Customer UFLEX Limited

PO No. 004/X-291/2013-14 Dt 12.11.2013


Project 132/33kV Switchyard
Contractor SREX POWER INDIA PVT. LIMITED
SIEMENS/GTP/145 KV HCB, Rev 0
ISOLATORS/GROUNDING SWITCHES 245KV CENTRE BREAK
1. General
a) Name of the Manufacturer SIEMENS Limited
Hyderabad-500 037
b) Country of Manufacture India
c) Manufacturer’s type designation Horizontal Centre Break
d) Standard applicable for Isolators and IS 9921/IEC 62271-102 &
earthing switches IEC 62271-1
e) Rated Voltage Ur(KV) 145 kV
f) Rated current under site conditions (A) 800A
at 50 C ambient
g) Rated frequency (Hz) 50 Hz
h) Number of poles Three
i) Whether all 3 poles are ganged Yes.
mechanically
j) Pole to pole spacing 3000 mm
k) Type of installation Out door
2. Guaranteed Ratings
a) Rated short time current of Isolator for 40 KA (rms) 102 kAP
3 sec(KA) and dynamic current (kAp)
b) Opening time of Isolator and earth Less than 12 seconds
switch(s)
c) Closing time of Isolator and earth Less than 12 seconds
switch(s)
d) Temperature rise over 50 C ambient Within limits as per table-IV of IS
temperature corresponding to maximum 9921 (Part II) of 1982 de-rated to
continuous current ( C ) 50 deg.C
3. Dielectric withstand capacity of
completely assembled Isolator/Isolator
and earth switch
a) One minute dry power frequency
withstand test voltage (kV rms)
i) between live terminals and ground 275 kV rms
ii) between terminals when Isolator open 315 kV rms
b) 1.2/50 microseconds impulse
withstand test voltage
i) between live terminals and ground 650 kVp
ii) between live terminals 750 kVp
c) 250/2500 microseconds switching
surge withstand test voltage (dry & wet)
i) between live terminals and ground (kVp) Not applicable
ii) between terminals (kVp) Not applicable
d) Corona extinction voltage (kV rms) 92 (min.)
Customer UFLEX Limited
PO No. 004/X-291/2013-14 Dt 12.11.2013
Project 132/33kV Switchyard
Contractor SREX POWER INDIA PVT. LIMITED
SIEMENS/GTP/145 KV HCB, Rev 0
ISOLATORS/GROUNDING SWITCHES 245KV CENTRE BREAK
e) Max. Radio interference level at 1.1 Less than 1000 at 92kV(rms) in
Ur 3 at 1.0 MHz (micro volts) all positions
f) Total creepage distance to ground (mm) 3625mm (Min.)
4. Operating Mechanism
(A) For Main Blades
a) Type of motor operating/manually Motor Operating Mechanism
driven Mechanism (AC Motor operated)
b) Manufacturer’s type designation MOM
c) Rated torque of the mechanism 36 KGM
d) Type, rating & make of motor A.C. induction motor, 3 phase
415V, 0.5 HP/0.373kW
(B) For Earth Switches
e) Type of motor operating/manually Manual Operating Mechanism
driven Mechanism (Hand Operated)
f) Manufacturer’s type designation BOM
g) Rated torque of the mechanism 36 KGM
4.1 Interlocks
a) Whether mechanical/constructional Yes.
interlock between Isolator & earth switch
provided
b) Details of electrical interlock enclosed
i) Isolator Yes. (Refer schematic diagram)
ii) Earth Switch Yes. (Refer schematic diagram)
c) Arrangement provided to prevent Yes
electrical or manual operation unless
interlock conditions are satisfied.
d) Whether interlock coil is continuously Yes
rated
e) Rated DC control voltage 110V DC, 10%
f) Power consumption (W) 35 W
4.2 Controls
a) Rated DC control voltage (V) 110 V
b) Limits of voltage 10%
c) Power consumption of control coils (W) 35 W
5. Constructional Features
a) Minimum clearance in air
i) Between phases (mm) 2300mm
(phase spacing being 3000mm)
ii) Between live parts to earth (mm) Equal to dry arcing distance of
Insulator selected.
Customer UFLEX Limited
PO No. 004/X-291/2013-14 Dt 12.11.2013
Project 132/33kV Switchyard
Contractor SREX POWER INDIA PVT. LIMITED
SIEMENS/GTP/145 KV HCB, Rev 0
ISOLATORS/GROUNDING SWITCHES 245KV CENTRE BREAK
b) Minimum clearance between live part Refer OGA drawings for details
and earth switch blade throughout the
entire arc of earth switch (mm)
d) Terminal pad details
i) Diameter & length (mm) 50 Dia. 100mm (approx)
ii) Material of pad Al stud
e) Insulator data
i) Make Not in our scope of supply
ii) Height (mm) 1500mm
iii) Type Solid Core
iv) No. of insulator stacks/phase Two
v) No. of insulators/stack One
f) Main contacts
i) Type of contacts Jaw & fist type, spring loaded
slide-in contacts
ii) Contact area (mm²) Line contact
iii) Material of contacts Silver plated copper
iv) Contact pressure 9 kgf/finger
v) Maximum current density under Sufficient maintains temp. Rise
normal current carrying capacity (A/mm²) within limits of values specified
in IS 9921/ IEC 129. Equal to
the cross-sections used in the
current carrying parts of type
tested equipment.
vi) Thickness of silver plating 15 microns
i) Auxiliary contacts
i) Rated voltage (V) 110 V DC
ii) Rated continuous current (A) 10 A
iii) Rated DC breaking current with 2A
20ms time constant (A)
j) Mounting dimensions of Isolators
l) Whether cable glands required included Inter pole cabling as well as
in the scope for inter pole cabling to be supply of glands are in the scope
done by the Purchaser of contractor
6. Auxiliary contacts for
Isolator 10NO + 10NC
Earth Switch 6NO + 6NC
All contacts are exclusively for
Customer Use only.