Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
College of Engineering
Legazpi City
Mechanical Engineering Department
A.Y. 2015-2016
Submitted by:
Deniel Ross P. Daep
Jose Dindo T. Diesta
Ronald John N. Dometita
Mel-john M. Montiveros
Ian A. Quiñones
Jonett Jan R. Resontoc
Jeffrey D. Villanueva
BSME 5-A
Submitted to:
Engr. Agerico U. Llovido, PME
Professor
1. Introductory Statement…………………………………………………………………. 1
2. Objectives of the Engineering Report……………………………………………….. 1
3. Importance of the Engineering Report ……………………………………………... 2
4. Limitation of the Engineering Report…………………………………………………. 2
5. Engineering Design Proper …………………………………………………………….. 3
5.1 Design Definitions …………………………………………………………….... 3
5.2 Types of Sprinkler Systems …………………………………………………..... 5
5.3 Definition of System Components ..………………………………………… 6
5.4 Types of Sprinkler ……………………………………………………………….. 7
5.5 Classification of Occupants …………………………………………………. 9
5.5.1 Light Hazard Occupancies …………………………………….…. 9
5.5.2 Ordinary Hazard Occupancies ………………………………..… 9
5.5.3 Extra Hazard Occupancies ……………………………………... 10
5.6 Sprinkler …………………………………………………………...………….… 12
5.6.1 Sprinkler Discharge Characteristics ..……………………….….. 12
5.6.2 Temperature Characteristics ……………………………………. 12
5.7 Design Requirements .……………………………………………………...... 13
5.8 Design Methodology ………………………………………………………… 13
5.9 Building Fire Hazard Classification ……………........................................ 13
5.10 Water Demand Requirement – Hydraulic Calculation Methods ….. 15
5.10.1 Hose Stream Demand ……………………………………………15
5.10.2 Density/Area Curves …………………………………………..….15
5.10.3 Systems with Multiple Hazard Classifications ……………..... 16
5.10.4 Restrictions ……………………………………………………….... 17
5.11 Hydraulic Calculation Procedures ……………………………………… 17
5.11.1 General ………………………….…………………………..…….. 17
5.11.2 Friction Loss Formula ….…………………………………………. 17
5.11.3 Hydraulic Junction Points …………………………………….….19
5.11.4 Equivalent Pipe Lengths of Valves and Fittings ………..…….19
5.11.5 C-Factor …………...………………………………………...…….. 20
5.11.6 Room Design Method …………………………………………… 20
5.11.7 Maximum Protection Area of Coverage ……………………. 20
5.11.8 Minimum Operating Pressure ………………………………...... 21
5.11.9 Pipe Schedule ……………………………………………………. 21
5.11.10 Hydraulic Design Calculation ………………………………… 23
5.12 Water Tank Sizing …………………………………………………………..... 41
5.13 Fire Pump and Fuel Tank Selection ………………………………………. 41
6. Specification ………………………………………………………………………….….. 43
6.1 Fire Pump ……………………………………………………………………….. 43
6.2 Sprinkler and Accessories ……………………………………………………. 45
7. Installation of Fire Sprinkler System ………………………………………………….... 46
8. Operation of Fire Sprinkler System ……………………………………………………. 48
9. Maintenance and Testing of Fire Sprinkler System ………………………………... 49
10. Engineering Economics – Analysis .……………………………………………….…. 57
10.1 Cost Estimates ………………………………….…………….……………..… 57
11. Evaluation, Observation, Conclusion and Recommendations ………………. 57
12. Bibliography ……………………………………………………………………….……. 59
APPENDICES
APPENDIX A – FIRE PUMPS MODEL BROCHURE
APPENDIX B – SPRINKLER MODEL BROCHURE
APPENDIX C – SPRINKLER SYSTEM PIPING LAYOUT
APPENDIX D – DESIGN CALCULATION
1. INTRODUCTORY STATEMENT
Over the years, fire sprinklers have become mandatory safety equipment
in certain occupancies, including, but not limited to newly constructed hospitals,
schools, hotels and other public buildings, subject to the local building codes
and enforcement. However, outside of the US and Canada, sprinklers are rarely
mandated by building codes for normal hazard occupancies which do not have
large numbers of occupants (e.g. factories, process lines, retail outlets, petrol
stations etc).
1
3. IMPORTANCE OF THE ENGINEERING REPORT
The report will explain procedures in designing the fire sprinkler pipe sizing
and pump size based on NFPA 13 design criteria.
Sprinkler systems for all hotels and motels can be designed under NFPA 13,
Standard for the Installation of Sprinkler Systems. All hotels and motels up to four
stories in height can be designed per NFPA 13R, Standard for the Installation of
Sprinkler Systems in Residential Occupancies up to and Including Four Stories in
Height.
The sprinkler systems are designed to deal mainly with solid-fuel fires, but
can serve also to hold a flammable-liquid fire in check and to extinguish some oil
fires (e.g. transformer oil fires) by deluge sprinklers, by purely using water. With
suitable foam concentrate added to the water, its fire-fighting capability on oil
fires can be greatly enhanced.
Each system is designed for its particular function, and its features may
vary widely according to the purpose. In general, a system will consist of the
following items:
2
6. A detector, or detector system, capable of actuating the fire-fighting /
protection system. The detector can be the sprinkler itself or other
detection device / system.
7. Other features include flow detectors, pressure switches for starting
pumps, and control / signal monitoring alarm panels etc.
Ceiling Height. The distance between the floor and the underside of the ceiling
above (or roof deck) within the area.
Dwelling Unit. One or more rooms arranged for the use of one or more individuals
living together, as in a single housekeeping unit normally having cooking, living,
sanitary, and sleeping facilities. For purposes of this standard, dwelling unit
includes hotel rooms, dormitory rooms, apartments, condominiums, sleeping
rooms in nursing homes, and similar living units.
3
Fire Suppression. Sharply reducing the heat release rate of a fire and preventing
its regrowth by means of direct and sufficient application of water through the
fire plume to the burning fuel surface.
Pipe Schedule System. A sprinkler system in which the pipe sizing is selected from
a schedule that is determined by the occupancy classification and in which a
given number of sprinklers are allowed to be supplied from specific sizes of pipe.
4
5.2 TYPES OF SPRINKLER SYSTEM
5
Pre-action Sprinkler System. A sprinkler system employing automatic
sprinklers that are attached to a piping system that contains air that might or
might not be under pressure, with a supplemental detection system installed in
the same areas as the sprinklers.
Branch Lines. The pipes in which the sprinklers are placed, either directly or
through risers.
Cross Mains. The pipes supplying the branch lines, either directly or
through risers.
Feed Mains. The pipes supplying cross mains, either directly or through
risers.
Flexible Listed Pipe Coupling. A listed coupling or fitting that allows axial
displacement, rotation, and at least 1 degree of angular movement of the pipe
without inducing harm on the pipe. For pipe diameters of 8 in. (203.2 mm) and
larger, the angular movement shall be permitted to be less than 1 degree but
not less than 0.5 degree.
6
5.4. TYPES OF SPRINKLER
Special Sprinkler. A sprinkler that has been tested and listed as prescribed
in 8.4.9.
7
Spray Sprinkler. A type of sprinkler listed for its capability to provide fire
control for a wide range of fire hazards.
Flush Sprinkler. A sprinkler in which all or part of the body, including the
shank thread, is mounted above the lower plane of the ceiling.
Recessed Sprinkler. A sprinkler in which all or part of the body, other than
the shank thread, is mounted within a recessed housing.
8
5.5. CLASSIFICATION OF OCCUPANCIES
Churches
Clubs
Eaves and overhangs, if of combustible construction with no combustibles
beneath
Educational
Hospitals
Institutional
Libraries, except large stack rooms
Museums
Nursing or convalescent homes
Offices, including data processing
Residential
Restaurant seating areas
Theaters and auditoriums, excluding stages and prosceniums
Unused attics
9
Ordinary Hazard (Group 2). Ordinary hazard (Group 2) occupancies shall
be defined as occupancies or portions of other occupancies where the quantity
and combustibility of contents are moderate to high, stockpiles do not exceed
12 ft (3.7 m), and fires with moderate to high rates of heat release are expected.
Cereal mills
Chemical plants — ordinary
Confectionery products
Distilleries
Dry cleaners
Feed mills
Horse stables
Leather goods manufacturing
Libraries — large stack room areas
Machine shops
Metal working
Mercantile
Paper and pulp mills
Paper process plants
Piers and wharves
Post offices
Printing and publishing
Repair garages
Resin application area
Stages
Textile manufacturing
Tire manufacturing
Tobacco products manufacturing
Wood machining
Wood product assembly
10
Tire manufacturing
Tobacco products manufacturing
Wood machining
Wood product assembly
Extra Hazard (Group 2). Extra hazard (Group 2) occupancies shall be
defined
as occupancies or portions of other occupancies with moderate to
substantial amounts of flammable or combustible liquids or occupancies
where shielding of combustibles is extensive.
Asphalt saturating
Flammable liquids spraying
Flow coating
Manufactured home or modular building assemblies (where finished
enclosure
is present and has combustible interiors)
Open oil quenching
Plastics processing
Solvent cleaning
Varnish and paint dipping
11
5.6. SPRINKLERS
12
5.7. DESIGN REQUIREMENTS
NFPA 13 - Standard for the Installation of Sprinkler Systems and NFPA 13R -
Standard for the Installation of Sprinkler Systems.
5. Hydraulic Calculation
Bedrooms Light
Corridors Light
Bathrooms Light
13
Hazard classification hierarchy
• Light Hazard
• Ordinary Hazard
• Extra Hazard
This same section in NFPA 13 also indicates that the ordinary hazard
classification is divided into two sub-classifications an ordinary group 1 hazard
and an ordinary group 2 hazard. Similarly, the extra hazard classification is also
divided into two sub-classifications — an extra group1 hazard and an extra
group 2 hazard.
• Storage height.
14
NFPA 13 defines an ordinary group 2 hazard as follows:
15
5.10.2. DENSITY/AREA CURVES
The water supply for sprinklers only shall be determined either from the
density/area curves of Figure 11.2.3.1.5 in accordance with the method of
11.2.3.2 or be based upon the room design method in accordance with 11.2.3.3,
at the discretion of the designer. NFPA 13 Standards.
For systems with multiple hazard classifications, the hose stream demand
shall be in accordance with one of the following:
(1) Add the hose demand for the highest hazard classification within the system,
or
(2) Add the hose demand for each individual hazard classification to the
calculations for the design area for that hazard, or
(3) For systems with multiple hazard classifications where the higher classification
only lies within single rooms less than or equal to 400 ft2 in area with no such
rooms adjacent, add the hose demand for the principal occupancy for the
remainder of the system.
16
5.10.4. RESTRICTIONS
Regardless of which of the two methods is used, the following restrictions shall
apply:
(1) For areas of sprinkler operation less than 1500 ft2 (139 m2) used for light and
ordinary hazard occupancies, the density for 1500 ft2 (139 m2) shall be used.
(2) For areas of sprinkler operation less than 2500 ft2 (232 m2) for extra hazard
occupancies, the density for 2500 ft2 (232 m2) shall be used.
5.11.1. GENERAL
Pipe sizes shall be no less than 1 in. (25.4 mm) nominal for ferrous piping
and ¾ in. (19 mm) nominal for copper tubing or non-metallic piping listed for fire
sprinkler service.
The size of pipe, number of sprinklers per branch line, and number of
branch lines per cross main shall otherwise be limited only by the available water
supply.
However, sprinkler spacing and all other rules covered in this and other
applicable standards shall be observed.
4.52𝑄1.85
𝑝 = 1.85 4.87
𝐶 𝑑
where:
Q = flow in gpm
17
d = actual internal diameter of pipe in inches
Qm = flow in L/min
0.001123𝑄2
𝑝𝑣 =
𝐷4
where:
Pn = Pt - Pv
where:
Pn = normal pressure
18
5.11.3. HYDRAULIC JUNCTION POINTS
Pressures at hydraulic junction points shall balance within 0.5 psi (0.03 bar).
The highest pressure at the junction point, and the total flows as adjusted,
shall be carried into the calculations.
Table 14.4.3.1.1 (NFPA 13, 2002) shall be used to determine the equivalent
length of pipe for fittings and devices unless manufacturer's test data indicate
that other factors are appropriate.
Specific friction loss values or equivalent pipe lengths for alarm valves, dry
pipe valves, deluge valves, strainers, and other devices shall be made available
to the authority having jurisdiction.
19
5.11.5. C-FACTORS
Where the design is based on the room design method, the calculation
shall be based on the room and communicating space, if any, that is
hydraulically the most demanding.
20
21
5.11.8. MINIMUM OPERATING PRESSURE
22
Schedule for Ordinary Hazard Occupancies
1. Design Area = 1600 square feet is less than 52 000 square feet, therefore,
one sprinkler system is enough.
23
2. Design Area with Sprinkler Lay-out
24
Floor lay-out of Sprinkler removing Lines.
25
3. Initial Pipe Sizing (Using Pipe Schedule)
26
4. Most remote area.
No. of sprinkler = 1600 ft2 / 130 ft2 = 12.3, so use 13 minimum.
27
*Using Elite Fire Version 6.02.23 Software.
28
Node 1-3
Beginning – 1
End – 3
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 1 + 1.16 + 4.58 = 6.74 ft.
K-factor = 5.9
K-factor = 0.0
Sprinkler Elevation = 25 – 1 = 24 ft.
Sprinkler Elevation = 25 ft.
Standard Fitting = 2E
(The rest is zero as default)
Node 2-3
Beginning – 2
End – 3
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 5.5 ft.
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 25 ft.
Sprinkler Elevation = 25 ft.
Standard Fitting = ET
(The rest is zero as default)
Node 3-6
Beginning – 3
End – 6
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 1 + 1.16 + 4.58 = 6.74 ft.
K-factor = 5.9
K-factor = 0.0
Sprinkler Elevation = 25 – 1 = 24 ft.
Sprinkler Elevation = 25 ft.
Standard Fitting = T
(The rest is zero as default)
Node 4-6
Beginning – 4
End – 6
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 1 + 5.9 = 6.9 ft.
29
K-factor = 5.9
K-factor = 0.0
Sprinkler Elevation = 25 – 1 = 24 ft.
Sprinkler Elevation = 25 ft.
Standard Fitting = E
(The rest is zero as default)
Node 5-6
Beginning – 5
End – 6
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 1 + 1.59 = 2.59 ft.
K-factor = 5.9
K-factor = 0.0
Sprinkler Elevation = 25 – 1 = 24 ft.
Sprinkler Elevation = 25 ft.
Standard Fitting = E
(The rest is zero as default)
Node 6-14
Beginning – 6
End – 14
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 3.8 ft.
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 25 ft.
Sprinkler Elevation = 25 ft.
Standard Fitting = T
(The rest is zero as default)
30
Node 7-9
Beginning – 7
End – 9
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 1 + 5.95 + 0.69 = 7.64 ft.
K-factor = 5.9
K-factor = 0.0
Sprinkler Elevation = 25 - 1 = 24 ft.
Sprinkler Elevation = 25 ft.
Standard Fitting = 2E
(The rest is zero as default)
Node 8-9
Beginning – 8
End – 9
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 1 + 1.6 = 2.6 ft.
K-factor = 5.9
K-factor = 0.0
Sprinkler Elevation = 25 – 1 = 24 ft.
Sprinkler Elevation = 25 ft.
Standard Fitting = ET
(The rest is zero as default)
31
Node 9-11
Beginning – 9
End – 11
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 5 ft.
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 25 ft.
Sprinkler Elevation = 25 ft.
Standard Fitting = T
(The rest is zero as default)
Node 10-11
Beginning – 10
End – 11
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 1 + 1.6 = 2.6 ft.
K-factor = 5.9
K-factor = 0.0
Sprinkler Elevation = 25 – 1 = 24 ft.
Sprinkler Elevation = 25 ft.
Standard Fitting = E
(The rest is zero as default)
Node 11-13
Beginning – 11
End – 13
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 5.32 ft.
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 25 ft.
Sprinkler Elevation = 25 ft.
Standard Fitting = T
(The rest is zero as default)
Node 12-13
Beginning – 12
End – 13
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 1 + 1.6 = 2.6 ft.
32
K-factor = 5.9
K-factor = 0.0
Sprinkler Elevation = 25 – 1 = 24 ft.
Sprinkler Elevation = 25 ft.
Standard Fitting = E
(The rest is zero as default)
Node 13-14
Beginning – 13
End – 14
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 1.1 ft.
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 25 ft.
Sprinkler Elevation = 25 ft.
Standard Fitting =
(The rest is zero as default)
33
Node 14-24
Beginning – 14
End – 24
Material – 4
Diameter = 50 mm = 2 in.
Length (Layout) = 13.96 ft.
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 25 ft.
Sprinkler Elevation = 25 – 1 = 24 ft.
Standard Fitting = ET
(The rest is zero as default)
Node 15-17
Beginning – 15
End – 17
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 1 + 0.68 + 7.5 = 9.18 ft.
K-factor = 5.9
K-factor = 0.0
Sprinkler Elevation = 25 – 1 = 24 ft.
Sprinkler Elevation = 25 ft.
Standard Fitting = 2E
(The rest is zero as default)
Node 16-17
Beginning – 16
End – 17
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 1 + 0.68 = 1.68 ft.
K-factor = 5.9
K-factor = 0.0
Sprinkler Elevation = 25 – 1 = 24 ft.
Sprinkler Elevation = 25 ft.
Standard Fitting = ET
(The rest is zero as default)
Node 17-19
Beginning – 17
End – 19
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 3.46 ft.
34
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 25 ft.
Sprinkler Elevation = 25 ft.
Standard Fitting = T
(The rest is zero as default)
Node 18-19
Beginning – 18
End – 19
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 1 + 1.02 = 2.02 ft.
K-factor = 5.9
K-factor = 0.0
Sprinkler Elevation = 25 – 1 = 24 ft.
Sprinkler Elevation = 25 ft.
Standard Fitting = E
(The rest is zero as default)
35
Node 19-23
Beginning – 19
End – 23
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 1.09 ft.
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 25 ft.
Sprinkler Elevation = 25 ft.
Standard Fitting = T
(The rest is zero as default)
Node 20-22
Beginning – 20
End – 22
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 1 + 0.68 + 7.5 = 9.18 ft.
K-factor = 5.9
K-factor = 0.0
Sprinkler Elevation = 25 – 1 = 24 ft.
Sprinkler Elevation = 25 ft.
Standard Fitting = 2ET
(The rest is zero as default)
Node 21-22
Beginning – 21
End – 22
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 1 + 0.68 = 1.68 ft.
K-factor = 5.9
K-factor = 0.0
Sprinkler Elevation = 25 – 1 = 24 ft.
Sprinkler Elevation = 25 ft.
Standard Fitting = E
(The rest is zero as default)
Node 22-23
Beginning – 22
End – 23
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 2.95 ft.
36
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 25 ft.
Sprinkler Elevation = 25 ft.
Standard Fitting =
(The rest is zero as default)
Node 23-24
Beginning – 23
End – 24
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 1 ft.
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 25 ft.
Sprinkler Elevation = 25 – 1 = 24 ft.
Standard Fitting =
(The rest is zero as default)
Node 24-25
Beginning – 24
End – 25
Material – 4
Diameter = 65 mm = 2.5 in
Length (Layout) = 3.66 ft.
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 25 – 1 = 24 ft.
Sprinkler Elevation = 25 – 1 = 24 ft.
Standard Fitting = T
(The rest is zero as default)
37
Node 25-26
Beginning – 25
End – 26
Material – 4
Diameter = 65 mm = 2.5 in
Length (Layout) = 3.47 ft.
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 25 – 1 = 24 ft.
Sprinkler Elevation = 25 – 1 = 24 ft.
Standard Fitting = T
(The rest is zero as default)
Node 26-27
Beginning – 26
End – 27
Material – 4
Diameter = 65 mm = 2.5 in
Length (Layout) = 7.72 ft.
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 25 – 1 = 24 ft.
Sprinkler Elevation = 25 – 1 = 24 ft.
Standard Fitting = T
38
(The rest is zero as default)
Node 27-28
Beginning – 27
End – 28
Material – 4
Diameter = 65 mm = 2.5 in
Length (Layout) = 7.98 ft.
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 25 – 1 = 24 ft.
Sprinkler Elevation = 25 – 1 = 24 ft.
Standard Fitting = T
(The rest is zero as default)
Node 28-29
Beginning – 28
End – 29
Material – 4
Diameter = 80 mm = 3 in
Length (Layout) = 6.67 ft.
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 25 – 1 = 24 ft.
Sprinkler Elevation = 25 – 1 = 24 ft.
Standard Fitting = T
(The rest is zero as default)
Node 29-30
Beginning – 29
End – 30
Material – 4
Diameter = 80 mm = 3 in
Length (Layout) = 8.11 ft.
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 25 – 1 = 24 ft.
Sprinkler Elevation = 25 – 1 = 24 ft.
Standard Fitting = T
(The rest is zero as default)
39
Node 30-31
Beginning – 30
End – 31
Material – 4
Diameter = 80 mm = 3 in
Length (Layout) = 7.75 ft.
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 25 – 1 = 24 ft.
Sprinkler Elevation = 25 – 1 = 24 ft.
Standard Fitting = T
(The rest is zero as default)
Node 31-32
Beginning – 31
End – 32
Material – 4
Diameter = 80 mm = 3 in
Length (Layout) = 31.82 ft.
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 25 – 1 = 24 ft.
Sprinkler Elevation = 0 ft.
Standard Fitting = 2ETG
(The rest is zero as default)
40
6. Hydraulic Calculation Result
https://rcwapp.xyleminc.com/fp_select.asp
Electric Pump
41
Jockey Pump Selection
Then,
Water flow rate = 5.9 Gpm
Head = 242. 3077 ft.
Efficiency = 43.9 %
Bhp = 0.79 hp
Motor hp = 0.79 / 0.439
= 1.7995 hp, use 2 hp.
42
6. SPECIFICATION
6.1 FIRE PUMP
The Contractor shall supply and install fire-fighting pumps as shown and
detailed on the drawings.
The fire sprinkler pump/ duty/standby and the Jockey pump, shall be
completely fully automatic, factory assembled, skid mounted units includes the
following features:
The motor shall be squirrel cage induction type and rated for continuous
operation at ambient temperature not less than 50 Deg. C, totally enclosed fan
cooled with insulation class F and IP 54-protection level and rated for 415 volt, 3
phase and 50 Hz.
The Engine shall be provided with double battery kit (12 VDC) and
charger, complete with exhaust pipe (insulated) and arranged to discharge
outside.
43
1 Starter with Overload protection for each motor.
1 Cyclic Controller
1 Earth leakage sensor with hooter, mute push button and Indication lamp.
The “hand” button shall be spring-loaded and shall override all control
circuits exception the overload, so that the selected pump can be checked for
performance and operation.
The pump sets shall operate under the control of pressure switches
44
The fire pump set shall be constructed to local Fire department’s
requirements and a certificate stating this shall be provided with the pumps and
shall confirm to B.S. and shall be a single stage horizontal split casing centrifugal
type.
A. General:
1. Minimum sprinkler orifice size shall be 1/2 inch.
2. Sprinklers in non-public spaces such as
mechanical/electrical equipment, and storage
rooms and sprinklers on exposed piping shall have
brass finish unless noted otherwise.
3. Sprinklers and escutcheons in finished areas to have
polished brass or white finish or finish as noted on
plans.
4. Style, size, and temperature rating to be type
specifically approved for such use.
5. Thermosensitive glass bulbs to be of all one color for
a given temperature classification.
6. For each sprinkler style, all sprinklers to be of same
type (fusible link or glass bulb).
B. Upright Sprinklers:
1. Thermosensitive glass-bulb or fusible solder/alloy
standard response.
2. Thermosensitive glass-bulb quick response.
3. Fusible solder/alloy quick response.
4. Installation style:
a. Exposed: No escutcheon
C. Pendent Sprinklers:
1. Thermosensitive glass-bulb or fusible solder/alloy
standard response.
2. Thermosensitive glass-bulb quick response.
3. Fusible solder/alloy quick response.
4. Installation style:
a. Exposed: No escutcheon.
45
4. Normal or extended coverage type is acceptable.
5. Installation style:
a. Exposed: No escutcheon.
E. Horizontal Sidewall Sprinklers:
1. Thermosensitive glass-bulb or fusible solder/alloy
standard response.
2. Thermosensitive glass-bulb quick response.
3. Fusible solder/alloy quick response.
4. Normal or extended coverage type is acceptable.
5. Fixed or field adjustable type is acceptable.
6. Installation style:
a. Exposed: No escutcheon.
F. Sprinkler Guards: Metal with red finish.
G. Spare Sprinkler Cabinet: Wall mounted. Storage capacity of
not less than minimum designated by NFPA 13.
H. Sprinkler Wrench: To match style and brand of sprinklers used
Sprinklers shall be installed in accordance with NFPA 13.
These shall be local Fire officer’s approved, pendant glass
bulb sprinklers rated for 79 degree C. for sprinklers mounted
in non-air conditioned areas and 68 degree C. for sprinklers
mounted in air conditioned areas, and suitable for maximum
ambient temperature of 50 degree C. sprinklers shall have k
factor of 80 with 15 mm (1/2”) MSPT male inlets. Recessed
type of sprinklers shall be installed in the false ceilings in order
to make the surroundings decorative. There shall be a 2-
piece design of the recessed enclosure and mounting plate
allows installation of the sprinklers prior to the installation of
the false ceiling. Both sprinklers and escutcheon plates shall
have chrome finish.
Toilet and pantry areas (AHU Plant room) shall be
provided with side wall type sprinklers and shall have
chrome finish.
Samples are to be submitted to the consultant for
approval.
Side sprinkler head to be installed at plant room of
swimming pool.
7. INSTALLATION OF FIRE SPRINKLER SYSTEM
PREPARATION
46
INSTALLATION
47
f) Control Valves:
1. Bolt position on lugged butterfly valves to allow removal of
downstream piping.
g) Sprinklers:
1. Unless noted otherwise, provide sprinkler types as indicated
on drawings.
2. Install sprinklers in fittings after piping is in place.
3. Install exposed sprinklers with frame parallel to branch line.
4. Install sprinkler guards where sprinklers are within 2.2 meters
of floor, or when subject to injury.
5. Line sprinklers up with themselves.
6. Prior to Date of Substantial Completion, deliver spare heads
and wrench and place in spare head cabinet(s).
48
9. MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEM
Introduction
Application
System types
The two types most commonly found in healthcare occupancies are wet
pipe and dry pipe sprinkler systems. Some buildings contain both types of systems
– a wet pipe system in heated areas and a dry-pipe system in unheated areas.
Simply put, a wet pipe sprinkler system is a piping system containing water so
arranged that water discharges immediately from sprinklers activated by heat
from a fire. A dry pipe sprinkler system is a piping system containing air or
nitrogen under pressure so arranged that upon activation of a sprinkler, the
49
water pressure opens a valve allowing water to flow into the pipe and out the
opened sprinkler.
Definitions
Personnel Qualifications
System History
As with just about anything, the hardest part of creating an historical log is
getting started – after that, it’s a matter of keeping it up-to-date. Basic questions
that need to be answered include:
50
Were any additions, modifications or repairs made to the system? When?
Who did the work?
It’s important to note that certain changes made to your building could
necessitate modifications to your fire protection system. Things to watch for
include: construction or removal of walls and installation of such things as drop-in
ceilings, new suspended light fixtures, tracks for lift systems and new cubicle
curtains.
Applicable Standards
Specific Requirements
New installations
All newly installed fire sprinkler systems are required to meet specific
acceptance requirements, such as flushing of fire service mains and testing of
both underground and aboveground piping [see NFPA13(99]. These services
must be provided by licensed contractors.
Monthly
51
Properly sealed
Locked and/or supervised
Free from leaks
Provided with appropriate signage identifying the portion of the
system they control
2. Visually inspect gauges on wet pipe systems to verify that they are in good
condition and that normal water pressure is being maintained.
3. Visually inspect gauges on dry pipe systems to verify that they are in good
condition and that normal air and water pressure are being maintained.
Quarterly
52
b. Test the water flow alarm on dry pipe sprinkler systems by using the
bypass connection.
Annually
Long term
1. A full flow trip test is required for dry pipe sprinkler systems every 3 years
[see NFPA 25(98), Sec. 9-4.4.2.2.1 or NFPA 25(02), Sec. 12.4.4.2.2.2].
2. Sprinkler system gauges typically have a life expectancy of 10 to 15 years.
As a result, these gauges must be replaced every 5 years or tested every 5
years by comparison to a calibrated gauge. Gauges not accurate to
within 3 percent of the full scale must be recalibrated or replaced [see
NFPA 25(98), Sec. 2-3.2 or NFPA 25(02), Sec. 5.3.2].
3. System check valves must be inspected internally every 5 years to verify
that all components operate properly, move freely and are in good
condition [see NFPA 25(98), Sec. 9-4.2.1 or NFPA 25(02), Sec. 12.4.2.1].
4. The 1998 edition of NFPA 25 has specific requirements dealing with testing
of sprinkler heads that have been in service for an extended period of
time [see NFPA 25(98), Sec. 2-3.1]. These requirements, which emphasize
the importance of knowing the history of your facility’s fire sprinkler system,
would include:
53
a. Sprinklers manufactured prior to 1920 must be replaced.
b. Representative samples of solder-type, extra-high temperature
sprinklers (i.e. 325°- 375° F) that are exposed to semi-continuous or
continuous maximum allowable ambient temperature conditions
are required to be tested at 5 year intervals. These would be
sprinklers you might find, for example, in your boiler room and
would have red-colored frame arms.
c. Sprinklers manufactured using fast response elements that have
been in service for 20 years are required to be tested. Retesting is
required at 10-year intervals.
Note: The first residential sprinkler was listed for service in 1981 and
the first quick response sprinkler was listed for service in 1983.
Fire pumps
1. Fire pumps, where present, are also subject to very specific inspection,
testing and maintenance requirements to help ensure that they will
function properly when needed. Some of the basics include:
a. Fire pumps must be inspected weekly to verify that the pump
assembly appears to be in operating condition and is free from
physical damage [see NFPA 25(98), Sec. 5-2 or NFPA 25(02), Sec.
8.2 for specific conditions that must be checked].
54
b. Fire pump assemblies must be tested weekly [see NFPA 25(98), Sec.
5-3.2 or NFPA 25(02), Sec. 8.3 for specific observations and
adjustments that need to be made while the pump is running].
c. An annual test of the fire pump assembly is required. This test must
be conducted under minimum, rated and peak flows of the pump
[see NFPA 25(98), Sec. 5-3.3 or NFPA 25(02), Sec. 8.3.3 for specific
visual observations, measurements and adjustments that need to
be made while the pump is running and flowing water under the
specified output condition].
2. NFPA 25 requires that a preventive maintenance program be established
on all components of the pump assembly in accordance with
manufacturer’s recommendations [see NFPA 25(98), Sec. 5-5 or NFPA
25(02), Sec. 8.5].
Documentation Requirements
Just as important as conducting required inspections, testing and
maintenance is documenting the fact that they occurred. Both NFPA 13 and
NFPA 25 require that these services be properly recorded. What follows is a brief
synopsis of some of the major documentation requirements you need to be
aware of.
55
a. All literature and instructions provided by the manufacturer
describing proper operation and maintenance of all equipment
and devices installed, and
b. A copy of NFPA 25 (Be aware that you very likely will not receive a
copy of the 1998 edition of NFPA 25, but rather the latest edition of
the standard adopted by NFPA).
3. The installing contractor is required to identify hydraulically designed
systems with a permanently marked weather-proof sign properly secured
near the valve controlling the corresponding hydraulically designed area
[see NFPA 13(99), Sec. 10-5]. This sign must include the following
information:
a. Location of the design area(s)
b. Discharge densities over the design area(s)
c. Required flow and residual pressure demand at the base of the
riser
d. Occupancy classification or commodity classification and
maximum permitted storage height and configuration
e. Hose stream demand included in addition to the sprinkler demand
Sample reports are also available for dry pipe sprinkler systems and fire
pumps as follows (again, these reports should be available through your local fire
sprinkler contractor):
56
Date dry pipe valve last tripped
Name of person and organization conducting the test
2. Separate records of initial air and water pressure, tripping air pressure
and dry pipe valve operating condition must be maintained on the
premises for comparison with previous test results.
It’s important that at least two people in your facility know where
your records are kept to increase the likelihood that they can be
readily provided if requested during an inspection.
It is required that these records be maintained on the premises for
at least three years and must be copied for the fire code official on
request.
57
11.2. CONCLUSION
In the design of fire sprinkler system, only the most remote area is
considered. Getting the required water demand and pressure develop. Sizing
fire pump is from the sum of sprinkler water demand and hose demand. Fire
pump package includes on-duty fire pump which is electric driven, standby fire
pump which is diesel engine driven and a jockey pump to maintain the system
pressure which is also electric driven. This for hotel which is a multilevel residential
building, the main parts of the design that need further consideration the
calculation of the required pressure at the most remote sprinkler.
11.3. RECOMMENDATION
Standard procedure based on NFPA 13, 13R and other related standard
shall be consulted first before proceeding to the design.
58
12. REFERENCES
Cheung, K.P. Fire Services Installations in Hong Kong
www.arch.hku.hk/~kpcheung/fire/fire23.html
Gummerhaul, M.L. and Pennel G.T. Hotel and Motel Fire Sprinkler
Systems Article in www.pmengineer.com, Nov. 1, 2008.
NFPA 13 – Standard for the Installation of Fire Sprinkler Systems, 2002 Ed.
Pipe Fittings and Flanges. Pipe Fittings by Type. Retrieved Jan. 10, 2016
from http://www.thepipefittings.com/pipe-fittings-types.html
Sanguri, Mohit. (July 12, 2012). Marine Insight. Pipe and Bends – An
Essential Guide for Second Engineers: Part 2. Retrieved Jan. 10, 2016
from http://www.marineinsight.com/tech/pipeing/pipes-and-bends-
an-essential-guide-for-second-engineers-part-2/
59
APPENDICES
APPENDIX A – FIRE PUMPS MODEL BROCHURE
Pump Designs
Flowserve offers a wide range of
complementary pump types, built to
recognized global standards and
costumer specification. These
include:
Single-stage process
Between bearing single- stage
Between bearing multistage
Vertical
Submersible motor
Positive displacement
Nuclear
Specially
Available Configurations
Sealed and seal less
Axially and radially split
Volute and diffuser
Close coupled and spacer
coupled
Single and double case
APPENDIX B – SPRINKLER MODEL BROCHURE
APPENDIX D – DESIGN CALCULATION
APPENDIX C - SPRINKLER SYSTEM PIPING LAYOUT
Stairway Stairway
Electrical Electrical
Room
Bedroom Bedroom Bedroom Bedroom Bedroom Bedroom
Room
Vestibule
Bedroom Vestibule Bedroom Bedroom Bedroom Bedroom Bedroom Bedroom Bedroom
Stairway
Stairway
Bedroom Bedroom
Bedroom
Bedroom Bath Unit Unit Unit Bath
Bath Bath Bedroom
Bedroom
Elevator Elevator
Elevator Elevator
Unit Unit Unit Bath Bath Bath
Bath Bath Bath Bath Bath
Bath Bath
Bedroom Bedroom
Bedroom
Corridor Unit Corridor Unit
Bedroom
Unit
Bedroom
Bath
Unit Bedroom Bath Bath Bath Bath
Bath Bath Bath Bedroom Bedroom
Bedroom Bedroom
Bedroom Bedroom Bedroom Bedroom Bedroom Bedroom Bedroom Bedroom Bedroom Bedroom Bedroom Bedroom Bedroom Bedroom Bedroom Bedroom Bedroom Bedroom
Unit Unit
Unit Unit
Stairway
25 mm
Stairway
25 mm
25 mm
Electrical
Bedroom Bedroom Bedroom Bedroom Bedroom Bedroom
25 mm
Electrical Room
Bedroom Bedroom Bedroom Bedroom Bedroom Bedroom
25 mm
Room 25 mm
25 mm
25 mm 25 mm 25 mm 25 mm
Vestibule 25 mm
25 mm
25 mm
25 mm
25 mm 25 mm 25 mm 25 mm 25 mm 25 mm
25 mm
Vestibule 25 mm
25 mm
25 mm
25 mm 25 mm 25 mm 25 mm Stairway
25 mm
25 mm 25 mm 25 mm
25 mm
Bedroom 25 mm Bedroom
25 mm
25 mm Stairway
25 mm
25 mm 25 mm 25 mm
Bedroom 25 mm Bedroom
25 mm
25 mm
Unit Utility Unit
32 mm
Unit Unit
25 mm
Utility Room
32 mm
25 mm
Room
25 mm 25 mm
25 mm
Unit Unit Unit
25 mm
25 mm
Bath
Unit Unit Unit Bath
25 mm
25 mm
32 mm
Bath Bedroom
25 mm
Bath
25 mm
Bedroom
32 mm
Bedroom
25 mm
32 mm
25 mm
25 mm
40 mm
25 mm Bath Bath Bath Bath
32 mm
25 mm 25 mm 25 mm Bath
32 mm
25 mm
32 mm 25 mm
25 mm
40 mm
Bath
32 mm
Bath
32 mm
32 mm 25 mm
25 mm
40 mm
25 mm
32 mm
32 mm
25 mm
40 mm
25 mm
32 mm
32 mm
32 mm
32 mm
40 mm
80 mm 80 mm 80 mm 80 mm 65 mm 50 mm
32 mm
32 mm
32 mm
32 mm
65 mm 65 mm 65 mm
40 mm
80 mm Bedroom
Corridor
80 mm 50 mm
80 mm 80 mm 65 mm Bedroom
Unit Unit
32 mm
65 mm 65 mm 65 mm
Corridor
40 mm
25 mm
Bedroom 25 mm
Bedroom
Unit Unit
25 mm
25 mm
40 mm
25 mm 25 mm 25 mm 25 mm
25 mm
25 mm 25 mm 25 mm 25 mm
40 mm
25 mm
32 mm
40 mm
32 mm
25 mm
25 mm
25 mm 25 mm 25 mm
25 mm 25 mm 25 mm 25 mm 25 mm Bath 25 mm 25 mm 25 mm 25 mm
25 mm Bath Bath Bath
25 mm
25 mm Bath 25 mm 25 mm 25 mm 25 mm
25 mm
Bath Bath Bath 25 mm Bedroom
25 mm
Bedroom
25 mm
25 mm Bedroom
25 mm
Bedroom
25 mm
Unit
25 mm
25 mm
Unit Unit Unit Unit
25 mm
25 mm
Bath
Unit Unit Unit Bath 25 mm
Bath Bath
25 mm
25 mm 25 mm
25 mm
25 mm
25 mm
25 mm
Bedroom
25 mm
25 mm
25 mm
25 mm
Bedroom
25 mm
Bedroom
25 mm
25 mm
25 mm
Bedroom
25 mm
25 mm
25 mm 25 mm
25 mm 25 mm Bedroom 25 mm 25 mm 25 mm 25 mm 25 mm 25 mm Bedroom
Bedroom 25 mm
25 mm 25 mm 25 mm 25 mm 25 mm 25 mm Bedroom 25 mm
25 mm
Bedroom Bedroom Bedroom Bedroom Bedroom Bedroom
Unit Bedroom Bedroom Bedroom Bedroom Bedroom Bedroom Bedroom Bedroom 25 mm
25 mm Unit Bedroom Bedroom 25 mm
25 mm
Unit
25 mm
Unit
Remote Area
GROUND FLOOR
A/4
ESCUTCHEON FOR COMBUSTIBLE MATERIALS CONDUIT
TO PIPE
FINISHED SURFACE
WIRE LEADS MOUNTING PLATE PIPE 2-15 X 50L BOLT W/
PIPE DOUBLE NUTS AND
A
A/2
FLAT WASHER LOCK WASHER
ROLL VANE OPPOSITE DIRECTION OF
FLOW ARROW ROD DIA. NUT W/ LOCK WASHER
SLEEVE OF FLOW ARROW TO
A/4
A/4
INSERT IN PIPE
NUT W/ LOCK WASHER
MOUNTING HOLE
A/2
2-15 X 50L BOLT W/
A
HOOK BOLT DOUBLE NUTS AND ROD DIA.
LOCK WASHER
CONCRETE SLAB PLASTIC WATERPROOF B/2
A/4
HOOK BOLT
OAKUM MASTIC PACKING 6.5MM THK. X 50MM PIPE
HEAT RESISTANT SHAP ON TYPE LOCK NUT X 50MM B
NOTES: CAULKING COMPOUND ESCUTCHEON PLATE INNER LOCKNUT
(FOR FINISHED SURFACE) MOUNTING BRACKET
SLEEVE SHALL BE PROVIDED AROUND ALL PIPING EXTENDING CONCRETE SPOUT HOOK FACES U-BOLT STEEL COLUMN
THRU WALLS & FOUNDATION. OUTWARD
HOOK FACES IDENTATION OW
CONCRETE WALL INWARD FL
A. MINIMUM CLEARANCE BETWEEN PIPES AND SLEEVES R
TE
SHALL NOT BE LESS THAN 25mm. FOR PIPES 25mm NOTE: WA
THROUGH 90mm.&50mm. FOR PIPES 100mm. LARGER. FOR SMALL VALVE FOR LARGE VALVE
PIPE SLEEVE SHALL HAVE A MINIMUM FIRE RATING SIMILAR
18 WATER FLOW SWITCH MOUNTING ARRANGEMENT
B. THE CLEARANCE BETWEEN THE PIPE SLEEVE SHALL BE TO PENETRATED WALL. FP-10 22 WALL PIPE HANGER DETAIL
FILLED W/ NON-COMBUSTIBLE FLEXIBLE MATERIALS SUCH
AS MINERAL WOOL FIBERGLASS OR EQUIVALENT PIPE SHALL
11 MONITOR SWITCH MOUNTING ARRANGEMENT FP-10
NOT DECLARE FIRE RATING OF WALLS AND FLOORS. 6 PIPE SLEEVE THRU WALLS & BEAMS FP-10
FLUSH ANCHOR OR
C-CLAMP FOR STEEL
PRESSURE SWITCH
25 175
25 175
FLUSH ANCHOR OR TRUSS
BOTTOM OF SLAB
C-CLAMP FOR STEEL OS & Y GATE VALVE
A B ROUND BAR VICTAULLIC 50 50 25 25
GA 18 G.I. SHT. BODY
TRUSS HANGER COUPLING
EPOXY PRIMED WITH AUTOMATIC RETARDING
WHITE BAKED INTERIOR CHAMBER
BOTTOM OF SLAB MACHINE BOLT SEMI-AUTO HOSE FINISHED & FIRE RED
WATER FLOW SWITCH HEXAGONAL NUTS SUPPLY PIPE RACK EPOXY PRIMED A
ROUND BAR W/ WASHERS W/ NUT FIRE RED BAKED (INCLUDING FRAME) BAKED ENAMEL
GATE VALVE
INDICATING TYPE FLOOR WIRING TO SPRINKLER ENAMEL FINISH EXTERIOR FINISHED
ALARM CONTROL PANEL C C
CONTROL VALVE W/ HEX . NUTS W/ (SIZE OF CABINET) (SIZE OF CABINET
WASHERS FLAT BAR COMBINED ANGLE TYPE
25 25 25 25 INCLUDING FRAME)
SUPERVISORY SWITCH 50 50 25 50 50 25
FLAT BARS LOWER PIPE RESTRICTING VALVE
5025 25
CAST BRASS FINISH
50 25
AUTOMATIC SPRINKLER NOTE:
PIPE RISER FOG NOZZLE CAST 25 X 50MM ANODIZED 25 X 50MM ANODIZED
NOTE: PIPE CROSSMAIN AND BRANCHLINE PIPE BRASS FINISH ALUMINUM FRAME FOR ALUMINUM FRAME FOR
(INCLUDING FRAME)
SHOULD BE MAXIMIZE TO THE CEILING LEVEL. RECESSED MOUNTED SURFACED MOUNTED
INCLUDING FRAME)
(SIZE OF CABINET)
(SIZE OF CABINET
30 CABINET CABINET
CROSSMAIN AND BRANCHLINE PIPE PIPE SIZE STEEL PLATE BAR ROD. DIA. MACHINE BOLT W/ NUT
FOUR WAY SWAY BRACE 25MM TEST FIRE HOSE B.I. PIPE 50MM (2") MAIN DRAIN
SHOULD BE MAXIMIZE TO THE CEILING LEVEL.
D
B
mm. in. mm. in. (DIA. x L) mm. DOUBLE JACKET
LOWER(thk. x W) LOWER(thk. x W)
GLOBE VALVE
PIPE SIZE STEEL PLATE BAR ROD. DIA. 50 2 3.2 x 25 MM 4.8 x 25 MM 9.5 3/8
32MM 65 2 1/2 3.2 x 25 MM 4.8 x 25 MM 9.5 3/8
mm. in. (thick x width) mm. in. 2MM THICK
50MM MAIN DRAIN SECTIONAL VALVE 80 3 3.2 x 25 MM 4.8 x 25 MM 9.5 3/8 CLEAR GLASS
25 1 3.2 x 19 MM 9.5 3/8 10 lbs. ABC DRY
25MM 100 4 3.2 x 25 MM 4.8 x 25 MM 9.5 3/8
25 50
32 2.25 9.5 3/8 CHEMICAL FIRE
25 25 50
3.2 x 19 MM
150 4.8 x 32 MM 6.4 x 32 MM 12.0 1/2 EXTINGUISHER
SIGHT GLASS 40 1.50 3.2 x 19 MM 9.5 3/8 6
FLEXIBLE COUPLING
32MM UNION B.S UNION W/ CORRISION 50 2 3.2 x 19 MM 9.5 3/8
(WHERE REQUIRED) RESISTANT ORIFICE W/ HOSE VALVE RECESSED MOUNTED SURFACED MOUNTED
FLOW EQUAL TO ONE 12 ADJUSTABLE TYPE CLEVIS HANGER INCLUDING
FRAME
SIZE OF
CABINET
SIZE OF CABINET
INCLUDING FRAME
32MM PIPE SPRINKLER HEAD
7 ADJUSTABLE TYPE FLAT IRON HANGER FP-10 RECESSED MOUNTED A B C D SURFACE MOUNTED C D TRUST BLOCK
60 METERS FIRE HOSE 950mm1050mm 900mm1000mm 60 METERS FIRE HOSE 900mm 1000mm
A - DISTANCE OF AT LEAST 24"(600MM) FROM GATE VALVE FP-10
30 METERS FIRE HOSE 850mm 950mm 800mm 900mm 30 METERS FIRE HOSE 800mm 900mm
B - DISTANCE OF AT LEAST 10"(250MM) FROM FITTINGS
23 METERS FIRE HOSE 750mm 850mm 700mm 800mm 23 METERS FIRE HOSE 700mm 800mm
W/C CHANGES FLOW DIRECTION
23 ALARM CHECK VALVE ASSEMBLY
FP-10
2 FLOOR CONTROL VALVE & AUXILLIARY DRAIN 19 FIRE HOSE CABINET AND ACCESSORIES DETAIL
FP-10 BRANCH LINE FP-10
ELBOW FITTING UPRIGHT
SPRINKLER
A
HEAD
FDC W/ PLUG & CHAIN
RISER NIPPLE W/ CHECK SNOOTS &
THREAD-O-LET (SEE PLAN FOR SIZES)
22 MM IN BOLT FITTINGS A - DEFLECTORS OF SPRINKLER SHALL PIPE HANGER
EXPANSION SHIELD BE LOCATED 25 mm TO 305mm
(1" TO 12" BELOW COMBUSTIBLE CEILING FIRE DEPARTMENT CONNECTION
VIBRON NEOPENE
FLUSHING CONN. 25mm X 13mm 50 DURA FREE HT.2"
COUPLING REDUCER REINFORCED CONCRETE
CONCRETE WALL OR BEAM 25mm DROP NIPPLE AIR SPACE FLOATING
900 mm
15MM U-BOLT PIPE CLAMP
65 x 65 x 7MM
8 FLUSHING CONNECTION DETAIL CEILING
STEEL ANGLE FP-10
13 COMBINATION SPRINKLER HEADS DETAIL 5/8 " PLYWOOD WITH
FIBERGLASS INSULATION
FLOOR SLAB
150MM OR 200MM
SPRINKLER PIPE FP-10
100MM FINISHED FLOOR LINE
NOTE:
16 FIRE PUMP PAD DETAIL
CROSSMAIN AND BRANCHLINE PIPE FP-10 SMOOTH BORE CORROSION
SHOULD BE MAXIMIZE TO THE CEILING LEVEL. RESISTANT OUTLET GIVING
20 FIRE DEPARTMENT CONNECTION FLOW EQUIVALENT TO ONE
SPRINKLER
3 PIPE RISER BRACKET DETAIL THIS VALVE CONTROL
AUTOMATIC SPRINKLERS
FP-8 FLOOR LINE FD
GROUND LINE
FP-10 SPRINKLER
FIRE-ALARM
MUST AT ALL
WHEN BELL RINGS BE OPEN TIMES
CALL
TO BE HANDLED ONLY BY AUTHORIZED PERSON
FIRE DEPT.-POLICE OR BY EMPLOYEE CARING FOR SPRINKLER SYSTEM
10" LONG NIPPLE "C" 10" LONG NIPPLE 'D' BOLT HOLE
FILLET WELD ALL AROUND
REGULAR REGULAR RECESSED
UPRIGHT PENDENT
TYPE SPRINKLER HEAD TYPE SPRINKLER HEAD ON THIS FLOOR IN THIS BUILDING IN THIS SECTION
MULTIPURPOSE DRY CHEMICAL
13MM NPT CHROME FINISH EXTINGUISHER (ABC) 15 lbs. or 24 INSPECTOR TEST CONNECTION DETAIL
13MM NPT CHROME FINISH FILLET WELD ALL AROUND
CO 2 EXTINGUISHER 10 lbs.
INSPECTION TEST AUXILIARY DRAIN ALARM LINE COUPLING FP-10
'A' 'B'
ORDINARY
SIDEWALL
EXTENDED COVERAGE
SIDEWALL 9 FIRE EXTINGUISHER FIRE HOSE FOR USE BY OCCUPANTS DRY STANDPIPE FOR FIRE DEPT.
TYPE SPRINKLER HEAD TYPE SPRINKLER HEAD FOR BUILDING USE ONLY
FP-10
FP-8 C
L C
L
13MM NPT CHROME FINISH
L 40 X 5MM HOUSING
BODY COVER
EII PIPE
'D'
PIPE 150 mm
10MM SUPPORT
PIPE
SUPPLY PIPE ELEVATION
ELL
BOLTS & NUTS GASKET
STD. PIPE
GONG BOLT LATERAL CLAMP LONGITUDINAL
(EVERY TWO LENGTH OF PIPE) INSTALLATION OF
5 WATER MOTOR ALARM GONG DETAIL 10 TWO-WAY SWAY BRACE 15 ROOF MANIFOLD 17 SEISMIC FLEXIBLE JOINT DETAIL 21 FLANGE CONNECTION DETAIL 25 FLEXIBLE COUPLING
FP-10 FP-10 FP-8 FP-10
FP-8 FP-10 FP-10