Page Features
8DH10 switchgear is a factory- Quality and environment
Application, Requirements assembled, type-tested, three-pole, Quality and environmental
Features, typical uses 2 and 3 metal-enclosed, metal-clad single- management system acc. to
busbar switchgear for in-door in- DIN EN ISO 9001 and
Technical Data stallation: DIN EN ISO 14001
Electrical data, filling pressure, • Up to 24 kV
temperature 4 and 5 Personal safety
• Feeder currents up to 630 A
Switchgear installation, shipping data 6 and 7
• Busbar currents up to 1250 A • Safe-to-touch and hermetically
Product Range sealed primary enclosure
Product range overview 8 to 15 Typical uses • HV HRC fuses and cable sealing
8DH10 switchgear is used – even ends are only accessible when
Design outgoing feeders are earthed
under severe environmental con-
Panel design 16 and 17 ditions – for power distribution in • Operation only possible when
Components secondary distribution systems, enclosure is closed
such as • Logical mechanical interlocking
3AH vacuum circuit-breaker 18 and 19
Substations, customer transfer • Capacitive voltage detecting sys-
Three-position switch-disconnector 20
substations, distribution sub- tem to verify safe isolation from
Busbars 21 stations and switching substa-
Transformers 22 to 27 supply
tions of power supply and
Cable connection 28 public utilities • Feeder earthing by means of
Low-voltage equipment 29 make-proof earthing switches
Industrial plants, such as:
Dimensions • Wind power stations Security of operation
Individual panels, panel blocks 30 to 34 • High-rise buildings • Hermetically sealed primary
Metering panel combinations 33 and 35 • Airports enclosure independent of
Floor openings and fixing points 36 to 39 environmental effects (such as
• Lignite open-cast mines pollution, humidity and small ani-
Cable connection examples 40
• Underground railway stations mals) – sealed for life:
Standards, Transport, Notes – Welded switchgear vessel
• Sewage treatment plants
Standards, specifications, guidelines 41 – Welded-in bushings and operating
• Port facilities mechanism
Transport data, classification 42
Notes 43 • Traction power supply systems • Operating mechanism parts
• Automobile industry maintenance-free
For further information, please refer to (IEC 60 694 / VDE 0670-1000)
• Petroleum industry
• Catalog HA 40.1: (Switchgear Type 8DJ and 8DH, • Operating mechanisms of switch-
General Part) • Chemical industry ing devices located outside the
• Supplements to Catalogs HA 45.31/41.11 • Cement industry switchgear vessel (primary enclo-
sure)
• Unit-type heating power stations
Invalid: Catalog HA 41.11 · 2006 • Switchgear interlocking system
• Textile, paper and food
with logical mechanical interlocks
industry
• Mechanical switch-position
• Emergency power supply
indicators integrated in the
installations
mimic diagram
Modular design
Cost-efficiency
• Individual panels and panel
Extremely low “life-cycle costs”
blocks can be freely combined
throughout the entire product
and extended – without gas work
service life as a result of:
on site
• Maintenance-free concept
• Low-voltage compartments can
be supplied in two overall heights • Climatic independence
and are wired to the panel by • Minimum space requirements
means of plug-in connections
• Maximum availability
Reliability
Security of investment
• Type and routine-tested
Innovative developments, such as:
The products and systems described in this catalog are • Standardized and manufactured
manufactured and sold according to certified quality using numerically controlled • Modular design
and enviromental management system (acc. ISO 9001 machines • Switchgear extension without gas
and ISO 14001). • More than 430,000 8DJ/ 8DH work on site
(DQS Certificate Reg. No. DQS 003473 QM UM). panels in operation worldwide • Maintenance-free 3AH vacuum
The certificate is accepted in all IQNet countries. for many years circuit-breaker
• SIPROTEC protection device family
© Siemens AG 2007
Application
Typical uses
Technology
• Maintenance-free
• Climate-independent
• Partition class: Class PM
(metallic partition)
• Three-pole primary enclosure,
metal-enclosed
• Insulating gas SF6
R-HA41-013a eps
• Welded switchgear vessel without
seals, made of stainless steel,
with welded-in bushings for elec-
trical connections and mechanical
components
• Three-position switch-discon-
nector with load-break and
make-proof earthing function
• Cable connection for bushings
with outside cone
• Connection with cable plugs
– In ring-main feeders and
circuit-breaker feeders with
bolted contact (M16) Example
– In transformer feeders with Customer transfer switchgear
plug-in contact
• Option: Connection with conven-
tional cable sealing ends
– For thermoplastic-insulated
cables via elbow adapter
AKE 20 / 630 (make Siemens)
– For paper-insulated mass-
impregnated cables via commer-
cially available adapter systems
• Easy installation
• Option: Pressure absorber system
– Maintenance-free
– For rated short-time withstand
current Ik £ 20 kA
– For single and multi-panel
combinations of 700 mm to
2000 mm width (for panel type
ME1 with max. 1 adjacent panel)
– With 300 mm high pressure ab-
sorber duct below the switchgear
and
– With 115 mm deep pressure
absorber duct for pressure relief
upwards
– With screwed-on cable
compartment cover
– Possible for switchgear with stand-
R-HA41-015 eps
building)
For further information concerning
the pressure absorber system,
please refer to page 39
and to Catalog HA 40.1
Standards Application
See page 41 Power supply of high-rise buildings
Technical Data
Electrical data
Panel data
Ring-main panel Rated normal current Ir 2) for feeder (for panel types RK ... and K ...) A 400, 630 400, 630 400, 630 400, 630 400, 630
type RK, for bus sectionalizer panel type LT2 A 400, 630 400, 630 400, 630 400, 630 400, 630
bus sectionalizer
Rated short-time for switchgear with tk = 1 s up to kA 20 25 20 25 20 25 20 25 20
panel type LT2,
withstand current Ik for switchgear with tk = 3 s (option) up to kA – – 20 – 20 – 20 – 20
cable panel
type K Rated peak withstand current Ip up to kA 50 63 50 63 50 63 50 63 50
Rated short-circuit making current Ima up to kA 50 63 50 63 50 63 50 63 50
Transformer Rated normal current Ir 2) for feeder 6) A 200 200 200 200 200
panel type TR Rated short-time for switchgear with tk = 1 s up to kA 20 25 20 25 20 25 20 25 20
withstand current Ik for switchgear with tk = 3 s up to kA – – 20 – 20 – 20 – 20
Rated peak withstand current Ip 6) up to kA 50 63 50 63 50 63 50 63 50
Rated short-circuit making current Ima 6) up to kA 25 25 25 25 25 25 25 25 25
Reference dimension “e“ of the HV HRC fuse links mm 292 7) 292 442 442 442
Circuit-breaker Rated normal current Ir 2) for feeder (for panel types LS ...) A 400, 630 400, 630 400, 630 400, 630 400, 630
panel type LS, for bus sectionalizer panel type LT1 A 400, 630 400, 630 400, 630 400, 630 400, 630
bus sectionalizer
Rated short-time for switchgear with tk = 1 s up to kA 20 25 20 25 20 25 20 25 20
type LK/LT1
withstand current Ik for switchgear with tk = 3 s up to kA – – 20 – 20 – 20 – 20
Rated peak withstand current Ip up to kA 50 63 50 63 50 63 50 63 50
Rated short-circuit making current Ima up to kA 50 63 50 63 50 63 50 63 50
Rated short-circuit breaking current Isc 8) up to kA 20 25 20 25 20 25 20 25 20
Electrical service life of at rated normal current 10 000 operating cycles
3AH vacuum circuit-breakers at rated short-circuit breaking current 50 breaking operations
*) Not for billing metering 2) The rated normal currents apply 6) Depending on the HV HRC fuse link,
panels type ME1 to ambient air temperatures of observe the max. let-through
1) According to some national require- max. 40 °C. The 24-hour mean current of the HV HRC fuse links
ments, higher values of the rated value is max. 35 °C (according to 7) Extension tube (150 mm long)
short-duration power-frequency IEC 60 694 / VDE 0670-1000) required additionally for fuse
withstand voltage available for 3) Operating conditions according to mounting 442 mm
Ik = 20 kA with: IEC 62 271-200. 8) For the 3AH vacuum circuit-breaker
- 42 kV for phase-to-phase, For application, see also pages
phase-to-earth and open contact 2 and 41 (climate and ambient
gap as well as conditions)
- 48 kV across the isolating distance 4) Temperature range, reduced
Higher values of the rated lighting normal currents at ambient air
impulse withstand voltage temperatures > +40 °C
(for IK = 20 kA) :
- 95 kV for phase-to-phase, 5) Classification according to
phase-to-earth and open contact IEC 62 271-200 (see also page 42)
gap as well as
- 110 kV across the isolating
distance
Technical Data
Electrical data
Panel data
Busbar earthing Rated short-time for switchgear with tk = 1 s up to kA 20 25 20 25 20 25 20 25 20
panel withstand current Ik for switchgear with tk = 3 s (option) up to kA – – 20 – 20 – 20 – 20
type SE,
Rated peak withstand current Ip up to kA 50 63 50 63 50 63 50 63 50
busbar voltage
metering panel Rated short-circuit making current Ima up to kA 50 63 50 63 50 63 50 63 50
type MS1V/ME3
Billing metering Rated normal current Ir 2) for transfer up to A 630 630 630 630 630
panels for feeder (T with cable panel as type ME1-K) up to A 630 630 630 630 630
types ME1
for busbar metering up to A 630 630 630 630 630
and ME2
Rated short-time for switchgear with tk = 1 s up to kA – 25 20 25 20 25 20 25 20
withstand current Ik for switchgear with tk = 3 s up to kA 20 – 20 – 20 – 20 – 20
Rated peak withstand current Ip up to kA 50 63 50 63 50 63 50 63 50
Technical Data
Switchgear installation
Room planning
Switchgear installation with Switchgear installation with rear-side
Switchgear installation standard panels pressure absorber duct (option)
Wall-standing arrangement
– Single row
Switchgear room Switchgear room
– Double row (for face-to-face * 23
arrangement) 22 2 22
³2400**
Option: Free-standing *** ³1000
arrangement 3 13
³1000
For room planning and 4 15
switchgear installation, please
note: 890
³2400**
5
775 ³1000
– Floor openings: Dimensions
2300*
828
2000
300
Room dimensions see opposite
dimension drawings
10 115 ~200
>600
Door dimensions 11 17
1
12 834
The door dimensions depend
Cable basement 13 Cable basement
on the
– Number of panels in a
Side view 14 Side view
transport unit
– Design with or without ³15 18 ³15
low-voltage compartment
Switchgear fastening
³50
10
Weight
20
For details, please refer to page 7.
21
HA41-2286g eps
³50
HA41-2287h eps
10
Technical Data
Shipping data
Individual panel, panel block Type Panel or panel combination Transport unit (including packing) for standard panels (without
or combinations thereof Short iden- pressure absorber system)
for standard switchgear tification B
(without pressure relief duct) Width B1 Net weight 1) Width B2 Height Depth Volume Gross weight 1)
current in mm approx. kg m m T2 m m3 approx. kg
future without / with without /with without /with without /with
LVC */ LVC * LVC */ LVC * LVC */ LVC * LVC */ LVC *
Technical
Product Range
Data
Short identifications *
current in future
Product Range
Ausstattungsmerkmale
Equipment features
x /
• Basic equipment bo n ED C )
) si m a tio LOS aker + 2N PEN nd
Additional equipment B n ic r C re O O ) a
° (option), further additional ker
B
ech
a
) s ) ic e
in
d
n
to -b N
ec cuit N: 2 D
d
an ch
it
B
r
a m * B
ice rv on cir PE SE w ke
equipment on request ) re B
h
B
it-b t
g
in ox * n d d ev r-se disc NC; D/O C LO on s rea
– Not available itc rcu on er
a b t ) a g fo ch- + 2 SE ) (f
. iti ) t-b
sw ci en B in y- t O BB os itc
h B
B
B
)
ui
n n ed op ism tm ch tch ead Swi NO CL -p w d B irc se
o o w e n r it i r d e s n d c
iti iti th cha pa sw r sw cal BB : N: 2 ING ) an thre
)
re g ) a n um le
a
os os /sc ov
e e m i H B in B
B
) a
cu d re
e -p e-p a ce b m l co ition g. fo ectr ) and OPE RT c h ee n
a rth tch h a e
r pl a g / i c v
hr
e
hr
e ve p. atin in
a s e. e el B ED , EA it w e
sw swi or
t at
r t or t t co d in po r( t h S C sw bet of ) AH er
fo f n e com per term ree- ato mo itc CLO 2N o s.
e l -p ro BB
tion on c at or 3 r op )
ck al o c w p e d i i i f
ism ism tm
e as r th ndi rr
e s
n G O
+ e- pan ak ) an -po
s it d e *
lo in he he fo ce i ) fo sitio HIN 2N re os lt in ism orm nt *
h an han par ver e rm in t ic e i T : f. th ker r r m B
h e e e -p u a n sf e
n s O o a e o r a ps nt
ec ec m co et st al
s e ea -ser 1 N
v
-p AR EN n. re ak t f itc th e
hr th-
f h
ec -tra part r
n m
m m e co nt ck he a in ltag rel r ( ree C, E /OP c ha it-b bre -ou sw for or t r m t la m e
g g l e a o - a n e m
in in b m br nic rm vo nt y-
f h h
tc or t 2N SED
e cu uit lock tion out ce f or e ting rre om cov le c uip
rat r at r ca art le te - u d i t. m ir c i - i c b
e e o p b e e w sh a sw ch f O + CLO ra c
n cir ing pos ock dev cuit ra s cu ge age ca ry e
q
op op ck f m ca ltag ltag te lo as n. re ng it N pe ki - l pe a ta t d
ual ual lo co l as v o v o ra se a lli s w : 2 LST r -o loc uum arth ree ing in g
t-cir r o se v ol v ol nte nda
r e i - - a h a x. EN pe o r -e th los ock hor o a - -
an an nte bl ra w ow epa ele ec gn ot nte vac ot ele w ow ou eco
M M I Ca C- Lo L S R M Si Au OP ty M I De of C L S M R Lo L M S
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
• – • – • • – – – • – – – –
• – • – • • – – – •
° ° ° – –
° ° ° – –
° ° ° °
• – • – • • – – – •
° ° ° – –
° ° ° – –
° ° ° °
• – • – – • – – – •
° ° ° – –
° ° °
– – –
° ° –
° °
• – • – – • – – – •
° ° ° – –
° ° – – –
° ° –
°
• – • – – • – – – •
° ° ° – –
° ° – –
° ° –
°
– – – • • • – – – •
° °
–
°
– – –
°
–
°
–
° – –
° ° °
– – – • – • – – – •
° – – – – – –
°
– – –
° ° °– °
• – • – • • – – – •
° – – – – – –
° ° °
• – • – – • – – – •
° ° – – – –
° °
– – –
° ° °– °
• – • – • – • – •
° ° – –
° – – –
° ° °
• – • – – – • –
° •
° ° ° –
° –
° – – –
° ° °– °
• – • – • – • –
° •
° ° ° –
° –
° – – –
° ° °
• – • – – – • –
° •
° ° ° –
° –
° – – –
° ° °– °
• – • – • – – –
° •
° ° ° °
–
° °• °
–
°
• – • – – – – –
° •
° ° ° ° –
° ° –
° ° ° • –
°– °
• – • – • – – –
° •
° ° ° ° –
° ° ° ° –
°
• – • – – – – –
° •
° ° ° ° –
° ° °– ° ° •• –
°– °
– – –
° ° °• ° °
–
° ° ° ° °
•
•
–
•
– •
•
–
•
–
•
– –
° •
•
° ° °
–
°– °• °– – ° ° –
° °– °
• – – • – – – –
° •
° ° ° ° – – • –
° ° •• – –
°
• – – • – • – –
°
– •
° ° ° °
– – – • –
°
–
°
– –
°
• – • – – • – – – •
° ° °
– – – – • – – –
° ° –
°
• – • – – • – – – •
° ° – – – – • – – –
° ° –
°
• – – • – • – – – •
° ° – – – – – –
° ° –
°
° ° ° ° ° ° °
– – – – – – – – – – – – – – – – – –
– – –
•
• • – –
•
• – – – – – – – – – – – –
° ° – °
– – – • – – – • – – – – – – – – – – – –
° ° –° °
– – – • • – – • – – – – – – – – – – – –
° ° °
– – – • – – – – – – – – – – – – – – – –
° ° –° °
° ° °
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
– – – – – 1) – – – – –
• • • • •1)
• – • – • • – – – •1)
° 1)
° ° – – –
° ° – –
° ° ° °
• – • – • – – – •1)
° 1)
° ° – –
° °
– – –
° ° ° °
• – • – • – – –
° •1)
° 1)
° ° –
° –
° – – –
° ° ° °
• – • – • • – –
°
– •1)
° 1)
° ° –
°
–
° – –
° ° ° °
• – • – • – – 1)
°
1)
° ° –
°– ° °
– – –
° ° ° °
• – • – • •
2)
– –
°
– •1) 1)
° ° –
°
–
° – –
° ° ° °
• – • – • – – 1)
°
1)
° ° –
°– ° °
– – –
° ° ° °
• – • – • •
2)
– –
°
– •1) 1)
° ° –
°
–
° – –
° ° ° °
• – • – • – – 1)
°
1)
° ° –
°– ° °
– – –
° ° ° °
– – – • • •
2)
– –
°
– • 1) 1)
°
–
°
– –
°
– –
°
– – –
° ° ° °
– – – – –
°
1) – –
° ° ° ° °
° – – –
• • 2)
• – • – • • – –
°
–
1)
•1)
° °
– –
°
– – – –
° ° ° °
• – • – • 2) – – 1)
°
1)
1)
° – –
° –° – –
° ° ° °
° ° ° ° ° ° ° ° °
Siemens HA 41.11 · 2007 9
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Product Range
HA41-2218_1d eps
HA41-2223_1d eps
Type RK1 1) 3)
500 mm wide HV HRC fuse
**
option Type RK * option Type K * option Type TR1-V B
350 mm wide 350 mm wide 500 mm wide Cable-type current
HA41-2214_1e eps
HA41-2219_1e eps
HA41-2224_1d eps
for 2nd cable* for 2nd cable * with plug-in transformer
voltage trans-
formers
HA41-2220_1d eps
HA41-2225_1d eps
(105 mm deeper
with plug-in with plug-in
cable compart-
surge surge
ment cover) Cable (not
arresters * arresters *
with plug-in included in the
voltage trans- scope of supply)
formers in-
option option stead of cable
connection
2nd cable (not
included in the
scope of supply)
HA41-2226_1d eps
HA41-2278e eps
Make-proof
earthing switch
Option:
Type RK1-U 3)
Type RK1V-U 2) 3)
500 mm wide
Option:
Type RK1-U 3)
Type RK1V-U 2) 3)
500 mm wide
Footnotes
see page 11
Product Range
HA41-2232_1d eps
700 mm wide 700 mm wide
consisting of consisting of
2 ring-main panels 1 ring-main panel and
1 transformer panel HV HRC fuse
Capacitive
voltage detecting
system
BB Capacitive voltage
RK RK RK RK RK TR c detecting system at
Type R-B3 Type 2RT-B3
HA41-2233_1c eps
HA41-2229_1c eps
HA41-2278e eps
Cable (not
included in the
scope of supply)
RK RK RK TR c
Type 3RT-B4
HA41-2234_1c eps
Footnotes
from page 10
B Deep cable
Cable connection/transformer panel block compartment
cover required
Designs and options for each panel, see page 10
* Depending on
TR TR TR K TR c the make/type of
Type T-B3 Type KT-B2 the cable
HA41-2235_1e eps
HA41-2231_1c eps
Product Range
HA41-2238_1e eps
HA41-2244_1e eps
HA41-2242_1e eps
Three-position
option option option option switch-disconnector
1) 1) 1) 1)
2)
option option option option
HA41-2239_1d eps
HA41-2245_1d eps
HA41-2243 _1d eps
HA41-2237_1d eps
Cable-type current
transformer
on the cable
option option option option
1) 1) 1) 1)
Plug-in
surge arrester
or limiter
HA41-2247_1d eps
Footnotes
see page 13
Product Range
Bus sectionalizer with circuit-breaker, bus sectionalizer with switch-disconnector, busbar earthing panels and
busbar voltage metering panel as individual panels DD
HA41-2252_1b eps
HA41-2254_1c eps
HA41-2248_1c eps
Three-position
option switch-disconnector
Capacitive
voltage detec-
ting system
option
HA41-2249_1e eps
Make-proof
earthing switch
option
4MT8 plug-in
voltage
transformer
at the connection
HA41-2278e eps
Type LK V/LT1-V Type SE1 V/SE2
500 mm wide 4MT3 plug-in
500 mm wide
voltage
with vacuum with plug-in transformer
circuit-breaker and voltage at the busbar
plug-in voltage transformers
transformers
Bus sectionalizer
with switch-disconnector
option
HA41-2250_1c eps
Footnotes from
page 12 and 13
option B Deep cable
compartment
cover required
BB Short identi-
fications of the
panels have
been harmo-
nized
Type LT2 * Depending on
500 mm wide the make/type of
the cable
plug or arrester:
Deep cable
compartment
cover required
** Cable-type
current trans-
former on the
2nd cable:
For 300 mm
deeper cable
compartment
Product Range
Billing metering panels Billing metering panels as end Billing metering panels for
(standard) panels, for cable connection busbar connection
Current trans-
former, cast-resin
option option option insulated
P1 P2
HA41-2262_1b eps
HA41-2258_1c eps
HA41-2266_1c eps
1)
P2 P2 Voltage transformer,
cast-resin insulated
1)
P1 P1 or on request:
Voltage transformer,
cast-resin insulated,
with HV HRC fuse
Scheme 1 Scheme 1 Scheme 1
Type ME1, 850 mm wide Type ME1-K, 850 mm wide Type ME1-S, 850 mm wide
Voltage trans-
for transfer to the right for transfer to the right for busbar metering former, cast-resin
insulated
HA41-2263_1b eps
HA41-2267_1c eps
Fixed earthing
points for busbar
1)
earthing
HA41-2278d eps
P2 P2
P1 P1
Cable (not
included in the
scope of supply)
Scheme 2 Scheme 2 Scheme 2
Type ME1, 850 mm wide Type ME1-K, 850 mm wide Type ME1-S, 850 mm wide P1 and P2
are terminal
for transfer to the right, for transfer to the right, for busbar metering, designations
transformer terminals transformer terminals transformer terminals of the current
interchanged interchanged interchanged transformer
option option option P2 P1
HA41-2436_1a eps
HA41-2264_1b eps
HA41-2260_1c eps
1)
P1 P1
P2 P2
Type ME1, 850 mm wide Type ME1-K, 850 mm wide Type ME1-S, 850 mm wide
for transfer to the right for transfer to the right for busbar metering,
transformer terminals
interchanged
option option option P2 P1
HA41-2261_1c eps
HA41-2437_1a eps
HA41-2265_1b eps
P1 P1
1)
P2 P2
Type ME1, 850 mm wide Type ME1-K, 850 mm wide Type ME1-S, 850 mm wide
for transfer to the right, for transfer to the right, for busbar metering,
transformer terminals transformer terminals transformer terminals
interchanged interchanged interchanged
Note Note
Schemes 1 to 4 also feasible Schemes 1 to 4 also feasible
for transfer to the left for transfer to the left
Product Range
Billing metering panels as end Billing metering panels Billing metering panels *
panels, for cable connection as individual panels, for cable with metal-enclosed
connection combined transformers Current trans-
former, cast-resin
option option insulated
HA41-2276_1d eps
P1 P2
HA41-2473a eps
HA41-2268_1e eps
1)
2) Voltage transformer,
P2 P2 cast-resin insulated
3) or on request:
P1 P1
1) 1)
Voltage transformer,
cast-resin insulated,
with HV HRC fuses
Scheme 1 Scheme 1 Scheme 1
Type ME1-KS, 850 mm wide Type ME1-KK, 850 mm wide Type ME2, 600 mm wide 4MK plug-in
for transfer to the right for cable connection for transfer to the right combined current
transformer,
metal-enclosed
3)
HA41-2277_1d eps
option option P1 P2
HA41-2474a eps
HA41-2269_1e eps
2) 4MK plug-in
1) 1)
combined voltage
3) transformer,
P2 P2
metal-enclosed
P1 P1
Fixed earthing
Scheme 2 Scheme 2 Scheme 2 points for busbar
earthing
HA41-2278e eps
Type ME1-KS, 850 mm wide Type ME1-KK, 850 mm wide Type ME2, 600 mm wide
for transfer to the right, for cable connection, for transfer to the right,
transformer terminals transformer terminals transformer terminals
interchanged interchanged interchanged Cable (not
included in the
HA41-2438_1b eps
HA41-2475a eps
2) P1 and P2
1) 1)
are terminal
3) designations
P1 P1
of the current
P2 P2 transformer
Type ME1-KS, 850 mm wide Type ME1-KK, 850 mm wide Type ME2, 600 mm wide
for transfer to the right for cable connection for transfer to the left
HA41-2439_1b eps
option option P2 P1
HA41-2271_1e eps
HA41-2476a eps
2)
P1 P1
3)
P2 P2
1) 1)
Type ME1-KS, 850 mm wide Type ME1-KK, 850 mm wide Type ME2, 600 mm wide
for transfer to the right, for cable connection, for transfer to the left,
transformer terminals transformer terminals transformer terminals
interchanged interchanged interchanged
Design
HA41-2280d eps
61 1 61
1
2 62
31
2 32
62 34
33
3 23 3
11 11
4 38 23
12 12
5 24 5 35
13 13
6 6
14 14
7 15 7 15
15 15
8
9 25 9 36
16 16
17 17 37
26
18 18
10 27 10 27
19 28 19 28
20 20
29 29
21 21
22 22
Type RK Type TR
40 7 Mimic diagram
11 62 8 Option: Short-circuit / earth-fault indicator
9 Sockets for voltage detecting system
39
39
10 Arrangement of the busbars
6 11 Feeder designation label
12 Option: Locking device for three-position
41 switch-disconnector
7 62 42 13 Manual operation for the mechanism of
the earthing function
14 Manual operation for the mechanism of
the load-break function
15 Interlock of the cable compartment cover
16 Arrangement of the cable connections
17 Busbar system
22
18 Switchgear vessel filled with gas
30
19 Busbar connection
Type ME1 20 Pressure relief device
Design
Vacuum circuit-breaker:
45 Opening for the hand crank
– for closing with manual operating mechanism
– for emergency operation with motor operating
mechanism
46 Operating mechanism box
47 Mechanical “ON” pushbutton (not supplied with
61 spring-operated mechanism)
48 Mechanical “OFF” pushbutton
56 49 Operating cycle counter
50 “Spring charged” indicator
57
51 Vacuum interrupter
52 Switch-position indicator
Components
Components
Anti-pumping (standard)
(mechanical and electrical) Hand crank opening is blocked
– Stored-energy mechanism with
• Function: If constant CLOSE and closing solenoid (Y9 *) and
OPEN commands are present at Maximum equipment with motor operating stored-energy mechanism
pushbutton (S12 *): The push-
the vacuum circuit-breaker at button (S12 *) operated by the
the same time, the vacuum cir- mechanical interlock prevents a Secondary equipment (view into the operating mechanism box)
cuit-breaker will return to the continuous command to the 1 Gear 11 Circuit-breaker “OPEN”
open position after closing. It closing solenoid 2 Position switch (S4 *) 12 Option: 2nd release
remains in this position until a
• During operation of the three- 3 Closing spring 13 1st release (Y1 *)
new CLOSE command is given.
In this manner, continuous clos- position switch-disconnector 4 Motor (M1 *) 14 Option: Mechanical inter-
ing and opening (= pumping) is from CLOSED to OPEN: locking with interrogation
5 Operating cycle counter
avoided. Vacuum circuit-breaker of the three-position
cannot be closed. 6 “Closing spring charged” indicator switch-disconnector
7 Closing solenoid (Y9 *) 15 Operating rod with contact
1) For utilization * Item Abbreviations: pressure springs
8 Option: Auxiliary switch
by the designation NO = normally-open contact
12 NO+12 NC 16 Interlocking to the three-
customer NC = normally-closed contact
position switch-disconnector
9 Auxiliary switch
For further technical data and description of typical applications, 6 NO+6 NC (S1 *) 17 Actuation for closing the
please refer also to Catalog HG 11.11 “3AH Vacuum Circuit-Breakers” vacuum circuit-breaker
10 Circuit-breaker “CLOSED”
Components
Three-position switch-disconnector
Features
• Switch positions: CLOSED –
OPEN – EARTHED
• Switching functions as
R-HA41-012 eps
general-purpose switch-
disconnector (class E3)
according to
– IEC 60 265-1/ VDE 0670-301
– IEC 62 271-102/ VDE 0671-102
(standards see page 41)
• Designed as a multi-chamber
switch with the functions
– Switch-disconnector and
– Make-proof earthing switch
• Operation via gas-tight welded-in
metal bellows at the front of the
switchgear vessel
Three-position switch-disconnector
EARTHED
HA41-2288a eps
OPEN
SF6 insulation
1 2 3 4 5 6 CLOSED
Components
Busbars
Features
• Safe-to-touch as a result of
use of metal covers
R-HA41-017a eps
• Plug-in type
• Consisting of round-bar
copper, insulated by means of
silicone rubber
• Busbar joints with cross and
end adapters, insulated by 2 8
means of silicone rubber
• Insensitive to pollution and 3
condensation
• Switchgear extension or
panel replacement is possi- 7
ble without gas work
• Special busbar connections
to metering panels type ME1
are possible. Connection to
the
– Cable connection bushings
of the adjacent panel Busbar compartments over 2 panels
with busbar connections, busbar covers removed
or to the
– Busbar bushings
• Busbar arrangement in panel
blocks within the switchgear 7
vessel filled with gas
HA41-2289b eps
8
• Option screened busbar:
– Field control by means of 9
electrically conductive layers
on the silicone-rubber
insulation 1 10
– Installation of 4MC70 32 2
current transformers is thus
possible 3
– Independent of the site 4
altitude
5
• Option: Capacitive voltage
detecting system for the
Top view
busbar, refer also to the
6
product range, pages 10
to 15
Insulated plug-in type busbar
unscreened design
Busbar system
1 End adapter
2 Cross adapter
3 Busbar insulation of silicone rubber
4 Threaded bolt M12 / M16
5 Busbar, Cu, diameter 32 mm
6 Stopper
Switchgear vessel
7 Primary enclosure panel 1
8 Primary enclosure panel 2
9 Bushing
10 Capacitive tap at the bushings,
earthed (standard)
Components
4MT3 * and 4MT8 * plug-in voltage transformers for panel types LS, TR, SE and ME3
Panel section
type LS2-V
R-HA41-019 eps
HA41-2290b eps
R-HA41-018a eps
4MT3 plug-in
voltage
1
transformer
(for the busbar)
R-HA41-020 eps
2
4MT8 plug-in
voltage
transformer
(at the cable
1 4MT3 * for the busbar 4MT8 plug-in voltage transformer connection)
2 4MT8 * at the cable connection mounted on cable T-plug (in panel type LS1-V)
* Disassembly is necessary in order to perform voltage tests on the switchgear on site (max. 80 % Ud)
Components
Panel section
type LS1
R-HA41-021b eps
HA41-2291b eps
R-HA41-022 eps
1
4MC63 three-phase
current transformer
1 4MC63 three-phase 4MC63 three-phase current transformer
current transformer on the bushings of the cable connection
• Arranged outside the switch- Rated peak withstand unlimited Rated peak withstand unlimited
current Idyn current Idyn
gear vessel on the bushings
of the cable connection Secondary data Secondary data
• Mounted at the factory Rated current A 1 0.67 0.5 0.33 Rated current A 1 0.75 0.5
Rating VA 2.5 1.7 1.25 0.8 Rating VA 4 3 2
Other designs
Rated current (option) 5A Rated current (option) 5A
(option)
Current at ID 4.2 A Current at ID 1.575 A
Three-phase current trans-
Protec- Class 10 P Protec- Class 10 P
former for protection equip- tion tion
ment based on the current- Overcurrent factor 10 Overcurrent factor 10
core core
transformer operation principle:
• 7SJ4x protection system
as definite-time overcurrent
protection
• Definite-time overcurrent pro-
tection relay make SEG, type
WIP 1 or type WIC
Components
4MC70 33 and 4MC70 31 cable-type current transformers for panel types LS, RK and TR
R-HA41-025 eps
R-HA41-023a eps
HA41-2292b eps
4MC70 31 cable-type
current transformer
R-HA41-024a eps
4MC70 33 cable-type
current transformers,
4 different overall heights
2 2
1 1
*
Components
4MC70 32 bus-type current transformers for panel type LT (for screened busbars only)
Panel section
type LT1
HA41-2293b eps
R-HA41-026a eps
R-HA41-027 eps
1
4MC70 32 bus-type
1 4MC70 32 bus-type current transformer
current transformer 4MC70 32 bus-type current transformer,
mounted on screened busbars, in some cases
between the panels
Components
4MA7 current transformers and 4MR voltage transformers
for air-insulated billing metering panels type ME1
R-HA41-029a eps
R-HA41-028 eps
4MR14 voltage
1 transformer
R-HA41-030a eps
2
4MA7 current
transformer
1 4MR voltage transformer 4MR voltage transformers and
2 4MA7 current transformer 4MA7 current transformers installed in
billing metering panel type ME1
Technical data
Features 4MA7 single-pole current transformer 4MR single-pole voltage transformer
• Insulation class E
Secondary data
• Secondary connection by Rated voltage 100/ 3 V
means of screw-type 110/ 3 V (option)
terminals 120/ 3 V (option)
Rated voltage for auxiliary 100/3 V
winding (option) 110/3 V (option)
120/3 V (option)
Rating 20 VA 50 VA 100 VA
Class 0.2 0.5 1
Components
4MK * metal-enclosed combined transformers
for billing metering panels type ME2
R-HA41-032 eps
R-HA41-031a eps
1
1 4MK3
Panel section type ME2 combined
voltage
HA41-2295b eps
transformer
2 4MK1
combined
1 current
transformer
2
4MK combined
transformer
1 4MK3 combined voltage 4MK combined transformers installed in
transformer billing metering panel type ME2
2 4MK1 combined current
transformer
Technical data
4MK1 combined current transformer 4MK3 combined voltage transformer
Rating 30 VA 75 VA 150 VA
Class 0.2 0.5 1
Components
Cable connection
Features
Cable connection · Examples
• Bushings with outside cone
• Uniform cable connection L1 L2 L3 L1 L2 L3
Cable connections in
height 575 mm ring-main panels
• With cable bracket, e.g. 1 Prepared for cable
type C40 according to plugs with bolted
contact (M16)
DIN EN 50 024 1 2
2 Phase L1:
• Access to the cable compart- 3
Make Euromold,
ment only if the feeder has 4 type K400 LB as
been isolated and earthed cable elbow plug
3 Phase L2:
Special features Make Euromold,
type K400 TB as
– In ring-main panels cable T-plug
– In circuit-breaker panels
4 Phase L3:
R-HA41-034 eps
R-HA41-033 eps
– In cable panels:
Make Euromold,
• With bolted contact (M16) type AGT 20/630 as
as interface type “C” cable T-plug
according to EN 50181/ Cable compartment, as-delivered Cable plugs with For options A, B, C
DIN EN 50181 condition * bolted contact (M16) and E, see below
• For thermoplastic-
insulated cables L1 L2 L3 L1 L2 L3 Cable connections in
• For paper-insulated circuit-breaker panels
mass-impregnated cables 5 Prepared for cable
with adapter systems plugs with bolted
contact (M16)
• For conventional cable 5 6
sealing ends via elbow 6 Phase L1:
7
Elbow adapter,
adapter AKE 20/630 make Siemens,
8
(make Siemens) type AKE 20/630
• For cable T-plugs or cable 7 Phase L2:
elbow plugs with bolted con- Make Euromold,
tact (M 16) type K400 TB as
cable T-plug
• For connection cross-
8 Phase L3:
R-HA41-035 eps
R-HA41-036 eps
Components
Low-voltage equipment
Low-voltage compartment *
Low-voltage compartment
• Overall height
– Standard 600 mm
– Option 900 mm
• Partitioned safe-to-touch from
the high-voltage part of the 1
panel
• Installation on the panel: 2 3
– Standard for circuit-breaker
panel type LS and bus section-
alizer with switch-disconnector
type LT1
– Option for all other panel 4
R-HA41-041a eps
R-HA41-039a eps
R-HA41-040 eps
7SJ63 1 LEDs
Low-voltage cables
• Control cables of the panel to
the low-voltage compartment
R-HA41-042 eps
Dimensions
600 (900****)
600 (900)*
426***
60
4 4
2000 (2300****)
2000 (2300)*
553
1400
1400
553
312 312
~565
575
HA41-2301e eps
HA41-2298g eps
40
40
600 (900****)
600 (900)*
426***
60
4 4
2000 (2300****)
2000 (2300)*
1
553
2
1400
553
1400
312 312
3
215 110 110
~565
575
HA41-2302e eps
HA41-2299g eps
40
40
60
* Option:
1400
515
312 With low-voltage compartment
** Dependent on the type of
cable plug
215 110 110
~565
Dimensions
HA41-2304c eps
HA41-2305c eps
HA41-2303c eps
4 4
4 4 4
2000 (2300)*
2000 (2300)*
2000 (2300)*
1400
1400
1400
RK RK RK RK RK TR TR
HA41-2307c eps
HA41-2308c eps
4 4
4 4 4
2000 (2300)*
2000 (2300)*
2000 (2300)*
1400
1400
1400
TR TR TR RK TR RK RK TR
HA41-2310c eps
4 4
4 4
2000 (2300)*
2000 (2300)*
Dimensions
Bus sectionalizers with circuit-breakers, bus sectionalizers with switch-disconnectors and
busbar voltage metering panel as individual panels
600 (900****)
600 (900)*
426***
60
1
1
2000 (2300****)
2000 (2300)*
1400
1400
312
1 312
1
215 110 110
HA41-2315e eps
40
40
500 ³15 750
775 500 ³15 750
Bus sectionalizer with
Voltage metering 775
circuit-breaker type LK/LT1
panel type MS1V/ME3
600 (900****)
426***
1
2000 (2300****)
1400
312
1
215 110 110
HA41-2312e eps
40
60
1
2000 (2300)*
1400
312
1 1 Cover screwed on
215 110 110
Dimensions
Busbar earthing panels Billing metering panel ME2 as individual panel and
as individual panels metering panel combin. with billing metering panel
600 (900)*
600 (900)*
339***
60
60
1 1
2000 (2300)*
2000 (2300)*
1400
1400
312
1 1
215 110 110
HA41-2323f eps
40
40
312
1
1400
1400
312
1
215 110 110
HA41-2317e eps
HA41-2477a eps
40
1 Cover screwed on
* Option: * Option:
With low-voltage compartment With low-voltage compartment
*** Available mounting depth
for low-voltage equipment
1) Panel block on request
Dimensions
600 (900)*
600 (900)*
60
60
1 1
2000 (2300)*
2000 (2300)*
1 1
1400
1400
312
1135
1135
1 1
255 255 255 255
215 110 110
675
675
HA41-2319f eps
HA41-2320f eps
40
40
850 ³15 750 850 ³15 ~145**
775 750
Billing metering panel Billing metering panel
type ME1 type ME1-K 775
600 (900)*
60
1
2000 (2300)*
1
1400
312
1135
1
255 255
215 110 110
675
HA41-2321f eps
40
60
1
2000 (2300)*
1
1400
312
255 255
1135
1
215 110 110
675
HA41-2322g eps
* Option:
With low-voltage compartment
** Dimension for cable routing: 323 mm for combination of 850 ³15 ~600
panel type ME1-K with pressure absorber duct Billing metering panel 750
type ME1-KS 775
Dimensions
1400
or KT-B2 (in TR-U panel)
• Types attached on the right
with connection at the busbar
HA41-2441b eps
Possibility 2
• Types attached on the left
Possiblity 2 with connection at the busbar
Only Billing metering Individual panel – Individual panel type
individual panel, panel or panel block, RK, K, TR, LS1, LS2, SE1, SE2, ME3 or LT
on the left type ME1 on the right
– Panel blocks cannot be attached
• Types attached on the right
with connection at the feeder
– Individual panel type
RK-U, K-U, TR-U, LS1-U or LS2-U
– Panel block type
R-B2 or R-B3 (in RK-U panel),
1400
Possibility 3
• Types attached on the left
with connection at the busbar
Connection 850 Connection – Individual panel type
at the busbar at the feeder ** RK, K, TR, LS1, LS2, SE1, SE2, ME3 or LT
– Panel blocks cannot be attached
Possiblity 3 • Types attached on the right
with connection at the busbar
Only Billing metering Individual panel
– Individual panel type
individual panel, panel or panel block, RK, K, TR, LS1, LS2, SE1, SE2, ME3 or LT
on the left type ME1-S on the right – Panel block type
R-B2, R-B3, T-B2, T-B3, RT-B2, 2RT-B3, 3RT-B4
or KT-B2
1400
L3 L2 L1
L3
L2
L1
HA41-2443b eps
Dimensions
350 850
14 x 28 4 14 x 28 4
175 275 300
2 2
31
55
63
31
55
63
• For ring-main panels • For billing metering
³15
³15
1 type RK 1 panels
233 122 69
233 122 69
• For cable panels – Type ME1
3 6
– Type ME1-K
480
type K
8 35 8 35 3 – Type ME1-S
623
713
610
775
623
713
610
110 110 255 255 – Type ME1-KS
panel – Type ME1-KK
10 7 7
47 197
type SE
150
47 197
HA41-2325e eps
HA41-2329e eps
19 106 100 19 206 375 231 19
28 x 14 4 28 x 14 4
40 270 40 770
500 700
14 x 28 4 • For circuit-breaker panel types 14 x 28 4
250 LS1 and LS2 for ring-main pan- 175 350
2 2
els type RK1 each without ca-
31
63
55
³15
³15
31
55
63
ble-type current transformers • For ring-main
1 1 panel block
233 122 69
233 122 69
480
8 35 35
• For ring-main/
• For bus sectionalizer with cir- 8 350
623
713
610
623
713
610
transformer
775
775
150 150 cuit-breaker type LK and bus 110 110 110 110 panel block
10 7 sectionalizer with switch-dis- 10 7 type RT-B2
47 197
150
47 197
150
connector type LT
• For cable connection/
• For busbar earthing
HA41-2326e eps
transformer
panel type SE2 panel block
19 106 125 125 19 106 100
28 x 14 4 • For busbar voltage 28 x 14 4 type KT-B2
HA41-2632 eps
40 420 19
metering panel type ME3 350 312
For individual panels
40 620
For panel blocks
500 1000
14 x 28 4 14 x 28 4
250 250 500
2 2
³15
31
55
63
31
55
63
• For transformer
³15
• For circuit-breaker
1 panel types LS1 and LS2 1 panel block
233 122 69
233 122 69
current transformers
480
8 35 8 35 500
623
713
425
623
713
610
150 150
775
775
47 197
150
50 135
HA41-2327d eps
28 x 14 28 x 14
40 420 19
5 500 462
15 470
40 920
For individual panels For panel block
600
14 x 28 4
2 1 Wall distance
31
55
63
³15
Dimensions
55
63
• For ring-main
³15
1 panel block
233 122 69
40 40 40 40
type R-B3
3
• For ring-main/
480
8 35
HA41-2609a_en eps
350 350
623
713
610
transformer
775
19 106 100
28 x 14 4
HA41-2633 eps
19 19
350 350 312
40 970
For panel blocks
1400
14 x 28 4
175 350
2 9 A
31
55
63
• For ring-main/
³15
1 transformer
233 122 69
40 40 40 40 40 40
panel block 31 69 122 233 197 47
3 type 3RT-B4 approx. 610
480
19 106 100
28 x 14 4
HA41-2634 eps
19 19 19
350 350 350 312
40 1320
For panel block
55
63
³15
former
HA41-2608a eps
1
233 122 69
panel block
40 40 40 40 3 type T-B3
480
8 35 500 500 3
623
713
610
775
19 19 28 x 14
500 500 462
40 1420
For panel block
1 Wall distance
2 Fixing frame (base) of an individual panel or panel block
3 Floor opening for high-voltage cables (and, if applicable, control cables)
4 Fixing points
7 Position of the incoming cables for the feeder
8 Overall panel depth (including cable compartment cover)
9 Fixing support
B Cutout in the fixing frame for extended floor opening for
panel with cable-type current transformers
Dimensions
350
14 x 28 4
175
2
• For ring-main panels
31
55
63
³15
1 type RK
233 122 69
3
• For cable panels
480
type K
8 35
623
713
425
775
110 110 7
10
150
47 197
50 135
HA41-2478a eps
19 106 100
28 x 14 4
40 270
11, 12
15 320
For individual panels with cable-type current transformers
or surge arresters
350 500
14 x 28 4 14 x 28 4
175 250
2 2
³15
31
55
63
³15
55
63
1 type RK 1 type RK1
233 122 69
233 122 69
480
648
713
635
775
775
10 10 ~101*
197
150
197
150
7 7
HA41-2479b eps
HA41-2482b eps
19 4 19
28 x 14 28 x 14 4
40 270 420 40
10, 11 10, 11
For individual panels with double cable connection or surge arresters make Tyco Electronics, type RDA 24
(panel depth 775 mm), standard or 25 mm deeper cable compartment cover
350 500
14 x 28 4 14 x 28 4
175 250
2 2
³15
31
55
63
³15
31
55
63
35
type K 35 type LS1 and LS2
8 8
728
818
715
728
818
715
7 10
7
10
42 110 197
150
42 110 197
150
~190*
~190*
HA41-2483b eps
HA41-2480b eps
350 500
14 x 28 4 14 x 28 4
175 250
2 2
³15
31
55
63
31
55
63
³15
233 122 69
480
8
923
1013
900
8
10 10
1075
1075
7 7
65 150 130 197
150
~245*
6 6
10 10
HA41-2481b eps
HA41-2484b eps
Dimensions
500 13
2
• For ring-main panels
type RK and RK1
115
215
550
type K
~675**
122
3
8 • For circuit-breaker panels
713
828
834
890
233
type TR
HA41-2485b eps
14
19 106 125 125
15
40 420 28 x 14 4
For individual panels with single cable connection
500 13 500 13
2 2
• For ring-main panels • For ring-main panels
type RK and RK1 type RK and RK1
115
115
215
215
550
550
122
3
8 • For circuit-breaker panels • For circuit-breaker panels
719
834
8 3
890
233
233
824
939
995
7
240
~101*
47 197
65 85 197
10
343
~190*
10
HA41-2486b eps
14
19
HA41-2487b eps
type K
550
122
tion with bolted contact 8 Overall panel depth (including cable compartment cover)
514
65 150 130
10 (M16)
10 Position of 2nd cable
11 For surge arrester
HA41-2488b eps
Dimensions
Cable connection examples in ring-main, cable and circuit-breaker panels
(non-binding examples, for further examples see Catalog HA 40.1)
Cable connection in Cable connection with Connection in 1 Elbow adapter, make Siemens,
ring-main panel surge arresters circuit-breaker panel type AKE 20/630 with
conventional cable sealing end,
make Lovink Enertech, type IAE 20
HA41-2339d eps
HA41-2620 eps
HA41-2346d eps
2 Cable T-plug, make Euromold,
type (K)400 TB/G
~565
575
575
5 Surge arrester,
make Euromold,
type 300 SA-5 or 300 SA-10
14
553*** 2 553*** 7 type RDA 21 (for type RDA 24,
15
a floor opening of 635 mm
instead of 610 mm is required)
290*
9 Cable T-plug,
~565
575
575
make Südkabel,
type SET (12/24)
and
~560** ~560** 8 ~560 101 10 Surge arrester,
63 610 63 610 63 635 make Südkabel,
750 750 750 type MUT (13/23)
775 775 775 or:
Standard cable compartment cover Standard cable compartment cover Standard cable compartment cover 9 Cable connector,
300**** make nkt cables, type AB 24-630
18 553*** and
HA41-2347d eps
HA41-2489 eps
HA41-2344e eps
19 16
553*** 553*** 9 10 Surge arrester,
18 make nkt cables, type ASA 24-5
HA41-2345c eps
make Südkabel,
of cable plug type SET 24
*** Dimension for bushing as 19 Coupling insert,
interface type “C” with make Südkabel,
~560** ~245** ~560** 12 bolted contact (M16)
63
type KU 23.2
63 900 610
**** Mounting depth for
1047 897
combination of cable T-plug
1075 925 and surge arrester
300 mm deeper cable compartment 150 mm deeper
cover for double cable connection cable compartment cover
Standards
Standards, Transport
Notes
Responsible for
Technical contents:
Christoph Maul
Siemens AG, Dept. PTD M 2 PPM
Erlangen
General editing:
Gabriele Pollok
Siemens AG, Dept. PTD CC M
Erlangen
The information in this document contains general descriptions of the technical options available, which do not always have to be present in individual cases.
The required features should therefore be specified in each individual case at the time of closing the contract.