The ability to access a SQL database in real time from WinCC runtime can be
beneficial for manufacturing processes. It can be used to determine what
should be run on a line, log parameters of a process, or provide tracking of
products in real time. This tutorial will go through some of the steps necessary
to access data from an SQL database with WinCC advanced.

An important note is that SQL access is not allowed through scripting from a
Siemens Comfort Panel. One way to work around this is to have WinCC
Advanced runtime running somewhere on your network to
handle communication with the database. You can then access the database
from WinCC Advanced, pass its values to the PLC, and then access them on the
PLC from the comfort panel.

Database Settings
I will not go through the entire setup of an SQL database here. However, the
user must update several essential settings for access from WinCC.

In SQL Server Management Studio


1. Open SQL Server Management Studio and connect to the server where the
database you wish to access from WinCC resides. 

Right-click that server and open its properties. In the Security tab choose SQL
Server and Windows Authentication Mode for Server Authentication. This
allows access to the server with a username and password instead of a standard
windows login.
 

2. In the connection explorer, open the Security folder and right click


Logins. Then choose New Login.

This step adds a user to this server.

3. Add a user, choose SQL Server Authentication, and set the default database
to the database you wish to access from WinCC.
In SQL Server Configuration Manager
1. Open SQL Server Configuration Manager. If you are having trouble finding it,
try browsing to the locations seen on this site. Under SQL Server Network
Configuration then Protocols for SQLEXPRESS, enable TCP/IP.

2. Under SQL Server Services, change the start mode of SQL Server Browser to
Automatic and ensure it’s running.

3. Right click on SQL Server and SQL Server Browser and restart them.

In Windows Firewall with Advanced


Features
1. Open Windows Firewall with Advanced Features. Choose Inbound
Rules from the bar on the left, then New Rule… on the right.
2. Make the rule with the following features:

Rule type: Port Protocol and Ports: UPD type, port number 1434 Action: Allow
the connection Profile: Choose all

Name: SQLExpressBrowser

3. Add another incoming rule. This time choose a custom type.

Rule Type: Custom


Program: Select Customize next to services and apply the rule to the service
SQL Server (SQLEXPRESS).
Protocol and Ports: Protocol type Any Scope: Any IP address local or remote
Action: Allow the connection Profile: Apply to all

Name: SQL Server Database Engine Service

Script Setup
Now that we have the settings for the database nailed down it’s time to get into
the fun part, the actual scripting!

Below, I will go through the lines of my code and explain what’s happening at
each part. In this example, I’m calling a stored procedure from the database
that takes inputs of integers and strings from the PLC and outputs to an array
of UDTs on the PLC.

'Keep running script if error occurs


Dim i, index, test, row, iType, sFirstInput, iSecondInput, offset
Dim connection, recordset, record, connectionstring, query

Line 3 ensures that if the script encounters an error, it keeps running. This line
allows us to record the error we’re getting and set status tags for the script.
Then declare all the variables being used and set the continue variable to true.
This variable will do error handling.

If Not SmartTags( "bCallScript" ) Then

Now, trigger the script on the PLC tag bCallScript. This tag has a continuous
cyclic acquisition and calls  ExampleScript on a value change. Lines 12-14
ensure that we only run the SQL logic on a positive value change of
bCallScript. 

'Create connection string and database object


connectionstring = "Provider=SQLOLEDB.1;Persist Security
Info=True;" &_
"User
ID=ExampleUser;Password=ExamplePassword;" &_
"Initial Catalog=ExampleDatabase;" &_
"Data Source=192.168.0.1\SQLEXPRESS;"
Set connection = CreateObject( "ADODB.Connection" )
'Open connection to database
connection.Open connectionstring

Make a connection string for the database using the password and User
ID created earlier. The data source is the IP address of the computer that hosts
the database.

Line 24 creates a database object and line 27 tries to connect to the database.
The connection string will vary based on the type of database you’re using, the
username and ID created, and other factors.

SmartTags( "ErrorTag" ) = "Opening Connection: " &


Err.Description

Put in the first error handling block. If an error has occurred trying to connect
to the database, write Opening Connection: actual text of error to the tag
dbSQL_sError.

Then, close the connection to the database and set the continue variable to
false. This is useful in troubleshooting, as you can check the tag dbSQL_sError
to help diagnose connection problems.

'Convert inputs to strings


sFirstInput = CStr (SmartTags( "dbPLC_sFirstInput" ))
iSecondInput = Cstr(SmartTags( "dbPLC_iSecondInput" ))
query = "EXECUTE dbo.ExampleStoredProcedure" & sFirstInput &
"," & iSecondInput
'Execcute query and create recordset object
Set recordset = connection.Execute(query)
If Err.Number <> 0 Then SmartTags( "ErrorTag" ) = "Database
query: " & Err.Description

Now that the database connection is open, run the first query. First, check
whether the continue variable is true. There is no use trying to run this logic if
we had an error connecting to the database earlier.

For this example, I am running a query that calls a stored procedure in our
database dbo.ExampleStoredProcedure. This procedure takes two inputs. The
first is a string, the second is an integer and returns a table of results.

I take two PLC tags, convert/ensure they are strings, and combine them with
another string to create the SQL query EXECUTE dbo.ExampleStoreProcedure
sFirstInput, iSecondInput that is passed to the database.

The query can be any valid SQL query. However, I found that it’s easier to
create stored procedures in the database than to write long queries in the VBA
editor in TIA Portal. This makes the scripting in portal simpler and easier to
troubleshoot.

We store the result of the query as the variable recordset, which is a recordset


object.  This makes it easy to manipulate the data later.

Once again, there is an error routine here that sets the continue variable to


false, records the error text, and closes the database connections in the case of
an error.

'Make sure we're at the start of the record


'Determine how many rows to offset
offset = (SmartTags( "dbPLC_iPageNumber" )-1)*10
If Err.Number <> 0 Then SmartTags( "ErrorTag" ) = "Page
offset: " & Err.Description
In this example, the goal was to display ten rows of the table produced by our
stored procedure on an HMI screen. 

This code is only run if our continue flag is true. The first line does the
MoveFirst command on the recordset object we created earlier. Think of the
recordset object like a big table with one row highlighted. The MoveFirst
command ensures highlighting of the first row. Then calculate how many rows
we need to offset to display entries 1-10 on page 1, 11-20 on page 2, 21-30 on
page 3, etc. 

This offset will always be a 0 or some multiple of 10.  Use the


recordset.Move(offset) command next to move our highlighted row down
however many rows required. The move command moves down the table for
positive numbers and up the table for negative numbers. 

For example, if we move to row 1 using the MoveFirst command, then offset 10
with the move command, we end up highlighting row 11. This would start the
second page of entries.

There is now an error routine again. This command catches errors such as the
stored procedure returning an empty table or trying to move to a second page
when there are less than ten entries.

If Not recordset.EOF Then


SmartTags( "dbPLC_Data{" & CStr (i)& "}.iOutputOne" ) =
CInt (recordset.Fields( "OutputOne" ).Value)
SmartTags( "dbPLC_Data{" & CStr (i)& "}.sOutputTwo" ) =
CInt (recordset.Fields( "OutputTwo" ).Value)
SmartTags( "dbPLC_Data{" & CStr (i)& "}.bExists" ) =
True
SmartTags( "dbPLC_Data{" & CStr (i)& "}.bExists" ) =
False
If Err.Number <> 0 Then SmartTags( "ErrorTag" ) =
"Retrieve Data: " & Err.Description

This block moves data into an array of UDTs on the PLC. The UDT has
three elements: iOutputOne, sOutputTwo, and bExists. The array has
ten elements and is called dbSQL_Data. Loop from 0 to 9 to fill each element of
the array.

Within the for loop, there is an if statement that checks recordset.EOF. This is


a property of the recordset object which tells whether you have moved past the
last row of the table. In this case, use it to ensure that we don’t attempt to read
data from an empty row.

If recordset.EOF is false, then read data from the recordset object using
the .Field and .Value properties. Each field corresponds to the name of a
column from the database table returned by the stored procedure. The .Value
property returns the value in that column from the row that is currently
selected.

Wrap the recordset.Fields.().Value commands in Cstr and Cint to ensure the


correct data types are in the PLC. We write to the dbSQL_bExists bit if we are
not at the end of the file, as this means we successfully populated this entry in
the array with information. This is useful for deciding whether or not to display
info on a screen or use it in the PLC.

After writing the data to the PLC, use the .MoveNext method to move down
one row in the data table.

If at the end of the file (recordset.EOF  = true), do not read any data, and set
the dbSQL_bExists bit to false.

Finish with another error routine for this part of the code.

SmartTags( "dbPLC_bErrorExists" ) = True


SmartTags( "dbPLC_Data{" & CStr (i)& "}.bExists" ) = False
SmartTags( "dbPLC_bScriptComplete" ) = True
SmartTags( "dbPLC_bCallSCript" ) = False

This is the end of the script. At this point, if the continue flag is false, write to a
dbSQL_ErrorExists status bit on the PLC. Furthermore, set the
“bSQL_bExists bit to false for all Data array elements to make it clear
something went wrong while trying to access the database.

Line 122 sets a PLC tag indicating that the script has completed running to
True, signaling to the PLC it can continue with other logic. Reset the
dbSQL¬_CallScript tag here so that the script can be called again.

Conclusion
This is a relatively simple implementation of SQL access, but it shows some of
the key features and methods you need to read data successfully to your PLC. I
hope it can be of use to you in future projects.

Learn more about DMC's WinCC programming expertise.