MITIGATION SELECTIONS
This Roadmap is a high-level summary of steps for a process owner to consider if combustible dust may be produced or handled in their
The results below reflect common situations; however, mitigation
facility. The process owner’s final selection of dust collectors and risk mitigation strategies should be based on the outcome of a Dust
strategies are influenced by variables not included in this simplified
Hazard/Process Hazard Analysis performed by the facility owner. Although early engagement of a dust collector supplier provides helpful
chart. Process owners should use the outcome of their DHA/PHA
insights on the availability and features of various products, facility owners should consult with a combustible dust expert and/or a process
and discussions with mitigation strategy experts before making
safety expert before making actual product and mitigation strategy selections.
actual strategy selections.
Dust Hazard Analysis [DHA]: A Dust Hazard Analysis allows a process owner to determine potential Prevention:
Completed and Maintained by the Process Owner combustion risks for dusts produced or handled in their facility. Ignition Source Mitigation Strategy Considerations
No -
However, sparks and
Dust Reactive
Yes Dust Combustible? Dust is Not embers may represent
or Unknown Combustible potential ignition sources.
Data and/or Tests
Yes
Embers Slow to Extinguish
The DHA/PHA may indicate
Active Spark Mitigation or a Wet
If Dust is confirmed as The DHA/PHA
Dust is Not Collection Strategy
Combustible Screening Not Combustible, may indicate
Determines if dust can burn in a pile Combustible
additional testing and mitigation Spark Mitigation
may not be required. is insufficient and
Sparks Quick to Extinguish
caution to avoid
Dust is Combustible mixing dust with other The DHA/PHA may indicate
materials such as Passive Spark Mitigation.
metals and Spark Cooler® is one example
metal oxides. of Passive Spark Mitigation.
Go/No-Go Screening Explosibility Testing:
Determines if dust is explosible Dust is Since the dust is explosible: Consider the following tests:
Explosible Reactive Example: Aluminum & Metal Oxide (thermite reactions).
in a cloud
Explosibility Severity (K st and Pmax)
– Used for explosion protection
Minimum Explosible Concentration (MEC)
Dust is Not – Used for explosion avoidance Fire Protection:
Explosible Extinguisher and Return Air Considerations
Minimum Ignition Energy (MIE)
– Used for ignition avoidance
Minimum Autoignition Temperature (MIT)
Ensure samples used for testing are representative. Samples – Avoidance of hot surfaces or hot environments Water will
Yes Extinguish Dust? No
may require special handling to ensure they stay representative
(e. g. avoid oxidation during transmission and storage).
Filtered Air
DHA/PHA No –
No Fire Indicates Explosion Explosion No Explosion
Mitigation Mitigation Explosion Protection:
Mitigation May Not Be Mitigation Venting/Suppression and Explosion Isolation Considerations
May Be Needed?
Needed