3 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
Our Solutions for
Power Transformers (outdoor)
■ HV-CONNEX Plug-in Bushings
■ MV-CONNEX Multiple Transformer Bushings
■ MV-CONNEX Separable Connectors
■ MV-CONNEX Surge Arresters
4
Public energy grids are our core markets since
almost 100 years.
6 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
CONNEX – Reliability and Safety with the Pluggable
Bushing and the Surge Arrester
7 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
An Universal Connection Interface
Designed not only to meet cable standards, the CONNEX socket is an integral part of the
transformer world
Transformer
Testing: IEC 60137
Housing: EN 50299
Cable termination
8 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
CONNEX Technology– high voltage
Cross section* 1600 mm² 1600 mm² 2500 mm² 2500 mm²
Max. diameter over
55.4 mm/ 55.4 mm/ 64.9 mm/ 64.9 mm/
conductor/insulatio
78.0 mm 76.0 mm 110.5 mm 113.5 mm
n
* Valid only, if values comply to max. diameter over conductor/max. diameter over insulation
9 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
CONNEX Plug in Contacts – extra high voltage
Size 7 Size 8
4000 A 4000 A
10 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
MV & HV CONNEX Plug in Terminations in
Horizontal Position
11 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
Connecting Principle - High Voltage (Um = 52..245 kV)
Air insulated Conventional Type / Wet Type Pluggable Dry-Type / CONNEX
Bare conductor Epoxy Insulator with Oil Filling Metal enclosed / touch proof
Frame construction needed Transformer compartment has to Separation of Cable System and
be opened for assembly Transformer in view of Assembly
and testing
Prevention against animals must Relatively High Assembly Time Integration of Epoxy Insulator in
be taken Transformer as an Interface
Space requirement very high Dielectric test of cable system Dielectric test of cable system
only with additional effort and transformer feasible
feasible
Medium Flexibility Low Flexibility Highest Flexibility
12 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
Principle & Function of the CONNEX pluggable
system
13 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
Motivation: conventional type vs. plug-in dry-type
transformer
compartment
14 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
Comparison
15 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
HV-CONNEX Pluggable Bushings
Initially designed for testing purposes, pluggable bushings were introduced
already 20 years ago
16 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
Principle of a pluggable HV-CONNEX Bushing
Bushing
17 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
Benefit of a pluggable Bushing
18 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
Pluggable Bushing Advantages
19 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
Benefits of CONNEX
20 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
Tests at factory site
Fully pluggable transformer on HV and MV side
21 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
Laboratory Tests
Preparing for
Plugging
■ Tests in High
Voltage Test
Laboratory
■ Combined test of
bushing and
PFISTERER
socket, IEC 60137
■ Test values cover
IEC and IEEE,
ANSI Test Tap
available
22 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
Innovation in Protection –
Pluggable solid insulated Surge Arrester
HV-CONNEX Surge Arrester Size 4 up to Umax 72.5
kV
23 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
Innovation in Protection –
Pluggable solid insulated Surge Arrester
HV-CONNEX Surge Arrester Size 5-S up to Umax 145
kV
24 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
Plug including Polymer insulating part Head flange incl.
contact and incl. FRP tube housing pressure release
insulating part field grading system
25 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
HV-CONNEX Separable Surge Arrester
Schedule of Test
Type test based on IEC 60099-4
Nominal discharge current (8/20 µs) 20 kA
Line discharge class 4
Dielectrical Test
Power frequency voltage test 275 kV
Lightning Impulse test (1.2/50 µs) 650 kV
Partial discharge test 1.05 * Uc
(<10 pC)
26 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
HV-CONNEX Surge Arrester
■ Costly
■ Relatively long assembly time
■ A lot of space required
■ Complex assembly
Our approach …
27 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
HV-CONNEX Surge Arrester – Compact Design
28 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
Advantages & Benefit of HV-CONNEX Pluggable SA
series
Pluggable
29 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
Case Study – Mobile test setup
Country: any
Voltage level: up to Um = 245kV
Year: any
30 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
Case Study EON Westfalen Weser
Country: Germany
Quantity: 3 substations
Country: any
Voltage level: up to Um = 170kV
Year: any
32 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
Case Study Canada – Padmount Transformers
Country: Canada
Voltage level: up to Um = 145kV
Year: any
33 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
Case Study – Offshore
Country: any
Voltage level: up to Um = 245kV
Year: any
34 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
High-Voltage Field-Installation Cables – Secure and
Reliable System Operation in Cases of
Reconstructions and Incidents from 145 kV to 362 kV
35 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
IXOSIL ESS cable termination
37 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
5. Conclusion
The network is changing and higher voltages and increased power
transmission require new solutions
38 February 22nd & 23rd, 2017 Scope Complex, Lodhi Road, Delhi, India
Thank you very much for your attention.