Application Sheet AAZD03 LU3 HQ

Synco™ 200 RLU236


Indoor air quality and fan control Basic type U06

Ventilation plant with mixed air dampers


Ventilation plant for rooms where the proportion of outside air shall be increased when the indoor air quality drops
(ppm), thus preventing odors and enhancing comfort. Typical applications are kitchens, public areas such as restau-
rants and bars, or buildings with varying occupancy levels, such as theatres and conference halls.

Options:
• Additional maximum selection from internal and external signal
• 6-speed fan
• Absolute remote setpoint adjuster
• Outside temperature-dependent functions
• Comfort / Economy changeover

Plant diagram

S01
AQ B4
M N.X1
Y2 [ppm]
M
Y1 Y6
N.Y1 M

T T R5
N.Q2 M1 N.X4
B9 N.Q3 N.Q1
N.X3 N.Q4
N.Q5
N .X 2 S5
N.Q6
N.D1
S6
N.D2

Function Indoor air quality control Demand-controlled supply air fan Winter compensation
diagrams
D01

Yctl Yctl Sp
D02

D03
M1
1 1
Y6 Y1, Y2

0 0
SET MAX AqR SET MAX AqR TOa

Legend SET MAX Setpoint


AqR Indoor air quality
Sp Setpoint
TOa Outside temperature
Yctl Controller output

1-5
TM
Made with the Synco Select Tool of Siemens Switzerland Ltd 31.12.2006
without control over or responsibility for content. AAZD03LU3HQ_en.doc CE1A3101en059
Application Sheet AAZD03 LU3 HQ
Synco™ 200 RLU236
Indoor air quality and fan control Basic type U06

Description of Basic functions Winter compensation


functions The universal controller (N1) compares the indoor air This function is activated if an outside sensor (B9) or
quality acquired by the air quality sensor (B4) with the duct temperature sensor (B9a) is used for acquiring the
setpoint. outside temperature.
If the air quality drops, exceeding the setpoint, the con- The values CMP-1D and CMP-2D for setpoint compen-
troller will continuously open the outside and exhaust sation are set to 0 K as standard. In that case, no set-
air dampers (Y1 and Y2) and, at the same time, close point compensation will take place.
the recirculated air damper (Y6). To enable the function, the value of CMP1-D must be
It controls the supply air fan (M1) via switching output preselected (refer to "Parameter settings").
Q1 depending on the load. In that case, to save energy, the indoor air quality set-
point will be continuously lowered (winter compensa-
When the plant is shut down, the outside and exhaust tion) when the outside temperature falls in the range
air dampers are closed and the recirculated air damper from 0 °C to −10 °C (CMP1-SST = 0 °C and
is open.
CMP1-END = −10 °C preset).
Operating mode selection Comfort / Protection Setpoint compensation acts on the Comfort and the
An external switch (e.g. time switch) can be used (S5) Economy setpoint.
to switch the controller’s operating mode from Comfort
Absolute setpoint adjustment
to Protection (PRT), or vice versa.
Absolute setpoint adjustment is activated as standard.
Operating mode selection Comfort / Economy This can be overridden by a remote setpoint adjuster
An external switch (e.g. manual switch) can be used (R5), which must be connected to input X4.
(S6) to switch the controller’s operating mode from The absolute remote setpoint adjuster acts on the Com-
Comfort to Economy (ECO), or vice versa. fort and Economy modes.

Optional functions External controller signal


An output signal of some other controller can be fed to
Control of a 6-stage direct expansion evaporator coil the controller's input X2 (DC 0...10 V signal). In that
The controller’s built-in step switch controls the speeds case, the controller delivers the maximum value from
of the fan (M7) via switching outputs Q1 through Q6 the external and the internal signal.
depending on the load. To save energy, the fan’s speed
is reduced as the indoor air quality rises.
The values for switching the speeds are preset:
S1-ON = 17 %, S1-OFF = 1 %
S2-ON = 33 %, S2-OFF = 17 %
S3-ON = 50 %, S3-OFF = 33 %
S4-ON = 67 %, S4-OFF = 50 %
S5-ON = 83 %, S5-OFF = 67 %
S6-ON = 100 % S6-OFF = 83 %

Device list

Standard Legend Device name Data Sheet Type reference Quantity


N1 Synco™ 200 universal controller, 2 control N3101 RLU236 1
loops
B4 CO2 / VOC sensors N1961 QPA2002D 1
Y1, Y2, Y6 Modulating damper actuators, N46… + G…6…E 3
AC 24 V, DC 0…10 V
S5 Digital time switch, 1 channel N5243 SEH62.1 1

Optional Legend Device name Data Sheet Type reference Quantity


B9 Outside sensor N1811 QAC22 1
R5 Setpoint adjuster, active N1992 BSG61 1

Variants Legend Device name Data Sheet Type reference Quantity


B9a Duct temperature sensor N1761 QAM2120.040 1

+ For selection of the actuators, refer to the Product Catalog

2-5
TM
Made with the Synco Select Tool of Siemens Switzerland Ltd 31.12.2006
without control over or responsibility for content. AAZD03LU3HQ_en.doc CE1A3101en059
Application Sheet AAZD03 LU3 HQ
Synco™ 200 RLU236
Indoor air quality and fan control Basic type U06

Connection diagram
L1
G

G (CO2/ 1
(CO2) VOC)
G0 U1 U2 B M 3 2

B4 B9 R5
AC 230 V
AC 24 V

G M X1 X2 M G1 X3 M X4 M G1 X5 M

G0 G1 Y1 G0 G1 Y2 G0 G1 Y3 G0

N1
1 8 1 8 1 8
G Y G Y G Y
G0 G0 G0
2 Y1 2 Y2 2 Y6

A01
G0
N

L1
G

L M D1 Q11 AC 24...230 V
N Q12 Q14 S6
S5
AC 230 V
AC 24 V

D1 M D2 M Q11 Q23 Q33 Q41 Q53 Q63

Q12 Q14 Q24 Q34 Q42 Q44 Q54 Q64


N1

K1 K2 K3 K4 K5 K6

M1
A02

G0
N

Legend M1 Fan, 1 or 6-speed


K1...6 Motor contactors for Fan, 1...6-speed
S6 Operating mode selector Comfort / Economy

3-5
TM
Made with the Synco Select Tool of Siemens Switzerland Ltd 31.12.2006
without control over or responsibility for content. AAZD03LU3HQ_en.doc CE1A3101en059
Application Sheet AAZD03 LU3 HQ
Synco™ 200 RLU236
Indoor air quality and fan control Basic type U06

Parameter settings

Path: ... > COMMIS > APPL ID


Parameter Setting Function Remarks
Basic type U06 Select application AAZD03 LU3 HQ

Path: ... > COMMIS > PARA > CTLOOP 1


Parameter Setting Function Remarks
CMP 1D 100 ppm Adjust value If winter compensation for sequence con-
troller 1 is required

Engineering • A number of settings are plant-specific and may need adjusting after the initial commissioning of the
controller
• The connection diagram does not show all plant interlocks but only those directly connected to the
controller or the associated equipment

4-5
TM
Made with the Synco Select Tool of Siemens Switzerland Ltd 31.12.2006
without control over or responsibility for content. AAZD03LU3HQ_en.doc CE1A3101en059
Application Sheet AAZD03 LU3 HQ
Synco™ 200 RLU236
Indoor air quality and fan control Basic type U06

Configuration diagram
RLU236 Basic type U 06 (AAZD03LU3HQ)
SIGNAL Y

SIGNAL Y

SIGNAL Y

SIGNAL Y
SIGNAL Y

X1 X2 X3 X4 X5
LABEL LABEL LABEL LABEL LABEL
0000 % OUTS REM1 DIG
x Y x Y x Y x Y x Y

D2
D1
x x x x x x x x x x x
SHIFT LIM SEQ SHIFT LIM SEQ

CH OVER
DIFF
MAIN

MAIN
DIFF

CTLOOP 1 1 CTLOOP 2 2 FROST


MODE

RELELEASE
DV ALM
SEQ2 Y
SEQ2 P
SEQ1 Y
SEQ1 P

SEQ4 Y
SEQ4 P
SEQ5 Y
SEQ5 P

SEQ1 Y
SEQ1 P

SEQ4 Y
SEQ4 P

y p y p y p y p Q y p y p Q

p1 p2 p1 p2 p1 p2 y1 y2 x y1 y2 x y1 y2 x y1 y2 x x x
IN X

IN X
MECH 1
MECH 2
IN X

IN X

PUMP 1 PUMP 2 PUMP 3 AO 1 AO 2 AO 3 HREC


1 2 3 1 2 3

Cooler
PUMP 1

PUMP 2

PUMP 3

HREC
A0
A0

A0

....................

Q Q Q Y Y Y Y

y1 y2 x y1 y2 x y1 y2 x y1 y2 x
IN X IN X IN X IN X
STEP V1 STEP
Var. V2
Stufensch. 2 STEP LIN STEP BIN
STEP 1
STEP 2

STEP 2
STEP 3
STEP 4
STEP 1
STEP 3
STEP 4
STEP 1
STEP 2

STEP 5
STEP 6

STEP 1
STEP 2
STEP 3
STEP 4
STEP 5
STEP 6
AO

AO

AO

AO

Q Q Y Q Q Q Q Q Q Y Q Q Q Q Q Q Y Q Q Q Q Y

Y Y Y Q Q Q Q Q Q
3101B08 en

Y1 Y2 Y3 Q1 Q2 Q3 Q4 Q5 Q6

5-5
TM
Made with the Synco Select Tool of Siemens Switzerland Ltd 31.12.2006
without control over or responsibility for content. AAZD03LU3HQ_en.doc CE1A3101en059