Sei sulla pagina 1di 18

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/303065427

Superimposed Energy-based Fault Detection and Classification Scheme for


Series-compensated Line

Article  in  Electric Power Components and Systems · May 2016


DOI: 10.1080/15325008.2016.1148082

CITATIONS READS

4 200

2 authors:

Om Hari Gupta Manoj Tripathy


National Institute of Technology, Jamshedpur Indian Institute of Technology Roorkee
20 PUBLICATIONS   84 CITATIONS    99 PUBLICATIONS   1,368 CITATIONS   

SEE PROFILE SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Protection aspects of transmission line and microgrid in the presence of switching devices View project

enhancement View project

All content following this page was uploaded by Om Hari Gupta on 07 April 2018.

The user has requested enhancement of the downloaded file.


Electric Power Components and Systems

ISSN: 1532-5008 (Print) 1532-5016 (Online) Journal homepage: http://www.tandfonline.com/loi/uemp20

Superimposed Energy-based Fault Detection and


Classification Scheme for Series-compensated Line

Om Hari Gupta & Manoj Tripathy

To cite this article: Om Hari Gupta & Manoj Tripathy (2016) Superimposed Energy-based Fault
Detection and Classification Scheme for Series-compensated Line, Electric Power Components
and Systems, 44:10, 1095-1110, DOI: 10.1080/15325008.2016.1148082

To link to this article: http://dx.doi.org/10.1080/15325008.2016.1148082

Published online: 13 May 2016.

Submit your article to this journal

Article views: 49

View related articles

View Crossmark data

Full Terms & Conditions of access and use can be found at


http://www.tandfonline.com/action/journalInformation?journalCode=uemp20

Download by: [Indian Institute of Technology Roorkee], [Om Hari Gupta] Date: 09 June 2016, At: 10:00
Electric Power Components and Systems, 44(10):1095–1110, 2016
Copyright C Taylor & Francis Group, LLC

ISSN: 1532-5008 print / 1532-5016 online


DOI: 10.1080/15325008.2016.1148082

Superimposed Energy-based Fault Detection and


Classification Scheme for Series-compensated Line
Om Hari Gupta and Manoj Tripathy
Electrical Engineering Department, Indian Institute of Technology Roorkee, Roorkee, India
Downloaded by [Indian Institute of Technology Roorkee], [Om Hari Gupta] at 10:00 09 June 2016

CONTENTS
Abstract—This article presents a fault detection and classification
1. Introduction scheme for a series-compensated transmission line that is based on
2. TCSC post-fault superimposed energy. The derivations of the scheme pre-
sented in this article are obtained with consideration of both the
3. SE-Based Fault Detection Scheme real and reactive components of the power system. However, the cri-
4. Results terion depends only on the real components of the power system.
5. Discussion For a forward fault, superimposed energy is negative, whereas it is
positive for a reverse fault. If the relays of both ends detect for-
6. Conclusion
ward fault, it is an internal fault; else, it is an external fault. The
References magnitude of superimposed energy depends on the fault type, loca-
Appendix A: Data for Test Power System tion, and resistance, which makes it difficult to classify the type of
fault as a fixed threshold cannot be set. Therefore, to classify the
type of fault, energy coefficients have been introduced that depend
on the superimposed energy measured at the relay. To test the ca-
pability of the superimposed energy based scheme, the test system
has been simulated in PSCAD/EMTDC (Manitoba HVDC Research
Centre) and an algorithm has been implemented in MATLAB (The
MathWorks, Natick, Massachusetts, USA). Results proved that the
scheme is accurate and robust against different system conditions and
uncertainties.

1. INTRODUCTION
Flexible AC Transmission System (FACTS) devices are used
to improve the power transfer capability of a transmission line
by changing the system parameters [1]. Though the FACTS
device improves the power flow, it seriously affects the trans-
mission line protection. The reason behind this is that a
FACTS device changes the system parameters, such as line
impedance and load current. The impact of FACTS devices
on the protective scheme changes with the system condi-
tions and degree of compensation. Besides changing the line
Keywords: fault detection, fault classification, protection of compensated impedance, the presence of a thyristor-controlled series ca-
line, superimposed components, superimposed energy, thyristor-controlled
series capacitor pacitor (TCSC) may also cause problems, such as voltage or
Received 20 January 2015; accepted 17 January 2016 current reversal at the relay bus during fault, and subsequently
Address correspondence to Mr. Om Hari Gupta, Electrical Engineering affects the protection schemes [2, 3]. The ordinary protection
Department, Indian Institute of Technology Roorkee, Roorkee, 247667,
India. E-mail: omggupta@gmail.com
schemes lead to mal-operation for a TCSC-compensated trans-
Color versions of one or more of the figures in the article can be found online mission line [4], and hence, distinct protection schemes are
at www.tandfonline.com/uemp. required.

1095
1096 Electric Power Components and Systems, Vol. 44 (2016), No. 10

Many directional relaying schemes are available [5–9] that


are based on the phase angle difference of certain parame-
ters. However, the relaying schemes proposed in [5–9] did
not classify the type of fault that is required for single-pole
tripping. In another study [10], the analysis of sequence di-
rectional elements has been conducted, and it has been con-
cluded that the change in source impedance may lead to mal-
function of the directional element. A current transient-based
directional scheme for a fixed-series compensated line was
presented in [11]. However, a very high sampling rate is re-
Downloaded by [Indian Institute of Technology Roorkee], [Om Hari Gupta] at 10:00 09 June 2016

quired to extract the transients. For the protection of a transmis-


sion line, instantaneous component based directional schemes FIGURE 1. TCSC module used in the present work.
were proposed in [12–14], which required a high sampling
rate to achieve high-speed relaying; also, the establishment value for faulty phase selection. To deal with this problem,
of the proposed criteria depends on the inception angle. This energy coefficients (ECs) have been introduced and used for
dependability reduces the reliability of the scheme. Direc- fault classification. These ECs range from –1 to +1. During
tional relaying scheme may also be used as a unit protec- the existence of superimposed components, if any phase pos-
tion scheme of the line with the help of the communication sesses the magnitude of EC greater than 0.1, then that phase
between the relays situated at both the ends of the line. In is considered to be faulty. If more than one phase is found
[12], the criterion for direction detection was established us- faulty at any of the relay end, it is a multi-phase fault. The
ing the impulse response. However, the duration of this estab- criterion has been established using both the real and reactive
lished criterion is very small. Moreover, in [13, 14], the power components of the power system. Results demonstrate that the
system was considered purely reactive, and the fault classi- scheme is fast and robust against various uncertainties exist-
fication problem was not addressed. A traveling-wave-based ing in the power system. Moreover, it does not require any
scheme used to obtain the direction of a fault fails as there will training (as required in ANN-based schemes) and is easy to
be no traveling wave appearance if a fault occurs at a zero- implement.
inception angle [15]. Artificial neural network (ANN) based
schemes have been used for fault direction estimation in the
power system [16–20], providing valuable results. However, an 2. TCSC
ANN requires extensive training data obtained from the power
A TCSC is a series-compensating device for which the re-
system.
actance can be controlled by controlling the firing pulses of
The aim of this study is to detect faults within the protected
thyristors. Both the inductive reactance and capacitive reac-
zone and to classify the type of fault. Usually, superimposed
tance can be achieved by using a TCSC. Figure 1 shows the
components are obtained by subtracting one cycle past a sam-
circuit diagram of the TCSC used in the present work. It con-
ple from the present sample. Hence, after the inception of a
sists of a parallel combination of a thyristor-controlled reactor
fault, superimposed components exist for approximately one
(TCR) and a capacitor. The metal oxide varistor (MOV) has
cycle. This article presents a superimposed energy (SE) based
been used to provide the over-voltage protection to capacitor.
relaying scheme for the protection of a TCSC-compensated
transmission line. The SE [21] is measured by integrating the
superimposed power at both relay buses. Though the super- 3. SE-BASED FAULT DETECTION SCHEME
imposed components exist for one cycle after the fault, the
measured SE oscillates and achieves a constant finite value 3.1. Internal Fault
and remains so, even when the superimposed components are For an internal fault at a distance ρ from the sending end,
zero. SE is calculated at both ends. If a fault occurs in front the equivalent superimposed component diagram of a two-
of a relay, measured SE is negative, and if a reverse fault source power system is shown in Figure 2. Here, the effect
occurs, measured SE is positive. If both the relays detect a of shunt capacitances has been ignored as they carry very
forward fault, it is an internal fault; else, it is an external fault. small charging currents. However, the distributed model of a
The magnitude of SE depends on the fault type, location, transmission line is considered later, and all the results have
and resistance. Hence, it will be difficult to set the threshold been taken on an actual system.
Gupta and Tripathy: Superimposed Energy-based Fault Detection and Classification Scheme for Series-compensated Line 1097

FIGURE 2. Equivalent superimposed component power system for a fault at a distance of ρ (per unit) from the sending end.
Downloaded by [Indian Institute of Technology Roorkee], [Om Hari Gupta] at 10:00 09 June 2016

3.1.1. Capacitive Mode of TCSC


Consider the equivalent impedance of section F–x (ZFx ) to be
inductive (i.e., the capacitive reactance of the TCSC is less
than the total inductive reactance of the section F – x). Then
the corresponding phasor will be as shown in Figure 3(a).
Similarly, if the impedance of section F – x is capacitive, the
phasor will be as depicted in Figure 3(b).
There may be a condition where the overall impedance of
section F – x is resistive (i.e., the capacitive reactance of TCSC
is equal to the inductive reactance of section F – x). For this
situation, the phasor diagram will be as shown in Figure 3(c).
In the above three cases, Is leads the fault current by θ s
and Ir lags the fault current by θ r . The derivation according
to the capacitive mode TCSC is obtained as follows. Let the
voltage at fault-point vf and fault current if be

v f = Vf sin (ωt + α) ,
i f = I f sin (ωt + α − ϕ) ,

The superimposed currents at the receiving- and sending-end


relay buses are
ir = Ir sin (ωt + α − ϕ − θr ) ,
(1)
i s = Is sin (ωt + α − ϕ + θs ) = Is sin (ωt + θ ) ,
where θ = α – ϕ + θ s and α is the inception angle.
Applying Kirchhoff ’s law at node S of Figure 2,
di s
vs = −Rs i s − L s . (2)
dt
Substituting the value of is from Eq. (1) into Eq. (2),

vs = −Rs Is sin (ωt + θ ) − ωL s Is cos (ωt + θ ) . (3) FIGURE 3. Phasor diagrams for internal fault when (a) ZFx is
inductive, (b) ZFx is capacitive, and (c) ZFx is resistive.
Multiplying Eq. (3) by is gives

vs i s = −Rs Is2 sin2 (ωt + θ )


−ωL s Is2 sin (ωt + θ ) cos (ωt + θ ) . (4) similarly, for the receiving-end side,
Taking the integral of Eq. (4) for one cycle gives
 2π /ω  2π /ω
I 2 Rs π Ir2 Rr π
ET s = (vs i s ) dt = − s ; (5) ET r = (vr ir ) dt = − . (6)
0 ω 0 ω
1098 Electric Power Components and Systems, Vol. 44 (2016), No. 10

inductive irrespective of the TCSC mode, as maximum capac-


itive reactance of TCSC can be 30–70 % of the line reactance.
The corresponding phasor diagram is shown in Figure 6.
Derivation for external fault has been obtained as follows.
Fault voltage vf and current if are given by

v f = Vf sin (ωt + α) ,
i f = I f sin (ωt + α − ϕ) .

From the phasor diagram of Figure 6, the equations for ir


and is are as follows:
Downloaded by [Indian Institute of Technology Roorkee], [Om Hari Gupta] at 10:00 09 June 2016

ir = Ir sin (ωt + α − ϕ + θr ) ,


i s = Is sin (ωt + α − ϕ + θr + π ) ,
i s = −Is sin (ωt + α − ϕ + θr ) = −Is sin (ωt + ψ) ,
(7)
where ψ = α – ϕ + θ r and α is the inception angle.
Applying Kirchhoff ’s law at node S,
FIGURE 4. Phasor for internal fault with inductive mode of
vs = −Rsr Is sin (ωt + ψ) − ωL sr Is cos (ωt + ψ) ,
the TCSC.
(8)
where Rsr and Lsr are the equivalent resistance and inductance
It is clear that for an internal fault, SEs at both the ends are
in front of node S.
negative. It is also clear that SE does not depend on the fault
The equation of SE remains the same at receiving-end side.
inception angle.
However, the sending-end side equation of SE will come out
3.1.2. Inductive Mode of TCSC to be
 2π /ω
The phasor diagram for the condition when the TCSC is oper- Is2 Rsr π
ating in inductive mode is depicted in Figure 4. ET s = (vs i s ) dt = + . (9)
0 ω
It is clear from Figure 4 that Is lags the fault current If by
θ s and that Ir leads the fault current by θ r . This condition So for an external fault, SE at one of the two ends will be
reveals that there are changes in the signs of θ s and θ r . How- positive, as one relay will detect a reverse fault.
ever, the final outcome will be the same as that derived earlier The measured voltage and current are passed through a
for an internal fault condition in capacitive mode of operation low-pass filter to reject high-frequency components. For this,
of the TCSC. a Butterworth low-pass filter with cutoff frequency of 192 Hz
[14] is used. After extracting the superimposed components,
3.2. External Fault the algorithm checks for the occurrence of fault using the
Consider an external fault behind the sending-end relay bus. following equation [22]:
The corresponding equivalent diagram is shown in Figure 5.
For this case, the impedance of section F – y will always be i (n) ≥ 0.2I R , (10)

FIGURE 5. Equivalent superimposed component power system for an external fault.


Gupta and Tripathy: Superimposed Energy-based Fault Detection and Classification Scheme for Series-compensated Line 1099

each other, and a trip signal is generated. In the event of an


external fault at F 2 , relay n detects a forward fault and com-
municates with the other end, while relay m detects a reverse
fault. As one of the relay detects a reverse fault, it is considered
to be an external fault and no trip signal is generated. In this
scheme, the communication channel is used only when a fault
occurs in the power system.
For different fault locations and resistances, SE will be
different. Hence, it would be difficult to choose a threshold for
faulty phase selection. To solve this problem, the following
Downloaded by [Indian Institute of Technology Roorkee], [Om Hari Gupta] at 10:00 09 June 2016

ECs have been obtained for each phase at each end:


E T ma E T mb E T mc
K ma = , K mb = , K mc = (11)
ET m ET m ET m
E T na E T nb E T nc
K na = , K nb = , K nc = , (12)
ET n ET n ET n
FIGURE 6. Phasor diagram for an external fault.
where E T m = max (|E T ma |, |E T mb |, |E T mc |) and E T n =
max (|E T na |, |E T nb |, |E T nc |).
where i (n) = | |(i n − i n−N )| − |(i n−N − i n−2N )| |, in is the
Now, instead of using SE, these coefficients are used to
line current at the nth sample, N denotes the samples per cycle,
obtain the direction of fault as well as to classify the type of
and IR is the rated line current.
fault (basically these coefficients are representing the per unit
If the fault is detected using Eq. (10), the algorithm will
SE with a maximum absolute value of 1). The forward fault
select the SE with maximum absolute value from both ends. If
is detected if the sign of EC with maximum absolute value
SEs at both ends are found to be negative, it is an internal fault;
(i.e., 1) at a particular end is negative. To classify the type of
else, it is an external fault. With the use of ECs, this algorithm
fault, the magnitudes of these coefficients are compared with
has been applied to all three phases, which provides flexi-
threshold value Kth (which is set to 0.1 for this case). After the
bility of using single-pole tripping in case of a single-phase
inception of a fault at any stage, if the magnitude of coefficient
fault.
of any phase (e.g., |Kma |) is found to be greater than or equal
to threshold Kth , that phase is considered to be a faulty phase.
3.3. Implementation of the Relaying Scheme If more than one phase is found faulty, it is considered to be a
Figure 7 depicts the power system considered to test the capa- multi-phase fault. Single-pole tripping takes place only when
bility of the relaying scheme. The lengths of line A and line B a single-phase fault is detected.
are 10 and 100 km, respectively. The aim is to protect line B The flowchart of the relaying scheme is shown in Figure 8.
against internal faults. Relay m and relay n are the relays lo- The voltages and currents of all three phases are measured
cated at the ends of line B, which are connected to each other at both relay locations. These measured voltages and currents
via a communication channel. In the case of an internal fault are filtered to remove any transient components present in
at F 1 , both relays detect a forward fault and communicate with the measured signals. If fault is not detected using Eq. (10),

FIGURE 7. Single-line diagram of the test power system (line B is protected with the proposed scheme).
1100 Electric Power Components and Systems, Vol. 44 (2016), No. 10
Downloaded by [Indian Institute of Technology Roorkee], [Om Hari Gupta] at 10:00 09 June 2016

FIGURE 9. Current-voltage (I-V) characteristics of MOV


model used.

the direction of the fault. If these coefficients at both ends are


equal to –1, it is an internal fault; else, it is an external fault.
Further, to classify the fault type, the magnitudes of all three
ECs are compared with the threshold (0.1 for this case). If the
magnitude of EC of any phase (e.g., phase A at relay m) is
found to be more than the threshold, the corresponding phase
is considered faulty, and the fault indicator of that phase (ma)
will be 1; else, the corresponding phase is sound and the fault
indicator (ma) will be 0. Now, if the sum of all indicator values
(ma to nc) is equal to or greater than 3 (i.e., if any of the end
detects more than one faulty phase), it is a multi-phase fault;
else, it is a single-phase fault.

4. RESULTS
The test system used for simulation study is shown in Figure 7.
The lengths of line A and line B are 10 and 100 km, respec-
tively. A fault at point F 1 in line B is an internal fault, and a
fault at point F 2 in line A is an external fault. To test the capa-
bility of the relaying scheme for a TCSC-compensated trans-
mission line, the test system is simulated in PSCAD/EMTDC
(Manitoba HVDC Research Centre, Manitoba, Canada) and
the algorithm is implemented in MATLAB (The MathWorks,
Natick, Massachusetts, USA). The data of the test power sys-
tem used in this simulation study are given in Appendix A
[6]. The MOV model available in the PSCAD/EMTDC library
FIGURE 8. Flow diagram of the proposed relaying scheme. has been utilized in the simulation [23]. Typically, the MOV
protective levels are in the range of 2.0–2.5 per unit [24]. In
this study, the default ASEA XAP-A characteristics [23] have
the algorithm will return to the measurement block and all been selected, as shown in Figure 9. The per unit MOV pro-
calculated SEs and corresponding coefficients (if calculated tective level has been chosen as per the maximum limit of
earlier) will be cleared. Otherwise, if the fault is detected in compensation by the TCSC, i.e., 70% [25].
the power system using Eq. (10), SEs of all the phases are
calculated and corresponding ECs are also calculated at both 4.1. Relaying Performance for Single-phase Fault
relay ends using Eqs. (11) and (12). Now, the ECs with unity Table 1 shows the results obtained for a single-phase fault
(i.e., maximum) magnitudes are selected at both ends to detect (phase A) at different locations. Kma , Kmb , and Kmc are the
Gupta and Tripathy: Superimposed Energy-based Fault Detection and Classification Scheme for Series-compensated Line 1101

Distance Kma Kmb Kmc Kna Knb Knc tm (ms) tn (ms) ma mb mc na nb nc


0 –1 –0.006 –0.006 –1 –0.000 –0.000 1 2 1 0 0 1 0 0
20 –1 –0.008 –0.008 –1 0.005 0.005 2 2 1 0 0 1 0 0
40 –1 –0.002 –0.002 –1 0.002 0.002 2 2 1 0 0 1 0 0
60 –1 0.003 0.003 –1 –0.000 –0.000 2 2 1 0 0 1 0 0
80 –1 0.009 0.009 –1 –0.003 –0.003 2 2 1 0 0 1 0 0
100 –1 0.004 0.004 –1 –0.003 –0.003 3 1 1 0 0 1 0 0
R0 1 –0.026 –0.026 –1 –0.000 –0.000 2 2 1 0 0 1 0 0
–5 1 –0.029 –0.029 –1 –0.006 –0.006 2 2 1 0 0 1 0 0
–10 1 –0.031 –0.031 –1 –0.017 –0.017 2 2 1 0 0 1 0 0
Downloaded by [Indian Institute of Technology Roorkee], [Om Hari Gupta] at 10:00 09 June 2016

TABLE 1. Obtained results for phase-A-to-ground (a-g) fault at different locations

ECs obtained at relay m for phases A, B, and C, respectively. 4.2. Relaying Performance for Multi-phase Fault
Similarly, Kna , Knb , and Knc are obtained at relay n. Distance R0 The relaying scheme has been tested for two-phase and three-
denotes the external fault behind relay m and at zero distance. phase faults at different locations, and the results are presented
At relay m, the unit value of ma denotes the involvement of in Tables 2 and 3. From the results of Tables 2 and 3, it is clear
phase A in the fault, while the zero values of mb and mc denote that all internal faults have been detected and the fault types
no involvement of phases B and C in the fault. Similarly, at have been classified successfully. In the case of a two-phase
relay n, the unit value of na denotes the involvement of phase fault, the sound phase has almost zero magnitude of EC (the
A in the fault, while the zero values of nb and nc denote no results have been truncated to three digits after the decimal
involvement of phases B and C in the fault. The values of tm and point).
tn denote the time taken to detect and identify the direction of In the case of internal three-phase faults, ECs with unity
the fault at relays m and n, respectively. The ECs are captured magnitudes have negative signs, and for external three-phase
at the moment when the fault is detected successfully. faults, ECs with unity magnitudes at relay m have positive
As can be seen in Table 1, during all internal faults (i.e., with signs, which indicate reverse faults for relay m. Hence, the
positive distances), the ECs with maximum absolute values are scheme clearly differentiates between the internal and external
negative (i.e., –1) at both ends. These negative values indicate faults. Further, the relay successfully detects multi-phase faults
that both relays detect a forward fault, which is ultimately a for all cases considered. Table 3 comprises the results obtained
condition of an internal fault. On the other hand, for reverse for three-phase faults at different locations.
faults, the ECs with a maximum absolute value are positive at
relay m. As both relays do not detect a forward fault, it is the
condition of an external fault. The ECs of healthy phases at 4.3. Relaying Performance for Different Fault
both relay ends are less than the set threshold value (i.e., 0.1) Resistances
and clearly classify the type of fault. It is clear from the results Tables 4, 5, and 6 give the results for phase-A-to-ground faults
of Table 1 that the relaying scheme successfully detects the with different fault resistances (Rf = 10, 50, and 100 Ω). It
internal fault and classifies the type of fault. is clear from the results of Tables 4, 5, and 6 that the relying

Distance (km) Kma Kmb Kmc Kna Knb Knc tm (ms) tn (ms) ma mb mc na nb nc
0 –0.999 –1 0.000 –1 –0.999 0.000 1 1 1 1 0 1 1 0
20 –0.999 –1 0.000 –1 –0.999 0.000 1 1 1 1 0 1 1 0
40 –0.999 –1 0.000 –1 –0.999 0.000 1 1 1 1 0 1 1 0
60 –0.999 –1 0.000 –1 –1 0.000 1 1 1 1 0 1 1 0
80 –0.999 –1 0.000 –1 –1 0.000 2 1 1 1 0 1 1 0
100 –0.999 –1 0.000 –1 –1 0.000 2 1 1 1 0 1 1 0
R0 1 0.999 0.000 –0.998 –1 0.000 2 2 1 1 0 1 1 0
–5 1 0.999 0.000 –0.998 –1 0.000 2 2 1 1 0 1 1 0
–10 1 0.999 0.000 –0.998 –1 0.000 2 2 1 1 0 1 1 0

TABLE 2. Obtained results for two-phase fault at different locations


1102 Electric Power Components and Systems, Vol. 44 (2016), No. 10

Distance (km) Kma Kmb Kmc Kna Knb Knc tm (ms) tn (ms) ma mb mc na nb nc
0 –0.332 –1 –0.177 –0.449 –1 –0.109 1 2 1 1 1 1 1 1
20 –0.264 –1 –0.234 –0.453 –1 –0.095 1 2 1 1 1 1 1 0
40 –0.330 –1 –0.180 –0.327 –1 –0.183 2 2 1 1 1 1 1 1
60 –0.313 –1 –0.182 –0.276 –1 –0.223 2 2 1 1 1 1 1 1
80 –0.197 –1 –0.310 –0.220 –1 –0.280 2 2 1 1 1 1 1 1
100 –0.142 –1 –0.394 –0.081 –1 –0.504 2 1 1 1 1 0 1 1
R0 0.339 1 0.173 –0.289 –1 –0.212 2 2 1 1 1 1 1 1
–5 0.367 1 0.153 –0.309 –1 –0.198 2 2 1 1 1 1 1 1
–10 0.398 1 0.135 –0.342 –1 –0.176 2 2 1 1 1 1 1 1
Downloaded by [Indian Institute of Technology Roorkee], [Om Hari Gupta] at 10:00 09 June 2016

TABLE 3. Obtained results for three-phase fault at different locations

Distance (km) Kma Kmb Kmc Kna Knb Knc tm (ms) tn (ms) ma mb mc na nb nc
0 –1 –0.006 –0.006 –1 0.000 0.000 1 2 1 0 0 1 0 0
20 –1 –0.008 –0.008 –1 0.006 0.006 2 2 1 0 0 1 0 0
40 –1 –0.002 –0.002 –1 0.002 0.002 2 2 1 0 0 1 0 0
60 –1 0.003 0.003 –1 –0.000 –0.000 2 2 1 0 0 1 0 0
80 –1 0.010 0.010 –1 –0.003 –0.003 3 2 1 0 0 1 0 0
100 –1 0.006 0.006 –1 –0.007 –0.007 3 2 1 0 0 1 0 0
R0 1 –0.026 –0.026 –1 0.000 0.000 2 2 1 0 0 1 0 0
–5 1 –0.029 –0.029 –1 –0.005 –0.005 2 2 1 0 0 1 0 0
–10 1 –0.033 –0.033 –1 –0.016 –0.016 2 2 1 0 0 1 0 0

TABLE 4. Results obtained for a-g faults with Rf = 10 Ω

Distance (km) Kma Kmb Kmc Kna Knb Knc tm (ms) tn (ms) ma mb mc na nb nc
0 –1 –0.012 –0.012 –1 0.003 0.003 2 2 1 0 0 1 0 0
20 –1 –0.008 –0.009 –1 0.006 0.006 2 2 1 0 0 1 0 0
40 –1 –0.003 –0.003 –1 0.002 0.002 2 2 1 0 0 1 0 0
60 –1 0.002 0.002 –1 –0.000 –0.000 3 2 1 0 0 1 0 0
80 –1 0.011 0.011 –1 –0.004 –0.004 3 2 1 0 0 1 0 0
100 –1 0.011 0.011 –1 –0.007 –0.007 4 2 1 0 0 1 0 0
R0 1 –0.029 –0.029 –1 0.005 0.005 3 3 1 0 0 1 0 0
–5 1 –0.033 –0.033 –1 0.003 0.003 3 3 1 0 0 1 0 0
–10 1 –0.038 –0.038 –1 0.002 0.002 3 3 1 0 0 1 0 0

TABLE 5. Results obtained for a-g faults with Rf = 50 Ω

Distance (km) Kma Kmb Kmc Kna Knb Knc tm (ms) tn (ms) ma mb mc na nb nc
0 –1 –0.012 –0.012 –1 0.005 0.005 2 3 1 0 0 1 0 0
20 –1 –0.009 –0.009 –1 0.007 0.007 2 3 1 0 0 1 0 0
40 –1 –0.003 –0.003 –1 0.002 0.002 2 2 1 0 0 1 0 0
60 –1 0.002 0.002 –1 –0.001 –0.001 3 2 1 0 0 1 0 0
80 –1 0.011 0.011 –1 –0.004 –0.004 4 2 1 0 0 1 0 0
100 –1 0.011 0.013 –1 –0.007 –0.007 13 2 1 0 0 1 0 0
R0 1 –0.030 –0.030 –1 0.007 0.007 3 3 1 0 0 1 0 0
–5 1 –0.034 –0.033 –1 0.007 0.007 4 4 1 0 0 1 0 0
–10 1 –0.043 –0.042 –1 –0.001 0.000 13 13 1 0 0 1 0 0

TABLE 6. Results obtained for a-g faults with Rf = 100 Ω


Gupta and Tripathy: Superimposed Energy-based Fault Detection and Classification Scheme for Series-compensated Line 1103
Downloaded by [Indian Institute of Technology Roorkee], [Om Hari Gupta] at 10:00 09 June 2016

FIGURE 11. Phase A MOV current for a forward a-g fault at


40 km.

the fault and its direction. Hence, the relaying scheme is unaf-
fected by the presence of sub-synchronous components (which
is clear from Figure 10), and the relay successfully detects the
internal fault. Following formula can be used to determine the
sub-synchronous frequency [27]:
1
fr =  , (13)
2π L f C T C SC
where LF is the equivalent inductance up to the fault point, and
CTCSC is the equivalent TCSC capacitance. Table 7 presents
FIGURE 10. Voltage, current, superimposed voltage, and su- the approximate values of sub-synchronous frequencies with
perimposed current waveforms of phase A (filtered and at the fault distance variations observed at relay m. It can be seen
secondary sides of CT and VT) and ECs at relay m for a forward in the results included in Tables 1–6 that the relaying scheme
a-g fault at 40 km.
successfully detects the fault direction for all fault locations
given in Table 7.
scheme successfully detects the internal faults up to 100-Ω
fault resistance. Also, the type of fault has been successfully 4.5. Effect of Inductive Mode of TCSC
classified, which helps in single-pole tripping. The fault indi- It has been shown in the derivation that the relaying scheme
cators ma and na are 1 in all cases, and all other indicators are is independent of the mode of operation of the TCSC as it
zero. This clearly indicates successful classification of an a-g depends on the real components of the power system. The
fault. results of Table 8 clearly indicate that the relaying scheme is
unaffected by the TCSC mode and successfully detects the
4.4. Effect of the Sub-synchronous Resonance internal faults. Further, it is able to classify the type of fault.
The presence of a TCSC in the transmission line (when work- The unit values of fault indicators ma and na indicate the
ing in capacitive mode) introduces the sub-synchronous fre- involvement of phase A in the fault while all other indicators
quency [26] during fault disturbances, as seen in Figure 10. are zero. The detection time is also less than 5 ms for this case.
The corresponding MOV current of phase A is depicted in Fig-
ure 11. Superimposed quantities are obtained by subtracting
one cycle past value from its present value; i.e., superimposed Distance from Sub-synchronous
quantities should exist for one cycle after the inception of S.N. relay m (km) frequency (Hz)
fault. However, in Figure 10, superimposed quantities (voltage 1 20 40
and current) exist for more than one cycle due to the pres- 2 40 35
ence of sub-synchronous frequency (which is nearly 35 Hz 3 60 32
for this case). The SE due to these sub-synchronous compo- 4 80 30
nents is negligible in comparison to that of the fundamental 5 100 27
component. Sub-synchronous frequency causes negative SE
for forward faults and vice versa, as its existence depends on TABLE 7. Sub-synchronous frequencies with distance variations
1104 Electric Power Components and Systems, Vol. 44 (2016), No. 10

Distance (km) Kma Kmb Kmc Kna Knb Knc tm (ms) tn (ms) ma mb mc na nb nc
0 –1 –0.006 –0.006 –1 –0.000 –0.000 1 2 1 0 0 1 0 0
20 –1 –0.007 –0.007 –1 0.006 0.006 2 2 1 0 0 1 0 0
40 –1 –0.003 –0.003 –1 0.004 0.004 2 2 1 0 0 1 0 0
60 –1 0.004 0.004 –1 –0.000 –0.000 3 2 1 0 0 1 0 0
80 –1 0.006 0.006 –1 –0.002 –0.002 3 2 1 0 0 1 0 0
100 –1 0.002 0.002 –1 –0.002 –0.002 4 1 1 0 0 1 0 0
R0 1 –0.022 –0.022 –1 –0.000 –0.000 2 3 1 0 0 1 0 0
–5 1 –0.024 –0.024 –1 –0.005 –0.005 2 3 1 0 0 1 0 0
–10 1 –0.037 –0.037 –1 –0.015 –0.015 2 3 1 0 0 1 0 0
Downloaded by [Indian Institute of Technology Roorkee], [Om Hari Gupta] at 10:00 09 June 2016

TABLE 8. Obtained results for a-g fault at different locations for inductive mode

4.6. Effect of Change in TCSC Location fault. Further, a phase A fault is detected as the ECs of phases
To test the performance of the relaying scheme against TCSC B and C are less than the threshold value (i.e., 0.1).
location variations, the TCSC has been placed in the middle
of line B of Figure 7. For a forward a-g fault 80 km from relay
4.7. Effect of Load Change
m, Figure 12 depicts different plots of results obtained at relay
m. As the EC with maximum magnitude at relay m is –1, it is If a load change of less than 20% occurs, the relay will not cal-
clear that the relaying scheme is unaffected from the change culate SE and no detection of direction takes place. Moreover,
in TCSC location and successfully detects the direction of the to test the robustness of the scheme against load changes, 50%
load has been reduced at end n. As this load variation is more
than the threshold value of Eq. (10), i.e., more than 20% of
the rated line current, the relay will consider it as a fault in the
power system and will start calculating the ECs to find the di-
rection of suspected fault. Relay n should detect a reverse fault
because the load change has occurred behind relay n. As per
the criterion, if one of the relays detects a reverse fault, it will
be considered as an external disturbance. For 50% load reduc-
tion at relay n, Figure 13 shows three-phase voltages, currents,
their superimposed values, and ECs at end n. The maximum
value out of all three ECs is +1, which indicates the detection
of a reverse disturbance at relay n. Therefore, as one of the
relays detects a reverse fault, the load reduction is identified
as an external disturbance. The relay will return with a similar
conclusion if, instead of removing the load, a large block of
load is applied suddenly. Figure 14 shows the results taken for
a 50% increase in the rated load. The maximum value out of
all three ECs is +1 at relay n, which again indicates a reverse
disturbance, and thus, this change of 50% load is treated as an
outside disturbance.
For different levels of load variations, Table 9 presents the
decision taken by the scheme in response to load variations at
end n; i.e., a disturbance due to load change occurs in the for-
ward direction of relay m and in the reverse direction of relay
n. It is clear from Table 9 that for a load variation of ±10%, no
FIGURE 12. Voltage, current, superimposed voltage, and su- EC is calculated, as this change is in the range of ±20%. For
perimposed current waveforms of phase A (filtered and at the load variations above ±20%, the EC with maximum magni-
secondary sides of CT and VT) and ECs at relay m for a forward tude at end m [ECm (max)] is –1 (i.e., forward disturbance), and
a-g fault at 80 km. the EC with maximum magnitude at end n [ECn (max)] is +1
Gupta and Tripathy: Superimposed Energy-based Fault Detection and Classification Scheme for Series-compensated Line 1105
Downloaded by [Indian Institute of Technology Roorkee], [Om Hari Gupta] at 10:00 09 June 2016

FIGURE 13. Voltage, current, superimposed voltage, and su- FIGURE 14. Voltage, current, superimposed voltage, and su-
perimposed current waveforms at end n (filtered and at the perimposed current waveforms at end n (filtered and at the
secondary sides of CT and VT) and ECs at relay n for 50% secondary sides of CT and VT) and ECs at relay n for sudden
load reduction. application of 50% of rated load.

(i.e., reverse disturbance). As relay n detects a reverse distur- up the threshold. Usually, in the practical power system, source
bance, the decision made by the scheme is an external dis- impedance is not always constant, which makes this scheme
turbance. Therefore, the scheme is unaffected from the load vulnerable to the source impedance variations. Moreover, the
variations, even if the load change exceeds the limit described schemes of [28, 30] used the communication channel all the
in Eq. (10), i.e., 20% of rated value. time.
Another high-speed directional-based scheme was pro-
4.8. Comparison with Existing Schemes posed in [14] that is applicable to the TCSC-compensated
Fault component integrated impedance (FCII) based schemes line and is of high speed. However, the scheme depends on
were proposed in [28, 29]. For an internal fault, FCII is very the fault inception angle; the duration of establishment of the
small, and for an external fault, FCII is large. The scheme criterion can be as small as 2.2 milliseconds. The proposed
clearly identifies the faults inside the protective zone even if the
fault resistances are very high. However, its dependability on
the source impedance makes it vulnerable to the large changes Load change (% of rated) ECm (max) ECn (max) Decision
in the system. On the other hand, the scheme presented in this
+10 — — —
article is independent of the source impedance variations and +30 –1 +1 External
only requires knowledge of the rated line current. +40 –1 +1 External
A fault component integrated power (FCIP) based pilot +50 –1 +1 External
relaying scheme was proposed in [30]. The FCIP is the sum –10 – – —
of real components of apparent powers at local and remote –30 –1 +1 External
ends. If the FCIP is negative, it is an internal fault; else, it –40 –1 +1 External
–50 –1 +1 External
is an external fault. The proposal describes a useful scheme
for transmission line protection. The scheme proposed in [30]
required information about source parameters before setting TABLE 9. Decision made by the scheme for load variations
1106 Electric Power Components and Systems, Vol. 44 (2016), No. 10

in the system). On the other hand, the scheme presented in


this article detects the fault direction at time t1 (1.002 sec),
i.e., as soon as the relay satisfies the condition of Eq. (10).
In all cases considered for the performance investigation of
the proposed relaying scheme, the detection time is nearly 5
milliseconds. Hence, the proposed relaying scheme is faster
than that of [6]. Furthermore, the scheme of [6] is not able to
classify the type of fault as it is based on positive-sequence
components.
Overall, the comparison reveals that the scheme presented
Downloaded by [Indian Institute of Technology Roorkee], [Om Hari Gupta] at 10:00 09 June 2016

in this study is fast, independent of the source impedance


variations, and independent of other external changes in the
system, whereas (1) the schemes of [28, 30] depend on source
impedance, (2) the scheme of [14] depends on the fault incep-
tion angle, and (3) the scheme of [6] does not classify the type
of fault.

FIGURE 15. Comparison with scheme of [6] for a fault in line 4.9. Effect of Change in Compensation Level
B 90 km from relay m.
In Sections 4.1–4.4 and 4.6–4.8, 48% TCSC capacitive com-
pensation is used, and in Section 4.5, 32% TCSC inductive
scheme, on the contrary, is independent of the inception angle, compensation is used. The results have been obtained using
which is clear from Eqs. (5) and (6). these two modes of operation, which clearly show the effec-
In [6], a directional relaying scheme was proposed for a tiveness of the relaying scheme. To further investigate the ef-
TCSC-compensated line that used three positive-sequence- fectiveness of the relaying scheme against change in compen-
based classifiers and a voting technique to distinguish between sation level, the TCSC is now operated in capacitive boost
forward and reverse faults. First, the classifier uses the an- mode with a 70% compensation level. In case of 70% com-
gle between the positive-sequence components of current and pensation, the rated secondary current IR changes to 5.04 A
voltage (φ 1 ). Second, the classifier uses the angle between (peak). So the threshold setting of current in Eq. (10) will
the positive-sequence superimposed voltage and current (φ 2 ). be 1.008 A. The scheme was found to work correctly, and
Third, the classifier is based on the angle between the positive- for a forward ab inter-phase fault at 60 km, different wave-
sequence components of fault current and pre-fault current forms of phase A and ECs at relay m are presented in Fig-
(φ 3 ). In the case of forward or reverse fault, at least two ure 16. It can be seen in the figure that after fault inception,
classifiers will estimate the correct direction, and using the EC magnitudes of phases A and B at relay m are more than the
voting technique method, a final decision is made. To com- threshold value, and the EC with maximum magnitude is –1.
pare the scheme presented in this study with the scheme of Therefore, a multi-phase forward fault is detected by relay m.
[6], a numerical result is obtained for a phase-A-to-C fault Similarly, at relay n, a multi-phase forward fault is detected,
90 km from relay n in line B; the comparative result is pre- and it is considered to be a multi-phase internal fault. As both
sented in Figure 15. The pre-fault φ 1 is 0.0604 radian (3.46◦ ), the line current and compensation level have increased, the
whereas pre-fault φ 2 and φ 3 are zero. A decision should be MOV will conduct most often and draws more current during
made only if any two out of three classifiers (φ 1 , φ 2 , and the fault, in turn changing the effective TCSC impedance as
φ 3 ) cross a certain threshold value. There should be certain shown in Figure 17. This is the reason behind small oscil-
threshold settings for classifiers to detect the changes in the lations (or small sub-synchronous frequency) in the current
classifier values as there can be small fluctuations during the waveform.
pre-fault condition due to load variations, etc. Assuming a In Section 4.10, 30% TCSC capacitive compensation is
threshold of 0.0604 radian (equal to pre-fault φ 1 ), the scheme provided in the middle of line B (Figure 18). Overall, four
of [6] detects the direction of fault at time t2 (1.007 sec), and compensation levels have been used: 30% capacitive, 32% in-
if the threshold changes, the detection time may further in- ductive, 48% capacitive, and 70% capacitive. The performance
crease (considering that the assumed threshold, 3.46◦ , is very of the proposed relaying scheme has been found to be accurate
small and makes the scheme vulnerable to the small changes in all cases.
Gupta and Tripathy: Superimposed Energy-based Fault Detection and Classification Scheme for Series-compensated Line 1107

depict different waveforms and ECs obtained for a phase A


fault at F 1 (forward 150 km from relay m) and at F 2 (reverse
25 km from relay m). It is clear from both figures that for a
forward fault, the EC at relay m with maximum absolute value
is –1, and for a reverse fault, the EC at relay m with maximum
absolute value is +1. However, at relay n, both were detected
as a forward fault. Hence, for an internal fault at F 1 , both
relays detect a forward fault and generate a trip signal. Though
the sub-synchronous frequency exists, which can be seen in
Figure 19, the change in line length does not affect the relaying
Downloaded by [Indian Institute of Technology Roorkee], [Om Hari Gupta] at 10:00 09 June 2016

scheme and successfully detects the internal faults.

4.11. Communication Delay and Speed of the Relaying


A relay must detect the fault within the specified time (i.e.,
three cycles) [31]. The relaying scheme has been tested us-
ing the synchronized samples of both ends obtained from
PSCAD/EMTDC simulations. However, the speed of the re-
laying also depends on the carrier that is used to carry the
data from the remote end to the local end. High-speed com-
munication channels are employed in newly built transmission
lines [32]. With the availability of optical fibers of low re-
fractive index (approximately 1.52) [33], the signal takes less
than 0.6 ms to reach the distance of 100 km [34]. Further, the
FIGURE 16. Voltage, current, superimposed voltage, and su- encoding and decoding delays are also present (approximately
perimposed current waveforms of phase A (filtered and at the 4 ms). Therefore, less than 10 ms are required for communi-
secondary sides of CT and VT) and ECs at relay m for a forward cation even if the transmission line is 300 km long. From the
fault at 60 km.
obtained results, it is clear that both relays take nearly 5 ms to
detect the fault direction when synchronized data are used. If
4.10. Relaying Performance for Long Transmission Line the communication delay is also included, the relay would still
A transmission network with two line sections of 250 km (line be able to detect internal fault within 20 ms (one cycle for a
B, to be protected) and 50 km (line A) has been simulated to test 50-Hz power system).
the effectiveness of the relaying scheme on a long transmission
line. The per unit transmission line parameters remain the same
5. DISCUSSION
as previous. The load angle has been increased from 30◦ to 45◦ .
With the compensation level of 30%, the TCSC is connected Generally, the real components of the power system are ig-
in the middle of line B, as shown in Figure 18. The rated nored while deriving the criterion of protection; however, in
secondary current IR is 3.42 A (peak), so the threshold setting this work, both the real and the reactive components have been
of current in Eq. (10) will be 0.684 A. Figures 19 and 20 considered while establishing the criterion. The advantage of
the relaying scheme is that it uses the communication channel
only when there is a fault in the power system. Further, the
criterion establishes immediately after the inception of fault
and provides both the fault detection and classification in less
than 10 ms. Including channel delay, encoding delay, and de-
coding delay, the fault is detected within one cycle of power
frequency. The relaying scheme is not only fast, but it is also
unaffected from the transients because the low-pass filter has
been used to filter out the high-frequency transients. Moreover,
the criterion is adaptive to system changes and only needs to
FIGURE 17. TCSC dynamic impedance in response to a dis- update the threshold value of Eq. (10) in case there is any
turbance at time 0.5 sec. change in the line parameters or load.
1108 Electric Power Components and Systems, Vol. 44 (2016), No. 10
Downloaded by [Indian Institute of Technology Roorkee], [Om Hari Gupta] at 10:00 09 June 2016

FIGURE 18. Mid-point TCSC-compensated transmission line (line B) protected with proposed scheme.

FIGURE 19. Voltage, current, superimposed voltage, and su- FIGURE 20. Voltage, current, superimposed voltage, and su-
perimposed current waveforms of phase A (filtered and at the perimposed current waveforms of phase A (filtered and at the
secondary sides of CT and VT) and ECs at relay m for a forward secondary sides of CT and VT) and ECs at relay m for a reverse
fault at 150 km. fault at 25 km.

6. CONCLUSION
An internal fault detection and fault classification relaying laying scheme has been analyzed using PSCAD/EMTDC sim-
scheme has been proposed in this study. ECs have been used ulations, and it was found that the scheme successfully detects
to obtain the direction of fault, and if both relays detect a for- the internal faults and also correctly classifies the type of fault.
ward fault, then it is considered to be an internal fault. If any Furthermore, the scheme was found to be accurate and robust
phase possesses a magnitude of EC less than 0.1, then that par- against sub-synchronous resonance, voltage/current reversals,
ticular phase is considered sound. Single-pole tripping can be and variations in TCSC mode, TCSC location, compensation
used if there is a single-phase fault; if it is a multi-phase fault, level, line length, fault resistance, and fault location. More-
all three phases have to be tripped. The performance of the re- over, the scheme is fast enough to detect the internal fault well
Gupta and Tripathy: Superimposed Energy-based Fault Detection and Classification Scheme for Series-compensated Line 1109

within one cycle, including delays in communication, encod- of thyristor-controlled series capacitor,” IET Gener. Transm.
ing, and decoding. Distrib., Vol. 8, No. 12, pp. 2083–2091, December 2014.
[15] Eissa, M. M., “Development and investigation of a new high-
speed directional relay using field data,” IEEE Trans. Power
REFERENCES Deliv., Vol. 23, No. 3, pp. 1302–1309, July 2008.
[16] Sidhu, T. S., Singh, H., and Sachdev, M. S., “Design, im-
[1] Hingorani, N. G., and Gyugyi, L., Understanding FACTS: Con- plementation and testing of an artificial neural network based
cepts and Technology of Flexible AC Transmission Systems. fault direction discriminator for protecting transmission lines,”
New York: Wiley, Chap. 1, 2000. IEEE Trans. Power Del., Vol. 10, No. 2, pp. 697–706, April
[2] Altuve, H. J., Mooney, J. B., and Alexander, G. E., “Advances 1995.
in series-compensated line protection,” 2009 62nd Annual Con- [17] Sanaye-Pasand, M., and Malik, O. P., “Implementation and lab-
ference for Protective Relay Engineers, pp. 263–275, TX, 30 oratory test results of an Elman network-based transmission
Downloaded by [Indian Institute of Technology Roorkee], [Om Hari Gupta] at 10:00 09 June 2016

March–2 April 2009. line directional relay,” IEEE Trans. Power Del., Vol. 14, No. 3,
[3] Gajbhiye, R. K., Gopi, B., Kulkarni, P., and Soman, S. A., pp. 782–788, July 1999.
“Computationally efficient methodology for analysis of faulted [18] Sanaye-Pasand, M., and Malik, O. P., “High speed transmis-
power systems with series-compensated transmission lines: A sion line directional protection evaluation using field data,”
phase coordinate approach,” IEEE Trans. Power Del., Vol. 23, IEEE Trans. Power Del., Vol. 14, No. 3, pp. 851–856, July
No. 2, pp. 873–880, April 2008. 1999.
[4] Bhaskar, M. A., and Indhirani, A., “Impact of FACTS devices [19] Verma, A., and Yadav, A., “ANN based fault detection & di-
on distance protection in transmission system,” 2014 IEEE Na- rection estimation scheme for series compensated transmission
tional Conference on Emerging Trends in New & Renewable lines,” 2015 IEEE International Conference on Electrical, Com-
Energy Sources And Energy Management (NCET NRES EM), puter and Communication Technologies (ICECCT), pp. 1–6,
pp. 52–58, Chennai, India, 16–17 December 2014. Coimbatore, India, 5–7 March 2015.
[5] Jena, P., and Pradhan, A. K., “A positive-sequence directional [20] Solat, A., and Deihimi, A., “A novel scheme for distance protec-
relaying algorithm for series-compensated line,” IEEE Trans. tion of series compensated transmission lines with TCSC using
Power Del., Vol. 25, No. 4, pp. 2288–2298, October 2010. artificial neural networks,” 20th Iranian Conference on Electri-
[6] Jena, P., and Pradhan, A. K., “Directional relaying in the cal Engineering (ICEE2012), pp. 517–522, Tehran, Iran, 15–17
presence of a thyristor-controlled series capacitor,” IEEE May 2012.
Trans. Power Deliv., Vol. 28, No. 2, pp. 628–636, April [21] He, B., Jin, H., and Li, J., “The energy based directional pro-
2013. tection of transmission lines,” Proceedings of the 1998 Interna-
[7] Biswal, M., Pati, B. B., and Pradhan, A. K., “Directional relay- tional Conference on Power System Technology (POWERCON
ing of series-compensated line using an integrated approach,” ‘98), Cat. No. 98EX151, Vol. 2, pp. 1163–1167, Beijing, 18-21
Electr. Power Compon. Syst., Vol. 40, No. 7, pp. 691–710, April August 1998.
2012. [22] Gao, H., and Crossley, P. A., “Design and evaluation of a di-
[8] Biswal, M., Pati, B. B., and Pradhan, A. K., “Directional relaying rectional algorithm for transmission-line protection based on
for double circuit line with series compensation,” IET Gener. positive-sequence fault components,” IEE Proc. Gener. Transm.
Transm. Distrib., Vol. 7, No. 4, pp. 405–413, April 2013. Distrib., Vol. 153, No. 6, pp. 711–718, November 2006.
[9] Jalilian, A., Hagh, M. T., and Hashemi, S. M., “An innovative [23] Manitoba HVDC Research Centre, “PSCAD/EMTDC—
directional relaying scheme based on postfault current,” IEEE 4.5.2.0: Electromagnetic transients program including DC sys-
Trans. Power Del., Vol. 29, No. 6, pp. 2640–2647, December tems,” 2013.
2014. [24] Woodworth, J., “MOV protection of series capacitor banks,”
[10] Funk, A. T., and Malik, O. P., “Performance of sequence direc- Arrester Factors008, 2008.
tional elements on MOV protected series compensated trans- [25] Yang, G. Y., Hovland, G. E., Majumder, R., and Dong, Z. Y.,
mission lines,” Eur. Trans. Electr. Power, Vol. 12, No. 1, pp. “Optimal TCSC placement based on line flow equations via
53–61, January 2002. mixed-integer linear programming,” 2006 Australasian Univer-
[11] Perera, N., and Rajapakse, A. D., “Series-compensated double- sities Power Engineering Conference (AUPEC’06), pp. 1–6,
circuit transmission- line protection using directions of cur- Melbourne, Australia, 10–13 December 2006.
rent transients,” IEEE Trans. Power Del., Vol. 28, No. 3, pp. [26] Novosel, D., “Problems and solutions for microprocessor pro-
1566–1575, July 2013. tection of series compensated lines,” 6th International Confer-
[12] Jafarian, P., and Sanaye-Pasand, M., “High-speed ence on Developments in Power Systems Protection, pp. 18–23,
superimposed-based protection of series-compensated Nottingham, UK, 25–27 March 1997.
transmission lines,” IET Gener. Transm. Distrib., Vol. 5, No. [27] Balance, J., and Goldberg, S., “Subsynchronous resonance in
12, pp. 1290–1300, 2011. series compensated transmission lines,” IEEE Trans. Power
[13] Hashemi, S. M., Hagh, M. T., and Seyedi, H., “Transmission- Appar. Syst., Vol. PAS-92, No. 5, pp. 1649–1658, September
line protection: A directional comparison scheme using the av- 1973.
erage of superimposed components,” IEEE Trans. Power Deliv., [28] Suonan, J., Liu, K., and Song, G., “A novel UHV/EHV
Vol. 28, No. 2, pp. 955–964, April 2013. transmission-line pilot protection based on fault component in-
[14] Hagh, M. T., Seyedi, H., and Hashemi, S. M., “High-speed relay- tegrated impedance,” IEEE Trans. Power Del., Vol. 26, No. 1,
ing scheme for protection of transmission lines in the presence pp. 127–134, January 2011.
1110 Electric Power Components and Systems, Vol. 44 (2016), No. 10

[29] He, S., Suonan, J., and Kang, X., “Fault component integrated Rated primary current is 2.78 kA (peak) and rated primary
impedance-based pilot protection scheme for the TCSC com- voltage is 319.56 kV (peak per phase); rated secondary
pensated EHV/UHV transmission line,” 2011 International current IR is 4.377 A (peak), so the threshold setting of the
Conference on Advanced Power System Automation and Pro-
current in Eq. (10) will be 0.8754 A; rated secondary voltage
tection, Vol. 1, pp. 517–523, Beijing, 16–20 October 2011.
[30] Hashemi, S. M., Seyedi, H., and Ghanizadeh Bolandi, T., at the relay bus is 100.9 V; current transformer (CT) ratio is
“Protection of transmission lines using fault component inte- 3000 A/5A; voltage transformer (VT) ratio is 3000, and VT
grated power,” IET Gener. Transm. Distrib., Vol. 8, No. 12, pp. is used because the transient performance of capacitor VT is
2163–2172, December 2014. inferior [35].
[31] Horowitz, S. H., and Phadke, A. G., Power System Relaying,
3rd ed., West Sussex, England: John Wiley & Sons Ltd., Chap.
1, 2008.
Downloaded by [Indian Institute of Technology Roorkee], [Om Hari Gupta] at 10:00 09 June 2016

[32] Xu, Z. Y., Du, Z. Q., Ran, L., Wu, Y. K., Yang, Q. X., and He, J. BIOGRAPHIES
L., “A current differential relay for a 1000-kv uhv transmission
line,” IEEE Trans. Power Del., Vol. 22, No. 3, pp. 1392–1399, Om Hari Gupta received his M.Tech. in electrical engi-
July 2007. neering with specialization in power electronics and ap-
[33] Hecht, E., Optics. Boston, MA: Addison-Wesley, Chap. 5, 2002. plication specific integrated circuit (ASIC) design from
[34] Gupta, O. H., and Tripathy, M., “An innovative pilot relaying MN National Institute of Technology, Allahabad, India,
scheme for shunt-compensated line,” IEEE Trans. Power Del.,
in 2011. Currently, he is pursuing his Ph.D. in elec-
Vol. 30, No. 3, pp. 1439–1448, June 2015.
[35] Ram, B., and Vishwakarma, D. N., Power System Protection and trical engineering at the Indian Institute of Technology
Switchgear, Vol. 1.,: New Delhi, India: McGraw-Hill Education Roorkee, India. He has more than 3 years of teaching expe-
(India) Pvt. Limited, 2011. rience. His research interests include power system compen-
sation and protection, control of drives, and soft computing
applications.
APPENDIX A: DATA FOR TEST POWER SYSTEM
Transmission line and source: 50 Hz, R1 = 0.018 /km, Manoj Tripathy received his B.E. in electrical engineering
L1 = 1.178 mH/km, R0 = 0.360 /km, L0 = 3.885 mH/km, from Nagpur University, Nagpur, India, in 1999; his M.Tech. in
C 1 = 14.020 nF/km, C 0 = 9.220 nF/km; two identical instrumentation and control from Aligarh Muslim University,
sources are of 400 kV, Rs1 = 1.430 , Ls1 = 51.590 mH, Aligarh, India, in 2002; and his Ph.D. in electrical engineering
Rs0 = 3.070 , and Ls0 = 91.490 mH; length of line A = from the Indian Institute of Technology Roorkee, Roorkee, In-
10 km, length of line B = 100 km. dia, in 2008. He is currently working as an assistant professor
TCSC: main capacitor = 179 μF, TCR inductance = 9 mH, in the Department of Electrical Engineering, Indian Institute
phase-locked loop (PLL) proportional gain = 30, and PLL of Technology Roorkee, Uttarakhand, India. He is a reviewer
integral gain = 300; the TCSC is working at β = 159.3◦ for for various international journals in the area of power systems
capacitive mode and β = 132◦ for inductive mode; ZTCSC = and speech processing. His fields of interest are wavelets, neu-
17.8 in capacitive mode and 11.98 Ω in inductive mode; ral networks, optimization techniques, content-based image
current reversal takes place for forward faults at a distance retrieval, digital instrumentation, digital protective relays, and
up to 1.2 km and voltage reversal up to 70 km. digital speech processing.

View publication stats

Potrebbero piacerti anche