Air Cooled Screw Chiller Performance

Datasheet
Net Cooling Nominal Power
Unit Tag Qty Model No Refrigerant Type
Capacity (ton.R) Volts-Ph-Hz
CH-1 1 YVAA0183ABF40BAVSXX 172.0 380-3-60.0 R134a

PIN:
YVAA0183AB F40BAVSXXX SAXLXXXX60 44ROSXXS18 7X1SXGA2BN XFXX1XXXXX XXXEXX
....5...10 ....5...20 ....5...30 ....5...40 ....5...50 ....5...60 ....5...70 ....5...80 ....5...90

Evaporator Data Evaporator Data (Cont.) Performance Data


EWT (°F) 54.00 Fluid Volume (USGAL) 48.08 EER (Btu/W·h) 11.92
LWT (°F) 44.00 Min. Flow Rate (USGPM) 206.1 NPLV.IP (Btu/W·h) 16.23
Design Flow Rate (USGPM) 411.7 Max. Flow Rate (USGPM) 792.5
Total Press. Drop (ft H2O) 11.5 Condenser Data Physical Data
Fluid Water Ambient Temp. Design (°F) 86.0 Rigging Wt. (lb) 12019
Fouling Factor (h.ft².F/Btu) 0.000100 Altitude (ft) 0.000 Operating Wt. (lb) 12460
VSD Screw - Semi
Number Passes 2 Compressor Type Refrigerant Charge (lb) 330.7
Hermetic

Electrical Data
Circuit 1 2 3 4
Compressor kW 88.7 67.1
Compressor RLA 176 141
Fan QTY/FLA (each) 6 / 4.1 4 / 4.1

Single Point
Min. Circuit Ampacity 407
Min. Fuse / CB Rating (A) 500
Max. Fuse / CB Rating (A) 500
Unit Short Circuit Withstand (STD) 30 kA [kA]
Wires Per Phase 2
Wire Range (Lug Size) #2 - 600 kcmil
Displacement Power Factor 0.95 Operating Condition Electrical Data
Control kVA 2 Compressor kW 155.8
Total kW 173.2

Notes:

Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Using Vapor
Compression Cycle Certification Program, which is based on AHRI Standard 550/590 (I-P) and
AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at
www.ahridirectory.org. Auxiliary components included in total KW - Oil heaters, Chiller controls.
Auxiliary power is already included in the compressor and fan power

Min DSD (Factory Purpose/Use only): 80 psig


Use Copper Conductors only
Displacement Power Factor refers to compressor only. Unit Power Factor depends on fan option
selected. Calculated value is available by request.

Minimum and maximum evaporator flow information are for full load ratings with water only. Contact Johnson Controls for application limits for gycol and
variable primary flow.
Evaporator Passes: 2, Condenser Type: M, Fan Type: F
Actuated suction service valves ARE NOT selected
Exclusion of actuated suction service valves will require incorporation of additional freeze protection including use of glycol, pump control or draining the
evaporator.

Part Load Rating Data


Load % Ambient (°F) Capacity (ton.R) Total kW Unit Efficiency
MLP Effective Date:4/15/2018 NewProject
Generated on 2018-06-08 E.18.2.1.9706-D.61.0045(REV. v8_06.idd) Datasheet Spec
Unit Folder: CH-1 Software Version: YW18.02b Page_1_of_2
Air Cooled Screw Chiller Performance
Datasheet
100 86.0 172.0 173.2 11.92
75 74.4 129.0 104.7 14.79
50 62.9 86.00 60.62 17.02
25 55.0 43.00 27.61 18.69

Sound Power Levels (In Accordance with AHRI 370)


Ambient 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
Load % LWA
(°F) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB)
100 86.0 96 96 97 98 96 88 84 80 100
75 74.4 96 96 97 96 92 87 83 79 98
50 62.9 94 95 95 95 91 86 82 78 96
25 55.0 91 91 92 91 88 82 78 73 93

Note: Unit is equipped with Low Sound Fans.

Performance at AHRI Conditions


Evaporator Data Condenser Data Performance Data
EWT (°F) 54.00 Ambient Temp. (°F) 95.0 EER (Btu/W·h) 10.41
LWT (°F) 44.00 Altitude (ft) 0.000 IPLV.IP (Btu/W·h) 15.53
Net Cooling Capacity
Flow Rate (USGPM) 411.7 172.0
(ton.R)
Pressure Drop (ft H2O) 11.5
Fluid Water
Fouling Factor (h.ft².F/Btu) 0.000100
Fluid Volume (USGAL) 48.08

Note: Unit rated at design condition capacity.

MLP Effective Date:4/15/2018 NewProject


Generated on 2018-06-08 E.18.2.1.9706-D.61.0045(REV. v8_06.idd) Datasheet Spec
Unit Folder: CH-1 Software Version: YW18.02b Page_2_of_2