Operaor select A B

<STOP>
Combustion spread monitor disabled
GT Load select Cleared
Purge valves are closed L14HM Reset
GT unloads with rate 8.33 %/min

Premix to Normal shutdown signal reset L94X


CRT=1570 F piloted-premix L14HP Reset
transfer Gas & Liquid fuel permissive reset

piloted-premix
IGV Close to min pos 28.5 deg
CRT=750 F to sub-piloted-
L14HC Reset
premix transfer
False staqrt drain solenoid L20TFD1

PM4 Purge circuit enable


Exciter from auto to manual
Sub piloted-premix to diffusion
L14HT Reset
PM1 purge enabled
L14HA Reset
F Turning gear motor running

Gen reverse False staqrt drain solenoid L20TFD2


Load comp vent fan stops
pwr @4.8MW
Lift oil solenoid energized
<OFF> mode selected

Gen breaker trips (Open) L2TV Vent timer reset


Cooldown <ON>

Compressor bleed valves open


If speed < 20%
Operator selects
Gen compt heater ON cooldown <OFF>

F
L14HF & HS Trip GT – Not counted as Bearing #2 fan stops
are reset Is Flame out? N emergency trip
AC Lube & hydraulic oil pump stops
Exciter tripped – 41DC breaker opens
L2W Warmup timer reset Turning gear stops

IBH system disabled


AC seal oil pump starts
Exhaust cooling fan stopped B
END