Sei sulla pagina 1di 2

Detailed Performance Summary For Untitled1(1)

Project: ~Untitled14 02/07/2008


Prepared By: 11:25AM

Unit Information
Tag Name:........................................Untitled1(1)
Model Number:....................................30XA0452
Condenser Type:................................Air Cooled
Compressor Type:......................................Screw
Nameplate Voltage:................................400-3-50 V-Ph-Hz
Quantity:.............................................................1
Refrigerant:................................................R134A
Minimum Capacity:........................................15.0 %
Shipping Weight:..........................................4416 kg
Operating Weight:.........................................4490 kg
Unit Length:..................................................4798 mm
Unit Width:....................................................2253 mm
Unit Height:...................................................2297 mm
Minimum Outdoor Operating Temp:................-10 °C

Performance Information
Cooling Capacity:........................................401.3 kW
Total Compressor Power:............................145.0 kW
Total Fan Motor Power:..................................11.6 kW
Total Unit Power (without pump):.................156.6 kW
Efficiency (without pump):.............................2.56 COP

Evaporator Information
Fluid Type:.......................................Fresh Water
Fouling Factor:...........................................0.0880 (sqm-K)/kW
Number of Passes:.............................................2
Leaving Temperature:......................................7.0 °C
Entering Temperature:...................................12.0 °C
Fluid Flow:...................................................19.13 L/s
Pressure Drop:..............................................28.6 kPa

Condenser Information
Altitude:...............................................................0 m
Number of Fans:.................................................8
Total Condenser Fan Air Flow:....................36111 L/s
Entering Air Temperature:..............................43.0 °C

Electrical Information
Unit Voltage:...........................................400-3-50 V-Ph-Hz
Connection Type:.............................Single Point
Standby Power:...............................................0.2 kW
Minimum Voltage:...........................................360 Volts
Maximum Voltage:..........................................440 Volts
Power Factor:................................................0.86

Electrical Electrical
Amps (Un) Circuit 1 Circuit 2
Max Unit Current Draw 316.4 N/A
(RLA)
Max Start Up Current 509.7 N/A
(ICF)
Nominal Unit Current 237.5 N/A
Draw (A)

Accessories and Installed Options


Opt. 119 High Efficiency Option
Opt. 253 Unit without Comp. Enclosure

Packaged Chiller Builder EMEA 3.24 Page 1 of 2


Detailed Performance Summary For Untitled1(1)
Project: ~Untitled14 02/07/2008
Prepared By: 11:25AM

Integrated Part Load Value (ARI) IPLV: 4.67 COP

Unit Performance
Percent of Full Load Capacity, % 100.0 75.0 50.0 25.0
Percent of Full Load Power, % 100.0 57.8 33.0 13.2
Unloading Sequence B B B B
Cooling Capacity, kW 446.6 335.0 223.3 111.7
Total Unit Power, kW 139.8 80.9 46.2 18.5
Efficiency, COP 3.19 4.14 4.84 6.04
Evaporator Data
Fluid Entering Temperature, °C 12.2 10.8 9.4 8.0
Fluid Leaving Temperature, °C 6.7 6.7 6.7 6.7
Fluid Flow Rate, L/s 19.23 19.23 19.23 19.23
Fouling Factor, (sqm-K)/kW 0.0176 0.0176 0.0176 0.0176
Condenser Data
Entering Air Temperature, °C 35.0 26.7 18.3 12.8

NPLV NPLV: 4.18 COP

Unit Performance
Percent of Full Load Capacity, % 100.0 75.0 50.0 25.0
Percent of Full Load Power, % 100.0 54.3 28.9 11.3
Unloading Sequence B B B B
Capacity, kW 401.3 301.0 200.6 100.3
Total Unit Power, kW 156.6 85.1 45.3 17.8
Efficiency, COP 2.56 3.54 4.43 5.65
Evaporator Data
Fluid Entering Temperature, °C 12.0 10.7 9.5 8.2
Fluid Leaving Temperature, °C 7.0 7.0 7.0 7.0
Fluid Flow Rate, L/s 19.13 19.13 19.13 19.13
Fouling Factor, (sqm-K)/kW 0.0880 0.0880 0.0880 0.0880
Condenser Data
Entering Air Temperature, °C 43.0 31.7 20.3 12.8

Load Line

Unit Performance
Percent of Full Load Capacity, % 100.0 75.0 50.0 25.0
Percent of Full Load Power, % 100.0 72.9 53.8 18.2
Unloading Sequence B B B B
Capacity, kW 401.3 301.0 200.6 100.3
Total Unit Power, kW 156.6 114.2 84.3 28.5
Efficiency, COP 2.56 2.63 2.38 3.52
Evaporator Data
Fluid Entering Temperature, °C 12.0 10.7 9.5 8.2
Fluid Leaving Temperature, °C 7.0 7.0 7.0 7.0
Fluid Flow Rate, L/s 19.13 19.13 19.13 19.13
Fouling Factor, (sqm-K)/kW 0.0880 0.0880 0.0880 0.0880
Condenser Data
Entering Air Temperature, °C 43.0 43.0 43.0 30.6

Cooling and/or heating performance data according to EN 14511 and certified by EUROVENT.
Sound Power Lw according to ISO 9614-1 and EUROVENT standard 8/1.