Sei sulla pagina 1di 11

CUST: PURE AQUA, INC. SIZE: 120" X 161" PO #: 11046 W.O.

#: 43651
PAI120161

Pure Aqua Reference:


SEAM "S2"
QTY: 1
SEAMS "S1" & "S3"
345°
0° 8° 20°
Filtered Water Tank 10K
DWG No.: 4176-FAB-251
MOD. #: PAI120161 INT: DEVOE 233H
328° 32° Rev. No: 0 SHEET: 1 OF 1 WT: 12,910 LBS. EXT: TNEMEC 1074 - SAFETY BLUE (N69F BASE) DUE: 10/26/12
Z STATUS: FOR APPROVAL TT______ HT______ 50 PSIG SN:
R45" ITEM Part # QTY. Description NOTES
TYP.
120" S1 579109 1 SHELL 60" X 377-1/2" X 3/8" NOM. SA-455 PLASMA - NO HOLES WT : 2,378 LBS.
N3 N7
D&E N4 N3 S2 579109 1 SHELL 60" X 377-1/2" X 3/8" NOM. SA-455 PLASMA - NO HOLES WT : 2,378 LBS.
S3 579109 1 SHELL 60" X 377-1/2" X 3/8" NOM. SA-455 PLASMA WT : 2,378 LBS.
6"
H1 649902 1 HEAD 2:1 ELLIP. 120" X .500 NOM. / .441 MIN. SA-516-70 PLASMA WT : 2,208 LBS.
H2 566007 1 BOTTOM PLATE 1/2" X 119-1/8" DIA. SA-516-70 PLASMA WT : 1,570 LBS.
285° 75°
30" 30" 30" N2 N1 738016 1 SLIP-ON FLANGE 24" R.F. 150#
H1 D&E D&E
N4 F.S. N1 119027 1 ROLLED RING 3/8" X 24-1/8" O.D. A-36 PLASMA
6"
N4 N7 N6 N1 - 1 DAVIT ASSY. FOR 24" SLIP-ON DETAIL DRAWING ATTACHED
270° 90° N2 337031 1 WELDNECK FLANGE 24" ANSI 150# RF
167 1/2"
6" N2 - 1 DAVIT ASSY. FOR 24" WELDNECK DETAIL DRAWING ATTACHED
N3
N3 738008 2 SLIP-ON FLANGE 6" R.F. 150#
S1
105° N3 157123 2 6" SCH. 40 PIPE X 9-1/2"
255°
N2 N4 738006 2 SLIP-ON FLANGE 4" R.F. 150#
30" 49 1/2" N4 157120 2 4" SCH. 40 PIPE X 9"
7" SHELL "S1"
N5 738005 1 SLIP-ON FLANGE 3" R.F. 150#
N1
N5 157100 1 3" SCH. 40 PIPE X 6-1/2"
N8 D&E
N6 320800 1 FULL COUPLING 2" NPS BLK
225° N7 320504 1 FULL COUPLING 1" NPT 304 S.S.
135° 118" N8 320301 1 FULL COUPLING 1/2" NPT 304 S.S.
A&B 212° A 150037 10 ANCHOR PAD 1" X 4" X 5" PLASMA - SEISMIC (SEE NOTE 4)
(10) PLCS. 6" 217 9/16" B 150004 20 ANCHOR GUSSET 3/8" X 5" X 6-1/2" PLASMA
C 188° 148°
165°
N5 180° C 579109 1 ANCHOR REPAD BAND 6-3/4" X 372" X 3/8" PLASMA, ROLL - USE DROP FROM "S1"
D 380096 2 LIFTING LUG MEDIUM
180° S2 59" E 780005 4 LIFT LUG REPAD 1/4" X 2" X 8"
N5
165°
148°
SHELL "S2" F 0 1 BEAM S6 X 17.25# X 119"
212°
G 0 2 BEAM S6 X 17.25# X 115-7/8"
H 0 2 BEAM S6 X 17.25# X 103-11/16"
135°
J 0 2 BEAM S6 X 17.25# X 78-1/4"
225° N1 K 0 2 BEAM S6 X 17.25# X 12-5/8"
N8
12" 12" 59" L 0 4 BEAM S6 X 17.25# X 11"
S3
12" 12" N1
115 7/8" 103 11/16"
12" 12"
42 1/2"
255° 105°
75° 58°
L L 59" TYP. TYP.
12" 12" N4
K K SHELL "S3"
N3
N8 N5 N4
270° 90°

14 1/2"
BEAM "G" DETAIL BEAM "H" DETAIL
12" 12"
N3 L L C
7 1/2" (BAND "C")
6 1/2" (PLATE "H2") 78 1/4"
285° 75°
0"
J J A&B A&B
G (10) PLCS. H2
H H 38°
G C TYP.
F BAND "C" SHOWN AS A PLATE
FOR DETAIL PURPOSES ONLY. 1/2"
BEAM "J" DETAIL 120" X 161" NON-CODE
C 1"
DRAWING APPROVAL
SAFETY RELIEF DEVICES SHALL BE
328° 32° 6" 11"
THE RESPONSIBILITY OF THE END USER
20° B B
B C 20° PLEASE INDICATE APPROVAL FOR
0° SEAMS "S1" & "S3" LEAVE A GAP IN BAND "C" DRAWING & RETURN TO QUICK TANKS
345° 6 3/4" 3" AROUND SEAM "S3"
SEAM "S2" APPROVED AS DRAWN.
PROCEED WITH FABRICATION.
6 1/2" C 75°
NOTES: A SEAM "S3" APPROVED AS NOTED. PROCEED WITH
FABRICATION IN ACCORDANCE WITH NOTED
1. DIMENSIONS SHOWN IN ( ) ARE FOR REFERENCE ONLY. 1 1/4"
A
COPE TO FIT CHANGES. RESUBMIT CORRECTED DRAWING.
INSIDE BEAM "J"
2. NO LINING WARRANTY ABOVE 120 F. (SAME FOR BEAM "K") DISAPPROVED. DO NOT FABRICATE.

3. BOLT HOLES OF FLANGES TO STRADDLE MAJOR VESSEL DETAIL Z S3 BEAM "L" DETAIL RESUBMIT DRAWING FOR APPROVAL.
1 1/2"
CENTERLINES.
BY DATE
1" 3/4"

NON-CODE
QUICI
PAI120161

4. SEISMIC & WIND LOADING DESIGN PER IBC 2006 FOR REV. DESCRIPTION DATE APPROVED
INSTALLATION LOCATION. 2" 2" TANKS, Inc.
5" KENDALLVILLE, INDIANA USA
5. LEAVE A 5/16" GAP BETWEEN LIFT LUG REPADS. 4"
WELD CONTINUOUSLY AROUND EACH PART. ANCHOR PAD DETAIL DATE: 9/17/12 DRAWN BY: JM SIZE: B SCALE: NTS

THIS PRINT, IN ALL MEDIA FORMATS, IS THE SOLE PROPERTY OF QUICK TANKS, INC. REPRODUCTION OR DISSEMINATION IS STRICTLY PROHIBITED WITHOUT PRIOR WRITTEN CONSENT.
CUST: PURE AQUA, INC. SIZE: 24" PO #: 11046 W.O. #: 43651
DAVIT ASSY. FOR 24" WELDNECK

MOD. #: DAVIT ASSY. FOR 24" WELDNECK INT: PER VESSEL DRAWING QTY: 1
SHEET: 1 OF 1 WT: 259 LBS. EXT: PER VESSEL DRAWING DUE: 10/26/12
TT______ HT______ 50 PSI SN:
ITEM Part # Qty. Description
A 963004 1 COVER PLATE 3/4" X 32" DIA. SA-516-70
K B 337111 1 GASKET 24" FOR BLIND FLANGE
J C 380028 1 LIFT LUG 1/2" FORGED
D 119031 1 GUSSET 1/2" X 8-11/16" X 5-13/16"
E 157090 1 2-1/2" SCH. 40 PIPE X 10-1/4"
G F 157090 1 2-1/2" SCH. 40 PIPE X 1/2"
H G 157162 1 BENT PIPE 2" SCH 40. 10"R. CUT TO LENG.
H 380292 1 EYEBOLT 3/4"-10 X 11-15/16" OPEN - WELD SHUT
9/16" A J 380156 1 FLAT WASHER 3/4" SAE PLATED
LIFT LUG NOT
CENTERED ON L-P 1 3/16" K 380065 2 NUT 3/4"-10 HEX PLATED GR.5
COVER PLATE. F L 399999 20 BOLT 1-1/4"-7 X 5" LG. HHCS PLATED
C 23 1/8"
M 380077 40 FLAT WASHER 1-1/4" PLATED
C 3 1/8" N 380164 20 LOCK WASHER 1-1/4" PLATED
P 380076 20 HEX NUT 1-1/4"-7 PLATED

10 1/4"
D
CENTER ON
WELDNECK
FLANGE

CUT PIPE "E" TO LENGTH.


COPE TO FIT & WELD TO E
VESSEL HEAD. 16° WELDNECK SHOWN FOR REFERENCE ONLY.
FLANGE IS INCLUDED IN TANK BOM.

21 3/4"
7/8" THRU

R2 1/8"

1 1/2"
2 15/16"
5 13/16"
R10"
3 5/16"
DAVIT ASSY. FOR 24" WELDNECK

R16" 24" DAVIT ASSY.


21 5/8"
DRAWING APPROVAL
SAFETY RELIEF DEVICES SHALL BE
8 11/16" THE RESPONSIBILITY OF THE END USER
PLEASE INDICATE APPROVAL FOR

GUSSET "D" DETAIL


DRAWING & RETURN TO QUICK TANKS

10 7/16" PLASMA # 18295


APPROVED AS DRAWN.
PROCEED WITH FABRICATION.

APPROVED AS NOTED. PROCEED WITH


PIPE "G" DETAIL FABRICATION IN ACCORDANCE WITH NOTED
CHANGES. RESUBMIT CORRECTED DRAWING.

DISAPPROVED. DO NOT FABRICATE.


RESUBMIT DRAWING FOR APPROVAL.

NOTES: BY DATE

NON-CODE
1. DIMENSIONS SHOWN IN ( ) ARE FOR REFERENCE ONLY.
QUICI
REV. DESCRIPTION DATE APPROVED

2. WELD "F" TO "G" ONLY, NOT TO "E". TANKS, Inc.


3. WELD EYEBOLT SHUT AFTER ATTACHING TO LIFT LUG. KENDALLVILLE, INDIANA USA
DATE: 9/14/12 DRAWN BY: JM SIZE: B SCALE: NTS

THIS PRINT, IN ALL MEDIA FORMATS, IS THE SOLE PROPERTY OF QUICK TANKS, INC. REPRODUCTION OR DISSEMINATION IS STRICTLY PROHIBITED WITHOUT PRIOR WRITTEN CONSENT.
CUST: PURE AQUA, INC. SIZE: 24" PO #: 11046 W.O. #: 43650
DAVIT ASSY. FOR 24" SLIP-ON

MOD. #: DAVIT ASSY. FOR 24" SLIP-ON INT: PER VESSEL DRAWING QTY: 1
SHEET: 1 OF 1 WT: 262 LBS. EXT: PER VESSEL DRAWING DUE: 10/26/12
50 PSI TT______ HT______ SN:
ITEM Part # QTY. Description
A 963004 1 COVER PLATE 3/4" X 32" DIA. SA-516-70 NOTES:
B 150009 1 WEB 3/4" X 2-5/16" X 9-5/8" 1) WELD "D" TO "E" ONLY, NOT TO "C"
C 157090 1 2-1/2" SCH. 40 PIPE X 10-5/8" 2) CUT THE BOTTOM OFF OF "F" AND INSERT
D 157090 1 2-1/2" SCH. 40 PIPE X 1/2" THRU EYEBOLT BEFORE WELDING TO "A"
3) CENTER "B" AND "F" ON THE FACE
E 157162 1 BENT PIPE 2" SCH. 40 OF THEIR RESPECTIVE FLANGES.
F 380028 1 LIFT LUG 1/2" FORGED - CUT
G 380071 1 EYEBOLT 3/4"-10 X 6-15/16" OPEN
H 380156 1 FLAT WASHER 3/4" SAE PLATED 6"
J 380065 2 NUT 3/4"-10 HEX PLATED GR.5
K 156124 1 HANDLE 1/2" C.R. ROUND X 10-3/8"
L 399999 20 BOLT 1-1/4"-7 X 5" LG. HHCS PLATED 3" R1/2" TYP.
M 380077 40 FLAT WASHER 1-1/4" PLATED 1/2"
N 380164 20 LOCK WASHER 1-1/4" PLATED
ITEM "K"
P 380076 20 HEX NUT 1-1/4"-7 PLATED
Q 337111 1 GASKET 24" FOR BLIND FLANGE

21 13/16"
SLIP-ON FLANGE SHOWN FOR
REFERENCE ONLY & INCLUDED 10 5/8"
IN TANK BOM.
E
D 7/8" THRU
1 9/16"
R8 13/16"
A 1 9/16"
K 20 5/8"

29 9/16"

H J
E

F G BENT PIPE "E"


WELDED TO DETAIL
COVER PLATE

23 1/16"
D
1/2"

12"
R16"
10 5/8"
2 5/16"
DAVIT ASSY. FOR 24" SLIP-ON

1/2"
B
WELDED C
TO
SLIP-ON 9 5/8" 24" DAVIT ASSY.
FLANGE
DRAWING APPROVAL
L-P SAFETY RELIEF DEVICES SHALL BE
THE RESPONSIBILITY OF THE END USER

PLEASE INDICATE APPROVAL FOR


19" DRAWING & RETURN TO QUICK TANKS
APPROVED AS DRAWN.
PROCEED WITH FABRICATION.

APPROVED AS NOTED. PROCEED WITH


FABRICATION IN ACCORDANCE WITH NOTED

WEB "B" DETAIL


CHANGES. RESUBMIT CORRECTED DRAWING.

PLASMA #13600 DISAPPROVED. DO NOT FABRICATE.


RESUBMIT DRAWING FOR APPROVAL.

BY DATE

CONFORMS TO ASME
REV. DESCRIPTION DATE APPROVED
QUICI TANKS, Inc.
KENDALLVILLE, INDIANA USA
REQUIREMENTS DATE: 9/13/12 DRAWN BY: JM SIZE: B SCALE: NTS

THIS PRINT, IN ALL MEDIA FORMATS, IS THE SOLE PROPERTY OF QUICK TANKS, INC. REPRODUCTION OR DISSEMINATION IS STRICTLY PROHIBITED WITHOUT PRIOR WRITTEN CONSENT.
www.hilti.us Profis Anchor 2.3.2
Company: Quick Tanks, Inc. Page: 1
Specifier: Phillip Perlich II Project: PAI120161 - Venezuela
Address: 545 N. Krueger St. Kendallville, IN, USA 46755 Sub-Project I Pos. No.:
Phone I Fax: (260) 347-3850 | Date: 9/20/2012
E-Mail: pperlich@quicktanks.com

Specifier's comments:

1 Input data
Anchor type and diameter: HDA-TR M16x190/40
Effective embedment depth: hef = 7.480 in., hnom = 7.992 in.
Material: 1.4401, 1.4404, 1.4571
Evaluation Service Report:: ESR 1546
Issued I Valid: 4/1/2012 | 3/1/2014
Proof: design method ACI 318 / AC193
Stand-off installation: eb = 0.000 in. (no stand-off); t = 1.000 in.
Anchor plate: lx x ly x t = 4.000 in. x 5.000 in. x 1.000 in.; (Recommended plate thickness: not calculated)
Profile: no profile
Base material: cracked concrete, , fc' = 3555 psi; h = 12.000 in.
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar
Seismic loads (cat. C, D, E, or F) yes (D.3.3.5)

Geometry [in.] & Loading [lb, in.lb]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.3.2
Company: Quick Tanks, Inc. Page: 2
Specifier: Phillip Perlich II Project: PAI120161 - Venezuela
Address: 545 N. Krueger St. Kendallville, IN, USA 46755 Sub-Project I Pos. No.:
Phone I Fax: (260) 347-3850 | Date: 9/20/2012
E-Mail: pperlich@quicktanks.com

2 Load case/Resulting anchor forces


Load case: Design loads
y
Anchor reactions [lb]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 6721 2703 0 2703
max. concrete compressive strain: 0.33 [‰] x
max. concrete compressive stress: 1416 [psi]
resulting tension force in (x/y)=(0.000/-0.500): 6721 [lb] 1
Tension
resulting compression force in (x/y)=(0.000/-2.330): 1442 [lb]

Compression
3 Tension load
Load Nua [lb] Capacity fNn [lb] Utilization bN = Nua/fNn Status
Steel Strength* 6721 21141 32 OK
Pullout Strength* 6721 13069 52 OK
Concrete Breakout Strength** 6721 10253 66 OK
* anchor having the highest loading **anchor group (anchors in tension)

3.1 Steel Strength


Nsa = ESR value refer to ICC-ES ESR 1546
f Nsteel ≥ Nua ACI 318-08 Eq. (D-1)

Variables
n Ase,N [in.2] futa [psi]
1 0.24 116000
Calculations
Nsa [lb]
28188
Results
Nsa [lb] fsteel f Nsa [lb] Nua [lb]
28188 0.750 21141 6721

3.2 Pullout Strength

√2500
'
fc
Npn,f'c = Np,2500 refer to ICC-ES ESR 1546

f Npn,f'c ≥ Nua ACI 318-08 Eq. (D-1)

Variables
f'c [psi] Np,2500 [lb]
3555 22481
Calculations

√2500
'
f c

1.192
Results
Npn,f'c [lb] fconcrete fseismic fnonductile f Npn,f'c [lb] Nua [lb]
26808 0.650 0.750 1.000 13069 6721

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.3.2
Company: Quick Tanks, Inc. Page: 3
Specifier: Phillip Perlich II Project: PAI120161 - Venezuela
Address: 545 N. Krueger St. Kendallville, IN, USA 46755 Sub-Project I Pos. No.:
Phone I Fax: (260) 347-3850 | Date: 9/20/2012
E-Mail: pperlich@quicktanks.com

3.3 Concrete Breakout Strength

Ncb = (AA ) y
Nc
Nc0
ed,N yc,N ycp,N Nb ACI 318-08 Eq. (D-4)
f Ncb ≥ Nua ACI 318-08 Eq. (D-1)
ANc see ACI 318-08, Part D.5.2.1, Fig. RD.5.2.1(b)
ANc0 = 9 h2ef ACI 318-08 Eq. (D-6)

( )
1
yec,N = 2 e'N ≤ 1.0 ACI 318-08 Eq. (D-9)
1+
3 hef

(
yed,N = 0.7 + 0.3 1.5h
ca,min
ef
)
≤ 1.0 ACI 318-08 Eq. (D-11)

(
ca,min 1.5hef
ycp,N = MAX c , c
ac ac
)
≤ 1.0 ACI 318-08 Eq. (D-13)
1.5
Nb = kc l √fc hef
'
ACI 318-08 Eq. (D-7)

Variables
hef [in.] ec1,N [in.] ec2,N [in.] ca,min [in.] yc,N
6.000 0.000 0.000 9.000 1.000

cac [in.] kc l f'c [psi]


- 24 1 3555

Calculations
ANc [in.2] ANc0 [in.2] yec1,N yec2,N yed,N ycp,N Nb [lb]
324.00 324.00 1.000 1.000 1.000 1.000 21032
Results
Ncb [lb] fconcrete fseismic fnonductile f Ncb [lb] Nua [lb]
21032 0.650 0.750 1.000 10253 6721

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.3.2
Company: Quick Tanks, Inc. Page: 4
Specifier: Phillip Perlich II Project: PAI120161 - Venezuela
Address: 545 N. Krueger St. Kendallville, IN, USA 46755 Sub-Project I Pos. No.:
Phone I Fax: (260) 347-3850 | Date: 9/20/2012
E-Mail: pperlich@quicktanks.com

4 Shear load
Load Vua [lb] Capacity fVn [lb] Utilization bV = Vua/fVn Status
Steel Strength* 2703 20898 13 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 2703 22084 13 OK
Concrete edge failure in direction y+** 2703 5350 51 OK
* anchor having the highest loading **anchor group (relevant anchors)

4.1 Steel Strength


Vseis = ESR value refer to ICC-ES ESR 1546
f Vsteel ≥ Vua ACI 318-08 Eq. (D-2)

Variables
n Ase,V [in.2] futa [psi]
1 0.24 116000
Calculations
Vsa [lb]
32150
Results
Vsa [lb] fsteel f Vsa [lb] Vua [lb]
32150 0.650 20898 2703

4.2 Pryout Strength

Vcp = kcp [(AA ) y


Nc
Nc0
ed,N yc,N ycp,N Nb ] ACI 318-08 Eq. (D-30)
f Vcp ≥ Vua ACI 318-08 Eq. (D-2)
ANc see ACI 318-08, Part D.5.2.1, Fig. RD.5.2.1(b)
ANc0 = 9 h2ef ACI 318-08 Eq. (D-6)

( )
1
yec,N = 2 e'N ≤ 1.0 ACI 318-08 Eq. (D-9)
1+
3 hef

yed,N = 0.7 + 0.3 (


ca,min
1.5hef
≤ 1.0) ACI 318-08 Eq. (D-11)

(
ca,min 1.5hef
ycp,N = MAX c , c
ac ac
≤ 1.0) ACI 318-08 Eq. (D-13)
1.5
Nb = kc l √fc hef
'
ACI 318-08 Eq. (D-7)

Variables
kcp hef [in.] ec1,N [in.] ec2,N [in.] ca,min [in.]
2 6.000 0.000 0.000 9.000

yc,N cac [in.] kc l f'c [psi]


1.000 - 24 1 3555

Calculations
ANc [in.2] ANc0 [in.2] yec1,N yec2,N yed,N ycp,N Nb [lb]
324.00 324.00 1.000 1.000 1.000 1.000 21032
Results
Vcp [lb] fconcrete fseismic fnonductile f Vcp [lb] Vua [lb]
42064 0.700 0.750 1.000 22084 2703

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.3.2
Company: Quick Tanks, Inc. Page: 5
Specifier: Phillip Perlich II Project: PAI120161 - Venezuela
Address: 545 N. Krueger St. Kendallville, IN, USA 46755 Sub-Project I Pos. No.:
Phone I Fax: (260) 347-3850 | Date: 9/20/2012
E-Mail: pperlich@quicktanks.com

4.3 Concrete edge failure in direction y+

Vcb = (AA ) y
Vc
Vc0
ed,V yc,V yh,V yparallel,V Vb ACI 318-08 Eq. (D-21)
f Vcb ≥ Vua ACI 318-08 Eq. (D-2)
AVc see ACI 318-08, Part D.6.2.1, Fig. RD.6.2.1(b)
AVc0 = 4.5 c2a1 ACI 318-08 Eq. (D-23)

( )
1
yec,V = 2e'v ≤ 1.0 ACI 318-08 Eq. (D-26)
1+
3ca1

yed,V = 0.7 + 0.3 1.5c(


ca2
a1
≤ 1.0) ACI 318-08 Eq. (D-28)

yh,V = √
1.5ca1
ha
≥ 1.0 ACI 318-08 Eq. (D-29)

(( ) )
0.2
l 1.5
Vb = 7 e √da l √f'c ca1 ACI 318-08 Eq. (D-24)
da

Variables
ca1 [in.] ca2 [in.] ecV [in.] yc,V ha [in.]
8.000 9.000 0.000 1.000 12.000

le [in.] l da [in.] f'c [psi] yparallel,V


7.480 1 1.140 3555 1.000

Calculations
AVc [in.2] AVc0 [in.2] yec,V yed,V yh,V Vb [lb]
216.00 288.00 1.000 0.925 1.000 14689
Results
Vcb [lb] fconcrete fseismic fnonductile f Vcb [lb] Vua [lb]
10191 0.700 0.750 1.000 5350 2703

5 Combined tension and shear loads


bN bV z Utilization bN,V [%] Status
0.656 0.505 5/3 82 OK
z z
bNV = bN + bV <= 1

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.3.2
Company: Quick Tanks, Inc. Page: 6
Specifier: Phillip Perlich II Project: PAI120161 - Venezuela
Address: 545 N. Krueger St. Kendallville, IN, USA 46755 Sub-Project I Pos. No.:
Phone I Fax: (260) 347-3850 | Date: 9/20/2012
E-Mail: pperlich@quicktanks.com

6 Warnings
• To avoid failure of the anchor plate the required thickness can be calculated in PROFIS Anchor. Load re-distributions on the anchors due to
elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be sufficiently stiff, in order not to be deformed when
subjected to the loading!
• Condition A applies when supplementary reinforcement is used. The Φ factor is increased for non-steel Design Strengths except Pullout Strength
and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout Strength. Refer to
ACI 318, Part D.4.4(c).
• Refer to the manufacturer's product literature for cleaning and installation instructions.
• Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI318 or the relevant standard!
• An anchor design approach for structures assigned to Seismic Design Category C, D, E or F is given in ACI 318-08 Appendix D, Part D.3.3.4 this
requires the governing design strength of an anchor or group of anchors be limited by ductile steel failure. If this is NOT the case, Part D.3.3.5
requires that the attachment that the anchor is connecting to the structure shall be designed so that the attachment will undergo ductile yielding at
a load level corresponding to anchor forces no greater than the controlling design strength. In lieu of D.3.3.4 and D.3.3.5, the minimum design
strength of the anchors shall be multiplied by a reduction factor per D.3.3.6.
An alternative anchor design approach to ACI 318-08, Part D.3.3 is given in IBC 2009, Section 1908.1.9. This approach contains "Exceptions"
that may be applied in lieu of D.3.3 for applications involving "non-structural components" as defined in ASCE 7, Section 13.4.2.
An alternative anchor design approach to ACI 318-08, Part D.3.3 is given in IBC 2009, Section 1908.1.9. This approach contains "Exceptions"
that may be applied in lieu of D.3.3 for applications involving "wall out-of-plane forces" as defined in ASCE 7, Equation 12.11-1 or Equation
12.14-10.
• It is the responsibility of the user when inputting values for brittle reduction factors (fnonductile) different than those noted in ACI 318-08, Part
D.3.3.6 to determine if they are consistent with the design provisions of ACI 318-08, ASCE 7 and the governing building code.
Selection of fnonductile = 1.0 as a means of satisfying ACI 318-08, Part D.3.3.5 assumes the user has designed the attachment that the anchor is
connecting to undergo ductile yielding at a force level <= the design strengths calculated per ACI 318-08, Part D.3.3.3.

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.3.2
Company: Quick Tanks, Inc. Page: 7
Specifier: Phillip Perlich II Project: PAI120161 - Venezuela
Address: 545 N. Krueger St. Kendallville, IN, USA 46755 Sub-Project I Pos. No.:
Phone I Fax: (260) 347-3850 | Date: 9/20/2012
E-Mail: pperlich@quicktanks.com

7 Installation data
Anchor plate, steel: - Anchor type and diameter: HDA-TR, M16x190/40
Profile: no profile; 0.000 x 0.000 x 0.000 in. Installation torque: 1062.089 in.lb
Hole diameter in the fixture: df = 1.260 in. Hole diameter in the base material: 1.181 in.
Plate thickness (input): 1.000 in. Hole depth in the base material: 7.992 in.
Recommended plate thickness: not calculated Minimum thickness of the base material: 11.200 in.
Cleaning: Manual cleaning of the drilled hole according to instructions for use is required.
y

2.000 2.000

2.500
3.000
x

1
2.500
2.000

2.000 2.000

Coordinates Anchor in.


Anchor x y c-x c+x c-y c+y
1 0.000 -0.500 9.000 9.000 9.000 9.000

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.3.2
Company: Quick Tanks, Inc. Page: 8
Specifier: Phillip Perlich II Project: PAI120161 - Venezuela
Address: 545 N. Krueger St. Kendallville, IN, USA 46755 Sub-Project I Pos. No.:
Phone I Fax: (260) 347-3850 | Date: 9/20/2012
E-Mail: pperlich@quicktanks.com

8 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using
the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in.
Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you.
Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to
compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms
and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific
application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the
regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use
the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each case
by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or
programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan