Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
July 2011
ABB AG
Calor Emag Mittelspannungsprodukte
Postal Address: Head Office: Mannheim Bank Details:
Postfach 10 12 20 Registry Court: Mannheim UniCredit Bank AG, München Commerzbank AG, Ratingen
40832 Ratingen Comm. Register: HRB 4664 BIC: 700 202 70 BIC: 300 800 00
Germany VAT: 38180/10046 Account-No.: 5 726 700 Account-No.: 3 020 903
VAT-Id: DE143840362 IBAN: DE34 7002 0270 0005 7267 00 IBAN: DE87 3008 0000 0302 0903 00
Visiting Address: SWIFT: HYVEDEMM SWIFT: DRESDEFF
Oberhausener Straße 33 Chairman Supervisory Board:
40472 Ratingen Dipl.-Ing. Bernhard Jucker
Phone: +49 2102 12- 0 Members of the Management Board:
Telefax: +49 2102 12- 1777 Dipl.-Ing. Dr. Peter Terwiesch (Chair.)
Internet: www.abb.de/mittelspannung Dipl.-Volkswirt Hans-Georg Krabbe
Dr.-Ing. Martin Schumacher
Dipl.-Kfm. Markus Ochsner
Page 2
If the short-circuit occurs at fault location (1) (busbar These two currents (I"k1 and I"k2) are likely to be
short-circuit), the tripping value would be 20 kA. familiar from normal short-circuit calculations.
With a short-circuit at fault location (2), the IS-limiter For the general determination of the tripping value, a
must still just trip when a short-circuit current of 25 short-circuit is assumed behind Z3 (figure 3) with
kA flows through impedance Z (cable and reactor). Z3 ǂ 0.
The current through the IS-limiter is then 12.5 kA. If,
however, a current less than 25 kA flows through The IS-limiter must trip when:
impedance Z, the outgoing feeder breaker can
interrupt the short-circuit current and the IS-limiter I3 = I1 + I2 > I"k, perm.1 (1)
does not have to trip. The tripping value calculated for
this example is therefore 12.5 kA.
I1
As the ratio of the currents is determined by
Conclusion: I2
impedances Z1 and Z2, the following applies:
If the IS-limiter trips on an expected current of 12.5
kA (rms) in the first current rise, the switchgear I1 I"k1
system is protected against excessively high short- = " (2)
circuit currents at all fault locations. I2 I k2
I" k2
I T2 I"k, perm.1 (3)
I" k1 I" k2
Figure 3: Simplified equivalent circuit diagram
It can be seen from equations (3) and (4) that only the
extreme values of the ratio I"k1/I"k2 have to be known
to determine the lowest tripping value.