Sei sulla pagina 1di 4

MicroGrids

R.H.Lasseter, Fellow, IEEE

separation device, usually a static switch. The feeder voltages


Abstract This paper provides an overview of the at the loads are usually 480 volts or less. Feeder A indicates
MicroGrid paradigm. This includes the basic architecture, the presents of several microsources with one providing both
control and protection and energy management. power and heat. Each feeder has circuits breakers and power
flow controllers. Consider the power flow controller near the
Index Terms MicroGrid, microsources, power electronics, heat load in feeder A. This controller regulates feeder power
voltage source inverter, microturbines, protection. flow at a level prescribed by the Energy Manger. As loads
down stream change the local microsources increase or
I. INTRODUCTION decreases their power output to hold the power flow constant.
The MicroGrid concept assumes a cluster of loads and In this figure feeders A and C are assumed to have critical
microsources operating as a single controllable system that loads and include microsources, while feed B is assumed to
provides both power and heat to its local area. This concept have non-critical loads which can be shed when necessary. For
provides a new paradigm for defining the operation of example when there are power quality problems on the
distributed generation. To the utility the MicroGrid can be distribution system the MicroGrid can island by using the
thought of as a controlled cell of the power system. For separation device shown in the figure. The non-critical feeder
example this cell could be controlled as a single dispatchable can also be dropped using the breaker at B.
load, which can respond in seconds to meet the needs of the
transmission system. To the customer the MicroGrid can be
designed to meet their special needs; such as, enhance local
reliability, reduce feeder losses, support local voltages,
provide increased efficiency through use waste heat, voltage
sag correction or provide uninterruptible power supply
functions to name a few.

II. BASIC STRUCTURE


The microsources of special interest for MicroGrids are small
(<100-kW) units with power electronic interfaces. These
sources, (typically microturbines, PV panels, and fuel cells)
are placed at customers sites. They are low cost, low voltage
and have high reliable with few emissions. Power electronics
provide the control and flexibility required by the MicroGrid
concept. Correctly designed power electronics and controls
insure that the MicroGrid can meet its customers as well as
the utilities needs. The above characteristics can be achieved
using a system architecture with three critical components;
Figure. 1. MicroGrid Architecture
¥ Local microsource controllers
¥ System optimizer
¥ Distributed protection III. MICROSOURCE CONTROLLER
Microsource controller is an important component of the
Figure 1 illiterates the basic MicroGrid architecture. In this MicroGrid infrastructure. This controller responds in
example the electrical system is assumed to be radial with milliseconds and uses local information to control the
three feeders A, B and C and a collection of loads. The radial microsource during all events. A key element is that
system is connected to the distribution system through a communications among microsources are unnecessary for basic
operation. Each inverter is able to respond to load changes in a
predetermined manner without communication of data from
The work described in this report was coordinated by the Consortium for other sources or locations, which enables plug and play
Electric Reliability Technology Solutions, and funded by the Assistant
Secretary of Energy Efficiency and Renewable Energy, Office of Power capabilities. Plug and play implies that a microsource can be
Technologies of the U.S. Department of Energy under Contract No. DE- added to the MicroGrid without changes to the control and
AC03-76SF00098 and by the California Energy Commission, Public Interest protection of units that are already part of the system. The
Energy Research Program, under Contract No. BG 99-396 (00) basic inputs to this controller are steady state set points for
output power, P, and local bus voltage, V.
Robert H. Lasseter is Professor at University of Wisconsin-Madison, 1415
Engineering Dr., Madison, WI 53706 (lasseter@engr.wisc.edu).

0-7803-7322-7/02/$17.00 © 2002 IEEE


305
Basic Control of Real and Reactive Power reactive current droop controller. Basically, as the reactive
There are two basic classes of microsources; one is a D.C. current generated by the microsource becomes more capacitive
source, such as fuel cells, photovoltaic cells, and battery the local voltage set point is reduced. Conversely as the
storage, the other is a high frequency ac source such as the current becomes more inductive the voltage set point is
microturbine, which needs to be rectified. In both cases the increased. The function of the basic controller is shown in
resulting D.C. voltage is converted to an acceptable ac source Figure 3.0. The Q limit shown in the figure is a function of
using a voltage source inverter. The general model for a the volts-ampere (VA) rating of the inverter and the power
microsource is shown in Figure 2.0. It contains three basic being provided by the prime mover.
elements; prime mover, dc interface and a voltage sourced
inverter. Coupling to the power system is through an Q2max= VA2- P2
inductor. The voltage source inverter provides control of both Vset point
the magnitude and phase of its output voltage, V. The vector
relationship between the inverter voltage, V, and the system
voltage, E, along with the inductor s reactance, X, determines
the flow of real and reactive power (P &Q) from the
microsource to the system.

Prime
Mover Inverter
Qcapactive Qinductive
V E
+ Qmax Qmax

Figure 3.0. Voltage set point with droop


X
DC Fast load tracking and the need for storage
Interface A system with clusters of microsources and storage could be
designed to operate both isolated and connected to the power
Figure 2.0 Interface Inverter System grid. In isolated operation, load-tracking problems arise since
microturbines and fuel cells have slow response and are
The P & Q magnitudes are coupled as shown in the equations inertia-less. The prime movers output power time constants
below. For small changes P is predominantly dependent on range from 10 to 200 seconds, which is too slow for most
the power angle, _p, while Q is dependent on the magnitude of loads. It must be remembered that the current power systems
the converter’s voltage, V. These provide for a basic feedback have storage provided though the generators inertia. When a
loops for the control of output power and bus voltage, E new load comes on line the initial energy balance is satisfied
through regulation of reactive power flow. by the system s inertia. This results in a slight reduction in
system frequency. A system with clusters of microsources
3 VE designed to operate in an island mode must provide some
P= sin δ p form of storage to insure initial energy balance.
2 X
3V The necessary MicroGrid storage can come is several forms;
Q= (V − E cos δ p ) batteries or supercapacitors on the dc bus for each microsource;
2X direct connection of ac storage devices (batteries, flywheels
δ p = δV − δ E etc.); or use of traditional generation with inertia with the
microsources. If the MicroGrid is not required to operate in
island mode the energy unbalance can be met by the ac system
Voltage regulation through droop without providing storage on the MicroGrid.
Integration of large numbers of microsources, implied in the Frequency droop for power sharing
MicroGrid concept, is not possible with basic P-Q controls.
MicroGrids provide premium power through the ability to
Voltage regulation is necessary for local reliability and
smoothly move from dispatched power mode (while connected
stability. Without local voltage control, systems with high
to the utility grid) to load tracking (while in island mode). In
penetration of microsources can experience voltage and/or
the island mode such problems as slight errors in frequencies
reactive power oscillations. Voltage control requires care to
generation at each converter and the need to change power-
insure that there are not large circulating reactive currents
operating points to match load changes imply a need for a
between sources. The issues are identical to those encountered
complex communication system. This is not so. These issues
in the control of large synchronous generators. In the power
can be addressed using power vs. frequency droop functions at
grid the impedance between generators is usually large enough
each microsource without an explicit communication network.
to greatly reducing the possibility of circulating currents. In a
MicroGrid, which is typically radial, the problem of large
When grid connected, the loads in the MicroGrid receive
circulating reactive currents is immense. With small errors in
power both from the grid and from the microsources
voltage set points the circulating current can exceed the ratings
depending on the customer s situation. With loss of the grid
of the microsources. This situation requires a voltage vs.
306
due to voltage drops, faults, blackouts etc. the MicroGrid smoothly transfer to island operation. With separation from
smoothly transfer to island operation. With separation from the grid the voltage phase angles at each microsource in the
the grid the voltage phase angles at each microsource in the MicroGrid change resulting in an apparent reduction in local
MicroGrid change resulting in an apparent reduction in local frequency. This frequency reduction coupled with a power
frequency. This frequency reduction coupled with a power increase allows for each microsource to provide it s
increase allows for each microsource to provide it s proportional share of load without new power dispatch from
proportional share of load without new power dispatch from the Energy Manager. In fact in island operation the Energy
the Energy Manager. In fact in island operation the Energy Manager is not used except for reconnection to the grid.
Manager is not used except for reconnection to the grid.

Consider two microsources, as suggested in Figure 4.0. In IV. SYSTEM OPTIMIZATION


this example, the sources are assumed to have different
ratings, P 1max, and P 2max. The dispatched power in grid mode System optimization is provided by the Energy
( P01 and P02 ) is defined at base frequency, ω 0 . The droop is Manager. The Energy Manager uses information on
local electrical and heat needs, power quality
defined to insure that both systems are at rated power at the requirements, electricity and gas costs,
same minimum frequency.
wholesale/retail service needs, special grid needs,
demand-side management requests, congestion levels,
etc. to determine the amount of power that the
ω MicroGrid should draw from the distribution system.
Some key functions of the Energy Manager are;
P02 P01
ωo ¥ Provide the individual power and voltage set point for
w1 each power flow/microsource controller
¥ Insure that heat and electrical loads are met
¥ Insure that the MicroGrid satisfies operational contracts
wmin with the transmission system
P ¥ Minimizes emissions and system losses
¥ Maximize the operational efficiency of the
P2max P1max microsources.
¥ Provides logic and control for islanding and
Figure 4.0. Power vs. Frequency Droop Control reconnecting the MicroGrid during events.

During a change in power demand, these two sources operate V. PROTECTION


at different frequencies, which causes a change in the relative Protection must respond to both system and MicroGrid faults.
power angles between them. As this happens, the two If the fault is on the utility grid, the desired response may be
frequencies tend to drift towards a lower, single value ω 1 . to isolate the MicroGrid from the main utility as rapidly as
Unit 2 was initially operating at a lower power level than Unit necessary to protect the MicroGrid loads. The speed of
1. However, at the new power level Unit 2 has increased its isolation is dependent on the specific customer s loads on the
share of the total power needs. Although power is adjusted MicroGrid. In some cases sag compensation can be used
within fractions of seconds, frequency restoration can take without separation from the distribution system to protect
longer. Because droop regulation decreases the MicroGrid, a critical loads. If the fault is within the MicroGrid, the
restoration function must be included in each controller. The protection coordinator isolates the smallest possible section of
droop control design is based on each microsource having a the radial feeder to eliminate the fault. Most conventional
maximum power rating. As a consequence, droop is dependent distribution protection is based on short-circuit current
on the dispatched power level while the microsources are sensing. Power electronic based microsources can not
connected to the grid. normally provide the levels of short circuit required.
Microsources may only be capable of supplying twice load
MicroGrids can provide premium power through the ability to current or less to a fault. Some overcurrent sensing devices
smoothly move from dispatched power mode (while connected will not even respond to this level of overcurrent, and those
to the utility grid) to load tracking (while in island mode). In that do respond will take many seconds to respond, rather than
the island mode such problems as slight errors in frequencies the fraction of a second that is required.
generation at each converter and the need to change power-
operating points to match load changes imply a need for a The unique nature of the MicroGrid design and operation
complex communication system. This is not so. These issues requires a fresh look into the fundamentals of relaying. One
can be addressed using power vs. frequency droop functions at approach that is quite powerful is to develop a real-time fault
each microsource without an explicit communication network. location technique that will identify the exact location of the
fault much more accurately that the classical relaying is
When grid connected, the loads in the MicroGrid receive capable of doing under any circumstances. These methods may
power both from the grid and from the microsources prove to costly. Low cost approach such a CT based zero
depending on the customer s situation. With loss of the grid sequence detection, and differential current and/or voltage
due to voltage drops, faults, blackouts etc. the MicroGrid methods also show promise. These means are not in common

307
use on distribution systems but can provide the required
functions. The nuances of applying these techniques to
distribution systems in a variety of different configurations are
not as well understood as overcurrent sensing.

Robert H. Lasseter (F’92) received the Ph.D. in Physics at


the University of Pennsylvania, Philadelphia in 1971. He was
a Consultant Engineer at General Electric Co. until he joined
the University of Wisconsin-Madison in 1980. Research
interest focus on the application of power electronics to
utility systems and technical issues which arise from the
restructuring of the power utility system. This work includes
interfacing micro-turbines and fuel cells to the distribution
grid, MicroGrids, control of power systems through FACTS
controllers, use of power electronics in distribution systems,
harmonic interactions, simulation methods, power electronic
circuits.. Professor Lasseter is a Fellow of IEEE, an expert
advisor to CIGRE SC14 and Chairman of IEEE Working
Group on Distributed Generation

308

Potrebbero piacerti anche