Remedy Action
supplied to motor and phase Shift for power factor but due to voltage taken from( Bus voltage ) Primary side
the calculated power and power factor is Wrong and all related calculation with voltage
as follow
So the problem Here is we don’t have Secondary VT for Voltage Sensing
Wrong Solutions
1- Dividing the power from P243 By 3 which is wrong because the power factor reading is wrong as
the angle of power factor is taken between primary voltage and secondary current
2- Changing the VT ratio in P243 to Be 11.5 KV /110V this also wrong as the same reason before
1- Putting VT at secondary side To Obtain 11KV voltage as Input for MICOM Motor relay P243
But we have this VT to Be added outdoor at transformer side and need more safety, construction and cost
2- Considering the power reading as Transformer input from P643 Micom relay as equal to motor power as
transformer efficiency deviate from from 99.3% to 99.5 % approximate Same for all loading condition
For example
1-
Max power will be at rated 4.645 MVA is about 37.16% of transformer rating ( 12.5 MVA )
2-
Max power will be at rated 6.96 MVA is about 46.4% of transformer rating ( 15 MVA )
3-
Max power will be at rated 4.89 MVA is about 39.13% of transformer rating ( 12.5 MVA )
Max power will be at rated 3.33 MVA is about 33.3 % of transformer rating ( 10 MVA)