Occidental COMMENT SHEET

of Oman Inc.
Additional Compressors & GDU at Wadi Latham
OXY Project Code 1212153 PAGE
Equipment GDU Package 1 of 1
Job No.: 24000089278

Comments on CRS for ELECTRICAL EQUIPMENT LIST REV00


OXY OXY
SR. COMMENTS / VENDOR REPLY 1 OXY VENDOR VENDOR
RESPONSE RESPONSE
NO QUERY (23/04/19) RESPONSE 1 REPLY 2 REPLY 3
2 3
Non-UPS and UPS loads are already indicated. Please see column
"type (4)", "N" means normal power and "U" means UPS. On the other
hand a table is alredy included for non-UPS and UPS loads:
1. Provide separate table
1. Noted.
ups & non-ups loads.

Noted. Provide the


KVA and Kvar
values in next
revision.

What we mean by
KVA and Kvar values shall be included in the next revision. Please working load is the
clarify what do you mean with working loads and connected loads. For actual absorbed
2.Provide the kva and
us it means the following: power of all
2. kvar values. working
- Working loads are the loads to be working and connected usually. individual loads.
load , connected loads .
- Connected loads are the loads connected but not working usually as (e.g. Absorbed
for example the spare motors (this is the only connected loads for us). power of pump etc.)
Connected load is
nothing but rated
load of equipment
(e.g Motor rating
etc)

Vendor to provide the Noted. This data shall be incorporated once the sub-vendor's motor
3. Noted.
details. datasheet is approved.

Page 1 of 1