentum in the To simply state that a mixing system should provide
entering air streams as well as the combined flow a set range of temperatures for all entering air-stream
serves to hold the uneven profile of temperatures or conditions fails to recognize the variables mentioned
constituents as they are introduced into the combined above. This manual recommends using the “Mixing
flow (see Figure 5, page 8). Effectiveness” method of rating static mixing systems.
This method takes the entering temperature
One typical misconception about mixing box design differential into account when rating a particular
is the idea that cold air introduced high will drop due mixing system. The equation is as follows:
to density difference and mix with the warmer air

( )
RangeDS Where:
below. In reality, the momentum of the main air ERdT = 1– ERdT = Mixing effectiveness based on
stream is typically so much greater than the force due dT range
to the density difference that the cold air introduced RangeDS = Maximum temperature
difference at testing grid (°F,°C)
on top is simply carried downstream before it has dT = Temperature difference between
time to drop. In short, any potential mixing action return and outside air streams (°F,°C)
due to buoyancy forces are far less than the Furthermore, it is important to state the mixing
momentum of the stratified air stream. effectiveness required in relation to various outside
The primary conditions which produce stratification air ratios and temperatures. An example of the
in an air handler are as follows: characteristic curve of required mixing effectiveness
■ The mixing-box layout and damper size, relative as a function of percent outside air for various mixed
to the total plenum, greatly affect the degree of air temperatures is shown in Figure 1.
stratification for a given mixing system. 1.00

■ As the opposing air streams approach a 50/50 0.95


0.90
proportion, the mixing becomes more difficult.
0.85
Required Mixing Effectiveness (ERdT)

■ Most importantly, as the temperature differential


0.80

F
between the two streams increases, the range of 0.75 5°
F
°F
10
downstream air temperatures widens. 0.70 °F
TM

15
ix

0.65 °F
=4

20

Stratification is relatively easy to develop, however


F

0.60
°F
mixing two air streams together is neither automatic 0.55 25
50
°F

0.50
nor easy. Without some form of agitation or mixing
55

0.45
°F

a stratified air stream can continue many duct 30


°F
60°

0.40
diameters downstream.
F

0.35
0.30

How to Define Mixing Effectiveness 0.25


0.20 35°F
T OA=
In the absence of independently established standards 0.15
0.10
that define how effectively a mixing system is 0.05
performing, many “rule-of-thumb” standards have 0.00
been used. At a minimum, the HVAC mixing system 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 0.70 0.75

should mix two air temperatures sufficiently to Percent Outside Air (By Mass)
eliminate freeze-stat trips and frozen coils, thus at Note: Chart based on the following conditions:
least ensuring continued operation of the air handler. TRA = 75°F, TFZ = 37°F TOA = Outside air temperature

A more stringent performance standard defines how Figure 1 – Required mixing effectiveness vs. percent outside
close the mixed-air temperature range approaches the air for various temperatures to eliminate freeze-stat trips
when freeze-stat is set at TFZ = 37°F.

4
4 Thermal-Stratification Problems and
Solutions
Nuisance Freeze-Stat Trips Wasted Energy Due to Sensor Error
The low-level thermostat, also called a freeze stat, Substantial energy is wasted by undetected errors
is designed with a long element that will trip if any originating at the mixed-air temperature sensor.
portion of the element is exposed to a temperature The most common cause for error is temperature
below the set point. The set point is typically between stratification within the mixing plenum2. This
35 and 38 degrees F. Although the coil protection potential error has been accentuated by the use of
provided by a low-limit thermostat is often beneficial, single-point electronic temperature sensors in large
the continuous trip out and resulting air-handler shut mixing plenums. It is very difficult to place a single
down can be a headache for the building facilities temperature sensor in a position where it will read
people. the average temperature of the ever-changing
temperature profile downstream of mixing dampers.
Whenever a “nuisance” trip of the freeze-stat occurs
Another source of error is a thermostat that is out
the building facilities staff gets the job of modifying
of calibration.
the system to eliminate the pesky problem. Often, in
an attempt to solve the problem, the outside air
dampers are wired shut or otherwise disabled to Averaging-Bulb Inaccuracy
eliminate cold, outside air altogether. Obviously, this A common solution to the stratification problem
so-called solution will not allow the proper amount of has been to place an averaging style temperature
ventilation air into the building. Major problems with sensor on the face of the filter or coil downstream
the indoor air quality will result (see section 6). The of the mixing plenum. This solution has some merit,
other common method of eliminating the problem is provided the sensor capillary or wire is properly
to disable or move the freeze-stat. This “solution” mounted so that it will record a representative
can, of course, meet with catastrophic results should sampling of temperatures. However, taking only
a freezing condition occur. the temperature value at a series of points ignores
the effect of varying velocity or mass flow across
Poor Mixed-Air Control the sample area. In the ASHRAE Fundamentals
In the past, HVAC mixing applications did not Handbook, Chapter 13, titled Measurements and
demand strict performance requirements. As long as Instruments3, the Sampling and Averaging section
the air-handling unit did not shut down, or a water coil warns against assuming that a sampling of
did not freeze due to stratification, the mixing was temperatures accurately represents the average
assumed to be satisfactory. However, with the advent temperature at a cross-section of a flowing stream.
of DDC and as control systems become more precise, The Section goes on to suggest that a weighted
the problems of an improper sensor read become more mass-flow average be taken across the stream to
pronounced. The root cause of sensor error can often determine the true temperature of the air stream.
be traced to a stratification problem in the mixed air In an effort to show the potential error for an
plenum1. The following sections address some of the averaging-bulb sensor applied to a mixing box
problems created by temperature stratification in the with a non-uniform velocity profile, a study was
control system of a typical HVAC installation. performed at Blender Products. A 25-foot capillary-

1
Coggan, Donald, P.E., “Mixed Air Control with DDC,” Heating/Piping/Air Conditioning, May 1986.
2
Kato, James Y. “Sensor Errors,” AHSRAE Journal, Volume 27, No. 1, American Socity of Heating, Refrigeration and Air Conditioning
Engineers, Inc., Atlanta, Georgia – January, 1985.
3
ASHRAE Fundamentals Handbook, 1985 – Chapter 13, “Measurements and Instruments,” American Society of Heating, Refrigeration and
Air Conditioning Engineers, Inc., Atlanta, Georgia – 1985.

5
tube averaging-bulb sensor was mounted to a test
grid as shown on the test setup drawing. Individual
temperature and velocity readings were taken at 25
Averaging-Bulb Test Results
points across the grid, providing data to calculate the Temperature and Velocity Traverse Without Air Blender Units
weighted mass average using the following equation4:
F° 90.8 103.5 109.2 100.1 87.1 77.2
Equation 1a Equation 1b FPM 125 50 50 38 50 162
Mass Flow Based Simplified Velocity Based F° 86.7 104.0 105 90.4 86.5 78.4
n n

Tmix = ∑
FPM 125 150 200 125 250 500
1
Tmix = m ∑ miTi i=1
TiVi
n F° 79.4 84.9 86.1 82.2 77.3 75.4

t
i=1 Vi FPM 650 600 475 675 625 925
Where: Where: i=1 F° 69.3 71.1 71.2 73.2 72.7 69.4
Tmix = Mixed air temperature Tmix = Mixed air temperature FPM 900 1000 975 1200 1050 1075
mt = Total mass flow (lbs/min) Ti = Individual temperature
mi = Mass flow in partial areas Vi = Individual velocity Total Flow = 12,500 CFM Tavg = 84.6°F
Ti = Individual temperature sample in equal areas THot = 133°F Tmix = 76.9°F
n = Number of readings TCold = 68°F Error = Tavg - Tmix = 7.7°F
DT=(TH-TC) = 65°F
The first test was run for a standard mixing box.
A second test was run with a static mixer installed as
Temperature and Velocity Traverse With Air Blender Units
shown in Figure 2. The results are shown in Table I.
F° 90.7 89.8 81.5 83.3 91.3 91.1
Return Air Dampers FPM 475 525 500 650 575 525
F° 91.7 92.9 84.3 80.6 95.0 89.2
36" FPM 450 375 525 575 400 450
F° 102.7 93.2 84.7 81.8 88.1 89.5
Outside Air FPM 500 300 500 525 300 300
Dampers
F° 83.6 83.3 75.6 75.4 79.3 75.2
FPM 425 400 350 325 350 425

Total Flow = 12,500 CFM Tavg = 86.6°F


Test THot = 139°F Tmix = 86.5°F
Sensor
Grid TCold = 68°F Error = Tavg - Tmix = 0.1°F
® DT=(TH-TC) = 71°F
Patented Air Blender
Figure 2 – Test setup to determine error in an averaging- Tavg = Arithmetic average temperature based on multipoint
bulb sensor. or averaging bulb sensor.
In these tests, the averaging bulb was placed in Tmix = Velocity weighted mixed air temperature based on
12 different paths. From Table II (see page 7), it equations 1a and 1b as shown above.
can be seen that some paths were more accurate
than others. Overall, the error was greatest when Table I – Averaging-bulb test results.
the velocity profile across the bulb was non-uniform.
The study clearly demonstrated that non-uniform
velocity across an averaging bulb will cause the
mixed-air sensor to falsely represent the mixed-air
temperature. In short, an averaging bulb can only
sense the temperature. It cannot sense the mass flow
across a section. Therefore, it is important to mix
the air-stream temperatures and diffuse the velocity
evenly across an averaging bulb to provide the most
accurate temperature reading.
4
ASHRAE Standard, 41.1-1986 “Standard Method for Temperature Measurement,” American Society of Heating, Refrigeration and
Air Conditioning Engineers, Inc., Atlanta, Georgia – 1987.

6
to squeeze as much free cooling from the outside air
1
by using only cool air and exhausting all the return air.
Path No Mixer 2 With Static Mixer2 For instance if the return-air damper leaks 12% into
Tavg Tmix Error Tavg Tmix Error the mixing plenum, the mixed air will be 55 degrees F
1 88.10 76.90 11.20 85.50 86.50 -1.00
when the outside air is only 51 degrees F. This
effectively shuts down the economizer cycle at 51
2 82.40 76.90 5.50 88.00 86.50 1.50
degrees, or 4 degrees higher than necessary. In a city
3 90.10 76.90 13.20 84.30 86.50 -2.20
like Omaha, this premature shut-down results in a loss
4 87.30 76.90 10.40 87.80 86.50 1.30
of 580 hours of potential free cooling. It also causes
5 87.30 76.90 10.40 83.50 86.50 -3.00
earlier start-up of mechanical cooling equipment.
6 80.20 76.90 3.30 85.80 86.50 -0.70
7 91.80 76.90 14.90 89.90 86.50 3.40 In order to keep economizers operating at maximum
8 80.90 76.90 4.00 90.00 86.50 3.50 efficiency, mixing systems must have tight seals on
9 88.40 76.90 11.50 88.90 86.50 2.40 both outside- and return-air dampers to insure positive
10 84.30 76.90 7.40 90.90 86.50 4.40
shut-off of either air stream.
11 87.80 76.90 10.90 89.40 86.50 2.90
12 82.70 76.90 5.80 84.10 86.50 -2.40 Excessive Reheat Coil Use
Average Error 9.04 0.84 Reheat coils are routinely used to heat the air
downstream of the mixed-air plenum. Often these
1
The 12 paths used are representative of paths used in a coils are controlled by an outside-air sensor and
typical system.
will run continuously at subfreezing temperatures.
2
Error is determined by using this equation: Error=Tavg-Tmix Obviously, this wastes large amounts of energy.
Additionally, if the heating-coil valve cannot be
Table 2 – Error comparison with and without static mixer. turned down sufficiently, the cooling-coil valve may
open, or outside air may be introduced, wasting
additional energy.
Poor Economizer Control
Generally, an air-side economizer offers free cooling Stratification Downstream of
when outside air temperatures fall below 50 degrees F,
provided the dew-point temperature is low enough. Face-and-Bypass Sections
Most economizers operate well down to about Face-and-bypass sections provide a good way to
35 degrees F. However, as the outside air temperature control temperature and humidity in the air handling
approaches freezing, the freeze stat is likely to trip. system. However, control of the discharge temperature
When this happens, the economizer is often abandoned downstream of a face-and-bypass coil is difficult
in the interest of keeping the unit operational. In the when the bypass air is located at the top or bottom of
absence of free cooling, the mechanical cooling the coil. A means of mixing the two air streams should
system is often used. This not only wastes energy, it be incorporated to assure proper control of the damper
also robs the building of fresh air during sub-freezing modulation, as shown in Figure 3.
temperatures. A properly operating mixing system
extends the economizer operation time. Bypass

Economizer systems may also be abandoned for Air


ineffective operation as the outside air temperature Flow

approaches the mixed-air set point. The problem often


stems from a leaky return-air damper. Leaking return- Coil
air dampers can allow up to 15% of the warmer return
air into the mixing plenum, thereby causing the
mixed-air temperature to rise 5 degrees F or more. Figure 3 – Internal face-and-bypass with Air Blender static
For an economizer to function properly, it is important mixer to mix bypass air with coil discharge air, or to diffuse
bypass air across a plenum.

7
Ineffective Refrigeration-Coil Control Uneven Moisture Absorption Across
A staggered DX refrigeration coil-array will often Humidifiers
create stratified temperatures downstream, making Temperature stratification can create problems with all
it difficult for the discharge thermostat to sense the plenum-mounted humidification systems. Normally,
average temperature. A high reading will cause the the cooler the air stream the longer the vapor travel
compressor to operate excessively and can lead to a downstream as shown in Figure 5. This condition
coil condensate freeze-up. A cold reading will result may cause problems such as air-filter saturation or
in unnecessarily high supply-air temperatures and condensation on turning vanes or duct walls. The
resulting loss of the cooling load. Furthermore, the best solution is to insure that the temperature of the
resulting stratified air streams will often persist into air stream is homogeneous and sufficient to absorb
and through a tee fitting downstream resulting in the moisture.
cooler air flowing down one duct and warmer air
Hot TRA
flowing down the other duct. This condition creates
significant control and comfort problems.

Stratified Steam-Coil Discharge


TOA Cold
Steam coils often result in a 20 to 50 degrees F
stratification. This stratified state creates problems
when a single downstream sensor is used to control
the coil valve. Control hunting is the usual result. The
addition of a static mixing device downstream has
proven effective in providing more precise steam-coil
Extended Vapor Travel in
control. In addition, it results in more homogenous Cold Area of Plenum
temperatures across processes downstream.
Figure 5 – Extended vapor travel in a stratified plenum.

Uneven Heating with Direct-Fired


Improper Filter Loading
Burners
A potential problem with stratified air streams in the
The temperatures downstream of a direct-fired burner, mixing plenum is uneven filter loading. This occurs
which combines hot combustion gases with the air to when one air stream has a greater particulate
be heated (Figure 4), are highly stratified. The air concentration than another. An example would be
stream requires some form of mixing to ensure homo- a street-level outside air intake that would introduce
geneous temperatures at the controlling temperature larger amounts of particulate than the indoor air
sensor, as well as for any process downstream. Static stream. If the outside air stream is not adequately
mixers are ideal choices for these applications. They mixed with the return air stream, the filter will have
have been used with much success on many projects. a higher concentration of outside air particulate in
one localized area. This uneven loading may cause
Flame excessive velocities across the balance of the filter
face, which will result in inconsistent velocity across
Air the downstream coil. To insure proper filter loading,
Flow some form of mixing device should be used ahead of
the filter.

Figure 4 – Direct-fired burner with Air Blender device to


mix air with products of combustion.

8
5 Water-Coil
Solutions
Freeze-Up Problems and

The most troublesome problem arising from heat exchangers in the system. Figure 6 shows coil
stratification is hydronic-coil freeze-up. If the air derating as ethylene glycol concentration is increased.
handler is running and the mixing-damper-control
sequence is operational when the coil freezes, the Unit Heaters in Mixed-Air Plenum
freeze-up is most likely due to thermal stratification.
In addition to a functioning low-limit freeze stat, Unit heaters are sometimes placed in mixing plenums,
there are a number of ways to protect coils from as shown in Figure 7, in an attempt to maintain a
freezing. This section will explore the various options minimum mixed-air temperature and thus protect
to provide coil-freeze-up protection. against coil freeze up or freeze-stat trips. Although a
unit heater may be a reasonable way to heat the mixed
Glycol Solutions air plenum during air-handler shut down, it is largely
ineffective when the air handler is operational. The
Mixtures of ethylene or propylene glycol with water primary reason for this failure is inherent in the unit-
are often used to protect hydronic coils during heater design. They are designed to heat a relatively
subfreezing weather conditions. The advantage of static air space. However, a mixed-air plenum has air
glycol solutions is their ability to protect all flowing at 400 to 500 FPM. This leaves little time for
components under any situation. For example, if the the unit heater to turbulate the air stream. Furthermore,
any heat introduced into the air stream serves only to
Pressure Drop as % of Pressure Drop
at 0% Etylene Glycol Concentration

100
create more stratification downstream, thus creating
Capacity as % of Capacity at 0%
Ethylene Glycol Concentration

Capacity
90 150 problems for mixed-air sensors, freeze stats, and coils.
The only reasonable use for unit heaters in mixed-air
80 140 plenums is during air handler shut-down to protect
water coils from cold outside-air migration through
70 130 leaky outside-air dampers, as shown in Figure 8.
60 120

Pressure
50 110

40 100
0 10 20 30 40 50 60
Ethylene Glycol Concentration
in % by Weight
Figure 6 – Effects of various concentrations of ethylene
glycol.

power shuts down, and the outside air damper stays


open, the glycol mixture will protect the coil and
associated piping. However, there are a number of Figure 7 – Typical unit heater in plenum configuration,
disadvantages of using glycol as a freeze-protection without Air Blender unit.
additive. The higher viscosity requires increased
pump horsepower. In addition, the lower specific heat
constant inhibits heat transfer, which requires higher
Heat Recovery
water flow and/or larger heat-transfer surfaces. It is Heat-recovery systems can be beneficial in reducing
also important to point out that some provision for the problems of stratification by preheating the cold
volume expansion must be included to protect the outside air with warm exhaust air. These systems

9
tend to be costly and outside-air temperatures to prevent water-coil
are often difficult to freezing. This sequence is effective as long as the
design into a pump is properly maintained and the control system
restricted mechanical is functioning. The primary downside is the use of
layout because the additional pump horsepower and run time.
exhaust-air streams
must be brought to a Static Mixing Devices
single point and in
close proximity to the Static mixing devices, such as the one shown in
outside air stream. Figure 9, provide excellent freeze protection for
The benefits of this hydronic coils by continuously mixing the cold
type of system are in outside air into the warm
their potential to return air whenever air
recover otherwise is flowing across the
Figure 8 – Large bank of device. A static mixer
outside air dampers could cause wasted energy.
is the only option that
outside air migration.
provides excellent freeze
Draining Water Coils protection without the
need for maintenance.
A widely used practice to guard against water-coil Figure 9 – Typical static Furthermore, the device
freezing, is to drain the water and isolate the coil mixing device. provides a high degree
during periods of subfreezing weather. This method is of flexibility during seasonal changeovers, when
obviously effective when all the required maintenance chilled water cooling may be needed. In addition to
is done in a “timely” manner. Potential problems occur freeze protection, the static mixer provides a solution
when warmer-than-normal temperatures occur in early to problems created by stratified temperatures in the
spring or late fall (when the cooling coil is drained) mixed-air plenum. These include mixed-air control-
and the building requires mechanical cooling. sensor error and uneven air distribution across filters
and coils.
Pumping Fluid at Subfreezing A summary of various coil-protection alternatives is
Outside Air Temperatures shown in Table III.
Control systems are often designed with a control
sequence to turn on the water pumps at subfreezing

Consideration

Maintenance Reliability Flexibility Protection


Protection Attention Operating For Freeze During During AHU
Alternative First Cost Required Cost Protection Changeover Shutdown

Add Glycol High High High Med High Yes


Unit Heaters High Med Med Low Low Yes
Heat Recovery High Low Med Med High No
Drain Coil Low High Low Med Low Yes
Pump Fluid Low High Med Med High Yes
Below 32°F
Static Mixing Med None Med High High No
Device

Table III – Summary of coil-protection alternatives.

10
6 Indoor Air Quality (IAQ) Concerns
IAQ has become one of the most heavily discussed Without a static mixing device there is concern that
topics in the HVAC industry. This issue will affect outside ventilation air may stratify and favor one side
the HVAC industry, and the design of systems, for of a centrifugal fan or duct branch fitting. The end
years to come. The following section discuss how the result can be a greater percentage of outside air
application of ASHRAE Standard 62-1989 creates delivery to one portion of the building at the expense
new challenges for HVAC designers and building of the rest of the building. Obviously, the ventilation
engineers relative to stratification in the mixing system should be designed to properly diffuse the
plenum. ventilation air into the return air stream. Figure 10
shows such a design.
Outside Air Dampers Blocked Shut to
Eliminate Stratification Problems Maintaining Minimum Ventilation
Control malfunctions due to equipment failure or
Air Under VAV Conditions
improper maintenance procedures can cause IAQ ASHRAE Standard 62-1989 requires a minimum of
problems. As discussed earlier, a typical practice 15-20 CFM of ventilation air per person. This
involves disabling the outside air dampers, or blocking translates to about 15-20% fixed outside air based on
the damper shut, to eliminate freeze-stat trips or maximum airflow. If the 15% rate is used, and the
frozen-coil problems. One situation was documented supply airflow turns down to 30%, the proportion of
in which an outside-air intake was blocked shut by fixed outside air increases to 50% of the total air
a 2x4 to prevent the water coil from freezing in the supply, as shown in Figure 11. This increased
winter. However, the 2x4 was left in place for years, percentage of sub-freezing outside air gives rise to
preventing the controls from functioning5. freeze-stat trip and potential frozen coils. To guard
against freeze problems the heating coil is often
Return air
activated as soon as the outside air drops below
Air Blender static mixer insures that fresh air is freezing.
evenly distributed throughout supply airstream
100%
Actual Outisde Air (OA) Flow

90%

.
Without Air Blender,

OA
80%
fresh air and return air

.
OA
in
can stratify through M

A.
70%
in
Percentage

nO
coils, fans and branch M
25

.
%

A
take-offs downstream 60%
Mi

nO
20

A.
Mi
15

50%

nO
Fresh outside air %
10

Mi
40% 5%
30%

20%

10% Turn Down


Percentage
0%
Figure 10 – Design to 100% 90% 80% 70% 60% 50% 40% 30% 20% 10%
effectively diffuse Full Flow
Varying Supply Air (SA) Flow
ventilation air into the Fresh air is evenly
distributed in supply air
return air stream. Figure 11 – Outside air percentage based on fixed outside
air with varying supply air.
Dilution of Fresh Ventilation Air Into
The Supply-Air Stream
One of the principal concerns in the IAQ discussion
is the ability to prove that adequate and proportional
ventilation air is delivered to each building occupant.
5
Roberson, Wayne K. “Troubleshooting IAQ Troublespots,” Engineered Systems, July/August 1993.

11
7 Application Guidelines For Static Mixing
Devices
How Much Mixing is Enough? VAV Concerns
Mixing performance levels are defined in various The mixing performance of the Air Blender static
ways. Blender Products has chosen the range-mixing- mixing device requires a minimum amount of airflow
effectiveness method as the most definitive way to to maintain adequate mixing action. Generally, if the
rate a mixer’s ability to mix. Generally effectiveness velocity through the Air Blender mixer is 400 FPM
can be grouped into three categories. Low-efficiency or above, the mixer will perform properly, as shown
mixing includes standard mixing boxes available in Figure 13. Therefore, if a 3 to 1 turndown is desired,
on typical air handlers. Medium-efficiency mixing the design velocity through the mixing device should
systems include some form of static mixing device be no less than 1200 FPM.
mounted after the mixing box. High-efficiency 90%
systems include a specially designed damper
80%
configuration in combination with a static mixing
device to provide the highest possible level of mixing Effectiveness
70%
performance. Figure 12, taken from the article “How
Much Mixing is Enough?”6 provides a way to 60%

determine the level of mixing required to prevent 50%


freeze-stat problems. It should be stressed that these
levels represent the minimum mixing required. It is 40%

also necessary to provide good mixing to ensure 30%


proper mixed-air control performance. 200 400 600 800 1000 1200 1400
Mixed Air Temperature: 55 F
Feet Per Minute (FPM) Velocity
1.00 AAAAAAAAAAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA
AAAA
AAAAAAAA
AAAA3AAAA
AAAAAAAAAAAAAAAA
4
0 AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA
5% AAAAAAAAAAAA% AAAA
5

AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA
4
5 5

AAAAAAAA AAAAAAAAAAAAAAAAAAAAO AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA


5 0 % 6
%
AAAAAAAAAAAAOAAAAAAAAAAAAAAAA A AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA
%

Figure 13 – Air Blender performance under variable air-


0
A
0.95 AAAA
30 AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA
6
O %
O O 5

AAAA
%AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA
AAAAAAAA
AAAA
O AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
A

AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
A

AAAAAAAA
AAAAAAAA
AAAAAAAA
A

AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
O

AAAAAA
AA
%

AAAA A AAAA
A
O

AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAA
0.90 AAAA
AAAA
25 AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA
AAAA
%
AAAA AAAAAAAAAAAAHigh
AAAAAAAA AAAAAAAAAAAA AAAAAAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAAAAAAAAAAAA
AA
A

volume conditions.
Efficiency Mixing System Required
AAAAAAAA
O
A AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA
0.85 AAAA
AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA
20 AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA
AAAA
%AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA
AAAAAAAA
AAAA AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA
O
AAAA A AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA
7

0.80 AAAAAAAA AAAA


AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAA
0

AAAAAAAA AA
%

15%
AAAA
AAAAAAAA
AAAAAAAA
OA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAA
AA
Proper Placement of Mixers in HVAC
O

0.75 AAAAAAAA AAAAAAAAAAAA AAAA AAAA AAAA AAAAAAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAAAAAA AAAA AAAA AAAA AA
A

AAAAAAAA
AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA
AAAAAAAA
AAAAAAAAAAAA AAAA AAAA AAAA AAAAAAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAAAAAA AAAA AAAA AAAAAA
AA
AAAA
AAAAAAAA
AAAAAAAAAAAA AAAA AAAA AAAA AAAAAAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAAAAAA AAAA AAAA
AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA AAAA
AA
0.70 AAAA AAAAAAAAAAAA AAAA AAAA AAAA AAAAAAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAAAAAA AAAA AAAA AAAA AA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA AAAA
AAAAAAAA
AAAAAAAAAAAA
AAAAAAAA
AAAAAAAA AAAA
AAAAAAAAAAAA
AAAAAAAA
AAAAAAAA AAAA
AAAAAAAA
AAAAAAAA
AAAAAA
0.65
AAAAAAAA
AAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAAAAAA
AAAAMedium
AAAA
AAAAAAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAA
Efficiency
AAAAAAAAAAAAAAAA
AAAAAAAA
AAAA
AAAA
AAAAAAAA
AAAAAAAA
AAAA
Mixing
AAAAAAAA
AAAAAAAA
AAAASystem
AAAA
AAAAAAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAAAAAA
AAAA
AAAA
AAAAAAAA
AAAAAAAA
AAAA
Required
AAAAAAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AA
AAAAAA
AA
AA
AAAAAA
AA
7

%
Systems
AAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAA
AAAAAAAA
AAAA
AAAAAA
AAAAAAAA AA
0.60
O

AAAA
AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA AA
There are a number of constraints on the proper
A

AAAAAAAA
AAAAAAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAA
AA
0.55 AAAAAAAA
AAAAAAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAA
AA
AAAAAAAA AAAAAAAAAAAA AAAA AAAA AAAA AAAAAAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAAAAAA AAAA AAAA AAAA
AAAAAA
0.50
AAAAAAAA
AAAAAAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA
AA
AA placement of static mixers in an air-handling system.
0.45 The first is to ensure that each mixing unit is
Low Efficiency Mixing System Required
0.40 positioned so that a proportionate amount of each
0.35
stream is introduced into each mixer. It is also
0.30
important to provide the proper mixing distance
0.25

0.20
downstream so there is adequate time for the air
0.15 stream to turbulate after flowing through the mixing
0.10 blades. Normally the static mixing units are centered
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35
in the plenum top to bottom and side to side. Figure
Outside Air Temperature (°F)
14 shows correct and incorrect placements of static
mixers.
Figure 12 – Mixing required to prevent freeze-stat
problems.

6
Robinson, Keith D., P.E., “How Much Air Mixing is Enough?” Heating/Piping/Air Conditioning, November 1995.

12
Sketch 1 – Correct Placement

A Turning
Vanes
Patented
Air Blender Air
Units Filter Handler

Air
Flow

Patented
Air Blender
Units

Side Elevation Front View

Sketch 2 – Incorrect Placement

RA RA
Air Air
Filter Handler Filter Handler

RA RA

OA Air Flow

Air Flow OA OA

Top View Top View


OA

• Use only in one single line.


• Each Air Blender device must see equal amounts of damper area and air flow.
• Inlet ducts can cause an unequal effect on air flow. Fresh air and return air dampers should be the same length. Use turning vanes,
as shown in (A), to equalize flow across Air Blender units when air enters from the side.
• Mixing dampers must open so that air streams face each other.
•. When a minimum outside damper is used it must be the full width of the return air damper and supply equal amounts of air to each
mixer. Note that a minimum air damper is available as an option on the BlenderBox™ mixing box.
• Blender Products tests, plus independent lab tests, show that multiple mixer configurations do perform when applied properly.
• When looking at available mixers, always question whether they have been tested under all standard operating and installation
conditions, including:
– Multiple mixer configurations,
– VAV Systems to 33% turn-down.
• Sketch 2 shows two misapplications of multiple Air Blender units.
• Parallel or opposed blade dampers with blade axles across the short dimensions of the damper opening will cause air flow to favor
the side of the mixing plenum and should not be used with multiple Air Blender applications. Blade axles should be oriented across
the long dimensions of the damper opening as shown in Sketch 1.

Figure 14 – Comparison of correct and incorrect configurations when using static mixers.

13
Effect of a Combination Filter/Mixing reduction in mixing effectiveness, as shown in
Figure 15. The preferred method is to place the
Box on Mixing Performance static mixer before the filter section. This provides
Filters are sometimes placed in mixing boxes to better mixing and diffusion across the filter and the
save space in the air handler. Placing air filters in coil downstream.
this seemingly “unused” space causes a significant

Combination Filter/Mixing Box Standard Mixing Box with


Without Air Blender Blender Section and Filter
Mixing Efficiency = 45% Section Downstream
Lowest Temperature Mixing Efficiency = 80%
at Coil Face = 28°F Lowest Temperature
at Coil Face = 45°F

Standard Mixing Box with BlenderBox Mixing Box with


Filter Section Downstream Filter Section Downstream
No Air Blender Mixing Efficiency = 85%
Mixing Efficiency = 55% Lowest Temperature
Lowest Temperature at Coil Face = 47°F
at Coil Face = 32°F

Notes:
Lowest temperature at coil face is based on return air temperature = 75°F, outside air = 15°F, 55°F mixed air temperature.

Figure 15 – Comparisons of mixing effectiveness with various filter configurations.

14
8 Velocity-Stratification Problems
This section defines the problems that occur with an coil is applied in a system, the velocity across the coil
uneven velocity profile and suggests practical face is far from homogeneous. This is especially true
remedies to rectify these problems. if the coil is applied in a blow-through configuration
down-stream of a fan discharge. The effect of this
Coil Condensate Carryover velocity variation is difficult to quantify, but it is
obvious that performance will not be the same as that
When a coil begins to remove moisture from the air shown by the test data.
stream, water is formed as droplets on the coil fins.
Normally the droplets fall to a condensate drain pan
at the bottom of the coil and are drained away.
Filter Loading, Damage and Particle
However, if the velocity profile across the coil is Bypass
uneven some of the condensate will “spit off” and Velocity variations across a bank of filters often
miss the drain pan. This carryover causes problems cause the filters to load unevenly or in some cases
by wetting the downstream areas such as duct liner to be damaged. This improper loading, coupled with
and other equipment. Equalizing the velocity profile the high localized velocity, will often cause particle
is very important to ensure that the coil condensate bypass. Again, this condition occurs downstream of
stays on the face of the coil and drains harmlessly a fan discharge.
into the drain pan.

Coil Inefficiency
Non-homogeneous velocity through a coil also
degrades coil performance. Coils are generally tested
with even velocity across the face. However, when a

15
9 Application Guidelines For Velocity-
Equalizing Diffusers
In blow-through applications, coils and/or filters
are located downstream of a fan discharge. These
components require relatively low velocities to
operate correctly. This typically requires a large
change in area downstream of a fan.
Figure 17 – No-outlet duct arrangement.
Distance Requirements
coil/filter, as shown in Figure 18. Like the no-outlet
To minimize the pressure loss of this expansion, it is duct arrangement, this configuration has a substantial
necessary to install a full-length outlet duct ahead of system-effect penalty. It can provide velocity diffusion,
the expansion, as shown in Figure 16. Although this but it is difficult to predict how well a system will
duct minimizes the pressure loss, its length can be work until after system startup. In general, the closer
quite large, especially with large fans. An additional a diffuser plate is to the fan discharge, the better the
drawback is that it provides no diffusion of the fan velocity profile. Unfortunately, as the diffuser plate
discharge jet. There is still a need for a diffusion is moved closer to the fan, the system-effect penalty
device or an extremely long diffusion distance increases rapidly.
between the fan outlet and downstream coil. A long
distance is needed because the discharge jet expands
at an angle of about 15°.

Figure 18 – Target plate, vertical diffuser plate and angled


diffuser plate configurations.

The use of the BlenderConeTM fan diffuser/mixer


(Figure 19) provides an alternative approach. The
Figure 16 – Full-length outlet duct, providing an ideal pressure drop of the BlenderCone is greater than the
installation for system effect. pressure drop of the full outlet duct, but is less than
half the pressure drop of the other arrangements.
System-Effect Considerations The distance required by the BlenderCone is less
than the distance required by the full-outlet duct and
The “No-outlet duct arrangement,” shown in Figure is essentially the same as that required by the other
17, may be used to save space. Like the full-length arrangements.
outlet-duct arrangement, this configuration does not
provide additional diffusion of the air stream. Thus
the distance between the fan outlet and downstream
component must be sufficient for the jet to naturally
expand and fill the plenum. This arrangement has a
large system-effect penalty.
Figure 19 – Short BlenderCone, for retrofit applications in
To enhance the diffusion of the no-outlet duct tight spaces, and the more efficient long BlenderCone for
arrangement, a diffuser plate or target plate can be new construction.
mounted between the fan outlet and the downstream

16
Application Guidelines For Velocity-
Equalizing Diffusers
Bibliography
Amoroso Jr., Victor, P.E. & Gjestvang, Ryan, P.E., “Air Handling Units for Hospitals,” Consulting/Specifying
Engineer, October 1989.
Faison Jr., T.K., Davis, J.C., & Achenbach, P.R., “Performance of Louvered Devices as Air Mixers,” Building
Science Series 27, US Dept. of Commerce, National Bureau of Standards, March 1970.
Haines, Roger W., “HVAC Systems Design Handbook,” Section 4.8 (pp 109-111) TAB Books, 1988.
Haines, Roger W., “Stratification,” Heating/Piping/Air Conditioning, November 1980.
Hallstrom, Arthur D., “Fixing the Frozen Coil Problem,” Contracting Business, October 1986.
Robinson, Keith D., P.E., “Blender Cone Basics,” Blender Products, Inc., December 1992.
Robinson, Keith D., P.E., “Fan Basics,” Blender Products, Inc., December 1992.
5010 Cook Street, Denver, CO 80216
Toll-Free: 800-523-5705
Fax: 303-296-1520
Phone: 303-295-6111

Potrebbero piacerti anche