ATyS t
r uc Automatic Transfer Switching Equipment
Inst ual
Man
EN
www.socomec.com
www.socomec.com
To download, brochures, catalogues and technical manuals:
This manual is available for download in French, English, German, Italian, Spanish, Dutch, Portugese, Russian, Polish, Turkish and Chinese.
2. INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4. QUICK START. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.1. Quick Start ATyS t Frame B3 to B5 (125A to 630A). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.1. Quick Start ATyS t Frame B3 to B5 (125A to 630A) continued . . . . . . . . . . . . . . . . . . . . . . . . 12
4.2. Quick Start ATyS t Frame B6 to B8 (800A to 3200A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.2. Quick Start ATyS t Frame B6 to B8 (800A to 3200A) continued . . . . . . . . . . . . . . . . . . . . . . . 16
5. GENERAL OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5.1. Product introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5.2. Product identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.3. ATS control module interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
5.4. Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.4.1. IP Rating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.4.2. Operating Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.4.3. Storage Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.4.4. Volume and shipping weights by reference ATyS t. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.4.5. CE marking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.4.6. Lead free process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.4.7. WEEE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.4.8. EMC standard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.5. ATyS t ACCESSORIES AVAILABLE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
6. INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6.1. Product dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6.1.1. Dimensions: Frame B3 to B5 (125A to 630A). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6.1.2. Dimensions: Frame B6 & B7 (800A to 1600A). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
6.1.3. Dimensions: Frame B8 (2000A to 3200A). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
6.2. Mounting orientation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
6.3. Assembly of customer mounted accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
6.3.1. Bridging bar installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
6.3.2. Terminal shrouds. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
6.3.3. Terminal screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
6.3.4. Copper bar connection kits (2000A to 3200A : Frame B8). . . . . . . . . . . . . . . . . . . . . . . . 30
6.3.5. Incoming copper bar connection kit assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
6.3.6. Outgoing bridge connection assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
7. CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
7.1. Power circuits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
7.1.1. Cable or bar connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
7.1.2. Power connection terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
7.1.3. Power connection cross-section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
7.1.4. Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
7.2. Networks and Power Connection possibilities. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
7.2.1. Type of networks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
7.2.2. Metering and sensing details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
7.3. Control circuits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.3.1. Typical ATyS t wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.3.2. ATyS t input and output contacts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
7.4. Voltage sensing and power supply kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
7.4.1. Standard configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
7.4.2. Sensing kit wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
7.4.3. Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
9. CHARACTERISTICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
12. ACCESSORIES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
12.1. Terminal shrouds. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58
• As a minimum the ATyS t comply with the following international standards:
- IEC 60947-6-1 - IEC 60947-3
- GB 14048-11 - IS 13947-3
- EN 60947-6-1 - EN 60947-3
- VDE 0660-107 - NBN EN 60947-3
- BS EN 60947-6-1 - BS EN 60947-3
- NBN EN 60947-6-1
he information provided in this instruction manual is subject to change without notice, remains for general
T
information only and is non-contractual.
The ATyS t is a full load break (switch type) derived transfer switching equipment where the main components are
proven technology devices also fulfilling requirements in IEC 60947-3 standards.
As a Class PC ATSE, the ATyS t is capable of “making and withstanding short circuit currents” assigned to IEC 60947-
3 utilization categories of up to AC23A, GB 14048-11, IEC 60947-6-1 and equivalent standards with utilization
categories of up to AC33B.
D10
ATyS t
LOAD
SOCOMEC has been manufacturing power control and safety products since 1922. The first generation SOCOMEC
“motorised changeover switches” were introduced in 1990 and today the ATyS brand has become trusted by major
players in the power industry worldwide.
The ATyS Family includes a complete range of remotely operated transfer switch equipment (RTSE) as well as
automatic fully integrated products and solutions (ATSE). Selecting the right ATyS will depend on the application as
well as the nature of installation in which the ATyS will be installed.
This instruction manual includes details and instructions specific to the “ATyS t” ATSE only. For all other ATyS family
of products please refer to the specific instruction manual related to that product.
(Available for download on www.socomec.com)
40A - 160A
Back to Back
Configuration
new ATyS p
Power / Genset
Management
ATyS p M
Evolved Genset
Management
ATyS g ATyS g M
Simple Genset
40A - 125A
Simple Genset
Management Management
ATyS t M
ATyS t Transformer (building)
Transformer Management
Management
ATyS d S ATyS d M
Small Genset ATyS d RTSE (DPS)
with DPS RTSE (DPS)
Side by Side
ATyS S (RTSE) ATyS r ATyS
(1)
Configuration
Small Genset RTSE RTSE
(1)
The UL version of ATyS r is available from 100 - 400A
UL 1008 ATyS
ATyS t
STEP 1 STEP 2 STEP 3 STEP 4 STEP 5 STEP 6
Cabinet / Back Power Terminal COMMAND / Power SUPPLY and CHECK PROGRAMMING STEP 7B the pro
Plate Installation Connections CONTROL terminal ATS Controller AUT Mode installe
connections Terminal (Remote Control) flat rig
Connections surfac
Motorised Source Changeover Switch
Automatic Transfer Switching Equipment STEP 7C
Manual Mode
Door c
Preliminary operations
20
Check the following upon delivery and after removal of the
packaging: STEP 7D
• Packaging and contents are in good condition. Padlocking Mode
• The product reference corresponds to the order.
• Contents should include:
Qty 1 x ATyS t
Qty 1 x Emergency handle and fixing clip STEP 4
Quick Start instruction sheet
Warning
Risk of electrocution, burns or injury to persons and /
or damage to equipment.
This Quick Start is intended for personnel trained in the
installation and commissioning of this product. For further
details refer to the product instruction manual available on
the SOCOMEC website.
• This product must always be installed and
commissioned by qualified and approved personnel.
• Maintenance and servicing operations should be
performed by trained and authorised personnel. Clip for
• Do not handle any control or power cables connected to storage of
the product when voltage may be, or may become the
present on the product, directly through the mains or emergency
indirectly through external circuits. handle
• Always use an appropriate voltage detection device to
confirm the absence of voltage.
• Ensure that no metal objects are allowed to fall in the
cabinet (risk of electrical arcing).
Failure to observe good enginering practises as well as to
follow these safety instructions may expose the user and
others to serious injury or death.
Accessories
• Bridging bars and connection kits. STEP 4 Power Supply, Sensing and Control wiring (ATS Controller)
Recommanded to use SOCOMEC
Voltage Sensing Kit Example
• Control voltage transformer (400Vac -> 230Vac). (refer to ATyS t
Connect the product with a cable of section of 1,5 to 2,5 mm2. accessories
• DC power supply (12/24Vdc -> 230Vac). Screw M3 - Tightening torque: min.: 0.5 Nm - max.: 0.6 Nm for details)
• Mounting spacers to raise the product x 10mm.
• Phase barriers. 2
• Terminal shrouds.
• Terminal screens. ATS Power Supply ATS Power Supply
• Auxiliary contacts (Additional). Input II Input I
• Padlocking in 3 positions (I - O - II). Power supply II - L/N Power supply I - L/N
• Lockout accessories (RONIS - EL 11 AP). Power supply II - N/L Power supply I - N/L
• Door escutcheon frame. 208-277 VAC ±20%: 208-277 VAC ±20%:
• ATyS D10 Interface (remote display). 50/60 Hz 50/60 Hz
• Voltage sensing kit.
• Sealable cover.
• RJ45 cable for ATyS D10 => ATyS t
ATS Voltage Sensing ATS Voltage Sensing
For further details refer to the product instruction manual Input Input
under chapter "Spares and Accessories" Source supply II Source supply I
S II - Phase / neutral S I - Phase / neutral
S II - Phase S I - Phase
S II - Phase S I - Phase
575 VAC (ph-ph) max 575 VAC (ph-ph) max
S II - Phase / neutral S I - Phase / neutral
332 VAC (ph-n) max 332 VAC (ph-n) max
www.socomec.com
To download, brochures, catalogues
417 416 415 414 413
Printing informations: 1 color Black. White paper 90g/m . 2 Dual auxiliary supply:
Uc 208-277V~ +/-20% 50/60Hz
Dual auxiliary supply: Dual auxiliary supply:
Uc 208-277V~ +/-20% 50/60Hz Uc 208-277V~ +/-20% 50/60Hz
Printing size: 420x297. Final size 210x297. This page visible first. ATS Module
64B 63B
64B 63B
72 71
A separate sheet for each language. See instruction sheet See instruction sheet
CORPORATE HQ CONTACT: (Product available)
SOCOMEC SAS, 1-4 RUE DE WESTHOUSE, 67235 BENFELD, FRANCE
74
74
To D10
To D10
Remote interface
RJ45 - to ATyS D10
M J1
=
Fix. 195
Fix. 180
=
=
Fix. 195
Fix. 180
STEP 1 Installation
Dimensions in mm.
M J1
=
ol) T U C 21
Caution: Recommended Ok Ok
Ensure that orientation
the product is T U C 21
installed on a
=
Fix. 195
Fix. 180
l) flat rigid
surface.
=
Door cut-out for front panel.
138 W T U C 21
20
W
Fix. 180
e
Fix. 180
165
Ø7
Fix. 195
3P 4P 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P
CA
CA
U U J1 34 34 34 34 34 34 35 35 35 35 35 35 34 34 34 34
Ø9 Ø9 M 120 150 120 150 120 150 160 210 160 210 160 210 210 270 210 270
T 36 36 36 36 36 36 50 50 50 50 50 50 65 65 65 65
50.5
C 244 244 244 244 244 244 244 244 244 244 244 244 320 320 320 320
U 20 20 W 20 20 20 20 25 25 35 35 35 35 32 32 45 45
Fix. 195
Fix. 180
W 9 9 9 9 9 9 11 11 11 11 11 11 13 13 13 13
W Ø7
CA 10 10 10 10 10 10 15 15 15 15 15 15 20 20 20 20
W
CA
U
CA
Ø9
CA
U
STEP 2 Power Terminal Connections
To be connected using terminal lugs, rigid or flexable busbars.
Maximum cable section Cu (mm2) 50 95 120 150 240 240 2x185 2x300
Maximum Cu busbar width (mm) 25 25 25 32 32 32 50 50
Type of screw M8 M8 M8 M10 M10 M10 M12 M12
Recommended tightening torque (N.m) 8.3 8.3 8.3 20 20 20 40 40
Maximum tightening torque (N.m) 13 13 13 26 26 26 45 45
SOCOMEC
Sensing Kit Example: Control wiring for a 400VAC application having a 3 phase and neutral supply. STEP 3 CONTROL / COMMAND Terminals
er to ATyS t Ensure that the product is in Manual Mode.
ccessories
for details)
2 1
1
F2 F1
201 202
102 101
17 17
II/1-2 II/3-4 II/5-6 II/7-8
16 16
2
15
64B 63B 417 416 415 414 413
14
13
12
11
64B 63B
64B 63B
72 71
72 71
See instruction sheet See instruction sheet See instruction sheet 7. Position II aux contact 17. Power Supply Inputs
8. Position I aux contact
74
74
74
To D10
To D20
To D20
3
ATyS
ATyS
t t
Dip Switch Setting Options 5 5 5 5 Auto Configuration of Mains Voltage and Frequency
1 1 1 1
10 10 10 10 2
0 0 0 0
SET the 4 Dip Switches using a small screw driver. Possible variants vary from positions “A to 20The
20 ATyS t20
includes
20 an “Auto Configuration” feature to detect the mains voltage and frequency
H” as described in the table below. For convenience, the position functions are also described nominal 1
60 60 60 60values, phase rotation and neutral position and saves them in the ATS controller.
on the front of the ATS controller adjacent to the dip switches. Note: Before configuring the nominal values ensure that the product is properly wired, verified
Note: The READY LED will flash green as soon as settings are changed and until the new settings and ready for commissioning. It is imperative that the network supply is available and that the 22
have been saved by pressing the PROG OK button momentarily. wiring to the ATyS t voltage sensing terminals 103 – 106 and 203 – 206 has been done. It is 5
1 10 1
preferable to use the ATyS sensing kit that may be provided as an accessory.
414 413
20
207 208
A: 3A:Ph3 Ph
frequency.
E: E: 60
415413
REMOTE
REMOTE
CONTROL
CONTROL
207209
Note:
F: F: The source available LED will flash while the available network is being measured. The
416414
AUT
AUT READY LED
F 5%will
F 5% flash green as soon as settings are measured and until these settings have
208210
PROG
PROG C: Neutral
C: Neutral G: U
G:10%
U 10%
OK OKATyS t H: U H:20%
U 20%
F 10%
F 10% ATyS g (Refer to STEP 4).
ATyS tD: Neutral
D: Neutral
415
been saved by pressing the PROG OK button a second time momentarily.
ATyS g
209 210
417
ATS CONTROLLER ATS CONTROLLER
64B 63B
Power
ATS comsumption:
CONTROLLER Power
ATS comsumption:
CONTROLLER A: 3 Ph E:
Dipswitch 1 Power
ATS comsumption:
CONTROLLER 22VA Power
ATS comsumption: 22VA
72 71 74
REMOTE
CONTROLLER CONTROL
B Single Phase Network Dual auxiliary supply: Dual auxiliary supply: B: 1 Ph F:
72 7172 7471 74
A/B See instruction
Dual auxiliary sheet50/60Hz
supply: See instruction
Dual sheet50/60Hz
auxiliary+/-20%
supply:
(Attn : Dipswitch 2 is inactive in this position)
Uc 208-277V~ +/-20% Uc 208-277V~
See instruction sheet
AUT
See instruction sheet PROG C: Neutral G: U
64B 63B
Uc 208-277V~
Power comsumption: +/-20%
22VA 50/60Hz Uc 208-277V~
Power comsumption: +/-20%
22VA 50/60Hz
C Three Phase 4 wire Network (Including PowerNeutral) AUT
AUT H: U
64B 63B
comsumption: 22VA Power comsumption: 22VA OK D: Neutral
To D10
Dipswitch 2 (Allows to detect a loss of neutral for unbalanced loads)sheet 72 71 74
To D10 To D10
See instruction See instruction sheet
C/D See instruction sheet See instruction sheet
D Three Phase 3 wire Network (Without Neutral)
Dipswitch 3 E Load supply down time of 0 second (0DT = 0 sec) To D10
Un N°: E
N°UnPP /N°PNPP / PN /ΔFFΔU% ΔF %
ΔUN°: F Load supply down time of 2 seconds (0DT = 2 sec)
1: 2201:/ 127
220 / 127
1: 51: 3 5 3 POWER
POWER
2: 3802:/ 220 Dipswitch
62: 3 6 43
380 / 220
2: G Threshold Delta U : 10% / Delta F : 5% Saving the configured values
50 Hz
50 Hz
3: 4003:/ 230
400 / 230
73: 4 7 4
3:
G 8/4:H4 8 4
4: 4154:/ 240
415 / 240
4: H Threshold Delta U : 20% / Delta F : 10% AUT
XXXXXXXX
XXXXXXXX
5: 4805:/ 277
480 / 277
5: 95: 5 9 5
6: 106: 510 5
6: 2086:/ 120
208 / 120 117: 611 6
7: 2207:/ 127
7:
220 / 127
8: 128: 612 6 To SAVE the recorded setting configuration press the PROG OK button momentarily: <60ms.
8: 2308:/ 132
230 / 132
9: 139: 713 7
Note: The flashing READY LED goes off once the values are saved in the ATS controller.
60 Hz
60 Hz
9: 2409:/ 138
240 / 138
10: 1410: 714 7
10: 38010:/ 220
380 / 220
11: 1511: 815 8
11: 40011:/ 230
400 / 230
12: 1612: 816 8
N°: ΔU ΔF %
12: 41512:/ 240
415 / 240
13: 1813: 918 9 Un N° PP / PN
At least one of the source availability LED must be ON. ATyS t
13: 48013:/ 277
480 / 277
14: 2014:1020 10 Potentiometer
XXX XXX Setting Options 1: 220 / 127
2: 380 / 220
1: 5 3
2: 6 3 5 5
50 Hz
3: 400 / 230 3: 7 4 1 10 1 10
Motorised
Motorised
Changeover
ChangeoverSwitch
Switch 4: 415 / 240 4: 8 4
PROG
PROG
XXXXXXXX
0 0
5: 480 / 277 5: 9 5 20 20
1
SET the 2 potentiometers using a1600A
1 2 Set2Dip
1600A
small
3 Set3Pot
Refscrew
: 95054160 driver paying attention to the arrow indicating
Ref : 95054160
6: 208 / 120
6: 10 5
7: 11 6 60 60
Set Dip Set Pot
the position. There are a total of 14 positions for which the specific settings are described in 7:
8:
220 / 127
230 / 132
8: 12 6
9: 13 7
the table below.
60 Hz
Ready ! !Note:
Ready The READY
5 Press
ATySATyS
4 4LED will flash green as soon as settings are changed and until the new settings
5 Press
11:
12:
400 / 230
415 / 240
12: 16 8
13: 18 9 READY
PressPress 13: 480 / 277 14: 20 10 XXX
3: 400 / 230 3: 7 4
208 / 120
5: 9 5
6: 10 5
7: 11 6
7: 220 / 127 8: 12 6
Potentiometer 2 RT Supply Source Return Time : 0 to 60 min 8:
Note: When the product is powered and properly configured, after switching the product from
230 / 132 9: 13 7
60 Hz
Ready !
ATyS
Press 5 Press 4
AUT 60ms 2s
Ø 4 ... 8mm
PROG PROG
READY
A: 3 Ph E:
REMOTE CONTROL
B: 1 Ph F:
WARNING Depending on the state of the ATyS t the ATS automation may change the switch
position as soon as the mode selector is switched to AUT. This is a normal operation.
POWER AUT
Un N° PP / PN N°: ΔU ΔF %
1: 220 / 127 1: 5 3 POWER
2: 380 / 220 2: 6 3
50 Hz
3: 400 / 230 3: 7 4
4: 415 / 240 4: 8 4
XXXXXXXX
5: 480 / 277 5: 9 5
6: 10 5
6: 208 / 120 7: 11 6
7: 220 / 127 8: 12 6
8: 230 / 132 9: 13 7
60 Hz
READY
the
rent 6 7 8 9 10 11 Ensure that the emergency handle is
eady not inserted in the product and turn ATyS t
the 5 Un N° PP / PN
1: 220 / 127
N°: ΔU ΔF %
1: 5 3 POWER
aved 2: 380 / 220 2: 6 3
50 Hz
3: 400 / 230 3: 7 4
4: 415 / 240 4: 8 4
XXXXXXXX
5: 480 / 277 5: 9 5 READY
6: 10 5
STEP 7B
6: 208 / 120 7: 11 6
y be 7:
AUT Mode
220 / 127 8: 12 6
4 A: 3 Ph E:
8: 230 / 132 9: 13 7
REMOTE CONTROL
60 Hz
9: 240 / 138 10: 14 7
F:
limit 10:
(Remote Control)
380 / 220 11: 15 8 B: 1 Ph
12
11: 400 / 230 12: 16 8
12: 415 / 240 13: 18 9 AUT PROG C: Neutral G: U 10% F 5%
efer 13: 480 / 277 14: 20 10 XXX OK D: Neutral H: U 20% F 10%
order I
14 ATyS
order 0
Ready ! Press 5 Press 4
AUT
AUT 60ms 2s
Ø 4 ... 8mm
3 PROG PROG
order II
Un N° PP / PN N°: ΔU ΔF %
POWER
position I
1: 220 / 127 1: 5 3
2: 380 / 220 2: 6 3
50 Hz
2 15 3: 400 / 230
4: 415 / 240
3: 7 4
4: 8 4
XXXXXXXX
5: 480 / 277 5: 9 5
position 0 6: 208 / 120
6: 10 5
7: 11 6
cy 7:
8:
220 / 127
230 / 132
8: 12 6
9: 13 7
1 16 position II
60 Hz
9: 240 / 138 10: 14 7
10: 380 / 220 11: 15 8
11: 400 / 230 12: 16 8
12: 415 / 240 13: 18 9
13:
Imp. ≥60ms
480 / 277 14: 20 10 XXX
maintened
ed
ATyS t PROG Motorised Changeover Switch
he 22 1 2 Set Dip 3 Set Pot
1600A Ref : 95054160
0 0
To operate: close AUT
the contact corresponding to
60ms 2s
207 208 209 210
Ø 4 ... 8mm
nd
414 413
20 20
207 208
PROG PROG 5 5
the desired position. 0
1 10 1
0
10
60 60
To force the product to 0 position “OFF” bridge 20 20
415413
207209
he 60 60
417 416 415 414 413
21
416414
ve
208210
ATyS p
415
. ATyS p 18
209 210
417
READY
ATS CONTROLLER
64B 63B 417 416
DY ATS CONTROLLER
ATyS p STEP 7C
A: 3 Ph E:
Dual auxiliary supply: REMOTE CONTROL
Dual auxiliary+/-20%
Uc 208-277V~ supply: 50/60Hz ATyS p Manual Mode B: 1 Ph F:
Uc 208-277V~ +/-20%
22VA 50/60Hz AUT PROG C: Neutral G: U 10% F 5%
64B 63B
A: 3 Ph E:
Power
ATS comsumption:
CONTROLLER OK D: Neutral H: U 20% F 10%
Power
ATS comsumption:
CONTROLLER 22VA
72 71 74
See instruction
Dual sheet50/60Hz
auxiliary+/-20%
Uc 208-277V~ supply:
C: Neutral G: U 10% F 5% See instruction sheet
64B 63B
Uc 208-277V~
Power comsumption: +/-20%
22VA 50/60Hz
H: U 20% F 10%
64B 63B
0
D: Neutral Power comsumption: 22VA
To D20
72 71 74
To D20 To D20
90° 90 AUT
°
To D20
Un N° PP / PN N°: ΔU ΔF %
1: 220 / 127 1: 5 3 POWER
2: 380 / 220 2: 6 3
50 Hz
3: 400 / 230 3: 7 4
4: 415 / 240 4: 8 4
XXXXXXXX
5: 480 / 277 5: 9 5
6: 10 5
I
6: 208 / 120 7: 11 6
T 20 19 7:
8:
220 / 127
230 / 132
8: 12 6
9: 13 7
II
60 Hz
1. MANUAL Mode LED indication. 12. READY LED indication PROG Motorised Changeover Switch
(Yellow steady light when in Manual Mode). Green steady light : Product in AUTO, 1 2 Set Dip 3 Set Pot
1600A Ref : 95054160
PROG
2s
Ø 4 ... 8mm
20
Green flashing light when in Auto with timers saved or have been changed since last
running in the background. saved.
(Press PROG OK button in manual mode to
3. REMOTE CONTROL Mode LED indication. save or revert to last saved settings).
Yellow steady light when in remote control
mode. 13. Sealing screw location 2 for use with the
Remote control mode is achieved with the sealing cover.
F 5%
Auto/Manu selector switched to Auto and 14. FAULT LED indication. (Red steady light in
F 10%
terminals 312 closed with terminal 317. case of an ATS controller internal fault). Padlocking Mode
Remote control orders are received through 15. Configuration dip switches : STEP 7D (as standard : in position O)
closing 314 to 316 with 317. (4 dip switches with 2 positions in each
4. Switch 1 LED position indication. A to H).
(Green when in position 1). 16. PROG OK: Configuration save push button.
5. Source supply I availability LED indication. (ATTN: Active in Manual Mode ONLY).
(Green when supply I voltage is within the Press briefly to confirm and save all set
R set limits). configuration settings.
he Hold pressed for 2 seconds to set the
6. Zero position LED indication.
(Yellow when in position 0). network supply voltage and frequency by
m Auto Configuration.
S t
7. Switch 2 LED position indication. This is to be followed by pressing briefly to
(Green when in position 2). save the set value configured.
10 8. Source supply II availability LED indication. 17. Green LED Indication: Power
20
(Green when supply II voltage is within the
set limits). 18. Red LED Indication: Product Unavailable /
Manual Mode / Fault Condition
9. Sealing screw location 1 for use with sealing
cover (Available as an accessory) 19. Auto / Manual mode selector switch
10. Potentiometer 1: Supply FAILURE Time (FT)
(Key version available as an option)
mm
3x
Adjustable from 0 to 60 seconds. 20. Padlocking facility Ø 4-8
(Up to 3 padlocks of dia. 4 – 8mm)
F 5%
F 10% 11. Potentiometer 2: Supply RETURN Time (RT)
Adjustable from 0 to 60 minutes. 21. Emergency manual operation shaft location
(Accessible only in manual mode)
itch 22. Switch position indication window:
I (On switch I) O (Off) II (On switch II).
ATyS t
STEP 1 STEP 2 STEP 3 STEP 4 STEP 5 STEP 6
STEP 7B produ
Cabinet / Back Power Terminal COMMAND / Power SUPPLY and CHECK PROGRAMMING
Plate Installation Connections CONTROL terminal ATS Controller AUT Mode a flat r
connections Terminal (Remote Control)
Connections
Motorised Source Changeover Switch
Automatic Transfer Switching Equipment STEP 7C
Manual Mode Door c
Preliminary operations front p
Check the following upon delivery and after removal of the
packaging: STEP 7D
• Packaging and contents are in good condition. Padlocking Mode
• The product reference corresponds to the order.
• Contents should include: STEP 4
Qty 1 x ATyS t ATyS t
Qty 1 x Emergency handle and fixing clip
Quick Start instruction sheet
Warning ø 15
Accessories
• Bridging bars and connection kits. STEP 4 Power Supply, Sensing and Control wiring (ATS Controller)
Recommanded to use SOCOMEC
Voltage Sensing Kit Example
• Control voltage transformer (400Vac -> 230Vac). (refer to ATyS t
Connect the product with a cable of section of 1,5 to 2,5 mm2. accessories
• DC power supply (12/24Vdc -> 230Vac). Screw M3 - Tightening torque: min.: 0.5 Nm - max.: 0.6 Nm for details)
• Mounting spacers to raise the product x 10mm.
• Phase barriers. 2
• Terminal shrouds.
• Terminal screens. ATS Power Supply ATS Power Supply
• Auxiliary contacts (Additional). Input II Input I
• Padlocking in 3 positions (I - O - II). Power supply II - L Power supply I - L
• Lockout accessories (RONIS - EL 11 AP). Power supply II - N Power supply I - N
• Door escutcheon frame. 208-277 VAC ±20%: 208-277 VAC ±20%:
• ATyS D10 Interface (remote display). 50/60 Hz 50/60 Hz
• Voltage sensing kit.
• Sealable cover.
• RJ45 cable for ATyS D10 => ATyS t
ATS Voltage Sensing ATS Voltage Sensing
For further details refer to the product instruction manual Input Input
under chapter "Spares and Accessories" Source supply II Source supply I
S II - Phase 1 S I - Phase 1
S II - Phase 2 S I - Phase 2
S II - Phase 3 S I - Phase 3
575 VAC (ph-ph) max 575 VAC (ph-ph) max
S II - Neutral S I - Neutral
332 VAC (ph-n) max 332 VAC (ph-n) max
www.socomec.com
To download, brochures, catalogues
417 416 415 414 413
64B 63B
72 71
Printing size: 420x297. Final size 210x297. This page visible first. See instruction sheet See instruction sheet
CORPORATE HQ CONTACT: (Product available)
SOCOMEC SAS, 1-4 RUE DE WESTHOUSE, 67235 BENFELD, FRANCE
74
74
To D10
To D10
Remote interface
RJ45 - to ATyS D10
=
product is installed on
250
280
a flat rigid surface.
l)
=
138 C 21
20 T
250
50.5
3P 4P 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P
15 28.5
10 33
ø 15
15
25 25
M 255 335 255 335 255 335 347 467 347 467 347 467 347 467
30 30 T 80 80 80 80 80 80 120 120 120 120 120 120 120 120
8.5 33 8.5 15.75 28.5 15.75 45 45
50 60 90 C 391 391 391 391 391 391 391 391 523 523 523 523 523 523
Recommended cable section Cu (mm2) at Ith 2x50x5 2x60x5 2x60x7 2x100x5 3x100x5 4x100x5 3x100x10
Maximum cable section Cu (mm2) 2x300 4x185 4x185 6x185 - - -
Maximum Cu busbar width (mm) 63 63 63 100 100 100 100
Type of screw M8 M8 M10 M12 M12 M12 M12
Recommended tightening torque (N.m) 8.3 8.3 20 40 40 40 40
Maximum tightening torque (N.m) 13 13 26 45 45 45 45
SOCOMEC
Sensing Kit Example: Control wiring for a 400VAC application having a 3 phase and neutral supply. STEP 3 CONTROL / COMMAND Terminals
er to ATyS t Ensure that the product is in Manual Mode.
ccessories
for details)
2 1
F2 F1
1
201 202
102 101
17 17
II/1-2 II/3-4 II/5-6 II/7-8
2
16 16
15
64B 63B 417 416 415 414 413
14
13
12
11
64B 63B
64B 63B
72 71
72 71
See instruction sheet See instruction sheet See instruction sheet 7. Position II aux contact 17. Power Supply Inputs
8. Position I aux contact
74
74
74
To D10
To D20
To D20
3
ATyS
ATyS
t t
Dip Switch Setting Options 5 5 5 5 Auto Configuration of Mains Voltage and Frequency
1 1 1 1
10 10 10 10 2
0 0 0 0
SET the 4 Dip Switches using a small screw driver. Possible variants vary from positions “A to 20The
20 ATyS t20
includes
20 an “Auto Configuration” feature to detect the mains voltage and frequency
H” as described in the table below. For convenience, the position functions are also described nominal 1
60 60 60 60values, phase rotation and neutral position and saves them in the ATS controller.
on the front of the ATS controller adjacent to the dip switches. Note: Before configuring the nominal values ensure that the product is properly wired, verified
Note: The READY LED will flash green as soon as settings are changed and until the new settings and ready for commissioning. It is imperative that the network supply is available and that the 22
have been saved by pressing the PROG OK button momentarily. wiring to the ATyS t voltage sensing terminals 103 – 106 and 203 – 206 has been done. It is 5
1 10 1
preferable to use the ATyS sensing kit that may be provided as an accessory.
414 413
20
207 208
A: 3A:Ph3 Ph
frequency.
E: E: 60
415413
REMOTE
REMOTE
CONTROL
CONTROL
207209
Note:
F: F: The source available LED will flash while the available network is being measured. The
416414
AUT
AUT READY LED
F 5%will
F 5% flash green as soon as settings are measured and until these settings have
208210
PROG
PROG C: Neutral
C: Neutral G: U
G:10%
U 10%
OK OKATyS t H: UH:20%
U 20%
F 10%
F 10% ATyS g (Refer to STEP 4).
ATyS tD: Neutral
D: Neutral
415
been saved by pressing the PROG OK button a second time momentarily.
ATyS g
209 210
417
ATS CONTROLLER ATS CONTROLLER
64B 63B
Power
ATS comsumption:
CONTROLLER Power
ATS comsumption:
CONTROLLER A: 3 Ph E:
Dipswitch 1 Power
ATS comsumption:
CONTROLLER 22VA Power
ATS comsumption: 22VA
72 71 74
REMOTE
CONTROLLER CONTROL
B Single Phase Network Dual auxiliary supply: Dual auxiliary supply: B: 1 Ph F:
72 7172 7471 74
A/B See instruction
Dual auxiliary sheet50/60Hz
supply: See instruction
Dual sheet50/60Hz
auxiliary+/-20%
supply:
(Attn : Dipswitch 2 is inactive in this position)
Uc 208-277V~ +/-20% Uc 208-277V~
See instruction sheet
AUT
See instruction sheet PROG C: Neutral G: U
64B 63B
Uc 208-277V~
Power comsumption: +/-20%
22VA 50/60Hz Uc 208-277V~
Power comsumption: +/-20%
22VA 50/60Hz
C Three Phase 4 wire Network (Including PowerNeutral) AUT
AUT H: U
64B 63B
comsumption: 22VA Power comsumption: 22VA OK D: Neutral
To D10
Dipswitch 2 (Allows to detect a loss of neutral for unbalanced loads)sheet 72 71 74
To D10 To D10
See instruction See instruction sheet
C/D See instruction sheet See instruction sheet
D Three Phase 3 wire Network (Without Neutral)
Dipswitch 3 E Load supply down time of 0 second (0DT = 0 sec) To D10
Un N°: E
N°UnPP /N°PNPP / PN /ΔFFΔU% ΔF %
ΔUN°: F Load supply down time of 2 seconds (0DT = 2 sec)
1: 2201:/ 127
220 / 127
1: 51: 3 5 3 POWER
POWER
2: 3802:/ 220 Dipswitch
62: 3 6 43
380 / 220
2: G Threshold Delta U : 10% / Delta F : 5% Saving the configured values
50 Hz
50 Hz
3: 4003:/ 230
400 / 230
73: 4 7 4
3:
G 8/4:H4 8 4
4: 4154:/ 240
415 / 240
4: H Threshold Delta U : 20% / Delta F : 10% AUT
XXXXXXXX
XXXXXXXX
5: 4805:/ 277
480 / 277
5: 95: 5 9 5
6: 106: 510 5
6: 2086:/ 120
208 / 120 117: 611 6
7: 2207:/ 127
7:
220 / 127
8: 128: 612 6 To SAVE the recorded setting configuration press the PROG OK button momentarily: <60ms.
8: 2308:/ 132
230 / 132
9: 139: 713 7
Note: The flashing READY LED goes off once the values are saved in the ATS controller.
60 Hz
60 Hz
9: 2409:/ 138
240 / 138
10: 1410: 714 7
10: 38010:/ 220
380 / 220
11: 1511: 815 8
11: 40011:/ 230
400 / 230
12: 1612: 816 8
N°: ΔU ΔF %
12: 41512:/ 240
415 / 240
13: 1813: 918 9 Un N° PP / PN
At least one of the source availability LED must be ON. ATyS t
13: 48013:/ 277
480 / 277
14: 2014:1020 10 Potentiometer
XXX XXX Setting Options 1: 220 / 127
2: 380 / 220
1: 5 3
2: 6 3 5 5
50 Hz
3: 400 / 230 3: 7 4 1 10 1 10
Motorised
Motorised
Changeover
ChangeoverSwitch
Switch 4: 415 / 240 4: 8 4
PROG
PROG
XXXXXXXX
0 0
5: 480 / 277 5: 9 5 20 20
1
SET the 2 potentiometers using a1600A
1 2 Set2Dip
1600A
small
3 Set3Pot
Refscrew
: 95054160 driver paying attention to the arrow indicating
Ref : 95054160
6: 208 / 120
6: 10 5
7: 11 6 60 60
Set Dip Set Pot
the position. There are a total of 14 positions for which the specific settings are described in 7:
8:
220 / 127
230 / 132
8: 12 6
9: 13 7
the table below.
60 Hz
Ready ! !Note:
Ready The READY
5 Press
ATySATyS
4 4LED will flash green as soon as settings are changed and until the new settings
5 Press
11:
12:
400 / 230
415 / 240
12: 16 8
13: 18 9 READY
PressPress 13: 480 / 277 14: 20 10 XXX
3: 400 / 230 3: 7 4
208 / 120
5: 9 5
6: 10 5
7: 11 6
7: 220 / 127 8: 12 6
Potentiometer 2 RT Supply Source Return Time : 0 to 60 min 8:
Note: When the product is powered and properly configured, after switching the product from
230 / 132 9: 13 7
60 Hz
Ready !
ATyS
Press 5 Press 4
AUT 60ms 2s
Ø 4 ... 8mm
PROG PROG
READY
A: 3 Ph E:
REMOTE CONTROL
B: 1 Ph F:
WARNING Depending on the state of the ATyS t the ATS automation may change the switch
position as soon as the mode selector is switched to AUT. This is a normal operation.
POWER AUT
Un N° PP / PN N°: ΔU ΔF %
1: 220 / 127 1: 5 3 POWER
2: 380 / 220 2: 6 3
50 Hz
3: 400 / 230 3: 7 4
4: 415 / 240 4: 8 4
XXXXXXXX
5: 480 / 277 5: 9 5
6: 10 5
6: 208 / 120 7: 11 6
7: 220 / 127 8: 12 6
8: 230 / 132 9: 13 7
60 Hz
READY
the
rent 6 7 8 9 10 11 Ensure that the emergency handle is
eady not inserted in the product and turn ATyS t
the 5 Un N° PP / PN
1: 220 / 127
N°: ΔU ΔF %
1: 5 3 POWER
aved 2: 380 / 220 2: 6 3
50 Hz
3: 400 / 230 3: 7 4
4: 415 / 240 4: 8 4
XXXXXXXX
5: 480 / 277 5: 9 5 READY
6: 10 5
STEP 7B
6: 208 / 120 7: 11 6
y be 7:
AUT Mode
220 / 127 8: 12 6
4 A: 3 Ph E:
8: 230 / 132 9: 13 7
REMOTE CONTROL
60 Hz
9: 240 / 138 10: 14 7
F:
limit 10:
(Remote Control)
380 / 220 11: 15 8 B: 1 Ph
12
11: 400 / 230 12: 16 8
12: 415 / 240 13: 18 9 AUT PROG C: Neutral G: U 10% F 5%
efer 13: 480 / 277 14: 20 10 XXX OK D: Neutral H: U 20% F 10%
order I
14 ATyS
order 0
Ready ! Press 5 Press 4
AUT
AUT 60ms 2s
Ø 4 ... 8mm
3 PROG PROG
order II
Un N° PP / PN N°: ΔU ΔF %
POWER
position I
1: 220 / 127 1: 5 3
2: 380 / 220 2: 6 3
50 Hz
2 15 3: 400 / 230
4: 415 / 240
3: 7 4
4: 8 4
XXXXXXXX
5: 480 / 277 5: 9 5
position 0 6: 208 / 120
6: 10 5
7: 11 6
cy 7:
8:
220 / 127
230 / 132
8: 12 6
9: 13 7
1 16 position II
60 Hz
9: 240 / 138 10: 14 7
10: 380 / 220 11: 15 8
11: 400 / 230 12: 16 8
12: 415 / 240 13: 18 9
13:
Imp. ≥60ms
480 / 277 14: 20 10 XXX
maintened
ed
ATyS t PROG Motorised Changeover Switch
he 22 1 2 Set Dip 3 Set Pot
1600A Ref : 95054160
0 0
To operate: close AUT
the contact corresponding to
60ms 2s
207 208 209 210
Ø 4 ... 8mm
nd
414 413
20 20
207 208
PROG PROG 5 5
the desired position. 0
1 10 1
0
10
60 60
To force the product to 0 position “OFF” bridge 20 20
415413
207209
he 60 60
417 416 415 414 413
21
416414
ve
208210
ATyS p
415
. ATyS p 18
209 210
417
READY
ATS CONTROLLER
64B 63B 417 416
DY ATS CONTROLLER
Dual auxiliary supply:
Dual auxiliary+/-20%
Uc 208-277V~ supply: 50/60Hz
ATyS p
ATyS p STEP 7C Manual Mode
AUT
REMOTE CONTROL
PROG
A: 3 Ph
B: 1 Ph
C: Neutral
E:
F:
G: U 10% F 5%
Uc 208-277V~ +/-20%
22VA 50/60Hz
64B 63B
A: 3 Ph E:
Power
ATS comsumption:
CONTROLLER OK D: Neutral H: U 20% F 10%
Power
ATS comsumption:
CONTROLLER 22VA
72 71 74
See instruction
Dual sheet50/60Hz
auxiliary+/-20%
Uc 208-277V~ supply:
C: Neutral G: U 10% F 5% See instruction sheet
64B 63B
Uc 208-277V~
Power comsumption: +/-20%
22VA 50/60Hz
H: U 20% F 10%
64B 63B
To D20 To D20
9 0°
To D20
Un N° PP / PN N°: ΔU ΔF %
1: 220 / 127 1: 5 3 POWER
2: 380 / 220 2: 6 3
50 Hz
3: 400 / 230 3: 7 4
4: 415 / 240 4: 8 4
XXXXXXXX
5: 480 / 277 5: 9 5
6: 10 5
6: 208 / 120 7: 11 6
T 20 19 7:
8:
220 / 127
230 / 132
8: 12 6
9: 13 7
60 Hz
0
11: 400 / 230 12: 16 8
12: 415 / 240 13: 18 9
1. MANUAL Mode LED indication. 12. READY LED indication PROG Motorised Changeover Switch
(Yellow steady light when in Manual Mode). Green steady light : Product in AUTO, 1 2 Set Dip 3 Set Pot
1600A Ref : 95054160
Ø 4 ... 8mm
10
no timers running. PROG PROG
saved or have been changed since last
°
20
Green flashing light when in Auto with timers
running in the background. saved.
(Press PROG OK button in manual mode to
3. REMOTE CONTROL Mode LED indication. save or revert to last saved settings).
Yellow steady light when in remote control I
mode. 13. Sealing screw location 2 for use with the
Remote control mode is achieved with the sealing cover.
F 5%
Auto/Manu selector switched to Auto and 14. FAULT LED indication. (Red steady light in
F 10%
terminals 312 closed with terminal 317. case of an ATS controller internal fault). Padlocking Mode
Remote control orders are received through 15. Configuration dip switches : STEP 7D (as standard : in position O)
closing 314 to 316 with 317. (4 dip switches with 2 positions in each
4. Switch 1 LED position indication. A to H).
(Green when in position 1). 16. PROG OK: Configuration save push button.
5. Source supply I availability LED indication. (ATTN: Active in Manual Mode ONLY).
(Green when supply I voltage is within the Press briefly to confirm and save all set
R set limits). configuration settings.
he Hold pressed for 2 seconds to set the
6. Zero position LED indication.
(Yellow when in position 0). network supply voltage and frequency by
m Auto Configuration.
S t
7. Switch 2 LED position indication. This is to be followed by pressing briefly to
(Green when in position 2). save the set value configured.
10 8. Source supply II availability LED indication. 17. Green LED Indication: Power
20
(Green when supply II voltage is within the
set limits). 18. Red LED Indication: Product Unavailable /
9. Sealing screw location 1 for use with sealing
Manual Mode / Fault Condition
19. Auto / Manual mode selector switch mm
3x
cover (Available as an accessory)
(Key version available as an option) Ø 4-8
10. Potentiometer 1: Supply FAILURE Time (FT)
Adjustable from 0 to 60 seconds. 20. Padlocking facility
(Up to 3 padlocks of dia. 4 – 8mm)
F 5%
F 10% 11. Potentiometer 2: Supply RETURN Time (RT)
Adjustable from 0 to 60 minutes. 21. Emergency manual operation shaft location
(Accessible only in manual mode)
itch 22. Switch position indication window:
I (On switch I) O (Off) II (On switch II).
2 3 4 5 6
7
8
19 9
10
16 17 16 15 14 13 12
11
2 3 4 6 5 7 9 8
10
11
1
12
15 14 13
4 5 6 7 8 9
ATyS t
5 5
1 10 1 10
0 0
3 20 20
2 60 60
10
READY
A: 3 Ph E:
REMOTE CONTROL
B: 1 Ph F:
AUT PROG
OK
C: Neutral
D: Neutral
G: U 10% F 5%
H: U 20% F 10%
16 15 14 13 12 11
Green flashing : Settings displayed not saved or have been changed since last saved.
(Press PROG OK button in manual mode to save or revert to last saved settings).
8. FAILURE Time (FT) Potentiometer to set the supply adjustable from 0 to 60s
9. RETURN Time (RT) Potentiometer to set the supply adjustable from 0 to 60min
10. Sealing screw location 2 for use with the sealing cover.
XXX 11. FAULT LED indication.
Red steady light in case of an ATS controller internal fault and blinking in case of an external fault
(rotation incorrect / neutral position incorrect)
Motorised
Switch Changeover
the product Switch
from Auto to Manual and back to Auto to reset a fault condition.
1600A Ref : 95054160
12. Configuration dip switches
4 dip switches with 2 positions in each
13. PROG OK: Configuration save push button.
ATTN: Active in Manual Mode ONLY
ATyS
Press briefly to confirm and save all set configuration settings.
Hold pressed for 2 seconds to set the network supply voltage and frequency by Auto Configuration.
This is to be followed by pressing briefly to save the set value
Ø 4 ...configured
8mm (see «8.3. Programming», page 50).
14. MANUAL Mode LED indication
Yellow steady light when in Manual Mode
15. AUTO Mode LED indication
Green steady light when in Auto mode with no timers running.
Green flashing light when in Auto with timers running in the background.
16. REMOTE CONTROL Mode LED indication.
Yellow steady light when in remote control mode.
Remote control mode is achieved with the Auto/Manu selector switched to Auto and terminals 312 closed with terminal
317. Remote control orders are received through closing 314 to 316 with 317.
5.4.1. IP Rating
ø 1 mm
• IP2X against direct contact for the ATyS t motorization control unit.
• IP2X against direct contact for the power section with the connections in place and when including suitable,
correctly installed incoming and outgoing terminal shields.
• IP 0 for the bare power section without terminal shields in place.
5.4.2.1. Temperature
• From -20 to +40°C without derating
• From -20 to +70°C when applying a Kt derating correction factor
5.4.2.2. Hygrometry
• 80% humidity without condensation at 55°C
• 95% humidity without condensation at 40°C
5.4.2.3. Altitude
• Up to 2000m in altitude without derating
• For higher altitude the Ka correction factors below apply
5.4.3.1. Temperature
• From -40 to +70°C
5.4.7. WEEE
The ATyS t is built in accordance with 2002/96/CE directive:
U
4
W
CA
270
119
6
=
Fix. 195
Fix. 180
101
AC
BA
AA
223
=
120
140
V
CA
10.5 Y Y 48
2 3
88
10 X T T T 11 Z1 138
3 20
Z2 5
F
A H
165
C
Fix. 195
1
Fix. 180
Ø7
CA
50.5
Ø9 U
7
Terminal Switch
Overall dimensions Body Connection
Rating (A) shrouds mounting
A 3p. A 4p. C AC F 3p. F 4p. H J 3p. J 4p. J1 M 3p. M 4p. T U V W X 3p. X 4p. Y Z1 Z1 AA BA CA
125 304 334 244 233 286.5 317 151 154 184 34 120 150 36 20 25 9 28 22 3.5 38 134 135 115 10
160 304 334 244 233 286.5 317 151 154 184 34 120 150 36 20 25 9 28 22 3.5 38 134 135 115 10
200 304 334 244 233 286.5 317 151 154 184 34 120 150 36 20 25 9 28 22 3.5 38 134 135 115 10
250 345 395 244 288 328 378 152 195 245 35 160 210 50 25 30 11 33 33 3.5 39.5 133.5 160 130 15
315 345 395 244 288 328 378 152 195 245 35 160 210 50 25 30 11 33 33 3.5 39.5 133.5 160 130 15
400 345 395 244 288 328 378 152 195 245 35 160 210 50 35 35 11 33 33 3.5 39.5 133.5 170 140 15
500 394 454 321 402 377 437 221 244 304 34 210 270 65 45 50 13 42.5 37.5 5 53 190 260 220 20
630 394 454 321 402 377 437 221 244 304 34 210 270 65 45 50 13 42.5 37.5 5 53 190 260 220 20
All dimensions in mm
250
V
6
169
=
250
200
AC
AA
B
280
=
166
166
atys_838_a_1_x_cat
2 Y 5 Y 48
12.5 X T T T 12.5 3
F Z1 3
253.5 94
1
293
391.5
ø9 16 x 11 ø12.5 138
20
5 5
12.5
15 28.5
10 33
svr_098_a_1_x_cat
ø 15
svr_077_a_1_x_cat
svr_078_b_1_x_cat
15
214
25 25
atys_843_a_1_x_cat
8.5 33 8.5 15.75 28.5 15.75 30 30
50 60 45 45
50.5
90
7
Overall Terminal
Body Switch mounting Connection
Rating (A) dimensions screens
B AC F 3p. F 4p. J 3p. J 4p. M 3p. M 4p. T U V X Y Z1 AA
800 370 461 504 584 307 387 255 335 80 50 60.5 47.5 7 66.5 321
1000 370 461 504 584 307 387 255 335 80 50 60.5 47.5 7 66.5 321
1250 370 461 504 584 307 387 255 335 80 60 65 47.5 7 66.5 330
1600 380 531 596 716 399 519 347 467 120 90 44 53 8 67.5 288
All dimensions in mm
90
125
°
330
461
258
250
380
I
atys_839_a_1_x_cat
50
4 Ø 6,5
50
Ø 31
2000 to 3200 A
138
ø12.5 20
5 5
12.5
svr_098_a_1_x_cat
15
214
25 25
atys_843_a_1_x_cat
30 30
45 45
50.5
90
8
All dimensions in mm
Never handle any customer mounted accessories while there may be the risk of
DANGER voltage being or becoming present.
2000A to 3200A
1 I th = 2000 A
14.96
10.15
9.84
258
250
380
3P 4P
0.49
12,5
0.59
15
37 37 60 0.98 0.98
2 I th = 2500 A 25 25
1.18 1.18
3P 4P 30 30
3.54
6.10
155
5.07
129
90
VERSION 02 - 03 - 05 - 06 - 09 - 12
1.18 (4x) 5.19 1.18 (4x) 0.86
30 (4x) 132 30 (4x) 22
8.30
211
3 I th = 3200 A
3P 4P
provided VERSION 07 - 08 - 10 - 11
fourni
1.18 (4x) 6.41
30 (4x) 163
8.89
226
! TO BE SUPPLIED BY OTHERS
x1
VERSION
x1 708 lb-in x6
80 Nm Rondelle contact
MOY. M M12
+ NFE 25 511 H M12
included with 3200A 01 H M12-35 6.8 - 6 x 12 x 6x
product as standard
708 lb-in x6
80 Nm 02 H M12-55 6.8 - 3 x 6x 3x
2699 1200 03 H M12-55 6.8 - 5 x 10 x 5x
2619 1200 2699 1201 2629 1200 A H M12-35 6.8 - 3 x 3x -
04
B H M12-45 6.8 - 3 x 3x -
x2 05 H M12-65 6.8 - 3 x 6x 3x
x1 x1 06 H M12-65 6.8 - 5 x 10 x 5x
07 H M12-55 6.8 - 3 x 6x 3x
+ + + 08 H M12-55 6.8 - 5 x 10 x 5x
x6 09 H M12-55 6.8 - 10 x 20 x 10 x
708 lb-in
708 lb-in x6 708 lb-in x6
80 Nm 80 Nm 10 H M12-65 6.8 - 3 x 6x 3x
80 Nm
11 H M12-65 6.8 - 5 x 10 x 5x
2639 1200 4109 0250 4109 0320 12 H M12-65 6.8 - 10 x 20 x 10 x
Note: Reference numbers and quantity given above and below are for one connection and per pole.
For a full set multiply the quantity indicated by the number of poles (3 or 4 pole) and then multiply by 2 (N° of switches)
Direct
Connection
V2 & V3
Kit :
2619 1200 x 1
2629 1200 x 1
2639 1200 x 1
V7 & V8
Kit :
2619 1200 x 2
2699 1201 x 2
2629 1200 x 1
4109 0320 x 1
V9
Kit :
2619 1200 x 2
2629 1200 x 2
2639 1200 x 2
3200A (Minimum Cu bar section 3x100x10mm)
VERSION 10 VERSION 11 VERSION 12
V12
Kit :
2629 1200 x 2
2639 1200 x 2
Source 1 Source 2
202 201
230 Vac 230 Vac
Pos I
Pos II
92 94 91 (fast-on)
Pos I Pos II
2x
81 82 84 91 92 94
(1) 81 82 84 91 92 94
When mounting one auxiliary contact on position I or II, use the short screws provided.
(1)
When mounting two auxiliary contacts on position I or II, use the long screws provided.
ø 15
svr_077_a_1_x_cat
svr_078_b_1_x_cat
15
25 25
8.5 33 8.5 15.75 28.5 15.75 30 30
50 60 45 45
90
Note for all ratings: Take into account the connection cable lengths and/or others environmental specific operating
conditions.
1 2
II
I
Source
Source
417 413
417 413
207 208 209 210 72 71
64B417
64B417
eTROLLER
instruction sheet See instruction sheet
ATS CONTROLLER See instruction sheet
ATS CONTROLLER See instruction sheet
ATS CONTROLLER
iliary supply: Dual auxiliary supply: Dual auxiliary supply: Dual auxiliary supply:
277V~ +/-20% 50/60Hz Uc 208-277V~ +/-20% 50/60Hz Uc 208-277V~ +/-20% 50/60Hz Uc 208-277V~ +/-20% 50/60Hz
74 72 71
74 72 71
74 72 71
D10
D20
D20
64B To63B
64B To63B
64B To63B
omsumption: 22VA Power comsumption: 22VA Power comsumption: 22VA Power comsumption: 22VA
e instruction sheet See instruction sheet See instruction sheet See instruction sheet
74
74
74
To D10
To D20
To D20
Source 1 Source 2
1 1
N N
Load
3BL Three
phase network without neutral 3NBL Three phase network without neutral
(with 1 CT connected on Phase 1)
2 2 2 2
3 3 3 3
Load Load
4BL Three phase network with neutral 4NBL Three phase network with neutral
(with 1 CT connected on Phase 1)
2 2 2 2
3 3 3 3
N N N N
Load Load
Source 1
N 3 3 N N
2 2 3 2 3 2
1 1 1 1
1
Source 2
N 3 3 N N
2 2 3 2 3 2
1 1 1 1
1 R2 R2
T1 R1 R1
R1 R1
ATyS p CT cabling (load side) R1 T2 R2 T2 R2
S2
R2 T1 S1
N 3 3 N N
2 S1 S2 2 3 2 3 2
Voltage sensing
Source 1 - U12, U23, U31 U12, U23, U31 U12, U23, U31 U12, U23, U31
V1 V1, V2, V3 V1, V2, V3
Source 2 - U12, U23, U31 U12, U23, U31 U12, U23, U31 U12, U23, U31
V1 - - V1, V2, V3 V1, V2, V3
Source presence (source
3 3 3 3 3
available)
Source in ranges (U, V, F) 3 3 3 3 3
Rotation phase order - 3 3 3 3
Neutral position - - - 3 3
Voltage unbalanced is lower
- 3 3 3 3
than threshold
2 1
Fus. 4A Fus. 4A
type gG F2 F1 type gG
201 202
102 101
17 17
ATyS t Voltage
Sensing and
II/1-2 II/3-4 II/5-6 II/7-8
15
11
10
RJ
6 7 8 9
312 313 314 315 316 317 63A 64A 24 14 04 13 D10
Remote
Display Unit
5 4 3 2 1
1 preferred source 6. Product Available output (Motor) 13. I/P Manual retransfer (RTC)
2 alternate source 7. Position II aux contact 14. I/P to define the source priority: Source priority
8. Position I aux contact set to S2 if closed, S1 if open
1. Position 0 order
9. Position 0 aux contact 15. I/P with/without source priority: no source
2. Position I order priority when closed
3. Position II order 10. O/P to D10 remote display
11. Product Available output (ATS) 16. Voltage sensing inputs
4. Zero position priority order 17. Power supply Inputs
5. Remote Control Enable (Priority over Auto) 12. I/P Inhibition of the ATS controls
Verify that the Auxiliary power supply feeding terminals 101 and 102 / (201 and
CAUTION 202) are within the limits of 208VAC -> 277VAC ±20%
Do not handle any control or power cables connected to the ATyS when voltage
DANGER may be present.
CAUTION
(166-332Vac)
101-L/N Power 230V
ATS Module
Common
ATyS p
7/8 - 103
1/2 - 106
RJ45
See instruction sheet
Power comsumption: 22VA
413
414
415
416
417
63B
64B
Dual auxiliary supply:
ATS CONTROLLER
ATyS t
5 5
1 10 1 10
ATyS p
0 0
20 20
60 60
Uc 208-277V~ +/-20% 50/60Hz Uc 208-277V~ +/-20% 50/60Hz
READY
Dual auxiliary supply:
A: 3 Ph E:
REMOTE CONTROL
B: 1 Ph F:
ATS CONTROLLER
AUT PROG
OK
C: Neutral
D: Neutral
G: U 10% F 5%
H: U 20% F 10%
ATyS g
AUT
417 416 415 414 413 64B 63B To D20
See instruction sheet
22VA
comsumption:
Un N°: ΔU ΔF %
ATS CONTROLLER
N° PP / PN
1: 220 / 127 1: 5 3 POWER
2: 380 / 220 2: 6 3
50 Hz
3: 400 / 230 3: 7 4
4: 415 / 240 4: 8 4
XXXXXXXX
5: 480 / 277 5: 9 5
6: 10 5
6: 208 / 120 7: 11 6
Power
7: 220 / 127 8: 12 6
8: 230 / 132 9: 13 7
Hz
1/2 - 203
7/8 - 206
ATyS
Source 2 - 1Ph/3Ph
Aux Supply-2
(166-332Vac)
Ensure to mount the kit onto the product before connecting the power cables.
CAUTION
Be careful not to damage the contacts during kit mounting and during power cables
connections (Tighten the cables carefully).
It can be used with top or bottom cables entry. The only connection to respect is that measures of the source on
Switch I must be connected to the inputs located on the right of the electronic module and the measures of the
source on Switch II must be connected to the inputs located on the left of the electronic module.
Load
LOAD
CAUTION
Sources
Sources
1 3 5 7
1 3 5 7
II
I
2 4 6 8
2 4 6 8
B A B A
mechanical cables
support
206 205 204 203 202201 101 102 103 104 105 106
B A B A
mechanical
cables support
7/8 5/6 3/4 1/2 L/N N/L L/N N/L 7/8 5/6 3/4 1/2
7.4.3. Network
Power inputs (terminals 101-102 & 201-202) are 220/240/277 VAC (208 - 277VAC) ± 20%. It is necessary to adapt
the power input cable connections according to the network configuration. (Power supply to be taken between
phase to phase or between phase and neutral).
Verify that the power supply between terminals 101 – 102 and 201 – 202 (nominal
CAUTION auxiliary voltage supply) is within 208-277VAC ± 20%.
Network 380/415 VAC ± 20% with neutral For network 220/240 VAC ± 20%, power supply
conductor (no kit modification required): cables A-B to connect between phases
B A mechanical B A B A mechanical B A
cables cables
7/8 5/6 3/4 1/2 L/N N/L support L/N N/L 7/8 5/6 3/4 1/2 7/8 5/6 3/4 1/2 L/N N/L support L/N N/L 7/8 5/6 3/4 1/2
AUTO MODE:
• Activates the remote control
inputs and the ATS controller
automation.
• Inhibits the padlocking facility
• Inhibits the insertion of the
manual operation handle
MODE when in AUT Mode
MANUAL MODE:
0 (Not Padlocked)
90° 90 AUT
• Inhibits the control inputs.
°
• Allows to insert the handle
for emergency manual
I II
operation.
• Allows padlocking in O
MODE Position. (With the handle for
manual operation removed)
MANUAL MODE:
(Padlocked)
POS 0
MODE
Padlocking in position I - O and
38xmm II is possible when the optional
function is included in the ATyS t.
Ø 4-
(Refer to product catalogue)
Depending on the state of the ATyS t the ATS automation may change the switch
WARNING position as soon as the mode selector is switched to AUT. This is a normal operation.
To operate the ATyS t manually ensure that no live parts are accessible, turn the front selector switch into the manual
position (see page 18) and insert the handle (see page 18) into the emergency handle shaft location hole
provided (see page 19).
Turn the handle 90° clockwise or anti-clockwise (depending on the position to be reached) for each consecutive
change in position. I -> O -> II -> O -> I.
CAUTION
Ensure to verify the product position and
direction of rotation before effecting manual
operation.
Ensure to remove the handle from the product
before changing the selector switch back to AUT
position.
8.1.2. Padlocking
The ATyS t can be padlocked in the 0 position as standard whilst padlocking in positions I, O or II is available as a
factory fitted option.
To padlock the ATyS t first ensure that the ATyS t mode selector switch is on Manual then ensure that the emergency
manual operation handle is not inserted into the location hole. (Remove if inserted).
Pull the padlocking mechanism outwards to reveal the slot for inserting up to 3x dia. 4 - 8mm padlocks.
Padlock the device with approved quality padlocks of minimum diameter 4mm and maximum diameter of 8mm. A
maximum of 3x 8mm padlocks may be padlocked onto the ATyS t to padlocking mechanism.
3x mm
Ø 4-8
64B 63B
64B 63B
64B 63B
22VA comsumption: 22VA comsumption: Power comsumption: 22VA
72 71
72 71
72 71
• Fsheet
See instruction requency within set limits See instruction sheet See instruction sheet See instruction sheet
This will depend on the nominal frequency configured using auto conf together with the hysteresis set in position
74
74
74
To D10
To D10
To D20
To D20
64B 63B
64B 63B
64B 63B
VA Power comsumption: 22VA Power comsumption: 22VA Power comsumption: 22VA Power comsumption: 22VA
72 71
72 71
72 71
eet See instruction sheet See instruction sheet See instruction sheet See instruction sheet
8.2.3. Fixed inputs
8.2.3.1. Description
The ATyS t includes for 5 off inputs through a 6 pin connector installed on the
motorisation module. No additional power supply should be used on these
contacts as the inputs MUST be used with the common supply taken from
terminal 317.
The ATyS t also includes 4 additional inputs on the ATS Control Module. Again
no additional power supply should be used on these contacts as the inputs
MUST be used with the common supply taken from terminal 417. At least one
of the ATyS t aux power supplies (101 – 102 or 201 - 202) must be available
to activate inputs 312 to 317 and 413 to 417.
Depending on the wiring configuration there are two types of logic that may be applied to the ATyS t.
• Impulse logic or
• Contactor logic.
In remote control, the ATyS t inputs give priority to orders I and II over 0 therefore contactor logic can be implemented
by simply bridging terminals 316 and 317.
As standard, the ATyS t is equipped with four fixed outputs located on the
motorisation module.
ATyS t
8.2.4.3. ATyS t Product available output (motorisation)
in 63A – 64A
P
(Normally Open contact that is held closed when the motorisation is available).
This contact gives constant feedback about the product’s availability and it’s capacity to transfer from the main
supply to the alternative. The feedback given is relative to the motorisation module excluding the ATS controller that
may be monitored separately.
The ATyS t performs a self diagnostics test on the motorisation module at startup, when put from Manual -> Auto
and then every 5 minutes. This test ensures that the ATyS t is operational in terms of control inputs. Should one of
the tests fail, a second test is performed to reconfirm the error state.
Should the ATyS t motorisation module become unavailable, contact 63A – 64A are opened, the power/ready LED’s
74 72 71 207 208 209 210
are switched off, and the fault LED is activated. The fault LED will remain active for as long as sufficient power is
available and the fault condition is not reset. The fault is reset when the product is switched from64BAUT
To D10 63B
-> Manual ->
417 416 415 414 413
Auto mode.
For added security, “Product Availability” is informative and does not necessarily inhibit motor operation.
The above contacts may be used separately for precise monitoring of the state
See instruction sheet
of each module or wired in series to monitor the availability of the ATS and
motorisation modules as a complete unit.
ATyS p
8.3. Programming
The ATyS t is to be programmed after wiring verification tests through the front of the ATS Controller.
ATyS t
5 5
1 10 1 10
0 0
20 20
60 60
READY
A: 3 Ph E:
REMOTE CONTROL
B: 1 Ph F:
AUT PROG
OK
C: Neutral
D: Neutral
G: U 10% F 5%
H: U 20% F 10%
Note: Ensure that the ATyS t is in “Manual Mode” with the auxiliary and network supplies available.
POWER
XXXXXXXX
XXX
ATyS
Ø 4 ... 8mm
Attn: As a safety measure the READY LED will flash when any of the settings shown on the controller are different
to those that are saved. To return to the steady READY LED revert to the saved setting values or switch to manual
mode and save the displayed value by pressing the PROG OK button briefly.
(This is intended as a visual alarm in case one has changed the configuration settings but has not yet saved the new
values in the product)
READY
READY
A: 3A:Ph3 Ph E: E:
REMOTE
REMOTE
CONTROL
CONTROL
B: 1B:Ph1 Ph F: F:
AUT
AUT PROG
PROG
OK OK
C: Neutral
C: Neutral G: U
D: Neutral H: U
D: Neutral
G:10%
U 10%
H:20%
F 5%F 5%
U 20%
F 10%
F 10%
3: 4003:/ 230
400 / 230
3: 73: 4 7 4
4: 4154:/ 240
415 / 240
4: 84: 4 8 4
D Three Phase 3 wire Network (Without Neutral)
XXXXXXXX
XXXXXXXX
5: 4805:/ 277
480 / 277
5: 95: 5 9 5
6: 106: 510 5
6: 2086:/ 120
208 / 120
7: 117: 611 6
7: 2207:/ 127
220 / 127
8: 128: 612 6
8: 2308:/ 132
230 / 132
9: 139: 713 7
60 Hz
9: 2409:/ 138
240 / 138
10: 1410: 714 7
10: 38010:/ 220
380 / 220
11: 1511: 815 8
11: 40011:/ 230
400 / 230
12: 1612: 816 8
12: 41512:/ 240
415 / 240
13: 1813: 918 9
13: 48013:/ 277
480 / 277
14: 2014:1020 10 XXX XXX
ATYS t - 541 995 D - SOCOMEC EN 51
Motorised
Motorised
Changeover
Changeover
Switch
Switch
ROG
PROG 1600A
1600A
Ref : 95054160
Ref : 95054160
1 2 2 3 3
Dipswitch 3 E Load supply down time of 0 second (0DT = 0 sec)
E/F F Load supply down time of 2 seconds (0DT = 2 sec)
Dipswitch 4 G Threshold Delta U : 10% / Delta F : 5%
G/H H Threshold Delta U : 20% / Delta F : 10%
When a transfer is initiated after a loss of source, the 2s time delay is counted down from the loss of source.
POWER
8.3.3. Step 3: ATyS t Auto configuration
The ATyS t includes an “Auto Configuration feature to detect the mains voltage, phase rotation, neutral position and
frequency nominal values and save them in the ATS controller. ATyS t
5 5
Before configuring the nominal values ensure that the product is properly
1 wired,
10 1verified10and ready for commissioning.
0 0
It is imperative that the network supply (208 – 277Vac ± 20%) is available and
20 that the
20 wiring to the ATyS t voltage
sensing terminals 103 – 106 has been done. It is preferable to use the60ATyS sensing
60 kit that may be provided as an
accessory.
ATyS g
5 5 5 5
Ø 4 ... 8mm 1
READY 1 10 1 10
Auto Conf 1 0 0
10
A: 3 Ph E: 20 20
REMOTE CONTROL 10
13 14 B: 1 Ph 60 F: 60
AUT PROG C: Neutral
D: Neutral
G: U 10% F 5%
H: U 20% F 10%
OK
Un
• Ensure that the product is in manual TEST
mode.OFF LOAD
READY
TEST ON LOAD
• P
ress and hold the Red “PROG OK” button for >2s to measureA:the
3 Ph
supplyE: voltage, frequency, phase rotation
REMOTE CONTROL
F:
and neutral position. AUT
B: 1 Ph
AUT PROG
OK
C: Neutral
D: Neutral
G:
H:
Note: The READY LED will flash green (on and off) as soon as settings are measured and until these settings have
Un N° PP / PN
been saved by pressing the PROG OK button a second time momentarily. (Refer to STEP 4).
N°: ΔU ΔF %
1: 220 / 127 1: 5 3 POWER
2: 380 / 220 2: 6 3
50 Hz
3: 400 / 230 3: 7 4
4: 415 / 240 4: 8 4
XXXXXXXX
5: 480 / 277 5: 9 5
10 5
AUT
6:
6: 208 / 120 7: 11 6
7: 220 / 127 8: 12 6
8: 230 / 132 9: 13 7
60 Hz
3: 400 / 230 3: 7 4
1600A
52
4: 415 / 240
EN 4: 8 4 Ref : 95054160
ATYS t - 541 995 D - SOCOMEC
XXXXXXXX
2 480
5: Set /Dip
277 35:Set9Pot
5
6: 10 5
6: 208 / 120 7: 11 6
7: 220 / 127 8: 12 6
8: 230 / 132 9: 13 7
ATyS t
5 5
8.3.4. Step 4: Saving the configured values 0
1 10 1
0
10
20 20
To SAVE the recorded setting configuration press the PROG OK button
60 momentarily:
60 <60ms.
Note: The flashing READY LED goes off once the values are saved in the ATS controller.
READY
A: 3 Ph E:
REMOTE CONTROL
B: 1 Ph F:
AUT PROG
OK
C: Neutral
D: Neutral
G: U 10% F 5%
H: U 20% F 10%
5: 480 / 277 5: 9 5
6: 10 5
6: 208 / 120 7: 11 6
7: 220 / 127 8: 12 6 ATyS t
8: 230 / 132 9: 13 7 5 5
9: 240 / 138 10: 14 7
0: 380 / 220 11: 15 8 1 10 1 10
1: 400 / 230 0 0
12: 16 8 20 20
2: 415 / 240 13: 18 9
3: 480 / 277 14: 20 10 XXX 60 60
y!
ATyS
AUT PROG
OK
C: Neutral
D: Neutral
G: U 10% F 5%
H: U 20% F 10%
Press 5 Press 4
60ms 2s
Ø 4 ... 8mm
PROG PROG
Depending on the
AUT state of the ATyS t the ATS automation may change the switch
WARNING position as soon as the mode selector is switched to AUT. This is a normal operation.
Un N° PP / PN N°: ΔU ΔF %
1: 220 / 127 1: 5 3 POWER
2: 380 / 220 2: 6 3
50 Hz
3: 400 / 230 3: 7 4
4: 415 / 240 4: 8 4
XXXXXXXX
5: 480 / 277 5: 9 5
6: 10 5
6: 208 / 120 7: 11 6
7: 220 / 127 8: 12 6
8: 230 / 132 9: 13 7
60 Hz
Ready !
ATyS
Press 5 Press 4
AUT 60ms 2s
Ø 4 ... 8mm
PROG PROG
125 to 630 A
Thermal current Ith to 40°C 125 A 160 A 200 A 250 A 315 A 400 A 500 A 630 A
Rated insulation voltage Ui (V) (power circuit) 800 800 800 1000 1000 1000 1000 1000
Rated impulse withstand voltage Uimp (kV) (power circuit) 8 8 8 12 12 12 12 12
Rated insulation voltage Ui (V) (control circuit) 300 300 300 300 300 300 300 300
Rated impulse withstand voltage Uimp (kV) (control circuit) 4 4 4 4 4 4 4 4
Rated operational currents Ie (A) according to IEC 60947-3
Rated voltage Utilisation category A/B A/B A/B A/B A/B A/B A/B A/B
415 VAC AC-21 A / AC-21 B 125/125 160/160 200/200 250/250 315/315 400/400 500/500 630/630
415 VAC AC-22 A / AC-22 B 125/125 160/160 200/200 250/250 315/315 400/400 500/500 630/630
415 VAC AC-23 A / AC-23 B 125/125 160/160 200/200 200/200 315/315 400/400 500/500 500/630
500 VAC AC-21 A / AC-21 B 125/125 160/160 200/200 250/250 315/315 400/400 500/500 630/630
500 VAC AC-22 A / AC-22 B 125/125 160/160 200/200 200/250 200/315 200/400 500/500 500/500
500 VAC AC-23 A / AC-23 B 80/80 80/80 80/80 200/200 200/200 200/200 400/400 400/400
690 VAC AC-21 A / AC-21 B 125/125 160/160 200/200 200/200 200/200 200/200 500/500 500/500
690 VAC AC-22 A / AC-22 B 125/125 125/125 125/125 160/160 160/160 160/160 400/400 400/400
690 VAC AC-23 A / AC-23 B 63/80 63/80 63/80 125/125 125/125 125/125 400/400 400/400
220 VDC DC-21 A / DC-21 B 125/125 160/160 200/200 250/250 250/250 250/250 500/500 630/630
220 VDC DC-22 A / DC-22 B 125/125 160/160 200/200 250/250 250/250 250/250 500/500 630/630
220 VDC DC-23 A / DC-23 B 125/125 125/125 125/125 200/200 200/200 200/200 500/500 630/630
440 VDC (1) DC-21 A / DC-21 B 125/125 125/125 125/125 200/200 200/200 200/200 500/500 630/630
440 VDC (1) DC-22 A / DC-22 B 125/125 125/125 125/125 200/200 200/200 200/200 500/500 630/630
440 VDC (1) DC-23 A / DC-23 B 125/125 125/125 125/125 200/200 200/200 200/200 500/500 630/630
Rated operational currents Ie (A) according to IEC 60947-6-1
Rated voltage Utilisation category
415 VAC AC-31 B 125 160 200 250 315 400 500 630
415 VAC AC-32 B 200 315 400 500 500
415 VAC AC-33 B 200 200 200 400 400
Current rated as conditional short-circuit with fuse gG DIN, according to IEC 60947-3
Prospective fuse protected short-circuit withstand at 415 VAC(6) 100 100 50 50 50 50 50 50
Prospective fuse protected short-circuit withstand at 690 VAC(kA rms) / / / 50 50 50 50 50
Associated fuse rating (A) 125 160 200 250 315 400 500 630
Current rated as conditional short-circuit according to IEC 60947-3
Current rated as short-time withstand Icw 0,3s, 415 VAC (kA rms) 12 12 12 15 15 15 17 17
Current rated as short-time withstand Icw 0,3s, 690 VAC (kA rms) / / / 15 15 15 17 17
Current rated as short-time withstand Icw 1s, 415 VAC (kA rms) 7 7 7 8 8 8 10 10
Current rated as short-time withstand Icw 1s, 690 VAC (kA rms) / / / 8 8 8 10 10
Power rated as closing short-circuit Icm at 415 VAC (peak kA) 11.9 11.9 11.9 22 22 22 17 17
Current rated as conditional short-circuit according to IEC 60947-6-1
Current rated as short-time withstand Icw 30 ms (kA rms), 415 VAC 10 10 10 10 10 10 / /
Current rated as short-time withstand Icw 60 ms (kA rms), 415 VAC / / / / / / 10 12.6
Power rated as closing short-circuit Icm at 415 VAC (peak kA) 17 17 17 17 17 17 17 25
Connection
Minimum Cu cable cross-section as per IEC 60947-1 (mm²) 35 35 50 95 120 185 2 x 95 2 x 120
Recommended Cu busbar cross-section (mm²) 2 x 32 x 5 2 x 40 x 5
Maximum Cu cable cross-section (mm²) 50 95 120 150 240 240 2 x 185 2 x 300
Maximum Cu busbar width (mm) 25 25 25 32 32 32 50 50
Min./max. tightening torque (Nm) 9/13 9/13 9/13 20/26 20/26 20/26 40/45 40/45
Switching time (rated voltage, after receiving command)
Time of transfer I-II or II-I (s) 0.85 0.85 0.85 0.9 0.9 0.9 0.95 0.95
I-0 or II-0 (s) 0.55 0.55 0.55 0.5 0.5 0.5 0.55 0.55
Time of contact transfer ("black-out" I-II) minimum (s) 0.3 0.3 0.3 0.4 0.4 0.4 0.4 0.4
Power supply
Min./max. power (VAC) 166/332 166/332 166/332 166/332 166/332 166/332 166/332 166/332
Control supply power demand
Demand/rated power (VA) - ATyS r, ATyS d 184/92 184/92 184/92 276/115 276/115 276/115 276/150 276/150
Demand/rated power (VA) - ATyS t, g , p 206/114 206/114 206/114 298/137 298/137 298/137 298/172 298/172
Mechanical specifications
Durability (number of operating cycles) 10,000 10,000 10,000 8,000 8,000 8,000 5,000 5,000
Weight ATyS r 3 P / 4 P (kg) 5.7/ 6.9 5.7/ 6.9 5.7/ 6.9 6.6/ 7.4 6.7/ 7.8 6.7/ 7.8 11.4/ 13.3 11.9/ 14.0
Weight ATyS d 3 P / 4 P (kg) 6.3/ 7.5 6.3/ 7.5 6.3/ 7.5 7.2/ 8.0 7.3/ 8.4 7.3/ 8.4 12.0/ 13.9 12.5/ 14.6
Weight ATyS t, g, p 3 P / 4 P (kg) 6.8/ 8.0 6.8/ 8.0 6.8/ 8.0 7.7/ 8.5 7.8/ 8.9 7.8/ 8.9 12.5/ 14.4 13.0/ 15.1
(1) 3-pole device with 2 „+“ poles in series and 1 „-“ pole. 4-pole device with 2 poles in series by polarity
Note: Maintenance should be planned carefully and carried out by qualified and authorised personnel. Consideration
of the critical level and application where the product is installed should form an essential and integral part of the
maintenance plan. Good engineering practice is imperative whilst all necessary precautions must be taken to ensure
that the intervention (whether directly or indirectly) remains safe in all aspects.
It is not possible to • erify that the front selector switch position is on the Manual position.
V
manually operate the • Make sure that the product is not padlocked
switch
• Verify the rotation direction of the handle
• Apply a sufficient progressive action in the direction as indicated on the handle
Electrical operation • V erify the selected control logic wiring (impulse or contactor)
does not correspond
to external order I,O,II • Verify the connector connections.
acces_206_a_2_cat
125 … 200 B3 3P top / bottom / front (I) / rear (II) 2694 3014(1)(2)
125 … 200 B3 4P top / bottom / front (I) / rear (II) 2694 4014(1)(2)
250 … 400 B4 3P top / bottom / front (I) / rear (II) 2694 3021(1)(2)
250 … 400 B4 4P top / bottom / front (I) / rear (II) 2694 4021(1)(2)
500 … 630 B5 3P top / bottom / front (I) / rear (II) 2694 3051(1)(2)
500 … 630 B5 4P top / bottom / front (I) / rear (II) 2694 4051(1)(2)
(1) To shroud front switch top and bottom 2 references required.
(2) To fully shroud front, rear, top and bottom 4 references required.
acces_207_a_2_cat
125 … 200 B3 3P top / bottom 1509 3012
125 … 200 B3 4P top / bottom 1509 4012
250 … 400 B4 3P top / bottom 1509 3025
250 … 400 B4 4P top / bottom 1509 4025
500 … 630 B5 3P top / bottom 1509 3063
500 … 630 B5 4P top / bottom 1509 4063
800 … 1250 B6 3P top / bottom 1509 3080
800 … 1250 B6 4P top / bottom 1509 4080
1600 B7 3P top / bottom 1509 3160
1600 B7 4P top / bottom 1509 4160
2000 … 3200 B8 3P top / bottom 1509 3200
2000 … 3200 B8 4P top / bottom 1509 4200
acces_459_a_1_x_cat
(Fig. 3). accessories are available in the user guide
downloadable from www.socomec.com.
The numbers given in the table below refer to the contact connection.
2000 – 2500 A 3200 A B
Part Fig. 1 Fig. 2 Fig. 3 Fig. 1 Fig. 2 Fig. 3
number Connection Outage bridge I Connection Outage bridge I
Flat Onsite and II Flat Onsite and II Fig. 2 C
Connection
2619 1200 1 1 2(2) included included included
part A
Screw kit 35 mm
2699 1201 1(1) 2(2) 1(1) 2(2)
part B
Screw kit 45 mm A
acces_460_a_1_x_cat
2699 1200 1(1) 1(1)
part B
T + screw kit
2629 1200 1 1 1 1
part C
Bracket + screw kit
2639 1200 1 1
part D
Bar + screw kit D
4109 0320 1 1
part E
acces_461_a_1_x_cat
For example, for a 4 P 2500 A with onsite upstream connection (Fig. 2) and downstream
bridging (Fig. 3), please order
16 x 2619 1200 12 x 2629 1200
8 x 2699 1201 4 x 4109 0320
8 x 2639 1200
atys_606_a_1_cat
Routing of the conductors is controlled,
which means that no specific protective
device is necessary for these connections.
atys_603_a_2_cat
1250 B6 1559 3120
1600 B7 1559 3160
2000 … 3200 B8 1559 3200
acces_397_a
Operating current Ie (A)
Nominal 125 to 630 A
Frame size 250 VAC 400 VAC 24 VDC 48 VDC
Rating (A) current (A)
AC-13 AC-13 DC-13 DC-13
125 … 3200 B3 … B8 16 12 8 14 6
acces_396_a
2000 … 3200 B8 - included
800 to 1600 A
(1) Up to 2 auxiliary contacts can be ordered.
atys_009_b_2_cat
per spacer.
Rating (A) Frame size Description of accessories Reference
125 … 630 B3 … B5 1 set of 2 spacers 1509 0001
atys_564_d_1_cat
atys_565_d_1_cat
Interfaces are powered from the ATyS transfer panel.
switch via the RJ45 connection cable. Protection degree: IP21.
Maximum cable length: 3 m. Door mounting
D10 - for ATyS d, t and g 2 holes Ø 22.5. ATyS transfer switch
To display source availability and position connection via RJ45 cable, not isolated.
indication on the front panel of an Cable available as an accessory. Interfaces are powered from the ATyS Drillings
enclosure. Protection degree: IP21. 96 x 96 Ø 22.5
atys_161_a_1_x_cat
36
D10 9599 2010
atys_597_a_1_cat
40
D20 9599 2020
20
= =
acces_209_a_2_cat
(type D10 or D20) and an ATyS transfer
switch (ATyS d, t, g or p).
Characteristics
For ATyS d, t, g and p
Type Length Reference
RJ45 cable 3m 1599 2009
atys_870_a
125 … 3200 B3 … B8 9599 0000
atys_621_c_1_gb_cat
ATyS d 9539 2001
ATyS t 9549 2001
ATyS g 9559 2001
ATyS p 9579 2001
Rating References
125 ... 200 A 9509 5020
250 ... 400 A 9509 5040
500 ... 630 A 9509 5063
atys_871_a
800 ... 1250 A 9509 5120
1600 A 9509 5160
2000 ... 3200 A 9509 5320
97 2 3 4 0 1 0
Product Type Ctrl Voltage N° of poles Rating
97 - UL : I - O - II 2 - ATYS 3 - 230VAC 2-2 Pole 010 - 100A
(208-277VAC 3-3 Pole 020 - 200A
Nominal) 4-4 Pole 026 - 260A
040 - 400A
Note: only valid for UL 1008 products
95 2 3 4 063
Product Type Ctrl Voltage N° of poles Rating
95 - IEC: I - O - II 2 - ATyS r 3 - 230VAC 3-3 Pole 012 - 125A
3 - ATyS d (166-332VAC) 4-4 Pole 016 - 160A
4 - ATyS t 020 - 200A
5 - ATyS g 025 - 250A
7 - ATyS p 031 - 315A
040 - 400A
050 - 500A
053 - 630A
080 - 800A
100 - 1000A
120 - 1250A
180 - 1600A
200 - 2000A
250 - 2500A
320 - 3200A
Ratings lth @
40 °C