STORM EYE INSTITUTE OPTICAL SHOP


167 ASHLEY AVE
CHARLESTON, SC 29425
A A

SEALS

C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.


THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS

AGENCY: MEDICAL UNIVERSITY OF SOUTH CAROLINA (MUSC) PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING THE COPYRIGHT.

MUSC PROJECT NO: H51-50068


NOTES:
CONSTRUCTION DOCUMENT PHASE
1.

ARCHITECTS / ENGINEERS / CONSULTANTS: GENERAL NOTES LIST OF DRAWINGS LOCATION MAP


ARCHITECT:
ROSENBLUM COE ARCHITECTS, INC. A. Before beginning construction, the contractor shall take field measurements and verify existing T-100 TITLE SHEET
1643 MEANS STREET
CHARLESTON, SC 29412
conditions and compare results with information given in the contract documents. Report any inconsistencies T-101 ABBREVIATIONS, LEGEND & CONDOC PROJECT AREA
(843) 577-6073
to the Architect at once.
B. “Align” as indicated on the drawings shall be understood to mean the walls or columns indicated. D-100 DEMOLITION FLOOR PLAN
MEP ENGINEER: C. Work of the engineering disciplines is shown on the Architectural Drawings for coordination purposes D-120 DEMOLITION REFLECTED CEILING PLAN
RMF ENGINEERING only. Refer to appropriate discipline drawings for complete and governing information regarding their work.
194 SEVEN FARMS DR.
A-101 FLOOR PLAN
SUITE G Incomplete, inconsistent or missing engineering information on Architectural Drawings shall not be construed A-121 REFLECTED CEILING PLAN
CHARLESTON, SC 29492 as binding for that work. A-124 TYPICAL SEISMIC CEILING DETAILS
B D. Do not scale drawings, use dimensions only. A-401 INTERIOR ELEVATIONS B
E. Dimensions are typically shown to: A-501 DETAILS
1. Column centerlines
APPLICABLE CODES 2.
3.
Face of unit masonry
Face of unfinished walls
P001
PD100
PLUMBING NOTES, SYMBOLS AND ABBREVIATIONS
PLUMBING CRAWL SPACE DEMOLITION PLAN
2015 INTERNATIONAL BUILDING CODE F. Contractor to coordinate with all equipment vendors, including headwalls, for all locations of boxes, PD101 PLUMBING FIRST FLOOR DEMOLITION PLAN
2015 INTERNATIONAL MECHANICAL CODE pipes, conduits, etc. prior to commencing work. P100 PLUMBING CRAWL SPACE PLAN
2015 NATIONAL ELECTRIC CODE G. Completely patch, trim, bush, repair, and refinish any damaged or imperfect columns, surfaces, or P101 PLUMBING FIRST FLOOR PLAN
2015 INTERNATIONAL PLUMBING CODE similar conditions affected prior to, during, or as a result of construction or demolition. P201 PLUMBING RISER DIAGRAM
2015 INTERNATIONAL FIRE CODE H. Repair, patch, prime, and paint existing walls where architectural, mechanical, or electrical items have P301 PLUMBING DETAILS
2009 INTERNATIONAL ENERGY CONSERVATION CODE been removed. Paint wall corner to corner.
2015 INTERNATIONAL FUEL GAS CODE M001 MECHANICAL NOTES, SYMBOLS AND ABBERIATIONS
2015 INTERNATIONAL MECHANICAL CODE EXISTING TO REMAIN FIRE RATED ASSEMBLIES MD101 MECHANICAL DEMOLITION FIRST FLOOR PLAN
2015 INTERNATIONAL PLUMBING CODE Integrity of remaining fire rated assemblies shall be maintained during demolition and throughout M101 MECHAINICAL FIRST FLOOR PLAN
WITH THE FOLLOWING INSERTIONS: construction. Any holes or other openings created by the removal of doors, frames, piping, duct conduit or M201 MECHANICAL DETAILS AND CONTROLS
1. SECTION 305.4.1, INSERT "18" AND INSERT "18" any other material shall be filled patched or infilled with a UL tested system or with appropriately rated M301 MECHANICAL SCHEDULES
2. SECTION 903.1 , INSERT "8" materials to prevent the passage of fire and smoke as required.
2014 NATIONAL ELECTRICAL CODE Contractor is responsible for protecting existing fire protection at columns, beams and other existing steel or E001 ELECTRICAL NOTES, SYMBOLS, AND ABBREVIATIONS
2012 NATIONAL ELECRTICAL SAFTY CODE concrete. ED101 ELECTRICAL DEMOLITION PLAN
E101 ELECTRICAL POWER AND SPECIAL SYSTEMS PLAN
NFPA 70-2014, NATIONAL ELECTRIC CODE. GENERAL LIFE SAFTEY NOTES E201 ELECTRICAL LIGHTING PLAN
C NFPA 101-2012, LIFE SAFETY CODE A. Contractor shall coordinate access routes, delivery, and debris removal schedule with Owner. After E601 ELECTRICAL SCHEDULES C
hour access shall also be coordinated with Owner.
ICC/ANSI-A117.1-2017 ACCESSIBLE AND USUABLE BUILDINGS AND FACILITIES B. Not smoking shall be allowed on the premise at any time. FP001 FIRE PROTECTION NOTES, SYMBOLS AND ABBREVIATIONS
2010 ADA STANDARDS FOR ACCESSIBLE DESIGN C. Contractor is responsible for protecting fire and life safety devices during construction – includes FP101 FIRE PROTECTION FLOOR PLAN
smoke detectors, emergency lights, fire extinguishers, and all other devices in construction area. Maintain PF201 FIRE PROTECTION SCHEDULES
SITE DEVELOPMENT: record of existing construction including location plan and photographs for review with completion of FP301 FIRE PROTECTION FIRST FLOOR AS-BUILTS
1.1. TOTAL AREA OF PROJECT SITE (IN ACRES): N/A construction. FP302 FIRE PROTECTION CRAWL SPACE AS-BUILTS
EXISTING PROPERTY AREA: N/A D. Fire extinguishers are to be provided throughout construction area.
A. TOTAL AREA OF PROJECT SITE THAT WILL BE DEVELOPED: N/A E. Illuminated exit signs are to be provided throughout construction area – Relocate throughout
B. MUNICIPALITY AND/OR COUNTY WHERE PROJECT IS LOCATED: CITY OF construction process as required.
CHARLESTON F. Emergency lighting to be provided to allow egress during a power outage.
C. JURISDICTION FOR: G. Contractor shall secure construction site when work completes each day.
FIRE DEPARTMENT: CHARLESTON FIRE DEPARTMENT H. Contractors shall properly chain, secure, and cap gas cylinders and limit to needed amounts.
I. Contractor shall limit combustible load. N
WATER: Charleston Water System
SEWER: Charleston Water System J. Contractor is responsible for repairing any existing construction or finishes affected by temporary
ELECTRICITY: SCE&G
ZONING: CITY OF CHARLESTON - LI
barrier constriction. Limit damage to existing floor.
K. Contractor to coordinate temporary construction barriers with as specified prior to start of construction.
ALLOWANCES SCOPE OF PROJECT AREA
Contractor shall protect against dust and debris and maintain air pressure as required.
L. Contractor to coordinate temporary constriction barriers prior to start of construction. ALLOWANCE NO 1: INCLUDE THE INDICATED SUM TO FURNISH MATERIALS AND SUPPLY LABOR TO LEVEL ENTIRE FLOOR
1.2. IS PROJECT IN FLOOD PLAIN: YES WITHIN LIMITS OF CONSTRUCTION WITH HYDRAULIC CEMENT WHERE REQUIRED AFTER COMPLETION OF DEMOLITION, REFER
FLOOD MAP INFORMATION:455-412 PANEL: 0021D TO SPECIFICATIONS FOR MORE INFORMATION.
FLOOD ZONE: ZONE "A5" (EL 13) GENERAL NOTES
BUILDING LOWEST FLOOR ELEVATION:12.25' MSL A. Existing conditions shown on drawings based on information provided by the Owner. This information ALLOWANCE NO 2: INCLUDE THE INDICATED SUM TO REPAIR/PATCH EXISTING FIREWALL. REFER TO SPECIFICATIONS FOR
MORE INFORMATION.
is for reference only and must be verified by the Contractors.

EH132A

EH131

EH130

EH129

EH128
1.3. IS PROJECT IN WETLANDS AREA: NO B. All work performed on existing warranted systems or assemblies should be performed by approved

EH132
EH132B
HA113A

contractors for such assemblies and in such a manner that existing warranties are no voided or jeopardized

EH109C

EH127

EH126
EH109
HA114 HA113 HA111 HA109 HA107 HA108

D in any manner. D

UP
2. OCCUPANCY CLASSIFICATIONS: BUSINESS (B) HA115

C. Wall dimensions shown on plans are centerline to centerline unless noted otherwise. Dimensions from

DN

EH109B
STAIR
HA112 HA110 HA106 HA101 EH108

HA116
HA105

existing construction processes which are hazardous to workers or future occupants are not permitted.

EH123
RAIL

EH107C
3. TYPE OF NEW CONSTRUCTION: HA118
HA117 HA128C HA128D

A. CONSTRUCTION CLASSIFICATION: 1A D. Construction materials or construction processes which are hazardous to workers or future occupants HA119 HA128B
LOBBY

HA103 ELEVATOR

EH107
EH106
HA120

are not permitted. HA121 HA128A


HA128

ELEVATOR

PROJECT NUMBER: H51-50068


B. IS THE BUILDING CONSTRUCTION PROTECTED OR UNPROTECTED: PROTECTED HA122 F.H.C.

E. The construction partition types shown indicate the general construction features of the work to be

EH128
C. IS THE BUILDING CONSTRUCTION COMBUSTIBLE OR NONCOMBUSTIBLE: HA123

MECHANICAL ROOM

DHEC PROJECT NUMBER: 580145

EH105
completed. They are not intended to represent the entire construction process and accessories used. The
HA125 HA126 HA127 HA129 HA130 HA131 HA104

NONCOMBUSTIBLE

EH111
HA124

D. IS THE BUILDING PROVIDED WITH A FIRE PROTECTION SPRINKLER SYSTEM: YES contractors are responsible for completed systems and to be in compliance with governing codes and the

EH116
EH105A
intent of the construction drawings.
PROJECT SCOPE CONSTRUCTION

93.7 SF

EH115
F. Testing and code references used in these drawings by abbreviation. Other testing agencies are

262.2 SF
HA102

4. GENERAL BUILDING DESIGN:

UP

EH110B
226.4 SF

EH110A
acceptable if in compliance with testing standards. 2 - HOUR WALL

DOCUMENTS

EH112
RENOVATION OF AN EXISTING OPTICAL CLINIC.

DN
1 - HOUR WALL

G. See vendor and mechanical drawings for additional notes and references. SMOKE SEPARATION

EH110

EH1??
5/9/2018 9:18:02 AM
H. Details are shown to describe design intent. Coordinate complete shop drawings, showing all
5. FLOOD LOADS:
construction details and layouts as required for a complete job, adhering to the manufacturer’s warranties
AGENCY APPROVALS

210.7 SF
A. LOWEST PROPOSED FLOOR: 12.25' MSL
and local and state codes.

792.8 SF

H123-0
STORM EYE INSTITUTE

35.7
SF

H101D1

65.2
68.9 SF

63.2 SF

H123- 07A
253.2 SF

H123-07
SF

166.7 SF

89.8 SF

59.9 SF
H103B2

STAIRS

H123-08
12.0 SF

H123D
256.0 SF

163.0 SF
127.2 SF

H103B3
H102

EH128
148.0 SF

H103E
H1SW6

H103C

H103D

304.4 SF
150.5 SF

H103A

H103A
I. Existing spray fire resistive material to be patched as required due to work of other trades. Contractor

94.4 SF

107.9 SF
H103B1
73.4 SF

146.8 SF
H123-06
H101D

H2SW7
6. FIRE RESISTANCE RATINGS:

H101E

60.5 SF
H123F
H103B

79.1 SF

H123-01
to maintain existing spray resistive material

588.3 SF
344.4 SF
H103
STRUCTURAL MEMBERS: EXISTING 2 HR 1. DHEC PROJECT NUMBER 580145 : AWAITING FINAL
OPTICAL SHOP

13.4 SF
H109Q

H123G
H123H
H109N

H123I
65.0 SF

68.8 SF
J. Provide access panels where needed to access valves, equipment, filters, etc. Even if not noted in

H123-05

638.5 SF
160.9 SF
H109M

H101A

81.6 SF
71.0 SF
63.6 SF
EXTERIOR WALLS: EXISITNG 2 HR

59.9 SF
drawings.

H103L
H51-50068

897.6 SF
H101B

83.1 SF
H109J

65.7 SF
H109L
65.1 SF

293.3 SF
INTERIOR WALLS: EXISTING 0 HR

H123J
H109H

H109K
59.5 SF
K. The Contractor is to provide dust partitions and tacky mats as necessary around demolition or new

63.4 SF

131.0 SF
H123-04
H101C
FLOOR CONSTRUCTION: EXISTING 2 HR

91.2 SF

185.7 SF
H109G

4458.8 SF

112.3 SF
411.2 SF

H123K
H103F
H103G

H123-L2
140.8

79.8 SF
56.2 SF

SF
construction to protect the Owner’s operations. Dust partitions shall be of non-combustible materials

3780.2 SF

H123
H109P
H109

14.8
H123B

SF
ROOF CONSTRUCTION: EXISTING 1HR

107.6
167 ASHLEY AVE

H123L1
63.7 SF

SF
60.3 SF

H109D

157.7 SF
H109F

488.7 SF
H123L
(including doors and frames) and maintained in good working order throughout the construction. Refer to the

H123-03
349.5 SF
661.3 SF
H109C

H123C2
44.8
SF
64.3 SF

130.1 SF
65.0 SF
H109E

546.7 SF

H123C
H103J

88.8 SF
H123M
H123C1
CHARLESTON, SC 29425

4324.7 SF

57.5
H104
Interim Life Safety Plans and Contractor Access Plan for additional information.

SF
63.7 SF
H109B

61.9 SF
H123N
7. OTHER FIRE PROTECTION REQUIREMENTS:

79.0 SF

H123A2
63.3 SF
H109A
L. The Contractor shall schedule all work including any interruption of utilities prior to commencing

330.0 SF
H123-02
H123-01
H106

H123A
E SPRINKLER SYSTEM: YES E

H123P

91.1 SF
18.4 SF

42.3 SF
H106A

46.5 SF
53.2 SF
H108A

33.5 SF
H103K
constriction. Contractor is responsible for maintaining an updated schedule and coordinating changes with

117.3 SF
294.2 SF

H105B
H108

85.2 SF
H105

73.2 SF
32.0 SF

H122B
143.1 SF
62.2 SF
H105A

51.8 SF

531.9 SF
244.8 SF
Owner and Architect.

147.0 SF
148.7 SF

310.3 SF
H122
63.2 SF

H149

71.7 SF

H122C

62.0 SF
H122A
8. STRUCTURAL DESIGN INFORMATION:

103.8
SF
H124

H127
108.1 SF

95.6 SF

H131

H132
H100A

H1SW5

H143
H141
M. Not used
A. FLOOR LIVE LOAD: N/A ROSENBLUM COE

H139
H135

H136

H137
H135A

H140

H142
H133
H125

10
N. Not used

124.1 SF

17.5
SF
231.2 SF

141.2 SF

146.9 SF
H126A1

135.8 SF

177.4 SF
55.8 SF

289.4 SF
H126A2A
H121
H100J1

82.5 SF

74.8 SF

67.8 SF

43.7 SF
471.2 SF

H137A
B. ROOF LIVE LOAD: N/A

H148D

H148B

66.4
SF
H121A
ARCHITECTS,

H126
O. Not used

36.6 SF

H107
263.0 SF

H126A
H116P

9.7
SF

214.6 SF

H126A2
H111

H148A
H148C
C. GROUND SNOW LOAD: N/A

672.1 SF
STAFFING OFFICE
71.7 SF
66.9 SF
NURSING STAFFING
152.5 SF

128.0 SF

H148E
128.6 SF

H121B

58.6 SF

335.7 SF

76.1 SF
H112
H116M

1 WS
26.4 SF

MAIL ROOM
24.9 SF

H137B
P. Not used

4 WS

H126B
H116N

0 WS

H126C1
172.7 SF
63.6
SF
60.5 SF
D. WIND LOADS: INC.

H126C
PATIENT CARE SERV.
H113A

75.8 SF
99.9 SF

82.1 SF

OFFICE
OFFICE
H116H6

263.8 SF

176.9 SF

H148J
Q. Refer to project manual for general conditions, debris removal and safety precautions.

1 WS
H148F

H149

380.4 SF
H148
H116

H148H

188.1 SF
326.7 SF

H123B1
BASIC WIND SPEED, V = N/A

H113
H116H5
71.8 SF

4679.4 SF

H137
270.6 SF
R. Casework dimension shall be field-verified prior to fabrication and installation.

H148G

77.0 SF
H126A3
138.8 SF

H148K
H148L
H116H8
H116H7

73.4 SF
93.3 SF

81.1 SF
OFFICE

MAIN CORRIDORS 11,799.0 SF


OFFICE
H116H4
61.3 SF

OFFICE
WIND IMPORTANCE FACTOR, (I) = N/A 1643 MEANS STREET

233.0 SF
482.8 SF
270.7 SF

483.6 SF

2120.0 SF
S. Contractor shall coordinate the Work of this Contract with work performed under separate contracts as

H126A4
140.4 SF
H116H7
61.8 SF

H148M

391.2 SF
H116H

OFFICE
101.5 SF

81.4 SF
H116H3

280.3 SF

72.8 SF
H148Q
OFFICE
H148P

OFFICE

931.4 SF
BUILDING CATEGORY: N/A CHARLESTON, SC 29412

H116D
follows: Voice/Data Cabling to RW wiring, HazMat Testing and Abatement. See Specficiation Section 011000

106.9 SF

H116H10

139.6 SF
H116H2

76.0 SF

37.0 SF

H116H1
97.6 SF
H116G

H148N
OFFICE

H123B3

H123B2
532.6 SF

H149

116.5 SF

112.4 SF
H148R
H148S
WIND EXPOSURE: N/A

72.1 SF

OFFICE
OFFICE

65.1 SF

79.7 SF

38.9

H168C
99.2 SF

H126A5

SF

104.3 SF
H168F
94.4 SF
“SUMMARY” for additional information and requirements.

H116C

94.3 SF
H168D

H168E

53.8

H171A 63.1 SF
137.2 SF

SF
OFFICE

H148T

H148V
843.577.6073

57.7 SF
H116B

H148X

99.0 SF

360.0 SF
49.9

273.8 SF

H164
H156A4

H156A3
SF

767.1 SF

H171B
H168G
519.7 SF
85.3 SF

116.1 SF
34.2 SF
H116H11

H116A
T. The Contractor shall be required to utilize SOLE SOURCE PROVIDERS, refer to specification 011000

114.6 SF

148.6 SF
228.0 SF

H187A
H187

273.8 SF

H126A6
H156A1

105.7 SF
103.1 SF
158.7 SF

103.9 SF
74.2 SF

H168A
H148U

120.1 SF

H156A
OFFICE

307.3 SF
H156

H168B

29.8
H148W
33.0 SF

SF
E. SEISMIC LOADS:

H164A

H168
H156A5

H156A2
96.8 SF
97.0 SF

H126A
H187B

162.3 SF

159.3 SF

7.5
SF
37.7
SF
U. All singage will be provided by owner

H171
H182
SEISMIC IMPORTANCE FACTOR, (I) = N/A

H184
H184A

H166
H181

H2SW2
V. No known asbestos or lead paint, should contractor encounter suspicious material he is to notify the

135.1 SF
57.7 SF

SF
30.4

27.8 SF
33.8 SF

26.0

H170B
H188

SF
163.2 SF
69.3 SF

H158J

H166A
136.0 SF

H165R
H165Q
X-RAY TRAUMA RM.

H158M3

22.8 SF

66.3
369.6 SF

SF
STAIRS
SEISMIC USE GROUP: N/A

203.9 SF

264.5 SF

H167F
H158

16.7
H158L
RADIOLOGYH173B

252.9 SF

SF

H167A
H165G

H165P
242.6 SF
354.3 SF

H158I

173.2 SF

216.2 SF

246.8 SF
H166B
96.0 SF

H165
104.5 SF
Owner/Architect immediately.

H170
H173A

H165A

128.7 SF
H165H

H170A
15.5 SF
H165N

18.5 SF

H167E
85.4 SF

121.2 SF
1816.1 SF

239.7 SF

153.5 SF

H158M1
H158M3
H186
SITE CLASS: N/A

H189

H158A

80.6 SF
H165M
40.9 SF
49.3 SF

287.3 SF
H166C
H165J
33.2

73.0 SF
28.6

63.8

H165B
SF

H167
SF

SF
59.4 SF

H173C

67.0 SF
H165K

H167D
995.9 SF
H190

H180

H178

H173

238.8 SF
H179

1593.9 SF

H166C1
SPECTRAL RESPONSE COEFFICIENT: N/A

H197
169.4 SF
H173D

H158L

130.1 SF
61.5 SF

H191

H167B
52.1 SF
238.0 SF

H167C
H165F
H193

52.5
182.1 SF
H177C

H177A
H177B

SF
200.5 SF

443.1 SF

52.4 SF
H158H

H158K
71.9 SF
70.7 SF

67.9 SF
137.2 SF

539.3 SF
74.5 SF
SEISMIC DESIGN CATEGORY: N/A

H177F
H192

32.6 SF
167.2 SF
164.4 SF

H174
H177D
TITLE SHEET

H158N
43.7 SF
SEISMIC DESIGN FORCE RESISTING SYSTEM: N/A

H175

522.5 SF
1050.4 SF

H165C
H165D
H158B
H158C
H177

804.7 SF
H158D
H158E
10.0 SF
H177E

11.8 SF

437.5 SF
419.8 SF

116.6 SF

H165E
121.0 SF

112.9 SF

123.6 SF
96.3 SF

111.7 SF
H193A
DESIGN BASE SHEAR (.7E): N/A

H176

131.6 SF
H197B

H197C

105.9 SF
H176A

H158C1

H158B1
H158G
43.4 SF

20.7 SF
H158F
61.2
SF

76.9
SF
OFFICE

93.8 SF

H193B
ANALYSIS PROCEDURE: N/A HE125F HE125E HE124F HE124G HE124J HE124K

400.3 SF
HE101EA HE125H HE125D HE124H

100.7 SF
OFFICE

H193C
169.0 SF 137.8 SF 92.0 SF 91.4 SF 91.2 SF 91.3 SF 91.7 SF 91.3 SF 91.5 SF 91.0 SF 91.2 SF 207.5 SF 210.7 SF 210.2 SF 211.9 SF HE118
32.5
HE101E SF HE101D HE101C HE101B HE101A HE126C 189.5 SF
HE125J
223.8 SF HE122E HE122D HE122C HE122B
215.3 SF 139.4 SF 136.9 SF 140.0 SF

OFFICE
15.9 15.6

96.8 SF

H193D
19.2
HE124L
HE125P 353.4 SF HE125C SF HE124E SF
HE1T1 17.9 201.9 SF
HE126B SF 90.4 SF
SF
110.8 SF
89.6 SF 90.2 SF HE124M 76.9 SF HE119 SHEET NAME
9. PLUMBING INFORMATION

H193H
HE124-I
65.6 SF 91.0 SF

H193E1
13 12 11

29.0 SF

CALL
HE102B HE125G

H193E
HE101 376.6 SF HE122A
HE124D 164.7 SF

68.6 SF
136.1 SF HE125-I HE125B
139.5 SF 90.0 SF

R.R.

RM.
107.0 SF HE125K 90.1 SF HE122-I
HE100A HE122F
HE100E1 HE101H HE1SW1 HE126A 35.9 SF 40.2 SF
130.0 SF HE124N 40.8 SF HE122A1 HE120
176.3 SF HE122J

71.9 SF
16.9 46.6 HE124N1 HEIM6
L1 13.9 97.6 HE124B HE124C HE122H

A. WATER SYSTEM: N/A UNITS:N/A PEAK GPM: N/A SERVICE LINE SIZE: N/A
41.0 HE125A 47.8 SF

H193F H193G
89.7 SF SF 37.3 SF 71.1 SF 38.3 SF 23.7 HE122G 34.0 SF 41.9 SF 248.3 SF
SF

H193J
HE102C
136.8 SF
SF HE100E
HE1M2

HE126E
SF

L2 13.8
HE1M4 19.5 HE124A 19.1
54.6 SF
47.7 SF PROJECT NUMBER
F 17016 F
SF HE121A1A

39.7
14 15 16
HE125Q

70.9 SF
HE1E1

SF
HE124P

H193G1 17.0
174.0 HE1SW2 HE100C 202.3 SF 117.2 145.3 SF
70.2 SF 77.2 155.7 SF SF HE1SW3
SF HE124 -O HE122

B. SANITARY SEWER SYSTEM LOADING: N/A


206.1 SF SF 193.5 SF HE124-I HE121A1
HE125L 190.3 SF
268.6 SF HE124 HE123 1413.8 SF 38.3 SF
47.9 HE100 HE126 HE125N HE125-I HE125 99.1 SF

SF
HE126D 145.6 SF
HE102 SF 99.5 SF 99.7 SF 99.2 72.6 49.5 17.1
50.2 SF HE100F HE100D 48.4 SF SF SF 21.0 25.5 SF 47.7 SF
HE101 99.5 SF 70.4 SF SF SF SF HE117 HE1E2

C. SERVICE LINE SIZE: N/A


43.2 SF HE100F1 HE121 HE121A
HE102
HE1FL 4438.3 SF 23.0
HE103A SF
HE105
64.6 SF
SF
HE1T2
DRAWN BY
D. MINIMUM NUMBER OF PLUMBING FIXTURES REQUIRED:
21.4 200.6 SF HE107 93.6 SF
128.O SF HE115

RML
HE104A 63.4 SF 70.8 SF 76.0 SF HE114
HE103A1 HE107 HE108 HE111H 89.5 SF
90.8 SF HE109 HE111A HE111A1 291.2 SF
130.4 SF HE104 HE111F HE111D HE111B HE113 146.1 SF 17 18

371.3 SF 238.6 SF HE112 HE113G


416.4 SF 192.8 SF HE110A4 HE1FLW HE1FLM
110.8 SF HE106 136.8 SF 326.9 SF 174.5 SF
86.7 59.0 60.3 58.9 45.3 134.4 SF 135.1 SF
460.8 SF SF
SF SF SF SF
HE111 276.1 SF

T100
48.9 SF 19.8 35.6 SF 35.7
HE110A3 HE110A2 HE110A1 20.0 HE1M5
HE104A1 HE1M1 SF HE1M3 SF SF
HE111E HE111A2 HE111A3
91.1 SF HE111J HE111G HE116

WATER CLOSETS PROVIDED: MALE: N/A FEMALE: N/A


HE110J HE110-I 42.8 SF HE111C 94.5 SF 56.0 SF HE113A
44.9 60.9 SF 82.6 SF
60.8 SF 135.4 SF

92.5 SF
HE107A
1829.7 SF 117.8 SF
197.1 SF
SF 14.4 SF

HE110H
HE110K 353.1 SF
HE110G

20.2
155.8 SF
HE113K HE113B
136.2 SF
HE113H
558.0 SF
CHECKED BY
258.1 SF

KEH
HE110 SF
HE106B 710.6 SF

LAVATORIES PROVIDED: MALE: N/A FEMALE: N/A


SF HE113J 20.2
HE113-I
20.5 SF
HE110F1
HE110B HE110E
HE109A HE110C HE110D HE110F
137.7 SF 101.0 SF 284.9 SF 212.7 SF 142.7 SF 213.0 SF
190.9 SF 138.6 SF 76.7 SF
HE106C HE106D HE107C HE107D HE113C HE113D HE113E HE113F

OTHER: SERVICE SINK: PROVIDED: N/A


139.3 SF
91.6 SF 91.7 SF 91.8 SF 92.4 SF

DATE
05/09/2018

SCALE
N 1" = 50'-0"

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

SYMBOLS: (SEE C, S, P, M & E SHEETS FOR ADDITIONAL SYMBOLS) WORKING DRAWINGS ORGANIZATION SYSTEM MASTER KEYNOTE LIST
Master Keynote Legend

Key Value Keynote Text

THE ConDoc SYSTEM:


078100.A APPLIED FIREPROFFING
DETAIL IDENTIFICATION 079200.A JOINT SEALANTS
1. A BASIC PRINCIPAL OF ConDoc IS TO SIMPLIFY THE PROCESS OF PRODUCING WORKING DRAWINGS,
SHEET COORDINATE LOCATION WITHOUT ANY COMPROMISE OF QUALITY OR CONTENT OF THE DOCUMENTS. THE USE OF KEYNOTE 081113.A HOLLOW METAL FRAMES
SHEET NUMBER SYMBOLS ON THE DRAWINGS, WHICH CROSS-REFERENCE TO NOTES IN LEGENDS (ON THE DRAWINGS) 081416.A FLUSH WOOD DOOR
IS AN ESSENTIAL ELEMENT OF THE METHODOLOGY. THESE KEYNOTE SYMBOLS ALLOW FOR TEXT
A REDUCTION AND SERVE THE FURTHER PURPOSE OF LINKING INFORMATION ON THE DRAWINGS 084126.A BUTT GLAZED STOREFRONT SYSTEM A
NAME 088810.A FIRE RATED GLASS AND FRAMING SYSTEM
SPACE IDENTIFICATION WITH THAT CONTAINED IN THE SPECIFICATIONS THROUGH THE USE OF A NUMBERING SYSTEM
XXX ROOM NAME WHICH IS COMMON TO BOTH THE DRAWINGS AND THE SPECIFICATIONS. 092116.I NON-STRUCTURAL METAL FRAMING SEALS
ROOM NUMBER 2. 092900.A GYPSUM BOARD
THE ORGANIZATION OF THE KEYNOTING SYSTEM ON THE DRAWINGS, WITH THE KEYNOTE REFERENCE
092900.B SOUND ATTENUATION BATTS C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.
NUMBERS RELATED TO THE SPECIFICATIONS SECTIONS NUMBERING SYSTEM, SHALL NOT CONTROL
THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
THE CONTRACTOR IN DIVIDING THE WORK AMONG THE SUBCONTRACTORS OR IN ESTABLISHING THE
X
095113.A ACOUSTICAL PANEL CEILINGS PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
STRUCTURAL GRID LINE EXTENT OF WORK TO BE PERFORMED BY ANY TRADE. 095113.B CEILING GRID RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
3. 096513.B RESILIENT BASE RIGHTS, INCLUDING THE COPYRIGHT.
USING THE ConDoc SYSTEM, "MATERIALS KEYING LEGEND" NOTES ARE NOT REPEATED ON CONSECUTIVE
DETAILS ON THE SAME SHEET. DIFFERENCES AND NEW MATERIALS ARE NOTED AS NECESSARY 099123.A INTERIOR PAINTING
102600.A BUMPER GUARD
INTERIOR ELEVATION 4. FOR THIS PROJECT, ONLY THE "A" SHEETS CONFORM TO THE ConDoc SYSTEM MATERIAL KEYING LEGEND. 104413.B FIRE EXTINGUISHER CABINET
NOTES:
DETAIL NUMBER
104416.C FIRE EXTINGUISHER
SHEET NUMBER
123661.A SOLID SURFACING COUNTERTOPS
1. ALPHA-NUMERIC SYSTEM CODE 260000.A INTERIOR LIGHTING - SEE 'E' SHEETS

DOOR NUMBER DRAWING NUMBER


XXX

X WALL TYPE IDENTIFICATION A100 GROUP DESIGNATION (ITEM 3)

DISCIPLINE PREFIX (ITEM 2)


X WINDOW TYPE IDENTIFICATION

B XX DOOR & WINDOW DETAIL B


2. BASIC DISCIPLINE IDENTIFICATION
IDENTIFICATION
DISCIPLINE PREFIX DISCIPLINE DISCIPLINE PREFIX DISCIPLINE
T TITLE, PROJECT
0'-0" INFORMATION M MECHANICAL
DATUM ELEVATION
DATUM C CIVIL E ELECTRICAL
D DEMOLITION FP FIRE PROTECTION

XXXX
X' XX"
A ARCHITECTURAL K KITCHEN
BUILDING ELEVATION S STRUCTURAL R ROOF
P PLUMBING LS LIFE SAFETY

3. DRAWING GROUPS IDENTIFICATION ('A' DRAWINGS)


BATT INSULATION A000, A001, ETC. GENERAL
A100, A101, ETC. PLANS
RIGID INSULATION A200, A201, ETC. EXTERIOR ELEVATIONS
A300, A301, ETC. BUILDING AND WALL SECTIONS
CMU WALL
A400, A401, ETC. INTERIOR ELEVATIONS
A500, A501, ETC. DETAILS
STEEL STUD &
C GWB WALL- SEE A600, A601, ETC. SCHEDULE AND DIAGRAMS
C
WALL TYPES
4. MATERIALS KEYING

NEW CONCRETE
PREFIX NUMBER; CORRESPONDS TO SPECIFICATION SECTION
FOR MATERIALS

REVISION NUMBER
(SHEET SPECIFIC)

X
REVISION MARK
009250.A
SUFFIX LETTER; IDENTIFIES THE SPECIFIC ITEM LISTED IN LEGEND

MATERIALS (SEE DRAWINGS AND SPECIFICATIONS FOR SPECIAL MATERIALS)


CLOUDED AREA
OF REVISION ABBREVIATIONS
SUPPLY AIR DIFFUSER
G Gas HB Hose Bibb
SEE 'M' SHEETS AB Anchor Bolt HC, H/C Handicapped QT Quarry Tile 1 Addendum 1 11/11/16
A/C Air Conditioned GA Gauge
GB Grab Bar HDW Hardware
APC Acoustical Panel Ceiling HM Hollow Metal R Riser
RETURN AIR GRILL ACE Air Conditioning Unit GL Glass RCP Reflected Ceiling Plan
GR Grade HP High Point
AD Access Door HR Hour RD Roof Drain
SEE 'M' SHEETS GWB Gypsum Wall Board
ADJ Adjustable HTG Heating RECEP Receptacle
AHJ Air Handler Unit GYP Gypsum REF Refrigerator
HW Hot Water
ALUM Aluminum HP Horsepower REINF Reinforcing, Reinforced
INCANDESCENT LIGHT FIXTURE AP Access Panel HB Hose Bibb REQ'D Required
D HC, H/C Handicapped Hz Hertz (Cycles) D
AS Aluminum Storefront RM Room
SEE 'E' SHEETS HDW Hardware
AFF Above Finish Floor IN Inch, Inches RO Rough Opening
HM Hollow Metal
HP High Point INSUL Insulation
EXIT SIGN INT Interior S Stain
BIT Bitumen HR Hour SB Sign Block
SEE 'E' SHEETS HTG Heating SCHD Schedule
PROJECT NUMBER: H51-50068
HW Hot Water JT Joint
SEC Section
EXHAUST FANS CA Compressed Air HP Horsepower
KIT Kitchen SF Square Feet DHEC PROJECT NUMBER: 580145
CAB Cabinet Hz Hertz (Cycles) SH Shelving, Shelf
KP Kick Plate
SEE 'M' & 'E' SHEETS CB Chalk Board SIM Similar
CCT
CI
Cubicle Curtain Track
Cast Iron
IN
INSUL
INT
Inch, Inches
Insulation
Interior
LAV
LKR
Lavatory
Locker
SPECS
SS
STC
Specification
Sanitary Sewer
Sound Transmission Coefficient
CONSTRUCTION
CG Corner Guard
DOCUMENTS
GWB CEILING & SOFFIT LP Low Point
CJ Control Joint LPD Light Proof Door STOR Storage
CL Center Line JT Joint STRUCT Structural
5/8/2018 2:52:17 PM
CLG Ceiling MAX Maximum S/S, SS Stainless Steel
CMU Concrete Masonry Unit KIT Kitchen ST Storm Sewer
KP Kick Plate MB Marker Board
COL Column MECH Mechanical SAT Suspended Acoustic Ceiling
APC SYSTEM (ACOUSTICAL PANEL CEILING)
COMP
CONC
Compressor
Concrete LAV
LKR
Lavatory
Locker
MES
MIN
Metal Edge Strip
Minimum T Tread STORM EYE INSTITUTE
TB Tack Board
OPTICAL SHOP
CONT Continuous MISC Miscellaneous
CONST Construction LP Low Point TCA Tile Council of America
LPD Light Proof Door MLDG Moulding
CPT Carpet MO Masonry Opening TBB Telephone Backboard
CT
CTR
Ceramic Tile
Counter MAX
MB
Maximum
Marker Board
MOD
MSL
Modified
Mean Sea Level
TYP
TEL
Typical
Telephone H51-50068
1 HOUR RATED WALL CO Clean Out TERR Terrazzo
MECH Mechanical MT Metal Threshold
CW Cold Water TOIL, T Toilet
CWP Concrete Wall Panel MES Metal Edge Strip MTD Mounted
TS Tackstrip
167 ASHLEY AVE
MIN Minimum MWP Metal Wall Pa
CBB Computer Backboard
MISC Miscellaneous
CHARLESTON, SC 29425
2 HOUR RATED WALL NIC Not in Contract UL Underwriters Laboratories
E DF Drinking Fountain MLDG Moulding UNO Unless Noted Otherwise E
DIA Diameter MO Masonry Opening
MOD Modified OBS Obscure
DIAG Diagonal OC On Center V Vinyl, Volts
3 HOUR RATED WALL DISP Dispenser MSL Mean Sea Level VCT Vinyl Composition Tile
OH Overhead
DS Downspout MT
MTD
Metal Threshold
Mounted OPNG Opening VEST Vestibule ROSENBLUM COE
DWGS Drawings OPP Opposite VTR Vent Thru Roof
MWP
GA
Metal Wall PaG
Gauge
Gas
OFD Overflow Drain ARCHITECTS,
EL Elevation WC Water Closet
CALLOUT OF DETAIL ELEC Electrical GB
GL
Grab Bar
Glass P Paint WCO Wall Clean-Out INC.
ELEV Elevator PART HT Partition Height WD Wood
EJ Expansion Joint GR Grade WH Waterheater
PLAN OR
GWB Gypsum Wall Board PB Pegboard
WP Waterproof(ing)
1643 MEANS STREET
DETAIL EP Electric Panel PROP Property Line
NUMBER EQUIP Equipment GYP Gypsum WP Working Point CHARLESTON, SC 29412
PL Plate
ETV Educational Television PLAS Plaster WS Weatherstrip
XX
XXX
EBB ETV Backboard PLWD Plywood 843.577.6073
EXT'G Existing PSB Pencil Sharpener Block
EXT Exterior PH Phase
EWC Electric Water Cooler PT Preservative Treated
SHEET NUMBER EXP Exposed, Expansion POLYCARB Polycarbonate
PF Prefinished
FCO Floor Clean Out
FD Floor Drain
FDC Fire Department Connection
FE Fire Extinguisher ABBREVIATIONS, LEGEND, &
FEC Fire Extinguisher & Cabinet
S SPEAKER FFE Finish Floor Elevation CONDOC
FIN Finish
FL Floor
SHEET NAME
FT Foot, Feet
FTG Footing
PROJECT NUMBER
FS Fire Sealant
F 17016 F
nel
DRAWN BY
WBN

CHECKED BY

DATE
KEH

05/09/2018
T101
SCALE

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

LEGEND

PROJECT SCOPE

NEW PARTITION & DOOR 1 HOUR RATED ASSEMBLY

A A

SEALS
HA106
HA107
C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.
EXISTING PARTITION & DOOR 2 HOUR RATED ASSEMBLY THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING THE COPYRIGHT.

HA114 HA113 HA110 NOTES:

DEMO'D PARTITION & DOOR 3 HOUR RATED ASSEMBLY 1. EXISTING RATED DOOR ASSEMBLY
HA105 2. NEW RATED DOOR ASSEMBLY

HA108 3. EXISTING FIRE HOSE LOCATION

HA1FL3
B HA104 B

HA115

NOTE 1 - 2 HR

HA112 HA109

PEDIATRIC WAITING
4
388 SF
HA116 N.I.C
NOTE 1 - 2 HR

C C
HA117

HA118

OPTICAL LAB
3
44 SF

HA119
RECEPTION
7
778 SF
N.I.C

104413.B
104416.C
OPTICAL
2
HA120
391 SF

2 - COMMOM PATH OF TRAVEL = 29'-6"


HA121

D D
NOTE 3

PROJECT NUMBER: H51-50068

HA122 DHEC PROJECT NUMBER: 580145

HA1FL 2B - EXIT ACCESS TRAVEL


DISTANCE = 91'-6"
1A - EXIT ACCESS TRAVEL
DISTANCE = 10'-2"
CONSTRUCTION
NOTE 2 - 1 HR
DOCUMENTS 5/8/2018 2:52:14 PM
1B - EXIT ACCESS TRAVEL 1A - EXIT ACCESS TRAVEL
DISTANCE = 68'-0" DISTANCE = 34'-10"
STORM EYE INSTITUTE
OPTICAL SHOP
1 - COMMOM PATH OF TRAVEL = 17'-2"

HA123 EXAM ROOM


5
H51-50068
113 SF
167 ASHLEY AVE
CHARLESTON, SC 29425
E E
Keynote Legend
WELCOME AREA
1
Key Value Keynote Text
460 SF HA130
N.I.C
HA131
N.I.C
ROSENBLUM COE
078100.A APPLIED FIREPROFFING ARCHITECTS,
079200.A JOINT SEALANTS INC.
HA124 EXAM ROOM 081113.A HOLLOW METAL FRAMES
6 1643 MEANS STREET
110 SF 081416.A FLUSH WOOD DOOR CHARLESTON, SC 29412
084126.A BUTT GLAZED STOREFRONT
SYSTEM 843.577.6073
NOTE 1 - 1 HR
088810.A FIRE RATED GLASS AND FRAMING
SYSTEM
092116.I NON-STRUCTURAL METAL
FRAMING
092900.A GYPSUM BOARD
092900.B SOUND ATTENUATION BATTS LIFE SAFETY PLAN
095113.A ACOUSTICAL PANEL CEILINGS
095113.B CEILING GRID
SHEET NAME
096513.B RESILIENT BASE
PROJECT NUMBER
F 099123.A INTERIOR PAINTING 17016 F
102600.A BUMPER GUARD
DRAWN BY
104413.B FIRE EXTINGUISHER CABINET RML
104416.C FIRE EXTINGUISHER
NOTE 1 - 2 HR
123661.A
260000.A
SOLID SURFACING COUNTERTOPS
INTERIOR LIGHTING - SEE 'E'
SHEETS
CHECKED BY

DATE
KEH

05/09/2018
LS-01
F1 LIFE SAFETY PLAN
LS-01 SCALE: 1/4" = 1'-0" N
SCALE
1/4" = 1'-0"

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

LEGEND

PROJECT SCOPE

NEW PARTITION & DOOR 1 HOUR RATED ASSEMBLY

A HA106 A
HA107

SEALS

C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.


EXISTING PARTITION & DOOR 2 HOUR RATED ASSEMBLY THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
HA114 HA113 HA110 DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING THE COPYRIGHT.

HA105
NOTES:
DEMO'D PARTITION & DOOR 3 HOUR RATED ASSEMBLY 1. DONOR WALL TO BE REMOVED, STORED AND
HA108 REINSTALLED AT DESIGNATED LOCATION.

2. REMOVE EXISTING WALL AND BASE COMPLETELY, REFER


TO PLUMBING, MECHANICAL AND ELECTRICAL DRAWINGS
FOR POSITION OF EXISTING DEVICES AND SERVICES. PATCH
DAMAGED FINISHES TO MATCH EXISTING WHERE SHOWN TO
REMAIN.

3. REMOVE EXISTING DOOR AND FRAME COMPLETELY

4. REMOVE EXISTING DOOR AND FRAME COMPLETELY,


INFILL OPENING TO MATCH EXISTING WHERE WALL IS TO
HA1FL3 REMAIN.
HA104
5. REMOVE PORTION OF WALL AS SHOWN FOR NEW DOOR
APPLICATION. CONTRACTOR TO PATCH/REPAIR EXISTING
HA115 WALL AS REQUIRED FOR NEW DOOR INSTALLATION AT NO
B B
COST.

6. REMOVE EXISTING FLOOR COVERING AS NOTED.

E 7. ALL CASEWORK IN THIS AREA IS TO BE REMOVED FOR


NEW DOOR ASSEMBLY IN WALL. CONTRACTOR IS TO STORE
CASEWORK WHILE DOOR IS INSTALLED AND REINSTALL
AFTER DOOR IS INSTALLED. ANY DISCREPANCIES MUST BE
BROUGHT TO THE ARCHITECTS ATTENTION PRIOR TO
HA112 HA109 REMOVAL.

8. NOT USED

9. NOT USED

HA116 ADOLESCENT WAITING ROOM 10. REMOVE PORTION OF WALL & BASE TO ACCOMMODATE
HA105 NEW STOREFRONT OPENING. CONTRACT TO RESTORE
N.I.C WALL ASSEMBLY TO 1 HOUR FIRE RATING AS REQUIRED.

11. BUILDING WILL REMAIN IN USE DURING RENOVATION.


E CONTRACTOR SHALL COORDINATE ALL MATERIAL DELIVERY
ROUTES WITH OWNER. PROVIDE TEMPORARY
CONSTRUCTION DUST PARTITION AND "STICKY MATS" AT
EACH DOOR TO CONSTRUCTION AREA
HA117
12. CONTRACTOR TO REMOVE FLOORING AT EXISTING
LOBBY TO ACCOMMODATE NEW RATED GLASS ASSEMBLY
C C
PHASE 2 AT LOBBY AREA.

13. SEE PD100 FOR DEOMLITION ON EXISTING SINKS

HA118
NOTE 1
GENERAL NOTES:
1. ALL FURNITURE IN PROJECT TO BE REMOVED & STORED
HA119 BY MUSC

RECEPTION DESK
HA128A E1 A401
N.I.C
NOTE 10
WAITING ROOM
HA120 HA128 NOTE 12

HA121

D D
NOTE 3
HA122 NOTE 11 NOTE 11
PROJECT NUMBER: H51-50068
HA1FL
DHEC PROJECT NUMBER: 580145

PHASE 1 NOTE 4
E
NOTE 3 NOTE 3 NOTE 2
CONSTRUCTION
E E

E
DOCUMENTS 5/9/2018 9:17:59 AM

HA123 NOTE 13 NOTE 13


STORM EYE INSTITUTE
OPTICAL SHOP
NOTE 6 NOTE 6 NOTE 6 NOTE 6
H51-50068
NOTE 7
167 ASHLEY AVE
CHARLESTON, SC 29425
NOTE 2 NOTE 2 NOTE 2 HA130 HA131
E E
N.I.C N.I.C
EXAM ROOM EXAM ROOM EXAM ROOM EXAM ROOM
HA125 HA126 HA127 HA129
ROSENBLUM COE
HA124
ARCHITECTS,
NOTE 5
INC.
1643 MEANS STREET
CHARLESTON, SC 29412

843.577.6073

DEMOLITION FLOOR PLAN

SHEET NAME

PROJECT NUMBER
F 17016 F
DRAWN BY
RML

CHECKED BY

DATE
SHC

05/09/2018
D100
F1 DEMOLITION FLOOR PLAN
D100 SCALE: 1/4" = 1'-0" N SCALE
1/4" = 1'-0"

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

LEGEND

PROJECT SCOPE

NEW PARTITION & DOOR 1 HOUR RATED ASSEMBLY

A A

SEALS

C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.


EXISTING PARTITION & DOOR 2 HOUR RATED ASSEMBLY THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING THE COPYRIGHT.

NOTES:
1. NOT USED.
DEMO'D PARTITION & DOOR 3 HOUR RATED ASSEMBLY
2. EXISTING ACT CEILING GRID, FIXTURES, & DIFFUSERS TO

RCP LEGEND BE REMOVED IN ITS ENTIRETY. CONTRACTOR TO REPAIR


EXISTING FINISHES PER ALLOWANCE #1.

3. NOT USED.

4. APPROX. LOCATION OF EXISITNG TRACK LIGHTING,


CONTRACTOR TO VERIFY IN FIELD. CONTRACTOR TO
EXISTING TO REMAIN REMOVE STORE AND REUSE AT NEW DONOR WALL
CAN LIGHT LOCATION.

5. CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS


PRIOR TO DEMOLITION.

2x2 LIGHT FIXTURE 2x4 LIGHT FIXTURE


B B

TRACK LIGHTING
HVAC RETURN

AREA OF NEW CEILING HVAC SUPPLY

CEILING TO REMAIN

N.I.C

C C

PHASE 2 AREA OF CEILING DEMOLITION

NOTE 3 NOTE 3 NOTE 3


NOTE 4

CEILING TO REMAIN
NOTE 2
N.I.C

NOTE 3 NOTE 3

NOTE 3

D D

PROJECT NUMBER: H51-50068

DHEC PROJECT NUMBER: 580145

CEILING TO REMAIN CONSTRUCTION


PHASE 1 AREA OF CEILING DEMOLITION DOCUMENTS 5/9/2018 9:18:00 AM

STORM EYE INSTITUTE


OPTICAL SHOP
H51-50068
167 ASHLEY AVE
CHARLESTON, SC 29425
E E
N.I.C N.I.C
Keynote Legend
Key Value Keynote Text
NOTE 2 NOTE 2 NOTE 2 NOTE 2 ROSENBLUM COE
NOTE 5 NOTE 5 NOTE 5 NOTE 5
078100.A APPLIED FIREPROFFING ARCHITECTS,
079200.A JOINT SEALANTS INC.
081113.A HOLLOW METAL FRAMES 1643 MEANS STREET
081416.A FLUSH WOOD DOOR CHARLESTON, SC 29412
084126.A BUTT GLAZED STOREFRONT
SYSTEM 843.577.6073
088810.A FIRE RATED GLASS AND FRAMING
SYSTEM
092116.I NON-STRUCTURAL METAL
FRAMING
092900.A GYPSUM BOARD
092900.B SOUND ATTENUATION BATTS DEMOLITION REFLECTED CEILING
095113.A ACOUSTICAL PANEL CEILINGS PLAN
095113.B CEILING GRID
SHEET NAME
096513.B RESILIENT BASE
PROJECT NUMBER
F 099123.A INTERIOR PAINTING 17016 F
102600.A BUMPER GUARD
DRAWN BY
104413.B FIRE EXTINGUISHER CABINET RML
104416.C FIRE EXTINGUISHER
123661.A
260000.A
SOLID SURFACING COUNTERTOPS
INTERIOR LIGHTING - SEE 'E'
SHEETS
CHECKED BY

DATE
SHC

05/09/2018
D120
DEMOLITION REFLECTED
F1 CEILING PLAN N SCALE
D120 SCALE: 1/4" = 1'-0" 1/4" = 1'-0"

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

LEGEND

PROJECT SCOPE

NEW PARTITION & DOOR 1 HOUR RATED ASSEMBLY

A HA106 A
HA107

SEALS

C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.


EXISTING PARTITION & DOOR 2 HOUR RATED ASSEMBLY THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
HA114 HA113 HA110 RIGHTS, INCLUDING THE COPYRIGHT.

NOTES:
HA105
DEMO'D PARTITION & DOOR 3 HOUR RATED ASSEMBLY 1. REPAIR WALL WHERE WALL PREVIOUSLY REMOVED.
HA108
2. INFILL EXISTING WINDOW OPENING WITH GWB. REFER
TO D1/A501

3. EXISTING DIRTT WALL ASSEMBLY TO REMAIN.

4. EXISTING COLUMNS TO BE V.I.F. BY CONTRACTOR TO


CONFIRM ELECTRICAL ACCESS ALONG COLUMN FINISH.

5. EXISTING FLOOR FINISH TO REMAIN WHERE SPECIFIED -


CONTRACTOR SHALL PROTECT AT ALL TIMES. ANY
DAMAGE AS A RESULT OF CONSTRUCTION SHALL BE
HA1FL3 REPAIRED TO "PRECONSTRUCTION" CONDITION AT NO
HA104 COST.

6. FURNITURE IS SHOWN FOR REFERENCE ONLY. - N. I. C.


B HA115 B
7. NEW STOREFRONT WALL TO BE ALIGNED WITH EXISTING
EDGE OF SOFFIT ABOVE.

8. EXISTING PORTION OF WALL TO BE FUR'D OUT TO ALIGN


E WITH PROJECTED PORTION OF WALL FOR DONOR WALL
APPLICATION. CONTRACTOR TO VARIFY CONSTRUCTION IN
FIELD.

9. EXISTING RECEPTION DESK TO REMAIN.


HA112 HA109
10. NEW SHAFT WALL TO ACCOMMODATE NEW RISER.
REFER TO "P" DRAWING FOR MORE DETAILS.

NOTE 3
PEDIATRIC WAITING 11. CONTRACTOR SHALL USE THIS EXIT/ ENTRY INTO THE
4 PROJECT SCOPE. CONTRACTORS LAYDOWN AREA SHALL
388 SF BE IN THE MUSC "HORSESHOE" JUST OUTSIDE OF THIS
HA116 DOORWAY. OWNER/ARCHITECT WILL COORDINATE EXACT
N.I.C.
NOTE 6 PARAMETERS PRIOR TO CONSTRUCTION.

E
NOTE 5
Sim
F7 F7
HA117 A501
A501 NOTE 3
A
C C
NOTE 9
GENERAL NOTES:

4"
PHASE 2 GEN NOTE 1. PAINT ALL DISTURBED AND NEW

1' - 10"
HA118
A1 A1 WALLS, CORNER TO CORNER, INCLUDING

ALIGN
OPTICAL LAB
3 SOFFITS.
3
44 SF
A1 ALIGN

4' - 2"
4' - 2" 10' - 8"
HA119
A ELEVATOR LOBBY
B HOLD
RECEPTION HA1FL2
7 081416.A B6 A401
738 SF
778 SF 123661.A

9"
N.I.C.
3' - 9 1/2"

FIELD VERIFY
3' - 6"

15' - 0" +/-


NOTE 5 CLEAR
SF1
2' - 0" 4' - 2 1/2" 2' - 0"
HA120 A1
104413.B
NOTE 7
104416.C OPTICAL
B3 A401 A3
2
391 SF
HA121 B1 NOTE 6 088810.A

NOTE 4
NOTE 5
NOTE 7
D D
10' - 0"

084126.A
HA122
SF2
PROJECT NUMBER: H51-50068
081416.A
HA1FL DHEC PROJECT NUMBER: 580145
2

PHASE 1 A A1
E
CONSTRUCTION
EXISTING FLOOR EXISTING FLOOR
E E
DOCUMENTS
CLR
6"

NEW FLOOR NEW FLOOR 5/8/2018 2:51:57 PM

NOTE 1
E NOTE 10

STORM EYE INSTITUTE


A1 A401 F2

081416.A
OPTICAL SHOP
HA123 EXAM ROOM
EQ.

5 WELCOME AREA

H51-50068
113 SF 1
460 SF
NOTE 6
13' - 3"
167 ASHLEY AVE
NOTE 8 CHARLESTON, SC 29425
C2 A401 C4
E HA130 HA131 E
A
C1 N.I.C. N.I.C.
ROSENBLUM COE
EQ.

HA124 EXAM ROOM


6
ARCHITECTS,
NEW FLOOR

Keynote Legend
110 SF INC.
EXISTING
FLOOR

ALIGN

081416.A NOTE 2 Key Value Keynote Text


1 1643 MEANS STREET
CHARLESTON, SC 29412
078100.A APPLIED FIREPROFFING
079200.A JOINT SEALANTS 843.577.6073
081113.A HOLLOW METAL FRAMES
081416.A FLUSH WOOD DOOR
D1 D1 084126.A BUTT GLAZED STOREFRONT
A501 A501 SYSTEM
088810.A FIRE RATED GLASS AND FRAMING
SYSTEM FLOOR PLAN
NOTE 11
092116.I NON-STRUCTURAL METAL
FRAMING
SHEET NAME
092900.A GYPSUM BOARD
PROJECT NUMBER
F 092900.B SOUND ATTENUATION BATTS 17016 F
095113.A ACOUSTICAL PANEL CEILINGS
DRAWN BY
095113.B CEILING GRID RL
096513.B RESILIENT BASE
099123.A
102600.A
104413.B
INTERIOR PAINTING
BUMPER GUARD
FIRE EXTINGUISHER CABINET
CHECKED BY

DATE
KEH

05/09/2018
A101
104416.C FIRE EXTINGUISHER
F1 FLOOR PLAN
N 123661.A SOLID SURFACING COUNTERTOPS SCALE
1/4" = 1'-0"
A101 SCALE: 1/4" = 1'-0"
260000.A INTERIOR LIGHTING - SEE 'E'
SHEETS
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

LEGEND

PROJECT SCOPE

NEW PARTITION & DOOR 1 HOUR RATED ASSEMBLY

HA106
A HA107 A

SEALS

C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.


EXISTING PARTITION & DOOR 2 HOUR RATED ASSEMBLY THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
HA114 HA113 HA110 RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING THE COPYRIGHT.

HA105 NOTES:

HA108 DEMO'D PARTITION & DOOR 3 HOUR RATED ASSEMBLY


1. CONTRACTOR TO BUILD TEMPORARY WALL DURING
PHASE CONSTRUCTION TO CONTAIN CONSTRUCTION
DEBRIS. SEAL TO PREVENT DUST MIGRATION.

2. BUILDING WILL REMAIN IN USE DURING RENOVATION.


CONTRACTOR SHALL COORDINATE ALL MATERIAL
DELIVERY ROUTES WITH OWNER. PROVIDE TEMPORARY
CONSTRUCTION DUST PARTITION AND "STICKY MATS" AT
EACH DOOR TO CONSTRUCTION AREA.

3. CONTRACTOR TO CONSTRUCT A TEMPORARY 1 HOUR


HA1FL3 RATED FIRE BARRIER AFTER THE DEMOLITION OF WALL
HA104
FOR NEW STOREFRONT APPLICATION IS TO CONTAIN
CONSTRUCTION AND PROVIDE A FIRE RESISTANCE
RATING FROM THE PROJECT AREA AND ELEVATOR
HA115
LOBBY.
B B
4. CONTRACTOR IS TO REFER TO MEP&FP SHEETS FOR
MORE INFORMATION REGARDING PHASING OF THOSE
DISCIPLINES.
E

HA112 HA109

PEDIATRIC WAITING
4
388 SF
HA116 N.I.C

HA117
PHASING LEGEND

C PHASE 2 C

WALK OFF MATT


HA118
OPTICAL LAB
3
44 SF
TEMPORARY WALL
HA119
RECEPTION
7
778 SF TEMPORARY 1 HOUR RATED WALL
N.I.C

NOTE 3

HA120

OPTICAL
2
391 SF
HA121 NOTE 1

D NOTE 1
D

PHASE 2
HA122

PROJECT NUMBER: H51-50068


HA1FL
NOTE 2 DHEC PROJECT NUMBER: 580145
NOTE 2
PHASE 1 E

CONSTRUCTION
DOCUMENTS 5/8/2018 2:51:58 PM
NOTE 1

HA123 EXAM ROOM


STORM EYE INSTITUTE
5
113 SF
WELCOME AREA
1 OPTICAL SHOP
H51-50068
460 SF

167 ASHLEY AVE


CHARLESTON, SC 29425
HA130 HA131
E N.I.C N.I.C
E
Keynote Legend

HA124 EXAM ROOM


Key Value Keynote Text ROSENBLUM COE
6 ARCHITECTS,
110 SF 078100.A APPLIED FIREPROFFING
079200.A JOINT SEALANTS
INC.
081113.A HOLLOW METAL FRAMES 1643 MEANS STREET
081416.A FLUSH WOOD DOOR CHARLESTON, SC 29412
084126.A BUTT GLAZED STOREFRONT
843.577.6073
SYSTEM
088810.A FIRE RATED GLASS AND FRAMING
SYSTEM
092116.I NON-STRUCTURAL METAL
FRAMING
092900.A GYPSUM BOARD
PHASING PLAN
092900.B SOUND ATTENUATION BATTS
095113.A ACOUSTICAL PANEL CEILINGS
095113.B CEILING GRID SHEET NAME

096513.B RESILIENT BASE PROJECT NUMBER


F 099123.A INTERIOR PAINTING 17016 F
102600.A BUMPER GUARD DRAWN BY
104413.B FIRE EXTINGUISHER CABINET RML

A102
104416.C FIRE EXTINGUISHER
CHECKED BY
123661.A SOLID SURFACING COUNTERTOPS SHC
260000.A INTERIOR LIGHTING - SEE 'E'
SHEETS DATE
05/09/2018
F1 PHASING PLAN
A102 SCALE: 1/4" = 1'-0" N SCALE
1/4" = 1'-0"

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

LEGEND

PROJECT SCOPE

NEW PARTITION & DOOR 1 HOUR RATED ASSEMBLY

A A

SEALS

C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.


EXISTING PARTITION & DOOR 2 HOUR RATED ASSEMBLY THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING THE COPYRIGHT.

NOTES:
1. NOT USED.
DEMO'D PARTITION & DOOR 3 HOUR RATED ASSEMBLY
2. EXISTING ACT CEILING GRID, FIXTURES, & DIFFUSERS TO

RCP LEGEND BE REMOVED IN ITS ENTIRETY. CONTRACTOR TO REPAIR


EXISTING FINISHES PER ALLOWANCE #1.

3. NOT USED.

4. APPROX. LOCATION OF EXISITNG TRACK LIGHTING,


CONTRACTOR TO VERIFY IN FIELD. CONTRACTOR TO
EXISTING TO REMAIN REMOVE STORE AND REUSE AT NEW DONOR WALL
CAN LIGHT LOCATION.

5. CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS


PRIOR TO DEMOLITION.

2x2 LIGHT FIXTURE 2x4 LIGHT FIXTURE


B B

TRACK LIGHTING
HVAC RETURN

AREA OF NEW CEILING HVAC SUPPLY

CEILING TO REMAIN

N.I.C

C C

PHASE 2 AREA OF CEILING DEMOLITION

NOTE 3 NOTE 3 NOTE 3


NOTE 4

CEILING TO REMAIN
NOTE 2
N.I.C

NOTE 3 NOTE 3

NOTE 3

D D

PROJECT NUMBER: H51-50068

DHEC PROJECT NUMBER: 580145

CEILING TO REMAIN CONSTRUCTION


PHASE 1 AREA OF CEILING DEMOLITION DOCUMENTS 5/8/2018 2:52:00 PM

STORM EYE INSTITUTE


OPTICAL SHOP
H51-50068
167 ASHLEY AVE
CHARLESTON, SC 29425
E E
N.I.C N.I.C
Keynote Legend
Key Value Keynote Text
NOTE 2 NOTE 2 NOTE 2 NOTE 2 ROSENBLUM COE
NOTE 5 NOTE 5 NOTE 5 NOTE 5
078100.A APPLIED FIREPROFFING ARCHITECTS,
079200.A JOINT SEALANTS INC.
081113.A HOLLOW METAL FRAMES 1643 MEANS STREET
081416.A FLUSH WOOD DOOR CHARLESTON, SC 29412
084126.A BUTT GLAZED STOREFRONT
SYSTEM 843.577.6073
088810.A FIRE RATED GLASS AND FRAMING
SYSTEM
092116.I NON-STRUCTURAL METAL
FRAMING
092900.A GYPSUM BOARD
092900.B SOUND ATTENUATION BATTS DEMOLITION REFLECTED CEILING
095113.A ACOUSTICAL PANEL CEILINGS PLAN
095113.B CEILING GRID
SHEET NAME
096513.B RESILIENT BASE
PROJECT NUMBER
F 099123.A INTERIOR PAINTING 17016 F
102600.A BUMPER GUARD
DRAWN BY
104413.B FIRE EXTINGUISHER CABINET RML
104416.C FIRE EXTINGUISHER
123661.A
260000.A
SOLID SURFACING COUNTERTOPS
INTERIOR LIGHTING - SEE 'E'
SHEETS
CHECKED BY

DATE
SHC

05/09/2018
A120
DEMOLITION REFLECTED
F1 CEILING PLAN N
A120 SCALE: 1/4" = 1'-0"
SCALE
1/4" = 1'-0"

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

LEGEND

PROJECT SCOPE

NEW PARTITION & DOOR 1 HOUR RATED ASSEMBLY

A A

SEALS

C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.


EXISTING PARTITION & DOOR 2 HOUR RATED ASSEMBLY THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING THE COPYRIGHT.

NOTES:
DEMO'D PARTITION & DOOR 3 HOUR RATED ASSEMBLY 1. EXISTING TRACK LIGHTING FROM PREVIOUS DONOR
WALL LOCATION TO BE REINSTALLED BY CONTRACTOR AT
NEW DONOR WALL LOCATION. EXACT LOCATION TO BE

RCP LEGEND DETERMINED ON SITE WITH ARCHITECTS AND/OR OWNER


APPROVAL. REPAIR TRACK AS NEEDED.

2. NEW CEILING LIGHTS & FIXTURES

3. ALL EXISTING ACT, LIGHTS AND FIXTURES TO REMAIN.

EXISTING TO REMAIN 4. CENTER CAN LIGHTS IN GRID UNLESS NOTE OTHERWISE.


CAN LIGHT
5. EXISTING SOFFIT TO REMAIN

6. AREA OF EXISTING LIGHT TO BE REPAIRED AS


NECESSARY
2x2 LIGHT FIXTURE 2x4 LIGHT FIXTURE
B B

TRACK LIGHTING
HVAC RETURN

8' - 0"
AREA OF NEW CEILING HVAC SUPPLY

PEDIATRIC WAITING
4
388 SF
8' - 4" 8' - 0"
8' - 0"
N.I.C

NOTE 3
C C
GENERAL NOTES:

NOTE 5 GEN NOTE 1. PAINT ALL DISTURBED AND NEW


PHASE 1 AREA OF NEW CEILING: NOTE 2 WALLS, CORNER TO CORNER, INCLUDING
SOFFITS.
8' - 0"

RECEPTION
NOTE 6

1' - 8"
7 OPTICAL LAB 5' - 0" 1' - 11"

2' - 6"
778 SF 3 F7
N.I.C 44 SF A501

9' - 0"
ELEVATOR LOBBY
HA1FL2
738 SF

1' - 0"

1' - 9"
9' - 0" 8' - 0"
ALIGN
8' - 4"
8' - 0"
OPTICAL NOTE 5
NOTE 5 2
8' - 0" 391 SF
9' - 0"
NOTE 3
NOTE 4
2' - 6"
D D

3' - 0"
4' - 3"
NOTE 5

PROJECT NUMBER: H51-50068


8' - 0"

DHEC PROJECT NUMBER: 580145

CONSTRUCTION
NOTE 3 8' - 4"
DOCUMENTS 5/8/2018 2:52:01 PM
PHASE 1 AREA OF NEW CEILING: NOTE 2

NOTE 1
STORM EYE INSTITUTE
EQ

EQ EQ
2' - 6"

EXAM ROOM 8' - 0"


5
113 SF OPTICAL SHOP
EQ 8' - 8" EQ
EQ EQ EQ
H51-50068
EQ

EQ

EQ EQ EQ EQ
167 ASHLEY AVE
CHARLESTON, SC 29425
2' - 6"
E NOTE 2 WELCOME AREA E
1
2' - 6" 9' - 0"
NOTE 2
EQ

EQ

EQ

460 SF Keynote Legend


EXAM ROOM Key Value Keynote Text ROSENBLUM COE
EQ

6
110 SF ARCHITECTS,
EQ 8' - 8" EQ 078100.A APPLIED FIREPROFFING INC.
079200.A JOINT SEALANTS
EQ EQ EQ EQ 1643 MEANS STREET
EQ

EQ

081113.A HOLLOW METAL FRAMES


CHARLESTON, SC 29412
081416.A FLUSH WOOD DOOR
EQ EQ

084126.A BUTT GLAZED STOREFRONT 843.577.6073


2' - 6"

NOTE 2
EQ

SYSTEM
088810.A FIRE RATED GLASS AND FRAMING
SYSTEM
092116.I NON-STRUCTURAL METAL
FRAMING
092900.A GYPSUM BOARD REFLECTED CEILING PLAN
092900.B SOUND ATTENUATION BATTS
095113.A ACOUSTICAL PANEL CEILINGS
SHEET NAME
095113.B CEILING GRID
096513.B RESILIENT BASE PROJECT NUMBER
F 17016 F
099123.A INTERIOR PAINTING
102600.A BUMPER GUARD DRAWN BY
RML
104413.B FIRE EXTINGUISHER CABINET
104416.C
123661.A
260000.A
FIRE EXTINGUISHER
SOLID SURFACING COUNTERTOPS
INTERIOR LIGHTING - SEE 'E'
CHECKED BY

DATE
KEH

05/09/2018
A121
SHEETS
F1 REFLECTED CEILING PLAN
A121 N
SCALE
1/4" = 1'-0"
SCALE: 1/4" = 1'-0"

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

CATEGORY D-F LAY-IN GRID LIGHT FIXTURE IBC CATEGORY D-F CAN LIGHT FIXTURE CATEGORY D-F LATERAL BRACING - REQUIRED AT ROOMS OVER 1000SF CATEGORY D-F SEISMIC CLIP CEILING LAYOUT

Tight Wall
12-gauge hanger wire

A Seismic clip A
Cross Tee
SEALS

Seismic clip or riveted


C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.
THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING THE COPYRIGHT.
Cross Tee
NOTES:

Floating Wall
Cross Tee

Cross Tee
Main Tee

Main Tee
FOR FIXTURES WEIGHING 56 LBS. OR MORE, INSTALL #12 GAUGE HANGER WIRE FOR FIXTURES WEIGHING 56 LBS. OR MORE, INSTALL #12 GAUGE HANGER WIRE
ATTACHED TO STRUCTURE ABOVE - ONE AT EACH CORNER OF FIXTURE FOR A TOTAL ATTACHED TO STRUCTURE ABOVE - ONE AT EACH CORNER OF FIXTURE FOR A TOTAL
OF FOUR. HANGER WIRES MUST BE INSTALLED VERTICAL, BUT NOT MORE THAN 1 IN 6 OF FOUR. HANGER WIRES MUST BE INSTALLED VERTICAL, BUT NOT MORE THAN 1 IN 6
OUT OF PLUMB. FOR FIXTURES WEIGHING LESS THAN 56 LBS., WIRES MAY BE OUT OF PLUMB. FOR FIXTURES WEIGHING LESS THAN 56 LBS., WIRES MAY BE
INSTALLED SLACK AT TWO CORNERS. INSTALLED SLACK AT TWO CORNERS.

B B

TYPICAL CEILING EXPANSION JOINT DETAIL CATEGORY D-F PERIMETER TREATMENT FIXED WALL CATEGORY D-F PERIMETER TREATMENT FIXED WALL

8" max. 8" max.


+-10˚ perimeter
hanger wire
6

1 ACM7 seismic clip


attach screw perimeter hanger wire
through either top
fastener opening screw attached (optional)
attach screw (optional)
through 7/8" x 7/8" wall molding tee
C C
either side
(optional)

ACM7 wall 7/8" Floating Wall


7/8" attachment clip

AIR TERMINAL / SERVICES SIESMIC RESTRAINT DETAIL CATEGORY D-F PERIMETER TREATMENT FLOATING WALL CATEGORY D-F PERIMETER TREATMENT FLOATING WALL

BASIC CONNECTIONS, PERIMETER, AND REQUIREMENTS


LATERAL SPLAY BRACING
8" max.
MIN. INTERSECTION STRENGTH LIMITS @ MT/CT 180 LBS
NO. 12 GAUGE 8" max.
HANGER
D WIRE. TYPICAL OF 2. perimeter VERTICAL HANGER WIRE 12-GAGUE @ 4'O.C. D
+-10˚ REQUIRED
hanger wire
ACM7 seismic clip
6 CONNECTION DEVICE FROM VETICAL WIRE TO THE STRUCTURE
perimeter hanger wire ABOVE MUST SUSTAIN MIN 100LBS REQUIRED
PROJECT NUMBER: H51-50068
1

CEILING GRID CLIPS AND/OR 3/4"


7/8" x 7/8 wall" molding tee
MAIN TEE CLASSIFICATIONS HEAVY-DUTY DHEC PROJECT NUMBER: 580145
LAY-IN CEILING min.
METAL CLIPS FASTENED WITH GRILLE OR TERMINAL
MECHANICAL FASTENERS TO
GRILLES, TERMINAL DEVICES
AND
1 IN 6 MAX PLUMB OF VERTICAL HANGER WIRES REQUIRED
CONSTRUCTION
CEILING GRID MAIN RUNNERS
CEILING GRID MAIN
RUNNER (TYPICAL)
7/8" PERIMETER VERTICAL HANGER WIRES NOT MORE THAN 8" FROM ALL REQUIRED DOCUMENTS 5/8/2018 2:52:05 PM
ACM7 wall
7/8" attachment clip GRID END/WALL CLEARANCE MIN 3/4"

ATTACHMENT NOTES: PERIMETER CLOSURE(MOLDING) WIDTH


STORM EYE INSTITUTE
MIN 2"
CEILING MOUNTED AIR TERMINALS OR SERVICES WEIGHING 20 LBS. OR LESS
SHALL BE POSITIVELY ATTACHED TO THE CEILING SUSPENSION MAIN RUNNERS OR OPTICAL SHOP
H51-50068
CROSS RUNNERS. AIR TERMINALS OR SERVICES WEIGHING MORE THAN 20 LBS AND
LESS THAN 56 LBS SHALL HAVE, IN ADDITION TO THE ATTACHMENTS NOTED ABOVE, GRID CONNECTION TO PERIMETER ATTACHED ON TWO ADJACENT WALLS REQUIRED
TWO NO. 12 GAUGE HANGES CONNECTED TO THE CEILING SYSTEM HANGERS OR TO
THE STRUCTURE ABOVE. WIRES MAY BE SLACK. AIR TERMINALS OR SERVICES
WEIGHING MORE THAN 56 LBS SHALL BE SUPPORTED DIRECTLY FROM THE PERIMETER TEE ENDS TIED TOGETHER REQUIRED 167 ASHLEY AVE
STRUCTURE ABOVE BY APPROVED HANGERS.
CHARLESTON, SC 29425
HORIZONTAL RESTRAINT(SPLAY WIRES OR RIGID BRACING) WITHIN
E 2" OF INTERSECTION AND SPLAYED 90 DEG. APARAT AT 45 DEG. REQUIRED(CEILINGS LARGER THAN 1000SF, E
ANGLES WHERE DESIGN CALCS NOT PROVIDED)

LIGHT FIXTURE ATTACHMENT REQUIREMENTS SERVICE APPLICATION REQUIREMENTS COMPRESSION POSTS(STRUTS) 12' O.C. IN BOTH DIRECTIONS,
STARTING 6' FROM WALLS
REQUIRED(CEILINGS LARGER THAN 1000SF, ROSENBLUM COE
WHERE DESIGN CALCS NOT PROVIDED)
ARCHITECTS,
LIGHT FIXTURE (ALL TYPES) MECHANICALLY ATTACHED TO GRID NEC SPLAY BRACING CONNECTION STRENGTH 200LBS OR THE DESIGN
410-16 (TWO PER FIXTURE UNLESS INDEPENDENTLY SUPPORTED)
180 LBS AIR TERMINALS 180 LBS
LOAD, WHICHEVER IS GREATER REQUIRED INC.
- SURFACE-MOUNTED FIXTURES ATTACHED TO GRID ≤ 20 LBS: POSITIVELY ATTACHED TO GRID PARTITION ATTACHMENT BRACING INDEPENDENT OF 1643 MEANS STREET
REQUIRED REQUIRED CEILING SPLAY BRACING CHARLESTON, SC 29412
- PENDANT-HUNG FIXTURES DIRECTLY SUPPORTED 21 TO 56 LBS - POSITIVELY ATTACHED TO GRID AND REQ'D FOR AREAS > 2,500 SF
FROM STRUCTURE WITH 9-GAGUE WIRE (OR REQUIRED TWO WIRES TO STRUCTURE (MAY BE SLACK) REQUIRED SEISMIC SEPARATION JOINT 843.577.6073
(OR FULL HEIGHT PARTITION)
APPROVED ALTERNATIVE)
- RIGID LAY-IN OR CAN LIGHT FIXTURES ≥ 57 LBS - DIRECTLY SUPPORTED TO STRUCTURE RIGID BRACING FOR CEILING PLANE ELEVATION CHANGES
HEAVY-DUTY HEAVY-DUTY REQUIRED

SPRINKLER HEADS AND OTHER PENETRATION MIN 2" DIA. OPENING


≤ 10LBS: ONE WIRE TO STRUCTURE (MAY BE SLACK) REQUIRED
CLEARANCE OR A SWING JOINT

11 TO 56 LBS: TWO WIRES FROM HOUSING TO CABLE TRAYS AND ELECTRICAL CONDUIT INDEPENDENTLY
TYPICAL SEISMIC CEILING DETAILS
REQUIRED REQUIRED
STRUCTURE (MAY BE SLACK) SUPPORTED AND BRACED

≥ 57LBS: SUPPORTED DIRECTLY TO STRUCTURE BY


REQUIRED SHEET NAME
APPROVED HANGERS
PROJECT NUMBER
F 17016 F
DRAWN BY
RML

CHECKED BY

DATE
SHC

05/09/2018
A122
SCALE
As indicated

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

INTERIOR ELEVATIONS
260000.A 260000.A 260000.A
NOTE 5

099123.A

NOTE 4
088810.A
084126.A
B.O. ACT

B.O. ACT
B.O. SOFFIT

B.O. SOFFIT
9' - 0"

9' - 0"
099123.A
8' - 0"

8' - 0"
NOTE 13 NOTE 13
A A
081416.A
SEALS

NOTE 10 NOTE 11 C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.


THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
104416.C 096513.B SF1 096513.B 2 NOTE 12
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING THE COPYRIGHT.
INTERIOR ELEVATION - INTERIOR ELEVATION - DEMOLITION LOBBY WALL
A1 OPTICAL NORTH A3 OPTICAL EAST A6 ELEVATION
A401 SCALE: 1/4" = 1'-0" NOTE 6, 16 A401 SCALE: 1/4" = 1'-0" NOTE 6, 16 A401 SCALE: 1/4" = 1'-0" NOTES:
1. EXISTING DIRTT WALL TO REMAIN.

2. GWB INFILL OVER EXISITING WINDOWS, REFER TO


D1/A501 FOR DETAILS

2' - 4" 3. INFILL OF EXISTING WALL FOR NEW DONOR WALL


APPLICATION.
NOTE 5 TYP. NOTE 5
4. LINE OF NEW WALL APPLICATION TO EXISITING WALL

5. LINE OF NEW WALL APPLICATION TO EXISITNG SOFFIT

088810.A 6. NEW FURNITURE AND EQUIMENT TO BE PROVIDED BY


081416.A OWNER

B.O. ACT

B.O. ACT
B.O. SOFFIT

B.O. SOFFIT
7. EXISTING DOOR TO BE REPLACED, FRAME TO REMAIN

9' - 0"

9' - 0"
099123.A

8' - 0"

8' - 0"
WAITING AREA
BEYOND 8. OWNER PROVIDED EQUIMENT
B B
081416.A 9. CONTRACTOR TO CORDINATE NEW 6" RUBBER BASE TO
EXISITNG MATCH EXISTING AT WALL APPLICATION.
RECEPTION
DESK BEYOND 2 SF1 10. APPROXIMITE AREA OF DEMOLITION OF EXISTING RATED
WALL ASSEMBLY. CONTRACTOR TO PREP AREA FOR NEW
096513.B 099123.A 096513.B 3 STOREFRONT GLAZING ASSEMBLY.
084126.A NEW LOBBY STOREFRONT
B6 ELEVATION 11. EXISTING FLOORING TO BE PROTECTED AT LOCATIONS
INTERIOR ELEVATION - INTERIOR ELEVATION - EFFECTED BY DEMOLITION OF WALL SECTION.
A401 SCALE: 1/4" = 1'-0" NOTE 16
B1 OPTICAL SOUTH B3 OPTICAL WEST
12. EXISTING FLOOR BASE TO BE REMOVED AT LOCATION
A401 SCALE: 1/4" = 1'-0" NOTE 6, 16 A401 SCALE: 1/4" = 1'-0" NOTE 6, 16 OF NEW STOREFRONT ASSEMBLY

13. CONTRACTOR TO REPAIR ANY DAMANGE TO EXISTING


RATED WALL ASSEMBLY TO INSURE RATED ASSEMBLY
INTEGRITY.

14. NEW DONOR WALL LOCATION TO BE IN CENTER OF


WIDTH OF PROPOSED WALL. MATCH EXISTING HORIZ. AND
VERTICAL SPACING.

15. APPROX. LOCATION OF EXISITNG TRACK LIGHTING,


CONTRACTOR TO VERIFY IN FIELD. CONTRACTOR TO
REMOVE STORE AND REUSE AT NEW DONOR WALL
LOCATION.

C 16. PAINT WALLS. AT EXISTING WALLS THAT ARE MODIFIED, C


B.O. ACT

B.O. ACT

B.O. ACT
B.O. SOFFIT

B.O. SOFFIT

B.O. SOFFIT
099123.A 099123.A 099123.A
9' - 0"

9' - 0"

9' - 0"
NOTE 2 NOTE 2 PAINT CORNER TO CORNER.
8' - 0"

8' - 0"

8' - 0"
2' - 8"

2' - 8"

2' - 8"
102600.A 102600.A
102600.A 096513.B 096513.B
096513.B
INTERIOR ELEVATION - INTERIOR ELEVATION - INTERIOR ELEVATION -
C1 WELCOME AREA SOUTH C2 WELCOME AREA WEST C4 WELCOME AREA EAST
A401 SCALE: 1/4" = 1'-0" NOTE 16 A401 SCALE: 1/4" = 1'-0" NOTE 16 A401 SCALE: 1/4" = 1'-0" NOTE 16

DONOR WALL ELEVATIONS & DETAILS

NOTE 15
D D

NOTE 16

PROJECT NUMBER: H51-50068

DHEC PROJECT NUMBER: 580145


CONTRACTOR SHALL TAKE EXTREME CARE IN REMOVING/RELOCATING
EXISTING DONOR WALL AND ALL RELATED COMPONENTS. ANY DAMAGE
THAT OCCURS AS A RESULT OF REMOVAL/RELOCATION WILL NEED TO BE
RESTORED TO “PRE PROJECT” CONDITIONS AT THE CONTRACTOR’S
EXPENSE. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS
CONSTRUCTION
ASSOCIATED WITH THE EXISTING DONOR WALL AND CONFIRM
ACCEPTABILITY WITH NEW LOCATION AS INDICATED IN CONTRACT
DOCUMENTS 5/8/2018 2:52:09 PM
DOCUMENTS. ANY REQUIRED MODIFICATIONS TO NEW LOCATION’S
SUBSTRATE TO SUPPORT THE DONOR WALL SHALL BE INCLUDED IN
CONTRACTOR’S BIDCONTRACTOR SHALL TAKE EXTREME CARE IN
REMOVING/RELOCATING EXISTING DONOR WALL AND ALL RELATED
COMPONENTS. ANY DAMAGE THAT OCCURS AS A RESULT OF STORM EYE INSTITUTE
REMOVAL/RELOCATION WILL NEED TO BE RESTORED TO “PRE PROJECT”
CONDITIONS AT THE CONTRACTOR’S EXPENSE. CONTRACTOR SHALL
FIELD VERIFY ALL DIMENSIONS ASSOCIATED WITH THE EXISTING DONOR
OPTICAL SHOP
WALL AND CONFIRM ACCEPTABILITY WITH NEW LOCATION AS INDICATED
IN CONTRACT DOCUMENTS. ANY REQUIRED MODIFICATIONS TO NEW H51-50068
LOCATION’S SUBSTRATE TO SUPPORT THE DONOR WALL SHALL BE
INCLUDED IN CONTRACTOR’S BID. CONTRACTOR SELECTED TO DO WORK
SHALL BE A QUALIFIED SIGN CONTRACTOR.
167 ASHLEY AVE
EXISTING DONOR WALL CHARLESTON, SC 29425
E1 ELEVATION
E E
A401 SCALE: 1/2" = 1'-0"
DONOR WALL EXISITING PICTURES
ROSENBLUM COE
EQ EQ Keynote Legend
ARCHITECTS,
Key Value Keynote Text
INC.
EXISITNG STRIP LIGHTING
NOTE 15 078100.A APPLIED FIREPROFFING 1643 MEANS STREET
NOTE 3 CHARLESTON, SC 29412
NOTE 16 079200.A JOINT SEALANTS
081113.A HOLLOW METAL FRAMES 843.577.6073
EXISITNG DONOR WALL 081416.A FLUSH WOOD DOOR
084126.A BUTT GLAZED STOREFRONT
SYSTEM
088810.A FIRE RATED GLASS AND FRAMING
SYSTEM
092116.I NON-STRUCTURAL METAL INTERIOR ELEVATIONS
FRAMING
092900.A GYPSUM BOARD
092900.B SOUND ATTENUATION BATTS SHEET NAME

095113.A ACOUSTICAL PANEL CEILINGS PROJECT NUMBER


F 095113.B CEILING GRID 17016 F
096513.B RESILIENT BASE DRAWN BY

099123.A INTERIOR PAINTING RML

NOTE 14
NOTE 3
NOTE 9
102600.A
104413.B
104416.C
BUMPER GUARD
FIRE EXTINGUISHER CABINET
FIRE EXTINGUISHER
CHECKED BY

DATE
SHC

05/09/2018
A401
123661.A SOLID SURFACING COUNTERTOPS
F2 NEW DONOR WALL ELEVATION
260000.A INTERIOR LIGHTING - SEE 'E'
A401 SCALE: 1/2" = 1'-0" NOTE 16 SHEETS
SCALE
As indicated

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

BACKER ROD &


SEALANT
1 HOUR RATED

2 1/2"
DECK ABOVE FRAME
DECK ABOVE
SEAL PENETRATIONS
A TO REDUCE SOUND SEAL PENETRATIONS A
TRANSMISSION TO REDUCE SOUND 15' - 0" 10' - 0"
TRANSMISSION 1 HOUR RATED
EQ EQ EQ EQ EQ EQ EQ EQ 1 HOUR RATED SEALS
GLAZING 1/4" GLAZING
095113.A 095113.A C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.
THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
A6 RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
A501 SILICONE SEALANT RIGHTS, INCLUDING THE COPYRIGHT.
4"
2 1/2" TYP 2 1/2" TYP

NOTES:
092900.B A6 H4 HEAD DETAIL A7 BUTT JOINT DETAIL
092900.B A3 A501 A501
A7 SCALE: 3" = 1'-0" SCALE: 3" = 1'-0" 1. BASIS OF DESIGN OF RATED STOREFRONT SYSTEM
A501 NOTE 2 A501 NOTE 3 TO BE SUPERLITE II-XLB.

8' - 0"

8' - 0"
092116.I
092116.I 2. FIRE RESISTIVE BUTT-GLAZED TEMPERED GLASS
4" AND RATED FRAME.
092900.A 3. 3/8" TEMPERED GLASS (088000) WITH STRUCTURAL
WALL TYPE A: BOTH SIDES 092900.A
SILICONE SEALANT
WALL TYPE A1: ONE SIDE
4. MATCH RATED STOREFRONT IN APPEARANCE.
1 HOUR RATED
B6 GLAZING 5. SEE FLOOR PLAN FOR LOCATION OF NEW WALL.
079200.A BACKER ROD & SEALANT JOINT
EACH SIDE 079200.A
A501
EACH SIDE 1 HOUR RATED GLAZING
FINISH FLOOR
FINISH FLOOR
B 1 HOUR RATED B
FRAME Keynote Legend

2 1/2"
SF1 SF2

4"
BACKER ROD Key Value Keynote Text
088810 084126 & SEALANT
1-HR FIRE RATED NOTE 4
NOTE 1 078100.A APPLIED FIREPROFFING
2 1/2"
1 HOUR RATED FRAME 079200.A JOINT SEALANTS
WALL TYPE A - 3 5/8" MTL STUD WALL TYPE B - 6" MTL STUD / 081113.A HOLLOW METAL FRAMES
B1 / GWB B2 GWB B3 STOREFRONT TYPES B6 S4 SILL DETAIL A3 J4 JAMB DETAIL
A501 A501 A501 A501 A501
081416.A FLUSH WOOD DOOR
SCALE: 1 1/2" = 1'-0" SCALE: 1 1/2" = 1'-0" SCALE: 1/2" = 1'-0" SCALE: 3" = 1'-0" SCALE: 3" = 1'-0"
084126.A BUTT GLAZED STOREFRONT
SYSTEM
088810.A FIRE RATED GLASS AND FRAMING
Room Finish Schedule SYSTEM
Room Number Room Name Floor Base Wall Ceiling Ceiling Height Comments 5/8" GWB B.S. 092116.I NON-STRUCTURAL METAL
FRAMING
1 WELCOME LVT 6" RUBBER EXST'G / GWB- ACT 9' - 0" FS 1
AREA PAINT 3 5/8" MTL STUD, TYP EXISTING CEILING 095113.A 092900.A GYPSUM BOARD
TO REMAIN 092900.B SOUND ATTENUATION BATTS
2 OPTICAL EXST'G LVT 6" RUBBER EXST'G / GWB- ACT 9' - 0" FS 1
PAINT GWB, BOTH SIDES 095113.A ACOUSTICAL PANEL CEILINGS
BOX HEADER
3 OPTICAL LAB EXST'G LVT 6" RUBBER GWB- PAINT ACT 9' - 0" FS 1 095113.B CEILING GRID
C C
5 EXAM ROOM LVT 6" RUBBER EXST'G / GWB- ACT 8' - 8" FS 1 096513.B RESILIENT BASE
PAINT MTL BOX HEADER SCHEDULED 099123.A INTERIOR PAINTING
SEALANT
6 EXAM ROOM LVT 6" RUBBER EXST'G / GWB- ACT 8' - 8" FS 1 102600.A BUMPER GUARD
HM FRAME
PAINT
EXISITNG SOFFIT 104413.B FIRE EXTINGUISHER CABINET

2 3/4"
HM FRAME
STRUCTURE 104416.C FIRE EXTINGUISHER
FINISH SCHEDULE NOTES: POCKET DOOR HARDWARE 123661.A SOLID SURFACING COUNTERTOPS
EQ EQ AS SCHEDULED
FS 1. RUBER BASE TO MATCH EXISTING BASE
FS 2. NO NEW FINISHES THIS SPACE. LIMIT ACCESS THROUGH SPACE TO MIN. REQUIRED. 6" 260000.A INTERIOR LIGHTING - SEE 'E'
POCKET DOOR AS SCHEDULED
SHEETS

C4 H1 HEAD DETAIL C5 H2 HEAD DETAIL Copy 1


A501 SCALE: 3" = 1'-0" A501 SCALE: 3" = 1'-0"

NOTE 5
EXISITING SOFFIT

EXISITING MTL STUD WALL WOOD PANELING - SEE


FLOOR PLANS AND
ELEVATIONS
EXISITING BRICK WALL
EXISITING WINDOW TO REMAIN
5/8" GWB B.S.
GWB, BOTH SIDES

3 5/8" MTL STUD, TYP DOOR CASING AS SCHEDULED


D EXISITING "DIRTT" WALL D
6" METAL STUDS
SEALANT
CJ CJ 092116.I
5/8" GWB TO BE FLUSH WITH EXISTING GWB @ 16" O.C. PROJECT NUMBER: H51-50068
2 3/4"

HM FRAME HM FRAME
1 1/2" MTL STUDS, TYP
DHEC PROJECT NUMBER: 580145
EQ EQ
092900.A
6" POCKET DOOR AS
SCHEDULED CONSTRUCTION
D1 D4 D5
A501
GWB OVER EXIST'G WINDOW
SCALE: 3/4" = 1'-0" A501
J1 JAMB DETAIL
SCALE: 3" = 1'-0" A501
J2 JAMB DETAIL
SCALE: 3" = 1'-0" DOCUMENTS 5/8/2018 2:52:11 PM

INFILL OPAQUE FILM TO


Door Schedule
Door Frame
1. ALL DOORS MUST OPEN TO A FULL 90 DEGREES (OR 180 DEGREES
WHERE INDICATED).
CAVITY SIDE OF ALL
TRANSPARENT PANEL TO
CONCEAL FRAMING FROM
STORM EYE INSTITUTE
Door Fire STRUCTURE
Number Type Room Width Height Thickness Material Finish Rating Type Material Finish Jamb Head Comments 2. MAINTAIN A 4" MINIMUM CLEARANCE ( UNLESS OTHERWISE SHOWN
IN PLAN) BETWEEN DOOR JAMB AND ADJACENT PARTITION.
PEDIATRIC VIEW
OPTICAL SHOP
1
2
A
B
6
7
3' - 0"
4' - 0"
7' - 0"
7' - 0"
0' - 1 3/4" WOOD STAIN
0' - 1 3/4" WOOD/GLASS CLEAR
N/A
20 min
F1
F1
HM
HM
PAINT
PAINT
J1
J1
H1
H1 DS 1
3. MAINTAIN CONTINUITY OF SMOKE AND RATED PARTITIONS AT
3 5/8" METAL STUD
H51-50068
FRAMES. STEEL STUDS
3 C 2 2' - 6" 7' - 0" 0' - 1 3/4" WOOD STAIN NA F1 HM PAINT J2 H2 RUNNER FASTENED WITH 167 ASHLEY AVE
4. CONTRACTOR TO COORDINATE DOOR VISION PANEL CUT-OUT WITH
SCREWS TO STUDS
DOOR SCHEDULE NOTES: HARDWARE CUTOUTS. CHARLESTON, SC 29425
E 5. REFER TO SPECIFICATIONS FOR HARDWARE SET TYPES. E
DS 1 - NEW FRAME IN EXISTING WALL, FIELD VERIFY THROAT WIDTH
6. ALL RATED DOORS AND SMOKE DOORS SHALL BE POSITIVE
LATCHING.
PEDIATRIC
WAITING
OPTICAL ROSENBLUM COE
7. MANUFACTURER'S INSTALLATION INSTRUCTIONS SHALL BE SHOWROOM
AVAILABLE ON THE JOB SITE FOR ALL RATED DOOR ASSEMBLIES.
STEEL STUDS
ARCHITECTS,
8. HAND ACTIVATED DOOR OPENING HARDWARE SHALL BE CENTERED
BETWEEN 30 INCHES AND 44 INCHES ABOVE THE FLOOR.
INC.
SEE SCH'D SEE SCH'D SEE SCH'D JAMB ANCHORS (TYPICAL)
9. FIELD VERIFY EXISTING WALL FOR THROAT DIMENSION OF FRAME
1643 MEANS STREET
WHERE A NEW DOOR IS INSTALLED IN AN EXISTING WALL. ALSO, FIELD CHARLESTON, SC 29412
VERIFY DIMENSIONS WHERE A NEW WALL IS TO ALIGN WITH THE
EXISTING WALL. 843.577.6073
0' - 2" TYP

10. REFER TO SPECIFICATIONS FOR GLAZING TYPES.

6"

NOTES:
SEE SCH'D

DETAILS
SEE SCH'D

SEE SCH'D

SEE SCH'D

1. LOCATE JAMB ANCHOR ABOVE HINGE


REINFORCEMENTS AND JUST BELOW TOP
REINFORCEMENT. CLIPS ON STRIKE SIDE TO OCCUR FLOOR ANCHORS SECURED
8"

DIRECTLY OPPOSITE HINGE SIDE ANCHORS. (POSITION TO FLOOR W/ NO LESS THAN


CONCRETE AND MASONRY ANCHORS SIMILARLY.) TWO SUITABLE FASTENERS SHEET NAME

2. FOR DOUBLE DOORS 5'-0" OR WIDER, PROVIDE PROJECT NUMBER


F ADDITIONAL ANCHORS AT HEAD 8" FROM JAMBS AND 24" FLOOR 17016 F
O.C. THEREAFTER.
DRAWN BY
RML
10"

A B C
SEE SCH'D

F1
F5
TYPICAL FRAME ELEVATION/
DETAIL F7 WALL SECTION AT DIRTT WALL
CHECKED BY

DATE
SHC

05/09/2018
A501
081416 081416 W/ 088813 081416 A501 SCALE: 3/4" = 1'-0" A501 SCALE: 1 1/2" = 1'-0"
WOOD DOOR 20 MIN RATED DOOR & GLAZING WOOD POCKET DOOR 081113
WOOD/GLASS DOOR ALUM FRAME
SCALE
As indicated

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

PLUMBING GENERAL NOTES PLUMBING SYMBOLS PLUMBING ABBREVIATIONS


1 ALL PLUMBING WORK SHALL BE IN ACCORDANCE WITH INTERNATIONAL PLUMBING CODE (IPC) CURRENTLY ADOPTED BY A COMPRESSED AIR
THE AUTHORITY HAVING JURISDICTION. F S O UT H C A
COMPONENTS AND SPECIATIES
BCWR BEARING COOLING WATER RETURN EO R

OL
T
STA
2 PROVIDE CLEANOUTS AT THE BASE OF EACH SANITARY STACK IN ACCORDANCE WITH INTERNATIONAL PLUMBING CODE BCWS BEARING COOLING WATER SUPPLY

INA
SYMBOL DESCRIPTION
(IPC) CURRENTLY ADOPTED BY THE AUTHORITY HAVING JURISDICTION. CLEANOUTS SHALL BE SIZED TO MATCH THE BO BLOW OFF RMF
PIPING BEING SERVED. FLOOR CLEANOUTS SHALL BE SPACED AT 75'-0" MAX. ALSO PROVIDE CLEANOUTS IN ENGINEERING INC.

HORIZONTAL CHANGE OF DIRECTIONS >45°. CO CLEAN OUT (WALL / PIPE) BTU BRITISH THERMAL UNIT CHARLESTON, SC
C-00831
BTUH BRITISH THERMAL UNITS PER HOUR
3 FIRE CAULK AND SLEEVE ALL PENETRATIONS THROUGH FIRE RATED ASSEMBLIES. REFER TO LIFE SAFETY PLANS FOR

RS
RE
G IS
RATED ASSEMBLY LOCATIONS. REFER TO THE ARCHITECTURAL SHEET FOR WALL DETAILS AND UL ASSEMBLY CA CONTROL AIR
T ER E N EE
A NUMBERS. CBD CONTINUOUS BLOWDOWN D E NG I A
PIPING SYMBOLS CC CAMPUS CONDENSATE
4 COORDINATE CRAWL SPACE PIPING WITH STRUCTURAL BEAM ELEVATIONS AND EXISTING SANITARY INVERT CF CHEMICAL FEED SEALS
ELEVATIONS PRIOR TO ANY PIPING INSTALLATION. SYMBOL DESCRIPTION CFM CUBIC FEET PER MINUTE
CHEL CHELANT C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.

5 VALVES AND FITTINGS SHALL BE THE SAME SIZE AS THE PIPING WHERE THEY ARE LOCATED UNLESS NOTED SANITARY CHR CHILLED WATER RETURN THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
OTHERWISE. CHS CHILLED WATER SUPPLY RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
VENT DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
CO CLEANOUT RIGHTS, INCLUDING THE COPYRIGHT.
6 CONCRETE CORING OR CUTTING MAY BE REQUIRED IN ORDER TO RUN PLUMBING OR OTHER SERVICES TO A SPECIFIC PIPE DROP
CW COLD WATER, DOMESTIC CITY WATER
AREA. IT IS IMPERATIVE WHEN CONSIDERING EITHER CORING, CUTTNG OR CHIPPING THAT REBAR, PLUMBING,
PIPE RISE
ELECTRICAL SERVICES, ETC WITHIN THE CONCRETE SLAB, WALL OR FLOOR BE LOCATED PRIOR TO DISTURBING THE NOTES:
INTEGRITY OF THE EXISTING CONCRETE. OBTAIN STRUCTURAL DRAWINGS OF THE EXACT LOCATIONS REQUIRED FOR DHR DISTRIBUTION HEATING WATER RETURN
NEW SERVICES. DETERMINE THE FINAL LOCATION OF THE CORE OR CUT BY LOCATING THE PRECISE POSITIONING OF DHS DISTRIBUTION HEATING WATER SUPPLY
ANY REBAR USING X-RAYS OR FERRO SCAN. DIA DIAMETER
REFERENCE SYMBOLS DW DISTILLED WATER
7 EXISTING SANITARY SYSTEM IS AN ENGINEERED SINGLE STACK SOVENT DRAINAGE SYSTEM. TO MAINTAIN
PERFORMANCE, IT IS CRITICAL THAT THE CONTRACTOR INSTALL NEW SOVENT AERATOR AND DEAERATOR FITTINGS DESIGNATION DESCRIPTION (E) EXISTING
AND IN-LINE OFFSETS OF EQUAL SIZE IN THE SAME LOCATIONS AND CONFIGURATIONS AS EXISTING. EA EXHAUST AIR
POINT OF CONNECTION TO EXISTING ED EQUIPMENT DRAIN
8 NOTIFY THE OWNER, IN WRITING, AT LEAST SEVEN (7) DAYS IN ADVANCE OF ALL REQUIRED SUTDOWNS OF WATER, EJ EXPANSION JOINT
FIRE, SANITARY, GAS, ELECTRICAL SERVICE, OR OTHER UTILITIES. UPON WRITTEN RECEIPT OF APPROVAL FROM POINT OF DISCONNECTION
OWNER, SHUTDOWN SHALL BE PERFORMED BETWEEN THE HOURS OF SIX (6) P.M. AND SIX (6) A.M. OR AS DIRECTED
OTHERWISE BY THE OWNER AND SHALL BE ACCOMPLISHED AT NO ADDITIONAL CONTRACT COST. AT THE END OF EACH #2FOR NUMBER 2 FUEL OIL RETURN
SHUTDOWN, ALL SERVICES SHALL BE RESTORED SO THAT NORMAL USE OF THE UTILITIES CAN CONTINUE. #2FOS NUMBER 2 FUEL OIL SUPPLY
#6FOR NUMBER 6 FUEL OIL RETURN
9 WHEN WORKING IN AND AROUND THE EXISTING BUILDING, EXTREME CARE SHALL BE EXERCISED WITH REGARD TO #6FOS NUMBER 6 FUEL OIL SUPPLY
PROTECTION OF THE EXISTING STRUCTURE, MECHANICAL AND ELECTRICAL SERVICES WHICH WILL REMAIN. REPAIR, F FIRE LINE
REPLACE, OR RESTORE TO THE SATISFACTION OF THE ARCHITECT, ALL EXISTING WORK DAMAGED IN THE RISER DESIGNATIONS
F&T FLOAT AND THERMOSTATIC
B PERFORMANCE OF DEMOLITION AND/OR NEW WORK. B
SYMBOL DESCRIPTION FD FORCED DRAFT
FDV FIRE DEPARTMENT VALVE
10 EXISTING DUCT, PIPE, AND EQUIPMENT SIZES NOTED ARE FOR THE CONVENIENCE OF THE CONTRACTOR ONLY AND ARE
FF FINISHED FLOOR
NOT WARRANTED TO BE CORRECT. CONTRACTOR SHALL VERIFY ALL SIZES IN THE FIELD IF THEY EFFECT HIS WORK.
S FFE FINISHED FLOOR ELEVATION
SANITARY RISER DESIGNATION (S)
FOF FUEL OIL FILL
11 EXISTING PIPING NO LONGER REQUIRED TO REMAIN IN SERVICE SHALL BE DISCONNECTED AND REMOVED BACK TO RISER NUMBER
SERVE MAINS, UNLESS OTHERWISE NOTED. REMOVE EXISTING PIPE HANGERS, SUPPORTS, VALVES, ETC. EXISTING FOO FUEL OIL OVERFLOW
PIPING INDICATED OR REQUIRED TO REMAIN IN SERVICE OR IN PLACE SHALL BE CAPPED, PLUGGED, OR OTHERWISE FOSUCT FUEL OIL SUCTION
SEALED. NO EXISTING PIPING SHALL BE LEFT OPEN END. FOT FUEL OIL TRANSFER
FOVENT FUEL OIL VENT
12 IN GENERAL ALL PIPING, EQUIPMENT, DUCTWORK, AND MATERIALS SHOWN "LIGHT" IS EXISTING TO REMAIN. FPM FEET PER MINUTE
COMPONENTS SHOWN "HEAVY AND DASHED" ARE EXISTING AND SHALL BE DEMOLISHED. FIRE RATED WALL LINETYPES
FPS FEET PER SECOND
FW FEED WATER
13 SEE ARCHITECTURAL DRAWINGS FOR PHASING PLAN. ALL WORK SHALL BE PERFORMED IN A SEQUENCE AND DURING SEE ARCHITECTURAL PLANS FOR RATED WALL LEGEND FWR FEED WATER RECIRCULATION
HOURS TO MINIMIZE DISRUPTION TO THE BUILDING WHICH WILL REMAIN OCCUPIED DURING CONSTRUCTION. ALL FWS FEED WATER SUPPLY
SEWER RISERS SHALL BE OPERATIONAL AT THE END OF EACH WORK SHIFT.
°F DEGREES FAHRENHEIT

G NATURAL GAS
GAL GALLON, GALLONS
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE

HPR HIGH PRESSURE STEAM RETURN


HPS HIGH PRESSURE STEAM SUPPLY
C HR HEATING WATER RETURN
C
HRR HEAT RECOVERY RETURN
HRS HEAT RECOVERY SUPPLY
HS HEATING WATER SUPPLY
HTHW HIGH TEMPERATURE HEATING WATER SUPPLY
HTWR HIGH TEMPERATURE HEATING WATER RETURN
HW HOT WATER
HWR HOT WATER RECIRCULATION

IA INSTRUMENT AIR

KW KILOWATTS

LP LIQUID PROPANE
LPG LIQUID PETROLEUM GAS
LPR LOW PRESSURE STEAM RETURN
LPS LOW PRESSURE STEAM SUPPLY

MAV MANUAL AIR VENT


MBH THOUSAND BRITISH THERMAL UNITS PER HOUR
MCC MOTOR CONTROL CENTER
MOD MOTOR OPERATED DAMPER
MPR MEDIUM PRESSURE STEAM RETURN
MPS MEDIUM PRESSURE STEAM SUPPLY

N/A NOT APPLICABLE


D NC NORMALLY CLOSED D
NO NORMALLY OPEN
No NUMBER
NPSH NET POSITIVE SUCTION HEAD
PROJECT NUMBER: H51-50068
OD OVERFLOW DRAIN
DHEC PROJECT NUMBER: 580145
PA PLANT AIR
PC PUMPED CONDENSATE
PCR
PPH
PUMP CONDENSATE RECIRCULATION
POUNDS PER HOUR
CONSTRUCTION
PSIG POUNDS PER SQUARE INCH GAUGE
DOCUMENTS 5/8/2018 3:45:12 PM
RA RETURN AIR, RELIEF AIR
RDR ROOF DRAIN
RPM REVOLUTIONS PER MINUTE
RV RELIEF VENT STORM EYE INSTITUTE
RX REMOVE EXISTING

SA SUPPLY AIR
OPTICAL SHOP
SAN
SS
SANITARY
STAINLESS STEEL
H51-50068
SSUL SODIUM SULFITE
STDR STORM DRAIN
167 ASHLEY AVE
SW SOFT WATER CHARLESTON, SC 29425
E E
TW TREATED WATER
TYP TYPICAL

VD VOLUME DAMPER ROSENBLUM COE


VFD
VSD
VARIABLE FREQUENCY DRIVE
VARIABLE SPEED DRIVE
ARCHITECTS,
VTR VENT THROUGH ROOF INC.
1643 MEANS STREET
CHARLESTON, SC 29412

843.577.6073

PLUMBING NOTES, SYMBOLS AND


ABBREVIATION
SHEET NAME

PROJECT NUMBER
F 17016 F
DRAWN BY
TSN

CHECKED BY

DATE
CRB

05/09/2018
P001
SCALE
1:1

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

F S O UT H C A
EO R

OL
T
STA

INA
RMF
ENGINEERING INC.
CHARLESTON, SC
C-00831

RS
RE
G IS
T ER E N EE
A D E NG I A

SEALS

C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.


THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING THE COPYRIGHT.

NOTES:
1 CONTRACTOR SHALL DEMOLISH SANITARY RISER FOR
RELOCATION, SEE NEW WORK PLANS FOR MORE INFORMATION.

2 CONTRACTOR SHALL DEMOLISH VENT PIPING.

3 CONTRACTOR SHALL STORE DEAERATOR FITTINGS FOR


RELOCATION. SEE NEW WORK PLANS AND RISER FOR MORE
INFORMATION.

B B

GENERAL NOTES
1. REFER TO P001 FOR GENERAL NOTES.

C C

(E) 5"ø SAN

D D
5"ø SAN

(E) 5"ø SAN PROJECT NUMBER: H51-50068


(E) CO
2 3"ø V DHEC PROJECT NUMBER: 580145

5"ø SAN 3"ø V 2


CONSTRUCTION
4"ø SAN UP
5"ø SAN
4"ø SAN UP
DOCUMENTS 5/8/2018 3:45:15 PM
APPROXIMATE
LOCATION OF
S S
ACCESS DOOR IN 1 3 1 3
FLOOR ABOVE 6 7 STORM EYE INSTITUTE
OPTICAL SHOP
H51-50068
167 ASHLEY AVE
CHARLESTON, SC 29425
E E

ROSENBLUM COE
ARCHITECTS,
INC.
1643 MEANS STREET
CHARLESTON, SC 29412

843.577.6073

PLUMBING CRAWL SPACE


DEMOLITION PLAN
1 PLUMBING CRAWL SPACE DEMOLITION PLAN
N
PD100 SCALE: 1/4" = 1'-0" SHEET NAME

PROJECT NUMBER
F 17016 F
DRAWN BY
TSN

CHECKED BY

DATE
CRB

05/09/2018
PD100
SCALE
1/4" = 1'-0"

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

F S O UT H C A
EO R

OL
T
STA

INA
RMF
ENGINEERING INC.
CHARLESTON, SC
C-00831

RS
RE
G IS
T ER E N EE
A D E NG I A

SEALS

C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.


THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING THE COPYRIGHT.

NOTES:
1 REMOVE WALL MOUNTED SINK PRIOR TO RISER DEMOLITION.
REMOVE SANITARY P-TRAP AND DOMESTIC HOT AND COLD
WATER LINES BACK TO MAINS LOCATED IN CORRIDOR.

2 CONTRACTOR SHALL DEMOLISH SANITARY RISER FOR


RELOCATION, SEE RENOVATION PLANS FOR MORE INFORMATION.

B B

GENERAL NOTES
1. REFER TO P001 FOR GENERAL NOTES.

2. ALL PIPING SHOWN IS LOCATED BELOW FIRST FLOOR SLAB


WITHIN CRAWL SPACE. FIRST FLOOR WALLS ARE SHOWN FOR
REFERENCE ONLY.
C C

D D

PROJECT NUMBER: H51-50068

PHASE 1 S
2
S
2
DHEC PROJECT NUMBER: 580145
6 7
4"ø SAN
CONSTRUCTION
4"ø SAN UP 1
DOCUMENTS 5/8/2018 3:45:16 PM
APPROXIMATE 1 4"ø SAN
LOCATION OF
ACCESS DOOR TO 4"ø SAN UP&DN
CRAWL SPACE
LOCATED IN
STORM EYE INSTITUTE
FLOOR 2"ø SAN
OPTICAL SHOP
H51-50068
167 ASHLEY AVE
CHARLESTON, SC 29425
E E

ROSENBLUM COE
ARCHITECTS,
2"ø SAN UP INC.
1643 MEANS STREET
CHARLESTON, SC 29412

843.577.6073

PLUMBING FIRST FLOOR


DEMOLITION PLAN
1 PLUMBING DEMOLITION PLAN
N
PD101 SCALE: 1/4" = 1'-0" SHEET NAME

PROJECT NUMBER
F 17016 F
DRAWN BY
TSN

CHECKED BY

DATE
CRB

05/09/2018
PD101
SCALE
1/4" = 1'-0"

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

F S O UT H C A
EO R

OL
T
STA

INA
RMF
ENGINEERING INC.
CHARLESTON, SC
C-00831

RS
RE
G IS
T ER E N EE
A D E NG I A

SEALS

C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.


THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING THE COPYRIGHT.

NOTES:

B B

GENERAL NOTES
1. REFER TO P001 FOR GENERAL NOTES.

2. ALL PIPING SHOWN IS LOCATED BELOW FIRST


FLOOR SLAB WITHIN CRAWL SPACE. FIRST FLOOR
C WALLS ARE SHOWN FOR REFERENCE ONLY. C

FEC

(E) 5"ø SAN

D D

(E)5"ø SAN PROJECT NUMBER: H51-50068


(E) CO
(E)5"ø SAN DHEC PROJECT NUMBER: 580145
3"ø V
5"ø SAN
3"ø V
CONSTRUCTION
S S
6 7 DOCUMENTS 5/8/2018 3:45:13 PM
APPROXIMATE 4"ø SAN UP 4"ø SAN UP
LOCATION OF
ACCESS DOOR IN
FLOOR ABOVE STORM EYE INSTITUTE
OPTICAL SHOP
H51-50068
167 ASHLEY AVE
CHARLESTON, SC 29425
E E

ROSENBLUM COE
ARCHITECTS,
INC.
1643 MEANS STREET
CHARLESTON, SC 29412

843.577.6073

PLUMBING CRAWL SPACE PLAN

1 PLUMBING CRAWL SPACE PLAN


N
P100 SCALE: 1/4" = 1'-0" SHEET NAME

PROJECT NUMBER
F 17016 F
DRAWN BY
TSN

CHECKED BY

DATE
CRB

05/09/2018
P100
SCALE
1/4" = 1'-0"

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

F S O UT H C A
EO R

OL
T
STA

INA
RMF
ENGINEERING INC.
CHARLESTON, SC
C-00831

RS
RE
G IS
T ER E N EE
A D E NG I A

SEALS

C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.


THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING THE COPYRIGHT.

NOTES:

B B

PEDIATRIC WAITING
4

GENERAL NOTES
1. REFER TO P001 FOR GENERAL NOTES.

PHASE 2
C C

RECEPTION
FEC

7
OPTICAL
2

D D

PROJECT NUMBER: H51-50068

PHASE 1 DHEC PROJECT NUMBER: 580145

4"ø SAN DN

4"ø SAN 4"ø SAN


CONSTRUCTION
2"ø SAN 4"ø SAN DN
(E)4"ø SAN UP
DOCUMENTS 5/8/2018 3:45:14 PM
APPROXIMATE
LOCATION OF (E) 4"ø SAN UP
ACCESS DOOR TO OFFICE #1
CRAWL SPACE
LOCATED IN
5 STORM EYE INSTITUTE
FLOOR
OPTICAL SHOP
(E) 2"ø SAN
WELCOME AREA H51-50068
1
167 ASHLEY AVE
CHARLESTON, SC 29425
E E
OFFICE #2
6
ROSENBLUM COE
ARCHITECTS,
(E) 2"ø SAN UP INC.
1643 MEANS STREET
CHARLESTON, SC 29412

843.577.6073

PLUMBING FIRST FLOOR PLAN

1 PLUMBING NEW WORK PLAN


N
P101 SCALE: 1/4" = 1'-0" SHEET NAME

PROJECT NUMBER
F 17016 F
DRAWN BY
TSN

CHECKED BY

DATE
CRB

05/09/2018
P101
SCALE
1/4" = 1'-0"

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

F S O UT H C A
EO R

OL
T
STA

INA
RMF
ENGINEERING INC.
CHARLESTON, SC
C-00831

RS
RE
G IS
T ER E N EE
A D E NG I A

SEALS

C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.


THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING THE COPYRIGHT.

NOTES:
1 NEW WORK SHALL CONNECT TO EXISTING PIPING IN CRAWL
SPACE. CONTRACTOR SHALL PROVIDE APPROPRIATE COUPLING
S S (PROFLEX OR EQUAL) WHERE REQUIRED TO CONNECT TO
EXISTING SYSTEM.
6 7
2 NEW WORK SHALL CONNECT TO EXISITNG SANITARY SYSTEM IN
FIRST FLOOR CEILING. CONTRACTOR SHALL PROVIDE
APPROPRIATE COUPLING (PROFLEX OR EQUAL) WHERE
REQUIRED TO CONNECT TO EXISTING SYSTEM.
4" 4"

SECOND FLOOR

B DOUBLE INLINE OFFSET (TYPICAL) B

2 2

2
2"

GENERAL NOTES
1. CONTRACTOR SHALL PROVIDE ALL TRANSITIONS AND FITTINGS
4" 4"
TO CONNECT NEW SOVENT FITTINGS (DEAERATOR) TO EXISTING
SANITARY PIPE.

2. CONTRACTOR SHALL COORDINATE REQUIRED SIZE AND


C QUANTITY OF CONNECTION PRIOR TO ORDERING DEAERATOR C
FITTINGS.
FIRST FLOOR
3. EXISTING SANITARY SYSTEM IS AN ENGINEERED SINGLE STACK
SOVENT DRAINAGE SYSTEM. TO MAINTAIN PERFORMANCE, IT IS
CRITICAL THAT THE CONTRACTOR INSTALL NEW SOVENT
AERATOR AND DEAERATOR FITTINGS AND IN-LINE OFFSETS OF
EQUAL SIZE IN THE SAME LOCATIONS AND CONFIGURATIONS AS
EXISTING.

3" RELOCATED DEAERATOR FITTING (TYPICAL) 3"

3"
CO 5"

1 1 1
5" 5" 5"
D D

CRAWL SPACE

PROJECT NUMBER: H51-50068

DHEC PROJECT NUMBER: 580145

DETAIL - SANITARY RISER DIAGRAM


SCALE: N.T.S. CONSTRUCTION
DOCUMENTS 5/8/2018 3:45:14 PM

STORM EYE INSTITUTE


OPTICAL SHOP
H51-50068
167 ASHLEY AVE
CHARLESTON, SC 29425
E E

ROSENBLUM COE
ARCHITECTS,
INC.
1643 MEANS STREET
CHARLESTON, SC 29412

843.577.6073

PLUMBING RISER DIAGRAMS

SHEET NAME

PROJECT NUMBER
F 17016 F
DRAWN BY
TSN

CHECKED BY

DATE
CRB

05/09/2018
P201
SCALE
12" = 1'-0"

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

F S O UT H C A
EO R
THROUGH PENETRATION FIRESTOP SCHEDULE

OL
T
STA

INA
RMF
ENGINEERING INC.
CHARLESTON, SC
C-00831

A. THIS SCHEDULE IDENTIFIES REQUIREMENTS FOR ACCEPTABLE THROUGH PENETRATION FIRESTOPS FOR THIS PROJECT BASED ON BARRIER TYPE, BASIS OF BARRIER CONSTRUCTION, AND PENETRANT TYPE.

RS
RE
G IS
B. THROUGH PENETRATION FIRESTOPS ARE NOT REQUIRED FOR FLOOR PENETRATIONS CONTAINED TOTALLY WITHIN A RATED SHAFT ENCLOSURE. T ER E N EE
A D E NG I A
C. FOR EACH PENETRATION, SELECT A THROUGH PENETRATION FIRESTOP BASED ON ACTUAL FIELD CONDITIONS, WHICH INCLUDE BUT ARE NOT LIMITED TO PENETRATION SIZE, PENETRATION SHAPE, PENETRANT MATERIAL(S), QUANTITY OF PENETRANTS PER PENETRATION, AND LOCATION(S) OF PENETRANT(S) WITHIN PENETRATION.
SEALS
D. NOMENCLATURE OF UL CLASSIFIED FIRESTOP ASSEMBLIES USED IN THIS SCHEDULE IS IDENTICAL TO THAT USED IN CATALOGS OF APPROVED FIRESTOP MANUFACTURERS (SEE DIVISION 15) AND IN UNDERWRITERS LABORATORIES "FIRE RESISTANCE DIRECTORY."
C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.
THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH

RATED BARRIER PENETRANT TYPE RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING THE COPYRIGHT.

NOTES:
METALLIC, NONMETALLIC, INSULATED PIPES INSULATED PIPES
UNINSULATED PIPE UNINSULATED PIPE (EX. COPPER, IRON (EX. COPPER, IRON
TYPE BASIS OF NO
OR TUBING OR TUBING PLASTIC, STEEL) IN PLASTIC, STEEL) IN METAL DUCT
CONSTRUCTION FIRESTOP ASSEMBLY REQUIREMENTS PENETRANTS
(EX. COPPER, IRON, (EX. PVC, PP, SYSTEMS OPERATING SYSTEMS OPERATING (NOTE 1)
STEEL) FRPP) BETWEEN 32°F AND 122°F BELOW 32°F OR ABOVE 122°F

SINGLE PENETRANT W-L-1000 SERIES W-L-2000 SERIES W-L-5000 SERIES W-L-5000 SERIES W-L-7000 SERIES
UL CLASSIFIED W-L-0000 SERIES
SERIES OR NOTE 2
METAL STUDS & W-L-8000 SERIES W-L-8000 SERIES W-L-8000 SERIES
MULTIPLE PENETRANTS N/A
GYPSUM WALLBOARD (NOTE 3) (NOTE 3) (NOTE 3)
WALL
B EQUAL TO WALL EQUAL TO WALL EQUAL TO WALL EQUAL TO WALL EQUAL TO WALL EQUAL TO WALL B
(U400 SERIES) F RATING
RATING RATING RATING RATING RATING RATING
T RATING NOTE 5 NOTE 5 NOTE 5 NOTE 5 NOTE 5 NOTE 5
EXCEPTIONS/ ADDED REQUIREMENTS NONE NOTE 8 NOTE 8 NONE NOTE 4 NONE
C-AJ-1000 OR C-AJ-2000 OR C-AJ-5000 OR C-AJ-5000 OR C-AJ-7000 OR
SINGLE PENETRANT
UL CLASSIFIED W-J-0000 SERIES W-J-1000 SERIES W-J-2000 SERIES W-J-5000 SERIES W-J-5000 SERIES W-J-7000 SERIES
POURED CONCRETE,
SERIES OR NOTE 2
CONCRETE BLOCK OR C-AJ-8000 OR W-J-8000 SERIES C-AJ-8000 OR C-AJ-8000 OR
MULTIPLE PENETRANTS N/A
MASONRY (NOTE 3) W-J-8000 (NOTE 3) W-J-8000 (NOTE 3)
WALL
EQUAL TO WALL EQUAL TO WALL EQUAL TO WALL EQUAL TO WALL EQUAL TO WALL EQUAL TO WALL
(BLOCK & U900 SERIES) F RATING
RATING RATING RATING RATING RATING RATING
(ANY THICKNESS)
T RATING NOTE 5 NOTE 5 NOTE 5 NOTE 5 NOTE 5 NOTE 5
EXCEPTIONS/ ADDED REQUIREMENTS NONE NOTES 7 & 8 NOTE 8 NONE NOTE 4 NONE
C-AJ-1000 OR C-AJ-2000 OR C-AJ-5000 OR C-AJ-5000 OR C-AJ-7000 OR
SINGLE PENETRANT C-AJ-0000 SERIES
UL CLASSIFIED F-A-1000 SERIES F-A-2000 SERIES F-A-5000 SERIES F-A-5000 SERIES F-A-7000 SERIES
F-A-0000 SERIES
C SERIES C
OR NOTE 2 C-AJ-8000 OR F-A-8000 SERIES C-AJ-8000 OR C-AJ-8000 OR
POURED CONCRETE MULTIPLE PENETRANTS N/A
(NOTE 3) F-A-8000 (NOTE 3) F-A-8000 (NOTE 3)
FLOOR
(ANY THICKNESS) EQUAL TO FLOOR RATING, EQUAL TO FLOOR RATING, EQUAL TO FLOOR RATING, EQUAL TO FLOOR RATING, EQUAL TO FLOOR RATING, EQUAL TO FLOOR RATING,
F RATING
BUT NOT LESS THAN 1 HR BUT NOT LESS THAN 1 HR BUT NOT LESS THAN 1 HR BUT NOT LESS THAN 1 HR BUT NOT LESS THAN 1 HR BUT NOT LESS THAN 1 HR
T RATING NOTE 6 NOTE 6 NOTE 6 NOTE 6 NOTE 6 NOTE 6
EXCEPTIONS/ ADDED REQUIREMENTS NONE NOTE 7 NONE NONE NOTE 4 NONE

NOTES:
1. THIS SCHEDULE'S DATA APPLY ONLY TO PENETRATIONS WITHOUT DAMPERS. FOR DAMPERED PENETRATIONS, REFER TO SPECIFICATIONS. 5. TEMPERATURE (T) RATINGS OF ASSEMBLIES IN WALLS MAY EQUAL ZERO.
AT DAMPERS, DO NOT APPLY MATERIAL THAT IS NOT INCLUDED IN THE DAMPER'S CLASSIFICATION. 6. TEMPERATURE (T) RATINGS OF ASSEMBLIES IN FLOORS SHALL EQUAL THE GREATER OF EITHER THE BARRIER RATING OR ONE HOUR EXCEPT AS FOLLOWS:
2. SEAL OPENING USING BARRIER'S ORIGINAL CONSTRUCTION. A. AN ASSEMBLY'S T RATING MAY EQUAL ZERO WHEN THE PENETRANT ABOVE THE FLOOR PENETRATION IS CONTAINED AND LOCATED
3. WHERE A SERIES 8000 CLASSIFIED SYSTEM IS NOT AVAILABLE, INSTALL PENETRANTS SINGLY, AND PROVIDE SINGLE-PENETRANT SYSTEMS. WITHIN THE CAVITY OF A WALL.
4. FOR SYSTEMS THAT OPERATE BELOW 32°F OR ABOVE 122°F, COMPLY WITH THE FOLLOWING ADDITIONAL REQUIREMENTS: 7. CLASSIFIED TPFS ASSEMBLY IS NOT REQUIRED WHEN ALL THE FOLLOWING CONDITIONS ARE MET:
A. PROVIDE TPFS SYSTEM USING INTUMESCENT ELASTOMERIC WRAP STRIP AS ITS FILL, VOID, OR CAVITY MATERIAL. A. PENETRANT HAS A MAXIMUM NOMINAL DIAMETER OF 6-INCHES.
B. DO NOT USE SERIES 8000 PENETRATIONS. PROVIDE ONLY SINGLE PENETRATIONS. B. PENETRATION HAS A MAXIMUM AREA OF 144 SQUARE INCHES.
C. ANNULAR SPACE IS COMPLETELY FILLED WITH CONCRETE, GROUT, OR MORTAR THE FULL THICKNESS OF THE BARRIER.
D D

PROJECT NUMBER: H51-50068


CONCRETE STRUCTURE LOAD SCHEDULE

DHEC PROJECT NUMBER: 580145


PIPE SIZE MAXIMUM SPACING ROD SIZE NOTES:

1/2"-2" 7' 1/2"


1. HANGER SPACING SHALL BE IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS.
CONSTRUCTION
2. PROVIDE SEISMIC SWAY BRACING FOR ALL PIPE HANGERS PER THE 2006 INTERNATIONAL
STEEL PLATE
3/8" MAX
CLEARANCE
STEEL PLATE
2 1/2"-3" 10' 3/4"
BUILDING CODE AND THE 2006 INTERNATIONAL MECHANICAL CODE. SANITARY RISER DOCUMENTS
5/8" DIAMETER EXPANSION 5/8" DIAMETER EXPANSION 4"-5" 14' 3/4" 5/8/2018 3:45:15 PM

ANCHOR BOLTS (4 REQUIRED) 1/4" ANCHOR BOLTS (4 REQUIRED) 6" 17' 3/4" 3. CONTRACTOR SHALL VERIFY MAXIMUM LOADING ON PIPE SUPPORT ASSEMBLIES.
PIPE RISER CLAMP
NEOPRENE ELEMENT 1/2" MINIMUM ROUND SHACKLE
OR ROPE THIMBLE
8" 19' 3/4"
WITH EXTENDED 1"x3/8" THICK STEEL STORM EYE INSTITUTE
VIBRATION ISOLATION HANGER

UPSTOP (STEEL WASHER


SEISMIC CABLE BRACING
ROUNDED EARS SLEEVE SUPPORT
TERMINATE FLUSH WITH OPTICAL SHOP
AND NUT) NOTCH TOP OF
CONCRETE TO
FLOOR
H51-50068
ACCOMMODATE
CONCRETE FLOOR SLAB
THREADED STEEL ROD, SIZE SHALL
SLEEVE ANCHOR. 167 ASHLEY AVE
BE CAPABLE OF CARRYING LOAD
EQUAL TO OR GREATER THAN
GROUT ALL VOIDS CHARLESTON, SC 29425
THREADED STEEL ROD, SIZE SHALL
E BE CAPABLE OF CARRYING LOAD
MAXIMUM LOAD ON CLEVIS HANGER E
WITH ROD STIFFENER AND STIFFENER
EQUAL TO OR GREATER THAN
CLAMP AS REQUIRED SEISMIC CABLE BRACING
MAXIMUM LOAD ON CLEVIS HANGER
WITH ROD STIFFENER AND STIFFENER
ROSENBLUM COE
CLAMP AS REQUIRED ARCHITECTS,
STEEL ANGLE
INC.
ADJUSTABLE CLEVIS PIPE HANGER
SEISMIC BRACING
ANVIL FIGURE NUMBER 260 1643 MEANS STREET
CHARLESTON, SC 29412
WELDLESS EYE NUT VAPOR BARRIER SHALL
ANVIL FIGURE NUMBER 290 EXTEND TO END OF
INSULATED PIPE SUPPORT
843.577.6073
STEEL SPACER
SLEEVE

16 GAUGE GALVANIZED
SHEET METAL JACKET
MINIMUM 12" LONG
SCHEDULE 40 BLACK PLUMBING DETAILS
STEEL FLOOR SLEEVE
CORE DRILL NEW OPENING
AS REQUIRED TO ACCOMMODATE
SHEET NAME
NEW FLOOR SLEEVE
PROJECT NUMBER
F FIRE SCALANT 17016 F
INSULATED PIPE SUPPORT
STANDARD PIPE INSULATION PIPE CLAMP
AT HANGER, SEE SPECIFICATIONS 1" (TYPICAL) DIRECT TO PIPE DRAWN BY
(NO WOOD BLOCKING ALLOWED) DOUBLE BOLT PIPE CLAMP TSN
ANVIL FIGURE NUMBER 295
NOTE:

1. PROVIDE FIRE STOPPING TO MAINTAIN FLOOR RATING IN ACCORDANCE WITH UL STANDARDS.


CHECKED BY

DATE
CRB

05/09/2018
P301
1
DETAIL - PIPE HANGER 2
DETAIL - PIPE FLOOR PENETRATIONS
SCALE: N.T.S. SCALE: N.T.S. SCALE
NONE

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

HVAC GENERAL NOTES MECHANICAL SYMBOLS MECHANICAL ABBREVIATIONS


EQUIPMENT DESIGNATIONS DUCTWORK SYMBOLS NOTE: THIS IS A STANDARD ABBREVIATION LIST. SOME ABBREVIATIONS MAY NOT APPEAR ON THE ACCOMPANYING DRAWINGS.
1 COMPLY WITH ALL APPLICABLE INTERNATIONAL BUILDING CODES FOR ALL WORK UNDER THIS CONTRACT.
F S O UT H C A
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
# NUMBER, POUND HWS HEATING WATER SUPPLY EO R
2 MAXIMUM, MINIMUM CFM AND RE-HEATING FOR VAV BOXES ARE AS INDICATED ON THE VAV UNIT SCHEDULE. IF NOT INDICATED, SET THE

OL
T
STA
$ DOLLAR HZ HERTZ

INA
MINIMUM CFM TO 50% OF THE MAXIMUM CFM. VAV-X VARIABLE AIR VOLUME TERMINAL UNIT DESIGNATION T TEMPERATURE SENSOR RMF
(E) VAV-X EXISTING VARIABLE AIR VOLUME TERMINAL UNIT DESIGNATION % PERCENT ENGINEERING INC.
3 PRESSURE DEPENDENT VAV BOXES SHALL NOT BE USED. & AND IA INSTRUMENT AIR CHARLESTON, SC
C-00831
SUPPLY AIR DIFFUSER + PLUS ICW INDUSTRIAL COLD WATER
PIPING SYMBOLS
4 ALL VAV BOXES SHALL BE PROVIDED WITH A MINIMUM OF TWO (2) DUCT DIAMETERS OF STRAIGHT DUCT RUN AT THE INLET. INLET DUCT - MINUS IHR INDUSTRIAL HOT WATER RECIRCULATION

RS
SYMBOL DESCRIPTION

RE
G IS
SHALL BE EQUAL TO THE BOX INLET SIZE. RETURN AIR GRILLE / DIVIDE BY, PER IHW INDUSTRIAL HOT WATER
T ER E N EE
A HR HEATING WATER RETURN < LESS THAN IN INCH, INCHES D E NG I A
5 FABRICATE ALL DUCTWORK IN ACCORDANCE WITH SMACNA STANDARDS. ALL DUCTWORK SHALL BE A MINIMUM OF 26 GAUGE. HS HEATING WATER SUPPLY = EQUALS, EQUAL TO INV EL INVERT ELEVATION
EXHAUST AIR GRILLE
PIPE DROP > GREATER THAN SEALS

6 PROVIDE ACCESS DOORS IN DUCTWORK TO SERVICE FIRE DAMPERS & DEVICES WITHIN DUCTS. PIPE RISE x MULTIPLY BY, BY KW KILOWATTS
VOLUME DAMPER x" INCHES, INCH C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.

7 PROVIDE ACCESS DOORS IN INACCESSIBLE CEILINGS TO ACCESS MEP DEVICES ABOVE CEILINGS NOT OTHERWISE ACCESSIBLE. x' FEET, FOOT L LONG, LENGTH THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
± PLUS OR MINUS LA LABORATORY AIR RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
REFERENCE SYMBOLS ELBOW W/ DOUBLE THICKNESS TURNING VANES DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
8 INSTALL FLEXIBLE DUCTS IN ACCORDANCE WITH SMACNA STANDARDS AND PROJECT SPECIFICATIONS. ≤ LESS THAN OR EQUAL TO LAT LEAVING AIR TEMPERATURE RIGHTS, INCLUDING THE COPYRIGHT.
≥ GREATER THAN OR EQUAL TO LBS POUNDS
DESIGNATION DESCRIPTION
9 MAXIMUM ALLOWED FLEXIBLE DUCT LENGTH SHALL BE FIVE (5) FEET. RECTANGULAR BRANCH TAKE-OFF LBS/HR POUNDS PER HOUR
@ AT LN LIQUID NITROGEN NOTES:
POINT OF CONNECTION TO EXISTING
10 PROVIDE MANUAL VOLUME DAMPERS AT EACH DUCT BRANCH LEADING TO AN OUTLET/INLET OPENING. INSTALL DAMPERS AS FAR AS A COMPRESSED AIR LP LIQUID PROPANE
POSSIBLE AWAY FROM THE DIFFUSER. BELL MOUTH BRANCH TAKE-OFF
AAV AUTOMATIC AIR VENT LPG LIQUID PETROLEUM GAS
POINT OF DISCONNECTION
ACV AUTOMATIC CONTROL VALVE LPR LOW PRESSURE STEAM RETURN
11 REFER TO AIR DEVICE SCHEDULE FOR INLET DUCT SIZES UNLESS OTHERWISE INDICATED. ROUND BRANCH TAKE-OFF AD ACCESS DOOR, AREA DRAIN LPS LOW PRESSURE STEAM SUPPLY
FIRE RATED WALL LINETYPES AF ANTIFREEZE LV LABORATORY VENT, LABORATORY VACUUM
12 VERIFY REFLECTED CEILING PLANS IN THE FIELD FOR EXACT LAYOUT LOCATION OF ALL CEILING GRILLES & DIFFUSERS, COORDINATE AFF ABOVE FINISHED FLOOR LW LABORATORY WASTE
WITH ALL OTHER TRADES FOR THEIR LAYOUTS. ROUND DUCT DROP OFF BOTTOM
AR ARGON GAS LWT LEAVING WATER TEMPERATURE
SEE ARCHITECTURAL PLANS FOR RATED WALL LEGEND ATC AUTOMATIC TEMPERATURE CONTROL
13 COORDINATE FINAL EQUIPMENT/FIXTURE LOCATIONS WITH THE GENERAL CONTRACTOR. THE LOCATION AS INDICATED ON THE DRAWING DUCT TRANSITION MA MEDICAL AIR
IS APPROXIMATE. INSTALL ALL MECHANICAL EQUIPMENT SUCH THAT MANUFACTURER'S MAINTENANCE AREA IS CLEAR.
BAS BUILDING AUTOMATION SYSTEM MAV MANUAL AIR VENT
SQUARE TO ROUND TRANSITION BBD BOILER BLOWDOWN MAX MAXIMUM
14 COORDINATE ALL MECHANICAL, PLUMBING AND ELECTRICAL WORK & EQUIPMENT WITH STRUCTURAL MEMBERS, ELECTRICAL WORK,
FIXTURES AND ALL OTHER TRADES. BCWR BEARING COOLING WATER RETURN MBH THOUSAND BRITISH THERMAL UNITS PER HOUR
BCWS BEARING COOLING WATER SUPPLY MCC MOTOR CONTROL CENTER
UP/DN DUCTWORK CHANGE IN ELEVATION (UP OR DOWN)
15 RUN ALL PIPING CONCEALED ABOVE CEILING EXCEPT WHERE INDICATED. BDD BACKDRAFT DAMPER MEQ MECHANICAL EQUIPMENT
BFP BACKFLOW PREVENTER MH-# MANHOLE
B 16 PROVIDE MANUAL AIR VENTS AT ALL HIGH POINTS & DRAIN VALVES WITH CAPPED HOSE CONNECTIONS AT ALL LOW POINTS OF PIPING SUPPLY / OUTSIDE AIR DUCT RISER BHP BRAKE HORSEPOWER MIN MINIMUM B
SYSTEMS. BMS BUILDING MANAGEMENT SYSTEM MISC MISCELLANEOUS
BO BLOW OFF MO MOTOR OIL PIPING
RETURN AIR DUCT RISER
17 FIRESTOP/SMOKESTOP AND SLEEVE ALL PENETRATIONS THROUGH FIRE/SMOKE RATED ASSEMBLIES. REFER TO LIFE SAFETY PLANS FOR BTU BRITISH THERMAL UNIT MOD MOTOR OPERATED DAMPER
RATED ASSEMBLIES AND LOCATIONS. BTUH BRITISH THERMAL UNIT PER HOUR MPR MEDIUM PRESSURE STEAM RETURN
EXHAUST / RELIEF AIR DUCT RISER BV BALANCING VALVE MPS MEDIUM PRESSURE STEAM SUPPLY
18 REGARDLESS OF HOW PIPING IS PRESENTED ON THE DRAWINGS, PROVIDE ECCENTRIC (FLAT ON TOP) REDUCERS IN HYDRONIC PIPING. MV MEDICAL VACUUM
ROUND DUCT RISER CA CONTROL AIR
19 COORDINATE FINAL THERMOSTAT LOCATIONS WITH INTERIOR FINISH AND FURNITURE EQUIPMENT DRAWINGS PRIOR TO INSTALLATION. CBD CONTINUOUS BLOWDOWN N NITROGEN
MOUNT SENSORS 48" AFF TO THE TOP OF THE DEVICE. TYPICAL FOR ALL SENSORS. CONTRACTOR SHALL SCHEDULE WALKTHROUGH MAINTENANCE CC CAMPUS CONDENSATE NA, N/A NOT APPLICABLE
WITH OWNER, ARCHITECT AND ENGINEER FOR FINAL DEVICE LOCATION DETERMINATION. ACCESS AREA CCMS CENTRAL CONTROL AND MONITORING SYSTEM NC NOISE CRITERIA, NORMALLY CLOSED
TERMINAL UNIT WITH REHEAT COIL CD CONDENSATE DRAIN NFPA NATIONAL FIRE PROTECTION ASSOCIATION
20 CONTRACTOR SHALL PROVIDE INDOOR AIR POLLUTION PREVENTION MEASURES DURING ALL DEMOLITION AND CONSTRUCTION CF CHEMICAL FEED NG NATURAL GAS
ACTIVITES BY CREATING, MAINTAINING AND MONITORING A NEGATIVE PRESSURE DIFFERENTIAL OF 0.015-INCH WATER GAUGE IN THE
X AIR DEVICE CFM CUBIC FEET PER MINUTE NO NORMALLY OPEN, NITROUS OXIDE
CONSTRUCTION WORK AREA RELATIVE TO AREAS OUTSIDE THE WORK ZONE. PORTABLE AIR SCRUBBERS SIZED FOR 300-800 CFM WITH AIR DEVICE IDENTIFIER
TYPE CHEL CHELANT No NUMBER
PARTICULATE PRE-FILTERS AND A TRUE HEPA FILTER CERTIFIED TO A MINIMUM FILTRATION EFFICIENCY OF 99.97% AT 0.3 MICRONS IN XX
ACCORDANCE WITH IEST-RP-CC001.3 REQUIREMENTS SHALL BE USED, AND THE VOLUME DAMPERS IN THE SUPPLY AIR DEVICES SERVING CFM CHR CHILLED WATER RETURN NOM NOMINAL
THE CONSTRUCTION ZONE SHALL BE TEMPORARILY CLOSED UNTIL ALL CONSTRUCTION ACTIVITIES ARE COMPLETE. THE CONTRACTOR CHS CHILLED WATER SUPPLY NPSH NET POSITIVE SUCTION HEAD
SHALL PROVIDE THE OWNER AND ARCHITECT WITH PROPOSED LOCATION(S) OF HEPA FILTERED AIR FILTRATION EQUIPMENT AND ALL --
EXISTING AIR DEVICE IDENTIFIER CHX CHILLED WATER HEAT EXCHANGER NPW NON-POTABLE WATER
NEGATIVE PRESSURE METHODS. METHODS UTILIZED SHALL BE IN ACCORDANCE WITH THE FACILITIES GUIDELINES INSTITUTE (FGIC) XX
CFM CO CLEANOUT
GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITALS AND OUTPATIENT FACILITIES SECTION 1.2 - 3.2.3 AND THE OWNER'S
REQUIREMENTS. ALL AIR SHALL BE EXHAUSTED TO THE EXTERIOR A MINIMUM OF 25 FEET FROM ANY AIR INTAKE. THE PRESSURE CO2 CARBON DIOXIDE O OXYGEN
DIFFERENTIAL SHALL BE CONTINUOUSLY MONITORED ACROSS THE BARRIERS BETWEEN THE CONSTRUCTION AREA AND ADJACENT CS CLEAN STEAM OA OUTSIDE AIR
AREAS, AND DAILY AIRBORNE PARTICLE SAMPLING/TESTING OF AIR QUALITY SHALL BE CONDUCTED IN AREAS ADJACENT TO THE CT COMBUSTION TURBINE OD OVERFLOW DRAIN
CONSTRUCTION WORK TO EVALUATE AND VERIFY BARRIER INTEGRITY. LINETYPE SYMBOLS CW COLD WATER, DOMESTIC CITY WATER OED OPEN ENDED DUCT
C C
CWR CONDENSER WATER RETURN OF OVERFLOW
21 REFER TO ARCHITECTURAL DRAWINGS FOR PHASING PLAN. ALL WORK SHALL BE PERFORMED IN A SEQUENCE AND DURING HOURS TO CWS CONDENSER WATER SUPPLY OS&Y OUTSIDE STEM AND YOKE
MINIMIZE DISRUPTION TO THE BUILDING WHICH WILL REMAIN OCCUPIED DURING CONSTRUCTION. DESIGNATION DESCRIPTION
°C DEGREE(S) CELSIUS
P&ID PROCESS AND INSTRUMENTATION DIAGRAM
HVAC GENERAL DEMOLITION NOTES DEMOLITION WORK (SHOWN ON DEMOLITION PLANS) D DEEP, DRAIN WATER PA PLANT AIR
DB DECIBEL, DRY BULB PC PUMPED CONDENSATE
1 NOTIFY THE OWNER, IN WRITING, AT LEAST SEVEN (7) DAYS IN ADVANCE OF ALL REQUIRED SHUTDOWNS OF WATER, FIRE, SEWER, GAS, EXISTING WORK DDC DIRECT DIGITAL CONTROL PCHR PRIMARY CHILLED WATER RETURN
ELECTRICAL SERVICE, OR OTHER UTILITIES. UPON WRITTEN RECEIPT OF APPROVAL FROM OWNER, SHUTDOWN SHALL BE PERFORMED NEW WORK DESIG DESIGNATION PCHS PRIMARY CHILLED WATER SUPPLY
BETWEEN THE HOURS OF SIX (6) P.M. AND SIX (6) A.M. OR AS DIRECTED OTHERWISE BY THE OWNER AND SHALL BE ACCOMPLISHED AT NO
DHR DISTRIBUTION HEATING WATER RETURN PCP PUMP CONTROL PANEL
ADDITIONAL CONTRACT COST. AT THE END OF EACH SHUTDOWN ALL SERVICES SHALL BE RESTORED SO THAT NORMAL USE OF THE
UTILITIES CAN CONTINUE. DHS DISTRIBUTION HEATING WATER SUPPLY PCR PUMPED CONDENSATE RECIRCULATION
DHWR DOMESTIC HOT WATER RETURN PCWR PROCESS COOLING WATER RETURN
2 WHEN WORKING IN AND AROUND THE EXISTING BUILDING, EXTREME CARE SHALL BE EXERCISED WITH REGARD TO PROTECTION OF THE DHWS DOMESTIC HOT WATER SUPPLY PCWS PROCESS COOLING WATER SUPPLY
EXISTING STRUCTURE AND MECHANICAL AND ELECTRICAL SERVICES WHICH WILL REMAIN. REPAIR, REPLACE, OR RESTORE TO THE DIA, Ø DIAMETER PD PRESSURE DROP, PUMP DISCHARGE
SATISFACTION OF THE ENGINEER ALL EXISTING WORK DAMAGED IN THE PERFORMANCE OF DEMOLITION AND/OR NEW WORK. DIR DEIONIZED WATER RETURN PG PILOT GAS
DIS DEIONIZED WATER SUPPLY PGR PROCESS GLYCOL WATER RETURN
3 ALL EXISTING PIPING, EQUIPMENT, DUCTWORK, AND MATERIALS NOT REQUIRED FOR RE-USE OR RE-INSTALLATION (SHOWN OR DL DOOR LOUVER PGS PROCESS GLYCOL WATER SUPPLY
OTHERWISE) SHALL BE REMOVED. ALL EXISTING MATERIALS AND EQUIPMENT WHICH ARE REMOVED AND ARE DESIRED BY THE OWNER, DN DOWN PH PHASE
OR ARE INDICATED TO REMAIN THE PROPERTY OF THE OWNER, SHALL BE DELIVERED TO HIM ON THE PREMISES BY THE CONTRACTOR DSP DRY SPRINKLER PIPE PHR PRIMARY HEATING RETURN
WHERE DIRECTED BY THE ENGINEER. ALL OTHER MATERIALS AND EQUIPMENT WHICH ARE REMOVED SHALL BECOME THE PROPERTY OF
THE CONTRACTOR AND SHALL BE REMOVED BY THE CONTRACTOR FROM THE PREMISES. DTR DUAL TEMPERATURE RETURN PHS PRIMARY HEATING SUPPLY
DTS DUAL TEMPERATURE SUPPLY PIV POST INDICATING VALVE
DW DISTILLED WATER PPH POUNDS PER HOUR
4 EXISTING CONDITIONS, I.E., PRESENCE AND LOCATION OF DUCTWORK, PIPING, EQUIPMENT AND MATERIALS, INDICATED ARE BASED ON
INFORMATION OBTAINED FROM AVAILABLE RECORD DRAWINGS AND FIELD SURVEYS AND ARE NOT WARRANTED TO BE COMPLETE OR PRV PRESSURE REDUCING VALVE, PRESSURE REGULATING
CORRECT. CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION OF ALL DUCTWORK, PIPING, EQUIPMENT AND MATERIALS IN THE FIELD (E) EXISTING VALVE
PRIOR TO STARTING ALL WORK. EA EXHAUST AIR PSI POUNDS PER SQUARE INCH
EAT ENTERING AIR TEMPERATURE PSIG POUNDS PER SQUARE INCH GAUGE
5 EXISTING DUCT, PIPE, AND EQUIPMENT SIZES NOTED ARE FOR THE CONVENIENCE OF THE CONTRACTOR ONLY AND ARE NOT ED EQUIPMENT DRAIN PW POTABLE WATER
D WARRANTED TO BE CORRECT. CONTRACTOR SHALL VERIFY ALL SIZES IN THE FIELD IF THEY EFFECT HIS WORK. EJ EXPANSION JOINT D
ELEV ELEVATION (R) RELOCATE, RELOCATED
6 EXISTING PIPING NO LONGER REQUIRED TO REMAIN IN SERVICE (SHOWN OR OTHERWISE) SHALL BE DISCONNECTED AND REMOVED BACK EMS ENERGY MANAGEMENT SYSTEM RA RETURN AIR, RELIEF AIR
TO SERVICE MAINS UNLESS OTHERWISE INDICATED OR NOTED ON THE PLANS. REMOVE EXISTING PIPE HANGERS, SUPPORTS, VALVES, RAF RETURN AIR FAN
EQ EQUIPMENT, EQUALIZING
ETC.. EXISTING PIPING INDICATED OR REQUIRED TO REMAIN IN SERVICE OR IN PLACE SHALL BE CAPPED, PLUGGED, OR OTHERWISE
ESP EXTERNAL STATIC PRESSURE RD REFRIGERANT DISCHARGE PROJECT NUMBER: H51-50068
SEALED. NO EXISTING PIPING SHALL BE LEFT OPEN END.
ETC ETCETERA RDR ROOF DRAIN
EVAC GAS EVACUATION RH RELATIVE HUMIDITY DHEC PROJECT NUMBER: 580145
7 EXISTING DUCTWORK INDICATED TO BE DISCONNECTED AND REMOVED SHALL INCLUDE ALL RELATED AIR DEVICES, HANGERS,
SUPPORTS, ETC., UNLESS OTHERWISE INDICATED OR NOTED ON THE PLANS. EXISTING DUCTWORK WHERE INDICATED TO BE CAPPED OR EWT ENTERING WATER TEMPERATURE RHR REHEAT WATER RETURN
REQUIRED TO REMAIN IN SERVICE SHALL BE CAPPED WITH 18 GAUGE SHEET METAL. SECURE CAP WITH SHEET METAL SCREWS AND SEAL EX EXISTING RHS REHEAT WATER SUPPLY
PERIMETER OF OPENING AIR TIGHT WITH DUCT SEALER. NO EXISTING DUCTWORK SHALL BE LEFT OPEN FOR ANY EXTENDED PERIOD OF
TIME. CAP EXISTING DUCTWORK IMMEDIATELY AS REQUIRED OR DIRECTED BY THE ENGINEER. CONTRACTOR SHALL RETURN ALL AIR F FIRE LINE
RI
RL
REMOVE AND REINSTALL
REFRIGERANT LIQUID
CONSTRUCTION
DEVICES TO OWNER.
F&T
FC
FLOAT AND THERMOSTATIC TRAP
FLEXIBLE CONNECTION
ROR
ROS
REVERSE OSMOSIS WATER RETURN
REVERSE OSMOSIS WATER SUPPLY DOCUMENTS
8 EXISTING MECHANICAL AND ELECTRICAL EQUIPMENT, PIPING, DUCTWORK, AND MATERIALS AFFECTED BY DEMOLITION OR NEW WORK RPM REVOLUTIONS PER MINUTE 5/8/2018 3:45:08 PM
INSTALLATION AND REQUIRED TO REMAIN IN SERVICE SHALL BE RE-INSTALLED OR SUPPORTED AS REQUIRED IN ACCORDANCE WITH NEW FD FIRE DAMPER, FOUNDATION DRAIN
WORK SPECIFICATION. ALL WORK SHALL BE COMPLETED TO THE SATISFACTION OF THE ENGINEER AND AT NO ADDITIONAL CONTRACT FDR FLOOR DRAIN RS REFRIGERANT SUCTION
COST. FDV FIRE DEPARTMENT VALVE RV RELIEF VENT, REFRIGERANT VENT
FF FINISHED FLOOR RX REMOVE EXISTING STORM EYE INSTITUTE
9 PATCH ALL DISTURBED SURFACES, INCLUDING WALLS, CEILINGS, ROOF, AND FLOOR. PATCHING SHALL MATCH EXISTING ADJACENT FFE FINISHED FLOOR ELEVATION
SURFACES AS TO THICKNESS, TEXTURE, MATERIALS, AND COLOR. ALL PATCHING SHALL BE PERFORMED TO THE SATISFACTION OF THE
OWNER/ENGINEER AND AT NO ADDITIONAL CONTRACT COST.
FIN/FT
FIN/INCH
FINS PER FOOT
FINS PER INCH
SA
SA
SUPPLY AIR
SHOCK ARRESTOR
OPTICAL SHOP
10 IN GENERAL ALL PIPING, EQUIPMENT, DUCTWORK, AND MATERIALS SHOWN "LIGHT" IS EXISTING TO REMAIN. ALL PIPING, CONDUITS,
FM FLOWMETER SAN
SCHR
SANITARY, SOIL, WASTE
SECONDARY CHILLED WATER RETURN
H51-50068
FMF FLOWMETER FITTING
EQUIPMENT, DUCTWORK, AND MATERIALS SHOWN "HEAVY AND DASHED" IS EXISTING AND SHALL BE DEMOLISHED. SCHS SECONDARY CHILLED WATER SUPPLY
FO FUEL OIL 167 ASHLEY AVE
FOF FUEL OIL FILL SD STORM DRAIN, SMOKE DETECTOR
11 ALL WORK SHALL BE PERFORMED IN A SEQUENCE AND DURING HOURS TO MINIMIZE DISRUPTION TO THE BUILDING WHICH WILL REMAIN
FOSUCT FUEL OIL SUCTION SF SQUARE FOOT CHARLESTON, SC 29425
OCCUPIED DURING CONSTRUCTION.
FOTP FUEL OIL TRANSFER PUMP SHR SECONDARY HEATING WATER RETURN
E E
FOV FUEL OIL VENT SHS SECONDARY HEATING WATER SUPPLY
12 ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE SOUTH CAROLINA CODES, CITY OF CHARLESTON, AND THE LOCAL FIRE
FPM FEET PER MINUTE SL SOUND LINING
MARSHALL'S REQUIREMENTS.
FPS FEET PER SECOND SP STATIC PRESSURE
13 THIS CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING WITH ALL OTHER TRADES/ SUBCONTRACTORS INCLUDING BUT NOT FS FLOW SWITCH SPR SPRINKLER LINE ROSENBLUM COE
LIMITED TO AUTOMATIC TEMPERATURE CONTROLS, ELECTRICAL, AND GENERAL TRADES. FT
FW
FOOT, FEET
FEED WATER
SQ FT
SS
SQUARE FOOT
STAINLESS STEEL
ARCHITECTS,
14 CONTRACTOR SHALL MAINTAIN ACCESS TO ALL STAIRWELLS AND EGRESS CORRIDORS DURING CONSTRUCTION. FWR FEED WATER RECIRCULATION SSUL SODIUM SULFITE INC.
FWS FEED WATER SUCTION STDR STORM DRAIN
15 CONCRETE CORING OR CUTTING MAY BE REQUIRED IN ORDER TO RUN ELECTRICAL, PLUMBING, CABLING OR OTHER SERVICES TO A °F DEGREE(S) FAHRENHEIT SW SOFT WATER 1643 MEANS STREET
SPECIFIC AREA. IT IS IMPERATIVE WHEN CONSIDERING EITHER CORING, CUTTING OR CHIPPING THAT REBAR, PLUMBING, ELECTRICAL CHARLESTON, SC 29412
SERVICES, ETC WITHIN THE CONCRETE SLAB, WALL OR FLOOR BE LOCATED PRIOR TO DISTURBING THE INTEGRITY OF THE EXISTING G NATURAL GAS TS TAMPER SWITCH
CONCRETE. OBTAIN STRUCTURAL DRAWINGS OF THE AREA IN QUESTION AND, USING THE BUILDING GRIDLINES, DETERMINE AND MARK GAL GALLON, GALLONS TSP TOTAL STATIC PRESSURE
THE EXACT LOCATIONS REQUIRED FOR NEW SERVICES. DETERMINE THE FINAL LOCATION OF THE CORE OR CUT BY LOCATING THE 843.577.6073
GEN GENERATOR TW TREATED WATER
PRECISE POSITIONING OF ANY REBAR USING X-RAYS OR FERRO SCAN.
GHR GLYCOL HEATING RETURN TWR TEMPERED WATER RETURN
GHS GLYCOL HEATING SUPPLY TWS TEMPERED WATER SUPPLY
16 ALL PENETRATIONS MUST BE SEALED WITH FIRE STOP MATERIAL AFTER SERVICES ARE RUN THROUGH. ALL PENETRATIONS THROUGH
EXTERIOR WALLS ABOVE AND BELOW GRADE OR SLAB ON GRADE MUST BE WATERPROOFED. GPH GALLONS PER HOUR TYP TYPICAL
GPM GALLONS PER MINUTE ∆T TEMPERATURE DIFFERENCE
17 FINAL CEILING HEIGHTS TO BE DETERMINED WITH ENGINEER IN FIELD AFTER DEMOLITION OF EXISTING CEILINGS. NO FABRICATION OF GR AUTOMOTIVE LUBRICATION PIPING
DUCTWORK, HVAC PIPING OR PLUMBING PIPING SHALL BEGIN UNTIL AFTER THE CONTRACTOR HAS COMPLETED COORDINATION UCD UNDERCUT DOOR
DRAWINGS AND COORDINATED THE CEILING HEIGHTS WITH THE ENGINEER. H HIGH UL UNDERWRITERS LABORATORIES MECHANICAL NOTES, SYMBOLS AND
HB HOSE BIB ABBREVIATIONS
18 ATC CONTRACTOR SHALL DESIGNATE AND NUMBER ALL EQUIPMENT IN ACCORDANCE WITH MUSC STANDARDS. NO DUPLICATE HED HOSE END DRAIN VALVE V VACUUM, VOLTS
DESIGNATION NUMBERS SHALL BE PROVIDED. ALL NUMBERS SHALL BE THE NEXT SEQUENTIAL NUMBER FOR THAT SPECIFIC PIECE OF HP HORSEPOWER VD VOLUME DAMPER
EQUIPMENT. VENT VENTILATION
SHEET NAME
HPR HIGH PRESSURE STEAM RETURN
HPS HIGH PRESSURE STEAM SUPPLY VFD VARIABLE FREQUENCY DRIVE PROJECT NUMBER
F 19 THE CONTRACTOR SHALL NOTIFY THE ENGINEER PRIOR TO CLOSING ANY CEILINGS FOR A COMPLETE CHECKOUT OF THE HVAC SYSTEM.
HR HEATING WATER RETURN VPD VACUUM PUMP DISCHARGE 17016 F
THE SYSTEM MUST BE COMPLETE AND OPERATIONAL INCLUDING CONTROLS, REGISTERS, INSULATION, AND BALANCING WITH REPORT.
HRR HEAT RECOVERY RETURN VSD VARIABLE SPEED DRIVE
THE SYSTEM SHALL BE RUN THROUGH ITS COMPLETE HEATING AND COOLING CYCLES. THE CONTRACTOR AND ALL APPROVED DRAWN BY
SUBCONTRACTORS SHALL BE PRESENT AT THE ENGINEER-ENGINEER CHECKOUT. THE TESTING AND BALANCE AGENCY SHALL CERTIFY HRS HEAT RECOVERY SUPPLY VTR VENT THROUGH ROOF
TSN
THAT THESE CONDITIONS ARE MET. HRSG HEAT RECOVERY STEAM GENERATOR

M001
HS HEATING WATER SUPPLY W WATTS, WIDE
CHECKED BY
20 MUSC WILL NOT TOLERATE ANY LOST TIME TO RESEARCH, TEACHING OR HEALTHCARE AND THEIR ASSOCIATED SPACES DUE TO HT HEIGHT WB WET BULB
CRB
DEFECTIVE OR IMPROPERLY INSTALLED MECHANICAL EQUIPMENT. THEREFORE IF ANY SYSTEMS ARE FOUND TO HAVE DEFECTIVE HTHR HIGH TEMPERATURE HEATING WATER RETURN WC WATER COLUMN
INSTALLATION OR MATERIALS AT BENEFICIAL OCCUPANCY, MUSC HAS THE RIGHT TO IMMEDIATELY HAVE CORRECTIVE WORK HTHS HIGH TEMPERATURE HEATING WATER SUPPLY WG WATER GAUGE
PERFORMED BY OTHERS AND BACK CHARGE THESE COSTS TO THE CONTRACTOR. WH WALL HYDRANT
DATE
05/09/2018
HW HOT WATER
HWR HOT WATER RECIRCULATION WWF WELDED WIRE FABRIC
21 THE CONTRACTOR SHALL BE RESPONSIBLE TO ASSURE THAT ALL WORK BY THE SUBCONTRACTORS IS INSTALLED AND COMPLETED IN WWM WELDED WIRE MESH
HWR HEATING WATER RETURN SCALE
ACCORDANCE WITH THE DRAWINGS AND SPECIFICATIONS AND THAT ALL MEP WORK IS 100% COMPLETE AT THE TIME OF SUBSTANTIAL As indicated
COMPLETION.

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

F S O UT H C A
EO R

OL
T
STA

INA
RMF
ENGINEERING INC.
CHARLESTON, SC
C-00831

RS
RE
G IS
T ER E N EE
A D E NG I A

SEALS

C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.


THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING THE COPYRIGHT.

NOTES:
1 DEMOLISH WALL MOUNTED RETURN AIR GRILL AND ASSOCIATED
DUCTWORK BACK TO MAIN.

2 TEMPORARILY SUSPEND DIFFUSERS FROM STRUCTURE TO


ALLOW FOR NEW CEILING INSTALLATION.

3 DEMOLISH VAV BOX AND DOWNSTREAM DUCTWORK.

4 DIFFUSERS TO BE RELOCATED, SEE M101 FOR FURTHER


INFORMATION.

5 DEMOLISH HEATING HOT WATER SUPPLY AND RETURN AS


INDICATED. CAP TEMPORARILY, SEE M101 FOR FURTHER
INFORMATION.

6 DEMOLISH DIFFUSER, FLEXIBLE DUCTWORK AND DUCTWORK TAP.


PATCH DUCTWORK AND INSULATE TO MATCH EXISTING.

B 7 PRIOR TO ANY WORK BEING PERFORMED THE CONTRACTOR B


SHALL PERFORM A BASELINE AIR AND PRESSURE READING AT
T THIS POINT. THE BASELINE AIR READINGS SHALL BE COMPILED
INTO A REPORT AND SUBMITTED TO THE OWNER AND ENGINEER
OF RECORD FOR REVIEW.

8 PRIOR TO ANY WORK BEING PERFORMED THE CONTRACTOR


SHALL PERFORM A BASELINE AIR AND PRESSURE READING ON
VAV BOX TO ENSURE EXISTING VAV BOX IS CAPABLE OF 400 CFM.
THE CONTRACTOR SHALL FORCE THE VAV BOX INTO ITS FULLY
OPEN POSITION TO OBTAIN REQUIRED FLOW READINGS, IF
NECESSARY. IF VAV BOX TOTAL AIRFLOW IS INSUFFICIENT,
CONTRACTOR SHALL CLEAN AND MAINTAIN THE VAV BOX TO
OPTIMAL CONDITIONS PRIOR TO RETESTING. IMMEDIATELY
NOTIFY THE OWNER, ARCHITECT AND ENGINEER IF AIRFLOWS
ARE INSUFFICENT. THE VAV BOX AIR READINGS SHALL BE
COMPILED INTO A REPORT AND SUBMITTED TO THE OWNER AND
ENGINEER OF RECORD FOR REVIEW.

7 7 9 PRIOR TO ANY WORK BEING PERFORMED THE CONTRACTOR


SHALL PERFORM A BASELINE AIR AND PRESSURE READING ON
VAV BOX TO ENSURE EXISTING VAV BOX IS CAPABLE OF 1100
CFM. THE CONTRACTOR SHALL FORCE THE VAV BOX INTO ITS
FULLY OPEN POSITION TO OBTAIN REQUIRED FLOW READINGS, IF
NECESSARY. IF VAV BOX TOTAL AIRFLOW IS INSUFFICIENT,
CONTRACTOR SHALL CLEAN AND MAINTAIN THE VAV BOX TO
OPTIMAL CONDITIONS PRIOR TO RETESTING. IMMEDIATELY
C NOTIFY THE OWNER, ARCHITECT AND ENGINEER IF AIRFLOWS C
7 ARE INSUFFICENT. THE VAV BOX AIR READINGS SHALL BE
COMPILED INTO A REPORT AND SUBMITTED TO THE OWNER AND
ENGINEER OF RECORD FOR REVIEW.

GENERAL NOTES
1. REFER TO M001 FOR GENERAL NOTES.
PHASE 2 2. ONE COPY OF THE PRE-TAB REPORT SHALL REMAIN WITH THE
CONTRACTOR ON SITE FOR THE DURATION OF THE PROJECT.
7 2 7 2

9
(E) VAV-4

7
D D
2"ø HS
1 1/2"ø HR

FD
7 PROJECT NUMBER: H51-50068

PHASE 1 16"x12"

3/4"ø HS
18"x12" 25"x12" 28"x12" DHEC PROJECT NUMBER: 580145

3/4"ø HR

T
CONSTRUCTION
5 DOCUMENTS 5/8/2018 3:45:12 PM

VAV (E) VAV-2


8 (E) VAV-3

16"x6"
3 8 STORM EYE INSTITUTE
6 7 7 6
OPTICAL SHOP
10"x6" 10"x6" 16"x10" 16"x10"
H51-50068
6
4 7 4 7 7 167 ASHLEY AVE
CHARLESTON, SC 29425
18"x6"
E E
1 18"x8"

7 1 7 DN
ROSENBLUM COE
18"x12" 22"x12" 1 7 30"x12"
ARCHITECTS,
INC.
1 7
1643 MEANS STREET
CHARLESTON, SC 29412

843.577.6073

MECHANICAL DEMOLITION FIRST


FLOOR PLAN
1 HVAC DUCTWORK DEMOLITION PLAN
N
MD101 SCALE: 1/4" = 1'-0" SHEET NAME

PROJECT NUMBER
F 17016 F
DRAWN BY
TSN

CHECKED BY

DATE
CRB

05/09/2018
MD101
SCALE
1/4" = 1'-0"

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

F S O UT H C A
EO R

OL
T
STA

INA
RMF
ENGINEERING INC.
CHARLESTON, SC
C-00831

RS
RE
G IS
T ER E N EE
A D E NG I A

SEALS

C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.


THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING THE COPYRIGHT.

NOTES:
1 PROVIDE MANUAL BALANCING DAMPER IN VERTICAL DUCT DOWN
TO AIR DEVICE. BALANCE TO AIRFLOW INDICATED.

2 TAP BOTTOM OF DUCTWORK. PROVIDE MANUAL BALANCING


DAMPER IN VERTICAL DUCT DOWN TO AIR DEVICE. BALANCE TO
AIRFLOW INDICATED.

3 PLACE DIFFUSER IN NEW CEILING GRID LOCATION.

4 RELOCATED DIFFUSER, BALANCE TO AIRFLOW INDICATED.

5 RELOCATE ONE PNEUMATIC THERMOSTAT TO LOCATION


INDICATION. EXTEND PNEUMATIC TUBING TO TIE TWO EXISTING
VAV BOXES INTO RELOCATED THERMOSTAT.

6 INSTALL NEW DDC THERMOSTAT.

B B
T

PEDIATRIC WAITING
4

-- --
180 180
GENERAL NOTES
1. REFER TO M001 FOR GENERAL NOTES.

2. BALANCE ALL AIR DEVICES AND VAV BOXES IN THE SCOPE OF


WORK AS INDICATED.

C 3. ALL NEW BRANCH PIPING SHALL BE 3/4", UNLESS OTHERWISE C


-- INDICATED.
160
OPTICAL LAB
3

A1
100
RECEPTION
7 PHASE 2 10"Ø
FEC

--
3 160
OPTICAL
2 --
3 160
12"Ø

(E) VAV-4

--
D 2"ø HS 160 D
1 1/2"ø HR

FD
PROJECT NUMBER: H51-50068
PHASE 1 16"x12" 18"x12" 25"x12" 28"x12" DHEC PROJECT NUMBER: 580145
3/4"ø HS
3/4"ø HR

T
CONSTRUCTION
6 T WELCOME AREA
1
DOCUMENTS
5 5/8/2018 3:45:09 PM
EXAM ROOM VAV-1 (E) VAV-2
5 A2
(E) VAV-3

--
12"x10" 16"x10" 400
16"x10"
STORM EYE INSTITUTE
4
B1
120
OPTICAL SHOP
1 120
H51-50068
2 2
B1
8"x6" A2 B2
18"x6"
B2 167 ASHLEY AVE
400 400 400
1 120 18"x6"
18"x6"
CHARLESTON, SC 29425
EXAM ROOM
E -- E
6 120 4

T DN
10"x8" ROSENBLUM COE
18"x12" 22"x12" 30"x12"
ARCHITECTS,
INC.
1643 MEANS STREET
CHARLESTON, SC 29412

843.577.6073

MECHANICAL FIRST FLOOR PLAN

1 HVAC DUCTWORK NEW WORK PLAN


N
M101 SCALE: 1/4" = 1'-0" SHEET NAME

PROJECT NUMBER
F 17016 F
DRAWN BY
TSN

CHECKED BY

DATE
CRB

05/09/2018
M101
SCALE
1/4" = 1'-0"

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

F S O UT H C A
SUPPORT DIFFUSER EO R
INDEPENDENT OF

OL
T
STA

INA
CEILING SYSTEM SHEET METAL DUCT
RMF
SEISMIC BRACING (TYP) ENGINEERING INC.
PROVIDE HARD CAST CHARLESTON, SC
DUCT SEALER AT SEISMIC BRACING (TYP) C-00831

FLEXIBLE DUCT JOINTS


SUPPORT DIFFUSER SHEET METAL

RS
RE
G IS
INDEPENDENT OF DUCT T ER E N EE
A D E NG I A
CEILING SYSTEM
HOT WATER REHEAT COIL
SEALS

MANUAL AIR VENT


C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.
THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
UNION RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
PROVIDE RIGID ELBOW DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
SUPPORT TO MAINTAIN RIGHTS, INCLUDING THE COPYRIGHT.
PRESSURE/TEMPERATURE PLUG
DUCT SHAPE
ECCENTRIC REDUCER
NOTES:
MANUAL AIR VENT
FLOWMETER
FITTING
RIGID DUCT CONNECTION

BALANCING VALVE
WITH MEMORY STOP
SPIN-IN DUCT COLLAR
AIR AUTOMATIC CONTROL VALVE
LAY IN CEILING DIFFUSER WITH VOLUME DAMPER
FLOW REFER TO SCHEDULE FOR "GENEFLEX" SM-10 SERIES
RE REFER TO FLOOR PLANS LENGTH AND CAPACITY
TU
RN FOR SIZE OF MAINS STAINLESS STEEL STRAP CLAMPS

LAY IN RETURN REGISTER VOLUME DAMPER FLEXIBLE DUCT MINIMUM SUSPENDED CEILING
3'-0" LONG, MAXIMUM 5'-0"
REFER TO SCHEDULE FOR LONG. SUPPORT AT
HOSE END
DRAIN SIZE AND CAPACITY CENTER
B B
STRAINER WITH
BLOWDOWN VALVE SUSPENDED CEILING
NOTES:
SU
PP 1. DUCT INSULATION SHALL BE PROVIDED AS SPECIFIED.
BALL VALVE LY
NOTES: 2. PROVIDE ADDITIONAL ROUND, RIGID SHEET METAL DUCTWORK AS REQUIRED TO LIMIT FLEXIBLE DUCT LENGTH TO 5'-0" MAXIMUM.
1. DUCT INSULATION AND LINING SHALL BE PROVIDED AS SPECIFIED. 3. MAXIMUM SAG 1/2" PER FOOT.
2. PROVIDE SEISMIC SWAY BRACING FOR ALL DUCTWORK AND HANGERS PER THE INTERNATIONAL BUILDING CODE AND INTERNATIONAL MECHANICAL CODE. 4. PROVIDE SEISMIC SWAY BRACING FOR ALL DUCTWORK AND HANGERS PER THE INTERNATIONAL BUILDING CODE AND INTERNATIONAL MECHANICAL CODE.
3. CONTRACTOR SHALL VERIFY MAXIMUM LOADING ON DUCTWORK SUPPORT ASSEMBLIES. 5. CONTRACTOR SHALL VERIFY MAXIMUM LOADING ON DUCTWORK SUPPORT ASSEMBLIES.

1
DETAIL - HYDRONIC COIL (3-WAY) 2
DETAIL - RETURN/EXHAUST AIR REGISTER BRANCH DUCT 3
DETAIL - CEILING DIFFUSER BRANCH DUCTS
SCALE: N.T.S. SCALE: N.T.S. SCALE: N.T.S.

C C

SUPPLY VARIABLE AIR VOLUME TERMINAL REHEAT UNIT


(REFER TO SCHEDULE FOR CAPACITY AND TYPE) ATTACH WITH MINIMUM 4 SHEET
SEQUENCE OF OPERATION METAL SCREWS AND SEAL
SUPPORT FROM STRUCTURE ABOVE WITH 3/8" HOT WATER REHEAT COIL WITH HARD CAST DUCT TAPE
A. THE VARIABLE VOLUME AIR TERMINAL SHALL OPERATE ON AN OCCUPIED/UNOCCUPIED SCHEDULE. OCCUPIED/UNOCCUPIED MODES SHALL BE AS DETERMINED BY THE DIAMETER RODS AND ANGLES
OCCUPIED/UNOCCUPIED PROGRAM OF THE BUILDING AUTOMATION SYSTEM (BAS).
TRANSITION AS REQUIRED TRANSITION AS REQUIRED STAINLESS STEEL
B. OCCUPIED MODE
TO INLET SIZE FOR DISCHARGE DUCT STRAP CLAMP
1. WHEN THE SPACE TEMPERATURE IS BETWEEN ITS COOLING AND HEATING SETPOINTS THE SUPPLY AIR TERMINAL DAMPER SHALL BE AT ITS MINIMUM POSITION SET POINT.
SHEET METAL
2. THE SUPPLY AIR TERMINAL DAMPER SHALL INITIALLY OPEN TO ITS MINIMUM POSITION.
DUCT
3. ON A RISE IN SPACE TEMPERATURE ABOVE SETPOINT, THE DAMPER SHALL MODULATE TOWARD IT'S MAXIMUM POSITION SET POINT. FLEXIBLE DUCT MAXIMUM
INSULATION 18" LONG
4. ON A DROP IN SPACE TEMPERATURE BELOW COOLING SET POINT, THE DAMPER SHALL MODULATE TOWARD IT'S MINIMUM POSITION SET POINT.

5. WHEN THE DAMPER REACHES ITS MINIMUM POSITION SET POINT AND THE SPACE TEMPERATURE FALLS BELOW SETPOINT THE HEATING CONTROL VALVE SHALL AND MODULATE TO OVERLAP
MAINTAIN SPACE TEMPERATURE SETPOINT. MINIMUM 4"
FLEXIBLE DUCT MAXIMUM 18"
DISCHARGE DUCT REFER
LONG. KEEP STRAIGHT WITHOUT

HR
6. ON A CONTINUED FALL IN SPACE TEMPERATURE THE HEATING VALVE SHALL CONTINUE TO MODULATE OPEN UNTIL THE DISCHARGE AIR TEMPERATURE REACHES THE SCHEDULED TO PLANS FOR SIZE
ANY KINKS OR BENDS (NOTE 1)
DESIGN MAXIMUM.

HS
7. ON A FURTHER DROP IN SPACE TEMPERATURE WITH THE DISCHARGE AIR TEMPERATURE AT ITS DESIGN MAXIMUM, THE DAMPER SHALL MODULATE FROM ITS MINIMUM AIRFLOW TO ACCESS DOOR PROVIDE
ITS MAXIMUM HEATING AIRFLOW WHILE MAINTAINING THE SCHEDULED MAXIMUM DISCHARGE AIR TEMPERATURE. DETAIL "A" DETAIL "A"
MAXIMUM SIZE ALLOWABLE

8. ON A RISE IN SPACE TEMPERATURE, THE REVERSE SHALL OCCUR.


3-WAY CONTROL VALVE
NOTE 2
C. UNOCCUPIED MODE
D REFER TO 3-WAY HYDRONIC PIPING DETAIL D
CONTROLLER PROVIDED BY ATC
1. THE SUPPLY AIR TERMINAL UNIT DAMPER SHALL CLOSE TO MINIMUM POSITION AND THE HEATING CONTROL VALVE SHALL BE CLOSED WHEN THE UNOCCUPIED MODE IS INITIATED.
CONTRACTOR, MOUNTED ON ACCESSIBLE SIDE
OF TERMINAL UNIT BY UNIT MANUFACTURER.
2. THE UNOCCUPIED SEQUENCE OF OPERATION SHALL BE THE SAME AS THE OCCUPIED SEQUENCE OF OPERATION, CONTROLLING TO THE UNOCCUPIED SETPOINTS.

D. WARM-UP MODE
PROJECT NUMBER: H51-50068

1. THE SUPPLY AIR TERMINAL DAMPER SHALL BE OPEN TO MAXIMUM HEATING POSITION AND THE HEATING VALVE SHALL ENERGIZE AND MODULATE TO MAINTAIN THE OCCUPIED DHEC PROJECT NUMBER: 580145
ROOM TEMPERATURE SET POINT.

E. COOL-DOWN MODE
NOTES: CONSTRUCTION
1. AIR TERMINAL UNIT DAMPER SHALL INITIALLY BE OPEN TO MAXIMUM COOLING POSITION AND SHALL MODULATE TO MAINTAIN THE OCCUPIED ROOM TEMPERATURE SET POINT.

F. THE SYSTEM AND AIR TERMINAL UNITS MAY BE PLACED INTO THEIR OCCUPIED MODE FOR A SCHEDULED OVERRIDE PERIOD FROM A CENTRAL COMMAND FROM THE BAS, OR THE
1. FLEXIBLE DUCTWORK SHALL NOT BE INSTALLED THROUGH WALLS OR PARTITIONS. SOLID DUCTWORK THE SAME DIMENSION AS THE FLEXIBLE DUCTWORK SHALL BE USED THROUGH THE PENETRATION, THEN TRANSITION TO THE FLEXIBLE DUCTWORK AS INDICATED ON THE DETAIL. DOCUMENTS 5/8/2018 3:45:10 PM
SYSTEM AND AIR TERMINAL UNITS MAY BE PLACED INTO THEIR OCCUPIED MODE FOR A 2-HOUR OVERRIDE PERIOD BY PUSHING THE OVERRIDE BUTTON LOCATED ON THE SPACE 2. A STRAIGHT SECTION OF UNRESTRICTED DUCT AT LEAST TWO (2) DIAMETERS LONG SHALL BE INSTALLED AT THE TERMINAL UNIT INLET.
TEMPERATURE SENSOR SERVING THE AIR TERMINAL UNIT.

G. UPON LOSS OF POWER, DAMPER SHALL FAIL TO THE LAST POSITION HELD PRIOR TO LOSS OF POWER.
STORM EYE INSTITUTE
OPTICAL SHOP
DRAWING NOTES:
H51-50068
1 TEMPERATURE SENSOR SHALL BE INSTALLED TWO FEET DOWNSTREAM OF AIR TERMINAL UNIT.
167 ASHLEY AVE
4
DETAIL - VARIABLE AIR VOLUME TERMINAL REHEAT UNIT CHARLESTON, SC 29425
SCALE: N.T.S.
E E
SAT SAT
AI 3 AI 2
SAT
ROSENBLUM COE
AI 5 1 TS ARCHITECTS,
THERMOSTAT
TS SPACE TEMPERATURE SENSOR
1. UNLESS OTHERWISE NOTED, DEVICES LOCATED IN OCCUPIED SPACES SHALL BE
INC.
MOUNTED 48" TO THE TOP OF THE DEVICE TO MATCH ELECTRICAL DEVICES.
SAT 1643 MEANS STREET
A0 1 2. COORDINATE FINAL SENSOR LOCATIONS WITH INTERIOR FINISH AND FURNITURE CHARLESTON, SC 29412
HOT WATER REHEAT COIL AIR FLOW MEASURING DEVICE EQUIPMENT DRAWINGS PRIOR TO INSTALLATION.
(INTEGRAL TO AIR TERMINAL)
843.577.6073
SAT 3-WAY CONTROL VALVE
A0 4

HR
HS T

48" MECHANICAL DETAILS AND


FINISHED FLOOR
CONTROLS
SHEET NAME

PROJECT NUMBER
F VARIABLE VOLUME SUPPLY AIR TERMINAL UNIT WITH 17016 F

5
REHEAT 6
SPACE SENSOR DRAWN BY

SCALE: N.T.S. SCALE: N.T.S. TSN

CHECKED BY

DATE
CRB

05/09/2018
M201
SCALE
N.T.S.

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

F S O UT H C A
THROUGH PENETRATION FIRESTOP SCHEDULE EO R

OL
T
STA

INA
RMF
ENGINEERING INC.
CHARLESTON, SC
C-00831
A. THIS SCHEDULE IDENTIFIES REQUIREMENTS FOR ACCEPTABLE THROUGH PENETRATION FIRESTOPS FOR THIS PROJECT BASED ON BARRIER TYPE, BASIS OF BARRIER CONSTRUCTION, AND PENETRANT TYPE.
B. THROUGH PENETRATION FIRESTOPS ARE NOT REQUIRED FOR FLOOR PENETRATIONS CONTAINED TOTALLY WITHIN A RATED SHAFT ENCLOSURE.

RS
RE
G IS
T ER E N EE
A C. FOR EACH PENETRATION, SELECT A THROUGH PENETRATION FIRESTOP BASED ON ACTUAL FIELD CONDITIONS, WHICH INCLUDE BUT ARE NOT LIMITED TO PENETRATION SIZE, PENETRATION SHAPE, PENETRANT MATERIAL(S), QUANTITY OF PENETRANTS PER PENETRATION, AND LOCATION(S) OF PENETRANT(S) WITHIN PENETRATION. D E NG I A

D. NOMENCLATURE OF UL CLASSIFIED FIRESTOP ASSEMBLIES USED IN THIS SCHEDULE IS IDENTICAL TO THAT USED IN CATALOGS OF APPROVED FIRESTOP MANUFACTURERS (SEE DIVISION 15) AND IN UNDERWRITERS LABORATORIES "FIRE RESISTANCE DIRECTORY." SEALS

C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.


THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS

RATED BARRIER PENETRANT TYPE


PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING THE COPYRIGHT.

NOTES:
METALLIC, NONMETALLIC, INSULATED PIPES INSULATED PIPES
UNINSULATED PIPE UNINSULATED PIPE (EX. COPPER, IRON (EX. COPPER, IRON
TYPE BASIS OF NO
OR TUBING OR TUBING PLASTIC, STEEL) IN PLASTIC, STEEL) IN METAL DUCT
CONSTRUCTION FIRESTOP ASSEMBLY REQUIREMENTS PENETRANTS
(EX. COPPER, IRON, (EX. PVC, PP, SYSTEMS OPERATING SYSTEMS OPERATING (NOTE 1)
STEEL) FRPP) BETWEEN 32°F AND 122°F BELOW 32°F OR ABOVE 122°F

SINGLE PENETRANT W-L-1000 SERIES W-L-2000 SERIES W-L-5000 SERIES W-L-5000 SERIES W-L-7000 SERIES
UL CLASSIFIED W-L-0000 SERIES
SERIES OR NOTE 2
METAL STUDS & W-L-8000 SERIES W-L-8000 SERIES W-L-8000 SERIES
MULTIPLE PENETRANTS N/A
GYPSUM WALLBOARD (NOTE 3) (NOTE 3) (NOTE 3)
WALL
B EQUAL TO WALL EQUAL TO WALL EQUAL TO WALL EQUAL TO WALL EQUAL TO WALL EQUAL TO WALL B
(U400 SERIES) F RATING
RATING RATING RATING RATING RATING RATING
T RATING NOTE 5 NOTE 5 NOTE 5 NOTE 5 NOTE 5 NOTE 5
EXCEPTIONS/ ADDED REQUIREMENTS NONE NOTE 8 NOTE 8 NONE NOTE 4 NONE
C-AJ-1000 OR C-AJ-2000 OR C-AJ-5000 OR C-AJ-5000 OR C-AJ-7000 OR
SINGLE PENETRANT
UL CLASSIFIED W-J-0000 SERIES W-J-1000 SERIES W-J-2000 SERIES W-J-5000 SERIES W-J-5000 SERIES W-J-7000 SERIES
POURED CONCRETE,
SERIES OR NOTE 2
CONCRETE BLOCK OR C-AJ-8000 OR W-J-8000 SERIES C-AJ-8000 OR C-AJ-8000 OR
MULTIPLE PENETRANTS N/A
MASONRY (NOTE 3) W-J-8000 (NOTE 3) W-J-8000 (NOTE 3)
WALL
EQUAL TO WALL EQUAL TO WALL EQUAL TO WALL EQUAL TO WALL EQUAL TO WALL EQUAL TO WALL
(BLOCK & U900 SERIES) F RATING
RATING RATING RATING RATING RATING RATING
(ANY THICKNESS)
T RATING NOTE 5 NOTE 5 NOTE 5 NOTE 5 NOTE 5 NOTE 5
EXCEPTIONS/ ADDED REQUIREMENTS NONE NOTES 7 & 8 NOTE 8 NONE NOTE 4 NONE
C-AJ-1000 OR C-AJ-2000 OR C-AJ-5000 OR C-AJ-5000 OR C-AJ-7000 OR
SINGLE PENETRANT C-AJ-0000 SERIES
UL CLASSIFIED F-A-1000 SERIES F-A-2000 SERIES F-A-5000 SERIES F-A-5000 SERIES F-A-7000 SERIES
F-A-0000 SERIES
SERIES
C OR NOTE 2 C-AJ-8000 OR F-A-8000 SERIES C-AJ-8000 OR C-AJ-8000 OR C
POURED CONCRETE MULTIPLE PENETRANTS N/A
(NOTE 3) F-A-8000 (NOTE 3) F-A-8000 (NOTE 3)
FLOOR
(ANY THICKNESS) EQUAL TO FLOOR RATING, EQUAL TO FLOOR RATING, EQUAL TO FLOOR RATING, EQUAL TO FLOOR RATING, EQUAL TO FLOOR RATING, EQUAL TO FLOOR RATING,
F RATING
BUT NOT LESS THAN 1 HR BUT NOT LESS THAN 1 HR BUT NOT LESS THAN 1 HR BUT NOT LESS THAN 1 HR BUT NOT LESS THAN 1 HR BUT NOT LESS THAN 1 HR
T RATING NOTE 6 NOTE 6 NOTE 6 NOTE 6 NOTE 6 NOTE 6
EXCEPTIONS/ ADDED REQUIREMENTS NONE NOTE 7 NONE NONE NOTE 4 NONE

NOTES:
1. THIS SCHEDULE'S DATA APPLY ONLY TO PENETRATIONS WITHOUT DAMPERS. FOR DAMPERED PENETRATIONS, REFER TO SPECIFICATIONS. 5. TEMPERATURE (T) RATINGS OF ASSEMBLIES IN WALLS MAY EQUAL ZERO.
AT DAMPERS, DO NOT APPLY MATERIAL THAT IS NOT INCLUDED IN THE DAMPER'S CLASSIFICATION. 6. TEMPERATURE (T) RATINGS OF ASSEMBLIES IN FLOORS SHALL EQUAL THE GREATER OF EITHER THE BARRIER RATING OR ONE HOUR EXCEPT AS FOLLOWS:
2. SEAL OPENING USING BARRIER'S ORIGINAL CONSTRUCTION. A. AN ASSEMBLY'S T RATING MAY EQUAL ZERO WHEN THE PENETRANT ABOVE THE FLOOR PENETRATION IS CONTAINED AND LOCATED
3. WHERE A SERIES 8000 CLASSIFIED SYSTEM IS NOT AVAILABLE, INSTALL PENETRANTS SINGLY, AND PROVIDE SINGLE-PENETRANT SYSTEMS. WITHIN THE CAVITY OF A WALL.
4. FOR SYSTEMS THAT OPERATE BELOW 32°F OR ABOVE 122°F, COMPLY WITH THE FOLLOWING ADDITIONAL REQUIREMENTS: 7. CLASSIFIED TPFS ASSEMBLY IS NOT REQUIRED WHEN ALL THE FOLLOWING CONDITIONS ARE MET:
A. PROVIDE TPFS SYSTEM USING INTUMESCENT ELASTOMERIC WRAP STRIP AS ITS FILL, VOID, OR CAVITY MATERIAL. A. PENETRANT HAS A MAXIMUM NOMINAL DIAMETER OF 6-INCHES.
B. DO NOT USE SERIES 8000 PENETRATIONS. PROVIDE ONLY SINGLE PENETRATIONS. B. PENETRATION HAS A MAXIMUM AREA OF 144 SQUARE INCHES.
C. ANNULAR SPACE IS COMPLETELY FILLED WITH CONCRETE, GROUT, OR MORTAR THE FULL THICKNESS OF THE BARRIER.
D D

SUPPLY VAV UNIT SCHEDULE PROJECT NUMBER: H51-50068

AIRFLOW (CFM) MAXIMUM AIR HEATING COIL PERFORMANCE DHEC PROJECT NUMBER: 580145
COOLING INLET SIZE OUTLET SIZE MAXIMUM PRESSURE EAT MIN LAT CAPACITY EWT COIL DELTA T WATER FLOW MAX WATER PD BASIS OF
DESIGNATION
VAV-1
TYPE
A
SERVICE
OFFICE #1 & OFFICE #2
MAXIMUM MINIMUM HEATING
240 100 140
(IN)
5
(IN)
12X8
NC
25
DROP (IN WG)
0.15
(°F)
55
(°F)
95
(BTU/HR)
5292
(°F)
200
(°F)
20
(GPM)
0.6
(FT WG)
5
DESIGN
TITUS / DESV
REMARKS
CONSTRUCTION
DOCUMENTS 5/8/2018 3:45:11 PM

AIR DEVICE SCHEDULE


STORM EYE INSTITUTE
CFM FACE/ MAX TOTAL MAX NOISE BASIS OF DESIGN
MODULE NOMINAL AIR PD (IN CRITERIA OPTICAL SHOP
NUMBER DUTY TYPE MIN MAX SIZE DUCT SIZE BLOW H2O) VALUE MANUFACTURER MODEL REMARKS
A1 SUPPLY A 0 150 24"x24" 6"ø 4-WAY 0.10 20 TITUS TDC-AA
H51-50068
A2 SUPPLY A 151 400 24"x24" 12"ø 4-WAY 0.10 20 TITUS TDC-AA
167 ASHLEY AVE
B1 RETURN B 0 150 24"x24" 8"x8" PERFORATED 0.10 20 TITUS PAR-AA
CHARLESTON, SC 29425
B2 RETURN B 151 400 24"x24" 12"x12" PERFORATED 0.10 20 TITUS PAR-AA
E E

ROSENBLUM COE
DUCT CONSTRUCTION AND LEAK TEST SCHEDULE
ARCHITECTS,
DUCT CONSTRUCTION DUCT PRESSURE TEST
MAXIMUM INC.
OPERATING PRESSURE POSITIVE SMACNA TEST TEST DUCT LEAK
DUCT SYSTEM REMARKS 1643 MEANS STREET
PRESSURE CLASS OR DUCT SEAL REQUIRED PRESSURE CLASS
(IN WG) (IN WG) NEGATIVE CLASS (YES/NO) (IN WG) CHARLESTON, SC 29412
RECT ROUND
SUPPLY AIR 4" 4" POSITIVE A NO 4" 4 2 1 843.577.6073
SUPPLY AIR 2" 2" POSITIVE A NO 2" 4 2 2
RETURN AIR -2" 2" NEGATIVE B NO 2" 8 4

1. UPSTREAM OF SUPPLY TERMINAL UNIT (FROM AIR HANDLING UNIT TO TERMINAL UNIT).
2. DOWNSTREAM OF SUPPLY TERMINAL UNIT (FROM TERMINAL UNIT TO AIR DEVICE).
MECHANICAL SCHEDULES

SHEET NAME

PROJECT NUMBER
F 17016 F
DRAWN BY
TSN

CHECKED BY

DATE
CRB

05/09/2018
M301
SCALE
12" = 1'-0"

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

ELECTRICAL SYMBOLS
ELECTRICAL ABBREVIATIONS
F S O UT H CA
LIGHTING SYMBOLS
SPECIAL SYSTEMS SYMBOLS
NOTE: THIS IS A STANDARD ABBREVIATION LIST. SOME ABBREVIATIONS MAY NOT APPEAR ON THE ACCOMPANYING DRAWINGS.
EO R

OL
T
POWER SYMBOLS

ST A
2S1W 2 SPEED SINGLE WINDING KW KILOWATTS

INA
RMF
SYMBOL DESCRIPTION MH (UON) SYMBOL DESCRIPTION MH (UON) SYMBOL DESCRIPTION MH (UON) SYMBOL DESCRIPTION 2S2W 2 SPEED DOUBLE WINDING KWH KILOWATT HOUR ENGINEERING INC.
CHARLESTON, SC
C-00831
SINGLE POLE TOGGLE SWITCH 48" TOD H FIRE ALARM HORN TYPE SPEAKER NOTE 5 COMBINATION SWITCH AND SIMPLEX RECEPTACLE 48" TOD RACEWAY "UP" OR "TOWARDS" A, AMP AMPERE LA LIGHTNING ARRESTOR
A/C AIR CONDITIONING LC LIGHTING CONTACTOR

RS
RE
SWITCH: AC ALTERNATING CURRENT LP LIGHTING PANEL GI E
F FIRE ALARM FLASHING STROBE LIGHT - WALL MOUNTED NOTE 5 ST
E R E D E N G IN E
a 48" TOD COMBINATION SWITCH AND DUPLEX RECEPTACLE 48" TOD RACEWAY "DOWN" OR "AWAY"
A SUB-LETTER INDICATES FIXTURES CONTROLLED (a)
AFCI ARC FAULT CIRCUIT INTERRUPTER LRA LOCKED ROTOR AMPERES A
F FIRE ALARM HORN NOTE 5 CIRCUIT CONCEALED IN WALLS OR CEILING SPACE: AFF ABOVE FINISHED FLOOR LTG LIGHTING
2 DOUBLE POLE TOGGLE SWITCH 48" TOD SIMPLEX RECEPTACLE 18" CTR SEALS
CONDUCTORS SHALL BE MINIMUM 2#12 AWG AND 1#12 AWG GROUND AFG ABOVE FINAL GRADE LTNG LIGHTNING
IN 3/4" CONDUIT (UON) AHU AIR HANDLING UNIT
F COMBINATION FIRE ALARM HORN AND FLASHING STROBE LIGHT NOTE 5 DUPLEX RECEPTACLE: C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.
3 THREE-WAY TOGGLE SWITCH (SPDT) 48" TOD E 18" CTR AIC AVAILABLE INTERRUPTING CURRENT MATV MASTER ANTENNA TELEVISION
'E' (IF SHOWN) INDICATES CONNECTED TO EMERGENCY CIRCUIT RACEWAY CONCEALED IN SLAB OR BELOW GRADE THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
ALT ALTERNATE MCB MAIN CIRCUIT BREAKER PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
S F S - CEILING SPEAKER, F - FIRE ALARM SPEAKER DUPLEX RECEPTACLE: ANN ANNUNCIATOR MCC MOTOR CONTROL CENTER RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
4 FOUR-WAY TOGGLE SWITCH (DPDT) 48" TOD BRANCH CIRCUIT HOMERUN TO PANELBOARD:
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
FLOOR MOUNTED APPROX APPROXIMATELY MEH METAL HALIDE RIGHTS, INCLUDING THE COPYRIGHT.
QUANTITY OF CIRCUITS INDICATED BY ARROWS
ARCH ARCHITECT MH MANHOLE, MOUNTING HEIGHT
S FIRE ALARM SPEAKER W/ STROBE DUPLEX RECEPTACLE: NUMBER OF CONDUCTORS SHALL BE MINIMUM 4#12 AWG AND 1#12
K KEY OPERATED SWITCH 48" TOD 18" CTR ATC AUTOMATIC TEMPERATURE CONTROL MLO MAIN LUGS ONLY
SPLIT WIRED, BOTTOM HALF SWITCHED AWG GROUND IN 3/4" CONDUIT (UON) NOTES:
ATS AUTOMATIC TRANSFER SWITCH MSP MOTOR STARTER PANEL
THREE WAY DIMMER SWITCH: RACEWAY RUN EXPOSED:
48" TOD S COMBINATION SPEAKER AND FLASHING STROBE LIGHT DUPLEX RECEPTACLE: AV AUDIOVISUAL MTD MOUNTED
3D a SUBLETTER INDICATES FIXTURES CONTROLLED (a) CEILING MOUNTED
CONDUCTORS SHALL BE MINIMUM 2#12 AWG AND 1#12 AWG GROUND
IN 3/4" CONDUIT (UON) AWG AMERICAN WIRE GAUGE MV MERCURY VAPOR ELECTRICAL SYMBOLS NOTES
MANUAL STARTER W/ OVERLOADS 48" TOD H MAGNETIC DOOR HOLDER DUPLEX RECEPTACLE:
M BUS DUCT OR CABLE TRAY "UP" OR "TOWARDS" BAS BUILDING AUTOMATION SYSTEM NC NORMALLY CLOSED 1. THIS IS A STANDARD SYMBOL LIST. SOME SYMBOLS MAY NOT APPEAR
PEDESTAL TYPE
BFC BELOW FINISHED CEILING NEC NATIONAL ELECTRIC CODE ON THE ACCOMPANYING DRAWINGS.
SWITCH W/ PILOT LIGHT 48" TOD DACT DIGITAL ALARM COMMUNICATOR TRANSMITTER DUPLEX RECEPTACLE: BFG BELOW FINISHED GRADE NFSS NON-FUSED SAFETY SWITCH
P BUS DUCT OR CABLE TRAY "DOWN" OR "AWAY"
MOUNTED 6" ABOVE BACKSPLASH OR COUNTER BLDG BUILDING NO NUMBER, NORMALLY OPEN 2. REFER TO SPECIFICATIONS FOR DETAILED REQUIREMENTS.
FAAP FIRE ALARM ANNUNCIATOR PANEL BOD BOTTOM OF DEVICE
DIMMER SWITCH 48" TOD DUPLEX RECEPTACLE: BUS DUCT: 3. PLAN AND SECTION SYMBOLS MAY ALSO BE USED ON RISER DIAGRAMS.
D GFI 18" CTR
GROUND FAULT INTERRUPTER TYPE OC ON CENTER
TYPE AND SIZE AS INDICATED
FACP FIRE ALARM CONTROL PANEL C, CND CONDUIT OFCI OWNER FURNISHED CONTRACTOR INSTALLED 4. ON SINGLE LINE DIAGRAMS FOR 3 PHASE SYSTEMS, DEVICE
4 BUTTON DIMMER SWITCH 48" TOD DUPLEX RECEPTACLE: QUANTITY = 3, UNLESS OTHERWISE NOTED.
4D GFI CATV CABLE TELEVISION OFOI OWNER FURNISHED OWNER INSTALLED
GFI MOUNTED 6" ABOVE BACKSPLASH OR COUNTER TELEPHONE AND POWER POLE ASSEMBLY
RAM RESCUE ASSISTANCE MASTER CONTROL PANEL 48" TOD CB CIRCUIT BREAKER OH OVERHEAD
5. DEVICE SHALL BE MOUNTED A MINIMUM OF 90” AFF TO BOTTOM OF
LOW VOLTAGE CONTROL SWITCH 48" TOD DUPLEX RECEPTACLE: CCTV CLOSED CIRCUIT TELEVISION
LV H 84" CTR CONCRETE ENCASED DUCTBANK BELOW GRADE DEVICE OR BELOW THE FINISHED CEILING OF NOT LESS THAN 6”
RAR RESCUE ASSISTANCE REMOTE STATION 48" TOD MOUNTED HIGH CKT, CCT CIRCUIT P POLE TO TOP OF DEVICE, WHICHEVER IS LOWER.
CL CURRENT LIMITING PB PUSHBUTTON
MANUAL TIME SWITCH 48" TOD DUPLEX RECEPTACLE:
B T TP FIRE ALARM TRANSPONDER IG
ISOLATED GROUND
18" CTR W SURFACE MOUNTED RACEWAY ASSEMBLY WITH REMOVABLE COVER CLG CEILING PF POWER FACTOR 6. UNLESS OTHERWISE NOTED, ALL INTERIOR CONDUITS AND BOXES B
CONN CONNECT PFCC POWER FACTOR CORRECTION CAPACITOR SHALL BE CONCEALED.
MULTI-OUTLET ASSEMBLY:
MOMENTARY CONTACT SWITCH 48" TOD DOOR SOLENOID, ELECTRIC STRIKE - LOCKING DEVICE CONNECTION DUPLEX RECEPTACLE: CPT CONTROL POWER TRANSFORMER PL PILOT LIGHT
C DS ES 54" CTR DARK SQUARES INDICATE PREWIRED RECEPTACLE LOCATIONS
POINT AT 54" A.F.F. CT CURRENT TRANSFORMER PLC PROGRAMMABLE LIGHTING CONTROL
SIZE AS INDICATED
DOUBLE DUPLEX RECEPTACLE 18" CTR CTR CENTER PNL PANEL
WP SWITCH WITH WEATHERPROOF ENCLOSURE 48" TOD MULTI-OUTLET ASSEMBLY:
F FIRE ALARM PULL STATION 48" TOD CU COPPER PP POWER PANEL
WITH RECEPTACLES LOCATED WHERE INDICATED
CWP COLD WATER PIPE Pp PUMP
OS OS OCCUPANCY SENSOR (CEILING & WALL MOUNTED) HEAT DETECTOR: IG DOUBLE DUPLEX RECEPTACLE 18" CTR 2 CELL MULTI-OUTLET ASSEMBLY:
H H CX CONNECT TO EXISTING PR PAIR
E E = ELEVATOR CONTROLS ISOLATED GROUND WITH COMMUNICATION DEVICES AND RECEPTACLES LOCATED PRN PRINTER
WHERE INDICATED
T TIME CLOCK SMOKE DETECTOR (PHOTOELECTRIC): SIMPLEX RECEPTACLE: DC DIRECT CURRENT PT POTENTIAL TRANSFORMER
P P C 36" CTR
AB E AB = AUDIBLE BASE, E = ELEVATOR CONTROLS CART RECHARGE MULTI-OUTLET ASSEMBLY: DISC DISCONNECT PVC POLYVINYL CHLORIDE
WITH COMMUNICATION DEVICES LOCATED WHERE INDICATED DN DOWN Ø, PH PHASE
R RELAY DUPLEX RECEPTACLE:
I SMOKE DETECTOR (IONIZATION) P 54" CTR DP DISTRIBUTION PANEL
PAY PHONE
FLEXIBLE CONDUIT DPDT DOUBLE POLE DOUBLE THROW QTY QUANTITY
L LIGHTING CONTACTOR DUPLEX RECEPTACLE: DPST DOUBLE POLE SINGLE THROW
D FIRE ALARM DUCT DETECTOR WITH RELAY C 36" CTR
CART RECHARGE DT DOUBLE THROW RCS REMOTE CONTROL SWITCH
CABLE TRAY
SPECIAL RECEPTACLE: DWG DRAWING REC, RECPT RECEPTACLE
P PHOTOCELL OR PUSHPLATE SWITCH C A 18" CTR
CARBON MONOXIDE DETECTOR NEMA 6-20R (20A, 2P, 3W, 208V) REQ'D REQUIRED
GROUND ROD E, EMERG EMERGENCY RFI RADIO FREQUENCY INTERFERENCE
LIGHTING FIXTURE: SPECIAL RECEPTACLE:
RECESSED, SURFACE, OR PENDANT MOUNTED - TYPE AS SPECIFIED ARC FIRE ALARM SYSTEM ADDRESSABLE RELAY - CONTROL B 18" CTR EA EACH RGS RIGID GALVANIZED STEEL
NEMA 6-30R (30A, 2P, 3W, 208V)
LIGHTNING PROTECTION AIR TERMINAL EC EMPTY CONDUIT RLA RUNNING LOAD AMPERES
LIGHTING FIXTURE: SPECIAL RECEPTACLE: EF EXHAUST FAN RM ROOM
2 BALLAST ARM FIRE ALARM SYSTEM ADDRESSABLE RELAY - MONITOR C 18" CTR
NEMA 14-20R (20A, 3P, 4W, 208/120V) EH ELECTRIC HEATER RVAT REDUCED VOLTAGE AUTO TRANSFORMER
C G G GROUND WIRE CONNECTION C
LIGHTING FIXTURE: ELEC ELECTRIC RX REMOVE EXISTING
SPECIAL RECEPTACLE:
INDUSTRIAL RAL FIRE ALARM SYSTEM REMOTE ALARM LIGHT D 18" CTR ELEV ELEVATOR
NEMA 15-30R (30A, 3P, 4W, 208V)
G G G GROUND WIRE ETR EXISTING TO REMAIN SC SURGE CAPACITOR
LIGHTING FIXTURE: SPECIAL RECEPTACLE: EWC ELECTRIC WATER COOLER SEC SECONDARY
WALL MOUNTED - TYPE AS SPECIFIED FS FLOW SWITCH CONNECTION A
FLOOR MOUNTED, NEMA 6-20R EX EXISTING SN, S/N SOLID NEUTRAL
LIGHTNING PROTECTION DOWN LEAD
LIGHTING FIXTURE: SPECIAL RECEPTACLE: EXP EXPOSED SP SURGE PROTECTION
RECESSED, SURFACE, OR PENDANT MOUNTED TS TAMPER SWITCH CONNECTION A SPD SURGE PROTECTION DEVICE
PEDESTAL TYPE, NEMA 6-20R
UTILITY POLE FA FIRE ALARM SPDT SINGLE POLE DOUBLE THROW
LIGHTING FIXTURE: FIRE ALARM LINEAR BEAM SMOKE DETECTOR:
LBT LBR TELEVISION RECEPTACLE 72" CTR FAAP FIRE ALARM ANNUNCIATOR PANEL SS SAFETY SWITCH
WALL MOUNTED - TYPE AS SPECIFIED TRANSMITTER (LBT) AND RECEIVER (LBR)
FACP FIRE ALARM CONTROL PANEL SST SOLID STATE
F FBO FURNISHED BY OTHERS ST SINGLE THROW
WALL WASHER FIRE FIGHTER'S TELEPHONE JACK 48" TOD H TELEVISION RECEPTACLE 18" BFC
FC FAN COIL SW SWITCH
FDR FEEDER SWBD SWITCHBOARD
ADJUSTABLE WALL WASHER M MONITOR SYSTEM JUNCTION BOX 36" CTR C CLOCK HANGER OUTLET 84" CTR FLA FULL LOAD AMPERES
FLR FLOOR TBR TO BE REMOVED
1 2 PROGRAM CLOCK OUTLET:
LIGHTING FIXTURE ON EMERGENCY OR NIGHT LIGHT CIRCUIT (NL) A 84" CTR FR FRAME TC TIME CLOCK
AMPLIFIER SINGLE FACE, DOUBLE FACE FU FUSED, FUSIBLE TEL, TELE TELEPHONE
EMERGENCY BATTERY PACK: FUSS FUSED SAFETY SWITCH TH TUNGSTEN HALOGEN
W/ NUMBER OF HEADS INDICATED K KEYPAD 48" TOD EPO EMERGENCY POWER OFF SWITCH 48" TOD FVNR FULL VOLTAGE NON-REVERSING TOC TOP OF CABINET
FVR FULL VOLTAGE REVERSING TOD TOP OF DEVICE
EMERGENCY BATTERY PACK:
B CARD READER 48" TOD J JUNCTION BOX TRANS, XFMR TRANSFORMER
W/ REMOTE HEADS CR
GEN GENERATOR, GENERAL TTB TELEPHONE TERMINAL BOARD
REMOTE EMERGENCY HEAD J JUNCTION BOX - WALL MOUNTED 48" TOD GFCI GROUND FAULT CIRCUIT INTERRUPTER TW TWISTED
DA DOOR ALARM CONTACT
GFI GROUND FAULT INTERRUPTER TYP TYPICAL
EMERGENCY BATTERY PACK: GFP GROUND FAULT PROTECTED
SEMI RECESSED, CEILING MOUNT ROUGH-IN JUNCTION BOX FOR CCTV CAMERA E EQUIPMENT CONNECTION AS NOTED GFR GROUND FAULT RELAY UCB UNIT CIRCUIT BREAKER
D GRD GROUND UG UNDERGROUND D
EXIT SIGN: GRS GALVANIZED RIGID STEEL UH UNIT HEATER
P PUSH BUTTON PLATE E EQUIPMENT CONNECTION AS NOTED - WALL MOUNTED 48" TOD
CEILING OR PENDANT MOUNTED (SHADED PORTION INDICATES FACE)
UON UNLESS OTHERWISE NOTED
EXIT SIGN: H HID HIGH INTENSITY DISCHARGE UV UNIT VENTILATOR
3 HEATER CONNECTION - NUMBER INDICATES KILOWATTS (3KW)
WALL MOUNTED - END, BACK TELEVISION ANTENNA OUTLET 18" CTR HOA HAND-OFF-AUTOMATIC PROJECT NUMBER: H51-50068
HP HEAT PUMP, HORSEPOWER V VOLTS
EXIT SIGN: H HEATER FAN - CEILING MOUNTED
W/ DIRECTIONAL ARROWS C CABLE TV OUTLET HPS HIGH PRESSURE SODIUM VFC VARIABLE FREQUENCY CONTROLLER DHEC PROJECT NUMBER: 580145
HTR HEATER VFD VARIABLE FREQUENCY DRIVE
POLE MOUNTED LIGHTING FIXTURE: 2 4 CB ENCLOSED CIRCUIT BREAKER HV HIGH VOLTAGE
SINGLE HEAD, DOUBLE HEAD W W TELEVISION SYSTEM SPLITTER - 2 WAY, 4 WAY

NON-FUSED DISCONNECT SWITCH:


HZ HERTZ W
W/
WATTS, WIRE
WITH
CONSTRUCTION
POLE MOUNTED LIGHTING FIXTURE:
SINGLE, POLE TOP DATA/TELEPHONE OUTLET, CEILING MOUNTED 30A, 3P (UON) IG ISOLATED GROUND WP WEATHER-PROOF
DOCUMENTS 5/8/2018 3:43:11 PM
FUSED DISCONNECT SWITCH:
LIGHTING POLE (SPORTS) TELEPHONE OUTLET 18" CTR 40 JB JUNCTION BOX XFMR, TRANS TRANSFORMER
FUSE SIZE AS INDICATED (40A)
XP EXPLOSION PROOF
DATA OUTLET ROUGH-IN, PROVIDE SINGLE GANG BOX WITH 1" CND
TO ACCESSIBLE CEILING
18" CTR MS MAGNETIC MOTOR STARTER
KCMIL
KV
THOUSAND CIRCULAR MILS
KILOVOLTS STORM EYE INSTITUTE
KVA KILOVOLT AMPERES
W
TELEPHONE OUTLET, WALL MOUNTED 54" CTR FVNR
COMBINATION MAGNETIC MOTOR STARTER:
ABBREVIATION INDICATES TYPE - FVNR, FVR, RVAT, 2S1W, 2S2W, SST KVAR KILOVOLT AMPERES REACTIVE OPTICAL SHOP
E
TELEPHONE OUTLET, EMERGENCY 54" TOD
VFC VARIABLE FREQUENCY CONTROLLER W/ FUSED DISCONNECT SWITCH H51-50068
VFD VARIABLE FREQUENCY DRIVE W/ DISCONNECT SWITCH
167 ASHLEY AVE
DATA/TELEPHONE OUTLET:
UNSHADED AREA = DATA, SHADED AREA = VOICE 18" CTR
ELECTRICAL DRAWING PRESENTATION CHARLESTON, SC 29425
NUMERALS INDICATE QUANTITY OF WIRED JACKS M MOTOR:
E HP NUMERALS (IF SHOWN) INDICATE HP E
TELEPHONE OUTLET, FLOOR MOUNTED GENERATOR: SYMBOL DESCRIPTION
G
kW NUMERALS (IF SHOWN) INDICATE KW
# REVISION NUMBER ROSENBLUM COE
DATA OUTLET, FLOOR MOUNTED
M MANUAL MOTOR STARTER W/ THERMAL OVERLOADS
1 DRAWING NOTE NUMBER
ARCHITECTS,
DATA/TELEPHONE OUTLET, FLOOR MOUNTED: CP CONTROL PANEL:
CIRCUIT DESIGNATIONS
INC.
UNSHADED AREA = DATA, SHADED AREA = VOICE TYPE AS INDICATED EQUIPMENT TAG NUMBER -
EQ-1
NUMERALS INDICATE QUANTITY OF WIRED JACKS LIGHTING A # a POWER # REFER TO EQUIPMENT SCHEDULE 1643 MEANS STREET
PB MOMENTARY CONTACT START-STOP PUSHBUTTON STATION 48" TOD CHARLESTON, SC 29412
WAP WIRELESS ACCESS POINT FIXTURE TYPE CIRCUIT DESIGNATION
CIRCUIT DESIGNATION (#12AWG MINIMUM)
PBM MAINTAINED CONTACT START-STOP PUSHBUTTON STATION 48" TOD
(#12AWG MINIMUM)
XX 843.577.6073
SECTION/ELEVATION IDENTIFICATION
XX XX
ES MAINTAINED CONTACT EMERGENCY STOP PUSHBUTTON STATION 48" TOD SWITCH DESIGNATION

BRANCH PANELBOARD 90" TOC


PART PLAN AND DETAIL IDENTIFICATION
XX
XX XX
DISTRIBUTION PANELBOARD SECTION / PLAN / DETAIL NUMBER ELECTRICAL NOTES, SYMBOLS, AND
SHEET NUMBER WHERE SECTION / PLAN /
DETAIL IS DRAWN ABBREVIATIONS
T TRANSFORMER, CONCRETE PAD MOUNTED
SHEET NUMBER WHERE SECTION / PLAN / DETAIL
IS TAKEN FROM SHEET NAME

PROJECT NUMBER
F EXISTING LINE TYPE 17016 F
NEW ELECTRICAL WORK LINE TYPE
FUTURE ELECTRICAL WORK LINE TYPE DRAWN BY
DEMOLITION LINE TYPE ON DEMOLITION DRAWINGS WSD
CHECKED BY

DATE
BAC

05/09/2018
E001
SCALE
As indicated

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

F S O UT H CA
EO R

OL
T
ST A

INA
RMF
ENGINEERING INC.
CHARLESTON, SC
C-00831

RS
RE
GI E
ST
A E R E D E N G IN E A

SEALS

C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.


THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING THE COPYRIGHT.

NOTES:
1 EXISTING TRACK LIGHTING TO BE RELOCATED. SEE SHEET E201
FOR NEW LOCATION. RELOCATED EXISTING CONTROLS.

B B
F

A1 A1 A1

P
A1

A1 A1 A1 A1
GENERAL NOTES
1. CIRCUITS SERVING LIGHTING FIXTURES SHALL BE REUSED FOR
A1 NEW FIXTURES.
A3

PHASE 2 2. SEE ARCHITECTURAL PLANS FOR PHASING.

C C
A1
A3

A1 - 27 A1 - 27 A1 - 27
A1
A3
1

J J
A3

A1 - 27 A1 - 27
A1
A3
A1 - 27

J
A3 A3 A3

D D
PANEL 1L2 EXISTING
TO REMAIN.
F

A1 A1 A1 A1
X1 X1
PROJECT NUMBER: H51-50068
P P
RELOCATE EXISTING DHEC PROJECT NUMBER: 580145
NURSE CALL, ETR NURSE CALL DEVICES
E

W1 W1 W1 W1 W1 W1
F F
CONSTRUCTION
DOCUMENTS
E

A2 A2 13 A2 A2
5/8/2018 3:43:12 PM

OS OS OS OS
8 STORM EYE INSTITUTE
PHASE 1
15 13 9
10 OPTICAL SHOP
8
A2
13
A2
8
A2 A2 H51-50068
14,16
A 167 ASHLEY AVE
E CHARLESTON, SC 29425
E E
9
8 13 9 5
A2 A2 A2 A2
11
ROSENBLUM COE
ALL CIRCUITS SHOWN ARE
X1
15 13
BASED ON EXISTING PANEL ARCHITECTS,
SCHEDULE. CONTRACTOR
14, 16 TO ALERT ENGINEER INC.
6 OF ANY DISCREPANCIES.
1643 MEANS STREET
CHARLESTON, SC 29412

843.577.6073

ELECTRICAL DEMOLITION PLAN

1 ELECTRICAL DEMOLITION PLAN


ED101 SCALE: 1/4" = 1'-0" N SHEET NAME

PROJECT NUMBER
F 17016 F
DRAWN BY
WSD
CHECKED BY

DATE
BAC

05/09/2018
ED101
SCALE
1/4" = 1'-0"

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

F S O UT H CA
EO R

OL
T
ST A

INA
RMF
ENGINEERING INC.
CHARLESTON, SC
C-00831

RS
RE
GI E
ST
A E R E D E N G IN E A

SEALS

C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.


THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING THE COPYRIGHT.

NOTES:
1 RECEPTACLES USED TO POWER CASEWORK. CONFIRM EXACT
LOCATIONS WITH ARCHITECT. RECEPTACLES TO BE SWITCHED
BY NON-DIMMABLE SWITCH SHOWN.

2 CONNECT TO EXISTING FIRE ALARM ANNUNCIATION CIRCUIT IN


THIS AREA.

3 MOUNT DEVICES +42" ABOVE FINISHED FLOOR.

B B
F

PEDIATRIC WAITING
4
F

GENERAL NOTES
1. ALL CIRCUITS FED FROM PANEL 1L2 UNLESS OTHERWISE NOTED.

C C

18 1

18 18 3 18

1 18
104413.B
104416.C 1
F
FEC

RECEPTION 2 18
P
7
OPTICAL
2

D D
F

PROJECT NUMBER: H51-50068


P P

DHEC PROJECT NUMBER: 580145


E

F F
CONSTRUCTION
OFFICE #1
13
13 J
DOCUMENTS 5/8/2018 3:43:11 PM
5 9
13

13 STORM EYE INSTITUTE


OPTICAL SHOP
13 13
WELCOME AREA
H51-50068
1
9
167 ASHLEY AVE
E 15 15 CHARLESTON, SC 29425
E E
15
OFFICE #2
6
15 ROSENBLUM COE
ARCHITECTS,
2
15 9 9 9 INC.
F
1643 MEANS STREET
CHARLESTON, SC 29412

843.577.6073

ELECTRICAL POWER AND SPECIAL


ELECTRICAL POWER AND SPECIAL SYSTEMS NEW WORK SYSTEMS PLAN
1 PLAN
E101 SCALE: 1/4" = 1'-0" N SHEET NAME

PROJECT NUMBER
F 17016 F
DRAWN BY
WSD
CHECKED BY

DATE
BAC

05/09/2018
E101
SCALE
1/4" = 1'-0"

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

F S O UT H CA
EO R

OL
T
ST A

INA
RMF
ENGINEERING INC.
CHARLESTON, SC
C-00831

RS
RE
GI E
ST
A E R E D E N G IN E A

SEALS

C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.


THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING THE COPYRIGHT.

NOTES:
1 EXISTING TRACK LIGHTING TO BE RELOCATED HERE. EXTEND
EXISTING CIRCUIT TO THIS LOCATION. CONFIRM EXACT
LOCATION WITH ARCHITECT. RECONNECT TO EXISTING
CONTROLS.

2 PROVIDE DIMMER COMPATIBLE WITH LAMP TYPE SPECIFIED IN


FIXTURE SCHEDULE ON SHEET E601.

3 FIXTURES IN THIS AREA ARE TO BE CONNECTED TO EXISTING


277V CIRCUIT IN THIS AREA.

B B

A1 A1 A1

A1

A1 A1 A1 A1
GENERAL NOTES
1. SEE ARCHITECTURAL DRAWINGS FOR REFLECTED CEILING PLAN.
A1
A3

PHASE 2 2
C C
A1 Dc Db Da
A3

T1 27 a D1 27 b D1 27 b
D3 27 c D3 27 c
D2 27 b
A1
A3 T1 27 a
T1 27 a

D1 27 b D1 27 b D1 27 b D1 27 b

T1 27 a
FEC

A3
T1 27 a
D3 27 b D3 27 b D3 27 b D3 27 b T1 27 a

A1
A3 D1 27 b
D2 27 T1 27 a

A3 A3 A3
D2 27 b D2 27 b D2 27 b D2 27 b

D D

A1 A1 A1 A1
X1 X1
PROJECT NUMBER: H51-50068

PHASE 1 DHEC PROJECT NUMBER: 580145

W1 W1 W1
1
E1 9
CONSTRUCTION
Da Db

D4 a D4 a D4 a D4 a

R2 R2
DOCUMENTS 5/8/2018 3:43:12 PM

OS

3 D4 a
R1 b R1 b R1 b
D4 a
STORM EYE INSTITUTE
3
OPTICAL SHOP
OS H51-50068
167 ASHLEY AVE
R1 b R1 b R1 b CHARLESTON, SC 29425
R2 R2 D4 a D4 a
E RELOCATED NURSE CALL E
DEVICES, EXTEND EXISTING
WIRE TO NEW LOCATION OS

3
ROSENBLUM COE
W1
X1
ARCHITECTS,
D4 a D4 a D4 a D4 a D4 a
INC.
1643 MEANS STREET
CHARLESTON, SC 29412

843.577.6073

ELECTRICAL LIGHTING PLAN

1 ELECTRICAL LIGHTING NEW WORK PLAN


E201 SCALE: 1/4" = 1'-0" N SHEET NAME

PROJECT NUMBER
F 17016 F
DRAWN BY
WSD
CHECKED BY

DATE
BAC

05/09/2018
E201
SCALE
1/4" = 1'-0"

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

F S O UT H CA
EO R

OL
T
ST A

INA
RMF
ENGINEERING INC.
CHARLESTON, SC
C-00831

RS
RE
GI E
ST
A E R E D E N G IN E A

SEALS

C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.


THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING THE COPYRIGHT.

NOTES:
1 PURCHASE 20A, 1P BREAKER TO MATCH EXISTING GE TYPE NLAB
TYPE FOR CIRCUIT IN EXISTING SPACE.

LIGHTING FIXTURE SCHEDULE 2 REPLACE EXISTING 2P 20A BREAKER WITH (2) 1P 20A BREAKERS
TO MATCH EXISTING GE TYPE.
LAMPS BALLAST MOUNTING 3 LED PAR-20 NARROW BEAM TYPE LAMP OWNER FURNISHED,
DESCRIPTION LOUVER/LENS TYPE WATTS QTY. COLOR TEMP. TYPE QTY. VOLTS WATTS MOUNTING SURFACE REMARKS BASIS OF DESIGN ALTERNATE #1 ALTERNATE #2 CONTRACTOR INSTALLED.
A1 EXISTING 2'x2' FLOURESCENT TROFFER T8 1 0K 1 277 0 CEILING RECESSED EXISTING FIXTURES, SEE 4 REMOVE 2P 60A CIRCUIT BREAKER AND PROVIDE (2) 1P 20A
E100 FOR DEMO PLANS BREAKERS.
A2 EXISTING 2'x4' FLOURESCENT TROFFER T8 1 0K 1 0 0 CEILING RECESSED EXISTING FIXTURES, SEE 5 CONTRACTOR TO VERIFY EXISTING LIGHTING CIRCUIT VOLTAGE.
E100 FOR DEMO PLANS
A3 EXISTING 6" DOWNLIGHTS 1 0K 1 0 0 CEILING RECESSED EXISTING FIXTURES, SEE
E100 FOR DEMO PLANS
B D1 6" DIRECTIONAL LED DOWNLIGHT, NARROW LED PAR-38 12 1 4000 K 1 120 12 CEILING RECESSED LAMP TO BE PROVIDED BY PATHWAY #TF711-ACF7150 LUM LIGHTING #CL-112-P38-NC-T JUNO #P8RA P381 ACC CS HBTL B
SPOT LUM LIGHTING GROUP
D2 6" DIRECTIONAL LED REMODEL DOWNLIGHT, LED PAR-38 12 1 4000 K 1 120 12 CEILING RECESSED LAMP TO BE PROVIDED BY PATHWAY #RM-TF711-ACF7150 LUM LIGHTING #CL-112-P38-RM-T JUNO #P8RA P381 ACC CS HBTL
NARROW SPOT 3 LUM LIGHTING GROUP
D3 6" DOWNLIGHT LED PAR-38 12 1 4000 K 1 120 12 CEILING RECESSED LAMP TO BE PROVIDED BY HE WILLIAMS LUM LIGHTING #CL-110-P38-NC-T INDY #P6P30-120-F-OR-CS-PF
3
LUM LIGHTING GROUP #R60-100-PAR38/MED-CS-120
D4 6" LED DOWNLIGHT, 80+ CRI, 900 LUMENS ACRYLIC LED 15 1 3500 K 1 120 15 CEILING RECESSED HE WILLIAMS #L60-L11C/835-CS/M-DRV-XX PRESCOLITE #LC6SLDM-6LCSL10L35K8 ALPHABET #NU6 RD 13LM 35K 83 HE60
3
XX DIM10 NC WH WH
E1 EMERGENCY BUG EYE TYPE FIXTURE ACRYLIC LED 5 1 1 120 5 WALL SURFACE XTRALIGHT #EMX-0036-SDT
R1 2'x2' LED LENSED TROFFER ACRYLIC LED 21 1 3500 K 1 277 5 21 CEILING RECESSED HE WILLIAMS COLUMBIA #LLT22-35LWG-FSA12F-EDU LITHONIA #2TL2-20L-FW-A12-EZ1-LP835
#LPT-22-L27/835-S-AF12125-DIM-UNV
R2 2'x4' LED LENSED TROFFER ACRYLIC LED 31 1 3500 K 1 277 31 CEILING RECESSED HE WILLIAMS COLUMBIA #LLT24-35LWG-FSA12F-EDU LITHONIA #2TL4-48L-FW-A12-EZ1-LP835
#LPT-24-L43/835-S-AF12125-DIM-UNV
T1 TRACK FIXTURES, LINE VOLTAGE LED PAR-20 20 1 4000 K 120 20 TRACK LAMP TO BE PROVIDED BY
3
LUM LIGHTING GROUP GENERAL NOTES
W1 EXISTING NURSE CALL LIGHTS 1 0K 120 0 WALL SURFACE EXISTING FIXTURE 1. -
X1 LED EXIT SIGN 1 277 0 CEILING RECESSED EXISTING FIXTURE

C C

PANELBOARD: 1L2
LOCATION: MAINS: MCB AMPS: 100
MOUNTING: Recessed VOLTS: 208/120 Wye
ENCL NEMA: Type 1 PHASE: 3
MIN AIC: SEE ONE-LINE DIAGRAM WIRES: 4

PANEL NOTES:
PROVIDE GROUND BUS
PROVIDE FULL SIZE NEUTRAL BUS UNLESS NOTED OTHERWISE
CIRCUIT NAMES STARTING WITH ETR ARE EXISTING, TO REMAIN
D D

TRIP TRIP
WIRE SIZE LOAD DESCRIPTION P AMPS TYPE CKT A B C CKT TYPE AMPS P LOAD DESCRIPTION WIRE SIZE
-- ETR - LTG RM 103 1 20 A -- 1 0.00 0.00 2 -- 20 A 1 ETR - OVRHD REC HWY 125 --
PROJECT NUMBER: H51-50068
-- ETR - REC WIRMLD RM 121 1 20 A -- 3 0.00 0.00 4 -- 20 A 1 ETR - REC RECEPTION DSK --
DHEC PROJECT NUMBER: 580145
-- ETR - REC ELVTR LBY + PIT 1 20 A -- 5 0.00 0.00 6 -- 20 A 1 EXISTING CIRCUIT --
-- ETR - WATER COOLER 1 20 A -- 7 0.00 0.00 8 -- 20 A 1 EXISTING CIRCUIT --
2#12, 1#12 GRD REC NEW WAITING RM
-- ETR - REC RM 129, 130
1
1
20 A
20 A --
9
11
0.90 0.00
0.00 0.00
10
12
--
--
20 A
20 A
1
1
ETR - REC UNDR COUNTER
EXISTING CIRCUIT
--
--
CONSTRUCTION
2#12, 1#12 GRD REC NEW OFFICE #1 1 20 A 13 0.90 0.00 14 -- 20 A 1 SPARE --
4
DOCUMENTS
2#12, 1#12 GRD REC NEW OFFICE #2 1 20 A 15 0.90 0.00 16 -- 20 A 1 SPARE -- 5/8/2018 3:43:12 PM

-- ETR - REC RM 124 1 20 A -- 17 0.00 1.32 18 20 A 1 REC OPTICAL DISPLAY 2#12, 1#12 GRD 1
-- ETR - REC RM 123 1 20 A -- 19 0.00 0.00 20 -- 20 A 1 ETR - OUTDR LTG, HRSHOE --
-- ETR - REC RM 122 1 20 A -- 21 0.00 0.00 22 -- 20 A 1 SPARE --
2
STORM EYE INSTITUTE
-- ETR - REC RM 120 1 20 A -- 23 0.00 0.00 24 -- 20 A 1 SPARE --
-- ETR - REC RM 121 1 20 A -- 25 0.00 0.00 26 -- 20 A 1 ETR - REC CLEANING CORR -- OPTICAL SHOP
2#12, 1#12 GRD LTG OPTICAL DISPLAY
-- ETR - REC NRS STN RM 122
1
1
20 A
20 A --
27
29
1.26 0.00
0.00 0.00
28
30
--
--
20 A
20 A
1
1
ETR - REC CLEANING CORR
ETR - UPS DISC 1 RM 114
--
--
H51-50068
-- ETR - REC 119, CPY 121 1 20 A -- 31 0.00 0.00 32 -- 20 A 1 ETR - UPS DISC 1 RM 114 --
-- SPACE -- -- -- 33 0.00 0.00 34 -- 20 A 1 ETR - UPS DISC 2 RM 114 --
167 ASHLEY AVE
-- SPACE -- -- -- 35 0.00 0.00 36 -- 20 A 1 ETR - UPS DISC 2 RM 114 -- CHARLESTON, SC 29425
E TOTAL LOAD: 0.90 kVA 3.06 kVA 1.32 kVA E
BREAKER TYPE KEYS:
LO - INDICATES C.B. EQUIPPED WITH "LOCK-ON" DEVICE
GF - INDICATES C.B. IS GROUND FAULT TYPE (5mA FOR PERSONNEL)
ST - INDICATES C.B. EQUIPPED WITH SHUNT TRIP DEVICE ROSENBLUM COE
HT - INDICATES C.B. EQUIPPED WITH 30mA GROUND FAULT FOR EQUIPMENT
ARCHITECTS,
Load Classification
LTG
Connected Load
1.26
Demand Factor
100.00%
Estimated Demand
1.26
Panel Totals
INC.
REC 4.02 100.00% 4.02 Total Conn. Load: 5.28 kVA 1643 MEANS STREET
Equipment 0.00 0.00% 0.00 Total Est. Demand: 5.28 kVA CHARLESTON, SC 29412
Total Conn. Current: 14.65 A
Total Est. Demand Current: 14.65 A
843.577.6073

ELECTRICAL SCHEDULES

SHEET NAME

PROJECT NUMBER
F 17016 F
DRAWN BY
WSD
CHECKED BY

DATE
BAC

05/09/2018
E601
SCALE

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

F S O UT H C A
EO R
FIRE PROTECTION GENERAL NOTES

OL
T
STA

INA
RMF
ENGINEERING INC.
CHARLESTON, SC
1 THE SPRINKLER CONTRACTOR SHALL REVIEW ARCHITECTURAL DRAWINGS, INCLUDING ALL REFLECTED CEILING PLANS C-00831
PRIOR TO PREPARING THE BID.

RS
RE
G IS
2 ALL LOW POINTS OF THE SPRINKLER SYSTEM SHALL BE PROVIDED WITH DRAINS PER NFPA-13 CURRENTLY ADOPTED T ER E N EE
A REVISION. LOW POINT DRAINS SHALL BE CLEARLY MARKED AND PIPED TO THE EXTERIOR OF THE BUILDING. A VALVE D E NG I A
DRAWING SHALL BE PROVIDED IN MECHANICAL ROOM SHOWING THE LOCATIONS OF ALL LOW POINT DRAINS.
SEALS
3 ALL SPRINKLER HEAD TEMPERATURE RATINGS SHALL BE ORDINARY (165°F) UNLESS OTHERWISE INDICATED. ALL
SPRINKLERS INSTALLED IN GYPSUM, PLASTER AND WOOD CEILINGS SHALL BE CONCEALED TYPE. ALL SPRINKLERS IN C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.
ACOUSTICAL CEILING TILE SHALL BE SEMI-RECESSED TYPE. THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
4 ALL PIPE PENETRATIONS THROUGH MASONRY WALLS SHALL BE PROVIDED WITH THE MINIMUM CLEARANCE DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING THE COPYRIGHT.
REQUIREMENTS FOR SEISMIC PROTECTION AS DEFINED BY NFPA-13. ALL PIPING LESS THAN FOUR (4) INCHES SHALL
HAVE A PIPE SLEEVE A NOMINAL DIAMETER 2 IN. LARGER THAN THE NOMINAL DIAMETER OF THE PIPE. ALL PIPING FOUR
(4) INCHES AND LARGER SHALL HAVE A PIPE SLEEVE A NOMINAL DIAMETER 4 IN. LARGER THAN THE NOMINAL DIAMETER
OF THE PIPE. NOTES:

5 FIRE CAULK AND SLEEVE ALL PENETRATIONS THROUGH FIRE RATED ASSEMBLIES. REFER TO LIFE SAFETY PLANS FOR
RATED ASSEMBLY LOCATIONS.

6 PROVIDE TEMPORARY PIPING AS REQUIRED SO AREAS OUTSIDE THE AREAS OF WORK CAN CONTINUE TO BE SERVED
FROM THE FIRE PROTECTION SYSTEM.

7 EXISTING DRAWINGS WITH SIZES ARE PROVIDED FOR THE CONVENIENCE OF THE CONTRACTOR ONLY AND ARE NOT
WARRANTED TO BE CORRECT. CONTRACTOR SHALL VERIFY ALL SIZES IN THE FIELD.

8 SEE ARCHITECTURAL DRAWINGS FOR PHASING PLAN.

B B

C C

D D

PROJECT NUMBER: H51-50068

DHEC PROJECT NUMBER: 580145

CONSTRUCTION
DOCUMENTS 5/8/2018 3:45:03 PM

STORM EYE INSTITUTE


OPTICAL SHOP
H51-50068
167 ASHLEY AVE
CHARLESTON, SC 29425
E E

ROSENBLUM COE
ARCHITECTS,
INC.
1643 MEANS STREET
CHARLESTON, SC 29412

843.577.6073

FIRE PROTECTION NOTES, SYMBOLS


AND ABBREVIATIONS
SHEET NAME

PROJECT NUMBER
F 17016 F
DRAWN BY
TSN

CHECKED BY

DATE
CRB

05/09/2018
FP001
SCALE

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

F S O UT H C A
EO R

OL
T
STA

INA
RMF
ENGINEERING INC.
CHARLESTON, SC
C-00831

RS
RE
G IS
T ER E N EE
A D E NG I A

SEALS

C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.


THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING THE COPYRIGHT.

NOTES:
1 MODIFY THE EXISTING SPRINKLER SYSTEM TO PROVIDE A
COMPLETE HYDRAULICALLY DESIGNED AUTOMATIC WET
SPRINKLER SYSTEM FOR ALL RENOVATED/UPFIT AREAS OF
WORK. SYSTEM SHALL BE IN ACCORDANCE WITH NFPA 13 AND
THE STATE FIRE MARSHAL REQUIREMENTS. THE EXISTING MAIN
AND BRANCH SPRINKLER PIPING WITHIN THE AREA OF WORK
SHALL BE REMOVED SUCH THAT THE PROGRAM AREAS OUTSIDE
THE AREAS OF WORK HAVE CONTINUED FIRE
PROTECTION. TEMPORARY PIPING SHALL BE PROVIDED AS
REQUIRED. PRIOR TO INSTALLATION, NEW SPRINKLER PIPING
SHALL BE FULLY COORDINATED WITH HVAC AND ELECTRICAL
SERVICES.

B B

PEDIATRIC WAITING
4

GENERAL NOTES
1. REFER TO FP001 FOR GENERAL NOTES.

2. REFER TO DRAWING FP301 AND FP302 FOR EXISTING FIRST

PHASE 2 FLOOR AND CRAWL SPACE FIRE PROTECTION LAYOUT (FOR


REFERENCE ONLY).
C C

OPTICAL LAB
3

RECEPTION
7

1
OPTICAL
FEC

484 SF

D D

PROJECT NUMBER: H51-50068

PHASE 1 DHEC PROJECT NUMBER: 580145

CONSTRUCTION
DOCUMENTS 5/8/2018 3:45:03 PM

OFFICE #1
5
STORM EYE INSTITUTE
OPTICAL SHOP
1
H51-50068
WELCOME AREA
1
167 ASHLEY AVE
CHARLESTON, SC 29425
703 SF
E E

OFFICE #2
6 ROSENBLUM COE
ARCHITECTS,
INC.
1643 MEANS STREET
CHARLESTON, SC 29412

843.577.6073

FIRE PROTECTION FLOOR PLAN

1 FIRE PROTECTION PIPING NEW WORK PLAN


N
FP101 SCALE: 1/4" = 1'-0" SHEET NAME

PROJECT NUMBER
F 17016 F
DRAWN BY
TSN

CHECKED BY

DATE
CRB

05/09/2018
FP101
SCALE
1/4" = 1'-0"

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

F S O UT H C A
EO R

OL
T
STA

INA
RMF
ENGINEERING INC.
CHARLESTON, SC
C-00831

RS
RE
G IS
T ER E N EE
A D E NG I A

SEALS

C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.


THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING THE COPYRIGHT.

THROUGH PENETRATION FIRESTOP SCHEDULE NOTES:

A. THIS SCHEDULE IDENTIFIES REQUIREMENTS FOR ACCEPTABLE THROUGH PENETRATION FIRESTOPS FOR THIS PROJECT BASED ON BARRIER TYPE, BASIS OF BARRIER CONSTRUCTION, AND PENETRANT TYPE.
B. THROUGH PENETRATION FIRESTOPS ARE NOT REQUIRED FOR FLOOR PENETRATIONS CONTAINED TOTALLY WITHIN A RATED SHAFT ENCLOSURE.
C. FOR EACH PENETRATION, SELECT A THROUGH PENETRATION FIRESTOP BASED ON ACTUAL FIELD CONDITIONS, WHICH INCLUDE BUT ARE NOT LIMITED TO PENETRATION SIZE, PENETRATION SHAPE, PENETRANT MATERIAL(S), QUANTITY OF PENETRANTS PER PENETRATION, AND LOCATION(S) OF PENETRANT(S) WITHIN PENETRATION.
D. NOMENCLATURE OF UL CLASSIFIED FIRESTOP ASSEMBLIES USED IN THIS SCHEDULE IS IDENTICAL TO THAT USED IN CATALOGS OF APPROVED FIRESTOP MANUFACTURERS (SEE DIVISION 15) AND IN UNDERWRITERS LABORATORIES "FIRE RESISTANCE DIRECTORY."

RATED BARRIER PENETRANT TYPE


B METALLIC, NONMETALLIC, INSULATED PIPES INSULATED PIPES B
UNINSULATED PIPE UNINSULATED PIPE (EX. COPPER, IRON (EX. COPPER, IRON
TYPE BASIS OF NO
OR TUBING OR TUBING PLASTIC, STEEL) IN PLASTIC, STEEL) IN METAL DUCT
CONSTRUCTION FIRESTOP ASSEMBLY REQUIREMENTS PENETRANTS
(EX. COPPER, IRON, (EX. PVC, PP, SYSTEMS OPERATING SYSTEMS OPERATING (NOTE 1)
STEEL) FRPP) BETWEEN 32°F AND 122°F BELOW 32°F OR ABOVE 122°F

SINGLE PENETRANT W-L-1000 SERIES W-L-2000 SERIES W-L-5000 SERIES W-L-5000 SERIES W-L-7000 SERIES
UL CLASSIFIED W-L-0000 SERIES
SERIES OR NOTE 2
METAL STUDS & W-L-8000 SERIES W-L-8000 SERIES W-L-8000 SERIES
MULTIPLE PENETRANTS N/A
GYPSUM WALLBOARD (NOTE 3) (NOTE 3) (NOTE 3)
WALL
EQUAL TO WALL EQUAL TO WALL EQUAL TO WALL EQUAL TO WALL EQUAL TO WALL EQUAL TO WALL
(U400 SERIES) F RATING
RATING RATING RATING RATING RATING RATING
T RATING NOTE 5 NOTE 5 NOTE 5 NOTE 5 NOTE 5 NOTE 5
EXCEPTIONS/ ADDED REQUIREMENTS NONE NOTE 8 NOTE 8 NONE NOTE 4 NONE

C C-AJ-1000 OR C-AJ-2000 OR C-AJ-5000 OR C-AJ-5000 OR C-AJ-7000 OR C


SINGLE PENETRANT
UL CLASSIFIED W-J-0000 SERIES W-J-1000 SERIES W-J-2000 SERIES W-J-5000 SERIES W-J-5000 SERIES W-J-7000 SERIES
POURED CONCRETE,
SERIES OR NOTE 2
CONCRETE BLOCK OR C-AJ-8000 OR W-J-8000 SERIES C-AJ-8000 OR C-AJ-8000 OR
MULTIPLE PENETRANTS N/A
MASONRY (NOTE 3) W-J-8000 (NOTE 3) W-J-8000 (NOTE 3)
WALL
EQUAL TO WALL EQUAL TO WALL EQUAL TO WALL EQUAL TO WALL EQUAL TO WALL EQUAL TO WALL
(BLOCK & U900 SERIES) F RATING
RATING RATING RATING RATING RATING RATING
(ANY THICKNESS)
T RATING NOTE 5 NOTE 5 NOTE 5 NOTE 5 NOTE 5 NOTE 5
EXCEPTIONS/ ADDED REQUIREMENTS NONE NOTES 7 & 8 NOTE 8 NONE NOTE 4 NONE
C-AJ-1000 OR C-AJ-2000 OR C-AJ-5000 OR C-AJ-5000 OR C-AJ-7000 OR
SINGLE PENETRANT C-AJ-0000 SERIES
UL CLASSIFIED F-A-1000 SERIES F-A-2000 SERIES F-A-5000 SERIES F-A-5000 SERIES F-A-7000 SERIES
F-A-0000 SERIES
SERIES
OR NOTE 2 C-AJ-8000 OR F-A-8000 SERIES C-AJ-8000 OR C-AJ-8000 OR
POURED CONCRETE MULTIPLE PENETRANTS N/A
(NOTE 3) F-A-8000 (NOTE 3) F-A-8000 (NOTE 3)
FLOOR
(ANY THICKNESS) EQUAL TO FLOOR RATING, EQUAL TO FLOOR RATING, EQUAL TO FLOOR RATING, EQUAL TO FLOOR RATING, EQUAL TO FLOOR RATING, EQUAL TO FLOOR RATING,
F RATING
BUT NOT LESS THAN 1 HR BUT NOT LESS THAN 1 HR BUT NOT LESS THAN 1 HR BUT NOT LESS THAN 1 HR BUT NOT LESS THAN 1 HR BUT NOT LESS THAN 1 HR
T RATING NOTE 6 NOTE 6 NOTE 6 NOTE 6 NOTE 6 NOTE 6
EXCEPTIONS/ ADDED REQUIREMENTS NONE NOTE 7 NONE NONE NOTE 4 NONE

D D
NOTES:
1. THIS SCHEDULE'S DATA APPLY ONLY TO PENETRATIONS WITHOUT DAMPERS. FOR DAMPERED PENETRATIONS, REFER TO SPECIFICATIONS. 5. TEMPERATURE (T) RATINGS OF ASSEMBLIES IN WALLS MAY EQUAL ZERO.
AT DAMPERS, DO NOT APPLY MATERIAL THAT IS NOT INCLUDED IN THE DAMPER'S CLASSIFICATION. 6. TEMPERATURE (T) RATINGS OF ASSEMBLIES IN FLOORS SHALL EQUAL THE GREATER OF EITHER THE BARRIER RATING OR ONE HOUR EXCEPT AS FOLLOWS: PROJECT NUMBER: H51-50068
2. SEAL OPENING USING BARRIER'S ORIGINAL CONSTRUCTION. A. AN ASSEMBLY'S T RATING MAY EQUAL ZERO WHEN THE PENETRANT ABOVE THE FLOOR PENETRATION IS CONTAINED AND LOCATED DHEC PROJECT NUMBER: 580145
3. WHERE A SERIES 8000 CLASSIFIED SYSTEM IS NOT AVAILABLE, INSTALL PENETRANTS SINGLY, AND PROVIDE SINGLE-PENETRANT SYSTEMS. WITHIN THE CAVITY OF A WALL.
4. FOR SYSTEMS THAT OPERATE BELOW 32°F OR ABOVE 122°F, COMPLY WITH THE FOLLOWING ADDITIONAL REQUIREMENTS: 7. CLASSIFIED TPFS ASSEMBLY IS NOT REQUIRED WHEN ALL THE FOLLOWING CONDITIONS ARE MET: CONSTRUCTION
A. PROVIDE TPFS SYSTEM USING INTUMESCENT ELASTOMERIC WRAP STRIP AS ITS FILL, VOID, OR CAVITY MATERIAL. A. PENETRANT HAS A MAXIMUM NOMINAL DIAMETER OF 6-INCHES.
DOCUMENTS
B. DO NOT USE SERIES 8000 PENETRATIONS. PROVIDE ONLY SINGLE PENETRATIONS. B. PENETRATION HAS A MAXIMUM AREA OF 144 SQUARE INCHES. 5/8/2018 3:45:04 PM

C. ANNULAR SPACE IS COMPLETELY FILLED WITH CONCRETE, GROUT, OR MORTAR THE FULL THICKNESS OF THE BARRIER.
STORM EYE INSTITUTE
OPTICAL SHOP
H51-50068
167 ASHLEY AVE
CHARLESTON, SC 29425
E E

ROSENBLUM COE
ARCHITECTS,
INC.
1643 MEANS STREET
CHARLESTON, SC 29412

843.577.6073

FIRE PROTECTION SCHEDULES

SHEET NAME

PROJECT NUMBER
F 17016 F
DRAWN BY
TSN

CHECKED BY

DATE
CRB

05/09/2018
FP201
SCALE
12" = 1'-0"

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

A A

SEALS

C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.


THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING THE COPYRIGHT.

NOTES:

B B

GENERAL NOTES
1. AS-BUILT FIRE PROTECTION SYSTEM DRAWINGS ARE PROVIDED FOR
CONTRACTOR'S REFERENCE ONLY TO ASSIST WITH DESIGN FLOW
RATE CALCULATIONS AS REQUIRED BY NFPA-13 (2013) 8.15.20.5.2.

C C

D D

PROJECT NUMBER: H51-50068

DHEC PROJECT NUMBER: 580145

CONSTRUCTION
DOCUMENTS 5/8/2018 3:45:06 PM

STORM EYE INSTITUTE


OPTICAL SHOP
H51-50068
167 ASHLEY AVE
CHARLESTON, SC 29425
E E

ROSENBLUM COE
ARCHITECTS,
INC.
1643 MEANS STREET
CHARLESTON, SC 29412

843.577.6073

FIRE PROTECTION FIRST FLOOR


AS-BUILTS
SHEET NAME

PROJECT NUMBER
F 17016 F
DRAWN BY
TSN

CHECKED BY

DATE
MER

05/09/2018
FP301
SCALE

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9

A A

SEALS

C COPYRIGHT 2017 ROSENBLUM COE ARCHITECTS, INC.


THIS DRAWING HAS BEEN PREPARED BY ROSENBLUM COE ARCHITECTS, INC. FOR THIS
PROJECT AND IS AN INSTRUMENT OF THE ARCHITECTS SERVICE FOR THE USE SOLELY WITH
RESPECT TO THIS PROJECT. THE ARCHITECT SHALL BE DEEMED THE AUTHOR OF THIS
DOCUMENT AND SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING THE COPYRIGHT.

NOTES:

B B

GENERAL NOTES
1. AS-BUILT FIRE PROTECTION SYSTEM DRAWINGS ARE PROVIDED FOR
CONTRACTOR'S REFERENCE ONLY TO ASSIST WITH DESIGN FLOW
RATE CALCULATIONS AS REQUIRED BY NFPA-13 (2013) 8.15.20.5.2.

C C

D D

PROJECT NUMBER: H51-50068

DHEC PROJECT NUMBER: 580145

CONSTRUCTION
DOCUMENTS 5/8/2018 3:45:07 PM

STORM EYE INSTITUTE


OPTICAL SHOP
H51-50068
167 ASHLEY AVE
CHARLESTON, SC 29425
E E

ROSENBLUM COE
ARCHITECTS,
INC.
1643 MEANS STREET
CHARLESTON, SC 29412

843.577.6073

FIRE PROTECTION CRAWL SPACE


AS-BUILTS
SHEET NAME

PROJECT NUMBER
F 17016 F
DRAWN BY
TSN

CHECKED BY

DATE
MER

05/09/2018
FP302
SCALE

1 2 3 4 5 6 7 8 9