Sei sulla pagina 1di 1

Mabara Panel Drive Wiring Details

Wire Ferules Description Delta


Name VFD-B
M Over Load Trip RB
M Over Load Trip RC
S1 Slow Speed MI1
S2 Medium Speed MI2
S3 High Speed MI3
S4 ARD Speed MI4
RST Drive Trip Reset MI5
UP Forward FRW
DN Reverse REW
VCOM Common DCM
CM Common DCM
5V Analog Input + AV1
-5V Analog Input - ACM
DBR DC Braking +2/B1,B2
Resistor Wiring

Delta VFD-B Drive Program Setting

Parameter NO Setting Parameter Name


00-02 09 PARAMETER RESET
00-09 02 VECTOR CONTROL
01-00 50 MAXIMUM FREQUENCY
01-01 50 MOTOR NAMEPLATE FREQUENCY
01-02 415 MAX OUTPUT VOLTAGE
01-09 2.5 ACCELERATION TIME
01-10 1.8 DECELERATION TIME
02-00 01 0 TO 10V FREQUENCY COMMAND
02-01 01 RUN COMMAND
03-00 08 DRIVE FAULT INDICATION
04-04 01 SPEED 1
04-05 02 SPEED 2
04-06 03 SPEED 3
04-07 04 SPEED 4
04-08 05 RESET
05-00 7Hz SLOW SPEED
05-01 25Hz MEDIUM SPEED
05-03 50Hz HIGH SPEED
05-07 5Hz ARD SPEED
06-03 2 OVER LOAD DETECTION ENABLE
06-04 175 OVER LOAD DETECTION LEVEL
06-05 2.2 OVER LOAD DETECTION TIME
07-00 100 MOTOR RATED CURRENT IN %
07-04 04 MOTOR NO OF POLES
04-02 200 ANALOG SETTING