Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
State Key Laboratory on Power System, Dept of Electrical Engineering, Tsinghua University, Beijing 100084, China;
Abstract: Identification of lighting stroke and fault is a key technology for travelling wave based protection because
stroke maybe cause maloperation of protection. This paper analyzed the characters of current travelling waves induced by
lightning stroke or fault in frequency domain and time domain. Energy coefficient is proposed to discriminate the lighting
without fault from normal fault, and a waveform characteristic is proposed to discriminate a lightning stoke without fault and
lightning stroke with fault. A novel scheme based on energy ratio and waveform characteristic is put forward to resolve the
impact of travelling waves induced by lightning stroke. The simulation results from Alternative Transient Program (ATP)
validate the feasibility and reliability of this scheme.
Keywords:lightning stroke, EHV transmission line, travelling wave based protection, analysis of frequency spectrum
110
----��
5
u
5 1�------T2----
00 10 20Time(us)30 40 50
�ia
_10 L-------�---L--�L---�
Figure 1 lEe normal lightning current o 5 10 15 20
Time(ms)
Where T 1 is 1. 21ls and T2 is 5OilS. This paper will use the Figure 3 (a) Fault current travelling waves of 20ms
IEC normal lightning waveform as the research object. 5
When lightning stroke happens, the lightning current
waves maybe result in a fault on the transmission line � 0
..
I'
sometimes. The travelling wave based protection should c
Q)
...
r V
give a trip signal immediately. However, sometimes the 5 -5
lightning current waves is only a disturbance wave, the (.) �ia
travelling wave based protection should not maloperation.
-10
So travelling wave protection must identify three situations: o 1.5 2 2.5 3
1) lightning stoke with a fault Time(ms)
2) lightning stoke without a fault Figure 3 (b) Fault current travelling waves oOms
3) normal fault Figure 3 Fault current travelling waves induced by lightning stroke
As shown in Figure 2, a 750kV transmission system is
adopted as research object.
L M N S
Line 2 Line 1
@1 Line 3 I�
I, i �
Line 5
Source 1 Source 2
F, 750kV
-
2315
2011The International Conference on Advanced Power System Automation and Protection
2
� When 10 is not significantly bigger than I], the
characteristic of frequency spectrum is similar to normal
1.5 2.5 3
fault. And the energy coefficient A is more than 25. Figure 7
Time(ms)
is the modal current travelling waves ia in the situation of a
Figure 5(b) Fault current travelling waves of 3ms
lightning stroke with a fault in phase A on line 1. Figure 8 is
Figure 5 Fault current travelling waves for normal fault corresponding frequency spectrum. In addition, 10 is 10kA,
II is 3. 5kA. Energy coefficient A is more than 25.
5 ,---�-.--�-----.
� 0
c:
-
CI)
"-
"-
� -5
U +-ia
o
0 2000 4000 6000 8000 10000 -10
Frequency(Hz) 0 0.5 tl 1 1.5 2 2.5 3
Time(ms)
Figure 6 Frequency spectrum of i.
Figure 7 Fault current travelling waves
Figure 6 is the Frequency spectrum of fault current
travelling wave ia with 2ms data window. It can be got that
the magnitude of frequency spectrum from 0 Hz to 10 kHz
CI)
"0
is not in the same order. From Figure 6 and Figure 4, it is :::l
obvious that characteristics of frequency spectrum can be � 0.5
Cl
used to discriminate lightning without fault from normal nI
:::i:
fault. Define Eo as the frequency spectrum of direct current
component of fault current travelling wave. The frequency o I�., m.��..u...� ��
o
______
band (}-10kHz is divided into 20 region, and every region is 2000 4000 6000 8000 10000
Frequency(Hz)
500Hz. El, E2, . . . ,E20 is represents the fault current
Figure 8 Frequency spectrum of fault current travelling waves
travelling waves energy in frequency of 500Hz,1000Hz, . . . ,
10000Hz respectively. And defme a energy coefficient However, When 10 is significantly bigger than I], the
A , where characteristic of frequency spectrum of fault current is
similar to lightning without fault. And the energy coefficient
max(EO' Ep- , E20 )
=
A A is no more than 5. Figure 9 is the modal current travelling
. .
(2)
min(Eo' E1, , E20 )
• • •
waves ia in the situation of a lightning stroke with a fault in
phase A on line 1. Figure lOis corresponding frequency
As to lightning stroke without fault, energy coefficient A
spectrum. In addition, 10 is 30kA, II is lkA. The Energy
usually is less than 5. However, energy coefficient A is
coefficient A is less than 5. So Energy coefficient A cannot
usually more than 25 for normal fault. Energy coefficient A
can be utilized to discriminate lightning without fault from discriminate lightning stroke with fault and lightning stroke
2316
2011The International Conference on Advanced Power System Automation and Protection
-5
�
1
:::l
-10
() -15
Wavelet transform and maxima modulus
-2 0 of wavelet MMI.,MMlp,MMl
r
-----'
-2 5 '-----
-- -,- .� --!t---�----,- .� ----2�---,- 2 .� -- 3
0 05 1 15 5 Analysis of frequency spectrum of max
Time(ms) modal current travelling wave ia"" mO(I,,/
In order to discriminate lightning stroke with fault and 1) Calculate the fault current travelling waves
lightning stroke without fault effectively, Characteristics of =
l1imCn) imCn) - 2imCn - N) + imCn - 2N) (4)
fault current in time domain will be discussed in this section.
Where im(n) is the sample current, N is number of
Figure 3 (b) is modal fault current travelling waves ia in the sample point in one power frequency period. Subscript m
situation of lightning stroke without fault. Define N I is the represents phase a, b and c respectively.
rii:al ±[ O][l1l1�iab]
than zero. Nz is the number of sample point which absolute Karenbauer transformation is utilized in the paper to
magnitude is equal zero. In Figure 3(b), it is the fault de-couple a three-phase current to three line-modal current.
2317
2011The International Conference on Advanced Power System Automation and Protection
spectrum of the modal fault current traveling wave. A 3.19 266 758 Result B
M
n=1
C 2.90 286 738 Result B
Where k represents the frequency point, N is the discrete
A 2.90 266 758 Result B
data point in 2ms data window. Sample rate is 500kHz and
N is 1000 in this paper. n represents discrete sample point of 2.5/50l-ls B 21.3 851 173 Result A
current. Energy coefficient A can be calculated according to C 2.89 306 718 Result B
equation (2). MeanwhileNI andNz is calculated according A 4.38 216 808 Result B
to equation (7).
10/I00I-lS B 28.13 891 133 Result A
i(n)-t53 > 0 (7)
C 4.48 366 658 Result B
Where 03 is the setting of modal fault current which is
utilized to judge whether the current i(n) is zero. 03 should Table 2 Simulations results of normal fault
take into account the error of measure device and Fault type 6 Nl N2 SILS
calculation.
Rg=300n,$a= - 80°,ABG 91.5 900 124 Result A
5) Procedure of logic judgment
Rg=O.1n,$a= - 80°,AG 63.7 890 134 Result A
A) If energy coefficient A smaller than OJ, it is judged as
lighting stroke without fault. Algorithm quit the fault Rg=O.1n ,$a= - 80°,ABC 62.00 926 98 Result A
meaning of Result A and Result B is showed in Figure 11. Developments in Power System Protection, Eighth lEE International
Conference on, Amsterdam, Netherlands, April 5-8,2004 , pp: 80 - 83
Table 2 is the simulation results of normal fault. From the 3 Ren Jin-feng, Duan Jian-dong,Zhang Bao-hui, et al. Identification of
lightning disturbance in ultra-high-speed transmission line protection.
simulation results, it can be found that SILS can
Transmission and Distribution Conference and Exhibition: Asia and
discriminate lightning stroke without fault from lightning Pacific IEEE/PES, Dalian,China, August 15-17,2005, pp:I - 5
4 Si Da-jun, Shu Hong-chun, Chen Xue-yun. Study on characteristics and
stoke with fault and normal fault effectively. identification of transient of transmission lines caused by lighting stroke.
Table 1 Simulations results of lightning stoke Proceedings of the CSEE, 2005, 25(7):64-69
5 Hegde, v.; Kumar, U.. Classification of strokes and identification of
. Lightning stroke location from the measured tower base currents of LPS to Indian
L·19htmng type Nl N2 SILS
stroke type
2318
2011The International Conference on Advanced Power System Automation and Protection
satellite launch pad-I. Power Engineering Conference, IPEC, Singapore, 7 Dong Xinzhou, Kong Wei, Cui Tao. Fault classification and
DEC 3-6, 2007 , pp: 1161 - 1166 faulted-phase selection based on the initial current traveling wave. Power
6 Guibin Zou, Houlei Gao, Ming Xu, et al. Identification of lightning Delivery, IEEE Transactions on, 2008,23(3):1-8
stroke and fault in the transient component based protection. Asia-Pacific 8 Xinzhou Dong, Yaozhong Ge, Jiali He. Surge impedance relay. Power
Power and Energy Engineering Conference, Wuhan, China. March Delivery, IEEE Transactions on, 2005,20(2):1247-1256.
28-30,2009 , pp:l - 5
2319