Sei sulla pagina 1di 40

CONFIDENTIAL. All rights reserved AREVA.

Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

AREVA PACiS

PACIS V4

RELEASE NOTE

V4.4.9

DISTRIBUTION
Confidentiality Category Control Category
Restricted Normal Controlled Not Controlled
Error: Error:
Reference source not Reference source not
foundError: Reference foundError: Reference
source not foundError: source not foundError:
Reference source not Reference source not
foundError: Reference foundError: Reference
source not foundError: source not foundError:
Reference source not Reference source not
foundError: Reference foundError: Reference
source not found source not found
Issue Error:
Identification Identification
Reference source Tr a n s m i s s i o n & D i s t r i b u t i o n
number letters
not found
2059660Error:
Reference source
not foundError:
Reference source
AREVA T&D Protection & Contrôle, Avenue de Figuières – BP75
not foundError: RN J
34975 Lattes Cedex - France
Reference source
not foundError:
Reference source
not found
CONFIDENTIAL. All rights reserved AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.
APPROVAL SIGNATURES

NAME POSITION DATE SIGNATURE

JM. BOISSET PACiS


PROJECT MANAGER
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

M. VERNEY R&D VALIDATION &


SUPPORT GROUP MANAGER

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 3/40
RECORD OF REVISION

ISSUE DATE AUTHOR COMMENTS


Z 12/01/07 G. JUVANON Delivery of C264 VB4.46, ES V1.6.3, GTW V4.19, OI
G.02.00B with SCADA 2000 M4RC46B, P_WATCH
V2.6, SBUS Agency V3.31, SCE V4.41.B, SMT J.03.01
Delivery of C264: CPU3

A 12/03/07 G. JUVANON Delivery of C264 VB4.48A, ES V1.6.3, GTW V4.21.1,


CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

OI G.02.02B with SCADA 2000 M4RC48A, SBUS


Agency V3.32, SCE V4.42.B, SMT J.03.03
Delivery of C264: IsaGraf: Multi DO in one step
Delivery of SCE: Automatic documentation for wiring &
SCADA
Availability of SWR21x & SWD21x switches
Availability of DSP260 Board Version B0
Delivery of C264 Web maintenance Server
Delivery of C264 Telnet with password
Delivery of CRA 758 (GTW part): SPS buffer overflow
on SCADA line,
Delivery of CRA 810: C264: DNP3 SCADA unsolicited
messages
Delivery of CRA 824: GTW: Time stamp handling on
SBUS-GI

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 4/40
B 31/07/07 G. JUVANON Delivery of C264 VB4.54A, ES V1.6.4, GTW V4.22.7,
OI G.03.06A with SCADA 2000 M4RC62A, SBUS
Agency V4.4, SCE V4.46, SMT K.00.04
Delivery of Control Originator function (PTR2007)
Delivery of CRA 717: C264: Datapoints Association,
Delivery of CRA 722: C264: Implementation of ASDU
106 in T101 protocol
Delivery of CRA 758 (C264 part): SPS buffer overflow on
SCADA line
Delivery of CRA 783: GTW: V35 at 64Kbauds on PACIS
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

gateway
Delivery of CRA 798/802: C264: T103 protocol: Generic
Services
Delivery of CRA 801: SCE: IEC Datamodel optimisation
Delivery of CRA 898: CMT with communication over IP
– finalisation
Delivery of CRA 914: GTW: 56K BCOM8 card testing
and integration
Delivery of miscellaneous functions:
- Memo management – display
- pop-up automatic closure after select
- "filtering in progress" indicator & filtering
criteria reset
- alarm ack date column in alarm viewer
- multistate for control in progress with future state
- title of control pop-up
Stabilisation of PSL, Synchrocheck and IsaGraf functions
C 04/09/07 G. JUVANON Delivery of C264 VB4.57F, GTW V4.22.11, OI G.03.06C
with SCADA 2000 M4RC62C, SBUS Agency V4.4, SCE
V4.47
Delivery of Configuration upload (PTR07-09)
Delivery of Configuration Alarm LED (PTR07-10)
Delivery of CT/VT measurement board with 5th VT
(PTR07-16)
Delivery of CRA 809: OI in Romanian language
Delivery of CRA 822: C264: Frequency measurement
based on Vn,
Delivery of CRA 966: C264: C264 to be compliant with
Px4x relays event extraction

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 5/40
D 08/10/07 G. JUVANON Delivery of C264 VB4.60B, GTW V4.23.1, OI G.03.07C
with SCADA 2000 M4RC63C, SBUS Agency V4.6B,
SCE V4.48
Delivery of AREVA Switch Manager V1.4
Delivery of Basic Data Manipulation – Simultaneous
control from PSL (PTR07-06)
Delivery of R&D07-23: DataPoint Unknown management
Delivery of CRA 668: AIU211 Board (8 AIU)
Delivery of CRA 911: T103 Protocol: ASDU 232
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

Delivery of CRA 933: GTW: Modification for IEC


T101messages dynamic under balanced mode,
Delivery of STB07-15: Increase number of configurable
reports (255)
Delivery of STB07-16: Configurable reports naming

E 07/12/07 G. JUVANON Delivery of C264 VB4.62, GTW V4.24, OI G.03.07G


with SCADA 2000 M4RC63G, SBUS Agency V4.7C,
SCE V4.48.B
Delivery of Buffered Report Management on PACiS OI
(PTR07-13)
Delivery of CRA 877: GTW: CDCII, DNP3, T101
protocol: Time Synchronisation of Master Clock from
Remote SCADA through GTW PC using HOPF 6039
board
Delivery of CRA 1024 : GTW: CDC II protocol: response
SCADA 2 Bytes
Delivery of CRA 1031: GTW: DNP3 & CDC II protocol:
Energy values as counter type

F 29/01/08 G. JUVANON Delivery of C264 VB4.63, OI G.03.07I with SCADA


2000 M4RC63I, SBUS Agency V4.8, SCE V4.48.D
Delivery of SCE: Synchro SNTP by third party device
(PTR07-31)
Delivery of C264: Local Alarm Acknowledgement

G 13/03/08 G. JUVANON Delivery of C264 VB4.66, GTW V4.24.5, OI G.03.07J2


with SCADA 2000 M4RC63J2, SBUS Agency V4.8B,
SCE V4.48.H, SMT K.00.07
Add OI Printer : Lexmark 2591
H 19/03/08 G. JUVANON Add Fixed Anomalies
I 23/05/08 G. JUVANON Delivery of C264 VB4.68A, GTW V4.24.6, OI G.03.07L
with SCADA 2000 M4RC63L, SBUS Agency V4.10, SCE
V4.48.J, SMT K.00.08
EXCEPT HORNS REV – AFS Project

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 6/40
J 18/07/08 G. JUVANON Delivery of C264 VB4.70, GTW V4.25.1, OI G.03.07M
with SCADA 2000 M4RC63M, SBUS Agency V4.11,
SCE V4.48.K, SMT K.00.09, Switch Manager V1.5
Delivery of "EvID4226Patch.exe" software for Extension
Socket TCP
Add Compatibility TMU200, TMU210, DSP, CPU260 &
CPU270
Windows XP SP3 for OI/SMT and GTW
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 7/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

Release Note
PACiS – V4.4

RN - Issue J – 18/07/08
Page: 8/40
Identification Number: 2059660
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

TABLE OF CONTENTS

1. SYSTEM IDENTIFICATION.........................................................................................................................911

2. ABBREVIATIONS...........................................................................................................................................911

3. LIST OF ITEMS.............................................................................................................................................1012
3.1. PACiS C264........................................................................................................................................1113
3.2. PACiS GATEWAY..............................................................................................................................1113
3.3. PACiS OI............................................................................................................................................1214
3.4. PACiS SBUS Agency.........................................................................................................................1315
3.5. PACiS SMT........................................................................................................................................1315
4. FEATURES.....................................................................................................................................................1416
4.1. Main evolutions..................................................................................................................................1416
4.2. Main features......................................................................................................................................1618
4.3. Change Request Analysis...................................................................................................................2224
5. ANOMALIES.................................................................................................................................................2325
5.1. Anomalies corrected...........................................................................................................................2325
5.2. Known Limitations.............................................................................................................................2426
5.2.1 - PACiS OI.................................................................................................................................2426
5.2.2 - PACiS SMT.............................................................................................................................2527
5.2.3 - PACiS GATEWAY...................................................................................................................2527
5.2.4 - PACiS C264............................................................................................................................2628
5.2.5 - PACiS SCE..............................................................................................................................2830
6. REFERENCE DOCUMENTS......................................................................................................................2931

7. EXTERNAL COMPATIBLE SUPPLIES....................................................................................................3032


7.1. PC – SCE and OI/SMT.......................................................................................................................3032
7.1.1 Windows 2000.........................................................................................................................3032
7.1.2 Windows XP............................................................................................................................3133
7.2. PC – GATEWAY................................................................................................................................3234
7.2.1 Windows 2000.........................................................................................................................3234
7.2.2 Windows XP............................................................................................................................3234
7.2.3 Windows XP Embedded..........................................................................................................3234
7.3. External clock.....................................................................................................................................3335
7.4. Printers................................................................................................................................................3335
7.5. Ethernet switches................................................................................................................................3335
7.6. Smart Card Reader.............................................................................................................................3335
7.7. ISAGRAF Workbench........................................................................................................................3335
7.8. ALERT Software................................................................................................................................3335
7.9. DAT Reader (for OI backup function)................................................................................................3335
7.10. SNTP..................................................................................................................................................3436
7.11. ODBC Driver......................................................................................................................................3436
7.12. XML parser.........................................................................................................................................3436
7.13. Crystal Report.....................................................................................................................................3436
7.14. Micom S1V2......................................................................................................................................3436
7.15. Microsoft SQL Server 2000...............................................................................................................3537
7.16. Microsoft SQL Server 2005...............................................................................................................3537
7.17. E_TerraControl...................................................................................................................................3537
8. INSTALLATION / USE.................................................................................................................................3638

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 9/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

9. COMPATIBILITY.........................................................................................................................................3739
9.1. Compatibility sub-systems.................................................................................................................3739
9.2. Database Compatibility......................................................................................................................3840

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 10/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

1. System identification

Name: PACiS V4

New release: V4.4.9 Availability date: 18/07/08

Previous release: V4.4.8

2. Abbreviations
CMT : Computer Management Tool
CRA : Change Request Analysis
DPS : Double Point Status
DSP : Digital Signal Processor, which supports module protection functionality
ES : Equipment Simulator
FBD : Functional Block Editor
FR : Fault Report
GTW : Gateway
HMI : Human Machine Interface
IED : Intelligent Electronic Device
MPS : Multiple Point Status
MV : Measurement Value
N/A : Not Applicable
NUC : Norwegian User Conventions
OI : Operator Interface
OWS : Operator WorkStation
P_WATCH : PACiS Watch
PLC : Programmable Logic Control
PPC : Power PC, C264 main CPU
PR_SIM : Process Simulator
PTR : Product Task Request
RCP : Remote Control Point
SCADA : Supervisory Control And Data Acquisition
SCE : System Configuration Editor
SCP : Substation Control Point
SMT : System Management Tool
SNTP : Simple Network Time Protocol
SPS : Single Point Status
TPI : Tap Position Indication (for Transformers)
WTS : Windows Terminal Services

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 11/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

3. List of items
Version Modified Identification
Sub-systems (X = Yes) number Comments

C264 VB4.70 X 2070643


ES V1.6.4 2070639
GTW V4.25.1 X 2070698
OI G.03.07M X 2070634 Including SCADA 2000 M4 RC63M &
"EvID4226Patch.exe"software – see Note 1 below
P_WATCH V2.6 2070997
SBUS Agency V4.11 X 2059660
SCE V4.48.K X 2070290
SMT K.00.09 X 2070635
Switch Manager V1.5 X 2071592 Including Getmac V5.0.2128.1 and WinPcap V4.0.1
See Note 3 below

The system is available in the following languages:


- Chinese (except the SCE data model)
- English
- French
- German (except the SCE data model)
- Romanian (except the SCE data model)
- Russian (except the SCE data model)
- Spanish (except the SCE data model)
- Turkish (except the SCE data model)
- Polish (expect the SCE data model)

Note 1: The "EvID4226Patch.exe" tool is delivered with PACiS OI to set-up the number of concurrent TCP
connections attempts, see "Readme" file to change this limit.

Note 2: OI, GTW and SMT on Windows 2000 SP4 or Windows XP SP3

Note 3: The Switch Manager software is a tool for internal use only (AREVA T&D Automation Business). Do not
distribute elsewhere without further written authorisation.
Install WinPcap software and also for Windows 2000 Getmac software.

Note 4 : This GTW V4.25.1 release contains the following change : "Transform COT 12 into COT 3 for transmitted
data to the SCADA" via a registry key "Cot_remote_cmd". In this case, this key must be set to 3.

Note 5: ISaGRAF: Available languages: see § 7.7

Note 6: Crystal Report: Available languages: see § 7.13

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 12/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

3.1. PACiS C264

C264 / CMT BSP Vxworks ISaGRAF Triangle Micom S1 SBUS WinPcap


(TORNADO) Runtime Agency

B4.70 B0.12 V6.2 V4.03 V3.00.25 M1.17B V4.12 V4.0.1

3.2. PACiS GATEWAY

Version Modified Identification Comments


(Files / Component / sub-systems) Global Hardware Software (X = Yes) number
TG_RCC.exe V4.25.1 V4.25.1 X 2070698 Gateway kernel
PROT.exe V4.25.1 V4.25.1 X 2070698 Process Protocol
SO_UCA2.dll V4.25.1 V4.25.1 X 2070698 UCA2 Acquisition
DLL_ECDD.dll V2.8.1 V2.8.1 X 2070698 Configuration library

genecdd.dll 3.H.0.0 3.H.0.0 2070698 Ecdd library


redundant.dll 4.5.0.1 4.5.0.1 2070698 Redundancy library
Iec.dll 4.H.0.6 4.H.0.6 X 2070698 Protocol IEC 870-5-101
library
Gi74.dll 2.3.9 2.0.0.0 2070698 Protocol GI74 library
version
ECDD
2.17
Iec104.dll 4.H.0.7 4.H.0.7 X 2070698 Protocol IEC 870-5-104
library
Modbus.dll 4.H.0.1 4.H.0.1 2070698 Protocol Modbus library
Dnp3.dll 4.H.0.3 4.H.0.3 2070698 Protocol DNP3
PROT_UCA_IEC.dll 4.H.0.4 4.H.0.4 2070698 Protocol UCA-61850
cdcii.dll 4.H.0.2 4.H.0.2 2070698 Protocol CDC type II
opc.dll 4.H.0.0 4.H.0.0 2070698 Protocol OPC library
OPCSvr.dll 1.04.010 4.G.0.1 2070698 Protocol OPC server library
WtOPCSvr.dll 1.0.8.4 4.H.0.0 2070698 Protocol OPC toolkit server
library

Opccomn_ps.dll 1.0.0.2 1.0.0.2 2070698 Opc foundation dll


Opchda_ps.dll 1.0.0.0 1.0.0.0 2070698 Opc foundation dll
OPCProxy.dll 2.0.0.1 2.0.0.1 2070698 Opc foundation dll
Clientopc_1.1.exe 1.1.0.0 1.1.0.0 2070698 Opc foundation dll

Ecdd_gen.exe 4.25 2.8.1.0 X 2070698 Configuration generator


(included in SCE)
Ecdd_conv.exe 4.25 2.8.1.0 X 2070698 Configuration conversion
(included in SCE)

GTW_V4.25.1.exe V4.25.1 V4.25.1 X 2070698 Installation software

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 13/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

3.3. PACiS OI

Version Modified
(Files / Component / sub-systems) (X = Yes) Comments
Global Hardware Software
XML Module
OdcBuilder.exe 4.51.1.12 X (*)
Hmi.dtd 2070290-J8 X (**)
Mimic.dtd 2070290-J8 X (**)
TrendViewer.dtd 2070290-J8 X (**)
Commonpart.dtd 2070290-J8 X
Svg-20000802-modify.dtd
OdcXmlParser.exe 4.51.1.12 X (*)
S2K.dtd Y3-55 A420765-T (**)
S2KloaderTemplate.xml

Loading Module
OdcLoading.exe 4.51.1.9 (*)
OdcProgressBar.ocx 1.0.0.5 (*)

IEC Coupling
OdcDataPoint.dll 4.51.1.12 X (*)
OdcIECCoupling.dll 4.51.1.12 X (*)

Appli. Layer Module


Template.fvp G.03.07M X (***)
OdcAlarming.ocx 2.3.0.2 (*)
OdcMemo.ocx 4.3.0.0 (*)
OdcPasswordUtility.ocx 3.5.0.0 (*)
UserProfilesMapping.ocx 4.51.1.11 (*)
OdcTimer.ocx 3.0.0.0 (*)
S2Kbalancing.dll 4.49.0.0 (*)
S2KbalMessages.dll
S2Kmessages.dll
PacisPolling.dll 44.51.1.9 (*)

Extended Command
OdcInterlocking.ocx 3.1.0.7 (*)
Interlocking.dtd

Miscellaneous Software
WatchOiClient.exe 4.49.0.0 (*)
WatchOiServer.exe (*)
EvID4226Patch.exe 2.23d X

SCADA 2000
Client Builder.exe M4 RC63M X
S2KServer.exe M4 RC63M X

(*) To check the component version, right click on the file from the Windows Explorer and go to Property\Version.
(**) To check the DTDs version, open the file in text mode.
(***) To check the Template version, open the About box from the Command banner.

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 14/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

3.4. PACiS SBUS Agency

SBUS Agency OdFoundry PACiS WinPcap


Tunnelling

V4.11 V2.2 V4.11 V4.0.1

3.5. PACiS SMT

Item Software version Modified Comment


(X=Yes)
SMT_hmi.exe K.00.06 To be checked with Windows Explorer
SMT_kernel.exe J.01.02 To be checked with Windows Explorer
SMT_icon.exe J.03.02 To be checked with Windows Explorer
conXmlToDm.exe J.01.02 To be checked with Windows Explorer
smtIcon.dll J.02.05 To be checked with Windows Explorer
IECservices.dll K.01.00 To be checked with Windows Explorer
Hmi.jar K.00.09 X Provided by the “About” window
Kernel.jar K.00.09 X Provided by the “About” window

File converter COMTRADE 2001 COMTRADE 1997


Version Version
Cid_launcher 1.0.0.1 1.0.0.1
CvtIedDist_mbus_m300 1.3.0.0 1.2.0.0
CvtIedDist_mbus_s20 1.3.1.0 1.2.1.0
CvtIedDist_t103 1.3.0.0 1.2.0.0

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 15/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

4. Features

4.1. Main evolutions

The main evolutions towards previous version are :

- Anomaly correction (refer to §5),

In order to benefit from the main evolutions, do the following actions with the SCE:
- open and convert the previous configuration data base,
- make a SBUS Automatic Addressing from Ethernet network item,
- regenerated the database
Then download the new databag to the equipments (GTW, C264, OI) via the SMT.

Note 1: Please Note Limitations for CRA or new functionalities (PTR) in § 5.2.

Note 2: Please refer to "Readme" file for CRA or new functionalities Configuration Guideline.

Note 3: C264: Capacity of Flash memory

CPU2: The capacity of Flash memory in CPU2 is 16 Mbytes, so with C264 VxWorks 6.2 (12 Mbytes), it
stays only 4 Mbytes, so perhaps only one Database can be loaded into the C264.

CPU3: The capacity of Flash memory in CPU3 is 64 Mbytes, so 2 Databases can be loaded into the C264.

Note 4: OI Server redundant : Twin Server Safe

The copy of persistence files from Master to Backup OI Server has been disable.

Therefore, after a switch of OI Client connected to the OI Server Backup, the user has to
acknowledge the alarms.

Note 5: In addition to the Global Alarm Acknowledgement SPS, a Local Alarm Acknowledgement SPS can be
defined on a par C264 basis, please refer to the "Readme" file for configuration.

Note 6: The Master Clock can be a C264 or a Third party device. In this case, no time accuracy can be guaranteed,
please refer to the "Readme" file for configuration.

Note 7: PACiS OI Server is compatible with Microsoft SQL Server 2000 and with Microsoft SQL Server 2005.

Note 8: IsaGraf: Use of MPS datapoints: please refer to the "Readme" file for use of such MPS datapoints.

Note 9: PACiS GTW-PC: Protocol T101: A new registry key has been added "SCADA_DEWA":
- If this key is set to 1: a Datapoint on Unknown State is transmitted with NT and IV information
- If this key is set to 0, a Datapoint on Unknown State is transmitted with only NT (Not Topical)
information

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 16/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

Note 10: PACiS GTW-PC: Protocol T101: A new registry key has been added "balanced mode Ack" to indicate
The T101 acknowledgement balanced mode
- If this key is set to 1: GTW always acknowledge at link level, even if waiting a SCADA
acknowledgement
- If this key is set to 0: GTW not relies to SCADA, if it's waiting acknowledgment

Note 11: GTW : For using HOPF 6039 board into a GTW-PC, registry keys have been added for CDCII, DNP3
and T101 protocol, please refer to the "readme" file to configure these keys

Note 12: PACiS GTW-PC: Protocol T101: A registry key has been added "ConcatAnalogEvent". This key indicates
if Suppression in a frame of several analog with same address is needed:
- 0 : No effect (default value),
- 1 : Suppression in a frame of several analog with same address

Note 13: PACiS GTW-PC: A registry key has been added "CheckLocalRemote" in
"HKEY_CURRENT_USER/Software/AREVA/Tg/main". This key indicates if a check must be made on
Local/Remote DPS:
- 0 : No check of the Local/Remote DPS,
- 1 : check of the Local/Remote DPS (default value)

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 17/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

4.2. Main features

Functions

NA = Not Available N = New A = Available D = Deleted


Function Reference NA N A D Comments
UCA2 PS01 X
IEC61850 PS01 X
Limits and performances PS01 X

RCP – T101 - Gateway PS03 X


RCP – GI74 – Gateway PS03 X
RCP – T104 – Gateway PS03 X
RCP – Modbus – Gateway PS03 X Refer to the PACiS protocol profile
RCP – OPC - Gateway X Refer to the PACiS protocol profile
RCP – DNP3 - Gateway X Refer to the PACiS protocol profile
RCP – CDC Type 2 - Gateway X Refer to the PACiS protocol profile
RCP – T101 – Computer PS03 X Refer to the PACiS protocol profile
RCP – DNP3 - Computer PS03 X Refer to the PACiS protocol profile
RCP – T104 – Computer PS03 X Refer to the PACiS protocol profile
RCP – Modbus - Computer X Refer to the PACiS protocol profile
SCP – Local architecture PS03 X Limited to 2 OI client and 2 displays, one OI client
on the same PC than OI server
SCP – Remote architecture PS03 X
SCP – Redundant architecture PS03 X
SCP – Languages PS03 X English, French, German, Spanish, Russian,
Chinese, Turkish and Polish
SCP – Pictorial representation PS03 X
SCP – Operator access rights PS03 X
SCP – Device controls PS03 X Setpoints not available
SCP – Event Viewer PS03 X
SCP – State Viewer PS03 X
SCP – Trend Viewer PS03 X
SCP – Manual operation on PS03 X
datapoints
SCP – Memo function PS03 X
SCP – Discordance management PS03 X
SCP – Maintenance dialog PS03 X Database upload not available
BCP – Local HMI PS03 X

Digital Input acquisition PS04 X


Digital measurement acquisition PS04 X
Counters acquisition PS04 X Limitation to 20 Hz
Analogue inputs acquisition PS04 X
CT/VT input acquisition PS04 X Following measurements are available:
Currents and voltages, frequency, active power,
reactive power, apparent power, power factor,
sequence component, ratio, phase angle, harmonics
Digital outputs PS04 X
Digital setpoints PS04 X
Analogue setpoints PS04 X
IED interface PS04 X
Power supply PS04 X

Binary input processing PS05 X


PACiS – V4.4 Identification Number: 2059660
Release Note
RN - Issue J – 18/07/08 Page: 18/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

Function Reference NA N A D Comments


Measurement processing PS05 X
Tap Position Indication PS05 X TPI up to 64 positions in 1/N coding
Metering PS05 X Counters cannot be managed on redundant
computers
Energy counting is available from C264 and from
IED on Legacy Bus
Computer Protection functions PS05 X See § 5.2 for limitations

Data logging – System Level PS06 X


Data logging – computer level PS06 X
Archiving – system level PS06 X Existing limitations – Refer to Industrialisation
team for details
Archiving – computer level PS06 X
Archiving – waveform PS06 X
Reporting PS06 X Existing limitations – Refer to Industrialisation
team for details

Control of non-synchronised PS07 X


circuit breaker
Control of synchronised circuit PS07 X Existing limitations – Refer to Industrialisation
breaker team for details
Control of disconnector PS07 X
Control of transformers PS07 X Existing limitations – Refer to Industrialisation
team for details
Control of ancillary devices PS07 X
System controls PS07 X
IED controls PS07 X Existing limitations – Refer to Industrialisation
team for details
Setpoints PS07 X

Interlocking equation PS08 X Existing limitations – Refer to Industrialisation


team for details
Topological interlocking PS08 X
Configurable automation (PLC) PS08 X
Fast configurable automation PS08 X See § 5.2 for limitations
(PSL)
Automatic Voltage regulation PS08 X Existing limitations – Refer to Industrialisation
team for details
Synchrocheck PS08 X
Auto-recloser PS08 X
Pole discrepancy protection PS08 X
Trip circuit supervision PS08 X

Alarm management – State basis PS09 X


Alarm management – Gravity PS09 X
level basis
Alarm management – data basis PS09 X
Alarm management – spurious PS09 X
alarm
Alarm acknowledgement PS09 X
Alarm clearing PS09 X
Audible alarms PS09 X
SCP – alarm viewer PS09 X
SCP – alarm banner PS09 X
SCP – graphical alarm PS09 X

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 19/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

Function Reference NA N A D Comments


BCP – alarm display on local PS09 X
HMI
Alarm notification PS09 X

IED – Station Bus PS10 X


IED – Modbus PS10 X
IED – T103 PS10 X
IED – DNP3 PS10 X
IED – T101 PS10 X

Time management – external PS11 X GPS only – connexion to computer through IRIG-
clock B only
Time management – PS11 X
synchronisation

Equipment operating mode PS12 X


Computer redundancy PS12 X See § 5.2.4 for limitations
Gateway redundancy PS12 X
Station bus redundancy PS12 X
OI redundancy PS12 X Only OI client redundancy. OI server redundancy
is not available but is replaced by Twin Server Safe
function
Local / remote control operating PS12 X
mode
System dependability PS12 X

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 20/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

Hardware

C264 & C264C

NA = Not Available N = New A = Available D = Deleted


Hardware Reference Version NA N A D Comments
Rack 80TE with CTVT 2070790A01 B0 X
Rack 80TE without CTVT 2070790A02 B0 X
Rack 40TE with CTVT 45196526A1 B0 X
Rack 40TE without CTVT 45196526A2 B0 X
CPU260 45196300 H1 X A1 - CPU2
CPU260 45196300 H2 X A5 – A6 - CPU2
CPU270 2071590 D0 X A01 - A02 - CPU3
DIU200 45196503 E2 X
DIU210 2071292 B0 X
DOU200 45196505 C1 X
AIU201 2070913 D4 X
AIU210 2071344 A4 X
AIU211 2071652 A2 X
CCU200 45196501 F1 X A01 – A03 – A04
CCU200 45196501 F2 X A02
CCU200 45196501 B1 X A07
BIU241 2070879 D0 X
BIU100 2071349 B0 X
FBP242 8 slots 2070820 Z0 X
FBP280 17 slots 45196539 A0 X
TMU200 2070766 C0 X
TMU210 2071469 C0 X A01 - A10
TMU220 2070613 D0 X
DSP260 2070871 C2 X For TMU 200
DSPIO 2071414 B1 X For TMU 210
GHU201 80TE (LCD) 2070962 G0 X
GHU211 80TE (Leds) 2070966 H0 X
GHU221 80TE (Blind) 2071172 B0 X
GHU200 40TE (LCD) 2071004 H0 X
GHU210 40TE (Leds) 2071010 G0 X
GHU220 40TE (Blind) 2071174 B0 X
ECU200 2070958 Z0 X RS232/optical converter
ECU201 2070960 Z0 X RS232/RS485 converter
SWU200 without optic 2070745 D1 X A01
SWU200 optic multimode 2070745 E1 X A02
SWU200 2 optic 2070745 E1 X A03
multimode
SWU200 2 optic 2070745 D1 X A04 - A05
monomode
SWR202 multimode 2071021 C0 X A01 - Redundant switch
SWR204 monomode 2071021 C0 X A02 - Redundant switch
SWD202 multimode 2071355 Z2 X A01 - Dual Homing switch
SWD204 monomode 2071355 Z2 X A02 - Dual Homing switch
SWR212 multimode 2071646 B0 X A01 - Redundant switch
SWR214 monomode 2071646 B0 X A02 - Redundant switch
SWD212 multimode 2071647 B0 X A01 - Dual Homing switch
SWD214 monomode 2071647 B0 X A02 - Dual Homing switch

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 21/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

TMU200, TMU220, DSP, CPU260 and CPU270 compatibility:

Definitions:
CPU260 F4&- : Ref. : 45196300 A0x up to F4 version (including)
CPU260 F5&+ : Ref. : 45196300 A0x F5 version and upper
CPU270 : Ref. : 2071590 A0x

DSP Zx : Ref. 2070871 Zx


DSP B0&+ : Ref. 2070871 B0 and upper (Ref 2070871 A0 has been removed).

TMU200 Ax&- (calibration type 1) : Ref. 2070766 up to Ax versions


TMU200 B0&+ (calibration type 2) : Ref. 2070766 B0 and upper
TMU220 (calibration type 2 and type 3) : Ref. 2071613

where "x" represents any value from 0 to 9

Software CPU260 cal1 : C264 Software release : V2.00 to V2.16P (PACIS V2)
(TMU calibration type1) or V3.01 to V3.45 (PACIS V3)
or V4.01 to V4.28 (PACIS V4)

Software CPU260 cal1-2 : C264 Software release : V3.46 and upper (PACIS V3)
(TMU calibration type1 or 2) or V4.29 and upper (PACIS V4)

Software CPU260/CPU270 : C264 Software release : VB3.59 and upper (PACIS V3)
(TMU calibration type1 or 2 or 3) or VB4.46 and upper (PACIS V4)

CPU260 F4&- CPU260 F5&+ CPU270

TMU200 Ax&- TMU200 B0&+ / TMU200 Ax&- TMU200 B0&+ / TMU200 Ax&- TMU200 B0&+ /
TMU220 cal2-3 TMU220 cal2-3 TMU220 cal2-3
DSP DSP DSP DSP DSP DSP DSP DSP DSP DSP DSP DSP
Zx B0&+ Zx B0&+ Zx B0&+ Zx B0&+ Zx B0&+ Zx B0&+
Soft
CPU260 OK NOK NOK NOK OK NOK NOK NOK NOK NOK NOK NOK
cal1
Soft
CPU260 OK NOK OK NOK OK OK OK OK NOK NOK NOK NOK
cal1-2
Soft
CPU260 / OK NOK OK NOK OK OK OK OK NOK OK NOK OK
CPU270

OK means the behaviour is correct


NOK means the behaviour is not correct but it is safe, because C264 does not start.
NOK means the behaviour is not correct but it is safe and the C264 starts. Problem is not always visible immediately and can cause
risky working (for example : wrong measurements, circuit breaker closing through synchrocheck with not allowed conditions,
uncertain frequency tracking).

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 22/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

These incompatibilities are source of following issues :


 Platform extension with new material using a "soft CPU260 cal1"
 Replace a "CPU260" by a "CPU270" board :
 With a "soft CPU260 cal1" or
 With a "soft CPU260 cal1-2" or
 With a "DSP Zx"
 Replace a "DSP Zx" by a "DSP B0&+" board :
 With a "soft CPU260 cal1" or
 With a "soft CPU260 cal1-2" and a "CPU F4&-"
 Replace a "TMU200 Ax&-" by "TMU200 B0&+ or "TMU220 cal2-3" with a "soft CPU260 cal1"board

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 23/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

4.3.

Release Note
PACiS – V4.4

RN - Issue J – 18/07/08
CRA Number
Change Request Analysis

Description

Identification Number: 2059660

Page: 24/40
Internal
reference
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

5. Anomalies

5.1. Anomalies corrected

Version PACiS V4.4.9 Date 18/07/2008

Issue ID Project / Num Subsytem Title

7220 G15 – DEWA 10SS OI Bad connection of OI Client during 20min at startiing of the server
DEWA – Frame C264 – Indus
7943 Agreement 132kV software TMU210 Board malfunctioning
OI Clients didn't get connected to Main Server after Restoration
7997 EAM_GCCIA OI (subsequent to Switchover)
OI connection fail to update alarms / curves / opc connection after
8112 EAM_GCCIA OI switch over
170519-UW Ost SW "SRD" in ASDU "M_EP_TB_1" (Type ident 18) is not transmitted
8197 Karlsruhe C264 about T101
8224 AIESH C264 Hyper terminal message not normal
DEWA – Frame
8272 Agreement 132kV OI OI server application stopped during the client startup
F92 - BAHRAIN
8305 2002-2006 GTW Synchro status for Gateway not update in IEC61850 client
Instable T104 SCADA line connection if disconnection longer than
8408 P5032_VW_Hannover GTW 60s
8474 P5061 Horns Rev SCE SCE Generation error on IEC61850 Gateway
F67 – TOUR
8479 GRANITE AGENCY C264 CPU3 reboot intempestif sur test de charge
CG1415 – IOCL Wrong frame sent by C264 - MODBUS legacy protocol - redundant
8484 PANIPAT C264 architecture
8531 NDIA SCE Slow waveform not getting generated in Pacis V4.4.6
8560 G15 – DEWA 10SS C264 BootInstall not possible with hyperterminal
8562 G15 – DEWA 10SS OI Bad association between OI and C264 with only 1 DB
8563 G15 – DEWA 10SS OI Unexpected stop of OI server
8568 G15 – DEWA 10SS OI Control SBO operate without execute
8599 H72 - Benslimane SCE Unaccessible template
8862 G15 – DEWA 10SS C264 Power factor random value

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 25/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

5.2. Known Limitations

For External Fault Reports still opened, use DevTrack Tool, or contact AREVA T&D PCL /
Industrialisation Team.

5.2.1 - PACiS OI

For PACiS OI Server, it is mandatory to setup a complete installation of PACiS OI (server & client)
and SCADA 2000.

OI in Turkish:
- only on Windows 2000 SP4 English,
- Some texts stay in English:
- Launch tool on Command Banner,
- Some menus, tooltips in AlarmViewer and Trendviewer

OI in Chinese:
- only on Windows 2000 SP3 Chinese,
- Some texts stay in English:
- Some menus,tooltips in AlarmViewer and Trendviewer

OI in Russian:
- only on Windows 2000 SP4 Russian,
- Some texts stay in English:
- Some menus, tooltips in AlarmViewer and Trendviewer

Windows XP SP3 is available on OI with following limitations:


 Same limitations for Turkish and Chinese language described above.

Buffered reports management:


 If case of buffer overflow, a "Buffer Overflow" datapoint is generated by C264. If this
datapoint is archived, it could have several events in the Historian Database (FR 6579).

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 26/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

5.2.2 - PACiS SMT

The command "Set Current" does not work correctly. It is better to use the switch command from
Equipment panel.

Chinese Language:
- only on Windows 2000 SP3 Chinese,
- Some texts stay in English:
- Some items on SMT HMI (Tree view)

Windows XP SP3 is available on SMT with following limitations:


 Same limitations for Chinese language described above.

5.2.3 - PACiS GATEWAY

GTW IEC/IEC:

 Extern Synchrocheck automatic : in case of SBO sequence with time-out in select phase, the
negative return code (TIME-OUT) is not displayed on the PACiS OI and the user has to click
on Abort (FR 3669).

GTW IEC/IEC redundant:

 After a switch, the RedSt information of the former active GTW is not correctly refreshed (FR
4260)

GTW: NUC Extensions: T101/T104: ASDU not implemented

 ASDU 51: Bitstring of 32 bits


 ASDU 110: Parameter of measured value, normalized value,
 ASDU 112: Parameter of measured value, short floating value,
 Setpoints: Parameter loading

T101 & T104 redundant GTW:

Incorrect Counter input reset and freeze value in standby GTW (FR 4130).

GTW Embedded:

The Gateway on PC Embedded doesn’t support CDC Type II and OPC protocol.

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 27/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

5.2.4 - PACiS C264

C264-GTW: T104 Protocol:

 No SPS Buffer Overflow is available (FR 6065)

PSL:

The designer of a PSL must insure that it's not possible to command an opposite control on a relay
while a control is already in progress on it same relay.

GOOSE Transmission:

Only 100 Digital Datapoints and 65 Analogue Datapoints can be transmitted by GOOSE.

C264 Protection Functions:

 Use only C264P in Simplex Architecture (not redundant)


 [Fast Waveform]: if two trigger conditions in a row, then depending on the timing the second
[FW] file is lost (FR 4828)
 [Fast Waveform]: Following specific default, the logic data into the [FW] are unusable until
the reboot of C264 (FR 4140)
 [Fast Waveform]: Following a change of date (hour) of C264, the logic data into the
Waveform are inconsistent

CRA 644 - Time synchronisation with SEPAM:

 SEPAM 1000 + S20: Synchronisable by Modbus – Tested and Validated,


 SEPAM 1000 + S40: Synchronisable by Modbus – Not tested (equipment not available),
 SEPAM 2000: Synchronisable by Modbus – Not tested (equipment not available),
 SEPAM PM650: Synchronisable by Modbus Not tested (equipment not available),
 SEPAM PM500: Not Synchronisable by Modbus – feature not available in the equipment

C264 GHU200 LED management:

The “C” button is now used for LED acknowledgement. It was formally used for the navigation in the
menu tree. This feature remains and so LED acknowledgement will not be allowed in the menu tree.

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 28/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

CRA 670 - Switched communication for C264 SCADA in DNP3:

Modem: Telenetics MIU14.4L

CAUTION: Even if the SCE would allow a resolution of 1 ms for the attributes "pre_tx" (time before
sending DATA) and "pos_tx" (time after sent DATA), the C264 resolution is 5 ms.
Therefore, refer to the table below to know the real value used by the C264 against the
value set in the SCE.

Time in the SCE 0 1 2 4 5 6 7 10 11 12 15 21 152 523 997 1000


for "pre_tx" or
"pos_tx"
Time used by the 0 5 5 5 5 10 10 10 15 15 15 25 155 525 1000 1000
C264

C264: Web maintenance Server:

 Only 1 client can be connected to the web server


 The client must be on the same network as the Computer
 Free use with Mozilla Firefox 1.5 (and upper)
 Limited use with Internet Explorer 5.0 (and upper). If a request is sent from Internet Explorer if the
page web is not fully displayed, a C264 halt occurs

CRA 822: Frequency measurement based on Vn:

 [81R] inhibition process, thresholds of the current df/dt are available from -10Hz to + 10 Hz, so the
thresholds of the protection relay must be between -9 Hz to + 9Hz (setting by Micom S1)
 Harmonic treatment: the df/dt requires particular attention. Please contact AREVA T&D PCL /
Industrialisation Team for Database Audit

CRA 966: C264 to be compliant with Px4x relays event extraction

Tests have been passed with the following relays:

 P127: - Type P127AA0M111 Serial Number: 0204665 Software version V6.B


 P143: - Type P143217A2M0150C Serial Number: 2306332C Software version P143____2_0150_H
 Speed of the Legacy Network: 9600 and 19200 bauds, Parity: Even

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 29/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

5.2.5 - PACiS SCE

Chinese Language:
- only on Windows 2000 SP3 Chinese,
- Some texts stay in English

Windows XP is available on SCE with following limitations:


 IsaGraf Workbench 4.12 has been tested with Windows XP, its works but not certified by
ICS Triplex company,
 Same limitations for Chinese language described above.

OI Mimic:

The background colour of a GIF bitmap must be the same as the background colour of the mimic.

The number of graphic elements must be less than 1700. Otherwise, the generation could be not
complete and the mimic can be not good displayed on PACiS OI Client.

A graphic element:
- an animated state or an action of a Multistate
- an action of a shape.

Buffered reports management:


 When Buffered report is configured for OI Server, do not Archive/Log the Unknown status of
all datapoints – a warning will be added into the SCE (FR 6712).

IED IEC61850 non PACiS:


 Do not put into spare electric Datapoints from an IED IEC61850 non PACiS

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 30/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

6. Reference documents

Title Reference Issue Comments Language


Product Specification V4.4 PS – 2059660 F E
System Internal Interfaces SII – 2059660 L E
Design Validation Plan DVP – 2059660 K E
Hardware Validation Plan HVP1 – 2059660 D2 E
Contraintes d’intégration ISAGRAF DSL – 2059660 D F
PACiS Technical Guides N/A C30 E
PACiS Operational Guides N/A C30 E

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 31/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

7. External compatible supplies

7.1. PC – SCE and OI/SMT

7.1.1 Windows 2000

For SCE application


Standard desktop PC with at least:
- Processor PIV 1,5 GHz
- Memory: 512 Mbytes RAM
- Hard-disk: 40 Gbytes (FT32 format)
- CD-Reader
- Optionally: Ethernet port, CD-Writer for database exchange
- OS: Windows 2000 Professional US SP4
For OI/SMT application
PC with at least:
- Processor PIV 1,8 GHz
- Memory: 512 Mbytes RAM
- Hard-disk: 40 Gbytes
- CD-Reader
- Ethernet port (100 Mb)
- OS: Windows 2000 Professional US SP 4
- PCI Parallel Port Board: NETMOS 9705
The A-Plus industrial PC with the following configuration has been validated:

PC – 9566085B3
DESIGNATION REFERENCE
Rack 19" 4 U(413 mm) – CE – for bus 14 Slots ICP-RACK305AW W/O PS
Power Supply ATX 400w 90-264 VAC ICP-ACE 841AP/S11
Passive Bus 14 Slots ISA/PCI 12PCI / 1PICMG / 2ISA ICP-PX14S3-RS-R30
CPU Board Socket 370 Base SBC & VGA 10/100 Mbps Lan ICP-ROCKY-4786EV-RS-R40
Processor INTEL PENTIUM IV 2.4 Ghz 533 MHZ (Windows 2000) INTEL P4 2.4 Ghz/533
Fan P4 for Frame 2U with ball bearings ICP-CF514
MEMORY DDRAM 256 MB DDRAM 256MB-4006
Hard-disk 80 GO MAXTOR SATA DD 80GB SATA 7200T MAXTOR
Reader/graver of CDROM 52X IDE CDR 52X IDE
Floppy Disk Reader FDD144
Connection Kit USB 2 Ports ICP-CB-USB02
Fan on square ICP-BF02
Cable DD REF 14642
Logo-AREVA LOGO-AREVA
Windows 2000 US SP4 (media + licence) 9566085A30
Keyboard 105T QWERTY – Mini DIN Ref G83-6104 LPNUS & 9566085A34
cable in Y
Optic Mouse with wheel INTELLIMOUSE-OPT 9566085A35
OPTIONS
Memory Extension to 2 Gbytes: add 2 DDRAM 1GB/400 Mhz 9566085B44
2nd Hard-Disk 80 Gbytes SATA 150 on silent bloc DD 80 GB SATA 9566085B46
2 removable slides SATA RD-03 IEI 9566085B47

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 32/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

7.1.2 Windows XP

For SCE application


Standard desktop PC with at least:
- Processor Xeon 2.8 GHz
- Memory: 2048 Mbytes RAM
- Hard-disk: 80 Gbytes
- CD-Reader
- Optionally: Ethernet port, CD-Writer for database exchange
- OS: Windows XP Professional US SP3

For OI/SMT application


Standard desktop PC with at least:
- Processor PIV 3 GHz
- Memory: 2048 Mbytes RAM
- Hard-disk: 80 Gbytes
- CD-Reader
- Ethernet port (100 Mb)
- OS: Windows XP Professional US SP 3
- PCI Parallel Port Board: NETMOS 9705

The A-Plus industrial PC with the following configuration has been validated

PC – 9566085B4
DESIGNATION REFERENCE
Rack 19" 4 U(413 mm) – CE – for bus 14 Slots ICP-RACK305AW W/O PS
Power Supply ATX 400w 90-264 VAC ICP-ACE 841AP/S11
Passive Bus 14 Slots ISA/PCI 12PCI / 1PICMG / 2ISA ICP-PX14S3
CPU Board Socket 370 Base SBC & VGA 10/100 Mbps Lan ICP-ROCKY-4786EV
Processor INTEL PENTIUM IV 3 Ghz 800 MHZ (Windows XP) INTEL-P4 3.00GHZ/800 1M
Fan P4 for Frame 2U with ball bearings ICP-CF514
MEMORY DDRAM 2 GBytes 2XDDRAM 1Gb-400-SAMSUNG
Hard-disk 80 GO MAXTOR SATA DD 80GB SATA 7200T MAXTOR
Reader/graver of CDROM 52X IDE CDR 52X IDE
Floppy Disk Reader FDD144
Connection Kit USB 2 Ports ICP-CB-USB02
Fan on square ICP-BF02
Cable DD REF 14642
Logo-AREVA LOGO-AREVA
Windows XP US SP2 (media + licence) 9566085A01
Keyboard 105T QWERTY – Mini DIN Ref G83-6104 LPNUS & 9566085A34
cable in Y
Optic Mouse with wheel INTELLIMOUSE-OPT 9566085A35
OPTIONS
Memory Extension to 2 Gbytes: add 2 DDRAM 1GB/400 Mhz 9566085B44
2nd Hard-Disk 80 Gbytes SATA 150 on silent bloc DD 80 GB SATA 9566085B46
2 removable slides SATA RD-03 IEI 9566085B47

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 33/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

7.2. PC – GATEWAY

7.2.1 Windows 2000

For Gateway application

PC – OI GATEWAY – 9566408C1
DESIGNATION REFERENCE
PC BASE B3 PACIS PIV 9566085B3
Windows 2000 US SP4 (media + licence) 9566085A30
BCOM8 PCI 56K

For GI74 application


PC referenced 2070368 (A07 for 48V, A08 for 110V, A09 for 220V)
The additional BCOM8 board (reference 9565913) is mandatory.

7.2.2 Windows XP

Standard desktop PC:


- Processor PIV 3 GHz
- Memory: 2048 Mbytes RAM
- Hard-disk: 80 Gbytes
- CD-Reader
- Ethernet port (100 Mb)
- OS: Windows XP Professional US SP 3

The A-Plus industrial PC with the following configuration has been validated

PC – OI GATEWAY – 9566408D1
DESIGNATION REFERENCE
PC BASE B4 PACIS PIV 9566085B4
Windows XP US SP2 (media + licence) 9566085A01
BCOM8 PCI 56K

7.2.3 Windows XP Embedded

ADVANTECH ARK-3382 fanless Embedded Box Computer:


- Processor: Low Voltage Pentium 1.4 Ghz
- Memory: 992 Mbytes RAM
- Compact Flash: 4 Gbytes
- 24 V Power Supply
- OS: Windows XP Embedded version 2002 - SP1

The Gateway on PC Embedded doesn't support CDC Type 2 and OPC Protocol.

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 34/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

7.3. External clock

- GPS-snap-in module for rail installation – Reference HOPF FG6870 version 5


- GPS Antenna – Reference HOPF FG4490G10

7.4. Printers

- At PACiS OI level: Lexmark 2491 and 2591


For Cyrillic characters, you must have code Cyrillic code page driver loaded into the printer (Not
validated).

- At PACiS C264 level: EPSON LX300

7.5. Ethernet switches

All 10 / 100 Mb Ethernet switches with auto-negotiation.

AREVA Switch (Rail din Format):


 H34 (simple) Ref 2070747 Version B0
 H35 (redundant) Ref 2071162 Version B0
 H36 (dual homing) Ref 2071347 Version Z0
 H15 (redundant) / H16 (dual homing) Ref 2071472 Version A0

7.6. Smart Card Reader

- Licence Calyx SSO, from Calyx NetSecure company, with smart card reader (external USB reader,
keyboard with card reader)

7.7. ISAGRAF Workbench (used by SCE)

- Licence limited to 32 I/O version 4.12, from ICS Triplex company.


- Using USB dongle, install the dongle management software: Sentinel Protection. This software is
available at: Driver dongle
- Supported Languages: English, French, German

7.8. ALERT Software

- Licence ALERT from Micromedia company. It must be purchase depending on the number of alarms
which must be notified (basic licence for 25, 50, 250, 500, 2500, 5000 or unlimited variables).

7.9. DAT Reader (for OI backup function)

- DAT Reader Hewlett-Packard 12Go SureStore,


- SCSI board Adaptec 2904 (if no SCSI port on the PC).

7.10. SNTP

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 35/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

- SNTP Server: Absolute Time Server from AdjustTime.

7.11. ODBC Driver

To compile ISaGRAF project for PACiS SCE and if Microsoft Access 97 is not installed, you need to
install the ODBC driver (dataacc.exe) provided in the MS Office 97 Value Pack, available from:
- www.microsoft.com (google key words : Office 97 ValuPack) or
- www.microsoft.com/downloads/details.aspx?FamilyID=F9DFA82C-9A3B-40DF-B6E4-
DC15E6112BBC&displaylang=en

7.12. XML parser

Only one version of Microsoft msxml DLL is compatible with PACiS.

Check if msxml.dll files available in WINNT\system32 folder have the same date than those provided in
tools\msxml_dlls.zip file. If no, extract from zip file these dll.

Note : new msxml dll files can be installed during third-party application installation.

7.13. Crystal Report

- Crystal Report Professional V8.5.

Supported Languages: English, French, German, Russian

Dedicated Reports: Maximum number of lines of a report: 32000.

7.14. Micom S1V2

- Micom S1 V2 Release V2.14.

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 36/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

7.15. Microsoft SQL Server 2000

- Microsoft SQL Server 2000 Personal Edition Rel. 8.00.194 English Version with Service Pack 1.

7.16. Microsoft SQL Server 2005

- Microsoft SQL Server 2005 Standard US CD/DVD ref Microsoft : 22804023.

Configuration required for SQL Server 2005:

Operating system:
- Microsoft Windows 2000 Professional SP4,
- Microsoft Windows XP Professional SP3,

Internet Configuration:
- Microsoft Internet Explorer 6.0 SP1 and upper,
- Internet Information Services 5.0 or upper,

7.17. E_TerraControl

- E_TerraControl V3.4, see Installation & Configuration Guide in E_TerraControl directory.


This release has been tested with PACiS V4.2.1. There is no test since PACiS V4.2.1.

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 37/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

Release Note
PACiS – V4.4

RN - Issue J – 18/07/08
8. Installation / Use
Refer to PACiS Technical Guides and PACiS Operational Guides.

Identification Number: 2059660

Page: 38/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

9. Compatibility

9.1. Compatibility sub-systems

PACiS Compatibility C264 ES GTW OI P_WATCH SBUS SCE SMT Compatibility Test On
with previous Agency
release
V4.4.0 Yes VB4.46 V1.6.3 V4.19 G.02.00B V2.6 V3.31 V4.41.B J.03.01 Marina Database
V4.4.1 Yes VB4.48A V1.6.3 V4.21.1 G.02.02B V2.6 V3.32 V4.42.B J.03.03 Marina Database
V4.4.2 Yes VB4.54A V1.6.4 V4.22.6 G.03.06 V2.6 V4.4 V4.46 K.00.04 Marina Database
V4.4.3 Yes VB4.57F V1.6.4 V4.22.11 G.03.06C V2.6 V4.4 V4.47 K.00.04 Marina Database
V4.4.4 Yes VB4.60B V1.6.4 V4.23.1 G.03.07C V2.6 V4.6B V4.48 K.00.05 Marina Database
V4.4.5 Yes VB4.62 V1.6.4 V4.24 G.03.07G V2.6 V4.7C V4.48.B K.00.05 Marina Database
V4.4.6 Yes VB4.63 V1.6.4 V4.24 G.03.07I V2.6 V4.8 V4.48.D K.00.05 Marina Database
V4.4.7 Yes VB4.66 V1.6.4 V4.24.5 G.03.07J2 V2.6 V4.8B V4.48.H K.00.07 Jafza Database

V4.4.8 Yes VB4.68A V1.6.4 V4.24.6 G.03.07L V2.6 V4.10 V4.48.JK.00.08 - Tunisie STEG Database
Configuration, Generation
- Test C264, GTW, OI, SCE, SMT
on R&D Platform
V4.4.9 Yes VB4.70 V1.6.4 V4.25.1 G.03.07M V2.6 V4.11 V4.48.K K.00.09 - Jafza Database Configuration,
Generation
- Test C264, GTW, OI, SCE,
SMT on R&D Platform

The last line describes the current version.

In order to benefit from the main evolutions, the previous configuration data must be regenerated from the SCE and downloaded to the equipments (GTW, C264,
OI) via the SMT.

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 39/40
CONFIDENTIAL. All rights reserved. AREVA. Passing on and copying of this document, use and communication of its contents are not permitted without prior written authorization.

9.2. Database Compatibility

PACiS SCE C264 ES GTW GTW OI OI PACiS S1 SBUS SMT


PIDD DTD PIDD Tools PIDD OSIS PIDD Tools Agency DTD
V4.4.0 V4.41.B E16 1.6.3 P 4.19.0 R J4 4.32 3.20 2.1
V4.4.1 V4.42.B E17 1.6.3 Q 4.21.0.1 R J4 4.32 3.20 2.1
V4.4.2 V4.46 E18 1.6.3 2.7.0.0 S J5 4.32 4.0 2.1
V4.4.3 V4.47 E19 1.6.3 2.7.0.0 S J5 M1.4 4.0 2.1
V4.4.4 V4.48 E20 1.6.3 2.7.0.0 T J6 M1.7 4.0 2.1
V4.4.5 V4.48.B E20 1.6.3 2.8.0.0 T J6 M1.10 4.0 2.1
V4.4.6 V4.48.D E20 1.6.3 2.8.0.0 T J6 M1.10 4.0 2.1
V4.4.7 V4.48.H E20 1.6.3 2.8.0.0 T J6 M1.13 4.0 2.1
V4.4.8 V4.48.J E20 1.6.3 2.8.0.0 T J6 M1.17 4.0 2.1
V4.4.9 V4.48.K E20 1.6.3 2.8.1.0 T J8 M1.17 4.0 2.1

PACiS – V4.4 Identification Number: 2059660


Release Note
RN - Issue J – 18/07/08 Page: 40/40