Sei sulla pagina 1di 40

LIQUID COOLED VARIABLE SPEED DRIVE

FOR YCAV (LATITUDE) CHILLERS


SERVICE INSTRUCTIONS Supersedes: 201.21-M1 (305) Form 201.21-M1 (307)

TROUBLESHOOTING GUIDE FOR


LIQUID COOLED VARIABLE SPEED DRIVE

50056

60 / 50 Hz (P/N 371-04178-XXX)
FORM 201.21-M1 (307)

IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES

This equipment is a relatively complicated apparatus. which it is situated, as well as severe personal injury or
During installation, operation, maintenance or service, death to themselves and people at the site.
individuals may be exposed to certain components or
conditions including, but not limited to: refrigerants, This document is intended for use by owner-authorized
oils, materials under pressure, rotating components, and operating/service personnel. It is expected that this in-
both high and low voltage. Each of these items has the dividual possesses independent training that will enable
potential, if misused or handled improperly, to cause them to perform their assigned tasks properly and safely.
bodily injury or death. It is the obligation and respon- It is essential that, prior to performing any task on this
sibility of operating/service personnel to identify and equipment, this individual shall have read and under-
recognize these inherent hazards, protect themselves, stood this document and any referenced materials. This
and proceed safely in completing their tasks. Failure individual shall also be familiar with and comply with
to comply with any of these requirements could result all applicable governmental standards and regulations
in serious damage to the equipment and the property in pertaining to the task in question.

SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to areas of potential hazard:

DANGER indicates an imminently CAUTION identifies a hazard which


hazardous situation which, if not could lead to damage to the machine,
avoided, will result in death or serious damage to other equipment and/or
injury. environmental pollution. Usually an
instruction will be given, together with
a brief explanation.

WARNING indicates a potentially NOTE is used to highlight additional


hazardous situation which, if not information which may be helpful to
avoided, could result in death or se- you.
rious injury.

External wiring, unless specified as an optional connection in the manufacturer’s product


line, is NOT to be connected inside the micro panel cabinet. Devices such as relays, switches,
transducers and controls may NOT be installed inside the micro panel. NO external wir-
ing is allowed to be run through the micro panel. All wiring must be in accordance with
YORK’s published specifications and must be performed ONLY by qualified YORK personnel.
YORK will not be responsible for damages/problems resulting from improper connections
to the controls or application of improper control signals. Failure to follow this will void the
manufacturer’s warranty and cause serious damage to property or injury to persons.

2 JOHNSON CONTROLS
FORM 201.21-M1 (307)

TABLE OF CONTENTS
SCREW COMPRESSOR DRIVE GENERAL INFORMATION ............................................................. 5
Reference Instructions ................................................................................................................................. 5

LATITUDE COMPRESSOR DRIVE COMPONENT OVERVIEW ....................................................... 6


Latitude Compressor Drive .......................................................................................................................... 6

LATITUDE COMPRESSOR DRIVE CONTROL SYSTEM OVERVIEW ............................................ 9


The Chiller Control Center .......................................................................................................................... 9
Latitude Compressor Drive Logic Board ..................................................................................................... 9
Chiller Control Center VSD Related Keypad Functions ........................................................................... 13

TROUBLESHOOTING UNIT SHUTDOWNS ....................................................................................... 14


General Information ................................................................................................................................... 14
DC Bus Voltage Imbalance ........................................................................................................................ 14
High DC Bus Voltage ................................................................................................................................. 14
High VSD Internal Ambient Temperature ................................................................................................. 15
Low DC Bus Voltage ................................................................................................................................. 15
Motor Current Overload ............................................................................................................................ 16
Precharge - DC Bus Voltage Imbalance ..................................................................................................... 16
Precharge - Low DC Bus Voltage .............................................................................................................. 16
Single Phase Input Voltage ........................................................................................................................ 17
VSD Communications Failure ................................................................................................................... 17
VSD CT Plug Fault .................................................................................................................................... 18
VSD Logic Board Failure .......................................................................................................................... 18
VSD Logic Board Power Supply ............................................................................................................... 18

TROUBLESHOOTING SYSTEM SHUTDOWNS .................................................................................. 20


General Information ................................................................................................................................... 20
Gate Driver................................................................................................................................................. 20
High Motor Current ................................................................................................................................... 21
High VSD Baseplate Temperature ............................................................................................................. 21
Table 1 - LCD - Thermistor Characteristics IGBT .................................................................................... 22
Motor Current Overload ............................................................................................................................ 22
VSD Run Relay.......................................................................................................................................... 23

WARNING MESSAGES ............................................................................................................................. 24


General Information ................................................................................................................................... 24
Invalid Number of Compressor Selected ................................................................................................... 24

START-UP PREPARATIONS..................................................................................................................... 25
Circuit Breaker Setup................................................................................................................................. 25
Verify Overload Settings ............................................................................................................................ 25

LCD FREQUENTLY ASKED QUESTIONS ............................................................................................ 26


TROUBLESHOOTING AND COMPONENT REPLACEMENT PROCEDURES ............................. 27
General Information ................................................................................................................................... 27
Verify Failure of the LCD IGBT Module .................................................................................................. 27
Verify Failure of the LCD SCR/Diode Module ......................................................................................... 32
Replacement of the LCD IGBT Module .................................................................................................... 33

JOHNSON CONTROLS 3
FORM 201.21-M1 (307)

TABLE OF CONTENTS - (CONT'D)

Replacement of the LCD SCR/Diode Module........................................................................................... 35


Replacement of the LCD Logic Board ...................................................................................................... 36
SOFTWARE REFERENCE LIST 50 HZ AND 60 HZ ............................................................................ 37

4 JOHNSON CONTROLS
FORM 201.21-M1 (307)

SCREW COMPRESSOR DRIVE GENERAL INFORMATION


This instruction is to be used in conjunction with the Operation and Service Instructions for YORK Model
YCAV (Latitude) chillers.

Reference Instructions
Installation, Operation and Service (Unit) Form 201.21-NM1 (2 Compr 60Hz)
Form 201.21-NM2 (2 Compr 50Hz)
Form 201.21-NM3 (3/4 Compr 60 Hz)
Form 210.21-NM4 (3/4 Compr 50 Hz)
Wiring Diagram Form 201.21-W1 (2 Compr 60 Hz)
Form 201.21-W2 (2 Compr 50 Hz)
Form 201.21-W3 (3 Compr 60 Hz)
Replacement Parts List Form 201.21-RP1 (2 Compr 60 Hz)
Form 201.21-RP2 (2 Compr 50 Hz)
Form 201.21-RP3 (3/4 Compr 60 Hz)

YCAV CHILLER COMPRESSOR DRIVE MODEL NUMBER DEFINITIONS

HES 2CMPR B I - 17
Voltage Range - 17 200 VAC
- 28 230 VAC
- 40 380 VAC
- 50 400 VAC
- 58 575 VAC
Remote Interface - I (installed), _ (not installed)
Circuit Breaker Option - B (installed), _ (lugs)
Number of Compressors Outputs - 2, 3, 4
Type of Drive

MODEL NUMBER PART NUMBER


60 HZ 50 HZ
HES2COMPR__-17 371-04178-101 —
HES2COMPR__-28 371-04178-102 —
HES2COMPR__-40 371-04178-103 —
HES2COMPR__-46 371-04178-105 —
HES2COMPR__-58 371-04178-106 —
HES2COMPR__-50 — 371-04178-104

The YCAV (Latitude) compressor drive is also available with other


options. Refer to the sales information for additional part numbers for
those models.

JOHNSON CONTROLS 5
FORM 201.21-M1 (307)

LATITUDE COMPRESSOR DRIVE COMPONENT OVERVIEW

Latitude Compressor Drive are gradually turned on with a delay angle to slowly
The YORK Latitude Compressor Drive (LCD) is a charge the DC link filter capacitors. This is called the
liquid cooled, transistorized, PWM inverter in a highly pre-charge period, which last for 20-seconds. After the
integrated package. Refer to FIG. 1. 20-second time period has expired, the SCR’s are gated
fully on. The SCR Trigger board (031-02060) provides
The LCD is not an option to the chiller as with other the turn on commands for the SCR’s during precharge,
YORK compressor drives. The LCD has a maximum and during normal running condition as commanded by
output of 200 Hz at 460 VAC OR 400 VAC (400 VAC the LCD Logic board (031-02477).
if input voltage is 380-415 VAC), 460 VAC for all
others.
The power section of the drive is composed of four Although many of the parts used in the
major blocks: LCD are similar to the parts used in previ-
ous Variable Speed Drive (VSD) designs,
● an AC to DC rectifier section with an integrated the LCD’s parts are only compatible with
pre-charge circuit, drives having the base part numbers in-
● a DC link filter section, cluded on the cover of this form. Failure
● a three phase DC to AC inverter section, and, to use the correct parts may cause major
damage to these and other components
● an output suppression network. in the drive. For example, the LCD logic
An electronic circuit breaker with ground fault sensing board 031-02477-XXX used in this drive is
is an option on this product. An input lug connection is not compatible with 031-02077-XXX logic
standard for all models other than 400VAC. The lugs board used in previous designs.
are connected from the AC line to the input fuses then
to an AC line choke, and then to the AC-DC converter. The figures included in this form are for
The following description of operation is specific for the 2 compressor drive.
the 2 and 3 compressor Latitude compressor drive.
Refer to FIG 2.

The AC to DC semi-converter uses 3 Silicon Controlled


Rectifiers (SCR’s) and 3 diodes. One SCR and one The DC Link filter section of the drive consists of one
diode are contained in each module. Three modules basic component, a series of filter capacitors (C1-C6).
are required to convert the 3 phase input AC voltage These capacitors provide a large energy reservoir for
into DC voltage (1SCR-3SCR) in a three-phase bridge use by the DC to AC inverter section of the LCD. The
configuration. Refer to FIG 2. The modules are mounted capacitors are contained in the LCD Power Unit. In
on a liquid cooled heatsink. The use of the SCR’s in the order to not exceed the voltage rating of each capacitor,
semi-converter configuration permits pre-charging of two capacitors are placed in series to form a “pair”.
the DC link filter capacitors when the chiller enters start Capacitors “pairs” are paralled to achieve the current
mode, and it also provides a fast disconnect from the rating needed thus forming a capacitor “bank”. In order
AC line when the chiller has a unit fault condition. to assure an equal sharing of the voltage between the
When the chiller enters the unit fault condition or is shut series connected capacitors and to provide a discharge
down via the unit rocker switch the LCD is turned off. path for the capacitor bank when the LCD is powered
The SCR’s in the semi-converter are no longer turned on off, “bleeder” resistors (1RES and 2RES) are connected
and remain in a turned off or non-conducting mode. The across the capacitor banks. The “Bleeder” resistors
DC link filter capacitors will start to discharge through are mounted on the front of the Power Unit under the
the bleeder resistors. When the chiller enters the start SCR’s.
cycle, the LCD is commanded to pre-charge, the SCR’s

6 JOHNSON CONTROLS
FORM 201.21-M1 (307)

COOLANT-TO-AIR OUTPUT
HEAT EXCHANGER CURRENT
TRANSFORMERS

LCD
LOGIC
BOARD

SCR
TRIGGER
BOARD

COMPRESSOR
#1 IGBT
MODULE

COMPRESSOR
#2 IGBT
MODULE
50045

INPUT POWER FUSES INPUT LINE INDUCTOR SCR/DIODE MODULES

FIG. 1 – LCD CONTROL PANEL

The DC to AC inverter section of the LCD serves to The “laminated bus” structure connects the IGBT
convert the DC voltage back to AC voltage at the proper module to the capacitor bank through 2 copper plates
magnitude and frequency as commanded by the LCD that are insulated from each other. When an insulator
Logic board. The inverter section is composed of one separates 2 copper plates they form a capacitor, which
power unit. This power unit is composed of very fast will counteract the inductance of the bus assembly.
switching transistors called an Insulated Gate Bipolar To further cancel the inductances in the laminated bus
Transistor (IGBT) module (1MOD & 2MOD) mounted structure, a series of small capacitors (C7-C12) are
on the same liquid cooled heatsink as the semi-converter connected between the positive and negative plates at
modules, the DC Link filter capacitors (C1-C6), a the IGBT modules connections.
semi-converter, and an LCD Gate Driver board (031-
02061) mounted directly to the IGBT module. The
LCD Gate Driver Board provides the turn on and turn The LCD output suppression network is composed
off commands to the IGBT’s output transistors. The of several capacitors (C13-C18) and resistors (3RES-
Latitude Compressor Drive Logic board determines 14RES). The parameters of the suppression network
when the turn on, and turn off commands should occur. components are chosen to work in unison with the
The gate driver board is mounted directly on top of the inductance of the DC to AC inverter sections in order to
IGBT module, and it is held in place with mounting simultaneously limit both the rate of change in voltage
screws and soldered to the IGBT module. and the peak voltage applied to the motor windings.

If the IGBT modules and the capacitor bank were By limiting the peak voltage to the motor windings, as
connected together with wire a large amount of well as the rate-of-change in motor voltage, problems
inductance from the wire would cause a failure in the commonly associated with PWM motor drives, such as
IGBT. To reduce the inductance of the bus assembly stator-winding end-turn failures and electrical fluting of
YORK employs a “laminated bus” structure technology. motor bearings can be avoided.

JOHNSON CONTROLS 7
FORM 201.21-M1 (307)

Other sensors and boards are used to convey information the board to provide a “safe” resistance between the
back to the LCD Logic board and provide safe operation DC link filter capacitors located in the LCD power unit
of the Latitude Compressor Drive. The IGBT modules and the LCD logic board. It provides the means to sense
contain a thermistor temperature sensor (RT1 and RT2) the positive, midpoint and negative voltage connection
that provides temperature information back to the LCD points of the LCD’s DC link. Six Current Transformers
logic board via the gate driver boards. The Bus Voltage (4T-9T) monitor the output current from the LCD power
Isolator board (031-01624) utilizes three resistors on unit and are used to protect the motor from overcurrent
conditions.

8 JOHNSON CONTROLS
FORM 201.21-M1 (307)

LATITUDE COMPRESSOR DRIVE CONTROL SYSTEM OVERVIEW

The LCD is housed in the same cabinet as the rest of the cooling fans and pump will continue to run until
chiller control system. The chiller control board dictates the value of the internal temperature has dropped
to the LCD what RPM to run the compressor based upon below a specified value.
the leaving chilled liquid temperature control or any In an attempt to keep the internal temperature of
limiting controls. The only time the LCD will override the LCD cool enough to start, the LCD’s internal
the control system is when a shutdown condition for cooling fans and pump will turn on without the
the LCD occurs. chiller running if the internal temperature is
within 10°F of the fault value. This fault value
The LCD control system is composed of various will depending on the number of compressors on
components located within Chiller Control Center the chiller. The internal cooling fans and pump
which allows integration between the Chiller Control will turn off when the internal temperature of the
Center and the LCD. The LCD system utilizes various drive is 15°F below the fault value.
microprocessors and Digital Signal Processors The LCD’s fans and pump will also turn on if
(DSPs) which are linked together through a serial the chiller is placed in service mode and the
communications link. status of the VSD cooling fans/pump is enabled.

The Chiller Control Center • The LCD Logic board sends a command signal
The Chiller Control Center contains 2 main boards. The to the SCR trigger board to precharge the bus
first main board, the chiller control board, controls all capacitors. The pre-charge command is sent to
aspects of the chiller as well as the output speed of the SCR trigger board on J11 pin 3-4.
LCD. The LCD logic board, the second main board,
determines precharge of the LCD, evaluates fault
conditions for the LCD, and determines how and when • The PWM generation is required so that the output
to turn on or off the output of the LCD. of the LCD will provide the proper voltage to the
motor for a given output frequency. The PWM
The chiller control board and the LCD logic board
signals are sent to the IGBT gate driver board via
communicate via a serial communications cable. Under
J6 for compressor #1, and J8 for compressor #2.
normal conditions the chiller control board sends an
RPM command to the LCD logic board. The LCD
logic board determines the correct output frequency The LCD logic board determines shutdown conditions
and voltage to rotate the compressor motor. If the LCD by monitoring all three phases of motor current for
determines that a fault condition is present, the LCD each compressor, baseplate temperature for each IGBT
logic board will open it’s fault relay, turn off the output module, internal ambient temperature, and the DC Link
of the drive and then report the fault along with fault voltage.
data to the chiller control board.
• Current transformers, mounted on the output
motor wiring to the compressors, monitor the
Latitude Compressor Drive Logic Board output motor current on each of the three phases
The LCD logic board performs numerous functions. and send this information to the J1 and J2
These functions include control of the LCD’s cooling connectors.
fans and pump, pre-charging of the bus capacitors, and • The baseplate temperature is monitored by a
generation of the PWM. Refer to FIG 3 for the location thermistor mounted inside each IGBT module.
of the various connectors on the LCD logic board. Any one of the thermistors can cause a high/low
• The internal cooling fans and pump are commanded temperature fault. The thermistor voltage is read
to turn on whenever the LCD is commanded to run at the J6 and J8 connector.
via J10 pins 1 and 2. They will turn off when the • The LCD internal ambient temperature is
drive is commanded to stop. If the LCD shutdown monitored by a temperature sensing device
is due to a high-temperature condition, the internal mounted on the LCD Logic board.

JOHNSON CONTROLS 9
FORM 201.21-M1 (307)

LD12651

FIG. 2 – LCD SCHEMATIC

10 JOHNSON CONTROLS
FORM 201.21-M1 (307)

LD12652

JOHNSON CONTROLS 11
FORM 201.21-M1 (307)

1 SCR TRIGGER OUTPUT J11 8 OVERLOAD SET POT COMPR #1 OVERLOAD LED
15
2 COMMS TO MICROBOARD J12 9 BUS VOLTAGE FEEDBACK J3 16 COMPRESSOR ENABLE LED'S

3 FAULT LED 10 MTR CURRENT FEEDBACK COMPR #2 J2 17 GATE DRIVER TEST SWITCH SW1

4 INPUT POWER SUPPLY J4 11 MTR CURRENT FEEDBACK COMPR #1 J1 18 POWER LED

5 MODBUS J5 12 IGBT GATE DRIVE COMPR #1 J6 19 RUN CMD, FAULT RELAY OUTPUT,
FAN & PUMP CONTROL J10
6 COMPRESSSOR RUN LED'S 13 IGBT GATE DRIVE COMPR #2 J8
20 SEND & RECEIVE COMMS LED'S
7 OVERLOAD SET POT COMPR #2 14 GATE DRIVER LED'S

1 2 3 4

20

19

18

17
7
16

15
8

14

13

12

9
11 10
50046
FIG. 3 – LATITUDE COMPRESSOR DRIVE LOGIC BOARD DETAILS

12 JOHNSON CONTROLS
FORM 201.21-M1 (307)

• The DC link isolator board monitors the DC link • Power LED will light any time power is applied
voltage and is connected to J3. to the LCD logic board.
• Fault LED will light whenever the fault relay
The LCD logic board also contains many LED’s to is open indicating a fault condition.
indicate various conditions of the drive. These LED’s • Compressor Enable LEDs will light when the
are used to monitor system operation during the drive has received the hardware and software
manufacturing process of the system. Refer to FIG. 3 run signal from the chiller control logic board
for the location of various LEDs. for that compressor. Four LEDs are located on
• 105% LED will light whenever any phase of the logic board 1 for each compressor.
motor current is 2% greater than 100% current • Compressor Run LEDs will light when the
rating as set by the percent FLA adjustment drive has received the hardware run signal
pot. from the chiller control logic board. Two LEDs
• A-, A+, B-, B+, C-, C+ LEDs light whenever are located on logic board 1 for each chiller
the IGBT gate driver is turned off, and will not system.
light whenever the IGBT gate driver is turned
on. At low motor output frequencies these LEDs
will flash. They will remain on constantly when
the drive is running at high output frequency.
Chiller Control Center VSD Related
Keypad Functions
• RCV (receive) and XMT (transmit) LEDs
will flash when the LCD logic board is
Refer to form 201.21-NM1, NM2, NM3 or NM4 for
communicating with the chiller control board.
related keypad functions.
Each should flash about once a second.

JOHNSON CONTROLS 13
FORM 201.21-M1 (307)

TROUBLESHOOTING UNIT SHUTDOWNS

This product contains voltages that could DC Bus Voltage Imbalance


cause injury! Before performing any of The DC bus voltage is filtered by many large capacitors,
these procedures, place the unit switch which are rated for 450 VDC. Two capacitors are wired
in the “STOP” position. Wait 5 minutes, in series to achieve a 900 VDC capability for the DC
ensure the DC bus voltage is 50 VDC, or bus voltage. It is important that the voltage is shared
less, on the display of the chiller. Remove equally across each capacitor.
all AC power sources and perform lockout
tagout procedures. Using a non-contact The voltage across each half of the bank is monitored
voltage sensor, ensure no AC power is and if the voltage on either half of the bank is greater
present in the enclosure. Measure the DC than ± 100 VDC from ½ of the total DC link voltage,
bus voltage at J3 pins 1-3 on the LCD logic then this shutdown will occur.
board using a dvm to ensure that the bus The DC Bus Voltage Imbalance shutdown will lockout
voltage is less than 50 VDC. the operation of the chiller on the first event.
Possible Causes:
General Information
The Unit Shutdowns are organized in alphabetical order • Bleeder resistor failure. Verify the two bleeder
based on the Chiller Control Center messages. resistors are the same value. The value should
be 2.4K ohms. Ensure that a thermal pad is
Whenever a Unit Shutdown is generated by the LCD a installed beneath each resistor and the mounting
series of events will occur. nuts of the bleeder resistor are tight. A new
thermal pad should be installed when the
• Any shutdown that occurs while the chiller is not resistors are replaced.
running will cause a start inhibit. The chiller cannot
start until the shutdown is cleared. • Intermittent wiring connection. Verify continuity
of the wiring between the large capacitors, bus
• If the chiller is running when the shutdown occurs isolator board, LCD logic board and the bleeder
the LCD logic board will turn off all of the IGBT resistors.
gate drivers.
• Failure of the bus voltage isolation board. Use
• The fault relay for the faulted system on the LCD an ohmmeter to measure from J1 pin 1 to J2
logic board will de-energize causing a momentary pin 1 on the bus voltage isolation board. The
open circuit between J10-3 and J10-4. This open ohm reading should be 150k ohm. Repeat
circuit will indicate to the Chiller Control Center this measurement for pin 2 and pin 3. The
that the LCD has shutdown. The fault relay will resistance reading should be the same for all
remain de-energized until the Chiller Control board 3 measurements. If the measurements are not
has acknowledged the cause of the shutdown. Once 150k ohms, then the bus isolator board needs
the Chiller Control board has acknowledged the to be replaced.
shutdown the fault relay will close.
• Shorted DC link capacitor. Using an analog
• The LCD logic board will send a shutdown code via
ohmmeter on the Rx10 scale, take an ohm
the serial communications link to the Chiller Control
reading across half of the bus. The needle of
board. The Chiller Control board will interpret the
the meter should first go to the right, and then
shutdown code, and display a shutdown message
gradually move to the left as the capacitor
on the display of the Chiller Control Center.
charges up to the meter’s output voltage. A
shorted capacitor will keep the needle to the
After the reason for the shutdown has been corrected, the
right and will not charge up. Repeat this test for
chiller may auto restart, but will lock out the operation
the other half of the capacitor bank. Replace the
of the chiller if the same shutdown were to occur 3 times
complete power assembly with the bus capaci-
within a 90-minute window unless otherwise noted in
tors included if a shorted capacitor is present.
the shutdown information.

14 JOHNSON CONTROLS
FORM 201.21-M1 (307)

• Open DC link capacitor. Using an analog meter High VSD Internal Ambient Temperature
on the Rx10 scale, take an ohm reading across The ambient temperature of the LCD is monitored by a
half of the bus. The needle of the meter should temperature sensing device mounted on the LCD logic
first go to the right, and then gradually move board. The high ambient trip threshold is set for 158°F
to the left as the capacitor charges up to the (70°C). If this shutdown occurs, the internal cooling
meter’s output voltage. An open capacitor will fans, coolant pump, and condenser fans will remain
not charge up, but the needle will remain to the on until the internal ambient temperature has fallen to
left, or discharge very little. Repeat this test for 143°F (62°C). The chiller will auto-restart when the
the other half of the capacitor bank. Replace the internal temperature has dropped below the shutdown
complete power assembly with the bus capaci- level.
tors included if an open capacitor is present.
Possible Causes:
• Failed LCD logic board. Replace the LCD logic
board. • Improper coolant level for the LCD. Refer to
form 201.21-NM1, NM2, NM3 or NM4 for the
proper coolant level.
High DC Bus Voltage • Failure of a coolant hose or clamp. Perform a
While the chiller is running, the DC bus voltage is visual inspection for a coolant leak. Ensure the
continuously monitored by the LCD logic board through coolant hoses at the drive or coolant pump are
the bus voltage isolation board. If the level of the bus not kinked.
voltage exceeds 766 VDC a shutdown is initiated. This
shutdown will protect the capacitors from a voltage that • Excessive coolant temperature. Coolant
exceeds their rating. temperature entering the LCD should not exceed
140°F or 60°C. Failure of a condenser fan,
condenser fan contactor or a condenser fan fuse
Possible Causes: could cause excessive coolant temperature.
• Supply voltage not within the chiller’s voltage
utilization range. Have the customer verify • Failure of the LCD coolant pump or internal
that the supply voltage to the chiller is within fans. Perform ohm check for the fan and the
specification. coolant pump fuses using the wiring diagram
for your chiller model and an ohmmeter. For
• Transient voltage surge. The shutdown may 50 Hz units, verify the fuses for the 50/60 Hz
be a result of a storm or power grid switching. inverter are not open. Refer to Form 201.21-
Speak with a person on site at the time of the NM1, NM2, NM3 or NM4 for instructions to
shutdown to determine if a voltage anomaly manually control the coolant pump and fans.
occurred. Listen to verify the coolant pump and fans are
• Meg the compressor motor. If a phase has gone running.
to ground this shutdown may be displayed. • Dirty condenser is causing higher than
Wiring between the LCD and the motor must normal coolant liquid temperatures. Regular
be disconnected before megging the motor. maintenance of the condenser is required.
LCD failure may result if motor wires are
not removed.
Low DC Bus Voltage
• Failure of the bus voltage isolation board. Use
While the chiller is running, the DC bus voltage is
an ohmmeter to measure from J1 pin 1 to J2
continuously monitored by the LCD logic board through
pin 1 on the bus voltage isolation board. The
the bus voltage isolation board. If the line voltage were
ohm reading should be 150k ohms. Repeat this
to quickly drop the current seen by the motor could
measurement for pin 2 and pin 3. The resistance
exceed it’s rating or the rating of the IGBT. The low
measurements should be the same for all 3
bus voltage shutdown will prevent this from happening.
measurements. If the measurements are not
This shutdown is generated when the bus voltage drops
150k ohms, then the bus isolator board needs
below 500 VDC (for 50 or 60 Hz).
to be replaced.
• Failed LCD logic board. Replace the LCD logic
board.

JOHNSON CONTROLS 15
FORM 201.21-M1 (307)

Possible Causes: for more than 30 seconds. The 102% RLA setpoint is
• Supply voltage not within the chiller’s specified determined by adjustment of the FLA trimpots on the
voltage utilization range. Have the customer LCD logic board. Each compressor motor has it’s own
verify that the supply voltage to the chiller is trimpot. This shutdown will lockout the operation of
within specification. the chiller on the first event.

• Transient voltage surge. This shutdown may Possible Causes:


be a result of a storm or power grid switching. • RLA value not properly set. Refer to form
Speak with a person on site at the time of the 201.21-NM1, NM2, NM3 or NM4 for details
shutdown to determine if a voltage anomaly on how to view the overload values Refer to the
occurred. LCD logic board replacement procedure in this
• Intermittent wiring connection. Verify continuity form for information on how to adjust the RLA
of the wiring between the large bus capacitors, value, if required.
the bus isolation board, the LCD logic board • Excessive operating condenser pressure. Refer
and the bleeder resistors. There could also be to form 201.21-NM1,, NM2, NM3 or NM4 for
an intermittent wiring connection between the possible causes.
SCR trigger board and the SCR’s or between • Restriction in the refrigerant circuit. Refer to
the SCR trigger board and the LCD logic form 201.21-NM1, NM2, NM3 or NM4 for
board. Refer to the wiring diagram for the wire possible causes.
numbers.
• The economizer valve not working properly
• Failed bus isolator board. Use an ohmmeter to or stuck open. Refer to form 201.21-NM1 for
measure from J1 pin 1 to J2 pin 1 on the bus possible causes.
isolator board. The reading should be 150k
ohms. Repeat this measurement for pins 2 and • Feed and drain valves not working properly.
3. The resistance readings should be the same Refer to form 201.21-NM1, NM2, NM3 or
for all 3 measurements. If the readings are not NM4 for possible causes.
150k ohms, then the bus isolator board needs
to be replaced. Precharge - DC Bus Voltage Imbalance
• Perform an ohm check between the + bus The definition for this shutdown is identical to “DC
connection on the power assembly and J3 pin Bus Voltage Imbalance”, except this shutdown occurs
1 of the LCD logic board. The reading should during the precharge period. Refer to “DC Bus Voltage
be 150k ohms. At the same time, gently try to Imbalance” shutdown for possible problems. This
move the connectors at the bus isolation board shutdown will lockout operation of the chiller on the
and the LCD logic board. Repeat this test for first event.
the center bus connection and J3 pin 2, and the
– bus connection and J3 pin 3. The ohm value Precharge - Low DC Bus Voltage
should not change. If the value does change
The LCD logic board determines this shutdown with
determine where the bad connection is and
information from the bus isolator board. This shutdown
replace that board.
has two different timing events. First, the DC Bus
• Failed SCR trigger board. Replace the SCR voltage must be equal to or greater than 41 VDC four
trigger board. seconds after pre-charge has begun. Second, the DC Bus
• Failed LCD logic board. Replace the LCD logic voltage must be equal to or greater than 500 VDC 19
board. seconds after pre-charge has begun. This shutdown is
important to determine if the converter is not working
properly or if the capacitor bank is shorted.
Motor Current Overload
This shutdown is generated when the LCD logic board Possible Causes:
has detected that the highest of the three output phase • Input power fuses to the LCD are open. Use an
currents for any compressor has exceeded 102% of ohmmeter to verify the input power fuses to the
the programmed 100% rated load amps (RLA) value LCD are not open.

16 JOHNSON CONTROLS
FORM 201.21-M1 (307)

• Intermittent wiring connection. Verify continu- Speak with a person on site at the time of the
ity of the wiring between the large capacitors, shutdown to determine if a voltage anomaly
the bus isolator board, the LCD logic board and occurred.
the bleeder resistors. There could also be an in-
• Input power fuses to the LCD are open. Use an
termittent wiring connection between the SCR
ohmmeter to verify the three input power fuses
trigger board and the SCR’s or between the SCR
to the LCD are not open.
trigger board and the LCD logic board. Refer
to the wiring diagram for wire numbers. • Input fuse to the SCR trigger board open. Use an
ohmmeter to verify the input fuse feeding TB3
• Shorted DC link capacitor. Using an analog
of the SCR trigger board is not open. Chillers
ohmmeter on the Rx10 scale, take an ohm
built before 7/05 had a ¼ amp fuse installed in
reading across half of the bus. The needle of
this circuit. This low amperage fuse sometimes
the meter should first go to the right, and then
caused this shutdown. After 7/05 the fuse was
gradually move to the left as the capacitor
changed to a 6 amp fuse. Change the fuse to
charges up to the meter’s output voltage. A
a 6 amp fuse, if required. Refer to the wiring
shorted capacitor will keep the needle to the
diagram for the fuse designation.
right and will not charge up. Repeat this test for
the other half of the capacitor bank. Replace the • Intermittent wiring connection. Verify continuity
complete power assembly with the bus capaci- of the wiring between the SCR trigger board
tors included if a shorted capacitor is present. terminals TB1, TB2 and TB3 to the input power
fuses. Refer to the wiring diagram for the wire
• Unseated connector. Verify that J4 on the
numbers.
SCR trigger board is properly installed. Verify
that J11 on the LCD logic board is properly • Unseated connectors. Verify connector J4 on
installed. Verify that the sockets are properly the SCR trigger board and connector J11 on
seated in the housings and that none of the the LCD logic board are properly seated. Verify
sockets are spread open. the sockets are properly seated in the connector
• Failed SCR trigger board. Replace the SCR housings and none of the sockets are spread
trigger board. open.

• Failed LCD logic board. Replace the LCD logic • Failed SCR trigger board. Replace the SCR
board. trigger board.

• Failure of an input diode/SCR pair. Replace the • Failed LCD logic board. Replace the LCD logic
input SCR/Diode module. board.

Single Phase Input Voltage VSD Communications Failure


This shutdown is generated by the SCR Trigger board At power-up, the LCD logic board will go through
and relayed to the LCD logic board to initiate a unit a process called initialization. At this time, memory
shutdown. The SCR trigger board uses circuitry to detect locations are cleared, jumper positions are checked and
the loss of any one of the three input voltage phases. The the serial communication link is established between the
SCR trigger board will detect the loss of a phase within LCD logic board and the chiller control logic board. If at
one half line cycle of the phase loss. This shutdown is any time the chiller control logic board does not receive
always an auto-restart when the fault has cleared. valid data from the LCD logic board for a period of 8
Possible Causes: seconds this shutdown will occur.

• Loss of power. This message is displayed every Possible Causes:


time power to the LCD is restored or if the input • Unseated connectors. Verify the communication
power dips to a very low level. This is not an wire harness connectors are properly seated on
indication of a problem with the LCD. the LCD logic board at J12 and the chiller control
• Transient voltage surge. The shutdown may logic board at J2. Ensure that the shield is only
be a result of a storm or power grid switching. connected at the chiller control logic board. Check
for continuity and also check to see that none of

JOHNSON CONTROLS 17
FORM 201.21-M1 (307)

the conductors are shorted together or shorted to • Failed RS-485 communication driver. Replace the
ground. RS-485 communications driver on both the LCD
logic (U86) and the chiller control (U5) boards.
• Incorrect Modbus address setting. Verify the
Modbus address jumper plug is properly installed • Failed LCD logic board. Replace the LCD logic
in J5 of the LCD logic board. The default board.
address is address #1. The table below shows • Failed chiller control board. Replace the chiller
the J5 jumper configurations for all of available control board.
Modbus addresses. The chiller control must be
programmed with the identical address as set per
the J5 jumper on the LCD logic board. The default VSD CT Plug Fault
address for both J5 on the LCD logic board and This shutdown is generated by the LCD logic board.
the address programmed into the chiller control Connectors J1 and J2 on the LCD logic board contain
is 1. jumpers between the 2 connectors. If either of the
connectors is loose or missing a fault will occur. This
LCD Logic Board LCD Logic Board ensures that the LCD always has current feedback
MODBUS Address Jumper Position
information from each compressor motor.
J5-1 to J5-2
1 Possible Causes:
J5-3 to J5-4
2 J5-3 to J5-4 • Unseated connector. Check to ensure J1 and J2
3 J5-1 to J5-2 on the LCD logic board are properly seated.
4 None
• Loose or intermittent wiring connection. Verify
continuity of the wiring between connector J1
• Unseated or incorrect EPROMs. Verify all sockets 7 or 8 and connector J2 sockets 7 or 8 on
EPROMs are properly seated in their sockets the LCD logic board. Refer to wiring diagram
and none of the pins are bent over. Refer to the for wire reference designators. Verify that the
Software Reference List near the back of this form sockets are not spread out and the sockets are
to verify the correct EPROMs are installed. properly installed in the connector housing.
• Improper powering of the chiller control center. Do not insert meter probes inside the
The chiller control logic board and the LCD sockets. Although, this is a simple way to
logic board must be energized at the same time. hold the probes, this practice will spread
Do not pull fuses in the control center to make the socket and may cause intermittent
wiring changes. Use the main disconnect device problems in the future. A better practice
to remove and apply power to the chiller control is to insert the probe into the back of the
center with all fuses installed. connector to make a measurement.
• Poor grounding. The LCD is the source of the
incoming earth ground for the chiller system. VSD Logic Board Failure
Ground is then conducted to the rest of the chiller This shutdown is generated by the LCD logic board.
by the mounting connections of the LCD and If a communications problem occurs between the two
the ground wiring to the compressor motors. All microprocessors on the LCD logic board, then this fault
mechanical connections from the LCD enclosure will occur. This fault is only verified during precharge
to the chiller frame are made with external tooth and run conditions.
lock washers. These washers cut through the paint
Possible Causes:
on the chiller and provide a ground connection.
Check the tightness of all ground wires within • Failed LCD logic board. Replace the LCD logic
the LCD and all the compressor motor terminal board.
boxes. Ensure the green earth wire from J4 of the
LCD logic board is attached to the LCD enclosure. VSD Logic Board Power Supply
Check and tighten as needed the mounting bolts
This shutdown is generated by the LCD logic board.
that attach the LCD to the chiller frame.
This shutdown indicates that one of the LCD logic board

18 JOHNSON CONTROLS
FORM 201.21-M1 (307)

DC power supplies has fallen outside their allowable • Unseated connector. Reseat the power supply
operating limits. The power supplies for the logic board connector J4 on the LCD logic board.
are derived from the secondary of the 120 to 24 VAC • Open fuse(s). Use an ohmmeter to verify fuses
transformer (FIG. 2) which in turn is derived from the 4FU, 5FU, 17FU, and 18FU are not open.
480 to 120 VAC control transformer (FIG. 2).
• Intermittent wiring connection. Use an
Possible Causes: ohmmeter to verify continuity of the wiring
• Momentary loss of power. This message is between transformers 2T and 3T and the LCD
displayed every time power to the LCD is logic board. Refer to the wiring diagram for
applied or if the input power dips to a very low wire numbers.
level. This is not an indication of a problem with • Failed LCD logic board. Replace the LCD logic
the LCD unless this shutdown does not clear. board.

JOHNSON CONTROLS 19
FORM 201.21-M1 (307)

TROUBLESHOOTING SYSTEM SHUTDOWNS

This product contains voltages that could Gate Driver


cause injury! Before performing any of The LCD has 2 methods of detecting an over current
these procedures, place the unit switch condition. One is from the output current transformers
in the “STOP” position. Wait 5 minutes. and the second is the gate driver fault. The gate driver
Ensure the DC bus voltage is 50 VDC, or fault is detected on the gate driver board. The on-state
less on the display of the chiller panel. or collector-to-emitter voltage of each IGBT is checked
Remove all AC power sources and perform while the device is turned on. This is also called the
lockout tagout procedures. Use a non-con- collector-to-emitter saturation voltage. If the voltage
tact voltage sensor to ensure no AC power across the IGBT is greater than a set threshold as
is present in the enclosure. Measure the defined by the gate driver board, the IGBT is turned
DC bus voltage at J3 pins 1-3 on the LCD off and a shutdown pulse is sent to the LCD logic
logic board using a dvm to ensure the bus board shutting down the chiller system. This fault
voltage is less than 50 VDC. can indicate that too much current is flowing through
the IGBT when the device is being commanded to
General Information turn on. This fault can also be caused if an IGBT is
The System Shutdowns are organized in alphabetical turned off when it should be turned on or if the gate
order based on the Chiller Control Center messages. drive power supply falls below permissible limits.

Whenever a System Shutdown is generated by the


Possible Causes:
LCD a series of events will occur.

• Any shutdown that occurs while the chiller is not • Unseated connector. Reseat connectors on the
running will cause a start inhibit for that system. LCD logic board, SCR trigger board and the
That chiller system cannot be started until the IGBT gate drive board.
shutdown has been cleared.
• Failure of the SCR trigger board. Inspect part
• If the chiller is running when the shutdown Q10 on the SCR trigger board. When an IGBT
occurs the LCD logic board will turn off the module fails it may cause Q10 to fail and the
IGBT gate drivers for the failed system. part may be burned and/or cracked. Replace the
• The fault relay for the faulted system on the LCD SCR trigger board if damage is noted to part
logic board will de-energize causing an open Q10.
circuit between J10-3 and J10-4. This action will • Intermittent wiring connection. Use an
indicate to the Chiller Control Center that the ohmmeter to verify the wiring between the
LCD has shutdown. The fault relay will remain LCD logic board, SCR trigger board and
de-energized until the Chiller Control board has the IGBT gate driver board. Also, verify the
acknowledged the cause of the shutdown. Once motor is properly wired inside the LCD and
the Chiller Control board has acknowledged the motor terminal box and that all connections are
shutdown the fault relay will close. tight.
• The LCD logic board will send a shutdown • Compressor motor snubber failure. On the back
code via the serial communications link to the wall of the LCD near the motor connections
Chiller Control board. The Chiller Control board there are a series of resistors and capacitors that
will interpret the shutdown code, and display a make up the motor snubber network. Use an
shutdown message on the display of the Chiller ohmmeter to verify the proper wiring of these
Control Center. components. Refer to the wiring diagram. Also
ensure with an ohmmeter that the value of the
After the reason for the shutdown has been corrected, resistors is 10 ohms and the capacitors are not
the chiller may auto restart, but will lock out the shorted. If a resistor does not have a value of 10
operation of the chiller if the same shutdown were ohms, then it should be replaced. If a capacitor
to occur 3 times within a 90-minute window, unless is shorted, it should be replaced.
otherwise noted in the shutdown information.

20 JOHNSON CONTROLS
FORM 201.21-M1 (307)

• Motor stator winding failure. Remove the motor • Intermittent wiring connection. Use an
wires between the LCD and the compressor ohmmeter to verify the wiring between the LCD
motor. Meg the motor phase to phase and logic board and the IGBT gate driver board.
phase to ground. Replace the motor is if this Refer to the wiring diagram
test fails. • Failure of an output current transformer. Disconnect
• Failure of the IGBT module. Follow the the connector for each of the output current
procedure to check an IGBT module found later transformers and take an ohm reading at the
in this form. connector. Each current transformer should have
• How to determine if a fault lies within the an ohm reading of 125 ± 19 ohms. Note: Readings
LCD or with the compressor/motor. Note the at connectors should be taken from the back of
system (#1 or #2) causing the fault. Swap the the connector so that the socket is not spread
three phases of output motor wiring, between apart. If the reading is within range, then reinstall
system #1 and system #2, at the IGBT modules. the connector. If the reading in not within range,
Also, swap the CT feedback plugs J44 and replace the faulty current transformer.
J45 (refer to wiring diagram). Do not run the • Motor stator winding failure. Meg the motor
chiller for a long period of time since the phase to phase and phase to ground. Wiring
condenser temperature control will not work between the LCD and the motor must be
correctly. If the opposite system indicates a disconnected before megging the motor.
fault, the problem lies with the compressor or LCD failure may result if motor wires are
compressor motor on the system now indicating not removed. Replace faulty motor if the motor
the fault. Replace the compressor/motor. If the fails the test.
original system is still indicating a fault then • Failure of the IGBT module. Check IGBT
the fault lies within the LCD. Replace the IGBT module per the procedure in this manual.
assembly for that system. If the IGBT assembly
is not failed, replace the LCD logic board. • Restriction in the refrigeration circuit. Refer
to form 201.21-NM1, NM2, NM3 or NM4 for
possible causes.
High Motor Current
• Failure of the LCD logic board. Replace the
This shutdown is generated by the LCD logic board.
LCD logic board.
If any one phase of motor current as measured by the
Output Current Transformers exceeds a pre-determined • Economizer valve is not working properly or
instantaneous level, a shutdown will occur. The current stuck open. Refer to form 201.21-NM1, NM2,
values displayed by the panel are averaged RMS values NM3 or NM4 for possible causes.
so the displayed value may not be indicative of the • Feed and drain valves not working properly.
instantaneous value of current which causes a high Refer to form 201.21-NM1, NM2, NM3 or
motor current trip. NM4 for possible causes.

Possible Causes: High VSD Baseplate Temperature


• Momentary line voltage sag. This message may A 5K ohm (at 77°F) thermistor sensor is embedded
be displayed if the input power sags below the inside each IGBT Module on the LCD power unit. If at
specified sag voltage rating for this product. anytime this thermistor detects a temperature in excess
This is especially true if the chiller was running or a predetermined limit, a shutdown will occur. The
at, or near, full load. The chiller cannot unload internal cooling fans and coolant pump will continue to
quickly enough to correct for this sudden run after the shutdown, until the thermistor temperature
increase in current. If this is the case, the chiller has dropped to an acceptable level. Refer to Table 1 for
will auto restart. This is not an indication of a detailed thermistor values.
problem with the LCD. Possible Causes:
• Unseated connector. Reseat the connectors on • Improper coolant level. Refer to form 201.21-
the LCD logic board and the IGBT gate drive NM1, NM2, NM3 or NM4 for the proper
board. coolant level.

JOHNSON CONTROLS 21
FORM 201.21-M1 (307)

• Failure of a coolant hose or clamp. Perform a TABLE 1 - LCD IGBT - THERMISTOR


visual inspection for a coolant leak. Also, check CHARACTERISTICS
TEMP°F TEMP°C R-THERMISTOR
for a kinked coolant hose. NOMINAL NOMINAL in ohms *
• Excessive coolant temperature. The coolant 40 4.4 11314
temperature entering the LCD is not to exceed 45 7.2 10080
140°F or 60°C. Failure of condenser fan, 50 10.0 8996
condenser fan contactor or a condenser fan 55 12.8 8031
fuse could cause excessive coolant temperature. 60 15.6 7193
Verify all condenser fans are operational. 65 18.0 6447
• Failure of the coolant pump. Perform an ohm 70 21.1 5793
check for the coolant pump fuses using the 75 23.9 5212
wiring diagram for your chiller model and an 80 26.7 4698
ohmmeter. Refer to Form 201.21-NM1 for 85 29.4 4242
instructions to manually control the coolant 90 32.2 3835
pump. Listen to verify the coolant pump is
95 35.0 3471
running.
100 37.8 3150
• Failure of the IGBT assembly or LCD logic 105 40.5 2859
board. Remove the gate driver connector from 110 43.3 2602
the LCD logic board (J6 for system #1 and J8
120 48.9 2162
for system #2). Take an ohm reading between
130 54.4 1807
pins 6 & 8 on J6 and J8 and compare the
140 60.0 1515
readings with the values shown in table #1. If
the values are in accordance with table #1, then 150 65.6 1278
replace the drive logic board. If the values are 160 71.1 1085
not in accordance with table #1, then repeat this 170 76.7 924
test at the J1 connector on the IGBT module 180 82.2 791
between pins 6 & 15. If the values are not in 190 87.8 679
accordance with table #1, then replaced the 200 93.3 587
appropriate IGBT assembly. 210 98.9 508
• No thermal grease used on the IGBT module. 220 104.4 442
The IGBT module requires that a thin even layer
of thermal grease be used to aid in the transfer
of heat to the chill plate. Motor Current Overload
• Clogged chill plate. This shutdown is generated when the LCD logic
board has detected that the highest of the three output
• The SCR module or IGBT module is not phase currents for any compressor has exceeded
properly torqued. The proper torque value is 102% of the programmed 100% rated load amps
48 in.-lbs. or 5.5 Nm (RLA) value for more than 20 seconds. The 100%
DO NOT insert the probes of the ohm- RLA setpoint is determined by adjustment of the
meter into the front side of any connector. FLA pots on the LCD logic board. Each compressor
This will cause the sockets in the connec- motor has its own FLA pot. This shutdown will
tor to spread apart and cause an intermit- lockout the operation of the chiller on the first event.
tent connection. Instead insert the probes
into the back of the connector. Possible Causes:
• FLA pot not adjusted properly. Refer to form
201.21-NM1, NM2, NM3 or NM4 for details
on how to view the overload value. See the
LCD logic board replacement segment of this

22 JOHNSON CONTROLS
FORM 201.21-M1 (307)

document for instructions on how to adjust the VSD Run Relay


RLA setting, if necessary. Two run signals are generated by the Chiller Control
• Excessive operating condenser pressure. Refer Board for each compressor system. One is through
to form 201.21-NM1, NM2, NM3 or NM4 for the communication system, and the other is through
possible causes. the wiring between the chiller control board, the relay
interface board and the LCD logic board. Upon receipt
• Restriction in the refrigerant circuit. Refer to
of either of the two run signals by the LCD logic board,
form 201.21-NM1, NM2, NM3 or NM4 for
a 5-second timer will begin timing on the LCD logic
possible causes.
board. If the second run signal is not received within
• The economizer valve not working properly or the 5-second window, the LCD logic board will not
stuck open. Refer to form 201.21-NM1, NM2, start the chiller.
NM3 or NM4 for possible causes.
Possible Causes:
• Feed and drain valves not working properly.
• Intermittent wiring connection. Use an
Refer to form 201.21-NM1, NM2, NM3 or
ohmmeter to verify the run signal wiring
NM4 for possible causes.
between the Chiller Control Board and the LCD
• Failure of an output current transformer. logic board. System #1 hardware run signal is
Remove the current transformer connector and sent on wire #113 to the LCD logic board at J10
take an ohmmeter reading. Note: Readings at pin 7. System #2 hardware run signal is sent
connectors should be taken from the back of on wire #213 to the LCD logic board at J10
the connector so that the socket is not spread pin 5. Also, perform a continuity check on the
apart. Each current transformer should read communication link between LCD logic board
125 ± 19 ohms. If the reading is within range, connector J12 pin #1 and chiller control board
reinstall the connector. If not, replace the faulty connector J2 pin #1. On the same 2 connectors,
current transformer. check continuity from pin #2 to pin #2, pin #3 to
• Chiller refrigerant charge is too low or too pin #3 and pin #4 to pin #4. Refer to the wiring
high. Refer to form 201.21-NM1, NM2, NM3 diagram.
or NM4 for possible causes. • Unseated connector(s). Reseat the J12 connector
on the LCD logic board and the J2 connector
on the chiller control board.
• Failure of the relay board. Replace the relay
board.
• Failure of the LCD logic board. Replace the
LCD logic board.
• Failure of the LCD chiller control board.
Replace the LCD chiller control board.

JOHNSON CONTROLS 23
FORM 201.21-M1 (307)

WARNING MESSAGES

General Information Possible Causes:


A WARNING message will indicate that the operation • Incorrect J1 wiring. Verify that the proper wire
of the Latitude Compressor drive or chiller is affected connections are made at the J1 connector per
in some manner, but the LCD is still functioning. the above table.
• Unseated connector. Reseat connector J1 on the
Invalid Number of Compressor Selected LCD logic board.
This message is displayed when the compressor selection • Intermittent or loose wiring. Verify that the
jumpers are not properly configured or missing. The sockets are not spread out and the sockets are
jumpers are located on the J1 connecter of the LCD logic properly installed in the connector housing.
board. The table below shows the correct connections
for the different compressor quantities.

Number of LCD Logic Board


Compressors Jumper Position
2 J1-10 to J1-9
3 J1-11 to J1-9
4 J1-12 to J1-9

24 JOHNSON CONTROLS
FORM 201.21-M1 (307)

START-UP PREPARATIONS

The settings for the circuit breaker should


Circuit Breaker Setup
not be changed from the setting above.
The circuit breaker used on the LCD has many settings for The warranty will be voided if the circuit
short circuit and ground fault protection. Generally, these breaker settings have been changed.
setting are adjusted by the manufacturer but these setting
should be verified before starting the chiller. The rating
plugs for the circuit breaker should be verified as well.
Rating plug for voltage ranges.
All 2 compressor LCD use the same circuit breaker settings
but the rating plugs are based on the input voltage range.
Input voltage range Rating plug value
460, 575 VAC 600 Amp
Name of Adjustment Setting Value
• Short Delay Pickup “2” 380, 400 VAC 800 Amp

• Short Delay Time “INST” 200, 230 VAC 1200 Amp


• Ground Fault Pickup “1”
• Ground Fault Time “150”
Verify Overload Settings
Refer to form 201.21-NM1, NM2, NM3 or NM4 for
these settings.

JOHNSON CONTROLS 25
FORM 201.21-M1 (307)

LCD FREQUENTLY ASKED QUESTIONS

Why doesn’t the measured input amps of the LCD How often should the coolant be changed?
agree with the rated RLA?
The coolant should be changed every 5 years.
The rated RLA is the motor current at full load. The input
current to the LCD is comprised of motor current, fan What is the function of the TEST Button on LCD
and pump contactor current, control circuitry current Logic Board?
and condenser fan current. The TEST button is used to test the system opera-
tion during the manufacturing process of the system.
How is the LCD cooled?

The LCD contains a liquid coolant loop that is directly How is the RPM of the compressor motor con-
connected to the condenser of the chiller. The loop is trolled?
closed. A pump is used to move the coolant from and As with other YORK drive products, control of the
through the LCD and the condenser. On hot days when RPM comes from the chiller control system. The chiller
the chiller is not running the coolant pump and con- control board determines the optimum RPM of each
denser fans may turn on to ensure that the LCD internal compressor by monitoring the status of various chiller
temperature is maintained at an acceptable level. The pressures and temperatures.
coolant is a long life inhibited propylene glycol solution
What is the maximum RPM of the compressor mo-
formulated specifically for the LCD system.
tor?
Why are condenser fans running when the chiller The maximum RPM of the compressor motor is a
is not? function of the size of the chiller but does not exceed
6000 RPM. This allows the compressor and motor to
It is possible on a hot sunny day that the internal tem- be directly coupled without the use of gears.
perature of the LCD may exceed the shutdown value.
In this case, the chiller will not be available to run. To
maintain the internal temperature at an acceptable level
the coolant pump is turned on. If the coolant pump does
not maintain the internal temperature, then the first stage
of condenser fans will turn on.

26 JOHNSON CONTROLS
FORM 201.21-M1 (307)

TROUBLESHOOTING AND COMPONENT REPLACEMENT PROCEDURES

This product contains voltages that could Verifying Failure of the LCD IGBT Module
cause injury! Before performing any of
these procedures, place the unit switch General Information:
in the “STOP” position. Wait 5 minutes. Personnel not familiar with AC drives and
Ensure the DC bus voltage is 50 VDC or proper electrical safety procedures should
less on the display of the chiller. Remove not be working on this product.
all AC power sources and perform lockout
tagout procedures. Using a non-contact
voltage sensor, ensure no AC power is
present in enclosure. Measure the DC bus
voltage at J3 pins 1-3 on the LCD logic • Follow LCD discharge procedure at the beginning
board using a dvm to ensure the bus volt- of this section.
age is less than 50 VDC.
• It is not necessary to remove any wiring to perform
this test.
General Information
• Test instructions will be given for both an analog
The following procedures are designed to guide the
meter and a digital meter. The analog meter must
service technician along the path that leads to the
be set to the Rx1 scale and the meter should also
identification of a problem. The service technician should
be adjusted for a 0 ohm reading with the probes
understand the operation of the Latitude Compressor
connected together. The digital meter must be
Drive (LCD) and function of each major component.
placed on the diode check scale. In this test, we
It is recommended that the service technician read and
are not looking for exact resistance measurements
understood the information contained in this instruction
but rather to verify if the semi-conductor switches
prior to troubleshooting this product. Also, the service
are open or shorted.
technician must understand the system interface, and be
able to utilize system wiring diagrams to follow signal • The details of this procedure are for the compres-
flow throughout the system. Due to the integration of sor #2 IGBT module. Other IGBT modules are
the LCD and the chiller control system, a good working tested in the same manner by using the right side
knowledge of the chiller control system is also necessary of the IGBT module as a reference point.
(Ref. Forms listed at the beginning of this form).
Test Procedure:
Several levels of documentation are required for the • Place the positive probe of the meter on the first
troubleshooting process. The LCD wiring diagram, right hand terminal of the IGBT module at the
supplied with every chiller is the top-level document. It bus structure. This is the negative bus connection.
provides the overall wiring and configuration. Sections Place the negative probe of the meter on the first
of this instruction provide the required lower levels. right hand terminal of the IGBT module. This is
Specifically, block diagrams provide signal flow and one phase of the motor output. The wire should
simplified representations of all board circuitry. be marked 201. An analog meter reading will
read approximately 5-10 ohms. A digital meter
Begin the troubleshooting process by selecting the
reading will read approximately 0.36 VDC. Ref.
appropriate procedure. It is not necessary to sequentially
to FIG.4
perform all of them. Perform a procedure only if there
is a problem with that function. • Place the positive probe of the meter on the next
terminal to the left on the IGBT module at the
bus structure. This is the positive bus connection.
The analog meter reading will be near full scale
to the left of the meter movement. The digital
meter reading will be OL. The 2 readings will
take several seconds to stabilize.

JOHNSON CONTROLS 27
FORM 201.21-M1 (307)

• Place the positive probe of the meter on the 3rd to the left of the meter movement. The digital
right hand terminal of the IGBT module at the meter reading will be OL. The 2 readings will
bus structure. This is the negative bus connection. take several seconds to stabilize.
Place the negative probe of the meter on the 3rd • Place the positive probe of the meter on the 5th
right hand terminal of the IGBT module. This right hand terminal of the IGBT module. This is
is the next phase of the motor output. The wire the negative bus connection. Place the negative
should be marked 202. An analog meter reading probe of the meter on the 5th left hand terminal
will read approximately 5-10 ohms. A digital me- of the IGBT module. The wire should be marked
ter reading will read approximately 0.36 VDC. 203. An analog meter reading will read approxi-
• Place the positive probe of the meter on the 4th mately 5-10 ohms. A digital meter reading will
right hand terminal of the IGBT module at the read approximately 0.36 VDC.
bus structure. This is the positive bus connection. • Place the positive probe of the meter on the 6th
The analog meter reading will be near full scale

0.35 VDC READING ON DIGITAL METER

POSITIVE PROBE
ON NEGATIVE
BUS CONNECTION

NEGATIVE PROBE
ON OUTPUT
MOTOR WIRE

WIRE 201

50048

FIG. 4 – IGBT MODULE VERIFICATION #1

28 JOHNSON CONTROLS
FORM 201.21-M1 (307)

right hand terminal of the IGBT module. This is marked 201. The digital meter reading will be OL.
the positive bus connection. The analog meter The analog meter reading will be near full scale to
reading will be near full scale to the left of the the left of the meter movement. The 2 readings will
meter movement. The digital meter reading will take several seconds to stabilize. Ref. to FIG. 5
be OL. The 2 readings will take several seconds • Place the negative probe of the meter on the
to stabilize. next terminal to the left of the IGBT module at
• Place the negative probe of the meter on the first the bus structure. This is the positive bus con-
right hand terminal of the IGBT module at the nection. An analog meter reading will read ap-
bus structure. This is the negative bus connection. proximately 5-10 ohms. A digital meter reading
Place the positive probe of the meter on the first will read approximately 0.36 VDC.
right hand terminal of the IGBT module. This is • Place the negative probe of the meter on the 3rd
one phase of the motor output. The wire should be right hand terminal of the IGBT module at the

ANALOG METER
READING FULL SCALE

NEGATIVE PROBE
ON NEGATIVE
BUS CONNECTION

POSITIVE PROBE
ON OUTPUT MOTOR
WIRE 201

50049
FIG. 5 – IGBT MODULE VERIFICATION #2

JOHNSON CONTROLS 29
FORM 201.21-M1 (307)

bus structure. This is the negative bus connection. • Place the negative probe of the meter on the 4th
Place the positive probe of the meter on the 3rd right hand terminal of the IGBT module at the
right hand terminal of the IGBT module. This bus structure. This is the positive bus connection.
is the next phase of the motor output. The wire An analog meter reading will read approximately
should be marked 202. The analog meter reading 5-10 ohms. A digital meter reading will read ap-
will be near full scale to the left of the meter move- proximately 0.36 VDC. Ref. to FIG. 6
ment. The digital meter reading will be OL. The
2 readings will take several seconds to stabilize.

ANALOG METER
READING 10 OHMS

NEGATIVE PROBE
ON POSITIVE
BUS CONNECTION

POSITIVE PROBE
ON OUTPUT MOTOR
WIRE 202

50050

FIG. 6 – IGBT MODULE VERIFICATION #3

30 JOHNSON CONTROLS
FORM 201.21-M1 (307)

• Place the negative probe of the meter on the 5th 203. The analog meter reading will be near full
right hand terminal of the IGBT module. This is scale to the left of the meter movement. The digital
the negative bus connection. Place the positive meter reading will be OL. The 2 readings will
probe of the meter on the 5th right hand terminal take several seconds to stabilize. Ref. to FIG. 7
of the IGBT module. The wire should be marked

DIGITAL METER
READING OVERLOAD

NEGATIVE PROBE
ON POSITIVE
BUS CONNECTION

POSITIVE PROBE
ON OUTPUT MOTOR
WIRE 202

50051

FIG. 7 – IGBT MODULE VERIFICATION #4

JOHNSON CONTROLS 31
FORM 201.21-M1 (307)

• Place the negative probe of the meter on the 6th • This test will be conducted for an analog meter
right hand terminal of the IGBT module. This is the and a digital meter. The analog meter must be
positive bus connection. An analog meter reading adjusted to ohms on the Rx1 scale, and the meter
will read approximately 5-10 ohms. A digital meter should also be adjusted for a 0 ohm reading with
reading will read approximately 0.36 VDC. the probes connected together. The digital meter
• If any one of the readings is not correct, then must be placed on the diode check scale. In this
the IGBT module and gate driver board must be test, we are not looking for exact resistance mea-
replaced. surements, but rather to verify if the semi-conduc-
tor switches are open or shorted.
• The details of this procedure are for the SCR/Di-
Verify Failure of the LCD SCR/Diode ode module used for system #1. All SCR/Diode
Module modules are tested in the same manner.

General Information: Test Procedure:


• Place the positive probe of the meter at the
Personnel not familiar with AC drives,
connection of the input line voltage and the
and proper electrical safety procedures
SCR/Diode module the wire is marked 4L1.
should not be working on this product.
Place the negative probe on the bus bar to the
right of the assembly. This is the positive bus.
The analog meter reading will be near full scale
to the left of the meter movement. The digital
• Follow drive discharge procedure at the beginning meter reading will be OL. The 2 readings will
of this section. take several seconds to stabilize. Ref. to FIGS.
• It is not necessary to remove any wiring to perform 8 and 9.
this test.

ANALOG METER READING NEGATIVE PROBE CONNECTED


FULL SCALE TO POSITIVE BUS

POSITIVE PROBE
CONNECTED TO
INPUT WIRE 412

50052

FIG. 8 – SCR / DIODE MODULE VERIFICATION #1

32 JOHNSON CONTROLS
FORM 201.21-M1 (307)

• Reverse the position of the 2 probes. The ana- • Repeat this test for the other 2 input wire 4L2,
log meter reading will be near full scale to the and 4L3. The results should be the same as the
left of the meter movement. The digital meter above test.
reading will be OL. The 2 readings will take • If a test for a SCR or diode fails, then that
several seconds to stabilize. SCR/diode module will need to be replaced.
• Repeat this test for the other 2 input wire 4L2,
and 4L3. The results should be the same as the
above test. Replacement of the LCD IGBT Module
• Place the positive probe of the meter at the The following step by step procedure includes several
connection of the input line voltage and the helpful hints which should make the process easier, and
SCR/Diode module the wire is marked 4L1. minimize the possibility of damage to other components
Place the negative probe on the bus bar to the or to the LCD.
left of the assembly. This is the negative bus. An Save all of the packing material. This material is to be
analog meter reading will read approximately re-used when returning a defective power module as
5-10 ohms. A digital meter reading will read ap- required for warranty.
proximately 0.36 VDC. Ref. to FIGS. 10 and 11.
• Reverse the position of the 2 probes. The ana- Personnel not familiar with AC drives,
log meter reading will be near full scale to the and proper electrical safety procedures
left of the meter movement. The digital meter should not be working on this product.
reading will be OL. The 2 readings will take
several seconds to stabilize.

POSITIVE PROBE CONNECTED NEGATIVE PROBE CONNECTED


TO INPUT WIRE 4L2 TO POSITIVE BUS

DIGITAL METER
READING
OVERLOAD

50053
FIG. 9 – SCR / DIODE MODULE VERIFICATION #2

JOHNSON CONTROLS 33
FORM 201.21-M1 (307)

NEGATIVE PROBE CONNECTED POSITIVE PROBE CONNECTED


TO INPUT WIRE 4L3 TO POSITIVE BUS

ANALOG METER
READING
10 OHMS

50054

FIG. 10 – SCR / DIODE MODULE VERIFICATION #3

POSITIVE PROBE CONNECTED NEGATIVE PROBE CONNECTED


TO NEGATIVE BUS TO INPUT WIRE 4L2

DIGITAL METER
READING
0.38 VDC

50055

FIG. 11 – SCR / DIODE MODULE VERIFICATION #4

34 JOHNSON CONTROLS
FORM 201.21-M1 (307)

• Follow drive discharge procedure at the beginning


of this section.
• Remove the 18-pin connector on the IGBT Gate
Driver Board.
• Remove and discard the 6 screws from the IGBT
module at the motor output connector tangs, and
the remaining 6 screws from the bus connections.
Keep the 3 capacitors which will be reused.
• Remove the bolt holding the power wire to the
output power tangs.
• Remove and discard the 8 screws holding the TORQUE TO 48 IN.LBS (5.5 Nm) ± 10%

IGBT module in place. SCREWS TO BE TORQUED IN SEQUENCE


1, 2, 3, 4, 5, 6, 7, 8 LD10605
• Carefully remove the IGBT power module by
FIG. 12 – IGBT MODULE TORQUE SEQUENCE
sliding it away from the bus structure while lift-
ing slightly. DO NOT place any stress on the bus
structure. Replacement of the LCD SCR/Diode
• Wipe the chill plate clean with a clean soft cloth. Module
DO NOT leave lint or any materials on the chill The following step by step procedure includes several
plate. DO NOT clean using compressed air. Rub- helpful hints which should make the process easier, and
bing alcohol works well to remove the thermal minimize the possibility of damage to other components
grease from the chill plate. or to the LCD. Save all hardware, as it will be reused.
• Apply a thin and even coat of thermal grease on
to the back side of the IGBT module. The thermal Personnel not familiar with AC drives,
grease should be provided in the service kit. The and proper electrical safety procedures
use of too much grease may cause IGBT failure. should not be working on this product.
• Place the new IGBT module on the chill plate so
that the connector is towards the right of the LCD
enclosure. Carefully slide the IGBT module power
connections under the bus structure. • Follow drive discharge procedure at the begin-
ning of this section.
• Insert the 8 screws through the new IGBT module
and engage a few threads in the chill plate, but DO • Remove the bolt holding the input power wire
NOT tighten. The new IGBT module should still to the copper tang.
be loose. • Remove the bolt holding the power tang to the
• Align the IGBT module so that 6 screws can be SCR/diode module.
installed through the 3 square capacitors, then bus • Remove the 6 bolts between the 3 SCR/diode
structure and into the IGBT module. DO NOT modules and the bus bars. Note the position of
tighten these screws. the bus bars.

• Tighten the IGBT mounting screws to 48 in.-lbs. (5.5 • Remove hardware supporting the bus bars, and
Nm) ± 10% in the sequence shown in FIG. 12. disconnect the bus bars from the bus structure
on the left and right of the assembly.
• Install the 3 power wire connectors tangs using 6
screws, and torque the screws to 48 in.-lbs. (5.5 • Remove the four Allen head mounting bolts
Nm) ± 10%. Install the output power wire to the from the failed SCR/diode module.
copper power tangs using the nut that was saved. • Gently remove the gate wires from the SCR/di-
Torque the bolt to 40-50 in-lbs. ode module. Note locate of the gate wires.
• The screws at the bus structure need to be tighten • Wipe the chill plate clean with a clean soft
to 48 in.-lbs. (5.5 Nm) ± 10%. cloth. DO NOT leave lint or any materials on
• Install the 18 pin connector on the IGBT Gate the chill plate. DO NOT clean using compressed
Driver Board. air. Rubbing alcohol works well to remove the
thermal grease from the chill plate.
JOHNSON CONTROLS 35
FORM 201.21-M1 (307)

• Apply a thin even coat of thermal grease on to the Replacement of the LCD Logic Board
back side of the SCR/diode module. The thermal The LCD logic board is shipped without software
grease should be provided in the service kit. The installed and with the RLA values set to minimum. If
use of too much grease may cause the SCR/diode the failure of the logic board is related to the power
module to fail. supplies on the logic board, then it is recommended that
• Gently install the gate wires onto the SCR/diode the software be replaced.
module. Ensure that these connections are tight. • Before the logic board is removed from the
The white wire is installed toward the center of drive write down the programmed RLA for
the module. Refer to FIG. 13. each compressor.
• Place the new SCR/diode module on the chill plate • Follow drive discharge procedure at the begin-
install the 4 Allen head screws. Do not tighten the ning of this section.
screws at this time. • Remove the existing logic board from the
• Reinstall the bus bars. Be sure that the bolt holes LCD.
are aligned with the new SCR/diode module.
• Install the new logic board.
• Tighten the SCR/diode mounting screws to 48
• Ensure that all connectors are installed including
in.-lbs. (5.5 Nm) ± 10% in the sequence shown
the J5 connector.
in FIG. 13.
• Install the 2 EPROM’s and the PROM into the
• Tighten the all bus bar bolts to 88 in.-lbs. (10 Nm)
logic board.
± 10%.
• Rotate the FLA pots to their full counter
• Install the copper power tang to the SCR/diode
clockwise position. The pots will start to click
module tighten the bolt to 88 in.-lbs. (10 Nm) ±
when they hit the end stop. Close the enclosure
10%.
door and apply power to the chiller, and note
• Install the input power wire to the copper power the value of the RLA.
tang using the nut that was saved. Torque the bolt
to 88 in.-lbs. (10 Nm) ± 10%. • Remove power from the chiller. Rotate the FLA
pots to their full clockwise position. The pots
will start to click when they hit the end stop.
Close the enclosure door and apply power to
the chiller, and note the value of the RLA.
• Subtract the 2 values and divide the different by 25.
For example: The first reading was 45 amps.
The second reading was 300 amps.
(300-45)/25 = 10.2. or for every turn of the
FLA pot the RLA value will increase by 10.2
amps.
• Remove power from the chiller.
• Rotate the FLA pots to their full counter
clockwise position.
• Take the compressor RLA rating, then subtract 45
LD10606 and divide by the amps per turn value from above.
FIG. 13 – ISCR / DIODE MODULE TORQUE
This answer is the number of the turns clockwise
SEQUENCE on the FLA pot for the compressor RLA rating.
For example: The compressor rating is 250 amps.
(250-45)/10.2 = 20.1 turns on the FLA pot.
• Adjust the pots per the previous step.

36 JOHNSON CONTROLS
FORM 201.21-M1 (307)

• Close the enclosure door and apply power to these fine adjustments to the FLA pot with
the chiller, and note the value of the RLA. power removed, and then close the enclosure
• Remove power from the chiller. If the door and apply power to the chiller. At no time
programmed RLA is lower then the required should the door of the LCD enclosure door be
value, then the FLA pot will need to be adjusted opened when power is applied.
clockwise. If the programmed RLA is higher
then the required value, then the FLA pot will
need to be adjusted counter clockwise. Make

Software Reference List 50 Hz and 60 Hz


Location Part Number
LCD Logic Board U36 031-02521-001
LCD Logic Board U39 031-02522-001
LCD Logic Board U41 031-02523-001

JOHNSON CONTROLS 37
FORM 201.21-M1 (307)

NOTES

38 JOHNSON CONTROLS
FORM 201.21-M1 (307)

NOTES

JOHNSON CONTROLS 39
P.O. Box 1592, York, Pennsylvania USA 17405-1592 Tele. 800-861-1001 Subject to change without notice. Printed in USA
Copyright © by Johnson Controls 2007 www.york.com ALL RIGHTS RESERVED
Form 201.21-M1 (307)
Supersedes: 201.21-M1 (305)

Potrebbero piacerti anche